April 8, 2011
Re: 4223 Spruce Way Remodel B11-0027
Bernie Weber
Starlite Design LLC
Dear Mr. Weber,
RESPONSE INSTRUCTIONS
● Submit four complete sets of revised construction documents containing the requested information with all plan revision items clouded or otherwise identified.
● Please respond in writing to each comment with a response letter addressing each comment.
BUILDING COMMENTS
Architectural Comments:
Sheet A1
1. Provide wall cross-sections showing fire rating, insulation, weather protection, and structural connections. See Town of Vail submittal requirements.
2. Provide door and window schedules on the plans verifying the required u values.
Structural Comments:
General Comment
1. Provide revised structural plans by the engineer showing all new construction included stairs, walls, structural members, and deck revisions. The plans shall reflect the seal of the
engineer with a current date indicating compliance with the currently adopted building code.
Plumbing Comments:
Sheet A0
1. Clearly identify on plans the proposed lower level plumbing fixtures are above the rim of the upstream manhole per section 715.1 IPC.
Sheet A1
1. Provide full size gas piping plans and isometric for proposed gas system. See Town of Vail submittal requirements for additional criteria.
Mechanical Comments:
Sheet A1
1. Annotate on plans the size of the propose fireplace, type and show fireplace venting per Town of Vail submittal requirements.
2. Show existing boiler size and sizing calculations verifying ability to handle additional heat loads.
Electrical Comments:
Sheet A1
1. Annotate on plans the new lighting to be a minimum of 50% high efficacy per the energy code.
2. Show required smoke and carbon monoxide detectors per the IRC.
PLANNING COMMENTS
Reviewed and accepted with conditions
FIRE COMMENTS
Reviewed and accepted
PUBLIC WORKS COMMENTS
NA
Sincerely,
Martin A. Haeberle
Chief Building Official