HomeMy WebLinkAboutB13-0164 REV1 PLANS approved Reviewed for Code Compliance Code: 2012 International Building Code (IBC) Reviewed for Code Compliance Code: 2012 International Building Code (IBC) Reviewed for Code Compliance Code: 2012 International Building Code (IBC) Reviewed for Code Compliance Code: 2012 International Building Code (IBC) Reviewed for Code Compliance Code: 2012 International Building Code (IBC) Reviewed for Code Compliance Code: 2012 International Building Code (IBC) Reviewed for Code Compliance Code: 2012 International Building Code (IBC) Reviewed for Code Compliance Code: 2012 International Building Code (IBC) Reviewed for Code Compliance Code: 2012 International Building Code (IBC) Reviewed for Code Compliance Code: 2012 International Building Code (IBC) Reviewed for Code Compliance Code: 2012 International Building Code (IBC) Reviewed for Code Compliance Code: 2012 International Building Code (IBC) S VENTURI/FLOW INDICATOR TC 12x24 CO P EPO CO2 BD D SINGLE LINE/DOUBLE LINE DUCTWORK SYMBOLS 45° WYE (ROUND) 90° TEE (ROUND) 45° RADIUS ELBOW. 90° CONICAL TEE 45° ELBOW (RECTANGULAR) DUCT DROP SYMBOLFLEX DUCT DUCT SPLIT 90° RADIUS ELBOW. SINGLE LINE DOUBLE LINE DUCT RISE SYMBOL D R SINGLE LINE DOUBLE LINE D R FLEX RIGID FLEX RIGID 45° CONICAL WYE (ROUND) (RECTANGULAR) SIZE OR SHAPE TRANSITION SP WALL CLEANOUTWCO- FCOFLOOR CLEANOUT- SECONDARY DRAIN SAND AND OIL WASTE EXHAUST FAN ON ROOF W/ DUCTTHRU ROOF.SUPPLY DIFFUSER; ARROWSINDICATE DIRECTION OF THROW DUCT SIZES ARE OUTSIDE SHEETMETAL (WIDTHxDEPTH) SECTION THRU OUTSIDE AIR, RETURN AIR,OR EXHAUST DUCT SIZE RADIANT FLOOR SUPPLY RADIANT FLOOR RETURN NON-SOFTENED DOMESTIC COLD WATER BACK DRAFT DAMPERBDD- SNOWMELT SUPPLY SNOWMELT RETURN HEATING WATER SUPPLY HEATING WATER RETURN CHILLED WATER SUPPLY CHILLED WATER RETURN CONDENSER SUPPLY CONDENSER RETURN NATURAL GAS MEDIUM PRESSURE GAS DRAIN PIPE HIGH PRESSURE STEAM SUPPLY HIGH PRESSURE STEAM RETURN LOW PRESSURE STEAM SUPPLY LOW PRESSURE STEAM RETURN PUMPED CONDENSATE FUEL OIL VENT FUEL OIL FILL GLYCOL FEED REFRIGERANT SUCTION REFRIGERANT LIQUID DOMESTIC COLD WATER DOMESTIC HOT WATER DOMESTIC HOT WATER (TEMP. SHOWN) HOT WATER CIRCULATION FIRE LINE PRESSURIZED WASTE PLUMBING VENT PIPE WASTE PIPE ACID WASTE PIPE STORM DRAIN PIPE STORM DRAIN OVERFLOW VACUUM PIPE COMPRESSED AIR PIPE MEDICAL AIR PIPE OXYGEN PIPE NITROGEN PIPE NITROUS OXIDE PIPE GREASE WASTE PIPE ACID VENT PIPE PRESSURE REDUCING VALVE SOLENOID VALVE FIRE RISER CHILLED WATER RISER PLUMBING RISER HEATING WATER RISER FLOW SWITCH SHOCK ABSORBER HOSE BIBB STRAINER W/ BLOW-OFF VALVE ROOF DRAIN SAFETY RELIEF VALVE FLOOR DRAIN FLOOR SINK HORIZONTAL CLEANOUT VACUUM BREAKER VERTICAL CLEANOUT PRESSURE GAUGE W/ PIG TAIL & COCK THERMOMETER THERMOSTAT PRESSURE - TEMP. TAP AIR VENT FT-FLOAT & THERMOSTATIC PIPE ANCHOR FLEXIBLE CONNECTOR PIPE EXPANSION JOINT IB-INVERTED BUCKET TD-THERMODYNAMIC PIPE UNION STEAM TRAP DOUBLE CHECK BACKFLOW PREVENTER PUMP & EQUIPMENT CONNECTOR PIPING SYMBOLS WALL HYDRANT HVAC RISER POINT OF DISCONNECTION POINT OF NEW CONNECTION TURNING VANES SHOWN IN 90~ ELBOW. MANUAL BALANCING DAMPER SUPPLY DUCT DOWN RETURN/EXHAUST DUCT DOWN TEMPERATURE CONTROLLER ACCESS PANEL SMOKE DETECTOR FIRE DAMPER FIRE/SMOKE DAMPER CLGCEILING ENTERING AIR TEMPERATUREEAT (E)EXISTING CONN CO DN CONNECT CLEANOUT DOWN BELOW FINISHED GRADE CUBIC FEET PER MINUTE BOTTOM OF PIPE FROM FINISHED FLOOR CFM BOP BFG ABOVE FINISHED GRADEAFG AFFABOVE FINISHED FLOOR- - - - - - - - - - - MOTORIZED DAMPER ENTERING WATER TEMPERATUREEWT OSAOUTSIDE AIR UNLESS NOTED OTHERWISE TYP UNO TYPICAL OPPOSED BLADE VOLUME DAMPER OC OBD NIC ON CENTER NOT IN CONTRACT LEAVING AIR TEMPERATURE LEAVING WATER TEMPERATURE LAT LWT FBOFURNISHED BY OWNER EXHEXHAUST- - - - - - - - - - - SECTION THRU SUPPLY AIR DUCT. DOOR GRILLE SUPPLY REGISTER RETURN AIR OR EXHAUST AIR REGISTER. AIR EXTRACTOR DUCTWORK SYMBOLS BACK DRAFT DAMPER SHUT OFF VALVE (BALL, GATE, BUTTERFLY) TEMPERATURE CONTROL VALVE DRAIN VALVE W/ HOSE END PLUG VALVE IN RISER FLOW BALANCING VALVE GATE OR GLOBE VALVE IN RISER FLOW CONTROL VALVE BALL VALVE PLUG OR BALANCING VALVE CHECK VALVE GLOBE VALVE BUTTERFLY VALVE ABBREVIATIONS/PLAN SYMBOLS SECTION CUT LETTER./ SHEET SHOWN ON. LIQUID PROPANE GAS PLAN SYMBOLS CARBON DIOXIDE SENSOR CARBON MONOXIDE SENSOR CONTROL PANEL DUCT STATIC PRESSURE SENSOR ROOM PRESSURE SENSOR HUMIDISTAT REMOTE TEMPERATURE SENSOR EMERGENCY POWER OFF SWITCH (N)NEW-COTGCLEANOUT TO GRADE- GPMGALLONS PER MINUTE (WATER FLOW RATE)- RARETURN AIR- SASUPPLY AIR- WITHW/- F/S T - - SD - - P - - - S H '*' ISSUED FOR INFORMATION ONLY ' ' NOT PART OF SET ' ' ISSUED AS PART OF A SET ISSUE LOG KEY: # DA T E ISSUE LOG MECHANICAL SHEET INDEX TITLE MECHANICAL COVER SHEETM1.0 PERMIT SET 05 / 1 0 / 2 0 1 3 SMS SMR HWS PC D FOF FOV LPG MA O2N 2O N 140° RS RL GF MG G CR CS CHR CHS HWR NS RFR RFS LPS LPR HPR HPS CA VAC ST(OF) ST GW AW AV V W PW F SO SD FSFS W H H B MECHANICAL SCHEDULESM1.1 MECHANICAL DEMOLIITON PLANMD2.1 MECHANICAL PLAN - 3rd FLOORM2.1 MECHANICAL ROOF PLANM2.2 PLUMBING PLAN - 3rd FLOORP2.1 MECHANICAL DIAGRAMSM3.1 1.THE ENTIRE THIRD FLOOR SHALL HAVE A PRE-TEST PERFORMED PRIOR TO DEMOLITION ON ALL VAV BOXES AND THE ASSOCIATED ROOFTOP UNIT. PROVIDE TEST REPORT TO OWNER/ARCHITECT/ENGINEER INDICATING AIRFLOW OF EACH VAV BOX, AIRFLOW OF ROOFTOP UNIT, AND EXTERNAL STATIC PRESSURE DEVELOPED BY ROOFTOP UNIT. THIS PRE-TEST SHALL BE COORDINATED WITH VVMC AND SHALL NOT BE PREFORMED DURING NORMAL BUSINESS HOURS SO AS NOT TO DISTURB THE BUILDING OCCUPANTS. 2.EXISTING FIRE/SPRINKLER PIPING SHALL BE RECONFIGURED AS REQUIRED FOR NEW SPACES. 3.GET EXISTING VALUES FOR SUPPLY AND RETURN DIFFUSERS. RE-SHEAVE UNIT TO EXISTING VALUES PER REDUCED CAPACITY. NOTES: MECHANICAL SPECIFICATIONSM1.2 MECHANICAL CONTROLS DIAGRAMSM3.2 PLUMBING PLAN - ROOFP2.2 ' ABOVE SEA LEVEL PROJECT ALTITUDE 8,000 O WNER REVIE W (REV LAYOUT) 08 / 3 0 / 2 0 1 3 DPA Project: Sheet Number: COPYRIGHT 2013 - DAVIS PARTNERSHIP, P.C. Sheet Title: 2301 Blake Street, Suite 100 Denver, CO 80205 303.861.8555 0225 Main Street, Unit C101 Edwards, CO 81632 970.926.8960 Denver Vail Consultant Issue/RevisionsDateNo. Sheet Information Project Information Permit Set30 August 2013 MedicalCenter VailValley Vail, Colorado 81657 US Bank Building 108 South Frontage Road Suite 306 S: \ B G P r o j e c t s \ 8 7 3 9 . 3 9 V V M C C o n c i e r g e C l i n i c \ C a d \ B G C E C A D\ 8 7 3 9 3 9 M 1 0 . d w g P r i n t e d B y : c ad d - j a c A u g u s t 3 0 , 2 0 1 3 - 1 1 : 0 0 a m L C - J A C COPYRIGHT 2013 B ANZEG EAUDIN (970)949-6108 (303) 278-3820 (970) 221-5691 (505) 323-9070 Vail: Denver: Fort Collins: Albuquerque: www.bgce.com Multi-Specialty Clinic 13915.00.000 MARTIN MARTIN 0225 MAIN STREET; SUITE C101 EDWARDS, COLORADO 81632 970.581.2546 BEAUDIN GANZE CONSULTING ENGINEERS 222 CHAPEL PLACE, UNIT AC-201 P.O. BOX 9650 AVON, COLORADO 81620 970.949.6108 M1.0 MECHANICAL COVER SHEET Reviewed for Code Compliance Code: 2012 International Building Code (IBC) DX GAS-FIRED ROOFTOP UNIT SCHEDULE EXHAUST FAN SCHEDULE GRILLE, REGISTER, DIFFUSER & LOUVER A B C D E PLUMBING FIXTURE SCHEDULE P1 P2 P3 P4 P5 P6 WATER HEATER SCHEDULE (ELECTRIC) PUMP SCHEDULE VARIABLE VOLUME TERMINAL BOX SCHEDULE VENTALATION SUMMARY ASSOCIATED VAV BOX SPACE NAME OCCUPANCY TYPE SPACE AREA, S.F. Az NUMBER OF PEOPLE Pz AREA OSA, CFM/S.F. Ra PEOPLE OSA, CFM/S.F. Rp PEOPLE OSA, CFM Rp*Pz AREA OSA, CFM Ra*Az BREATHING ZONE OSA, CFM Vbz ZONE OUTDOOR AIRFLOW, CFM Voz MAX PRIMARY AIRFLOW, CFM Vpz MIN PRIMARY AIRFLOW, CFM Vpz AIA REQUIRED TOTAL AIR CHANGES CFM TO MEET AIR CHANGE RATES AIA REQUIRED OUTSIDE AIR CHANGES OUTDOOR CFM TO MEET AIR CHANGE RATES MAX PRIMARY OUTDOOR AIR FRACTION Zp MIN PRIMARY OUTDOOR AIR FRACTION Zp VAV-1RECEPTION/WAITING 301OFFICE448150.0657527102128450370----0.280.35 VAV-2HALL 303OFFICE62900.06503838483251702170--0.150.28 VAV-1NURSE 304OFFICE14830.06 5 1592430125100----0.240.30 VAV-2 LAB 305 MEDICAL ROOM712 0153003038110110660 2 200.350.35 VAV-2EXAM 306MEDICAL ROOM1662015300455737516561352450.15 0.35 VAV-2EXAM 307MEDICAL ROOM1232015300354435012561002350.13 0.35 VAV-2TECH WORK 308OFFICE8420.0651051519325165----0.06 0.12 VAV-4PROCEDURE 310MEDICAL ROOM195401560080100400390153903800.250.26 VAV-3OFFICE 314OFFICE11020.065107172110060----0.210.35 VAV-3 OFFICE 315OFFICE 107 2 0.06510616 21 10060 ----0.210.35 VAV-4EXAM 316MEDICAL ROOM106201530030381101106852300.350.35 VAV-5EXAM 318MEDICAL ROOM1292015300354425012561052350.18 0.35 VAV-5EXAM 319MEDICAL ROOM111201530030381501106902300.250.35 VAV-5OFFICE 320OFFICE11120.0651071721250125----0.080.17 VAV-5OFFICE 321OFFICE11320.0651071721200100----0.110.21 UNCORRECTED OUTDOOR AIR INTAKE FLOW RATE, CFM: SYSTEM VENTILATION EFFICIENCY: OUTDOOR AIR INTAKE FLOW RATE, CFM: 530 0.8662.5 NOTES: CALCULATIONS PREFORMED IN ACCORDANCE WITH 2009 INTERNATIONAL MECHANICAL CODE. ZONE AIR DISTRIBUATION EFFICTIVE Ez IS 0.8 FOR ALL ZONE. CALCULATIONS BASED ON MINIMUM VAV BOX AIRFLOWS DPA Project: Sheet Number: COPYRIGHT 2013 - DAVIS PARTNERSHIP, P.C. Sheet Title: 2301 Blake Street, Suite 100 Denver, CO 80205 303.861.8555 0225 Main Street, Unit C101 Edwards, CO 81632 970.926.8960 Denver Vail Consultant Issue/RevisionsDateNo. Sheet Information Project Information Permit Set30 August 2013 MedicalCenter VailValley Vail, Colorado 81657 US Bank Building 108 South Frontage Road Suite 306 S: \ B G P r o j e c t s \ 8 7 3 9 . 3 9 V V M C C o n c i e r g e C l i n i c \ C a d \ B G C E C A D\ 8 7 3 9 3 9 M 1 1 . d w g P r i n t e d B y : c ad d - j a c A u g u s t 3 0 , 2 0 1 3 - 1 1 : 0 0 a m L C - J A C COPYRIGHT 2013 B ANZEG EAUDIN (970)949-6108 (303) 278-3820 (970) 221-5691 (505) 323-9070 Vail: Denver: Fort Collins: Albuquerque: www.bgce.com Multi-Specialty Clinic 13915.00.000 MARTIN MARTIN 0225 MAIN STREET; SUITE C101 EDWARDS, COLORADO 81632 970.581.2546 BEAUDIN GANZE CONSULTING ENGINEERS 222 CHAPEL PLACE, UNIT AC-201 P.O. BOX 9650 AVON, COLORADO 81620 970.949.6108 M1.1 MECHANICAL SCHEDULES Reviewed for Code Compliance Code: 2012 International Building Code (IBC) MECHANICAL WORK SHALL CONFORM TO THE FOLLOWING CODES: ALL LOCAL. CITY, COUNTY. AND STATE CODES, AABC - ASSOCIATE AIR BALANCE COUNCIL ADC - AIR DIFFUSION COUNCIL AGA - AMERICAN GAS ASSOCIATION AMCA - AIR MOVING AND CONTROL ASSOCIATION ANSI - AMERICAN NATIONAL STANDARDS INSTITUTE ASHRAE - AMERICAN SOCIETY OF HEATING, REFRIGERATION, AND AIR CONDITIONING ENGINEERS ASME - AMERICAN SOCIETY OF MECHANICAL ENGINEERS ASTM - AMERICAN SOCIETY OF TESTING MATERIALS AWWA - AMERICAN WATER WORKS ASSOCIATION NFPA - NATIONAL FIRE PROTECTION ASSOCIATION OSHA - OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION UL - UNDERWRITERS' LABORATORIES SMACNA - SHEET METAL AND AIR CONDITIONING NATIONAL ASSOCIATION GVI - GAS VENT INSTITUTE, EDITION 10-A IN CASE OF DIFFERENCES BETWEEN BUILDING CODES, SPECIFICATIONS, STATE LAWS, LOCAL ORDINANCES, INDUSTRY STANDARDS, UTILITY COMPANY REGULATIONS, AND THE CONTRACT DOCUMENTS, THE MOST STRINGENT SHALL GOVERN. SHOULD THE CONTRACTOR PERFORM ANY WORK THAT DOES NOT COMPLY WITH THE REQUIREMENTS OF THE APPLICABLE BUILDING CODES, SPECIFICATIONS, STATE LAWS, LOCAL ORDINANCES, INDUSTRY STANDARDS, AND ORDINANCES, INDUSTRY STANDARDS, AND UTILITY COMPANY REGULATIONS, THEY SHALL BEAR ALL COST ARISING IN CORRECTING THESE DEFICIENCIES & UNLESS SPECIFICALLY DESIGNATED OTHERWISE, THIS CONTRACTOR SHALL FURNISH AND/OR INSTALL EACH AND EVERT ITEM OF EQUIPMENT SHOW OR DESCRIBED, TOGETHER WITH ALL COMPONENTS AND INCIDENTALS (MATERIAL LABOR, FEES, TRANSPORTATION, TOOLS, STORAGE, CUTTING PATCHING, TRENCHING, CLEAN-UP, ETC.) NECESSARY TO COMPLETE THE WORK WITH NO ADDITIONAL EXPENSE TO OWNER LOCATIONS, QUANTITIES AND OTHER MEASUREMENTS OF THE BUILDING AND EQUIPMENT ARE OFFERED AS A GENERAL GUIDE ONLY, WITHOUT GUARANTEE AS TO COMPLETE ACCURACY. THE CONTRACTOR SHALL EXAMINE THE DRAWINGS AND EQUIPMENT AND VERIFY TO HIS OWN SATISFACTION; ALL CONDITIONS AND THEIR RELATIONS AND EFFECT REQUIRED FOR A COMPLETE AND CORRECTLY OPERATING MECHANICAL SYSTEM EACH CONTRACTOR SHALL VISIT THE SITE, ASCERTAIN THE CONDITIONS TO BE MET THEREIN IN INSTALLING THE WORK. AND MAKE DUE PROVISIONS FOR SAME IN HIS BID SUM. FAILURE TO COMPLY WITH THIS REQUIREMENT SHALL NOT BE CONSIDERED AS JUSTIFICATION FOR THE OMISSION OF WORK, FAULTY WORK OR FOR PAYMENT OF EXTRA COMPENSATION. WHERE THE PRODUCT OF A SINGLE MANUFACTURER'S NAME IS GIVEN, NO SUBSTITUTIONS SHALL BE CONSIDERED OR ACCEPTED. AT ALL TIMES, TAKE CARE TO PROTECT APPARATUS FROM DAMAGE. ADEQUATELY PROTECT STORED APPARATUS AT THE SITE, PROVIDE TARPAULINS OR OTHER PROTECTION COVERING AS REQUIRED TO THE SATISFACTION OF THE OWNER LOCATE ALL EQUIPMENT, FIXTURES, PIPING, DUCTWORK, ETC., APPROXIMATELY AS SHOWN N GENERAL LOCATION SHOWN, BUT COMFORM TO ALL STRUCTURAL AND FINISH CONDITIONS OF BUILDNG. REFER TO ARCHITECTURAL/STRUCTURAL DRAWINGS AND COORDINATE WITH GENERAL CONTRACTOR PRIOR TO STARTING WORK. CONTRACTOR SHALL PROVIDE ADDITIONAL SUPPORTS, HANGERS. OPENINGS, ETC., AS REQUIRED FOR A COMPLETE INSTALLATION. CONTRACTOR SHALL COORDINATE ALL CLEARANCES, LOCATIONS, AND REQUIREMENTS WITH OTHER TRAMS AS REQUIRED. ALL EQUIPMENT SHALL BE INSTALLED PER MANUFACTURES RECOMMENDATIONS, IN FULL ACCORDANCE WITH ALL APPLICABLE CODES HAVING JURISDICTION. COOPERATE WITH OTHER CONTRACTORS TO KEEP THE AREA CLEAN AND FREE OF UNNECESSARY MATERIALS OR DEBRIS. WHEN WORK IS COMPLETE, REMOVE ALL TOOLS, SCAFFOLDING, MACHINERY, AND DEBRIS. BROOM SWEEP THE AREA. COOPERATE WITH THE OWNER AND GENERAL CONTRACTOR TO MEET CONSTRUCTION SCHEDULES. COOPERATE IN ESTABLISHING THESE SCHEDULES AND AVOID DELAYING OTHER CONTRACTORS. PREPARE AS-BUILT DRAWINGS INDICATING ACTUAL ROUTINGS OF UNDERSLAB PIPING INCLUDING LABELING OF EACH LINE SHOWING SIZE, SERVICE, VALVE LOCATIONS, ETC IDENTIFY EACH MECHANICAL EQUIPMENT, ETC, WITH AN ENGRAVED PLASTIC LABEL STATING NUMBER, SERVICE, LOCATION, ETC AT TIME OF FINAL INSPECTION, TEST ALL CONNECTIONS, OPERATION OF ALL EQUIPMENT, ETC, ALL EQUIPMENT, AND SYSTEMS SHALL BE DEMONSTRATED TO ENGINEER. THIS CONTRACTOR WARRANTS TO THE OWNER ALL LABOR AND MATERIALS FURNISHED UNDER THIS CONTRACT FOR A PERIOD OF ONE 1 YEAR FOLLOWING DATE OF RECEIPT OF SATISFACTORY ACCEPTANCE CONTRACTOR SHALL WARRANT TO REPAIR ALL DEFECTS IN MATERIAL ANY OMISSIONS OR ERRORS FOUND BY THE CONTRACTOR SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT SO THAT AN ADDENDUM MAY BE ISSUED BEFORE BIDDING. ANY OMISSIONS OR ERRORS FOUND AFTER BIDDING WILL BE AT THE EXPENSE OF THE CONTRACTOR. FIRE STOPPING REQUIREMENT: PENETRATIONS THROUGH RATED WALLS AND FLOORS SHALL BE SEALED WITH A MATERIAL CAPABLE OF PREVENTING THE PASSAGE OF FLAMES AND HOT GASSES WHEN SUBJECTED TO THE REQUIREMENTS OF THE TEST STANDARD SPECIFIC FOR FIRE STOPS ASTM-E-814. ACCEPTABLE MATERIALS INCLUDE: DOW CORNING RTV FIRE STOP FOAM FOR BARE PIPE, METAL CONDUIT, AND ELECTRICAL CABLE; 3M FIRE DAM 150 CAULK FOR BARE PIPE, METAL CONDUIT, AND BUILDING CONSTRUCTION GAPS; 3M CP-25 CAULK AND FS-195 INTUMESCENT STRIPS FOR INSULATED PIPES, PLASTIC PIPE OR CONDUIT, AND ELECTRICAL CABLE. SUBMIT UL LISTED APPLICATION DATA FOR EACH TYPE OF PENETRATION ENCOUNTERED. PIPING AND EQUIPMENT LABELS: LABEL ALL PIPING AND EQUIPMENT. PROVIDE FULL BAND OR STRIP TYPE MARKERS AND FLOW ARROWS ON PIPING. PROVIDE ENGRAVED PLASTIC VALVE TAGS WITH VALVE NUMBER AND ATTACH WITH STANDARD CHAIN OR S-HOOKS. PROVIDE ENGRAVED PLASTIC SIGN ON OR NEAR SPECIFIED EQUIPMENT. SCOPE OF WORK PROVIDE ALL LABOR MATERIALS, EQUIPMENT, FEES AND PERMITS, AND PAY ALL COSTS CONNECTED WITH THE INSTALLATION OF COMPLETE HEATING AND AIR CONDITIONING SYSTEMS. IT IS THE INTENT OF THE SPECIFICATION AND OF THE PLANS TO PROVIDE COMPLETE INSTALLATIONS. IT SHALL BE THE CONTRACTORS RESPONSIBILITY TO FURNISH ALL ITEMS OF MATERIALS AND LABOR AND ALL OTHER COSTS TO COMPLETE THE CONTRACT WITHIN THE INTENT OF THIS SPECIFICATION AND THE PLANS EVEN THOUGH EACH AND EVERY ITEM NECESSARY IS NOT SPECIFICALLY MENTIONED OR SHOWN. SUBMIT SHOP DRAWING AND/OR MANUFACTURER'S BROCHURES ON AIR CONDITIONING EQUIPMENT, EXHAUST FANS, AIR DEVICES, AND VENTILATORS. WORK INCLUDED BUT NOT INCLUSIVE THE MECHANICAL HVAC SYSTEM REQUIRED FOR THIS WORK AS INDICATED ON THE DRAWINGS INCLUDES BUT IS NOT LIMITED TO: PACKAGE ROOFTOP UNITS INCLUDING PRE-FAB FACTORY CURBS, STARTERS, SMOKE DETECTORS, ETC COMPLETE WITH ALL SPECIALTIES EXHAUST FANS, MAKEUP AIR FANS, INCLUDING PRE-FAB CURBS, STARTERS, ETC COMPLETE WITH ALL SPEACIALTIES ALL SUPPLY, RETURN, MAKE-UP, VENTILATION, AND EXHAUST DUCTWORK, INCLUDING DISTRIBUTION DAMPERS, PLENUMS, TURING VANES, GRILLES, REGISTERS, AND DIFFUSERS. ALL SUPPLY AND RETURN HYDRONIC PIPING. TEMPERATURE CONTROL SYSTEM AND 24 VOLT WIRING. THERMAL AND ACOUSTIC INSULATION OF DUCTS THERMAL INSULATION OF PIPING. INSPECTIONS, TESTING AND BALANCING OF HVAC VIBRATION ISOLATION DEVICES AIR CONDITIONING EQUIPMENT AIR CONDITIONING EQUIPMENT SHALL BE OF CAPACITIES CHARACTERISTICS, SIZE, ETC AS INDICATED AND SCHEDULED ON THE DRAWINGS COOLING COIL SECTION SHALL INCLUDE REFRIGERATION COMPRESSOR COOLING COIL, CONDENSATE COILS, CONDENSER FAN, REFRIGERANT PIPING SYSTEM, CONTROLS, ETC. HEATING SECTIONS AND ACCESSORIES SHALL BE AS SCHEDULED UNITS SHALL BE COMPLETE WITH THERMOSTATS (HEAT/COOL/OFF/ON/AUTO) EXHAUST FANS AND MAKE-UP FANS EXHAUST AND MAKEUP FANS SHALL BE OF CAPACITIES CHARACTERISTICS, SIZE, ETC AS INDICATED AND SCHEDULED ON THE DRAWINGS. EACH FAN SHALL BE AMCA RATED AND COMPLETE WITH MOTORS DRIVE AND ACCESSORIES AS SCHEDULED ON THE DRAWINGS DUCTWORK AND PLENUMS DUCTS AND PLENUMS SHALL BE FABRICATED IN ACCORDANCE WITH THE LATEST ADDITION OF THE ASHRAE GUIDE AND SMACNA MANUAL DUCTWORK: G60 GALVANIZED SHEET STEEL; LOCK FORMING QUALITY; CONSTRUCTED TO THE LATEST EDITION OF SMACNA “HVAC DUCT CONSTRUCTION STANDARDS”; +/- 1” W.C. PRESSURE CLASSIFICATION, SEAL CLASS “C”; WITH GALVANIZED STEEL FASTENERS, ANCHORS, ANGLES, STRAPS, ETC. SEAL ALL SEAMS (LONGITUDINAL AND TRANSVERSE) AIRTIGHT WITH UNITED MCGILL “UNI-GRIP” UL LISTED, WATER BASED, NON-HARDENING, ELASTIC SEALANT OR EQUIVALENT. TAPE NOT ALLOWED. IN EACH SQUARE ELBOW PROVIDE AIR-FOIL PATTERN DOUBLE THICKNESS TURNING VANES. TWNING VANES SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE SMACNA MANUAL AT EACH BRANCH DUCT FROM MAIN, PROVIDE 150% TAKE OFF AND A SPLITTER DAMPER CONSISTING OF BLADE ON A SQUARE OPERATING ROD FITTED WITH AN ADJUSTING DEVICE UNLESS OTHERWISE INDICATED ON THE PLANS. THE ADJUSTING DEVICES LOCATED IN FINISHED CEILINGS SHALL BE VENTFABRICS, INC, NO. 666, WITH THE ADJUSTING DEVICE SECURELY FASTENED TO THE FURRING AND CEILING AND COVER SHALL BE PAINTED TO MATCH CEILING. WHERE SPLITTERS OCCUR ABOVE REMOVABLE CEILING, THE DAMPER QUADRANT SHALL BE ABOVE THE CEILING AGAINST THE DUCT AND SHALL BE VENTFABRICS, NC NO. 637 AT EACH DUCT OR PLENUM CONNECTION TO FANS OR AIR UNITS, PROVIDE A FLEXIBLE CONNECTION OF VENTIFABRICS, 'VENTGLASS' 30 OZ. INSTALLED WITH 1-1/2” SLACK TO RENDER IT FLEXIBLE AT EACH ROUND DUCT TAP-OFF FROM MAH DUCTWORK SHALL BE EQUIVALENT TO THERMOFLEX TD BELL MOUTH TWIST-IN CONNECTIONS WITH INTEGRAL DAMPER FLEXIBLE INSULATED METAL DUCT SHALL BE SELF SUPPORTING, SPIRAL ALUMINUM, CORRUGATED, WITH 1” THICK INSULATION EQUAL TO CLEVAFORM SPV. CEILING DIFFUSERS, RETURN GRILLES SIZE AS INDICATED ON THE DRAWINGS EQUAL TO TITUS AS SCHEDULED ON THE DRAWINGS. DUCT INSULATION INSULATION SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURES RECOMMENDATIONS AND BY MECHANICS SKILLED AND PERMANENTLY ENGAGED IN INSULATING. UNSIGHTLY WORK SHALL BE JUST CAUSE FOR REJECTION SUPPLY, RETURN AND OUTSIDE AIR 1” THICK, 3/4 LB DENSITY FOIL BACKED FIBERGLASS WRAPPED WITH VAPOR SEALED JOINTS. INSULATION OF ALL DUCTWORK WHICH INCLUDES ALL SUPPLY AIR DUCTWORK, ALL MAKE-UP/OUTSIDE AIR DUCTWORK, ALL RETURN AIR DUCTWORK, AND THE BACKS OF ALL DIFFUSERS. ALL APPARATUS CASINGS SHALL BE ACOUSTICALLY LINED. HYDRONIC PIPING SYSTEMS FURNISH AND INSTALL A COMPLETE HYDRONIC SYSTEM AS SHOWN ON THE DRAWINGS AND/OR HEREINAFTER SPECIFIED. ALL PIPING SHALL RUN STRAIGHT AS POSSIBLE GRADE AND VALVE ALL HYDRONIC PIPING WITH 3/4” HOSE END VALVES TO PERMIT COMPLETE DRAINAGE OF THE SYSTEM. VENT ALL HIGH POINTS IN EQUIPMENT ROOMS AS NECESSARY WITH AUTOMATIC AIR VENTS PIPED TO CONVENIENT DRAIN. ALL HIGH POINTS IN SYSTEM OUTSIDE OF EQUIPMENT ROOMS WITH COMBINATION AUTOMATIC/MANUAL AIR VENTS AS REQUIRED TO RELIEVE AIR IN THE SYSTEM. FURNISH AND INSTALL DIELECTRIC UNIONS AT EACH CONNECTION OF DISIMMILAR METALS. HYDRONIC PIPING ABOVE GRADE PIPING UP THROUGH 2-1/2”: SCHEDULE 40 STEEL PIPE WITH MALLEABLE IRON THREADED FITTINGS, OR TYPE “L” COPPER TUBE WITH WROUGHT COPPER FITTINGS AND 95-5 NO LEAD SOLDER. ABOVE GRADE PIPING 3” AND LARGER: SCHEDULE 40 STEEL PIPE WITH CAST STEEL WELDING FITTINGS. INSULATE ALL CHILLED WATER AND HEATING HOT WATER PIPING WITH U.L. APPROVED, WHITE, ALL SERVICE, GLASS FIBER, SNAP-ON, PIPE INSULATION. INSULATE FITTINGS WITH GLASS FIBER BLANKET INSULATION AND PREMOLDED P.V.C. COVERS. ALL MATERIALS SHALL HAVE A SMOKE DEVELOPED RATING OF 50 OR LESS AND A FLAME SPREAD RATING OF 25 OR LESS. INSULATION SHALL PASS UNINTERRUPTED THROUGH HANGERS. VAPOR BARRIERS SHALL BE CONTINUOUS, AND SEALED WITH “NON-BREATHING” MASTIC ON COLD PIPING. ALL RAW EDGES OF INSULATION SHALL BE NEATLY TRIMMED AND SEALED WITH MASTIC. INSULATION THICKNESS BELOW BASED ON INSULATION CONDUCTIVITY VALUE NOT EXCEEDING 0.27 BTU*IN/(HR*FT^2*°F): HOT WATER, CHILLED WATER, BRINE AND REFRIGERANT - ALL PIPE SIZES, 1.5” THICK. STARTERS, CONTROLLERS AND RELAYS THAT ARE PART OF THE DIVISION 23 EQUIPMENT ARE PROVIDED BY EQUIPMENT SUPPLIERS, ELECTRICAL CONTRACTORS OR OTHERS. VERFY WITH EQUIPMENT SPECIFICS IN CONTRACT DOCUMENTS FOR ADDITIONAL INFORMATION. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL ELEMENTS OF INSTALLATION, INCLUDING ALL WIRING, ETC. ALL WATER PIPING SHALL BE PRESSURIZED HYDRAULICALLY AT 150 PSI AND THIS PRESSURE SHALL BE HELD WITHOUT ADDITIONAL PERSSURIZATION FOR NOT LESS THAN ONE (1) HOUR. EQUIPMENT, ETC. IN THE SYSTEM THAT ME BE DAMAGED BY THIS PRESSURE SHALL BE ISOLATED OR DISCONNECTED FROM THE SYSTEM. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR BALANCING ENTIRE HVAC SYSTEM: HYDRONIC PIPING, HYDRONIC DEVICES, DUCTS, DIFFUSERS, FANS EXHAUST AND SUPPLY FANS; PER AIR BALANCE SCHEDULE FOUND WITHIN THESE DOCUMENTS. WHEN PROPERLY BALANCED, FIX AND MARK DAMPER SETTINGS ON EACH PIECE OF EQUIPMENT. A.A.B.C. OR N.E.B.B. CERTIFIED AIR BALANCE SPECIALITY CONTRACTOR IS RECOMMENDED TO PERFORM THE AIR BALANCE AND CREATE A REPORT FOR ENGINEER'S REVIEW. SCOPE OF WORK. PROVIDE ALL MATERIALS, EQUIPMENT, LABOR FEES AND PERMITS, AND PAY ALL COSTS CONNECTED WITH THE INSTALLATION OF COMPLETE PLUMBING SYSTEMS AND AS SHOWN ON PLANS AND AS HEREINAFTER SPECIFIED IT IS THE INTENT OF THIS SPECFICATION AND OF THE PLANS TO PROVIDE COMPLETE INSTALLATIONS. IT SHALL BE THE CONTRACTORS RESPONSIBILITY TO FURNISH ALL (THIS OF MATERIAL AND LABOR AND ALL OTHER COSTS TO COMPLETE THE CONTRACT WITHIN THE INTENT OF THIS SPECFICATICN AND THE PLANS EVEN THOUGH EACH AND EVERY ITEM NECESSARY IS NOT SFECFICALLY MENTIONED OR SHOWN. SUBMIT MANUFACTURERS BROCHURES ON PLUMBING FIXTURES TO THE ARCHITECT / ENGINEER FOR APPROVAL WORK INCLUDED BUT NOT INCLUSIVE THE PLUMBING SYSTEM REQUIRED FOR THIS WORK AS INDICATED ON THE DRAWINGS AND INCLUDES, BUT IS NOT LIMITED TO: DOMESTIC COLD WATER SYSTEM, INCLUDING DISTRIBUTION AND BACK-FLOW PREVENTION, AS REQUIRED BY CODE AND CONNECTION TO WATER MAIN. DOMESTIC HOT WATER SYSTEM INCLUDING WATER HEATER CIRCULATING PUMPS AND DISTRIBUTION. SANITARY SEWER SYSTEM INCLUDING DISTRIBUTION AND CONNECT TO SANITARY SEWER MAIN. NATURAL GAS SYSTEM, INCLUDING DISTRIBUTION, METER AND CONNECTION TO GAS MAIN. PLUMBNG FIXTURES AND TRIM INCLUDING FURNISHING, SETTING, AND FINAL CONNECTIONS. GAS AND CONDENSATE DRAIN CONNECTIONS TO ALL AIR CONDITIONING EQUIPMENT. THERMAL INSULATION OF PIPING. ROUGH-IN AND FINAL CONNECTIONS FOR OWNER FURNISHED EQUIPMENT AND EQUIPMENT FURNISHED BY OTHER TRADES. ALL PERMITS AND FEES. INSPECTION AND TESTING. UTILITY CONNECTIONS THIS CONTRACTOR SHALL, BEFORE COMMENCEMENT OF THE PROJECT, VERIFY THE LOCATION, DEPTH, SIZE, AND PRESSURE OR GRADE OF ALL UTILITY LINES TO WHICH HE IS TO MAKE CONNECTIONS FOR SERVICE FOR ANY REASON, CONDITIONS APPEAR THAT WILL ADVERSELY AFFECT THE PROPER INSTALLATION AND OPERATION OF THE SYSTEMS, SUCH CONDITIONS SHALL BE REPORTED TO THE ARCHITECT IN WRITING FOR HIS DECISION. ALL CHARGES FOR CONNECTIONS TO UTILITY SERVICES AND COST FOR CUTTING AND PATCHING OF PAVING, CURBS, WALKS, ETC, REQUIRED FOR THE SERVICES SHALL BE INCLUDED IN THE BID. SANITARY SEWER SYSTEM AND CONDENSATE DRAIN FURNISH AND INSTALL A COMPLETE SANITARY SYSTEM OF SOIL, WASTE AND VENT PIPING FOR ALL FIXTURES, DRAINS, EQUIPMENT DISCHARGES, ETC. AS SHOWN ON THE DRAWINGS AND/OR HEREINAFTER SPECIFIED. ALL PIPING SHALL RUN STRAIGHT AS POSSIBLE AND INSTALLED TO BE GRADE 1/4' PER FOOT MINIMUM UNLESS OTHERWISE NOTED ON THE PLANS, ALL SANITARY SYSTEM SOIL, WASTE, AND VENT PIPING SHALL BE ASPHALT COATED SERVICE WEIGHT CAST IRON SOIL PIPE AND FITTINGS. JOINTS SHALL BE MADE WITH 'TY-SEAL' DOUBLE SEAL NEOPRENE GASKETS AND 'LUBRFAST' COMPOUND. THE CONTRACTOR SHALL INSTALL ALL UNDERGROUND SANITARY WITH LEAD AND OAKUM JOINTS. CAULKING LEAD DEPTH SHALL NOT BE LESS THAN 1”. AT THE CONTRACTORS OPTION, AND WHERE ALLOWED BY LOCAL CODE, THE SANITARY SYSTEM MAY BE CONSTRUCTED OF PVC PIPING (DWV GRADE) AND 'DRAINAGE WASTE' FITTINGS. INSTALL THE SYSTEM IN ACCORDANCE WITH THE LOCAL CODE SANITARY VENTS SHALL EXTEND 15” ABOVE ROOF. FLASH SANITARY VENTS WITH A FABRICATED WATERPROOFING FLASHING CONSISTING OF A BASE AND A RISER SLEEVE ALL MADE OF 4 LB SHEET LEAD. JOINTS AND SEAMS OF FABRICATED FLASHINGS SHALL BE WELDED. FLASHING BASE SHALL EXTEND OVER THE ROOF 12' FROM THE STACK. DRESS THE FLASHING RISER OVER TOP OF AND DOWN INTO THE VENT STACK FOR A RAIN TIGHT LEAK-PROOF INSTALLATION. (FLASH WITH ROOFING MANUFACTURER ACCESSORIES TO MAINTAIN WARRANTY ON PENETRATIONS.) PROVIDE CLEANOUTS WHERE INDICATED ON THE PLANS AND AS REQUIRED FOR SNAKING OF THE SANITARY SYSTEM PIPING. ADJUST CLEAN-OUT BODIES TO HAVE THE ACCESS COVER TOP SURFACE FLUSH WITH FINISH FLOOR CLEAN-OUT SPACNG IN STRAIGHT PIPE LENGTHS SHALL NOT EXCEED 30' INSIDE AND 100' OUTSIDE EXPOSED PIPE CONNECTIONS TO WASTE STACKS LOCATED IN TOILETS AND OTHER FNISHED SPACES SHALL BE CHROME PLATED. PROVIDE CONDENSATE DRAIN PIPING FOR THE A/C UNITS AS INDICATED ON THE PLANS AND AS REQUIRED. PIPING SHALL BE TYPE M HARD COPPER WITH CAST BRASS DRAINAGE FITTINGS. MAKE JOINTS WITH 95/5 SOLDER. FLOOR DRAINS INSTALL FLOOR DRAINS SO THAT THE TOP OF DRAIN IS FLUSH WITH FINISH FLOOR QUARRY TILE OR CONCRETE. SLOPE TO DRAIN SHALL BE IN ACCORDANCE WITH THE FOUNDATION PLAN. SHALL BE OF CAPACITIES, CHARACTERISTICS, SIZES, ETC, AS INDICATED AND SCHEDULED ON THE DRAWINGS. GAS SYSTEM FURNISH AND INSTALL A COMPLETE OF GAS PIPING A5 INDICATED ON THE PLANS AND AS SPECIFIED. GAS PIPING SHALL BE STANDARD WEIGHT BLACK STEEL PIPE ALL INTERMEDIATE GAS PRESSURE PIPE AND ALL PIPE 2 1/2' AND LARGER SHALL HAVE WELDED JONTS. FITTINGS 1-1/2' AND SMALLER SHALL BE STANDARD WEIGHT MALLEABLE IRON SCREWED. FITTINGS 2' AND LARGER SHALL BE TUBE-IURN' OR EQUAL, STANDARD WEIGHT FORGED STEEL WELD FITTNGS. SCREW THREAD JOINTS SHALL BE MADE WITH AN APPROVED THREAD COMPOUND. DOMESTIC MANUFACTURED. ALL EQUIPMENT CONNECTIONS SHALL BE PRECEDED BY A MANUAL STOP COCK. GAS COCK 2” AND SMALLER SHALL BE CRANE COMPANY NO. 1228 PROVIDE SWING CONNECTIONS THROUGHOUT THE SYSTEM TO ALLOW FOR ADEQUATE HORIZONTAL AND VERTICAL EXPANSION AND CONTRACTION, UNIONS OF COMPANION FLANGES SHALL BE PROVIDED FOR REMOVAL OF EQUIPMENT. WATER PIPING SYSTEM FURNISH AND INSTALL A COMPLETE WATER SYSTEM WITH BRANCH LINES, SERVICING ALL PLUMBING FIXTURES, FAUCETS, EQUIPMENT, ETC., AS INDICATED ON THE PLANS AND HEREIN SPECFIED. ALL WATER PIPING LOCATED ABOVE GRADE 2-1/2' AND SMALLER SHALL BE TYPE L HARD COPPER TUBING WITH ASA B16.22 WROUGHT COPPER FITTINGS. JOINTS SHALL BE MADE WITH LEAD FREE SOLDER WATER PIPING LOCATED BELOW GRADE SHALL BE TYPE L SOFT COPPER THERE SHALL BE NO JOINTS IN TUBING LOCATED UNDER THE SLAB PIPING SHALL BE INSTALLED WITH A GRADE FOR DRAINAGE TOWARD MAIN SUPPLY RISERS AND TO FIXTURE CONNECTIONS TO ALLOW COMPLETE DRAINAGE OF THE SYSTEM WATER SYSTEM SHALL BE STERILIZED WITH A SOLUTION IN ACCORDANCE WITH THE REQUIREMENTS OF THE STATE PUBLIC HEALTH DEPARTMENT. PUMP THE HTH SOLUTION INTO THE WATER SYSTEM AND FILL THE COMPLETE SYSTEM, INCLUDING BRANCH PIPES. EACH OUTLET SHALL BE PURGED OF AIR DURING THE STERILIZATION PROCESS. AT EACH FIXTURE FAUCET PROVIDE A STOP VALVE IN EACH SUPPLY. STOP VALVES SHALL BE IN ACCORDANCE WITH PLUMBING CODE INSTALL AIR CHAMBERS 1'6” MINIMUM HEIGHT AT ALL CONNECTIONS. ALL HORIZONTAL RUNS OF PIPING SHALL BE SUSPENDED FROM THE STRUCTURAL MEMBERS ABOVE BY MEANS OF APPROVED HANGERS. SUPPORTS AND HANGERS SHALL BE INSTALLED TO PERMIT FREE EXPANSION AND CONTRACTION IN THE PIPING SYSTEM PROVIDE ACCESS DOORS AS REQUIRED FOR ACCESS TO ALL VALVES BEHIND GYPSUM BOARD CEILINGS AND WALLS. PAINT TO MATCH FURINISH AND INSTALL DIELECTRIC UNIONS AT EACH CONNECTION OF DISIMMILAR METALS. INSTALL CHECK VALVES IN THE HOT AND COLD WATER BRANCHES TO MIXING TYPE FAUCETS FOR MIXING VALVES. PLUMBING PIPING INSULATION INSULATION OF ALL HOT AND COLD WATER PIPING WITHIN THE BUILDING, ALL CONDENSATE DRAIN PIPING, EXCEPT FOR DRAIN LINES ABOVE THE ROOF DOMESTIC COLD AND HOT WATER - 1” MOLDED FIBERGLASS WITH FIRE RESISTANT JACKET. ELBOW AND FITTINGS WILL BE THE SAME THICKNESS. 1/2' AT COLD WATER REFRIGERANT-SAME AS DOMESTIC WATER CONDENSATE DRAIN - 1/2* ARMAFLEX. ROOF AND OVERFLOW DRAINS - HORIZONTAL RUN ONLY* SAME AS DOMESTIC WATER PLUMBING FIXTURES PLUMBING FIXTURES SHALL BE OF CAPACITIES, CHARACTERISTICS, SIZES, ETC, AS INDICATED AND SCHEDULED ON THE DRAWINGS. WATER HEATERS WATER HEATER SHALL BE OF CAPACITIES, CHARACTERISTICS, SIZES, ETC, AS INDICATED AND SCHEDULED ON THE DRAWINGS. TESTS AND INSPECTIONS WASTE AND VENT PIPING SHALL BE TESTED ON COMPLETION OF THE ROUGH WORK AND BEFORE FIXTURES AND TRAPS ARE CONNECTED. ALL OPENINGS, EXCEPT HIGHEST VENTS ARE TO BE PLUGGED AND THE SYSTEM COMPLETELY TESTED WITH WATER. SYSTEM SHALL STAND WITHOUT LEAKS OR LOSS OF WATER FOR A PERIOD OF NOT LESS THAN FOUR (4) HOURS. ALL WATER PIPING SHALL BE PRESSURIZED HYDRAULICALLY AT 150 PSI AND THIS PRESSURE SHALL BE HELD WITHOUT ADDITIONAL PRESSURIZATION FOR NOT LESS THAN ONE (1) HOUR. EQUIPMENT, ETC. IN THE SYSTEM THAT ME BE DAMAGED BY THIS PRESSURE SHALL BE ISOLATED OR DISCONNECTED FROM THE SYSTEM. GAS PIPING SHALL BE TESTED WITH AIR PRESSURE BY MERCURY GAUGE TO A PRESSURE EQUAL TO 18” MERCURY COLUMN FOR A PERIOD OF FOUR (4) HOURS. SYSTEM SHALL HOLD THE PRESSURE WITHOUT RE- PRESSURIZATION. FIRE PROTECTION SCOPE OF WORK PROVIDE RECONFIGURED / NEW FIRE PROTECTION SYSTEM DESIGNED AND INSTALLED IN ACCORDANCE WITH NFPA 13. RECONFIGURED / NEW SYSTEM SHALL BE HYDRAULICALLY CALCULATED AND SHALL BE DESIGNED WITH A 10% MARGIN OF SAFETY BELOW THE WATER SUPPLY CURVE AS DETERMINED BY A HYDRANT FLOW TEST. PROVIDE ALL MATERIALS, EQUIPMENT, LABOR FEES AND PERMITS, AND PAY ALL COSTS CONNECTED WITH THE INSTALLATION OF COMPLETE PLUMBING SYSTEMS AND AS SHOWN ON PLANS AND AS HEREINAFTER SPECIFIED IT IS THE INTENT OF THIS SPECIFICATION AND OF THE PLANS TO PROVIDE COMPLETE INSTALLATIONS. IT SHALL BE THE CONTRACTORS RESPONSIBILITY TO FURNISH ALL (THIS OF MATERIAL AND LABOR AND ALL OTHER COSTS TO COMPLETE THE CONTRACT WITHIN THE INTENT OF THIS SPECIFICATION AND THE PLANS EVEN THOUGH EACH AND EVERY ITEM NECESSARY IS NOT SPECIFICALLY MENTIONED OR SHOWN. SUBMIT MANUFACTURERS BROCHURES ON FIRE PROTECTION FIXTURES TO THE ARCHITECT / ENGINEER FOR APPROVAL. WORK INCLUDED BUT NOT INCLUSIVE THE FIRE PROTECTION SYSTEM REQUIRED FOR THIS WORK AS INDICATED ON THE DRAWINGS AND INCUDES, BUT IS NOT LIMITED TO: A COMPLETE BUILDING FIRE PROTECTION SYSTEM INCLUDING DISTRIBUTION AND CONNECTION TO WATER SUPPLY. ALL PERMITS INSPECTION AND TESTING FIRE PROTECTION SYSTEMS SHALL BE IN FULL ACCORDANCE WITH NFPA BULLETINS, GOVERNING INSURANCE CODES, AND OWNERS INSURANCE REQUIREMENTS EXISITNG CONDITIONS CONTRACTOR SHALL VISIT JOBSITE PRIOR TO BIDDING AND FIELD VERIFY EXTENT OF WORK AND EXACT LOCATIONS/CONDITIONS OF ALL EXISITNG CONSTRUCTION, STRUCTURAL, CLEARANCES, ELEVATORS, SERVICE POINTS ETC AND REQUIRED FOR COMPLETE AND CORRECTLY OPERATING SYSTEM. CONTRACTORS SHALL COORDINATE WITH HENERAL CONTRACTOR OWNERS REP. AND LANDLORD REP AND REPORT CONFLICTS OR PROBLEMS WHICH MAY ARISE. PRIOR TO LOCATING AND INSTALLING ANY EQUIPMENTOR FIXTURES CONTRACTOR SHALL INCLUDE ALL COST IN HIS BUID WITH NO ADDITIONAL EXPENSE TO THE OWNER. RELOCATE ALL EXISITNG DUCTWORK, PIPING OR EQUIPMENT AS SHOWN AND AS REQUIRED TO ACCOMMODATE THE NEW CONSTRUCTION WHETHER OR NOT THE EXISTING MATERIAL IS SHOWN ON THE DRAWINGS. CONTRACTOR SHALL COORDINATE ALL CUTTING PATCHING OF EXISITNG WALLS FLOORS AND ROOF AS REQUIRED FOR HIS WORK WITH GENERAL CONTRACTOR DPA Project: Sheet Number: COPYRIGHT 2013 - DAVIS PARTNERSHIP, P.C. Sheet Title: 2301 Blake Street, Suite 100 Denver, CO 80205 303.861.8555 0225 Main Street, Unit C101 Edwards, CO 81632 970.926.8960 Denver Vail Consultant Issue/RevisionsDateNo. Sheet Information Project Information Permit Set30 August 2013 MedicalCenter VailValley Vail, Colorado 81657 US Bank Building 108 South Frontage Road Suite 306 S: \ B G P r o j e c t s \ 8 7 3 9 . 3 9 V V M C C o n c i e r g e C l i n i c \ C a d \ B G C E C A D\ 8 7 3 9 3 9 M 1 2 . d w g P r i n t e d B y : c ad d - j a c A u g u s t 3 0 , 2 0 1 3 - 1 1 : 0 0 a m L C - J A C COPYRIGHT 2013 B ANZEG EAUDIN (970)949-6108 (303) 278-3820 (970) 221-5691 (505) 323-9070 Vail: Denver: Fort Collins: Albuquerque: www.bgce.com Multi-Specialty Clinic 13915.00.000 MARTIN MARTIN 0225 MAIN STREET; SUITE C101 EDWARDS, COLORADO 81632 970.581.2546 BEAUDIN GANZE CONSULTING ENGINEERS 222 CHAPEL PLACE, UNIT AC-201 P.O. BOX 9650 AVON, COLORADO 81620 970.949.6108 M1.2 MECHANICAL SPECIFICATIONS Reviewed for Code Compliance Code: 2012 International Building Code (IBC) SCALE: MECHANICAL DEMOLITION PLAN 1/8" = 1'-0" T T REMOVE DUCT BACK TO POINT OF CONNECTION AT ASSOCIATED MAIN DUCT. COMPLETELY CAP, SEAL, AND INSULATE (E) DUCT MAIN AT SHAFT. (E) SUPPLY AIR DIFFUSER TO BE REMOVED. (E) RETURN AIR GRILLE TO BE REMOVED. (E) HWS/R PIPING TO BE REMOVED BACK TO (E) VALVES AND CAPPED. (E) PNEUMATIC THERMOSTAT TO BE REMOVED. (E) VAV BOX TO BE REMOVED. APPROXIMATE LOCATION OF (E) VAV BOX FOR PRE-TEST. CONTRACTOR TO VERIFY EXACT LOCATION AND NUMBER OF VAV BOXES. (E) 10" ROUND DUCT UP TO ROOF CAP TO BE REMOVED. ROOF TO BE COMPLETELY PATCHED, SEALED, AND INSULATED IN ITS PLACE. (E) SA AND RA DUCTS UP TO (E) RTU TO BE REMOVED. DEMOLITION FLAG NOTES: 1 1 2 3 4 3 3 3 3 3 3 3 3 3 3 3 3 444 4 4 4 4 5 4 1.(E) BUILDING PNEUMATIC SYSTEM TO BE RECONFIGURED AS REQUIRED TO ACCOMMODATE REMOVAL OF (E) PNEUMATIC THERMOSTATS SHOWN HEREIN. DEMOLITION NOTES: 5 6 5 5 6 7 7 7 7 7 7 7 7 7 8 8 7 2 3 3 3 3 3 4 4 4 6 9 9 DPA Project: Sheet Number: COPYRIGHT 2013 - DAVIS PARTNERSHIP, P.C. Sheet Title: 2301 Blake Street, Suite 100 Denver, CO 80205 303.861.8555 0225 Main Street, Unit C101 Edwards, CO 81632 970.926.8960 Denver Vail Consultant Issue/RevisionsDateNo. Sheet Information Project Information Permit Set30 August 2013 MedicalCenter VailValley Vail, Colorado 81657 US Bank Building 108 South Frontage Road Suite 306 S: \ B G P r o j e c t s \ 8 7 3 9 . 3 9 V V M C C o n c i e r g e C l i n i c \ C a d \ B G C E C A D\ 8 7 3 9 3 9 M D 2 1 . d w g P r i n t e d B y : c ad d - j a c A u g u s t 3 0 , 2 0 1 3 - 1 1 : 0 0 a m L C - J A C COPYRIGHT 2013 B ANZEG EAUDIN (970)949-6108 (303) 278-3820 (970) 221-5691 (505) 323-9070 Vail: Denver: Fort Collins: Albuquerque: www.bgce.com Multi-Specialty Clinic 13915.00.000 MARTIN MARTIN 0225 MAIN STREET; SUITE C101 EDWARDS, COLORADO 81632 970.581.2546 BEAUDIN GANZE CONSULTING ENGINEERS 222 CHAPEL PLACE, UNIT AC-201 P.O. BOX 9650 AVON, COLORADO 81620 970.949.6108 MD2.1 MECHANICAL DEMOLITION PLAN Reviewed for Code Compliance Code: 2012 International Building Code (IBC) SCALE: MECHANICAL DEMOLITIONROOF PLAN 1/8" = 1'-0" (E) CONDENSING UNIT. (E) CONDENSING UNIT. (E) RTU TO BE RE-BALANCED (E) RTU (E) RTU (E) EXHAUST FAN (E) SA DUCT (E) RTU TO BE REMOVED. PATCH ROOF AS REQUIRED FOR A COMPLETELY INSULATED, WATER TIGHT, AND SEALED ASSEMBLY INTEGRATED WITH EXISTING ROOFING. DEMOLITION FLAG NOTES: 1 1.(E) BUILDING PNEUMATIC SYSTEM TO BE RECONFIGURED AS REQUIRED TO ACCOMMODATE REMOVAL OF (E) PNEUMATIC CONTROLS ASSOCIATED WITH WORK SHOWN HEREIN. DEMOLITION NOTES: 1 DPA Project: Sheet Number: COPYRIGHT 2013 - DAVIS PARTNERSHIP, P.C. Sheet Title: 2301 Blake Street, Suite 100 Denver, CO 80205 303.861.8555 0225 Main Street, Unit C101 Edwards, CO 81632 970.926.8960 Denver Vail Consultant Issue/RevisionsDateNo. Sheet Information Project Information Permit Set30 August 2013 MedicalCenter VailValley Vail, Colorado 81657 US Bank Building 108 South Frontage Road Suite 306 S: \ B G P r o j e c t s \ 8 7 3 9 . 3 9 V V M C C o n c i e r g e C l i n i c \ C a d \ B G C E C A D\ 8 7 3 9 3 9 M D 2 2 . d w g P r i n t e d B y : c ad d - j a c A u g u s t 3 0 , 2 0 1 3 - 1 1 : 0 1 a m L C - J A C COPYRIGHT 2013 B ANZEG EAUDIN (970)949-6108 (303) 278-3820 (970) 221-5691 (505) 323-9070 Vail: Denver: Fort Collins: Albuquerque: www.bgce.com Multi-Specialty Clinic 13915.00.000 MARTIN MARTIN 0225 MAIN STREET; SUITE C101 EDWARDS, COLORADO 81632 970.581.2546 BEAUDIN GANZE CONSULTING ENGINEERS 222 CHAPEL PLACE, UNIT AC-201 P.O. BOX 9650 AVON, COLORADO 81620 970.949.6108 MD2.2 MECHANICAL DEMOLITION ROOF PLAN Reviewed for Code Compliance Code: 2012 International Building Code (IBC) COPIER SCALE: MECHANICAL PLAN - 3RD LEVEL 1/8" = 1'-0" 1.REFER TO DIAGRAMS AND , SHEET M3.1 FOR AIR DEVICE INSTALLATION. 2.REFER TO DIAGRAMS AND , SHEET M3.1 FOR BRANCH DUCT TAKEOFFS. 3.REFER TO DIAGRAM , SHEET M3.1 FOR VAV BOX INSTALLATION. 4.REFER TO DIAGRAM , SHEET M3.1 FOR VAV BOX COIL PIPING DIAGRAM. 5.REFER TO DIAGRAM , SHEET M3.1 FOR PIPE HANGER DIAGRAM. 6.EXISTING RTU AND VAV BOXES ON THIRD FLOOR SHALL BE RE-BALANCED AFTER NEW CONSTRUCTION AS PART OF THIS PROJECT SCOPE. 7.HWS/HWR TO INDIVIDUAL VAV COILS IS TO BE 34" U.N.O. NOTES: 22x16 RA DUCT OPEN TO PLENUM. MOTORIZED DAMPER INTERLOCKED WITH EF-1 OPERATION. MOTORIZED DAMPER INTERLOCKED WITH RTU-1 OPERATION. ROUTE (N) DUCTWORK THROUGH (E) PENETRATIONS IN ROOF. PROVIDE CAPS AT ISOLATION VALVES. (E) HWS/HWR PIPING 1 FLAG NOTES: 2 3 B C D G E L H 18x16 14 x 1 2 14 x 8 A 185 24x24 TYP. 2 A 175 24x24 TYP. 2 16 x 1 2 A 325 24x24 D RA 24x24 10x8 A 100 24x24 6" Ø A 100 24x24 B 20 0 24 x 2 4 B 2 0 02 4 x 2 4 12x8 6x6 8x6 A 100 24x24 8x8 8x 8 B 25 0 24 x 2 4 D RA 24 x 1 2 D RA 24 x 1 2 20x8 20 x 8 8x 4 8x6 B 100 24x24 DRA 24x24 DRA 24x12 B100 24x24 6x618x14 A 125 24x24 10"Ø T 6"Ø 8x 8 1 T B 250 24x24 16x4 T T T 16x4 8x8 10x8 EXH UP 10 " Ø 6" Ø 8x 8 B 150 24x24 B 200 24x24 10x8 6"Ø 8x8 8x 6 10x10 C 100 24x24 B 150 24x12B 250 24x12 16 x 4 16x4 16x4 D 100 24x12 d 40 0 24 x 1 2 D 350 24x12 8" Ø 8"Ø 8"Ø 16x12 D 370 24x12 14"Ø 24x22 RA UP 20x18 SA UP 3 3 D 100 24x12 E100 8x8 10"Ø 6" Ø 8" Ø 12x10 -115 24x24 TYP. 4 2 10 x 8 B100 24x24 8" Ø 8x6 4 5 5 4 4 1" 1" 34" 6 HWSHWR 6 DPA Project: Sheet Number: COPYRIGHT 2013 - DAVIS PARTNERSHIP, P.C. Sheet Title: 2301 Blake Street, Suite 100 Denver, CO 80205 303.861.8555 0225 Main Street, Unit C101 Edwards, CO 81632 970.926.8960 Denver Vail Consultant Issue/RevisionsDateNo. Sheet Information Project Information Permit Set30 August 2013 MedicalCenter VailValley Vail, Colorado 81657 US Bank Building 108 South Frontage Road Suite 306 S: \ B G P r o j e c t s \ 8 7 3 9 . 3 9 V V M C C o n c i e r g e C l i n i c \ C a d \ B G C E C A D\ 8 7 3 9 3 9 M 2 1 . d w g P r i n t e d B y : c ad d - j a c A u g u s t 3 0 , 2 0 1 3 - 1 1 : 0 1 a m L C - J A C COPYRIGHT 2013 B ANZEG EAUDIN (970)949-6108 (303) 278-3820 (970) 221-5691 (505) 323-9070 Vail: Denver: Fort Collins: Albuquerque: www.bgce.com Multi-Specialty Clinic 13915.00.000 MARTIN MARTIN 0225 MAIN STREET; SUITE C101 EDWARDS, COLORADO 81632 970.581.2546 BEAUDIN GANZE CONSULTING ENGINEERS 222 CHAPEL PLACE, UNIT AC-201 P.O. BOX 9650 AVON, COLORADO 81620 970.949.6108 M2.1 MECHANICAL PLAN - 3rd LEVEL Reviewed for Code Compliance Code: 2012 International Building Code (IBC) SCALE: MECHANICAL ROOF PLAN 1/8" = 1'-0" EF-1 10x8 EXH DN. 1.COORDINATE RTU LOCATION TO BE 10'-0" AWAY FROM ALL EXISTING PLUMBING VENT DISCHARGES. 2.REFER TO DIAGRAMS AND , SHEET M3.1 FOR RTU CURB AND CONDENSATE RAIN INSTALLATION. 3.REFER TO DIAGRAM , SHEET M3.1 FOR EXHAUST FAN INSTALLATION. NOTES: F J A (E) CONDENSING UNIT. (E) CONDENSING UNIT. (E) RTU TO BE RE-BALANCED (E) RTU (E) EXHAUST FAN (E) SA DUCT EXTERIOR DUCTWORK SHALL BE WRAPPED WITH 3" OF ELASTOMERIC FOAM INSULATION. ALUMINUM ALL SERVICE JACKET SHALL BE PROVIDED OVER ELASTOMERIC INSULATION. ALL JACKET SEAMS SHALL BE ON BOTTOM OF DUCT. SEAMS SHALL BE COATED WITH UV RESISTANT SILICONE. (N) SA/RA DUCTWORK SHALL BE ROUTED THROUGH EXISTING ROOF DUCT OPENINGS IN ROOF. ENLARGE OPENINGS AS REQUIRED. COMPLETELY PATCH, SEAL, AND INSULATE OPENINGS AROUND (N) DUCTWORK AND INTEGRATE INTO (E) ROOFING. 1 FLAG NOTES: 22x24 RA DN. 20x18 SA DN. 1 2 2 DPA Project: Sheet Number: COPYRIGHT 2013 - DAVIS PARTNERSHIP, P.C. Sheet Title: 2301 Blake Street, Suite 100 Denver, CO 80205 303.861.8555 0225 Main Street, Unit C101 Edwards, CO 81632 970.926.8960 Denver Vail Consultant Issue/RevisionsDateNo. Sheet Information Project Information Permit Set30 August 2013 MedicalCenter VailValley Vail, Colorado 81657 US Bank Building 108 South Frontage Road Suite 306 S: \ B G P r o j e c t s \ 8 7 3 9 . 3 9 V V M C C o n c i e r g e C l i n i c \ C a d \ B G C E C A D\ 8 7 3 9 3 9 M 2 2 . d w g P r i n t e d B y : c ad d - j a c A u g u s t 3 0 , 2 0 1 3 - 1 1 : 0 1 a m L C - J A C COPYRIGHT 2013 B ANZEG EAUDIN (970)949-6108 (303) 278-3820 (970) 221-5691 (505) 323-9070 Vail: Denver: Fort Collins: Albuquerque: www.bgce.com Multi-Specialty Clinic 13915.00.000 MARTIN MARTIN 0225 MAIN STREET; SUITE C101 EDWARDS, COLORADO 81632 970.581.2546 BEAUDIN GANZE CONSULTING ENGINEERS 222 CHAPEL PLACE, UNIT AC-201 P.O. BOX 9650 AVON, COLORADO 81620 970.949.6108 M2.2 MECHANICAL ROOF PLAN Reviewed for Code Compliance Code: 2012 International Building Code (IBC) 140° D PIPING DIAGRAM DOMESTIC WATER HEATER FLOOR D S NO SCALE SUPPORT FROM STRUCTURE AS REQUIRED. COLD WATER SUPPLY. DIAPHRAGM TYPE EXPANSION TANK. AMTROL ST-12. PIPE RELIEF VALVE INDIRECT TO DRAIN PAN. TERMINATE 1-1/2" ABOVE DRAIN PAN. SHELF WITH SAFE PAN, DRAIN PIPE FROM SAFE PAN TO SINK TAIL PIECE OR APPROVED RECEPTOR. HOT WATER TO PUBLIC FIXTURES.WATER HEATER 3/ 4 " CEILING N PROVIDE 3 DUCT DIAMETERS OF STRAIGHT DUCT DOWNSTREAM OF VAV BOX PRIOR TO ELBOWS OR TRANSITIONS. NO SCALE VAV BOX DIAGRAM E 8x8 ACCESS PANEL IN BOTTOM OF DUCT FOR HEATING COIL ACCESS. HOT WATER HEATING COIL SECTION. VAV DAMPER SUSPEND UNITS WITH 38"ALL-THREADED TOD AND OPTIONAL SUPPORT BRACKETS OR WITHIN GALVANIZED STEEL BANDS. CENTER AVERAGING AIRFLOW SENSOR. RIGID DUCT, NO FLEXIBLE DUCT, EQUAL TO VAV BOX INLET DUCT DIAMETER FOR A MINIMUM OF 3 DUCT DIAMETERS UPSTREAM OF VAV BOX PRIOR TO TRANSITION OR ELEBOWS. PROVIDE 18" CONTROL BOX CLEARANCE. HEATING HOT WATER PIPING. RE: DIAGRAM , THIS SHEET. L CONTROL BOX. ROUND DUCT OF SIZE INDICATED IN PLANS. PRESSURE-INDEPENDANT VAV BOX. ROOF EXHAUST FAN DIAGRAM NO SCALE ( FLAT ROOF ) PRE-FAB CURB WITH 112" INSULATION. ROOFING. ANCHOR FAN TO CURB. EXTEND (E) ROOFING OVER (N) ROOF CURB AND MAKE WATER TIGHT AS REQUIRED. DUCT TRANSITION FROM DUCT SIZE TO FAN INLET SIZE. 14" ROOF CURB WITH MINIMUM R-8 INSULATION. A (N) EF-1 NOTE: (N) FAN CURB INTERFACE WITH (E) ROOFING SHALL BE COMPLETELY WATERTIGHT AND WARRANTED FROM DEFICIENCIES FOR A PERIOD OF ONE YEAR. NOTE: ROOF PENETRATION SHALL BE FIELD-COORDINATED SUCH THAT PENETRATION IS CENTERED BETWEEN CONCRETE BEAMS OF ROOF STRUCTURE. VERIFY LOCATION WITH ENGINEER/OWNER PRIOR TO CUTTING PENETRATION. NOTE: INSTALLATION DETAILS OF ROOF CURB APPLY TO LOUVERED PENTHOUSE. CEILING DIFFUSER. NO SCALE TYPICAL DIFFUSER CONNECTION DIAGRAM EXTERIOR DUCT INSULATION. INSULATED FLEX DUCT. INTERNALLY LINED SUPPLY DUCT, OR AS NOTED IN SPECIFICATIONS. SPIN-IN FITTING WITH S.B.D. SHEET METAL STRAP S.S. WORM DRIVE CLAMP. SHEET METAL SHIELD B NOTE: FLEXIBLE DUCT CONNECTIONS TO BAND DUCT AND DIFFUSERS SHALL BE SEALED AIR TIGHT WITH MASTIC AND TAPE IN ACCORDANCE WITH UL 181B-FX. PROVIDE FLEXIBLE DUCT SUPPORT AS REQUIRED SUCH THAT FLEXIBLE DUCT HAS NO KINKS. AIR HANDLING UNIT DRAIN TRAP DIAGRAM NO SCALE 1" B A DRAIN PAN DRAIN LINE SHALL BE AT LEAST THE SAME SIZE AS THE NIPPLE ON THE DRAIN PAN. PITCH DOWN TOWARD DRAIN. CLEAN OUT, TYP. OPEN SANITARY DRAIN. COORDINATE DIMENSION "A" AND "B" WITH MANUFACTURER. PIPE THRU ROOF DIAGRAM NO SCALE 6" M I N . 24 GA. GALV. ROOF JACK W/ 6" FLANGE BY M.C., SET IN PLASTIC CEMENT BY G.C. PIPE BY M.C. 24 GA. GALV. STORM COLLAR BY M.C., CLAMP IN PLACE & CAULK WEATHERTIGHT. PIPE SLEEVE & CAULKING BY M.C. SOLDERED LAP SEAM 2 LAYERS OF FELT BY G.C. FINISHED ROOF FELTS BY G.C. 2" MIN. COOR'D ROOF PENETRATION AND SEALING WITH ROOF MANUFACTURER AND INSTALLING CONTRACTOR. GAS PIPING ON ROOF SUPPORT DIAGRAM NO SCALE: GAS LINE. U-BOLT. NUT. 16 GAUGE GALV. SHEET METAL TRIANGULAR PIPE SUPPORT 12" LONG. BOLT JUNCTION TOGETHER. DO NOT SECURE SUPPORT TO TREAD. ROOF TREAD SECURE TO ROOF. ROOF DECK. SUPPORT SHALL MEET THE APPROVAL OF THE ROOFING MANUFACTURER. 60°60° 60° 12" MIN. TYPICAL HANGER DIAGRAM NO SCALE THREADED ROD. HANGER. PIPE. HUNG FROM STRUCTURE. ALL PIPING WITH INSULATION TO HAVE INSULATION RUN FULL SIZE THROUGH HANGER WITH SHIELD AND INSERT.AI R F L O W NO SCALE USE DUCT SEALANT OR GASKETED FITTING ON HIGH VELOCITY DUCT. CONICAL SPIN-IN FITTING W/ MANUAL DAMPER, HANDLE, & LOCK NUT. FLEX DUCT. WORM DRIVE S.S. CLAMP. DIAGRAM FOR LOW & HIGH VELOCITY DUCTWORK EXCEPT UPSTREAM OF VAV BOXES. OMIT DAMPER & FLEX DUCT UPSTREAM OF VAV BOXES. ROUND DUCT TAKE-OFF DIAGRAMOFF DIAGRAM 45° DUCT TAKE- 45° NO SCALE W H 1/4 OF "W" OR 6" MINIMUM. END BEARING. SINGLE BLADE DAMPER IF H<8" OPPOSED BLADE DAMPER IF H>=8" SEAL AIRTIGHT AROUND ENTIRE TAKE-OFF. NO SCALE SHEET METAL BOX (NO INSULATION FOR RETURN/EXHAUST, DUCT WRAP FOR SUPPLY) SHALL BE THE SIZE OF GRILLE DUCT CONNECTION NECK AND SHALL BE 4" HIGHER THAN HEIGHT OF CONNECTED DUCT HEIGHT. CEILING GRILLE OR DIFFUSER. SUPPLY, RETURN, OR EXHAUST AIR DUCT. 2-WAY COIL PIPING DIAGRAM NO SCALE COIL : 1.PIPE ALL MULTI-ROW COILS FOR COUNTERFLOW (WATER ENTERS MOST DOWNSTREAM COIL, LEAVES MOST UPSTREAM COIL). 2.REFER TO CONTROLS DRAWINGS FOR ADDITIONAL INFORMATION. 3.2-WAY VALVE NORMALLY OPEN FOR HEATING. STRAINER WITH BLOWDOWN AND CAP. MANUAL AIR VENT AT HIGHEST POINT IN PIPING. RETURN SUPPLY CDGH K FLM JNATURAL GAS TERMINATION DIAGRAM G 11'WC (FIELD VERIFY W/ MANUF.) INCREASE AS REQUIRED. GAS FIRED EQUIPMENT. PROVIDE PRV ASSEMBLY WHERE INDICATED ON PLANS. MATCH TO SCHEDULED EQUIPMENT. VENT OUTDOORS (AS REQ'D) PER MANUFACTURER'S WRITTEN INSTRUCTIONS. DIRT LEG. SHUT-OFF VALVE. UNION (TYP.) PRV P ROOFTOP UNIT DIAGRAM NO SCALE ROOF ROOFTOP UNIT FILL CURB WITH 8" BATT INSULATION. (2) LAYERS OF p" GYPSUM (TYPE X) PROVIDE 1"RIGID INSULATION ON VERTICAL SURFACES OF CURB (AS REQUIRED). ANGLE IRON SUPPORT STRUCTURE (SEAL PENETRATIONS AS REQUIRED). ROOF STRUCTURE (SEE PLANS FOR DETAILS). SEE PLANS FOR DUCT ROUTING FLASH CURB WEATHER TIGHT. COORDINATE WITH ROOF SUPPLIER. 6" FLEX CONNECTION AT DUCT CONNECTION. DPA Project: Sheet Number: COPYRIGHT 2013 - DAVIS PARTNERSHIP, P.C. Sheet Title: 2301 Blake Street, Suite 100 Denver, CO 80205 303.861.8555 0225 Main Street, Unit C101 Edwards, CO 81632 970.926.8960 Denver Vail Consultant Issue/RevisionsDateNo. Sheet Information Project Information Permit Set30 August 2013 MedicalCenter VailValley Vail, Colorado 81657 US Bank Building 108 South Frontage Road Suite 306 S: \ B G P r o j e c t s \ 8 7 3 9 . 3 9 V V M C C o n c i e r g e C l i n i c \ C a d \ B G C E C A D\ 8 7 3 9 3 9 M 3 1 . d w g P r i n t e d B y : c ad d - j a c A u g u s t 3 0 , 2 0 1 3 - 1 1 : 0 1 a m L C - J A C COPYRIGHT 2013 B ANZEG EAUDIN (970)949-6108 (303) 278-3820 (970) 221-5691 (505) 323-9070 Vail: Denver: Fort Collins: Albuquerque: www.bgce.com Multi-Specialty Clinic 13915.00.000 MARTIN MARTIN 0225 MAIN STREET; SUITE C101 EDWARDS, COLORADO 81632 970.581.2546 BEAUDIN GANZE CONSULTING ENGINEERS 222 CHAPEL PLACE, UNIT AC-201 P.O. BOX 9650 AVON, COLORADO 81620 970.949.6108 M3.1 MECHANICAL DIAGRAMS Reviewed for Code Compliance Code: 2012 International Building Code (IBC) CURRENT SENSORTHERMOSTAT (ON PLANS) CONTROLS DIAGRAM SYMBOLS CARBON DIOXIDE SENSOR CARBON MONOXIDE SENSOR STATIC PRESSURE SENSOR HUMIDISTAT IN FLOOR TEMPERATURE SENSOR EMERGENCY POWER OFF SWITCH TE DM 72 AOBOBIAI SMK FRZ TEAFMS DPT MOTOR STARTER RELATIVE HUMIDITY SENSOR RELAY VARIABLE SPEED/FREQUENCY DRIVE THERMOSTAT DIFFERENTIAL PRESSURE TRANSMITTER SMOKE DETECTOR MANUAL SWITCH DIGITAL THERMOSTAT 2-WAY CONTROL VALVE SP EPO CO2 FS CO CS MS RH VFD RLY TSTAT DDC POINTS (ANALOG, BINARY, IN, OUT) FLOW SWITCH SOLENOID VALVE 3-WAY CONTROL VALVE AVERAGING TEMPERATURE SENSOR FREEZESTAT AIRFLOW MEASURING STATION INSERTION TEMPERATURE SENSOR MOTORIZED DAMPER MODULE AS LABELED FAN OR PUMP TC TEMPERATURE SENSOR T A CP CONTROL PANEL / MODULE T S H CONTROL NOTES: DX C O O L I N G FIRE RE T U R N SU P P L Y DM SM K SYSTEM POINTS LIST -- PACKAGED VAV AIR HANDLING UNIT ANALOGBINARYSYSTEM FEATURE INPUTOUTPUTINPUTOUTPUTALARMSPROGRAMS SYSTEM POINT DESCRIPTION GR A P H I C S C R E E N AN I M A T E D P O I N T O N G R A P H I C TE M P E R A T U R E PR E S S U R E RE L A T I V E H U M I D I T Y KW KW H BT U H R GP M PE R C E N T CF M DD C ( 4 - 2 0 m a , 0 - 1 0 v d c ) ST A T U S ST A T U S O N / O F F FI L T E R S T A T U S ST A T U S O P E N / C L S D . TI M E D O V E R R I D E ST O P / S T A R T OP E N / C L O S E D LO C K O U T EN A B L E / D I S A B L E HI G H / L O W S P E E D FL O A T I N G C O N T R O L HIG H O R L O W V A L U E OU T O F R A N G E ST A T U S D I F F . F R O M C M D FR E E Z E S T A T T R I P SM O K E D E T E C T O R T R I P FI L T E R C H A N G E D U E TR E N D V A L U E TR E N D S T A T U S LE A D / L A G RO T A T I O N A L L Y S E Q U N C E OUTSIDE TEMP XX RETURN AIR TEMP XX SUPLY FAN S/S XX SUPPLY FAN STATUS XX X SMOKE DETECTORS XXX X X X GENERAL NOTES: PO S I T I O N EXHAUST FAN STATUS EXHAUST FAN S/S X X X GAS FIRED SECTION XXX X X SUPPLY AIR TEMP X XXXX FILTER DP AIAOAIBOAOBI TE TE BOBO OA D A M P E R PO W E R E X H A U S T F A N SM O K E D E T E C T O R DX C O O L I N G SU P P L Y F A N RE T U R N T E M P GA S - F I R E D H E A T I N G S E C T I O N SU P P L Y T E M P AI AI BI AI BO AOBIB0 HWR HWS SEQUENCE OF OPERATION - VAV BOX WITH HOT WATER REHEAT THE SYSTEM CONSIST OF A PRESSURE INDEPENDENT VARIABLE AIR VOLUME BOX COMPLETE WITH MOTORIZED DAMPER, HOT WATER REHEAT COIL, FLOATING OR MODULATING CONTROL VALVE, AND AIR FLOW PRESSURE TRANSDUCER. SCHEDULING: THE ROOM TEMPERATURE SETPOINT SHALL BE SCHEDULED THROUGH THE OPERATOR WORKSTATION SUCH THAT HEATING ROOM TEMPERATURE SETPOINT AND COOLING ROOM TEMPERATURE SETPOINT ARE SET UP AND SET BACK RESPECTIVELY DURING UNOCCUPIED MODES. A THERMOSTAT MOUNTED TIMED OVERRIDE BUTTON SHALL ALLOW ROOM OCCUPANTS TO OVERRIDE THE VAV BOX INTO AN OCCUPIED MODE FOR A SET TIME DURATION SHOULD OCCUPANTS DESIRE TO USE THE SPACE DURING UNOCCUPIED TIMES. THE RESPECTIVE AIR HANDLING UNIT SHALL BE OPERATIONAL WHENEVER VAV BOX IS IN OCCUPIED MODE. CONTROL: THE AIRFLOW PRESSURE TRANSDUCER SHALL INDICATE TO THE UNIT MOUNTED DDC CONTROLLER MEASURED AIRFLOW. THE DDC CONTROLLER SHALL MODULATE THE VAV BOX DAMPER TO MAINTAIN AIRFLOW AT SETPOINT. AIRFLOW SETPOINT SHALL BE RESET BASED ON THE DIFFERENCE BETWEEN SPACE TEMPERATURE AND SPACE SETPOINT. UPON A RISE IN SPACE TEMPERATURE ABOVE COOLING SETPOINT AIRFLOW SHALL MODULATE TO THE MAXIMUM SETPIONT. UPON A DROP IN SPACE TEMPERATURE BELOW COOLING SETPOINT AIRFLOW SHALL MODULATE TO THE MINIMUM SETPOINT. UPON DROP IN SPACE TEMPERATURE BELOW SPACE HEATING SETPOINT, HOT WATER CONTROL VALVE SHALL MODULATE OPEN. A SPACE MOUNTED TEMPERATURE SENSOR SHALL INCORPORATE A WARMER/COOLER ADJUSTMENT ALLOWING ZONE OCCUPANTS TO BIAS THE SPACE TEMPERATURE SETPOINT BY A FIXED AMOUNT IN EITHER DIRECTION. FEATURES: SPACE TEMPERATURE 5 DEGREES OR MORE ABOVE OR BELOW SETPOINT SHALL INITIATE AN ALARM SA DM SCALE: 1 VAV BOX WITH HW REHEAT NONE SPACE MOUNTED T-STAT SYSTEM POINTS LIST -- VAV BOX WITH HW REHEAT ANALOG BINARY SYSTEM FEATURE INPUTOUTPUTINPUTOUTPUTALARMSPROGRAMS SYSTEM POINT DESCRIPTION GR A P H I C S C R E E N AN I M A T E D P O I N T O N G R A P H I C TE M P E R A T U R E PR E S S U R E RE L A T I V E H U M I D I T Y KW KW H BT U H R GP M PE R C E N T CF M DD C ( 4 - 2 0 m a , 0 - 1 0 v d c ) ST A T U S ST A T U S O N / O F F FI L T E R S T A T U S ST A T U S O P E N / C L S D . TI M E D O V E R R I D E ST O P / S T A R T OP E N / C L O S E D LO C K O U T EN A B L E / D I S A B L E HIG H / L O W S P E E D FL O A T I N G C O N T R O L HIG H O R L O W V A L U E OU T O F R A N G E ST A T U S D I F F . F R O M C M D TR E N D V A L U E TR E N D S T A T U S LE A D / L A G RO T A T I O N A L L Y S E Q U N C E NOTES SPACE TEMP xxx WAMER/COOLER x TIMED OVERRIDE x AIRFLOW x DISCHG AIR TEMP x DAMPER OPEN x DAMPER CLOSE x VAV VALVE OPEN x VAV VALVE CLOSE x GENERAL NOTES: FROM AHU SCALE:2 PACKAGED GAS/DX VAV RTU NONE DESCRIPTION: THE SYSTEM SHALL CONSIST OF A PACKAGED DX, GAS-FIRED ROOFTOP UNIT WITH VFD-OPERATED SUPPLY FAN, COMPRESSORS, HOT GAS BYPASS, STAGED GAS HEAT, AND A POWER EXHAUST FAN FOR BUILDING PRESSURIZATION. THE UNIT SHALL BE PROVIDED WITH A FACTORY-INTEGRATED DIGITAL CONTROLLER WHICH IS CAPABLE OF STAND-ALONE OPERATION AS WELL AS CONNECTION TO A BUILDING-WIDE NETWORK. SCHEDULING: 1.THE AIR HANDLING UNIT SHALL BE SCHEDULED THROUGH THE OPERATOR WORKSTATION INTERFACE. 2.WHEN IN UNOCCUPIED MODE, FANS SHALL SHUT OFF AND CONTROLLED DEVICES SHALL RETURN TO THEIR NORMAL POSITIONS. CONTROL DAMPERS ARE NORMALLY CLOSED TO THE OUTDOOR AIR, STEAM/HEATING WATER VALVES ARE NORMALLY OPEN, COMPRESSORS AND CONDENSER FANS ARE OFF, AND CHILLED WATER VALVES ARE NORMALLY CLOSED. 3.DURING UNOCCUPIED MODE SHOULD ANY SPACE TEMPERATURE FALL BELOW 60 DEG F (ADJUSTABLE) OR RISE ABOVE 90 DEG F (ADJUSTABLE), THE DDC SYSTEM SHALL RETURN THE AIR HANDLING UNIT TO AN OCCUPIED MODE FOR A MINIMUM 1 HOUR DURATION. EITHER MOMENTARY CONTACT SWITCHES LOCATED THROUGHOUT THE OCCUPIED SPACES, OR THERMOSTAT OVERRIDE SWITCHES SHALL ALLOW AFTER HOURS BUILDING OCCUPANTS TO OVERRIDE THE SYSTEM INTO A TIME-ADJUSTABLE OCCUPIED MODE. MIXED AIR CONTROL: 1.WHEN NOT IN ECONOMIZER MODE, OUTSIDE AIR SHALL MODULATE TO MAINTAIN OUTSIDE AIR FLOW AT SETPOINT. 2.WHEN OUTSIDE AIR TEMPERATURE FALLS BELOW ECONOMIZER ENABLING SETPOINT, ENABLE ECONOMIZER OPERATION. WHEN IN ECONOMIZER MODE, MIXING DAMPERS SHALL MODULATE TO MAINTAIN MIXED AIR TEMPERATURE AT SETPOINT. DISCHARGE AIR CONTROL: 1.DISCHARGE AIR TEMPERATURE IS TO BE MAINTAINED AT COOLING SETPOINT OF 55 DEG F AND HEATING SETPOINT OF 60 DEG F. FAN CONTROL: 1.THE SUPPLY FAN VFD SHALL BE MODULATED TO MAINTAIN SPACE PRESSURE AT SETPOINT. SAFETIES AND ALARMS: 1.UNIT SHALL BE COMPLETELY SHUT DOWN UPON DETECTION OF SMOKE AS SENSED BY THE DUCT-MOUNTED SMOKE DETECTOR IN THE RETURN AIR DUCT. 2.GENERATE AN ALARM SHOULD DISCHARGE AIR TEMPERATURE VARY FROM DISCHARGE AIR TEMPERATURE SETPOINT BY 5 DEG OR MORE. 3.GENERATE AN ALARM SHOULD FAN STATUS NOT MATCH FAN COMMAND. BO SCALE: A.EXHAUST FAN SHALL RUN CONTINUOUSLY DURING OCCUPIED HOURS. B.ASSOCIATED MOTORIZED OSA DAMPERS SHALL BE OPEN WHEN FAN OPERATES. OTHERWISE, DAMPERS SHALL BE CLOSED. DM BO 3 STORAGE EXHAUST NONE DP AI DU C T S T A T I C P R ES S U R E DM DM DO SU P P L Y A I R D A M P E R BO RE T U R N A I R D A M P E R 72 VAV CROSS FLOW AIR SENSOR DPA Project: Sheet Number: COPYRIGHT 2013 - DAVIS PARTNERSHIP, P.C. Sheet Title: 2301 Blake Street, Suite 100 Denver, CO 80205 303.861.8555 0225 Main Street, Unit C101 Edwards, CO 81632 970.926.8960 Denver Vail Consultant Issue/RevisionsDateNo. Sheet Information Project Information Permit Set30 August 2013 MedicalCenter VailValley Vail, Colorado 81657 US Bank Building 108 South Frontage Road Suite 306 S: \ B G P r o j e c t s \ 8 7 3 9 . 3 9 V V M C C o n c i e r g e C l i n i c \ C a d \ B G C E C A D\ 8 7 3 9 3 9 M 3 2 . d w g P r i n t e d B y : c ad d - j a c A u g u s t 3 0 , 2 0 1 3 - 1 1 : 0 1 a m L C - J A C COPYRIGHT 2013 B ANZEG EAUDIN (970)949-6108 (303) 278-3820 (970) 221-5691 (505) 323-9070 Vail: Denver: Fort Collins: Albuquerque: www.bgce.com Multi-Specialty Clinic 13915.00.000 MARTIN MARTIN 0225 MAIN STREET; SUITE C101 EDWARDS, COLORADO 81632 970.581.2546 BEAUDIN GANZE CONSULTING ENGINEERS 222 CHAPEL PLACE, UNIT AC-201 P.O. BOX 9650 AVON, COLORADO 81620 970.949.6108 M3.2 MECHANICAL CONTROLS DIAGRAMS Reviewed for Code Compliance Code: 2012 International Building Code (IBC) COPIER SCALE:1 THIRD LEVEL UNDERFLOOR WASTE & VENT PLUMBING PLAN 1/8" = 1'-0" SCALE:3 WASTE & VENT ISOMETRIC NONE 1.COORDINATE DEMOLITION AND NEW WORK BELOW THE 3rd FLOOR WITH BUILDING OWNER AND SECOND FLOOR TENANT TO OCCUR AFTER NORMAL BUSINESS HOURS. 2.FIELD COORDINATE LOCATIONS OF (E) WASTE ON FLOOR BELOW. NOTES: C.O. C.O. CONNECT (N) 4"W TO (E) 4"W. 4"W UP 112"W UP 4" 2" 4" 2" 4" 2" 2" 2" 4" 2" 4" 112"W UP 112"W UP 112"W UP W W W 112"W UP W 112"W UP 2" 2" 2" 2" 112"W UP 4"W UP REMOVE (E) WATER CLOSET. PREPARE (E)W FOR (N) CONNECTION. REMOVE (E) LAV. PREPARE (E)W FOR (N) CONNECTION. EXTEND (N) 4"W TO (N) WATER CLOSET. EXTEND (N) 112"W TO (N) LAV. 1 FLAG NOTES: 2 3 4 112"W UP 3 4 LAV LAV LAV LAV WC KS KS LAV LAV LAV LAV LAV LAV WC 2" 2" 2" 2" 2 " 4 " 4" 2" 2" 2 " 2 " 4 " 2" 4" 4 " 3" 1 -1 /2 "1-1/2" 4" 3 " 3 " 2 " W W W W W W W W W W 4"VTR V V V V V V V V V V V V V V SCALE:2 PARTIAL THIRD FLOOR PLUMBING DEMOLITION PLAN 1/8" = 1'-0" W REMOVE (E) WASTE & VENT PIPING TO (E) FIXTURES IN THIS AREA. 1 2 DPA Project: Sheet Number: COPYRIGHT 2013 - DAVIS PARTNERSHIP, P.C. Sheet Title: 2301 Blake Street, Suite 100 Denver, CO 80205 303.861.8555 0225 Main Street, Unit C101 Edwards, CO 81632 970.926.8960 Denver Vail Consultant Issue/RevisionsDateNo. Sheet Information Project Information Permit Set30 August 2013 MedicalCenter VailValley Vail, Colorado 81657 US Bank Building 108 South Frontage Road Suite 306 S: \ B G P r o j e c t s \ 8 7 3 9 . 3 9 V V M C C o n c i e r g e C l i n i c \ C a d \ B G C E C A D\ 8 7 3 9 3 9 P 2 0 . d w g P r i n t e d B y : c ad d - j a c A u g u s t 3 0 , 2 0 1 3 - 1 1 : 0 1 a m L C - J A C COPYRIGHT 2013 B ANZEG EAUDIN (970)949-6108 (303) 278-3820 (970) 221-5691 (505) 323-9070 Vail: Denver: Fort Collins: Albuquerque: www.bgce.com Multi-Specialty Clinic 13915.00.000 MARTIN MARTIN 0225 MAIN STREET; SUITE C101 EDWARDS, COLORADO 81632 970.581.2546 BEAUDIN GANZE CONSULTING ENGINEERS 222 CHAPEL PLACE, UNIT AC-201 P.O. BOX 9650 AVON, COLORADO 81620 970.949.6108 P2.0 THIRD LEVEL WASTE & VENT PLUMBING PLAN Reviewed for Code Compliance Code: 2012 International Building Code (IBC) COPIER SCALE:1 THIRD LEVEL DOMESTIC WATER PLUMBING PLAN 1/8" = 1'-0" 2" G UP AND DN TO GARAGE LEVEL. CONTRACTOR TO FIELD-COORDINATE ROUTING OF PIPE UP THROUGH BUILDING. M ROUTING OF (N) GAS PIPING IN CEILING OF GARAGE. CONTRACTOR TO FIELD-COORDINATE EXACT ROUTING. G G 2" APPROXIMATE LOCATION OF (E) GAS METER. COORDINATE WITH GAS UTILITY FOR THE ADDITION OF 150 MBH (APPROXIMATELY170 CFH) OF GAS LOAD TO METER. 1.COORDINATE DEMOLITION AND NEW WORK BELOW THE 3rd FLOOR WITH BUILDING OWNER AND SECOND FLOOR TENANT TO OCCUR AFTER NORMAL BUSINESS HOURS. 2.FIELD COORDINATE LOCATIONS OF (E) WASTE, DHW AND DCW PIPING IN FLOOR BELOW. NOTES: 1"CW AND 2" V DN. TO WC.1" 3 4"1" 12"HW AND 1"CW DN. TO SINK AND WC. 114"114"34" 12"HW/CW AND 1 1/2" V DN. 12"HW/CW AND 1 1/2" V DN. 12"HW/CW AND 1 1/2" V DN.12"HW/CW AND 1 1/2" V DN. 12" 3" 1-1/2"1-1/2"3"3" 4"VTR VV VV 12"HW/CW AND 1 1/2" V DN. V V V 12"HW/CW AND 1 1/2" V DN. 12"HW/CW AND 1 1/2" V DN. 12"HW/CW AND 1 1/2" V DN. 12" 1 14" 1" 12" 1 12" 1 14" BALANCE TO 0.5 GPM. BALANCE TO 0.5 GPM. BALANCE TO 0.5 GPM. BALANCE TO 0.5 GPM. P1 P1 P1 P1 P1 P1 P2 P2 P4 P6 P6 V 2" 1" 112" 12"CW/HW & 112"V DN. P3 P5 REMOVE (E)CW TO WATER CLOSET. PREPARE FOR (N) CONNECTION. REMOVE (E)CW/HW FROM LAV. PREPARE FOR (N) CONNECTION. EXTEND (E)CW TO (N) WATER CLOSET. EXTEND (E)CW/HW TO (N) LAV. 1 FLAG NOTES: 2 3 4 4 3 112"DCW CONNECTED TO MAIN. SCALE:2 PARTIAL THIRD FLOOR PLUMBING DEMOLITION PLAN 1/8" = 1'-0" DISCONNECT (E) CW/HW IN CEILING BELOW. CAP HW & PREP CW FOR FUTURE EXTENSION. 1 2 DPA Project: Sheet Number: COPYRIGHT 2013 - DAVIS PARTNERSHIP, P.C. Sheet Title: 2301 Blake Street, Suite 100 Denver, CO 80205 303.861.8555 0225 Main Street, Unit C101 Edwards, CO 81632 970.926.8960 Denver Vail Consultant Issue/RevisionsDateNo. Sheet Information Project Information Permit Set30 August 2013 MedicalCenter VailValley Vail, Colorado 81657 US Bank Building 108 South Frontage Road Suite 306 S: \ B G P r o j e c t s \ 8 7 3 9 . 3 9 V V M C C o n c i e r g e C l i n i c \ C a d \ B G C E C A D\ 8 7 3 9 3 9 P 2 1 . d w g P r i n t e d B y : c ad d - j a c A u g u s t 3 0 , 2 0 1 3 - 1 1 : 0 1 a m L C - J A C COPYRIGHT 2013 B ANZEG EAUDIN (970)949-6108 (303) 278-3820 (970) 221-5691 (505) 323-9070 Vail: Denver: Fort Collins: Albuquerque: www.bgce.com Multi-Specialty Clinic 13915.00.000 MARTIN MARTIN 0225 MAIN STREET; SUITE C101 EDWARDS, COLORADO 81632 970.581.2546 BEAUDIN GANZE CONSULTING ENGINEERS 222 CHAPEL PLACE, UNIT AC-201 P.O. BOX 9650 AVON, COLORADO 81620 970.949.6108 P2.1 THIRD LEVEL DOMESTIC WATER PLUMBING PLAN Reviewed for Code Compliance Code: 2012 International Building Code (IBC) SCALE: PLUMBING ROOF PLAN 1/8" = 1'-0" G3/4" 2" G DN. 3" VTR. EXISTING BATHROOM GROUP PLUMBING VENT. 1.REFER TO DIAGRAM , SHEET M3.1 FOR RTU GAS PIPING SUPPORT ON ROOF INSTALLATION. 2.REFER TO DIAGRAM , SHEET M3.1 FOR PIPE THROUGH ROOF INSTALLATION. 3.REFER TO DIAGRAM , SHEET M3.1 FOR NATURAL GAS CONNECTION TO RTU. NOTES: K A M (E) CONDENSING UNIT. (E) CONDENSING UNIT. (E) RTU. (E) RTU (E) EXHAUST FAN EF-1 10x10 EXH DN. 4"VTR DPA Project: Sheet Number: COPYRIGHT 2013 - DAVIS PARTNERSHIP, P.C. Sheet Title: 2301 Blake Street, Suite 100 Denver, CO 80205 303.861.8555 0225 Main Street, Unit C101 Edwards, CO 81632 970.926.8960 Denver Vail Consultant Issue/RevisionsDateNo. Sheet Information Project Information Permit Set30 August 2013 MedicalCenter VailValley Vail, Colorado 81657 US Bank Building 108 South Frontage Road Suite 306 S: \ B G P r o j e c t s \ 8 7 3 9 . 3 9 V V M C C o n c i e r g e C l i n i c \ C a d \ B G C E C A D\ 8 7 3 9 3 9 P 2 2 . d w g P r i n t e d B y : c ad d - j a c A u g u s t 3 0 , 2 0 1 3 - 1 1 : 0 1 a m L C - J A C COPYRIGHT 2013 B ANZEG EAUDIN (970)949-6108 (303) 278-3820 (970) 221-5691 (505) 323-9070 Vail: Denver: Fort Collins: Albuquerque: www.bgce.com Multi-Specialty Clinic 13915.00.000 MARTIN MARTIN 0225 MAIN STREET; SUITE C101 EDWARDS, COLORADO 81632 970.581.2546 BEAUDIN GANZE CONSULTING ENGINEERS 222 CHAPEL PLACE, UNIT AC-201 P.O. BOX 9650 AVON, COLORADO 81620 970.949.6108 P2.2 PLUMBING ROOF PLAN Reviewed for Code Compliance Code: 2012 International Building Code (IBC) ABBREVIATIONS AFC - ABOVE FINISHED CEILING AFF - ABOVE FINISHED FLOOR AFG - ABOVE FINISHED GRADE AL - ALUMINUM BFG - BELOW FINISH GRADE C - CONDUIT CKT - CIRCUIT CT - CURRENT TRANSFORMER EM - EMERGENCY EWC - ELECTRIC WATER COOLER (E) - EXISTING FBO - FURNISHED BY OTHERS GFI - GROUND FAULT CIRCUIT INTERRUPTER IC - INTERMEDIATE CROSS-CONNECT IAW - IN ACCORDANCE WITH NIC - NOT IN CONTRACT DW - DISHWASHER DISP - GARBAGE DISPOSAL NL - NIGHT LIGHT NTS - NOT TO SCALE REF - REFRIGERATOR TVSS - TRANSIENT VOLTAGE SURGE SUPPRESSOR UG - UNDERGROUND UNO - UNLESS NOTED OTHERWISE WP - WEATHER PROOF XP - EXPLOSION PROOF +18" - MOUNTING HEIGHT TO CENTERLINE OF DEVICE ABOVE FINISH FLOOR POWER SYMBOLS SINGLE RECEPTACLE DUPLEX RECEPTACLE DOUBLE DUPLEX RECEPTACLE GFCI DUPLEX RECEPTACLE DUPLEX RECEPTACLE; HALF SWITCHED ISOLATED GROUND DUPLEX RECEPTACLE WALL MOUNTED SPECIAL OUTLET AS NOTED SPECIAL OUTLET AS NOTED JUNCTION BOX WALL MOUNTED JUNCTION BOX FLOOR MOUNTED JUNCTION BOX DUPLEX RECEPTACLE MOUNTED ABOVE COUNTERC FLUSH FLOOR MOUNTED DUPLEX RECEPTACLE FLUSH FLOOR MOUNTED DOUBLE DUPLEX RECEPTACLE FLUSH FLOOR MOUNTED DUPLEX RECEPTACLE; HALF SWITCHED FLUSH FLOOR MOUNTED DUPLEX RECEPTACLE AND TELECOM DIVISION 15 EQUIPMENT POWER CONNECTION FUSED DISCONNECT NON FUSED DISCONNECT MOTOR STARTER ENCLOSED CIRCUIT BREAKER PULL BOX PUSH BUTTON TRANSFORMER PANELBOARD OR LOADCENTER CONTACTOR ELECTRIC MOTOR METER THERMOSTAT ATS AUTOMATIC TRANSFER SWITCH ONE-LINE DIAGRAM SYMBOLS CIRCUIT HOMERUN CONDUIT RUN CONDUIT RUN BELOW GRADE CONDUIT UP CONDUIT DOWN DISCONNECT SWITCH FUSE CIRCUIT BREAKER CURRENT TRANSFORMER POTENTIAL TRANSFORMER METER SURGE SUPPRESSION DEVICE VOLT-METER SELECTOR SWITCH GROUND GF GROUND FAULT PROTECTION AMP-METER ST SHUNT TRIP NORMALLY OPEN CONTACT NORMALLY CLOSED CONTACT COLD WATER GROUND CONNECTION BUILDING STEEL GROUND CONNECTION TIMER SWITCH MULTI-OUTLET PLUG STRIP TIME CLOCK PHOTO-CELL SWITCH THERMAL OVERLOAD SWITCH VARIABLE SPEED SWITCH KEY SWITCH LIGHTING FIXTURE SYMBOLS RECESSED LIGHTING FIXTURE WALL MOUNTED LIGHT WALL MOUNTED UP-LIGHT PENDANT MOUNTED LIGHT SURFACE MOUNTED LIGHT DIRECTIONAL/ADJUSTABLE RECESSED LIGHTING FIXTURE MONO-POINT LIGHTING FIXTURE RECESSED STEP LIGHT FLUORESCENT STRIP LIGHT WALL MOUNTED LINEAR FLUORESCENT LIGHT RECESSED OR SURFACE MOUNTED FLUORESCENT TROFFER FIXTURE WITH EMERGENCY BACKUP OR ON EM CIRCUIT WALL MOUNTED EXIT SIGN W/ FACES & ARROWS AS SHOWN EMERGENCY LIGHTS CEILING MOUNTED EXIT SIGN W/ FACES & ARROWS AS SHOWN SWITCH THREE-WAY SWITCH FOUR-WAY SWITCH DOOR JAMB SWITCH LIGHTING CONTROL SYMBOLS FIRE ALARM SYMBOLS FIRE ALARM CONTROL PANEL REMOTE ANNUNCIATOR PANEL SMOKE DETECTOR HEAT DETECTOR COMBO SMOKE/HEAT DETECTOR FIRE ALARM HORN FIRE ALARM STROBE FIRE ALARM COMBO HORN/STROBE FIRE ALARM PULL STATION F FIRE ALARM SPEAKER F FIRE ALARM COMBO SPEAKER/STROBE FIREMAN'S PHONE JACK DUCT SMOKE DETECTOR SPRINKLER SYSTEM FLOW SWITCH SPRINKLER SYSTEM TAMPER SWITCH FIRE/SMOKE DAMPER AWG - AMERICAN WIRE GAUGE AP - ACCESS POINT AHJ - AUTHORITY HAVING JURISDICTION BMS - BUILDING MANAGEMENT SYSTEM CATV - COMMUNITY (CABLE) ANTENNA TELEVISION SYSTEM CCTV - CLOSED CIRCUIT TELEVISION CPU - CENTRAL PROCESSING UNIT FA - FIRE ALARM FACP- FIRE ALARM CONTROL PANEL GRD - GROUND GC - GENERAL CONTRACTOR IDF - INTERMEDIATE DISTRIBUTION FRAME IG - ISOLATED GROUND IR - INFRARED OC - ON CENTER MDF - MAIN DISTRIBUTION FRAME LAN - LOCAL AREA NETWORK PA - PUBLIC ADDRESS WAN - WIDE AREA NETWORK WLAN- WIRELESS LOCAL AREA NETWORK W - WATT V - VOLT TTB - TELEVISION TERMINAL BOARD EXTERIOR POLE MOUNTED LIGHT EXTERIOR POST (BOLLARD) MOUNTED LIGHT DAYLIGHT PHOTO SENSORDL KEY SWITCH LV VARIABLE SPEED SWITCH DIMMER THREE-WAY DIMMER LOW VOLTAGE SWITCH WALL OCCUPANCY SENSOR/SWITCH THERMAL OVERLOAD SWITCH SMALL ROOM OCCUPANCY SENSOR LARGE ROOM OCCUPANCY SENSOR CORRIDOR OCCUPANCY SENSOR OC OC ST SO D 3 D SV SK OC SJ S4 S3 S FSD FT FF DD F F H H SH HD SD ANN FACP A V SS M SK SV ST S PC TC T C T PB CB N TS - - J J J '*' ISSUED FOR INFORMATION ONLY ' ' NOT PART OF SET ' ' ISSUED AS PART OF A SET ISSUE LOG KEY: # DA T E ISSUE LOG ELECTRICAL SHEET INDEX TITLE ELECTRICAL COVER SHEETE1.0 PERMIT SET 05 / 1 0 / 2 0 1 3 GENERAL NOTES: 1.THESE DRAWING NOTES ACCOMPANY THE CONSTRUCTION DOCUMENT SPECIFICATIONS. 2.DO NOT SCALE DRAWINGS. VERIFY DIMENSIONS ON ARCHITECTURAL DRAWINGS AND IN FIELD PRIOR TO COMMENCEMENT OF WORK. 3.VISIT SITE PRIOR TO BID AND VERIFY THAT CONDITIONS ARE AS INDICATED. CONTRACTOR SHALL INCLUDE IN HIS BID COSTS REQUIRED TO MAKE HIS WORK MEET EXISTING CONDITIONS. 4.REVIEW STRUCTURAL, MECHANICAL, AND OTHER DRAWINGS PRIOR TO BID. 5.WORK SHALL BE PERFORMED IN A WORKMANLIKE MANNER TO THE SATISFACTION OF THE ARCHITECT. 6.WORK, MATERIALS, AND EQUIPMENT SHALL CONFORM TO THE LATEST EDITIONS OF LOCAL, STATE OF COLORADO, NATIONAL AND LIFE SAFETY CODE. 7.SYSTEMS SHALL BE COMPLETE, OPERABLE, AND READY FOR CONTINUOUS OPERATION. LIGHTS, SWITCHES, RECEPTACLES, MOTORS, ETC. SHALL BE CONNECTED AND OPERABLE. 8.PANEL DIRECTORIES SHALL BE REMOVABLE. SUBMIT PROPOSED SCHEDULE OF DIRECTORIES TO OWNER FOR APPROVAL. ROOM NAMES AND NUMBERS SHALL BE AS DIRECTED BY OWNER. DIRECTORIES SHALL BE TYPED AND INSTALLED UNDER CLEAR PLASTIC COVERS. 9.PROVIDE DYMO-TAPE TAG INSIDE COVER OF EACH FUSIBLE SWITCH, INDICATING SIZE AND TYPE OF FUSES PROVIDED. 10.CONTRACTOR'S FAILURE TO ORDER OR RELEASE ORDER FOR MATERIALS AND/OR EQUIPMENT WILL NOT BE ACCEPTED AS A REASON TO SUBSTITUTE ALTERNATE MATERIALS, EQUIPMENT, OR INSTALLATION METHODS. 11.LABEL COVER OF EACH DEVICE WITH SOURCE PANEL AND BRANCH CIRCUIT NUMBER WITH DYMO MARKER. 12.FINAL CONNECTIONS TO EQUIPMENT SHALL BE IN ACCORDANCE WITH MANUFACTURER'S APPROVED WIRING DIAGRAMS, DETAILS, AND INSTRUCTIONS. 13.ALL EMPTY RACEWAY SYSTEMS SHALL HAVE A NYLON PULLSTRING OR EQUAL, AND SHALL BE IDENTIFIED AT ALL JUNCTION, PULL AND TERMINATION POINTS, USING PERMANENT METALLIC TAGS. TAG SHALL INDICATE INTENDED USE OF CONDUIT, ORIGINATION, AND TERMINATION POINTS OF EACH INDIVIDUAL CONDUIT. 14.INSTALL ALL MATERIALS IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. ANY DEVIATIONS SHALL BE BROUGHT TO THE ARCHITECT/ENGINEER'S ATTENTION PRIOR TO INSTALLATION. 15.CONTRACTOR SHALL BE RESPONSIBLE FOR REPLACING EQUIPMENT WHICH IS DAMAGED DUE TO INCORRECT FIELD WIRING PROVIDED UNDER THIS SECTION, OR FACTORY WIRING IN EQUIPMENT PROVIDED UNDER THIS SECTION. 16.WIRE TERMINATION PROVISIONS FOR PANELBOARDS, CIRCUIT BREAKERS, SAFETY SWITCHES, AND ALL OTHER ELECTRICAL APPARATUS SHALL BE LISTED AS SUITABLE FOR 75 DEGREE CELSIUS. 17.RECEPTACLES WHICH ARE SHOWN WALL MOUNTED ON THE ELECTRICAL DRAWINGS ON WALLS WHICH, ON THE ARCHITECTURAL DRAWINGS AND ELEVATIONS, ARE SHOWN AS GLASS OR PARTITIONS SHALL BE FLUSH FLOOR DUPLEX RECEPTACLES MOUNTED ADJACENT TO BASE OF WALLS. 18.WIRING DEVICES SHALL BE SPECIFICATION GRADE AND RATED AT 20 AMPERES FOR LIGHT SWITCHES, AND 20 AMPERES FOR DUPLEX RECEPTACLES. IVORY IN COLOR. 19.PULLBOXES, CABINETS, ETC. MOUNTED ON THE EXTERIOR AT GRADE LEVEL, SHALL BE WEATHERPROOF TYPE WITH HINGED LOCKABLE COVERS. 20.MINIMUM WIRE SIZE USED ON THIS PROJECT SHALL BE #12 COPPER. ALL DEVICES INDICATED TO BE INSTALLED AT DIFFERENT MOUNTING HEIGHTS & LOCATED WITHIN ONE STUD SPACE FROM EACH OTHER SHALL ALIGN VERTICALLY, WALL MOUNTED TELEPHONES OCCUR OVER LIGHT SWITCHES. VOLUME CONTROLS, ETC. ON THE SAME SIDE OF THE STUD WHERE NO SCALE TYPICAL DEVICE MOUNTING HEIGHTS PANELS CONTROL TS K HEIGHTS SHOWN ARE TYPICAL TO CENTERLINE OF BOX UNLESS WHERE EVER DEVICES ARE INDICATED TO BE ABOVE DOORS, DEVICE SHALL BE CENTERED BETWEEN TOP OF DOOR TRIM & CEILING-LINE. MOUNTING HEIGHTS SHOWN ON ARCHITECTURAL ELEVATIONS SHALL NOTED OTHERWISE. GOVERN OVER THOSE SHOWN ABOVE. NOTES: 1. 2. 3. 84 " ( 7 ' - 0 " ) U N O FAP ANN DF 18 " ( 1 ' - 6 " ) U N O 48 " ( 4 ' - 0 " ) U N O 64 " ( 5 ' - 4 " ) U N O 72 " ( 6 ' - 0 " ) U N O 78 " ( 6 ' - 6 " ) U N O TOP OF CABINET TOP OF CABINET TOP OF CABINET S TV FINISHED FLOOR NOTE: OFFSET ONE STUD SPACE. H DOOR HOLD OPEN DEVICEDH ELECTRICAL DEMOLITION PLAN - 3rd FLOORED2.1 ELECTRICAL PLAN - GARAGE LEVEL PLANE2.0 ELECTRICAL LIGHTING PLAN - 3rd FLOORE2.1 ELECTRICAL ONE-LINE DIAGRAME3.1PARTIAL FIRE ALARM DIAGRAM NO SCALE FIRE ALARM EXISTING NOTIFIER #NSF-3030D ANNUNCIATORS TO REFLECT NEW / MODIFIED UPDATE EXISTING FIRE ALARM PANEL AND REMOTE FIRE ALARM WORK. 3. PROVIDE POWER BOOSTER AS REQUIRED TO DRIVE TO ACCOMMODATE NEW FIRE ALARM DETECTION PROVIDE REQUIRED PROGRAMMING OF SYSTEM NEW VISUAL DEVICES. DEVICES. 2. 1. NOTES: PANEL PB CAMPUS APPROVED FIRE ALARM CONTRACTOR. ALL FIRE ALARM WORK SHALL BE PERFORMED BY 4. FLAG NOTES: NEW FIRE ALARM NOTIFICATION APPLIANCE.1 1 NEW FIRE ALARM POWER BOOSTER (AS REQUIRED) IN TELEPHONE CLOSET AS REQUIRED. 2 2 1 H H ELECTRICAL SPECIFICATIONSE1.1 ELECTRICAL SCHEDULESE3.2 ELECTRICAL POWER PLAN - 3rd FLOORE2.2 ELECTRICAL PLAN - ROOFE2.3 DDDD ELECTRICAL SPECIFICATIONSE1.2 O W NER REVIE W (REV LAYOUT) 08 / 2 3 / 2 0 1 3 PERMIT (REV LAYOUT) 08 / 3 0 / 2 0 1 3 DPA Project: Sheet Number: COPYRIGHT 2013 - DAVIS PARTNERSHIP, P.C. Sheet Title: 2301 Blake Street, Suite 100 Denver, CO 80205 303.861.8555 0225 Main Street, Unit C101 Edwards, CO 81632 970.926.8960 Denver Vail Consultant Issue/RevisionsDateNo. Sheet Information Project Information Permit Set30 August 2013 MedicalCenter VailValley Vail, Colorado 81657 US Bank Building 108 South Frontage Road Suite 306 S: \ B G P r o j e c t s \ 8 7 3 9 . 3 9 V V M C C o n c i e r g e C l i n i c \ C a d \ B G C E C A D\ 8 7 3 9 3 9 E 1 0 . d w g P r i n t e d B y : c ad d - j a c A u g u s t 3 0 , 2 0 1 3 - 9 : 5 5 a m L C - J A C COPYRIGHT 2013 B ANZEG EAUDIN (970)949-6108 (303) 278-3820 (970) 221-5691 (505) 323-9070 Vail: Denver: Fort Collins: Albuquerque: www.bgce.com Multi-Specialty Clinic 13915.00.000 MARTIN MARTIN 0225 MAIN STREET; SUITE C101 EDWARDS, COLORADO 81632 970.581.2546 BEAUDIN GANZE CONSULTING ENGINEERS 222 CHAPEL PLACE, UNIT AC-201 P.O. BOX 9650 AVON, COLORADO 81620 970.949.6108 E1.0 ELECTRICAL COVER SHEET Reviewed for Code Compliance Code: 2012 International Building Code (IBC) DIVISION 16 - ELECTRICAL SPECIFICATIONS SECTION 16010--GENERAL PROVISIONS: PART 1 - GENERAL 1.01PROJECT DESCRIPTION A.THIS PROJECT IS A REMODEL OF AN EXISTING MEDICAL OFFICE BUILDING. THE PROJECT IS APPROXIMATELY 2,000 SQUARE FEET LOCATED IN VAIL, COLORADO. 1.02PROVISIONS A.WORK PERFORMED UNDER THIS DIVISION OF THE SPECIFICATIONS SHALL CONFORM TO THE REQUIREMENTS OF DIVISION 1, AND THE ELECTRICAL DRAWINGS AND ALL ITEMS HEREINAFTER SPECIFIED. 1.THE DRAWINGS AND SPECIFICATIONS FOR THE ELECTRICAL WORK ARE INTENDED TO DESCRIBE A COMPLETE ELECTRICAL SYSTEM; OMISSION OF MINOR ITEMS OBVIOUSLY NECESSARY TO ACCOMPLISH THE ABOVE INTENT SHALL NOT RELIEVE THE CONTRACTOR FROM PROVIDING SAME. 2.PRIOR TO ANY WORK BEING PERFORMED UNDER THIS DIVISION EXAMINE ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND INTERIOR DESIGN DRAWINGS AND SPECIFICATIONS AND IF ANY DISCREPANCIES OCCUR BETWEEN THEM AND THE ELECTRICAL DRAWINGS AND SPECIFICATIONS, REPORT SAME TO THE ARCHITECT IN WRITING AND OBTAIN WRITTEN INSTRUCTIONS FOR THE WORK. 3.ELECTRICAL DRAWINGS ARE DIAGRAMMATIC BUT SHALL BE FOLLOWED AS CLOSELY AS ACTUAL CONSTRUCTION OF THE BUILDING WILL PERMIT. ALL CHANGES FROM DRAWINGS NECESSARY TO MAKE THE ELECTRICAL WORK CONFORM TO THE BUILDING AS CONSTRUCTED SHALL BE MADE WITHOUT COST TO THE OWNER. 4.COORDINATE THE ELECTRICAL WORK WITH THE GENERAL CONTRACTOR AND BE RESPONSIBLE TO HIM FOR SATISFACTORY PROGRESS OF SAME. COORDINATE ELECTRICAL WORK WITH ALL OTHER TRADES ON THE PROJECT WITHOUT COST TO THE OWNER. 5.DO NOT SCALE DRAWINGS. VERIFY DIMENSIONS ON ARCHITECTURAL DRAWINGS AND IN FIELD PRIOR TO COMMENCEMENT OF WORK. 6.ALL WORK AND MATERIALS COVERED BY DRAWINGS AND SPECIFICATIONS SHALL BE SUBJECT TO REVIEW AT ANY TIME BY REPRESENTATIVES OF THE ARCHITECT AND OWNER. IF THE ARCHITECT OR OWNER'S AGENT FINDS ANY MATERIAL OR INSTALLATION THAT DOES NOT CONFORM TO THESE DRAWINGS AND SPECIFICATIONS, CONTRACTOR SHALL REMOVE THE MATERIAL FROM THE PREMISES AND CORRECT THE INSTALLATION TO THE SATISFACTION OF THE AGENT. 7.IN ACCEPTANCE OR REJECTION OF INSTALLED ELECTRICAL SYSTEMS, NO ALLOWANCE WILL BE MADE FOR LACK OF SKILL ON THE PART OF THE INSTALLERS. 1.03WORK INCLUDED A.THE ELECTRICAL SYSTEM REQUIRED FOR THIS WORK TO INCLUDE, BUT IS NOT NECESSARILY LIMITED TO: 1.NEW FEEDERS IN EXISTING CONDUIT TO REPLACEMENT PANEL ON THE 3RD FLOOR. 2.COMPLETE BRANCH CIRCUIT WIRING FOR LIGHTING, MOTORS, RECEPTACLES, JUNCTION BOXES, AND SIMILAR USES. 3.LIGHTING FIXTURES, WALL SWITCHES, RECEPTACLES AND SIMILAR ITEMS. 4.CONDUITS AND BOXES FOR DATA SYSTEM. 5.FIRE ALARM SYSTEM AS REQUIRED BY NATIONAL, STATE, AND LOCAL CODES. 1.04CODES AND STANDARDS A.THE LATEST EDITIONS OF THE FOLLOWING STANDARDS (INCLUDING SUPPLEMENTS AND OFFICIAL INTERPRETATIONS) ARE MINIMUM REQUIREMENTS: 1.NFPA 70 - NATIONAL ELECTRICAL CODE (NEC). 2.NFPA 72 - NATIONAL FIRE ALARM CODE. 3.NFPA 101 - LIFE SAFETY CODE. 4.NFPA 110 - EMERGENCY POWER SYSTEMS 5.COLORADO DEPARTMENT OF HEALTH “RULES AND REGULATIONS GOVERNING HOSPITALS IN THE STATE OF COLORADO”. 6.CONFORM TO ALL APPLICABLE STATE AND LOCAL CODES. 7.AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI). 8.NATIONAL ELECTRICAL SAFETY CODE (NESC). 9.AMERICANS WITH DISABILITIES ACTS (ADA) AND AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI) 117. 10.NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION (NEMA). 11.A.I.A. “GUIDELINES FOR DESIGN AND CONSTRUCTION OF HOSPITAL AND HEALTHCARE FACILITIES.” 12.UNDERWRITER'S LABORATORIES (UL). 13.JOINT COMMISSION FOR ACCREDITATION FOR HEALTHCARE ORGANIZATIONS (JCAHO). 14.INSULATED CABLE ENGINEERS ASSOCIATION (ICEA). 15.INTERNATIONAL BUILDING CODE. 16.INTERNATIONAL MECHANICAL CODE. 17.INTERNATIONAL FIRE CODE. 18.INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS (IEEE). 19.SHEET METAL AND AIR CONDITIONING CONTRACTORS NATIONAL ASSOCIATION (SMACNA). B.COMPLY WITH REQUIREMENTS OF UNDERWRITERS LABORATORIES FOR ALL ITEMS INSTALLED FOR WHICH U.L. STANDARDS HAVE BEEN ESTABLISHED. C.THE DRAWINGS AND SPECIFICATIONS TAKE PRECEDENCE WHEN THEY ARE MORE STRINGENT THAN CODES, STATUTES, OR ORDINANCES IN EFFECT. APPLICABLE CODES, ORDINANCES, STANDARDS AND STATUTES TAKE PRECEDENCE WHEN THEY ARE MORE STRINGENT OR CONFLICT WITH THE DRAWINGS AND SPECIFICATIONS. 1.05EXAMINATION OF BIDDING DOCUMENTS A.EACH BIDDER SHALL EXAMINE THE BIDDING DOCUMENTS CAREFULLY, AND NOT LATER THAN SEVEN DAYS PRIOR TO THE DATE OF RECEIPT OF BIDS, SHALL MAKE WRITTEN REQUEST TO THE ARCHITECT FOR INTERPRETATION OR CORRECTION OF ANY DISCREPANCIES, AMBIGUITIES, INCONSISTENCIES, OR ERRORS THEREIN WHICH HE MAY DISCOVER. THE ARCHITECT WILL ISSUE ANY INTERPRETATION OR CORRECTION AS AN ADDENDUM. ONLY A WRITTEN INTERPRETATION OR CORRECTION BY ADDENDUM SHALL BE BINDING. NO BIDDER SHALL RELY UPON INTERPRETATIONS OR CORRECTIONS GIVEN BY ANY OTHER METHOD. IF DISCREPANCIES, AMBIGUITIES, INCONSISTENCIES, OR ERRORS ARE NOT COVERED BY ADDENDUM OR WRITTEN DIRECTIVE, CONTRACTOR SHALL INCLUDE IN HIS BID, LABOR, MATERIALS AND METHODS OF CONSTRUCTION RESULTING IN HIGHER COST. AFTER AWARD OF CONTRACT, NO ALLOWANCE OR EXTRA COMPENSATION WILL BE MADE ON BEHALF OF THE CONTRACTOR DUE TO HIS FAILURE TO MAKE THE WRITTEN REQUESTS AS DESCRIBED ABOVE. B.FAILURE TO REQUEST CLARIFICATION DURING THE BID PHASE OF ANY INADEQUACY, OMISSION, OR CONFLICT WILL NOT RELIEVE THE CONTRACTOR OF THEIR RESPONSIBILITIES. THE SIGNING OF THE CONTRACT WILL BE CONSIDERED AS IMPLICITLY DENOTING THAT THE CONTRACTOR HAS A THOROUGH COMPREHENSION OF THE FULL INTENT AND SCOPE OF THE WORKING DRAWINGS AND SPECIFICATIONS. 1.06EXAMINATION OF PREMISES A.VISIT SITE PRIOR TO BID AND VERIFY THAT CONDITIONS ARE AS INDICATED. CONTRACTOR SHALL INCLUDE IN HIS BID COSTS REQUIRED TO MAKE HIS WORK MEET EXISTING CONDITIONS. 1.07EXISTING CONDITIONS A.EXISTING SYSTEMS AND CONDITIONS SHOWN ON DRAWINGS FOR EXISTING BUILDINGS ARE TO BE NOTED "FOR GUIDANCE ONLY". THE ELECTRICAL CONTRACTOR SHALL FIELD CHECK ALL EXISTING CONDITIONS PRIOR TO BIDDING AND IS TO INCLUDE IN HIS BID AN ALLOWANCE FOR EXTENSION, REMOVAL AND/OR RELOCATION OF EXISTING CONDUITS, WIRES, DEVICES, FIXTURES, OR OTHER EQUIPMENT AS INDICATED ON THE PLANS OR AS REQUIRED TO COORDINATE AND ADAPT NEW AND EXISTING ELECTRICAL SYSTEM TO ALL OTHER WORK. B.SYSTEM OUTAGES SHALL BE PERMITTED ONLY AT TIMES APPROVED BY OWNER IN WRITING. WORK WHICH COULD RESULT IN AN ACCIDENTAL OUTAGE (BEYOND BRANCH CIRCUITS) SHALL BE PERFORMED WITH THE OWNER'S MAINTENANCE PERSONNEL ADVISED OF SUCH WORK. C.SERVICE SHALL BE MAINTAINED TO EXISTING AREAS DURING CONSTRUCTION. CONTRACTOR SHALL PROVIDE PORTABLE GENERATORS, CABLES, OUTLETS, ETC. AS REQUIRED TO MAINTAIN CONTINUITY OF SERVICE. PLACEMENT OF SUCH PORTABLE EQUIPMENT SHALL BE SUBJECT TO OWNER APPROVAL. GENERATOR SYSTEM SHALL BE COMPLETE AND OPERABLE AND SHALL INCLUDE REQUIRED ACCESSORIES, FUEL TANKS, PIPING, MUFFLER, BLOCK HEATER, BATTERY CHARGER, ETC. D.PROVIDE NEW UPDATED PANELBOARD DIRECTORIES FOR EXISTING AND NEW CIRCUITS BEING UTILIZED FOR COMPLETION OF PROJECT. 1.08PERMITS, FEES & NOTICES A.OBTAIN AND PAY FOR ALL NECESSARY PERMITS, INSPECTIONS AND CERTIFICATES THAT MAY BE NECESSARY FOR THE FULL COMPLETION OF THE WORK. FURNISH THE OWNER WITH A CERTIFICATE OF FINAL INSPECTION AND APPROVAL FROM THE AHJ OVER THE ELECTRICAL INSTALLATION. B.NOTIFY PROPER AUTHORITIES WHEN WORK IS READY FOR INSPECTIONS REQUIRED BY APPLICABLE CODES, RULES AND REGULATIONS, ALLOWING SUFFICIENT TIME FOR INSPECTIONS TO BE MADE WITHOUT HINDERING PROGRESS OF THE WORK. FURNISH TO THE OWNER COPIES OF INSPECTION CERTIFICATES OF ACCEPTANCE. 1.09TESTS A.UPON COMPLETION OF ALL WORK AND ADJUSTMENT OF ALL EQUIPMENT, PROVIDE COMPLETE OPERATIONAL TESTS OF ALL ELECTRICAL EQUIPMENT PROVIDED UNDER THIS DIVISION. 1.10WARRANTY A.GUARANTEE THAT ALL WORK GOVERNED BY THIS DIVISION SHALL BE FREE OF DEFECTS IN WORKMANSHIP, MATERIALS AND PARTS FOR A PERIOD OF ONE (1) YEAR AFTER WRITTEN ACCEPTANCE. PROMPTLY REPAIR, REVISE, AND REPLACE DEFECTS AS DIRECTED WITH NO ADDITIONAL COST TO THE OWNER (LAMPS AND FUSES ARE EXEMPT). 1.11RECORD DRAWINGS A.DURING THE PROGRESS OF THE WORK, MAINTAIN AN ACCURATE RECORD OF THE INSTALLATION OF THE ELECTRICAL SYSTEM. UPON COMPLETION OF THE ELECTRICAL INSTALLATION, TRANSFER ALL RECORD DATA TO PRINTS OF THE ORIGINAL DRAWINGS. DRAWINGS SHALL INCLUDE ALL ADDENDUM ITEMS, CHANGE ORDERS, ALTERNATES, REROUTINGS, ETC. AS A CONDITION OF ACCEPTANCE OF THE PROJECT, DELIVER TO THE ARCHITECT ONE COPY OF THE RECORD DRAWINGS. 1.12PROTECTION A.OF PEOPLE: ARRANGE BARRIERS, SIGNS, ETC. AS REQUIRED TO MINIMIZE THE HAZARD OF PEOPLE. COMPLY WITH APPLICABLE SAFETY AND HEALTH REGULATIONS. COORDINATE AS NECESSARY WITH THE OWNER AND THE GENERAL CONTRACTOR. B.OF WORK: TAKE ALL MEASURES NECESSARY TO PROTECT THE WORK BOTH BEFORE AND AFTER INSTALLATION, TO ASSURE THAT IT WILL BE IN CLEAN, UNDAMAGED, UNBLEMISHED CONDITION WHEN TURNED OVER TO THE OWNER. REPAIR/REPLACE WORK DAMAGED DURING CONSTRUCTION. PART 2 - PRODUCTS 2.01STANDARD FOR MATERIALS A.ALL ELECTRICAL MATERIAL SHALL BE NEW AND OF THE QUALITY AND TYPE SPECIFIED. B.MANUFACTURER AND CATALOG NUMBER SHOWN IN THESE SPECIFICATIONS OR ON DRAWINGS ARE INTENDED AS A GUIDE TO QUALITY. EQUIVALENT MATERIALS AND EQUIPMENT OF OTHER MANUFACTURERS WILL BE CONSIDERED PROVIDED SUCH SUBSTITUTIONS ARE REQUESTED IN ACCORDANCE WITH THE PROVISIONS OF PARAGRAPH 2.03 AND SHALL INCLUDE ALL INFORMATION NECESSARY TO SUPPORT THE CLAIM OF EQUIVALENCY. C.NO EXTENSION OF COMPLETION DATE SHALL BE ALLOWED FOR TIME LOST IN CONSIDERATION, SHIPPING, OR INSTALLATION OF APPROVED SUBSTITUTIONS. REVIEW OF SUBSTITUTIONS SIGNIFIES GENERAL EQUALITY OF MATERIALS AND EQUIPMENT ONLY. THIS REVIEW DOES NOT RELIEVE THE CONTRACTOR OF RESPONSIBILITY FOR PROPER OPERATION OF THE SYSTEM, COMPLIANCE WITH SPECIFICATIONS AND NECESSARY CHANGES DUE TO DIMENSIONAL DIFFERENCES OR SPACE REQUIREMENTS. 2.02SHOP DRAWINGS A.SHOP DRAWINGS REQUIRED FOR THIS PROJECT ARE AS FOLLOWS: 1.LIGHTING FIXTURES 2.LAMPS 3.LOAD CENTERS 4.WIRING DEVICES 5.FIRE ALARM AND DETECTION SYSTEM 6.DISCONNECTS 7.FUSES 8.MOTOR STARTERS B.PRESENT SHOP DRAWING SUBMITTAL DATA AT ONE TIME, BOUND IN THREE-RING BINDERS, INDEXED IN A NEAT AND ORDERLY MANNER. PARTIAL SUBMITTALS WILL NOT BE ACCEPTED. PROVIDE FOUR SETS OF SUBMITTAL DATA, UNLESS NOTED OTHERWISE IN DIVISION I. C.PLACE ORDERS FOR ALL EQUIPMENT IN TIME TO PREVENT ANY DELAY IN CONSTRUCTION SCHEDULE OR COMPLETION OF PROJECT. IF ANY MATERIALS OR EQUIPMENT ARE NOT ORDERED IN TIME, ADDITIONAL CHARGES MADE BY EQUIPMENT MANUFACTURERS TO COMPLETE THEIR EQUIPMENT IN TIME TO MEET CONSTRUCTION SCHEDULE, TOGETHER WITH ANY SPECIAL HANDLING CHARGES, SHALL BE BORNE BY THE CONTRACTOR. D.SHOP DRAWINGS: CONTRACTOR AGREES THAT SHOP DRAWING SUBMITTALS PROCESSED BY THE ENGINEER ARE NOT CHANGE ORDERS; THAT THE PURPOSE OF SHOP DRAWING SUBMITTALS BY THE CONTRACTOR IS TO DEMONSTRATE TO THE ENGINEER THAT THE CONTRACTOR UNDERSTANDS THE DESIGN CONCEPT, THAT HE DEMONSTRATES HIS UNDERSTANDING BY INDICATING WHICH EQUIPMENT AND MATERIAL HE INTENDS TO PROVIDE AND BY DETAILING THE FABRICATION AND INSTALLATION METHODS HE INTENDS TO USE. CONTRACTOR FURTHER AGREES THAT IF DEVIATIONS, DISCREPANCIES, OR CONFLICTS BETWEEN SHOP DRAWING SUBMITTALS AND CONTRACT DOCUMENTS IN THE FORM OF DESIGN DRAWINGS AND SPECIFICATIONS ARE DISCOVERED EITHER PRIOR TO OR AFTER SHOP DRAWING SUBMITTALS ARE PROCESSED BY THE ENGINEER, THE DESIGN DRAWINGS AND SPECIFICATIONS SHALL CONTROL AND SHALL BE FOLLOWED. 2.03BID ALTERNATE(S) A.REFER TO DIVISION 1 FOR ADDITIONAL INFORMATION. B.ALTERNATE(S) FOR MATERIAL AND EQUIPMENT 1.EQUIPMENT AND MATERIAL BID ALTERNATE(S) SHALL BE PROPOSED AS ADDITIVE OR DEDUCTIVE ALTERNATE(S) TO SPECIFIED ITEMS BY SUBMITTING IT AS A SEPARATE LINE ITEM FROM THE BASE BID ON THE BIDDER'S LETTERHEAD. 2.SUCH BID ALTERNATE PROPOSALS SHALL NOT BE SUBSTITUTED OR INCLUDED IN THE BASE BID. BID ALTERNATE PROPOSAL(S) MUST BE ACCOMPANIED BY FULL DESCRIPTIVE DATA ON THE PROPOSED EQUIPMENT, TOGETHER WITH A STATEMENT OF THE COST TO BE ADDED OR DEDUCTED FOR EACH ITEM. THE BID ALTERNATE SHALL INCLUDE ALL MATERIALS, EQUIPMENT, LABOR, CONNECTIONS, COORDINATION WITH ALL OTHER TRADES, ETC. FOR A COMPLETE AND OPERATIONAL SYSTEM. 3.THE CONTRACTOR SHALL SUBMIT THE BID ALTERNATES AT THE TIME THE BASE BIDS ARE DUE. 2.04SUBSTITUTIONS A.BIDDER'S CHOICE: MATERIAL OR EQUIPMENT LISTED BY SEVERAL MANUFACTURERS' NAMES ARE INTENDED TO BE BIDDER'S CHOICE, AND ANY OF THE LISTED MANUFACTURERS MAY BE USED IN THE BASE BID. B.PERFORMANCE SPECIFICATIONS: WHEN ANY ITEM IS SPECIFIED BY REQUIREMENTS TO MEET A PERFORMANCE, INDUSTRY OR REGULATING BODY STANDARD, OR IS SPECIFIED BY A GENERIC SPEC, (NO MANUFACTURER'S NAME LISTED) NO PRIOR REVIEW BY THE ENGINEER IS NEEDED UNLESS SPECIFICALLY CALLED FOR IN THESE SPECIFICATIONS. C.CONTRACTOR TO BE RESPONSIBLE FOR ANY CHANGES AND COSTS TO ACCOMMODATE ANY EQUIPMENT EXCEPT THE FIRST NAMED IN THE SPECIFICATION. D.SUBSTITUTIONS OF MATERIAL (CONTRACTOR AND OWNER INITIATED) 1.OTHER ITEMS OF MATERIAL AND EQUIPMENT NOT LISTED AS EQUIVALENTS MAY BE OFFERED (AT THE CONTRACTOR'S OPTION) AS SUBSTITUTIONS TO SPECIFIED ITEMS BY SUBMITTING IT AS A SEPARATE PRICE WITH HIS BASE BID ON THE BIDDER'S LETTERHEAD. 2.SUCH SUBSTITUTE PROPOSALS SHALL NOT BE INCLUDED UNDER THE BASE BID AND MUST BE ACCOMPANIED BY FULL DESCRIPTIVE DATA ON THE PROPOSED EQUIPMENT, TOGETHER WITH A STATEMENT OF THE COST TO BE DEDUCTED FOR EACH ITEM AND ALL DEVIATIONS FROM SPECIFIED ITEMS. HIGHLIGHT ALL DIFFERENCE FROM SPECIFIED EQUIPMENT. IF ANY SUCH SUBSTITUTIONS ARE TO BE CONSIDERED, THE CONTRACTOR SHALL SUBMIT A LIST OF THE PROPOSED SUBSTITUTION ITEMS WITHIN 14 DAYS OF AWARD OF CONTRACT. LATE REQUESTS FOR PROPOSED SUBSTITUTIONS SHALL NOT BE ACCEPTED BY THE ENGINEER DUE TO SCHEDULING OR DELIVERY CONCERNS. 3.IF SUBSTITUTIONS ARE REJECTED, ELECTRICAL CONTRACTOR SHALL SUPPLY BASE BID ITEM AS SPECIFIED. 2.05PRODUCT HANDLING A.USE ALL MEANS NECESSARY TO PROTECT ELECTRICAL SYSTEM MATERIALS BEFORE, DURING AND AFTER INSTALLATION AND TO PROTECT THE INSTALLED WORK AND MATERIALS OF ALL OTHER TRADES. B.IN THE EVENT OF DAMAGE, IMMEDIATELY MAKE ALL REPAIRS AND REPLACEMENTS NECESSARY TO THE APPROVAL OF THE ARCHITECT AT NO ADDITIONAL COST TO THE OWNER. C.UPON COMPLETION OF ALL INSTALLATIONS, LAMPING AND TESTING, THOROUGHLY INSPECT ALL EXPOSED PORTIONS OF THE ELECTRICAL INSTALLATION AND COMPLETELY REMOVE ALL EXPOSED LABELS, SOIL, MARKINGS, AND FOREIGN MATERIALS. PART 3 - EXECUTION 3.01WORKMANSHIP AND COMPLETION OF INSTALLATION A.CONTRACTOR'S PERSONNEL AND SUBCONTRACTORS SELECTED TO PERFORM THE WORK SHALL BE WELL VERSED AND SKILLED IN THE TRADES INVOLVED. B.COORDINATE ELECTRICAL EQUIPMENT AND MATERIALS INSTALLATION WITH OTHER BUILDING COMPONENTS. C.SEQUENCE, COORDINATE, AND INTEGRATE INSTALLATIONS OF ELECTRICAL MATERIALS AND EQUIPMENT FOR EFFICIENT FLOW OF THE WORK. GIVE PARTICULAR ATTENTION TO LARGE EQUIPMENT REQUIRING POSITIONING PRIOR TO CLOSING-IN THE BUILDING. D.ANY CHANGES OR DEVIATIONS FROM THE DRAWINGS AND SPECIFICATIONS MUST BE ACCEPTED IN WRITING BY THE ARCHITECT/ENGINEER. ALL ERRORS IN INSTALLATION SHALL BE CORRECTED AT THE EXPENSE OF THE CONTRACTOR. ALL SPECIALTIES SHALL BE INSTALLED AS DETAILED ON THE DRAWINGS. WHERE DETAIL OR SPECIFIC INSTALLATION REQUIREMENTS ARE NOT PROVIDED, MANUFACTURER'S RECOMMENDATIONS SHALL BE FOLLOWED. E.UPON COMPLETION OF WORK, ALL EQUIPMENT AND MATERIALS SHALL BE INSTALLED COMPLETE, THOROUGHLY CHECKED, CORRECTLY ADJUSTED, AND LEFT READY FOR INTENDED USE OR OPERATION. ALL WORK SHALL BE THOROUGHLY CLEANED AND ALL RESIDUE SHALL BE REMOVED FROM SURFACES. EXTERIOR SURFACES OF ALL MATERIAL AND EQUIPMENT SHALL BE DELIVERED IN A PERFECT, UNBLEMISHED CONDITION. F.CONTRACTOR SHALL PROVIDE A COMPLETE INSTALLATION, INCLUDING ALL REQUIRED LABOR, MATERIAL, CARTAGE, INSURANCE, PERMITS, AND TAXES. 3.02PROGRESS OF WORK A.ORDER THE PROGRESS OF ELECTRICAL WORK TO CONFORM TO THE PROGRESS OF THE WORK OF THE OTHER TRADES. COMPLETE THE ENTIRE INSTALLATION AS SOON AS THE CONDITION OF THE BUILDING WILL PERMIT. ANY COST RESULTING FROM DEFECTIVE OR ILL-TIMED WORK PERFORMED UNDER THIS SECTION SHALL BE BORNE BY THIS CONTRACTOR. 3.03CUTTING AND PATCHING A.PROVIDE ALL CUTTING, TRENCHING, BACKFILLING, PATCHING AND REFINISHING OR RESURFACING REQUIRED FOR ELECTRICAL WORK IN A MANNER MEETING THE APPROVAL OF THE ENGINEER AND AT NO ADDITIONAL COST TO THE OWNER. B.ALL OPENINGS MADE IN FIRE-RATED WALLS, FLOORS, OR CEILINGS SHALL BE PATCHED AND MADE TIGHT IN A MANNER TO CONFORM TO THE FIRE RATING FOR THE SURFACE PENETRATED. 3.04DELIVERY AND STORAGE OF MATERIALS A.ARRANGE AND BE HELD RESPONSIBLE FOR DELIVERY AND SAFE STORAGE OF MATERIALS AND EQUIPMENT FOR ELECTRICAL INSTALLATION. B.CAREFULLY CHECK MATERIALS FURNISHED TO THIS CONTRACTOR FOR INSTALLATION, AND PROVIDE RECEIPT ACKNOWLEDGING ACCEPTANCE OF DELIVERY AND CONDITION OF THE MATERIALS RECEIVED. THEREAFTER, ASSUME FULL RESPONSIBILITY FOR ITS SAFEKEEPING UNTIL THE FINAL INSTALLATION HAS BEEN REVIEWED AND ACCEPTED. 3.05PROTECTION OF WORK AND PROPERTY A.WHERE THERE ARE EXISTING FACILITIES, BE RESPONSIBLE FOR THE PROTECTION THEREOF, WHETHER OR NOT SUCH FACILITY IS TO BE REMOVED OR RELOCATED. MOVING OR REMOVING ANY FACILITY MUST BE DONE SO AS NOT TO CAUSE INTERRUPTION OF THE WORK OF OWNER'S OPERATION. B.CLOSE ALL CONDUIT OPENINGS WITH CAPS OR PLUGS DURING INSTALLATION. COVER ALL FIXTURES AND EQUIPMENT AND PROTECT AGAINST INJURY. AT THE FINAL COMPLETION, CLEAN ALL WORK AND DELIVER IN AN UNBLEMISHED CONDITION, OR REFINISH AND REPAINT AT THE DISCRETION OF THE ARCHITECT. C.ANY EQUIPMENT OR CONDUIT SYSTEMS FOUND TO HAVE BEEN DAMAGED OR CONTAMINATED ABOVE “MILL” OR “SHOP” CONDITIONS SHALL BE REPLACED OR CLEANED TO THE ENGINEER'S SATISFACTION. 3.06FINAL ACCEPTANCE A.FINAL ACCEPTANCE BY THE OWNER WILL NOT OCCUR UNTIL ALL OPERATING INSTRUCTIONS ARE RECEIVED AND OWNER'S PERSONNEL HAVE BEEN THOROUGHLY INDOCTRINATED IN THE MAINTENANCE AND OPERATION OF ALL EQUIPMENT. B.OPERATING MANUAL, PARTS LISTS, AND INDOCTRINATION OF OPERATING AND MAINTENANCE PERSONNEL: FURNISH THE SERVICES OF A QUALIFIED REPRESENTATIVE OF THE SUPPLIER FOR EACH ITEM OR SYSTEM ITEMIZED BELOW WHO SHALL INSTRUCT SPECIFIC PERSONNEL, AS DESIGNATED BY THE OWNER, IN THE OPERATION AND MAINTENANCE OF THAT ITEM OR SYSTEM. C.DELIVER THREE (3) COMPLETE OPERATING MANUALS AND PARTS LISTS TO THE OWNER (OR HIS DESIGNATED REPRESENTATIVE) AT THE TIME OF THE ABOVE REQUIRED INDOCTRINATION. FULLY EXPLAIN THE CONTENTS OF THE MANUALS AS PART OF REQUIRED INDOCTRINATION AND INSTRUCT THE OWNER'S PERSONNEL IN THE CORRECT PROCEDURE IN OBTAINING SERVICE, BOTH DURING AND AFTER THE GUARANTEE PERIOD. THE OPERATING MANUAL AND PARTS LISTS SHALL GIVE COMPLETE INFORMATION AS TO WHOM THE OWNER SHALL CONTACT FOR SERVICE AND PARTS, INCLUDING THE ADDRESS AND PHONE NUMBER. FURNISH EVIDENCE THAT AN AUTHORIZED SERVICE ORGANIZATION REGULARLY CARRIES A COMPLETE STOCK OF REPAIR PARTS FOR THESE ITEMS (OR SYSTEMS), AND THAT THE ORGANIZATION IS AVAILABLE FOR SERVICE. SERVICE SHALL BE FURNISHED WITHIN TWENTY FOUR (24) HOURS AFTER REQUESTED. D.CLEAN UP: REMOVE ALL MATERIALS, SCRAP, ETC., RELATIVE TO THE ELECTRICAL INSTALLATION AND LEAVE THE PREMISES AND ALL EQUIPMENT, LAMPS, FIXTURES, ETC. IN A CLEAN, ORDERLY CONDITION. ANY COSTS TO THE OWNER FOR CLEAN UP OF THE SITE WILL BE CHARGED AGAINST THE CONTRACTOR. E.ACCEPTANCE DEMONSTRATION: UPON COMPLETION OF THE WORK, AT A TIME TO BE DESIGNATED BY THE ARCHITECT, THE CONTRACTOR SHALL DEMONSTRATE FOR THE OWNER THE OPERATION OF THE ENTIRE INSTALLATION, INCLUDING ALL SYSTEMS PROVIDED UNDER THIS CONTRACT. F.OPERATING AND ACCEPTANCE TESTS: PROVIDE ALL LABOR, INSTRUMENTS, AND EQUIPMENT FOR THE PERFORMANCE OF TESTS AS SPECIFIED. SUBMIT THREE (3) COPIES OF A TYPEWRITTEN TEST REPORT FOR THE ARCHITECT FOR HIS APPROVAL. 1.RECORD THE FULL LOAD CURRENT IN EACH PHASE OR LINE AT THE MAIN SERVICE ENTRANCE AND FOR EACH FEEDER LEAVING THE MAIN DISTRIBUTION PANELBOARD. READINGS SHALL BE TAKEN WITH THE MAXIMUM INSTALLED LOAD CONNECTED AND IN OPERATION. 2.PERFORM A CAREFUL INSPECTION OF THE MAIN SWITCHBOARD BUS STRUCTURE AND CABLE CONNECTIONS TO VERIFY THAT ALL CONNECTIONS ARE MECHANICALLY AND ELECTRICALLY TIGHT. 3.MEASURE THE RESISTANCE TO GROUND FOR THE SERVICE GROUND, WHICH SHALL NOT EXCEED TEN (10) OHMS UNDER NORMAL SOIL MOISTURE CONDITIONS. IF REQUIRED, INSTALL ADDITIONAL GROUND PROVISIONS IN A MANNER ACCEPTED BY THE ENGINEER AT NO ADDITIONAL COST TO THE OWNER. 3.07IDENTIFICATION A.GENERAL: PROVIDE THE FOLLOWING SERVICES AND MATERIALS TO ASSIST THE OWNER IN OPERATION AND MAINTENANCE. B.DIRECTORY CARDS, NAMEPLATES AND LABELS: NO TEMPORARY MARKINGS, WHICH ARE VISIBLE ON EQUIPMENT, SHALL REMAIN AFTER THE PROJECT IS COMPLETE. REPAINT TRIMS, HOUSING, ETC., WHERE SUCH MARKINGS CANNOT BE READILY REMOVED. DEFACED FINISHES MUST BE REFINISHED. ALL ENGRAVED METAL OR PLASTIC NAMEPLATES SHALL BE WHITE LETTERS ON A BLACK OR GRAY BACKGROUND. RAISED LETTER TYPE TAPE SHALL NOT BE USED. NO ABBREVIATIONS IN LABELING WILL BE PERMITTED WITHOUT SPECIAL APPROVAL. ALL PANELBOARDS SHALL BE LABELED AS DESIGNATED ON THE ELECTRICAL DRAWINGS. THOROUGHLY CLEAN SURFACE TO WHICH PRESSURE SENSITIVE TYPE LABELS ARE APPLIED TO ASSURE ADHERENCE OF LABEL. DIRECTORY CARDS, NAMEPLATES, AND LABELS SHALL INDICATE THE GENERAL AREA AND TYPE OF ELECTRICAL LOAD SERVED BY EACH CIRCUIT. PROVIDE THE FOLLOWING TYPES OF LABELS AT THESE LOCATIONS. 1.ON EACH FEEDER SWITCH, COMBINATION STARTER, OR CIRCUIT BREAKER LOCATED IN MOTOR CONTROL CENTERS, MAIN SERVICE EQUIPMENT, THE MAIN SWITCHBOARD OR PANELBOARD, SUBDISTRIBUTION PANELBOARDS, AND ALL SPECIAL EQUIPMENT HOUSED IN CABINETS, THE LABELING SHALL BE ONE FOURTH INCH (1/4”) MINIMUM HEIGHT LETTERS. 2.ON EACH SEPARATE MOUNTED DISCONNECT AND STARTER FOR A MOTOR OR FIXED APPLIANCE, INDICATE MOTOR OR APPLIANCE DESIGNATION, VOLTAGE, AND PHASE. (MOTOR OR APPLIANCE DESIGNATIONS SHALL BE AS GIVEN ON THE MECHANICAL OR ARCHITECTURAL PLANS.) USE THREE-SIXTEENTH INCH (3/16”) MINIMUM HEIGHT LETTERS. 3.ON ALL BRANCH CIRCUIT PANELBOARDS INDICATE PANEL DESIGNATION, VOLTAGE AND PHASE. USE THREE-FOURTHS INCH (3/4”) MINIMUM HEIGHT STENCILED LETTERS IN METAL TAPE OR ONE-HALF INCH (1/2”) ENGRAVED LETTERS ON LAMINATED NAMEPLATE. APPLY TO THE INSIDE OF EACH DOOR. ALL EMERGENCY PANELS AND DISCONNECTS SHALL BE PAINTED WITH RED ENAMEL. 4.FOR ALL BRANCH CIRCUIT PANELBOARD DIRECTORIES, PROVIDE NEATLY TYPED, REMOVABLE CARDS AND PROTECTIVE PLASTIC FACES. SPARE CIRCUIT BREAKERS SHALL BE IDENTIFIED AS SUCH. 5.FOR ALL DEVICE PLATES FOR SWITCHES USED TO CONTROL EXHAUST FANS OR OTHER EQUIPMENT, PROVIDE ONE-EIGHTH INCH (1/8”) MINIMUM HEIGHT BLACK FILLED, ENGRAVED LETTERS ON STAINLESS STEEL DEVICE PLATES. 6.FOR ALL RECEPTACLE DEVICE PLATES, PROVIDE ONE-EIGHTH INCH (1/8”) MINIMUM HEIGHT LETTERS ON WHITE (NORMAL POWER) AND RED (EMERGENCY POWER) NAMEPLATES INDICATING PANEL AND CIRCUIT NUMBER. 7.FOR ALL EXPOSED CONDUITS, JUNCTION BOXES, WIRING GUTTERS, ETC., PROVIDE THREE-FOURTHS INCH (3/4”) MINIMUM HEIGHT STENCILED LETTERS, OR ONE-HALF INCH (1/2”) MINIMUM HEIGHT PRESSURE SENSITIVE LABELS EQUAL TO BRADY SELF-STICKING VINYL CLOTH. LABELS SHALL BE PROVIDED AT THE FOLLOWING LOCATIONS: a.ENTERING OR LEAVING PANELS OR SWITCHGEAR OR ENCLOSURES. b.ALL JUNCTION BOXES SHALL BE IDENTIFIED AS TO CIRCUITS CONTAINED WITHIN. 3.08CONSTRUCTION LIGHTING AND POWER A.PROVIDE ALL TEMPORARY FACILITIES REQUIRED TO SUPPLY CONSTRUCTION POWER AND LIGHT. INSTALL AND MAINTAIN FACILITIES IN A MANNER THAT WILL PROTECT THE PUBLIC AND WORKMEN. COMPLY WITH ALL APPLICABLE LAWS AND REGULATIONS. 3.09REMODELING PROVISIONS A.EXISTING SYSTEMS AND CONDITIONS SHOWN ON THE DRAWINGS ARE PROVIDED FOR GUIDANCE ONLY. THE ELECTRICAL CONTRACTOR SHALL FIELD CHECK ALL EXISTING CONDITIONS PRIOR TO BIDDING AND SHALL INCLUDE IN HIS BID AN ALLOWANCE FOR THE REMOVAL AND RELOCATION OF EXISTING CONDUITS, WIRES, DEVICES, FIXTURES, OR OTHER EQUIPMENT AS INDICATED ON THE PLANS OR AS REQUIRED TO COORDINATE AND ADAPT NEW AND EXISTING ELECTRICAL SYSTEMS TO ALL OTHER WORK REQUIRED FOR THIS PROJECT. B.CONNECT NEW WORK TO EXISTING IN A MANNER THAT WILL ASSURE PROPER RACEWAY GROUNDING THROUGHOUT IN CONFORMANCE WITH THE NATIONAL ELECTRICAL CODE. C.REMODEL WORK CUTTING AND PATCHING: THE CONTRACTOR SHALL PERFORM CUTTING, CHANNELING, CHASING, DRILLING, ETC., AS REQUIRED TO INSTALL OR REMOVE ELECTRICAL EQUIPMENT IN AREAS OF REMODELING. THIS WORK SHALL BE PERFORMED SO AS TO MINIMIZE DAMAGE TO PORTIONS OF WALL FINISHES, SURFACES, PLASTERING, OR THE STRUCTURE WHICH ARE TO BE REUSED, RESURFACED, PLASTERED OR PAINTED UNDER ANOTHER DIVISION OF THESE SPECIFICATIONS. D.CAREFULLY COORDINATE WITH THE REQUIRED REMODELING WORK, CUTTING AND PATCHING ETC., PERFORMED BY THE OTHER TRADES. REMOVE OR RELOCATE EXISTING ELECTRICAL CONDUITS, WIRES, DEVICES, FIXTURES AND OTHER EQUIPMENT AS NECESSARY. E.ALL OUTAGES ON PORTIONS OF EXISTING ELECTRICAL SYSTEMS SHALL BE MINIMIZED AND SHALL BE AT A TIME AND OF DURATION AS ACCEPTED BY THE OWNER. 3.10ELECTRICAL DEMOLITION A.EXAMINATION 1.VERITY FIELD MEASUREMENTS AND CIRCUITING ARRANGEMENTS ARE AS SHOWN ON DRAWINGS. 2.VERIFY THAT ABANDONED WIRING AND EQUIPMENT SERVE ONLY ABANDONED FACILITIES. 3.DEMOLITION DRAWINGS ARE BASED ON CASUAL FIELD OBSERVATION AND EXISTING RECORD DOCUMENTS. REPORT DISCREPANCIES TO ARCHITECT BEFORE DISTURBING EXISTING INSTALLATION. 4.BEGINNING OF DEMOLITION MEANS INSTALLER ACCEPTS EXISTING CONDITIONS. B.PREPARATION 1.DISCONNECT ELECTRICAL SYSTEMS IN WALLS, FLOORS, AND CEILINGS SCHEDULED FOR REMOVAL. 2.COORDINATION OUTAGES WITH ARCHITECT/OWNER. 3.PROVIDE TEMPORARY WIRING AND CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING CONSTRUCTION. WHEN WORK MUST BE PERFORMED ON ENERGIZED EQUIPMENT OR CIRCUITS, USE PERSONNEL EXPERIENCED IN SUCH OPERATIONS. 4.FIRE PROTECTION, FIRE ALARM, AND DETECTION SYSTEMS SHALL BE MAINTAINED AND CAPABLE OF PROPER OPERATION DURING CONSTRUCTION. THE LOCAL FIRE MARSHALL SHALL BE NOTIFIED BEFORE CONSTRUCTION STARTS, WHEN SCHEDULED INTERRUPTIONS ARE EXPECTED AND AFTER CONSTRUCTION IS COMPLETE. PROTECT AND SUPPORT LIFE SAFETY SYSTEMS ROUTED THROUGH AREAS OF DEMOLITION. 5.EXISTING TELEPHONE SYSTEM: MAINTAIN EXISTING SYSTEM IN SERVICE. DISABLE SYSTEM ONLY TO MAKE SWITCHOVERS AND CONNECTIONS. NOTIFY OWNER/ARCHITECT IN WRITING AT LEAST 24 HOURS BEFORE PARTIALLY OR COMPLETELY DISABLING SYSTEM. MINIMIZE OUTAGE DURATION. C.DEMOLITION AND EXTENSION OF EXISTING ELECTRICAL WORK 1.REMOVE, RELOCATE, AND EXTEND EXISTING INSTALLATIONS TO ACCOMMODATE NEW CONSTRUCTION. 2.REMOVE ABANDONED WIRING TO SOURCE OF SUPPLY. 3.DISCONNECT ABANDONED OUTLETS AND REMOVE DEVICES. REMOVE ABANDONED OUTLETS IF CONDUIT SERVICING THEM IS ABANDONED AND REMOVED. PROVIDE BLANK COVER FOR ABANDONED OUTLETS, WHICH ARE NOT REMOVED. 4.DISCONNECT AND REMOVE ELECTRICAL DEVICES AND EQUIPMENT SERVING UTILIZATION EQUIPMENT THAT HAS BEEN REMOVED. 5.DISCONNECT AND REMOVE ABANDONED LUMINAIRES. REMOVE BRACKETS, STEMS, HANGERS, AND OTHER ACCESSORIES. 6.REPAIR ADJACENT CONSTRUCTION AND FINISHES DAMAGED DURING DEMOLITION AND EXTENSION WORK. 7.MAINTAIN ACCESS TO EXISTING ELECTRICAL INSTALLATIONS, WHICH REMAIN ACTIVE. MODIFY INSTALLATION OR PROVIDE ACCESS PANEL AS APPROPRIATE. 8.EXTEND EXISTING INSTALLATIONS USING MATERIALS AND METHODS COMPATIBLE WITH EXISTING ELECTRICAL INSTALLATION, OR AS SPECIFIED IN INDIVIDUAL SECTION. D.CLEANING AND REPAIR 1.CLEAN AND REPAIR EXISTING MATERIALS AND EQUIPMENT, WHICH REMAIN OR ARE TO BE REUSED. 2.PANELBOARDS: CLEAN EXPOSED SURFACES AND CHECK TIGHTNESS OF ELECTRICAL CONNECTIONS. REPLACE DAMAGED CIRCUIT BREAKERS AND PROVIDE CLOSURE PLATES FOR VACANT POSITIONS. PROVIDE TYPED CIRCUIT DIRECTORY SHOWING REVISED CIRCUITING ARRANGEMENT. 3.LUMINARIES: REMOVE EXISTING LUMINAIRES FOR CLEANING. USE MILD DETERGENT TO CLEAN ALL EXTERIOR AND INTERIOR SURFACES; RINSE WITH CLEAN WATER AND WIPE DRY. REPLACE LAMPS, NON-OPERATIONAL BALLASTS, AND BROKEN ELECTRICAL PARTS. END OF SECTION 16010 SECTION 16100--BASIC MATERIALS AND METHODS PART 1 - GENERAL (NOT USED) PART 2 - PRODUCTS 2.01RACEWAYS AND FITTINGS A.CONDUIT: 1.CONDUITS SUBJECT TO MECHANICAL DAMAGE OR WHERE OTHERWISE REQUIRED BY CODE SHALL BE GALVANIZED RIGID HEAVY WALL CONDUIT; ALL OTHER CONDUIT MAY BE ELECTRIC METALLIC TUBING. 2.FLEXIBLE METALLIC CONDUIT SHALL BE USED WHERE VIBRATION OR OTHER REASONS DO NOT ALLOW SOLID CONNECTIONS TO MOTORS, EQUIPMENT, ETC. FLEX MAY ALSO BE USED TO FISH IN EXISTING WALLS OR WHERE REQUIRED TO CONNECTION IN MILLWORK. THE USE OF FLEX SHALL BE HELD TO A MINIMUM. WHERE FLEXIBLE METALLIC CONDUIT IS USED IN AREAS SUBJECT TO MOISTURE, PVC-COATED FLEX (LIQUIDTIGHT) SHALL BE USED. B.FITTINGS: 1.USE COMPRESSION FITTINGS FOR ALL EMT CONDUIT. 2.02WIRE AND CABLE A.VOLTAGE RANGE 0 TO 24: HIGH CONDUCTIVITY COPPER, THERMO-PLASTIC INSULATION, 300 VOLT RATING. B.VOLTAGE RANGE 24 TO 600: HIGH CONDUCTIVITY COPPER, MOISTURE-RESISTANT THERMO-PLASTIC INSULATION, 600 VOLT 75°C RATING FOR GENERAL USE. FOR HID FIXTURES AND WIRING WITHIN 3 INCHES OF FLUORESCENT BALLASTS, WIRE SHALL BE COPPER, MINIMUM 90°C RATED. SIZES INDICATED ARE FOR INSTALLATION IN A MAXIMUM 30°C AMBIENT. CONDUCTOR AMPACITY SHALL BE DERATED FOR HIGHER AMBIENT INSTALLATIONS. C.CONDUCTORS USED SPECIFICALLY FOR EQUIPMENT OR SERVICE GROUND MAY BE BARE OR HAVE INSULATION TO MATCH CIRCUIT/FEEDER CONDUCTORS. 2.03WIRE CONNECTIONS A.ALL ELECTRICAL CONNECTIONS SHALL BE ELECTRICALLY AND MECHANICALLY SECURE, USING THE FOLLOWING METHODS: 1.WIRE SIZE #8 AND SMALLER--PRESSURE TYPE CONNECTORS (SCOTCH-LOK) OR EQUIVALENT. 2.WIRE SIZE #6 AND LARGER--MECHANICAL OR COMPRESSION LUGS, BURNDY, T & B, ILSCO OR EQUIVALENT. B.WIRE TERMINATION PROVISIONS FOR PANELBOARDS, CIRCUIT BREAKERS, SAFETY SWITCHES, AND ALL OTHER ELECTRICAL APPARATUS SHALL BE LISTED AS SUITABLE FOR 75°C. 2.04OUTLET BOXES A.OUTLET BOXES SHALL BE: ONE PIECE STEEL, GALVANIZED, STEEL CITY ELECTRIC, APPLETON ELECTRIC, RACO OR APPROVED EQUIVALENT. WHERE NMC OR ENT IS USED, PLASTIC BOXES ARE ACCEPTABLE. 2.05DEVICES A.WIRING DEVICES SHALL BE HOSPITAL GRADE AND RATED AT 20 AMPERES FOR LIGHT SWITCHES AND 20 AMPERES FOR DUPLEX RECEPTACLES. SWITCHES, RECEPTACLES, AND OTHER DEVICES SHALL BE LEVITON DECORA STYLE, OR PASS SEYMOUR, COOPER, OR HUBBELL EQUIVALENT. COLOR SHALL BE AS DIRECTED BY THE ARCHITECT. B.GFCI RECEPTACLES SHALL BE STRAIGHT BLADE FEED THROUGH TYPE WITH INDICATOR LIGHT THAT IS LIGHTED WHEN DEVICE IS TRIPPED. C.SWITCHES SHALL BE 120/277V, 20A, ROCKER TYPE. D.WALL SWITCH OCCUPANCY SENSORS: 120/277V, ADJUSTABLE TIME DELAY UP TO 20 MINUTES, 180 DEGREE FIELD OF VIEW SWITCH A MINIMUM COVERAGE AREA OF 300 SQUARE FEET. PASSIVE INFRARED TYPE SHALL BE WATT STOPPER WS-200. ADAPTIVE TECHNOLOGY TYPE SHALL BE WATT STOPPER WA-200. E.AREA OCCUPANCY SENSORS: 120/277V, ADJUSTABLE TIME DELAY UP TO 30 MINUTES 260 DEGREE FIELD OF VIEW. MANUFACTURE SHALL BE WATT STOPPER OR APPROVED EQUAL. MODEL NUMBER AS SHOWN IN THE FOLLOWING APPLICATIONS: 1.SMALL ROOM SENSOR - PASSIVE INFRARED TYPE, MINIMUM COVERAGE OF 500 SQUARE FEET. WS CI-300-1. 2.LARGE ROOM SENSOR - DUAL TECHNOLOGY WITH BOTH INFRARED AND ULTRASONIC TYPE SENSING, MINIMUM COVERAGE OF 1,000 SQUARE FEET. WS DT-300. 3.CORRIDOR SENSOR: ULTRASONIC TYPE. MINIMUM COVERAGE OF 90 LINEAR FEET. WS WT-2250. F.WALL PLATES SHALL BE 0.035-INCH THICK, SATIN FINISHED STAINLESS STEEL MATERIAL FOR FINISHED SPACES. 2.06DISCONNECTS A.SAFETY SWITCHES SHALL BE HEAVY-DUTY, QUICK-MAKE, QUICK-BREAK WITH COVER INTERLOCK, FUSIBLE OR NON-FUSIBLE, AND GROUNDING LUGS IN ENCLOSURE TO SUIT LOCATIONS AND REQUIREMENTS. G.E., SIEMENS, SQUARE D, CUTLER-HAMMER. 2.07FUSES A.TIME DELAY, REJECTION TYPE, HIGH CAPACITY OR CURRENT LIMITING AS SHOWN ON THE DRAWINGS. MANUFACTURERS SHALL BE BUSSMANN, LITTELFUSE OR GOULD SHAWMUT. 2.08STARTERS A.SINGLE PHASE MANUAL STARTERS SHALL BE “QUICK MAKE-QUICK BREAK” TOGGLE SWITCH. SINGLE OR DOUBLE POLE WITH A THERMAL OVERLOAD HEATER ELEMENT CAPABLE OF INTERRUPTING THE CIRCUIT IN CASE OF OVERLOAD. B.MAGNETIC CONTROLLERS SHALL BE FULL VOLTAGE, NON-REVERSING, ACROSS THE LINE STARTERS, WITH AMBIENT COMPENSATED INVERSE TIME-CURRENT CHARACTERISTIC AND NEMA ICS2, CLASS 2 TRIPPING CHARACTERISTIC. C.COMBINATION MAGNETIC CONTROLLER: FACTORY-ASSEMBLED COMBINATION CONTROLLER AND HEAVY DUTY DISCONNECT SWITCH. D.PROVIDE TWO NORMALLY OPEN AND TWO NORMALLY CLOSED AUXILIARY CONTACTS FOR EACH SINGLE SPEED MOTOR AND FOR EACH SPEED OF MULTI-SPEED MOTORS. E.ENCLOSURE SHALL BE NEMA 250, TYPE 1 FOR DRY INDOOR LOCATIONS, NEMA 250, TYPE 3R FOR OUTDOOR, NEMA 250, TYPE 4 FOR DAMP/WET LOCATIONS, AND NEMA 250, TYPE4X FOR KITCHENS. F.STARTERS WHICH ARE FURNISHED WITH CONTROL CIRCUITS SHALL HAVE INTEGRAL TRANSFORMER (WITH SUFFICIENT CAPACITY TO OPERATE CONNECTED DEVICES PLUS 100% SPARE CAPACITY) AND 120 VOLT CONTROL CIRCUIT. ALL STARTERS TO HAVE THERMAL OVERLOAD RELAYS SIZED FOR APPROXIMATELY 115% OF FULL LOAD MOTOR CURRENT. PART 3 - EXECUTION 3.01CONDUIT INSTALLATION A.ALL WIRING SHALL BE INSTALLED IN LISTED EMT RACEWAYS. B.MAKE CONDUIT BENDS WITH STANDARD CONDUIT ELBOWS OR CONDUIT BENT TO NOT LESS THAN THE SAME RADIUS. ALL BENDS SHALL BE FREE FROM DENTS OR FLATTENING. C.RUN CONCEALED CONDUITS IN A DIRECT LINE. RUN EXPOSED CONDUITS PARALLEL TO, OR AT RIGHT ANGLES WITH, LINES OF THE BUILDING. INSTALL ALL CONDUITS AT LEAST 6" AWAY FROM FLUES, STEAM AND HOT WATER PIPES. INSTALL HORIZONTAL RACEWAY RUNS ABOVE WATER AND STEAM PIPING. D.SEAL ALL CONDUIT PENETRATIONS OF FIRE RATED WALLS, FLOOR, OR CEILINGS WITH U.L. LISTED "DOW CORNING" #2000 OR #2001 FIRE STOP SEALANT OR EQUIVALENT. E.ALL EMPTY RACEWAY SYSTEMS SHALL HAVE A POLYPROPYLENE PULLWIRE OR EQUAL, AND SHALL BE IDENTIFIED AT ALL JUNCTION, PULL AND TERMINATION POINTS USING PERMANENT METALLIC TAGS. TAG SHALL INDICATE INTENDED USE OF CONDUIT, ORIGINATION, AND TERMINATION POINTS OF EACH INDIVIDUAL CONDUIT. F.CONDUITS PENETRATING THROUGH ROOF SHALL HAVE ROOF FLASHING WITH CAULK TYPE COUNTER FLASHING SLEEVE. INSTALLATION SHALL BE WATERTIGHT. ELECTRICAL SPECIFICATIONS: DPA Project: Sheet Number: COPYRIGHT 2013 - DAVIS PARTNERSHIP, P.C. Sheet Title: 2301 Blake Street, Suite 100 Denver, CO 80205 303.861.8555 0225 Main Street, Unit C101 Edwards, CO 81632 970.926.8960 Denver Vail Consultant Issue/RevisionsDateNo. Sheet Information Project Information Permit Set30 August 2013 MedicalCenter VailValley Vail, Colorado 81657 US Bank Building 108 South Frontage Road Suite 306 S: \ B G P r o j e c t s \ 8 7 3 9 . 3 9 V V M C C o n c i e r g e C l i n i c \ C a d \ B G C E C A D\ 8 7 3 9 3 9 E 1 1 . d w g P r i n t e d B y : c ad d - j a c A u g u s t 3 0 , 2 0 1 3 - 9 : 5 5 a m L C - J A C COPYRIGHT 2013 B ANZEG EAUDIN (970)949-6108 (303) 278-3820 (970) 221-5691 (505) 323-9070 Vail: Denver: Fort Collins: Albuquerque: www.bgce.com Multi-Specialty Clinic 13915.00.000 MARTIN MARTIN 0225 MAIN STREET; SUITE C101 EDWARDS, COLORADO 81632 970.581.2546 BEAUDIN GANZE CONSULTING ENGINEERS 222 CHAPEL PLACE, UNIT AC-201 P.O. BOX 9650 AVON, COLORADO 81620 970.949.6108 E1.1 ELECTRICAL SPECIFICATIONS Reviewed for Code Compliance Code: 2012 International Building Code (IBC) ELECTRICAL SPECIFICATIONS: 3.02WIRE INSTALLATION A.BRANCH CIRCUIT CONDUCTORS SHALL BE AS FOLLOWS: 1.FOR GENERAL APPLICATIONS THROUGH SIZE #8: THHN/THWN 75OC WIRE AND FULL SIZE GROUND, OR TYPE THHN 90OC. 2.BRANCH CIRCUIT CONDUCTORS THROUGH SIZE #10 TO BE SOLID, #8 AND LARGER STRANDED. 3.UNLESS INDICATED ON THE DRAWINGS, (THE MINIMUM) WIRE USED FOR BRANCH CIRCUITS SHALL BE #12 THWN PROTECTED BY 20 AMPERE CIRCUIT BREAKERS. B.THE DRAWINGS INDICATE THE GENERAL DIRECTION OF ROUTES OF BRANCH CIRCUIT HOME RUNS. CONTINUE ALL SUCH HOME RUNS TO PANELS AS THOUGH THE ROUTES WERE COMPLETELY INDICATED. 1.CONDUCTORS SHALL BE CONTINUOUS FROM OUTLET BOX TO OUTLET BOX, OR JUNCTION BOX, WITH NO SPLICES EXCEPT IN SUCH BOXES. 3.03WIRING DEVICE INSTALLATION A.REVIEW ARCHITECTURAL AND MECHANICAL DRAWINGS BEFORE INSTALLING OUTLETS. CHANGING OF OUTLETS TO CONFORM TO THESE DRAWINGS AND ANY OTHER SLIGHT CHANGE IN MOUNTING HEIGHT OR LOCATION OF OUTLETS REQUIRED SHALL BE CONSIDERED AS A PART OF THIS CONTRACT. USE OUTLET BOXES OF SUFFICIENT SIZE AND SHAPE TO BEST SUIT THE PARTICULAR LOCATION AND TO CONTAIN THE ENCLOSED WIRE AND CONNECTIONS WITHOUT CROWDING. SIZE ALL BOXES PER N.E.C. ARTICLE 370. B.SWITCH AND RECEPTACLE OUTLET BOXES SHALL BE STANDARD BOXES WITH COVER PLATES. WHERE MORE THAN ONE SWITCH OR DEVICE IS LOCATED AT ONE POINT, USE GANG BOXES AND GANG COVER PLATES. C.RECEPTACLES IN WET LOCATIONS SHALL BE INSTALLED WITH A HINGED OUTLET COVER/ENCLOSURE MARKED “SUITABLE FOR WET LOCATIONS WHILE IN USE” AND “UL LISTED”. THERE MUST BE A GASKET BETWEEN THE ENCLOSURE AND THE MOUNTING SURFACE, AND BETWEEN AND HINGED COVER AND MOUNTING PLATE/BASE TO ASSURE PROPER SEAL. TAYMAC; SPECIFICATION GRADE OR EQUIVALENT. D.FLUSH MOUNT LIGHTING SWITCHES 4'0" CENTERLINE ABOVE FINISHED FLOOR UNLESS OTHERWISE INDICATED. FLUSH MOUNT WALL TYPE RECEPTACLES AND OTHER WALL MOUNTED WIRING DEVICES AND OUTLETS 18 INCHES CENTERLINE ABOVE FINISHED FLOOR UNLESS OTHERWISE INDICATED. E.ROUTE DEDICATED NEUTRAL CONDUCTORS ON LINE AND LOAD SIDE OF DIMMERS PER MANUFACTURER'S INSTRUCTIONS. F.IDENTIFY PANELBOARD AND CIRCUIT NUMBER ON RECEPTACLES WITH HOT STAMPED OR ENGRAVED MACHINE PRINTED LABEL ON FACE OF PLATE. 3.04ELECTRICAL SUPPORTING DEVICES A.SUPPORT ALL PANELS, JUNCTION BOXES AND OTHER ELECTRICAL DEVICES IN A MANNER AS REQUIRED BY THE N.E.C. USE EXTRA BRACING, SUPPORTS, ETC. AS NECESSARY TO PROVIDE A PROPER AND SUBSTANTIAL BASE TO WHICH ALL ELECTRICAL EQUIPMENT IS ATTACHED. 3.05EQUIPMENT FURNISHED BY OTHERS AND/OR OWNER A.VERIFY EXACT LOCATION AND REQUIREMENTS OF EQUIPMENT TO BE FURNISHED BY OTHERS PRIOR TO ROUGH-IN. B.SEE DIVISION 15 DRAWINGS FOR LOCATION OF MECHANICAL EQUIPMENT. PROVIDE SERVICE TO, AND CONNECT EQUIPMENT AS REQUIRED. C.INSPECT OWNER FURNISHED EQUIPMENT FOR DAMAGE, DEFECTS, MISSING COMPONENTS, ETC. REPORT DEFICIENCIES TO THE OWNER IMMEDIATELY. DO NOT INSTALL OR CONNECT DEFICIENT EQUIPMENT. 3.06EQUIPMENT CONNECTIONS A.FINAL CONNECTIONS TO MOTORS, TRANSFORMERS AND OTHER VIBRATING EQUIPMENT SHALL BE WITH SEAL TITE FLEX AND APPROVED FITTINGS. DO NOT SECURE CONDUITS, DISCONNECTS, OR DEVICES TO DUCTWORK OR MECHANICAL EQUIPMENT. B.FINAL CONNECTIONS TO EQUIPMENT SHALL BE IN ACCORDANCE WITH MANUFACTURER'S APPROVED WIRING DIAGRAMS, DETAILS, AND INSTRUCTIONS. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE MATERIALS AND EQUIPMENT COMPATIBLE WITH EQUIPMENT ACTUALLY SUPPLIED. C.ELECTRICAL CONTRACTOR SHALL PROVIDE CONTROLS, INTERLOCKS, ACCESSORIES, ETC. IN MOTOR CONTROL STARTERS AS REQUIRED BY THE TEMPERATURE CONTROL CONTRACTOR. STARTERS SHALL CONTAIN 120V CONTROL TRANSFORMER, PILOT LIGHT, AND PUSHBUTTONS OR SELECTOR SWITCH AS REQUIRED, IN ADDITION TO OTHER ITEMS (AUXILIARY CONTACTS, DOOR SWITCHES, RELAYS, ETC.) REQUIRED. SUBMIT ELEMENTARY CONTROL DIAGRAMS. END OF SECTION 16100 SECTION 16400--SERVICE AND DISTRIBUTION PART 1 - GENERAL PART 2 - PRODUCTS 2.01LOAD CENTERS A.BOLT ON CIRCUIT BREAKER TYPE WITH HINGED DOOR, INDOOR CIRCUIT DIRECTORY. CIRCUIT BREAKERS TO MEET THE NON-INTERCHANGEABILITY REQUIREMENTS OF THE N.E.C. WHERE APPLICABLE; ALL BREAKERS 20 AMPERE SINGLE POLE UNLESS OTHERWISE NOTED; ALL MULTIPLE UNITS COMMON TRIP. MAINS WITH LUGS OR MAIN CIRCUIT BREAKERS AS SHOWN ON THE PANELBOARD SCHEDULES. ALL PANELS TO HAVE NEUTRAL AND GROUND BUS. GENERAL ELECTRIC, ITE, SQUARE D, CUTLER-HAMMER EQUIVALENT. B.MOLDED CASE CIRCUIT BREAKERS WITH SERIES-CONNECTED RATING TO MEET AVAILABLE FAULT CURRENTS. GFCI CIRCUIT BREAKERS SHALL BE SINGLE OR TWO POLE CONFIGURATIONS WITH 5OR 30 MA TRIP SENSITIVITY. PART 3 - EXECUTION 3.01MOUNTING A.INSTALL DISTRIBUTION EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATION, AND AS SHOWN ON THE DRAWINGS. B.INSTALL WALL-MOUNTED EQUIPMENT 5' 0" CENTERLINE ABOVE FINISHED FLOOR UNLESS OTHERWISE INDICATED. C.INSTALL TOP OF PANELBOARDS 6'6” ABOVE FINISHED FLOOR UNLESS OTHERWISE NOTED ON THE DRAWINGS. MOUNT PLUMB AND RIGID WITHOUT DISTORTION OF BOX. MOUNT RECESSED PANELBOARDS WITH FRONTS UNIFORMLY FLUSH WITH WALL FINISH. 3.02IDENTIFICATION A.IDENTIFY PANELBOARD NAME, VOLTAGE AND AMPACITY WITH ENGRAVED MACHINE PRINTED NAMEPLATE ON PANELBOARD MOUNTED WITH CORROSION RESISTANT SCREWS. B.CREATE A TYPEWRITTEN DIRECTORY SCHEDULE INDICATING INSTALLED CIRCUIT LOADS MOUNTED TO INSIDE DOOR COVER IN REMOVABLE TRANSPARENT POCKET. 3.03COMPATIBILITY A.THE CONTRACTOR IS RESPONSIBLE FOR ALL COORDINATION WITH THE UTILITY COMPANY FOR THIS PROJECT, TO INSURE THE INSTALLATION OF ELECTRICAL SERVICES SHALL BE COMPATIBLE WITH THE ENTIRE PROJECT, AND TO INSURE THAT ELECTRICAL SERVICE IS INSTALLED AT A TIME AS TO PROVIDE NECESSARY ELECTRICAL POWER AS REQUIRED TO THE COMPLETED PROJECT. SINGLE PHASE EQUIPMENT ON A THREE PHASE DISTRIBUTION SYSTEM SHALL BE CONNECTED TO INSURE AS NEAR A BALANCED SYSTEM LOAD AS POSSIBLE. END OF SECTION 16400 SECTION 16500--LIGHTING PART 1 - GENERAL 1.01PROVISIONS A.PROVIDE ALL INTERIOR AND EXTERIOR LIGHTING FIXTURES AS SHOWN ON THE PLANS AND HEREINAFTER SPECIFIED. ALL ITEMS SHALL BE PROVIDED TO MAKE A COMPLETE AND OPERABLE LIGHTING SYSTEM, INCLUDING LAMPS, BALLASTS, POLES, HANGERS, PAINTING, PLASTER FRAMES, ETC. B.FIXTURES SHALL BE AS SHOWN IN THE FIXTURE SCHEDULE. CATALOG NUMBERS SHOWN ARE THE LATEST AVAILABLE AT THE TIME OF DESIGN. IF DISCREPANCIES OCCUR BETWEEN DESCRIPTION AND CATALOG NUMBER, DESCRIPTION WILL TAKE PRECEDENCE. C.VERIFY TRIM, FINISH AND GENERAL DESCRIPTION OF ALL LIGHTING FIXTURES THROUGH SHOP DRAWING APPROVAL PRIOR TO PLACING ORDER FOR FIXTURES. MODIFY CATALOG NUMBERS ACCORDINGLY. PART 2 - PRODUCTS 2.01INCANDESCENT FIXTURES A.INCANDESCENT FIXTURES TO BE COMPLETE WITH LAMPS, AND ALL NECESSARY ACCESSORIES TO PROVIDE FOR THEIR INSTALLATION. PROVIDE NECESSARY BLOCKING OR OTHER PROTECTION TO MAINTAIN SEPARATION OF RECESSED FIXTURES FROM COMBUSTIBLE MATERIAL AND BUILDING INSULATION SYSTEM. ALL RECESSED FIXTURES TO HAVE THERMAL PROTECTION DEVICE. PROVIDE SLOPING CEILING ADAPTORS WHERE REQUIRED TO PLACE LAMP CENTER LINE BEAM CANDLEPOWER PERPENDICULAR TO THE WORKING PLANE. 2.02FLUORESCENT FIXTURES A.FLUORESCENT FIXTURES TO BE COMPLETE WITH LAMPS, AND ALL NECESSARY ACCESSORIES TO PROVIDE FOR THEIR COMPLETE INSTALLATION. BALLASTS TO BE HPF, CBM/ETL, AND U.L. LISTED, CLASS P. SURFACE FLUORESCENT FIXTURES TO BE MOUNTED ON LOW DENSITY COMBUSTIBLE CEILINGS TO HAVE A U.L. LISTING FOR SUCH MOUNTING. ALL LENSES TO BE ACRYLIC PRISMATIC PLASTIC TYPES OR AS SHOWN IN THE SCHEDULE. B.FLUORESCENT BALLASTS SHALL BE ELECTRONIC PROGRAMMED-START TYPE, SOUND RATING A, THD LESS THAN 10 PERCENT, BALLAST FACTOR OF .88 OR HIGHER AND POWER FACTOR OF 0.95 OR HIGHER. 2.03EMERGENCY OR NIGHT LIGHTING A.FIXTURES INDICATED AS BEING ON EMERGENCY, OR NIGHT LIGHT CIRCUITS SHALL BE PROVIDED WITH SELF-CONTAINED BATTERY POWERED INVERTER UNIT FOR DIRECT MOUNTING IN FIXTURE. PROVIDE UNIT WITH FULLY AUTOMATIC TWO RATE CHARGER, NICKEL CADMIUM BATTERY, AC "ON" PILOT LIGHT, AND TEST SWITCH. DESIGN AND WIRE UNIT TO AUTOMATICALLY TRANSFER TO BATTERY SUPPLY ON LOSS OF NORMAL AC POWER AND TO OPERATE 32 WATT T8 FLUORESCENT LAMP WITH MINIMUM OUTPUT OF 600 LUMENS FOR MINIMUM 1-1/2 HOURS. 2.04LAMPS A.LAMPS SHALL BE AS SHOWN IN THE FIXTURE SCHEDULE AS MANUFACTURED BY OSRAM-SYLVANIA, G.E., PHILLIPS, OR APPROVED EQUIVALENT. PART 3 - EXECUTION 3.01INSTALLATION A.INSTALL LIGHTING FIXTURES STRAIGHT AND TRUE WITH REFERENCE TO ADJACENT WALLS, AND SECURELY FASTEN TO AND SUPPORT BY STRUCTURAL MEMBERS OF THE BUILDING. REFER TO ARCHITECTURAL OR INTERIOR REFLECTED CEILING PLANS AND ELEVATIONS FOR EXACT LOCATION OF FIXTURES. B.PROVIDE PHOTOCONTROLS, TIME CLOCKS, CONTACTORS, RELAYS, ETC. TO CONTROL INTERIOR AND EXTERIOR FIXTURES. ALL ITEMS FOR LIGHTING CONTROLS THAT ARE TO BE MOUNTED OUTDOORS OR IN WET LOCATIONS SHALL BE INSTALLED IN WEATHERPROOF HOUSINGS. C.RECESSED LIGHT FIXTURES INSTALLED IN GYP. BOARD OR PLASTER CEILINGS SHALL HAVE PLASTER FRAMES INSTALLED PRIOR TO CEILING MATERIAL. D.MULTI-BALLASTED FLUORESCENT FIXTURES SHALL BE DUAL SWITCHED UNLESS NOTED OTHERWISE. E.FIXTURES RECESSED IN "T-BAR" CEILING SHALL BE SUPPORTED INDEPENDENTLY OF CEILING SYSTEM, WITH FOUR #12 HANGER WIRES UP TO STRUCTURE. SECURE HANGER WIRES TO CORNERS OF FIXTURE. CLIP FIXTURE TO GRID ON TWO SIDES WITH FACTORY-FURNISHED CLIPS. FINAL CONNECTION TO FIXTURE SHALL BE MADE WITH A FLEXIBLE U.L. APPROVED ASSEMBLY. END OF SECTION 16500 SECTION 16700--COMMUNICATION SYSTEMS PART 1 - GENERAL 1.01FIRE ALARM SYSTEM (DESIGN/BUILD) A.GENERAL 1.MODIFY EXISTING NOTIFIER PANEL (LOCATED IN MAIN ELECTRICAL ROOM) AND ANNUNCIATOR PANEL TO ACCOMMODATE NEW NOTIFICATION APPLIANCES. 2.THE SYSTEM SHALL COMPLY WITH THE APPLICABLE PROVISIONS OF THE NATIONAL FIRE PROTECTION ASSOCIATION, (NFPA), STANDARD 72, UNIFORM BUILDING CODE, UNIFORM FIRE CODE, NATIONAL ELECTRICAL CODE, AMERICANS WITH DISABILITIES ACT (ADA), NFPA 70 AND 90A. THE SYSTEM SHALL ALSO MEET ALL REQUIREMENTS OF THE FIRE MARSHALL OR BUILDING AUTHORITY HAVING JURISDICTION. ALL EQUIPMENT AND DEVICES SHALL BE LISTED BY THE UNDERWRITERS LABORATORIES, INC. FIRE ALARM PANEL SHALL BE UL LISTED AS AN ASSEMBLED UNIT. 3.PROVIDE SHOP DRAWINGS SHOWING EQUIPMENT AND DEVICE LOCATIONS AND CONNECTING WIRING OF ENTIRE FIRE ALARM SYSTEM. INCLUDE WIRING DIAGRAMS, PANEL LAYOUT DRAWINGS, AND DESCRIPTIVE LITERATURE OF ALL COMPONENTS. UPON COMPLETION OF PROJECT, PROVIDE TO THE OWNER AS BUILT SYSTEM PLANS AND 3 SETS OF SYSTEM OPERATION AND MAINTENANCE MANUALS. 4.TO ESTABLISH THE TYPE AND QUALITY OF SYSTEM DESIRED, THE FOLLOWING EQUIPMENT IS CONSIDERED EQUIVALENT: PYROTRONICS, SIMPLEX AND NOTIFIER. OTHER MANUFACTURER'S EQUIPMENT MAY BE CONSIDERED UPON PROPER SUBMITTAL PER SECTION 16010. B.QUALIFICATIONS OF INSTALLERS: THE ENTIRE FIRE ALARM SYSTEM SHALL BE FABRICATED, INSTALLED, AND TESTED BY A CONTRACTOR WITH FIVE YEARS MINIMUM EXPERIENCE SPECIALIZING IN SUCH SYSTEMS. IF REQUIRED WITHIN JURISDICTION OF PROJECT, CONTRACTOR SHALL BE A LICENSED SPECIALIST. C.SUBMITTALS: 1.SHOP DRAWINGS: BEFORE ANY FIRE ALARM SYSTEM MATERIALS ARE DELIVERED TO THE JOB SITE, SUBMIT COMPLETE SHOP DRAWINGS TO THE ARCHITECT IN ACCORDANCE WITH THE PROVISIONS OF THESE SPECIFICATIONS. a.PRIOR TO SUBMITTAL FOR ARCHITECT'S REVIEW, SECURE APPROVAL AND STAMP OF ACCEPTANCE OF THE FIRE MARSHALL/DISTRICT HAVING JURISDICTION. b.UPON REQUEST, THE ARCHITECT WITH FURNISH WITHOUT CHARGE TO THE CONTRACTOR ONE SET OF REPRODUCIBLE TRANSPARENCIES OF THOSE DRAWINGS INCLUDED IN THE CONTRACTOR DOCUMENTS WHICH MAY BE SUITABLE FOR USE IN PREPARATION OF SHOP DRAWINGS. c.SHOP DRAWINGS SHALL INCLUDE: 1)LAYOUT DRAWING OF THE COMPLETE FIRE ALARM SYSTEM INDICATING RELATIONSHIP OF ALL OTHER OVERHEAD ITEMS INCLUDING CEILING AIR DIFFUSERS, LIGHTING FIXTURES, AND ALL OTHER ITEMS. 2)COMPLETE DETAILS AND SECTIONS AS REQUIRED TO CLEARLY DEFINE AND CLARIFY THE DESIGN, INCLUDING A MATERIALS LIST DESCRIBING ALL PROPOSED MATERIALS BY MANUFACTURER'S NAME AND CATALOG NUMBER. 3)AS-BUILT DRAWINGS: DURING PROGRESS OF THE WORK, MAINTAIN AN ACCURATE RECORD OF ALL CHANGES MADE IN THE FIRE SPRINKLER SYSTEM INSTALLATION FROM THE LAYOUT AND MATERIALS SHOWN ON THE REVIEWED SHOP DRAWINGS. 4)MANUAL: UPON COMPLETION OF THIS PORTION OF THE WORK, AND AS A CONDITION OF ITS ACCEPTANCE, DELIVER TO THE ARCHITECT A COPY OF A MANUAL COMPLIED IN ACCORDANCE WITH THE PROVISIONS OF SECTIONS 16010 AND 16100 OF THESE SPECIFICATIONS; INCLUDE A COPY OF THE AS-BUILT DRAWINGS. END OF SECTION 16700 END OF DIVISION DPA Project: Sheet Number: COPYRIGHT 2013 - DAVIS PARTNERSHIP, P.C. Sheet Title: 2301 Blake Street, Suite 100 Denver, CO 80205 303.861.8555 0225 Main Street, Unit C101 Edwards, CO 81632 970.926.8960 Denver Vail Consultant Issue/RevisionsDateNo. Sheet Information Project Information Permit Set30 August 2013 MedicalCenter VailValley Vail, Colorado 81657 US Bank Building 108 South Frontage Road Suite 306 S: \ B G P r o j e c t s \ 8 7 3 9 . 3 9 V V M C C o n c i e r g e C l i n i c \ C a d \ B G C E C A D\ 8 7 3 9 3 9 E 1 2 . d w g P r i n t e d B y : c ad d - j a c A u g u s t 3 0 , 2 0 1 3 - 9 : 5 5 a m L C - J A C COPYRIGHT 2013 B ANZEG EAUDIN (970)949-6108 (303) 278-3820 (970) 221-5691 (505) 323-9070 Vail: Denver: Fort Collins: Albuquerque: www.bgce.com Multi-Specialty Clinic 13915.00.000 MARTIN MARTIN 0225 MAIN STREET; SUITE C101 EDWARDS, COLORADO 81632 970.581.2546 BEAUDIN GANZE CONSULTING ENGINEERS 222 CHAPEL PLACE, UNIT AC-201 P.O. BOX 9650 AVON, COLORADO 81620 970.949.6108 E1.2 ELECTRICAL SPECIFICATIONS Reviewed for Code Compliance Code: 2012 International Building Code (IBC) SCALE: SS S S S S S S S S 1.ALL ITEMS INDICATED ON THIS DRAWING ARE TO BE REMOVED UNLESS NOTED OTHERWISE. 2.FOR ALL ITEMS TO BE DEMOLISHED REMOVE CIRCUIT BACK TO POINT OF CONNECTION. MAKE BRANCH CIRCUIT WITH REMAINING DEVICES CONTINUOUS. 3.ELECTRICAL CONTRACTOR SHALL REMOVE ALL DEMOLISHED ITEMS FROM SITE UNLESS OWNER WISHES TO RETAIN. ITEMS REMOVED FROM SITE SHALL BE DISPOSED OF IN A LEGAL MANNER. 4.EVERY ATTEMPT WAS MADE TO LOCATE ALL ITEMS TO BE INCLUDED IN THE DEMOLITION SCOPE IN THIS OCCUPIED SPACE. ELECTRICAL CONTRACTOR SHALL PROVIDE A REASONABLE ALLOWANCE TO INCLUDE THE REMOVAL OF ITEMS NOT INDICATED ON THE ELECTRICAL DEMOLITION PLAN DEMOLITION NOTES: DISCONNECT ROOF TOP UNIT ON ROOF. DEMOLITION FLAG NOTES: 1 ELECTRICAL DEMOLITION PLAN - 3rd FLOOR 1/8" = 1'-0" SS SD SS RTU 1 S SS SD SD SD SS SS DPA Project: Sheet Number: COPYRIGHT 2013 - DAVIS PARTNERSHIP, P.C. Sheet Title: 2301 Blake Street, Suite 100 Denver, CO 80205 303.861.8555 0225 Main Street, Unit C101 Edwards, CO 81632 970.926.8960 Denver Vail Consultant Issue/RevisionsDateNo. Sheet Information Project Information Permit Set30 August 2013 MedicalCenter VailValley Vail, Colorado 81657 US Bank Building 108 South Frontage Road Suite 306 S: \ B G P r o j e c t s \ 8 7 3 9 . 3 9 V V M C C o n c i e r g e C l i n i c \ C a d \ B G C E C A D\ 8 7 3 9 3 9 E D 2 1 . d w g P r i n t e d B y : c ad d - j a c A u g u s t 3 0 , 2 0 1 3 - 9 : 5 5 a m L C - J A C COPYRIGHT 2013 B ANZEG EAUDIN (970)949-6108 (303) 278-3820 (970) 221-5691 (505) 323-9070 Vail: Denver: Fort Collins: Albuquerque: www.bgce.com Multi-Specialty Clinic 13915.00.000 MARTIN MARTIN 0225 MAIN STREET; SUITE C101 EDWARDS, COLORADO 81632 970.581.2546 BEAUDIN GANZE CONSULTING ENGINEERS 222 CHAPEL PLACE, UNIT AC-201 P.O. BOX 9650 AVON, COLORADO 81620 970.949.6108 ED2.1 ELECTRICAL DEMOLITION PLAN - 3rd FLOOR Reviewed for Code Compliance Code: 2012 International Building Code (IBC) SCALE: THE PURPOSE OF THIS SHEET IS TO INDICATE THE APPROXIMATE LOCATION OF THE EXISTING BUILDING ELECTRICAL DISTRIBUTION EQUIPMENT FOR BIDDING PURPOSES. THE FLOOR PLAN LAYOUT IS NOT CORRECT SINCE THIS DRAWING USED THE 1ST FLOOR PLAN TO CREATE SINCE A GARAGE LEVEL PLAN WAS NOT AVAILABLE. GENERAL NOTES: 1. ELECTRICAL PLAN - GARAGE LEVEL 1/8" = 1'-0" FA C P EXISTING "MDP" EXISTING "MMC-3" EXISTING "MMC-2" T EXISTING 500 KVA PAD MOUNTED UTILITY TRANSFORMER EXISTING FIRE ALARM PANEL DPA Project: Sheet Number: COPYRIGHT 2013 - DAVIS PARTNERSHIP, P.C. Sheet Title: 2301 Blake Street, Suite 100 Denver, CO 80205 303.861.8555 0225 Main Street, Unit C101 Edwards, CO 81632 970.926.8960 Denver Vail Consultant Issue/RevisionsDateNo. Sheet Information Project Information Permit Set30 August 2013 MedicalCenter VailValley Vail, Colorado 81657 US Bank Building 108 South Frontage Road Suite 306 S: \ B G P r o j e c t s \ 8 7 3 9 . 3 9 V V M C C o n c i e r g e C l i n i c \ C a d \ B G C E C A D\ 8 7 3 9 3 9 E 2 0 . d w g P r i n t e d B y : c ad d - j a c A u g u s t 3 0 , 2 0 1 3 - 9 : 5 6 a m L C - J A C COPYRIGHT 2013 B ANZEG EAUDIN (970)949-6108 (303) 278-3820 (970) 221-5691 (505) 323-9070 Vail: Denver: Fort Collins: Albuquerque: www.bgce.com Multi-Specialty Clinic 13915.00.000 MARTIN MARTIN 0225 MAIN STREET; SUITE C101 EDWARDS, COLORADO 81632 970.581.2546 BEAUDIN GANZE CONSULTING ENGINEERS 222 CHAPEL PLACE, UNIT AC-201 P.O. BOX 9650 AVON, COLORADO 81620 970.949.6108 E2.0 ELECTRICAL PLAN - GARAGE LEVEL Reviewed for Code Compliance Code: 2012 International Building Code (IBC) COPIER SCALE: F1 EXISTING EXIT SIGN TO REMAIN.1 FLAG NOTES: 1 ELECTRICAL LIGHTING PLAN - 3rd FLOOR 1/8" = 1'-0" 1.CIRCUIT ALL EXIT SIGNS AND BATTERY PACKS TO LIGHTING BRANCH CIRCUIT SERVING AREA AHEAD OF SWITCHING AND LIGHTING CONTROL FUNCTION. 2.THE NUMBERS NEXT TO ELECTRICAL DEVICES INDICATE THE CIRCUIT POSITION THAT THE BRANCH CIRCUIT SHALL OCCUPY IN PANEL "3D" UNLESS NOTED OTHERWISE. NOTES: EXISTING LOAD CENTER "3C" EXISTING LOAD CENTER "3B" EXISTING LOAD CENTER "3A" REPLACEMENT LOAD CENTER "3D" EXISTING HOUSE LOAD CENTER EXISTING LOAD CENTER "3E" F1 F1 F2 F2F2 F2 F1 F2 SSS F1 F1 F7 SSS F2 F1F1 SS F9 F3 SS SO F4 F3 F4 SS F1 SS F1F1F1F1F1F1F1 S3 SS F1 F1 F1F1 F3 F4 F3 F6 F10 I1 I1F10 I1 I1 F10F8 b b b b aa a aa a a c c a c c S3 S3 a b OC OC X1 X1 X1 a F8 SO F10 I2 a F5b SSSSSS F10 F10 F10F10 F10F10 F10 F10 a F11 F11 F11 F11 a a a a S3c S3 SS F3 SO F4 F3 b X1 b b F3 b SS F2 F2 F2 F2 F2 F1 F1 S F9 S F9 F9X1 S1 bb b bb b b OC OC OC OC 59 57,59 55,57,59 61 OC OC OC OC OC OC OC OC OC OC OC S3 S3 c b S3a DPA Project: Sheet Number: COPYRIGHT 2013 - DAVIS PARTNERSHIP, P.C. Sheet Title: 2301 Blake Street, Suite 100 Denver, CO 80205 303.861.8555 0225 Main Street, Unit C101 Edwards, CO 81632 970.926.8960 Denver Vail Consultant Issue/RevisionsDateNo. Sheet Information Project Information Permit Set30 August 2013 MedicalCenter VailValley Vail, Colorado 81657 US Bank Building 108 South Frontage Road Suite 306 S: \ B G P r o j e c t s \ 8 7 3 9 . 3 9 V V M C C o n c i e r g e C l i n i c \ C a d \ B G C E C A D\ 8 7 3 9 3 9 E 2 1 . d w g P r i n t e d B y : c ad d - j a c A u g u s t 3 0 , 2 0 1 3 - 9 : 5 6 a m L C - J A C COPYRIGHT 2013 B ANZEG EAUDIN (970)949-6108 (303) 278-3820 (970) 221-5691 (505) 323-9070 Vail: Denver: Fort Collins: Albuquerque: www.bgce.com Multi-Specialty Clinic 13915.00.000 MARTIN MARTIN 0225 MAIN STREET; SUITE C101 EDWARDS, COLORADO 81632 970.581.2546 BEAUDIN GANZE CONSULTING ENGINEERS 222 CHAPEL PLACE, UNIT AC-201 P.O. BOX 9650 AVON, COLORADO 81620 970.949.6108 E2.1 ELECTRICAL LIGHTING PLAN - 3rd FLOOR Reviewed for Code Compliance Code: 2012 International Building Code (IBC) COPIER SCALE: ELECTRICAL POWER PLAN - 3rd FLOOR 1/8" = 1'-0" F H F H H EXISTING FIRE ALARM PULL STATION TO REMAIN. EXISTING FIRE ALARM NOTIFICATION APPLIANCE TO REMAIN. EXISTING TELEPHONE BOARD TO REMAIN. 1 FLAG NOTES: 2 2 2 1 2 1 3 3 1.FOR EACH COMMUNICATION DEVICE INDICATED PROVIDE RECESSED JUNCTION BOX WITH A SINGLE GANG MUD RING. FROM RECESSED JUNCTION BOX ROUTE ONE 1" EMT CONDUIT TO ABOVE ACCESSIBLE CEILING WITH BUSHING ON EXPOSED END OF CONDUIT AND GRADUAL SWEEP ELBOWS. 2.THE NUMBERS NEXT TO ELECTRICAL DEVICES INDICATE THE CIRCUIT POSITION THAT THE BRANCH CIRCUIT SHALL OCCUPY IN PANEL "3D" UNLESS NOTED OTHERWISE. NOTES: EXISTING LOAD CENTER "3C" EXISTING LOAD CENTER "3B" EXISTING LOAD CENTER "3A" REPLACEMENT LOAD CENTER "3D" EXISTING HOUSE LOAD CENTER EXISTING LOAD CENTER "3E" +48" COFFEE UNDERCOUNTER REFRIGERATOR COPIER C C TV +66" C C C C C CC CC C C C +48" +52"C C +48" +52" +48" +52" C C C C +48" C C +48" +52" +48" C 32 C +48" +48" C C C +48" H H +48" 15 15 15 15 17 17 17 17 19 19 19 19 21 21 21 21 21 23 23 23 25 25 25 27 27 29 29 29 29 31 31 31 33 33 33 3333 35 35 35 3535 35 35 37 3939 41 45 4343 47 49 51 51 53 51 C 20 2224 24 24 24 2424 24 24 26 28 30 32 C 26 WH 1 22 DPA Project: Sheet Number: COPYRIGHT 2013 - DAVIS PARTNERSHIP, P.C. Sheet Title: 2301 Blake Street, Suite 100 Denver, CO 80205 303.861.8555 0225 Main Street, Unit C101 Edwards, CO 81632 970.926.8960 Denver Vail Consultant Issue/RevisionsDateNo. Sheet Information Project Information Permit Set30 August 2013 MedicalCenter VailValley Vail, Colorado 81657 US Bank Building 108 South Frontage Road Suite 306 S: \ B G P r o j e c t s \ 8 7 3 9 . 3 9 V V M C C o n c i e r g e C l i n i c \ C a d \ B G C E C A D\ 8 7 3 9 3 9 E 2 2 . d w g P r i n t e d B y : c ad d - j a c A u g u s t 3 0 , 2 0 1 3 - 9 : 5 6 a m L C - J A C COPYRIGHT 2013 B ANZEG EAUDIN (970)949-6108 (303) 278-3820 (970) 221-5691 (505) 323-9070 Vail: Denver: Fort Collins: Albuquerque: www.bgce.com Multi-Specialty Clinic 13915.00.000 MARTIN MARTIN 0225 MAIN STREET; SUITE C101 EDWARDS, COLORADO 81632 970.581.2546 BEAUDIN GANZE CONSULTING ENGINEERS 222 CHAPEL PLACE, UNIT AC-201 P.O. BOX 9650 AVON, COLORADO 81620 970.949.6108 E2.2 ELECTRICAL POWER PLAN - 3rd FLOOR Reviewed for Code Compliance Code: 2012 International Building Code (IBC) SCALE: ELECTRICAL ROOF PLAN 1/8" = 1'-0" RTU 1 EF 1 +30",WP 3D-17 DD DPA Project: Sheet Number: COPYRIGHT 2013 - DAVIS PARTNERSHIP, P.C. Sheet Title: 2301 Blake Street, Suite 100 Denver, CO 80205 303.861.8555 0225 Main Street, Unit C101 Edwards, CO 81632 970.926.8960 Denver Vail Consultant Issue/RevisionsDateNo. Sheet Information Project Information Permit Set30 August 2013 MedicalCenter VailValley Vail, Colorado 81657 US Bank Building 108 South Frontage Road Suite 306 S: \ B G P r o j e c t s \ 8 7 3 9 . 3 9 V V M C C o n c i e r g e C l i n i c \ C a d \ B G C E C A D\ 8 7 3 9 3 9 E 2 3 . d w g P r i n t e d B y : c ad d - j a c A u g u s t 3 0 , 2 0 1 3 - 9 : 5 6 a m L C - J A C COPYRIGHT 2013 B ANZEG EAUDIN (970)949-6108 (303) 278-3820 (970) 221-5691 (505) 323-9070 Vail: Denver: Fort Collins: Albuquerque: www.bgce.com Multi-Specialty Clinic 13915.00.000 MARTIN MARTIN 0225 MAIN STREET; SUITE C101 EDWARDS, COLORADO 81632 970.581.2546 BEAUDIN GANZE CONSULTING ENGINEERS 222 CHAPEL PLACE, UNIT AC-201 P.O. BOX 9650 AVON, COLORADO 81620 970.949.6108 E2.3 ELECTRICAL PLAN - ROOF Reviewed for Code Compliance Code: 2012 International Building Code (IBC) PARTIAL BUILDING ELECTRICAL ONE LINE DIAGRAM NONESCALE: M #76770 125A2P M SPACE M #83944 150A2P M 100A2P #71820 M #83834 150A2P M 100A2P #84017 M 100A2P #83890 M #76973 125A2P M SPACE M #83967 150A2P M 150A2P #83891 M #75896 150A2P M 100A2P #83892 M 100A2P #83973 NEW LOAD 3D 600 AS 800 AS 400 AS 400 AS 60 AS 200 AS EXIST PANEL MEP ELEV 1 AHU 1 EXIST 2ND FL00R HOUSE PANEL AC 2 AC 1 600 AS EXISTING HOLY CROSS ENERGY 500 KVA, 208/120-VOLT, 3-PHASE, 4-WIRE PAD MOUNTED TRANSFORMER EXISTING SECTION #1 2000 AMPS 208/120 VOLT, 3-PHASE, 4-WIRE EXISTING SECTION #2 800 AMPS 208/120 VOLT 3-PHASE, 4-WIRE EXISTING SECTION #3 800 AMPS 208/120 VOLT 3-PHASE, 4-WIRE 600 AF (JJN) 2 SETS OF 4#500 KCMIL AL IN WIREWAY M X F0 EXIST BANK PANEL EXIST BANK PANEL EXISTING BANK SERVICE DISCONNECT SWITCHES IN MAIN ELECTRICAL ROOM EXISTING BANK CT CABINET IN MAIN ELECTRICAL ROOMEXISTING METER #95228 M EXISTING METER #95651 1.ITEMS IN LIGHT LINE WEIGHT ARE EXISTING TO REMAIN. ITEMS IN BOLD LINE WEIGHT ARE NEW. 2.EXISTING INFORMATION OBTAINED FROM "RECORD DRAWINGS" AND SURVEY INFORMATION AND IS BELIEVED TO BE CORRECT. IF FOUND TO BE INCORRECT NOTIFY ENGINEER IMMEDIATELY. NOTES: EXISTING 6 SETS OF (3#500 KCMIL+1#250G)3"C. X F1 600A, 208/120 VOLT, 3 PHASE, 4 WIRE, 10,000 A.I.C. 600A, 208/120 VOLT, 3 PHASE, 4 WIRE, 10,000 A.I.C. 2000A, 208/120 VOLT, 3 PHASE, 4 WIRE, ELECTRICAL CONTRACTOR SHALL CONFIRM THAT 800 AMP FUSES ARE CURRENTLY INSTALLED IN THIS FUSIBLE SWITCH. NOTIFY ENGINEER IF THIS SWITCH IS NOT PROVIDED WITH 800 AMP FUSES. DISCONNECT AND REMOVE CONDUIT FROM EXISTING MODULAR METER #3 (MMC-3) TO CEILING OF ELECTRICAL ROOM. EXTEND REMAINING 2" CONDUIT TO MDP SECTION #3. REMOVE FEEDER IN ENTIRE LENGTH OF EXISTING CONDUIT UP TO PANEL "3D" AND REPLACE WITH (4#3/0+1#6G-THHN/THWN INSULATION TYPE) FROM PANEL "3D" TO NEW CIRCUIT BREAKER IN MDP SECTION #3. REMOVE EXISTING WESTINGHOUSE SINGLE FUSIBLE SWITCH AND REPLACE WITH TWO CUTLER HAMMER # HFD3200. TERMINATE EXISTING CONDUCTORS SERVING 2ND FLOOR HOUSE PANEL ONTO NEW CIRCUIT BREAKER. PROVIDE REQUIRED FILLER PLATED IN MDP SECTION #3 TO COMPLETELY COVER THE BUS OF MDP SECTION #3. PROVIDE NEW 600 AMP JJN FUSES AND REQUIRED FUSE HOLDER IN EXISTING FUSIBLE SWITCH. THIS IS BEING DONE TO REDUCE THE AVAILABLE FAULT CURRENT AT "MMC-2" AND "MMC-3" FROM ITS CURRENT SITUATION. 1 FLAG NOTES: 1 200 AF 200 AF 200 AS J 2 2 XF2 X F3 X F4 3 3 4 4 4 600 AS 600 AF (JJN)200 AT200 AT CENTER EXIST LOAD 3E CENTER EXIST LOAD HHPT CENTER EXIST LOAD 3B CENTER EXIST LOAD 3C CENTER EXIST LOAD 3A CENTER EXIST LOAD 2D CENTER EXIST LOAD 2B CENTER EXIST LOAD 2C CENTER EXIST LOAD 1B CENTER EXIST LOAD 2E CENTER EXIST LOAD 2A CENTER DPA Project: Sheet Number: COPYRIGHT 2013 - DAVIS PARTNERSHIP, P.C. Sheet Title: 2301 Blake Street, Suite 100 Denver, CO 80205 303.861.8555 0225 Main Street, Unit C101 Edwards, CO 81632 970.926.8960 Denver Vail Consultant Issue/RevisionsDateNo. Sheet Information Project Information Permit Set30 August 2013 MedicalCenter VailValley Vail, Colorado 81657 US Bank Building 108 South Frontage Road Suite 306 S: \ B G P r o j e c t s \ 8 7 3 9 . 3 9 V V M C C o n c i e r g e C l i n i c \ C a d \ B G C E C A D\ 8 7 3 9 3 9 E 3 1 . d w g P r i n t e d B y : c ad d - j a c A u g u s t 3 0 , 2 0 1 3 - 9 : 5 6 a m L C - J A C COPYRIGHT 2013 B ANZEG EAUDIN (970)949-6108 (303) 278-3820 (970) 221-5691 (505) 323-9070 Vail: Denver: Fort Collins: Albuquerque: www.bgce.com Multi-Specialty Clinic 13915.00.000 MARTIN MARTIN 0225 MAIN STREET; SUITE C101 EDWARDS, COLORADO 81632 970.581.2546 BEAUDIN GANZE CONSULTING ENGINEERS 222 CHAPEL PLACE, UNIT AC-201 P.O. BOX 9650 AVON, COLORADO 81620 970.949.6108 E3.1 ELECTRICAL ONE-LINE DIAGRAM Reviewed for Code Compliance Code: 2012 International Building Code (IBC) EXISTING BUILDING ELECTRICAL SERVICE IS A 2000 AMP (SECTION #1) , 208/120 VOLT, 3-PHASE, 4-WIRE- BUILDING LOAD SUMMARY EXISTING MODULAR METER CENTER IS AN EXISTING 3-PHASE AND SINGLE PHASE OUT MODULAR METER - LOAD ON MMC-2 CENTER RATED AT 600 AMPS. THE EXISTING MODULAR METER CENTER HAS THREE 100A2P, ONE 125A2P AND TWO 150A2P FEEDS TO - THIRD FLOOR TENANT. -MAXIMUM POSSIBLE LOAD ON THIS MODULAR METER CENTER WOULD BE 420 AMPS AT 208 VOLT, 3-PHASE. EXISTING MODULAR METER CENTER IS AN EXISTING 3-PHASE AND SINGLE PHASE OUT MODULAR METER - LOAD ON MMC-3 CENTER RATED AT 600 AMPS. THE EXISTING MODULAR METER CENTER HAS TWO 100A2P, ONE 125A2P AND THREE 150A2P FEEDS TO - THIRD FLOOR TENANT. ONE OF THE 150A2P TENANT FEEDS (PANEL 3D) WILL BE REMOVED AS PART OF THIS PROJECT AND- RELOCATED TO MDP SECTION #3. MAXIMUM POSSIBLE LOAD ON THIS MODULAR METER CENTER WOULD BE 303 AMPS AT 208 VOLT, 3-PHASE.- SERVICE WITH A 800 AMP SUBFED SECTION #3. PEAK DEMAND ON SECTION #3 PER HOLY CROSS ENERGY (METER #95651 WAS 126.1 KW)- SERVICE WITH A 800 AMP SUBFED SECTION #3. 126.1 KW x 125% (PER NEC) = 157.6 KW - (157.6 KW x 1000) / 360 = 437.8 AMPS- 800 AMPS (SUBFED SECTION #3 CAPACITY) - 437.8 AMPS (EXISTING PEAK DEMAND ON THIS SECTION) = 362.1 AMPS- OF SPARE CAPACITY ON THIS SECTION OF THE ELECTRICAL SERVICE. SECTION #1 OF THE ELECTRICAL SERVICE IS RATED FOR 2000 AMPS, 208/120 VOLT, 3-PHASE.- EXISTING LOAD ON THIS SECTION IS 303 AMPS (MMC-3) + 420 AMPS (MMC-2) +437.8 AMPS ( 800 AMP SUBFED SECTION)- + 64.2 AMPS (METER #95228) + 107.4 AMPS (LOAD ADDED TO LOAD CENTER 3D AS A RESULT OF THIS PROJECT) = 1332 AMPS EXISTING LOAD CENTER IS BEING CHANGED FROM SINGLE PHASE TO 3-PHASE TO SUPPORT THIS PROJECT.- LOAD CENTER 3D LOAD SUMMARY 48,400 WATTS (LOAD ADDED TO LOAD CENTER AS A RESULT OF THIS ) - 9,721 WATTS (LOAD REMOVED FROM - LOAD CENTER AS A RESULT OF THIS PROJECT = 38,679 WATTS OF LOAD ADDED TO THIS LOAD CENTER AS A RESULT OF THIS PROJECT. LOAD REMOVED FROM LOAD CENTER AS A RESULT OF THIS PROJECT:- (24) 2'x4', 3-LAMP FIXTURES AT 96 WATTS EACH (1) FLUORESCENT OVER THE DOOR FIXTURE AT 34 WATTS EACH TOTAL LOAD REMOVED AS A RESULT OF THIS PROJECT: LOAD ADDED TO LOAD CENTER AS A RESULT OF THIS PROJECT WAS 48,400 WATTS.- (8) 2'x2', 3-LAMP FIXTURES AT 51 WATTS EACH (9) MR-16 DOWNLIGHTS AT 75 WATTS EACH (35) RECEPTACLES AT 180 WATTS EACH = 2,304 WATTS = 34 WATTS = 408 WATTS = 675 WATTS = 6,300 WATTS = 9,721 WATTS 38,679 WATTS / 360 VOLTS = 107.4 AMPS OF ADDED LOAD TO LOAD CENTER AS A RESULT OF THIS PROJECT.- 2000 AMPS (SERVICE CAPACITY) - 1332 AMPS (MAXIMUM POSSIBLE LOAD ON ELECTRICAL SERVICE AND LOAD ADDED - TO ELECTRICAL SERVICE AS A RESULT OF THIS PROJECT) = 667 AMPS OF MINIMUM SPARE CAPACITY ON EXISTING ELECTRICAL SERVICE. SHORT CIRCUIT CALCULATIONS SUMMARY PO I N T EQUIP.LENGTHVOLTWIRE SIZE CONDUCTOR MATERIAL CONDUIT VOLTAGE CLASS (V) # OF CABLES (S or T) C VALUE * # OF PARALLEL RUNS Isc AVAILABLE UPSTREAM f *M *Isc (FAULT) * LET THRU (AIC)PO I N T F1 MDP20208500CN600S 26,706 6 99,500 0190,174 11000 F1 F2 MMC-318208500AS600S 18,755 2 90,174 0166,288 N/A F2 F3 MMC-220208500 A S600S 18,755 2 66,288 0 1 51,215 N/A F3 F4 LOAD CENTER 3D802083XCS600S 12,843 1 90,174 5015,883 N/A F4 * AUTOMATICALLY CALCULATED UTILITY TRANSFORMER SIZE:500 KVA MAXIMUM AVAILABLE (SYMMETRICAL) FAULT AT THE SECONDARY:99500AMPS MECHANICAL EQUIPMENT SCHEDULE MARKDESCRIPTION VOLT / PHASE HPWATTSFLAMCASTARTERDISCONNECT/ FUSE SIZEFEEDERCIRCUITSPECIFIC NOTES RTU-1ROOF TOP UNIT #1208/3N/A 16092 WATTS 44.749.6N/A 60A3P, NON FUSED DISCONNECT SWITCH (NEMA 3R)(3#6+1#10G)1"C.3D-80,82,84 EF-1EXHAUST FAN #1208/33/4 HP 1332 WATTS 3.74.6 #00 STARTER IN NEMA 3R ENCLOSURE 30A3P NON FUSED DISCONNECT SWITCH (NEMA 3R)(3#12+1#12G)3/4"C.3D-68,70,72 P-1RECIRCULATION PUMP #1 120/1N/A 125 WATTS 1.01.3 #00 STARTER IN NEMA 1 ENCLOSURE 20A1P MOTOR RATED SWITCH (NEMA 1)(2#12+1#12G)3/4"C.3D-66 WH-1ELECTRIC WATER HEATER #1208/3 6000 WATTS 16.620.8 N/A 30A3P /25 AMP (NEMA 1)(4#10+1#10G)3/4"C.3D-74,76,78 GENERAL NOTES: A. SPECIFIC NOTES: (1) WITH THE TRANSFER OF LOAD CENTER 3D TO THIS ELECTRICAL DISTRIBUTION SECTION A LOAD OF 173 AMPS WILL BE- ADDED TO THIS ELECTRICAL DISTRIBUTION SECTION. 362.1 AMPS (SPARE CAPACITY ON SUBFED SECTION #3) - 173 AMPS (LOAD ADDED TO SUBFED SECTION #3 AS A RESULT OF - TRANSFERRING OF LOAD CENTER "3D" TO THIS SUBFED SECTION #3) = 189.1 AMPS OF REMAINING SPARE CAPACITY ON SUBFED SECTION #3. LUMINAIRE SCHEDULE TYPEDESCRIPTIONMOUNTING RECESS DEPTH LAMPS INPUT WATTSVOLTMANUFACTURERCATALOG NUMBER SPECIFIC NOTESQTYTYPE F1 RECESSED MOUNTED INDIRECT FIXTURE WITH T5 LAMPS AND STEPPED DIMMING RECESSED3-1/4"228 WATT T560MVOLTCOOPER2AC-228T5-UNV-EBT1NDIM#2 F2 4'-0" SURFACE MOUNTED UNDERCOUNTER LIGHT FIXTURE WITH SOLID FRONT SURFACEN/A213 WATT T530120METALUXSFCL-213T5-EB-120V#2 F3 SAME AS FIXTURE TYPE "F1" EXCEPT WITHOUT STEPPED DIMMING RECESSED3-1/4"228 WATT T560MVOLTCOOPER2AC-228T5-UNV-EBT1#2 F4 SAME AS FIXTURE TYPE "F3" EXCEPT WITH INTEGRAL BATTERY PACK RECESSED3-1/4"228 WATT T560MVOLTCOOPER2AC-228T5-UNV-EL8-EBT1#2 F5SAME AS FIXTURE TYPE "F3" EXCEPT IN 2'x2' SIZERECESSED3-1/4"214 WATT T528MVOLTCOOPER2AC-214T5-UNV-EBT1#2 F6 SAME AS FIXTURE TYPE "F5" EXCEPT WITH INTEGRAL BATTERY PACK RECESSED3-1/4"2 14 WATT T528 MVOLTCOOPER2AC-214T5-UNV-EL8-EBT1#2 F7SAME AS FIXTURE TYPE "F1" EXCEPT IN 2'x2' SIZERECESSED3-1/4"214 WATT T528MVOLTCOOPER2AC-214T5-UNV-EBT1NDIM#2 F8WALL MOUNTED ABOVE VANITY WALL SCONCESURFACEN/A214 WATT T528120SHAPER605-25-W-T5/2/14-120V-NA#2 F9PROCEDURE ROOM DIRECT FIXTURE WITH ACRYLIC LENS.RECESSED4-1/2"228 WATT T556MVOLTFAIL-SAFEMOR-G-228-UNV-EB52#2 F10 OPEN COMPACT FLUORESCENT DOWNLIGHT WITH HORIZONTAL LAMPS RECESSED6-1/2"126 WATT DTT26MVOLTPORTFOLIOC6126-E6281-LI-HB50#2 F11WALL MOUNTED DECOTATIVE WALL SCONCESURFACEN/A140 WATT A1940120ELK LIGHTING10168/1 I1INCANDESCENT DECORATIVE PENDNTSURFACEN/A1 40 WATT A1940120 ELK LIGHTING 10169 I2SURFACE MOUNTED DECORATIVE BOWL FIXTURESURFACEN/A 318 WATT GU 2454120JUSTICE DESIGNALR-9681-NCKL S1CEILING MOUNTED SURGICAL LIGHTCEILINGN/A3100 WATT HALOGEN300120BURTONA10-0-SC X1 LED EXIT SIGN WITH RED LETTERS AND ALUMINUM HOUSING SURFACEN/AWITH FIXTURE5MVOLTEVENLITERZR-AC-X-1-AW-T#1 GENERAL NOTES: A.THE LUMINAIRE SCHEDULE CAN NOT BE USED INDEPENDENTLY OF THE DRAWINGS AND SPECIFICATIONS TO OBTAIN LUMINAIRE COSTS. THE INDIVIDUAL ESTABLISHING LUMINAIRE COSTS SHALL NOT QUOTE PRICING WITHOUT FIRST SEEING APPLICABLE ELECTRICAL DRAWINGS AND ELECTRICAL DIVISION SPECIFICATIONS. THE CONTRACTOR IS REPONSIBLE FOR PROVIDING NECESSARY DRAWINGS AND SPECIFICATIONS TO THE INDIVIDUAL QUOTING LUMINAIRE PRICING. B.ALL FLUORESCENT LAMPS ARE TO BE 3500° KELVIN COLOR TEMPERATURE C.SOME BUILDING STOCK UNDERCOUNTED FIXTURES MAY BE AVALIBLE FOR USE ON THIS PROJECT. COORDINATE WITH BUILDING OWNER. SPECIFIC NOTES: (1)COLOR TO MATCH EXISTING BUILDING STANDARD. (2)PROVIDE WITH PROGRAM START BALLAST. (3) LOAD CENTER:(N) 3D VOLTAGE:120/208V, 3PH, 4W MINIMUM BUS:225 LOCATION:3RD FLOOR ELEC MAIN:MLO MOUNTING:SURFACE MINIMUM AIC:22,000 NO.LOAD TYPELOAD DESCRIPTION BREAKERBUSBREAKER TYPELOAD DESCRIPTION LOAD NO.ABCPOLETRIPABCTRIPPOLEABC 11000E (E) FAN COIL (1)120+201L (E) #308 LIGHTING (1)15002 31200E (E) COPIER (1)120 +201L (E) #306 LIGHTING (1)15004 51080R (E) #310 REC (1)120 +201R (E) RECEPTACLES (1)10806 71080R (E) #310 REC (1)120+201R (E) RECEPTACLES (1)10808 91500L (E) ACC LTG (1)120 +201R (E) #308 REC (1)108010 111080R (E) RECEPTACLES (1)120 +201R (E) #310 REC (1)108012 131080R (E) RECEPTACLES (1)120+201R (E) ACC REC (1)108014 15720 R (N) OFFICE #321 REC 1 20 +20 1R(E) REC (1)108016 17720R (N) OFFICE #320 REC 120 +201R (E) RECEPTACLES (1)108018 19720R (N) OFFICE #315 REC 120+201A (N) COFFEE 100020 21900R (N) OFFICE #314 REC 120 +201A (N) UC REF 50022 23540R (N) EXAM #319 REC 120 +201R (N) RECEPT REC 126024 25540R (N) EXAM #318 REC 120+201E (N) PROCEDURE REC 50026 27 360 R (N) NURSE STAT REC 1 20 +20 1E(N) PROCEDURE REC 50028 29720R (N) EXAM #316 REC 120 +201E (N) PROCEDURE REC 50030 31540R (N) TECH WORK REC 120+201E (N) PROCEDURE REC 50032 33900R (N) EXAM #307 REC 120 +201SPARE 34 351260R (N) EXAM #306 REC 120 +201SPARE 36 37180E (N) LAB REC 120+201SPARE 38 39500E (N) NURSE #304 REC 120 +201SPARE 40 41 500E (N) NURSE #304 REC 1 20 +20 1 SPARE 42 43500E (N) NURSE #304 REC 120+201SPARE 44 45500E (N) NURSE #304 REC 120 +201SPARE 46 47500E (N) NURSE #304 REC 120 +201SPARE 48 491000E (N) COPIER 120+201SPARE 50 51540R (N) RECEPTION REC 120 +201SPARE 52 531000E (N) PRINTER 120 +201SPARE 54 55 908LRECEPT LTG120 +SPACE 56 57950 LCORRIDOR LTG1 20 +SPACE 58 591856LOFFICE LTG120 +SPACE 60 61300LEXAM LIGHT120 +SPACE 62 63SPARE120 +SPACE 64 65SPARE120 +151MP-1 12566 67SPARE120 + 153 LMEF-144468 69 SPARE1 20 +LM--444 70 71SPARE120 +LM--44472 73SPARE120 + 253 EWH-1200074 75SPARE120 +E--200076 77SPARE120 +E--200078 79SPARE120 + 603 E RTU-1 (2)595280 81SPARE120 +E--595282 83SPARE 1 20 +E--595284 LOAD TYPEPANEL TOTAL FEED THRU TOTAL SUBFEED TOTAL FEEDER SUBTOTAL DEMANDFEEDER TOTAL GENERAL NOTES: A. (L) LIGHTING 8514 8514 125%10643B. (R) RECEPTACLES 21600 21600 NEC 22015800C. (LM) LARGEST MOTOR 1332 1332 25%333D. (M) MOTORS (ALL)1457 1457 100%1457 E. (E) EQUIPMENT 32736 32736 100%32736 SPECIFIC NOTES: (A) APPLIANCES 1500 1500 31350 (1)EXISTING LOAD ON LOAD CENTER TO BE PANEL TOTAL (KVA):62.3 RELOCATED TO REPLACEMENT LOAD CENTER. (2)LOAD IS MCA SO IT INCLUDES LARGEST MOTOR PANEL TOTAL (A):173 AT 125% PER NEC DPA Project: Sheet Number: COPYRIGHT 2013 - DAVIS PARTNERSHIP, P.C. Sheet Title: 2301 Blake Street, Suite 100 Denver, CO 80205 303.861.8555 0225 Main Street, Unit C101 Edwards, CO 81632 970.926.8960 Denver Vail Consultant Issue/RevisionsDateNo. Sheet Information Project Information Permit Set30 August 2013 MedicalCenter VailValley Vail, Colorado 81657 US Bank Building 108 South Frontage Road Suite 306 S: \ B G P r o j e c t s \ 8 7 3 9 . 3 9 V V M C C o n c i e r g e C l i n i c \ C a d \ B G C E C A D\ 8 7 3 9 3 9 E 3 2 . d w g P r i n t e d B y : c ad d - j a c A u g u s t 3 0 , 2 0 1 3 - 9 : 5 7 a m L C - J A C COPYRIGHT 2013 B ANZEG EAUDIN (970)949-6108 (303) 278-3820 (970) 221-5691 (505) 323-9070 Vail: Denver: Fort Collins: Albuquerque: www.bgce.com Multi-Specialty Clinic 13915.00.000 MARTIN MARTIN 0225 MAIN STREET; SUITE C101 EDWARDS, COLORADO 81632 970.581.2546 BEAUDIN GANZE CONSULTING ENGINEERS 222 CHAPEL PLACE, UNIT AC-201 P.O. BOX 9650 AVON, COLORADO 81620 970.949.6108 E3.2 ELECTRICAL SCHEDULES Reviewed for Code Compliance Code: 2012 International Building Code (IBC)