HomeMy WebLinkAboutF13-0035 stamped approved plans1/4" WATER PRESSURE GUAGE
FLOW SWITCH, WIRED TO H/S
1/4" PRESSURE SWITCH
GOULDS HSC 2hp FIRE PUMP
1" FEBCO 860
1" SWEAT BRONZE CHECK VALVE
3/4" BALL VALVE FOR TEST AND DRAIN-TEST/DRAIN IS TO BE PIPED OUTSIDE
NOTES FOR RISER DETAIL
1" COPPER UNION
1 1/4" x 3/4" REDUCER
ELECTRICAL WIRE TO PUMP
3/4" COPPER UNDERGROUND PIPE FROM STREET-INSTALLED AND TESTED BY OTHERS
NOT USED
110 VOLT HORN & STROBE (wired by others)
3 HEAD SPRINKLER CABINET (w/ spare heads & wrenches)
NOT USED
2.1 GALLON EXPANSION TANK (WILKINS WXTP-8) W/ 3/4" BRONZE BALL VALVE
THIS ANTIFREEZE SYSTEM WILL HOLD APROX 6 gal OF ANTI FREEZE SOLUTION
PRESSURIZE SYSTEM TO 105 PSI OF ANTI FREEZE SOLUTION
ANTI-FREEZE IS TO BE A PRE-MIX GLYCERIN SOLUTION. FREEZE POINT TO BE -16
SOLUTION WILL BE 48% GLYCERIN AND 52% WATER
PROVIDE SIGN STATING ANTIFREEZE TYPE, CONCENTRATION
AND FREEZE POINT AT RISER AND
CONTACT INFO FOR ANTIFREEZE SUPPLIER
G2 SOLUTIONS
9009 QUINCE STREET, UNIT C
HENDERSON, CO
303-287-4870
GARAGE TEST POINT
HYDRAULIC NODE
NO SCALE
8'
-
1
1
"
9'
-
2
1
/
2
"
9'
-
2
1
/
2
"
16
'
-
0
"
6
12
40 total sprinklers for this job
13 heads for lower level
9 heads for middle level
18 heads for upper level
51
5
1
B
a
n
n
o
c
k
S
t
.
De
n
v
e
r
,
C
O
8
0
2
1
6
30
3
-
2
9
1
-
1
0
1
2
30
3
-
3
8
3
-
5
0
2
3
F
A
X
fi
r
e
s
p
r
i
n
k
l
e
r
@
a
f
s
s
c
o
.
c
o
m
A
F
I
R
E
S
P
R
I
N
K
L
E
R
DE
S
I
G
N
C
O
M
P
A
N
Y
MI
L
E
H
I
G
H
DE
S
I
G
N
G
R
O
U
P
MIS-REPRESENT THE EXACT LAYOUT OF THE
LAYOUT & CALCULATIONS.
AID THE AUTHORITY HAVING JURISDICTION WITH
SPRINKLER SCHEMATIC MAY IN SOME CASES
SPRINKLER SYSTEM. IT IS INTENDED TO HELP
ACCEPTING THIS COPY IS DEEMED AS AGREEING TO THE FOLLOWING: THIS DRAWING COPY, ITS CONTENTS,
INFORMATION AND PRINCIPALS OF DESIGN ARE THE EXCLUSIVE PROPERTY OF THE FIRE PROTECTION
CONTRACTOR LISTED AND MILE HIGH DESIGN GROUP, LLC AND IS BEING SUBMITTED TO YOU WITH THE
UNDERSTANDING THAT IT IS NOT TO BE REPRODUCED, COPIED OR MODIFIED IN ANY MANNER; NEITHER SHALL
IT BE RELAYED IN WHOLE OR IN PART TO ANY OTHER INDIVIDUAL OR FIRM FOR ANY OTHER PROJECT OR
EXTENSION OF THIS PROJECT EXCEPT THRU WRITTEN AGREEMENT WITH THE FIRE PROTECTION CONTRACTOR
AND MILE HIGH DESIGN GROUP, LLC. ERRORS AS A RESULT OF THIS FILE BEING ELECTRONICALLY
TRANSMITTED ARE BEYOND THE CONTROL OF AND ARE NOT THE RESPONSIBILITY OF THE FIRE PROTECTION
CONTRACTOR OR MILE HIGH DESIGN GROUP. MILE HIGH DESIGN GROUP IS NOT RESPONSIBLE FOR
INSTALLATION OR INSPECTION OF WORK INSTALLED. THESE PLANS ARE DIAGRAMMATICAL ONLY. ON SITE
COORDINATION MUST BE ARRANGED WITH ALL OBSTRUCTIONS, i.e.: MECHANICAL, ELECTRICAL, AND
STRUCTURAL. ANY ALTERATIONS FROM ENGINEERED DRAWINGS MUST BE APPROVED BY MILE HIGH DESIGN
GROUP. MILE HIGH DESIGN GROUP IS NOT RESPONSIBLE FOR LAYOUT DESIGN ISSUES OR CONFLICTS WITH
ANY OBSTRUCTIONS. IF ADDITIONAL FIRE SPRINKLER PIPING AND/OR FIRE SPRINKLER HEADS ARE REQUIRED
THIS WILL BE THE RESPONSIBILITY OF THE FIRE SPRINKLER CONTRACTOR. ALL CHANGES MUST ME APPROVED
BY MILE HIGH DESIGN GROUP, LLC
THE OWNER IS RESPONSIBLE TO PROVIDE SUFFICIENT HEAT THROUGHOUT THIS BUILDING TO PREVENT
FREEZING OF WATER IN THE FIRE SPRINKLER SYSTEM -
THIS SET OF FIRE SPRINKLER SHOP
DRAWINGS HAVE BEEN REVIEWED
AND FOUND TO BE ACCEPTABLE BY
TIMOTHY N. TROSTEL, JR - N.I.C.E.T.
IV # 102055. SR. ENGINEERING
TECHNICIAN - FIRE PROTECTION
NATIONAL INSTITUTE FOR CERTIFICATION IN
ENGINNERING TECHNOLOGIES
____________________________________/____/____
SCALE: NO TO SCALE
PIPE INSULATION DETAILS
SCALE: 1/8" = 1'-0"
PLAN
NORTH
FIRE SPRINKLER PLANS
1 2 3 4 5 6 7 8 9 10
SECTION VIEW A
SCALE: 1/8" = 1'-0"
PLAN
NORTH
FIRE SPRINKLER PLANS
1 2 3 4 5 6 7 8 9 10
SECTION VIEW B
GARAGE
21
2" Single
FDC
Horn &
Strobe
Check
Valve
1" CPVC PIPE
pendent head
in ceiling
1" valve to test
antifreeze
SCALE:
FDC Detail
not to scale
EXPOSED TO BE
STEEL PIPE
F13-0035
Received
By Carolyn Godfrey at 8:23 am, Oct 02, 2013
40 total sprinklers for this job
13 heads for lower level
9 heads for middle level
18 heads for upper level
GUEST
BEDROOM
GUEST
BATH
MASTER BEDROOM
MASTER
BATH
HALL
VESTIBULE
M. CLOSET
LINEN
SHOWER
DA Name: 1
DA Area: 198.03
DINING PATIO
SUNSET PATIO
BATH 2
DINING
ROOM
BBQ PATIO
OPEN TO
ABOVE
fire pump
67.50 0.00
64.50 10.00
61.00 20.00
56.30 30.00
49.80 40.00
41.60 50.00
105.00 0.00
85.00 1556.00
Hose stream allowance of is included in the above.
This system as shown on company print no dated
for at
contract no is designed to discharge at a rate of
a maximum area of when supplied with water at a rate of
Occupancy classification:
Commodity classification:
Maximum storage height:
Storage arrangement:
Number of heads flowing:
System Type:
Maximum velocity:
Flow from In-Rack sprinklers:
Flow from Overhead sprinklers:
Flow from Inside Hoses:
Flow from Outside Hoses:
Other fixed flows:
Total flow in system piping:
Additional flow at/beyond source:
Total of all flows:
Calculation results for Design Area
JSPIWð/PLQPðRIIORRUDUHDRYHU
-
Surplus Pressure at Source:
Pressure Required at Source:
Pressure Available at Source:
at at the base of the riser.
1 Great Room
Phoenix Automatic 9/28/13
Nate Ford Res 1079 Sandstone Dr. #W
0.05
IWð 27.1 gpm 79.5 psi
Res 2
Wet
16.83 ft/s
0 gpm
27.1 gpm
0 gpm
0 gpm
0 gpm
27.1 gpm
0 gpm
27.1 gpm
79.5 psi
105 psi
25.4 psi
MI
L
E
H
I
G
H
DE
S
I
G
N
G
R
O
U
P
51
5
1
B
a
n
n
o
c
k
S
t
.
De
n
v
e
r
,
C
O
8
0
2
1
6
30
3
-
2
9
1
-
1
0
1
2
30
3
-
3
8
3
-
5
0
2
3
F
A
X
fi
r
e
s
p
r
i
n
k
l
e
r
@
a
f
s
s
c
o
.
c
o
m
A
F
I
R
E
S
P
R
I
N
K
L
E
R
DE
S
I
G
N
C
O
M
P
A
N
Y
ACCEPTING THIS COPY IS DEEMED AS AGREEING TO THE FOLLOWING: THIS DRAWING COPY, ITS CONTENTS,
INFORMATION AND PRINCIPALS OF DESIGN ARE THE EXCLUSIVE PROPERTY OF THE FIRE PROTECTION
CONTRACTOR LISTED AND MILE HIGH DESIGN GROUP, LLC AND IS BEING SUBMITTED TO YOU WITH THE
UNDERSTANDING THAT IT IS NOT TO BE REPRODUCED, COPIED OR MODIFIED IN ANY MANNER; NEITHER SHALL
IT BE RELAYED IN WHOLE OR IN PART TO ANY OTHER INDIVIDUAL OR FIRM FOR ANY OTHER PROJECT OR
EXTENSION OF THIS PROJECT EXCEPT THRU WRITTEN AGREEMENT WITH THE FIRE PROTECTION CONTRACTOR
AND MILE HIGH DESIGN GROUP, LLC. ERRORS AS A RESULT OF THIS FILE BEING ELECTRONICALLY
TRANSMITTED ARE BEYOND THE CONTROL OF AND ARE NOT THE RESPONSIBILITY OF THE FIRE PROTECTION
CONTRACTOR OR MILE HIGH DESIGN GROUP. MILE HIGH DESIGN GROUP IS NOT RESPONSIBLE FOR
INSTALLATION OR INSPECTION OF WORK INSTALLED. THESE PLANS ARE DIAGRAMMATICAL ONLY. ON SITE
COORDINATION MUST BE ARRANGED WITH ALL OBSTRUCTIONS, i.e.: MECHANICAL, ELECTRICAL, AND
STRUCTURAL. ANY ALTERATIONS FROM ENGINEERED DRAWINGS MUST BE APPROVED BY MILE HIGH DESIGN
GROUP. MILE HIGH DESIGN GROUP IS NOT RESPONSIBLE FOR LAYOUT DESIGN ISSUES OR CONFLICTS WITH
ANY OBSTRUCTIONS. IF ADDITIONAL FIRE SPRINKLER PIPING AND/OR FIRE SPRINKLER HEADS ARE REQUIRED
THIS WILL BE THE RESPONSIBILITY OF THE FIRE SPRINKLER CONTRACTOR. ALL CHANGES MUST ME APPROVED
BY MILE HIGH DESIGN GROUP, LLC
THE OWNER IS RESPONSIBLE TO PROVIDE SUFFICIENT HEAT THROUGHOUT THIS BUILDING TO PREVENT
FREEZING OF WATER IN THE FIRE SPRINKLER SYSTEM -
THIS SET OF FIRE SPRINKLER SHOP
DRAWINGS HAVE BEEN REVIEWED
AND FOUND TO BE ACCEPTABLE BY
TIMOTHY N. TROSTEL, JR - N.I.C.E.T.
IV # 102055. SR. ENGINEERING
TECHNICIAN - FIRE PROTECTION
NATIONAL INSTITUTE FOR CERTIFICATION IN
ENGINNERING TECHNOLOGIES
____________________________________/____/____
SCALE: 1/8" = 1'-0"
PLAN
NORTH
FIRE SPRINKLER PLANS
1 2 3 4 5 6 7 8 9 10
LOWER LEVEL
SCALE: 1/8" = 1'-0"
PLAN
NORTH
FIRE SPRINKLER PLANS
1 2 3 4 5 6 7 8 9 10
MIDDLE LEVEL
SCALE: 1/8" = 1'-0"
PLAN
NORTH
FIRE SPRINKLER PLANS
1 2 3 4 5 6 7 8 9 10
UPPER LEVEL