HomeMy WebLinkAboutB12-0401 FLUE CHASE INSPECTION LETTER/TRANSMITTAL Department of Community Development
0 75 South Frontage Road
TOWN OF VAIL # Vail, CO 81657
Tel: 970.479.2128
www.vailgov.com
Development Review Coordinator
TRANSMITTAL FORM
Use this form when submitting additional information for planning applications or building permits.
This form is also used for requesting a revision to building permits. A two hour minimum building review
fee of$110 will be charged upon reissuance of the permit.
Application/Permit#(s) information applies
to: Attention: ( ) Revisions
r/ ( ) Response to Correction Letter
_attached copy of correction letter
(k) Deferred Submittal
( ) Other
Project Street Address:
(Number) (Street) (Suite#)
Building/Complex Name: �eeyti Description of Transmittal/List of Changes, Items Attached:
Applicant Information ��1 QD "s`I �-t_UE lLf� �IJS( CTI Ol�l
(architect, contractor, owner/owner's rep)
t
Contact Name:
Address:
City (�fi� State: 4-le Zip: oolzlf
Contact Name:
(use additional sheet if necessary)
Contact Phone: Building Permits:
�� �� Revised ADDITIONAL Valuations (Labor&Materials)
Contact E-Mail: �i.r� �� G% s C'G � (DO NOT include original valuation)
I hereby acknowledge that I have read this application,filled out Building: $
in full the information required,completed an accurate plot plan,
and state that all the information as required is correct. I agree to Plumbing: $
comply with the information and plot plan,to comply with all Town
ordinances and state laws, and to build this structure according Electrical: $
to the town's zoning and subdivision codes, design review ap-
proved, International Building and Residential Codes and other Mechanical: $
ordinances of the applicable,.�hereto.
��� 7,/, Total: $
Owner/Owner's Representative Signature(Required)
Date Received:
For Offiee Use Only: OUT U 8 2013
Fee Paid:
Received From: T
Cash Check# OWN OF VAIL
CC: Visa/VIC Last 4 CC# exp.date:
Authorization #
1,4 TnangleTube
�40
a Tn-%g*Tuhe
Friday, September 20, 2013
RE: Flue Chase Application Review
Application: Venting of the PT399 Nat Gas boiler in a "conditioned" space.
The following comments and approval are based on the proposed flue chase sketch received
in an e-mail from R&R Heating on Wednesday September 18, 2013.
• Proposed chase as shown is constructed to meet the criteria of a heated/conditioned
space similar to the garage below it where the boiler is installed.
• The lower portion of that chase is open to the heated/conditioned garage as to allow
warm air to flow in and around the entire chase.
• The top of the chase is constructed to be closed, insulated and suitable to receive an
appropriate vent flashing.
• This assembly as proposed should keep the condensed products of combustion in the
flue/vent pipe from freezing.
All other conditions and restrictions noted in our Prestige Solo Boiler Installation and
Maintenance Manual dated 06/10/13, as well as our PVC/CPVC/PP & SS Vent Supplement
dated 05/09/13 apply.
If there are clarifications please contact me directly.
Thank you.
��4
Rick Mayo
Product and Applications Instructor
rmayoCtriangletube.com
Triangle Tube
1 Triangle Lane