HomeMy WebLinkAboutA13-0066 cut sheets Honeywell
580000
CARBON MONOXIDE DETECTOR WITH BUILT-IN '`���'
WIRELESS TRANSMITTER �
I�
�
�
U� U�C
The 580000 is a 3V battery powered wireless carbon The detector consists of an electrochemical carbon
monoxide (CO)detector intended for use with Honeywell monoxide sensor assembly coupled with a wireless
alarm systems that support 5800 Series wireless devices. transmitter. The transmitter can send alarm, trouble,
It provides early warning when its electrochemical sensing end-of-life, tamper and low battery condition messages
technology measures carbon monoxide levels in the air. to the alarm panel.
The 580000 is specifically designed for system operation Since there are no holes to drill or wires to run, you can
and is fully listed to UL 2075 as a system supervised preserve the beauty of the home or building while
detector.* It contains a piezoelectric horn which generates protecting its occupants from harmful carbon monoxide
the ANSI S3.41 temporal 4 pattern in an alarm condition. gas. The 580000 is an ideal carbon monoxide detector
for difficult to wire locations, applications where room
aesthetics are critical or where hazardous materials exist.
What is Carbon Monoxide and How Can it Harm Consumers?
Carbon monoxide (CO)is an odorless, colorless, tasteless and highly toxic gas that is produced when fuels such as wood,
gasoline, charcoal and oil are burned with insufficient air. The majority of residential and commercial fatalities caused from
these fuels come from heating systems, engine powered tools and charcoal grills. Carbon monoxide is harmful when
inhaled because it displaces oxygen in the blood and deprives the heart, brain and other vital organs of oxygen. Large
amounts of CO can overcome a person in minutes without warning—causing them to lose consciousness and suffocate.
The 580000 is designed to warn the end-user well before the CO reaches a fatal level. The detector's CO sensitivity is
evaluated to UL 2034.
CO Levels and Time to Alarm
CO Concentration Min. Time to Alarm Max. Time to Alarm
30 ppm +/- 5 ppm 30 days Indefinite*�
70 ppm +/- 5 ppm 60 minutes 240 minutes
150 ppm+/- 5 ppm 10 minutes 50 minutes
400 ppm+/- 5 ppm 4 minutes 15 minutes
"For a complete list of products that support system operation of the 580000 to UL standard 2075, please visit:
www.honeywell.com/security/hsc/resources/agency/co
`"Life of product
580oC0 Honeywell
CARBON MONOXIDE DETECTOR WITH BUILT IN
WIRELESS TRANSMITfER
KEY FEATU RES
Electrochemical Sensing Technology- Electrochemical Full Supervision - The 580000 is fully supervised to monitor
detectors are the newest, most refined CO detectors available for low battery, case tamper and trouble conditions.
and provide the most accurate measurement of CO Test/Hush Button- This dual purpose button allows the
concentration obtainable. They can take readings from low end-user to perform periodic testing of the detector. In the
levels that may be hazardous over long periods of time to event of a CO alarm, this button will silence the local sounder
high concentrations that present an immediate danger. alarm for a five minute period. Note: the Hush feature will not
Local Sounder-A built-in piezoelectric horn generates the operate at levels above 350 ppm (parts per million)carbon
ANSI S3.41 temporal 4 pattern in an alarm condition. The monoxide(see figure 1).
local sounder will also alert the end-user of other conditions
Versatile Mounting - Whether you choose to affix the
such as low battery, detector trouble and end-of-life.
detector to the ceiling or a wall, mounting is made simple
LED Status Indicators- Dual LEDs provide local visual with the enclosed hardware. The mounting base has large
indication of the detector's status�ncluding normal operation, mounting ports, which accommodate drywall anchors for
alarm, low battery, trouble and end-of-life(see figure 1). easy surface mounting (see figure 2).
End of Life Timer- When the detector has reached the end Tamper Protection and Tamper Resistant Element-
of its life, the detector will send a trouble signal to the panel. The detector has a built-in tamper switch that can
This indicates that the CO sensor inside the detector has communicate back to the control panel in the event it is
passed the end of its life and the detector needs to be removed from the base. For an added level of security,
replaced. The detector's lifespan is approximately six years the detector also includes a tamper resistant element that
from the date of manufacture. prevents removal from the base without the use of a tool
(see figure 2).
�
� MOUNTING
' SCREWS
� (INSTALLED)
i .
i �
I / ��hJO � \
I /�v�\` � ��'��N,� J \
/ � ���f \
; ��J
' ' �I i � \
TEST BUTTON � � �� �
i �
��'°nedd� � � �
aa'�ow >eti�ue � ow � �
�,°+� snH �o�o � d��N�Hedm I TAMPER
e
ao� N 1s�1 °6� � s °n+ i RELEASE TAB
GREEN LED a� o� i �1l1dlF,� ��� ' CUT OFF
�� 5 Q � ��'U���� t� SMALL TAB TO
�O o °� i �� � ��� ACTIVATE
� �` i ti �� TAMPER RESIST
�q ooN°SeP � � �y \ �Z X � FEATURE)
RM i Z = O O / ,
RED LED I �
�/
i �'� Z � /
� Q � �
i �P
�
i
� ENGAGE NOTCH WITH
� TAMPER RELEASE TAB
� ON BASE AND TURN
i CLOCKWISE TO LOCK
i
Figure 1 ; Figure 2
580oC0 Honeywell
CARBON MONOXIDE DETECTOR WITH BUILT IN
WIRELESS TRANSMITfER
MOUNTING RECOMMENDATIONS
CO is slightly lighter than air and when heated by a fuel-burning source, the lighter weight and warm temperature of the CO
causes it to quickly rise to the ceiling and mix freely with the air. Check with the local Authority Having Jurisdiction (AHJ)for
CO detector requirements in your area. Some recommendations for installing the 580000 are as follows:
- On every floor of the facility
- Inside any areas that contain a fuel-burning appliance
- In the vicinity of flame-fueled appliances, but no
closer than 10 feet ■
• For wall mount BEDROOM
- The detector should be at least as high as a light �
switch and at least six inches from the ceiling To
BEDROOM gR BEDROOM
• For ceiling mount �
KITCHEN GARAGE
- The detector should be at least 12 inches from , CLOSED
LIVING DOOR
any wall ROOM
■
BASEMENT
� CARBON MONOXIDE ALARM
LOCATION FOR MULTI-LEVEL RESIDENCE
SPECIFICATIONS
• Power Source: One 3V CR123A lithium battery(included)
• Audible Signal (temporal 4 tone): 85 dB in alarm (at 10 ft.)
• Height: 2.3" (58mm)
• Diameter: 5.3" (135mm)with mounting base
• Weight: 7 oz. (241 g)without battery
• Operating Ambient Temperature Range: 32° F to 100° F(0° C to 37.8° C)
• Operating Humidity Range: 15% to 95% relative humidity, non-condensing
• Agency Listings:
- Listed to UL standard 2075, *CO sensitivity is evaluated to UL 2034
- 580000A ULC Listed - tested to the CAN/CSA 6.19.01 standard
ORDERING
580000 Wireless Carbon Monoxide Detector with Built-in Wireless Transmitter
580000A Wireless Carbon Monoxide Detector with Built-in Wireless Transmitter with ULC listing
`For a complete list of products that support system operation of the 580000 to UL standard 2075 and 580000A ULC standard, please visit:
www.honeywell.com/security/hsc/resources/agency/co
Automation and Control Solutions
Honeywell Security&Communications Honeywell
2 Corporate Center Dr. Suite 100
P.O. Box 9040
Melville, NY 11747 ussoocowo
March 2009
www.honeywell.com �O 2009 Honeywell International Inc.
Honeywell
5808W3 _` ��,�-.-
PHOTOELECTRIC SMOKE/HEAT
DETECTOR WITH BUILT-IN � �
WIRELESS TRANSMITTER
�' � +►�
�
�
;� I
Honeywell's 5808W3 is a 3V lithium powered, Since there are no holes to drill or wires to run, you can
photoelectronic smoke/heat detector with a built-in preserve the beauty of the building while protecting it. The
wireless transmitter. It is intended for use with any 5808W3 is an ideal smoke detector for those difficult to wire
5800 Series Wireless Receiver/Transceiver for residential locations, applications where room aesthetics are critical, or
installations (for commercial installations, the 5881 ENHC where hazardous materials exist.
or the 5883H receiver is required).
All models also feature a restorable, built-in, fixed temperature
The transmitter can send alarm, tamper, maintenance(when (135°F)thermal detector that is also capable of sensing a
control panels are equipped to process maintenance signals), pre-freeze condition if the temperature is below 41°F.
and battery condition messages to the system's receiver.
Smoothing algorithms minimize nuisance alarms by
smoothing out short term spikes from dust and smoke—
virtually eliminating nuisance alarms.
FEATURES
• Improved Robust RF Field • Drift Compensation • Easy-to-install Mounting Base
Strength Virtually eliminates nuisance alarms The sturdy mounting base allows the
The distance between the detector from long-term dust build-up by detector to be more easily installed
and receiver has been significantly automatically adjusting the detector's on uneven surfaces (i.e. stucco). The
increased without the need for a sensitivity mounting base has larger mounting
repeater • Removable Detector Cover and ports, which accommodate drywall
• Smoothing Algorithms Chamber Top anchors for easy surface mounting.
Mathematical calculations in the The technician is able to quickly and
detector's software that minimize easily clean the detector chamber ADDITIONAL FEATURES:
nuisance alarms by smoothing out without disassembling the detector
short term spikes from dust and head • Utilizes one long-life 3V lithium
battery
smoke
• Approved UL Listings for Residential . Microcontroller runs on a 4.0 MHz
• Smart Check and Commercial Applications clock
A signal is sent to the control panel Both residential and commercial . Horn operates at 3.3 KHz with sound
when the detector requires cleaning. installation requirements are met pressure level of 85 dBA at 10 feet
This allows a regular, non-emergency
•Additional LED Status Indicators • Built-in wireless transmitter, temporal
service call to clean the detector ldentifying between alarm or trouble code 3 sounder
before it goes into alarm.
conditions is a snap with green and • Maintenance signal fully complies
red LED status indicators.A green LED with the sensitivity test requirement
denotes a normal condition while the specified in NFPA 72, 7-2.2 and is
red LED indicates abnormal conditions. approved by UL
5808W3
PHOTOELECTRIC SMOKE/HEAT DETECTOR WITH BUILT-IN WIRELESS TRANSMITTER
SPECIFICATIONS
• Dimensions •Air Velocity • Power Source
-Diameter: 5.3"", Height; 2.30" - 1,000 ft./min. max. -One 3V CR123A lithium Batteryt
•Weight • Operating Voltage •Audible Output
-8.5 ounces(without batteries) -2.5-3.6VDC -85 dB min. at 10 ft.
• Operating Temperature • Standby Current • Fixed Temperature Heat Sensor
-32-100° F(0-37.8° C) -8.5 mA avg. - 135° F Fixed
• Humidity Range •Alarm Current •Agency Listings
-0%to 95% RH, non-condensing -35 mA max. -UL268-Commercial and
Residential
*With adapter bracket(4.9"without mounting base)
tReplacement batteries include Duracell DL123A,Sanyo CR123A,Panasonic CR123A,or ADEMCO 466
ACCESSORIES(sold separately)
SENS-RDR Infrared RT Removal Tool
Sensitivity Reader -""'"�!� ;
�x5 Simplifies the attachment 2�; > �II�] -"
Reduce testing time with the , *� and removal of the �
handheld SENS-RDR infrared � detector head to the � . �"� '"„�
sensitivity reader. The reader I � mounting base; it may
simplifies sensitivity measurements be attached to a threaded `k • *
��� Y; �����a
and displays them precisely in extension pole or broom -
terms of percent per foot handle thereby eliminating �,
obscuration. The SENS-RDR the need for ladders. '
eliminates the need for magnets, _
voltmeters and ladders. ^� _ +: �
���ti� ' ------ '
--.�- ---—---_. _ �
ORDERING
5808W3 Photoelectric Smoke/Heat Detector with Built-in Wireless Transmitter
Accessories sold separately:
SENS-RDR Hand-held Sensitivity Reader
RT i3 Removal Tool used for easy installation and removal of head from base
Automation and Control Solutions
Honeywell Security&Communications HonG�Gl'
2 Corporate Center Dr. Suite 100
P.O. Box 9040
Melville, NY 11747 v5aoaws�sio
September 2008
www.honeywell.com OO 2008 Honeywell International Inc.
K0903V1 2/06 Rev.B
Honeywell ADEMCO 6160RF
Keypad/Transceiver
Installation and Setup Guide
GENERAL INFORMATION
The ADEMCO 6160RF keypad/transceiver is a combination unit that combines the functions of the following
devices:
• 6160 Alphanumeric Addressable Keypad
• 5881H RF Receiver
• 5800TM Transmitter Module
The 6160RF Keypad/Transceiver may be used on any control panel that supports 5800 Series wireless devices
(e.g.,VISTA-10P, VISTA-15P,VISTA-20P).
FEATURES
• Supports wireless key transmitters (e.g.; 5804) and bi-directional transmitters(e.g.; 5804BD, 5828/5828V).
• Supports wireless keys with high-security(encryption) capability(e.g.; 5804E).
• Provides a nominal range of 200 feet' for RF transmitters (some transmitters have a shorter range).
• Supports RF jam detection when the receiver is enabled.
• Capable of sending status signals (Armed, Ready, etcJ to bi-directional units such as 5804BD, 5804BDV and
5828/5828V.
uL The following 5800 series transmitters are not intended for use in UL installations: 5802, 5804, 5804BD, 5804BDV, 5804E,
5814, 5816TEMP, 5819, 5819BRS, 5819WHS, 5828/5828V and 5850.
INSTALLING THE 6160RF 2. Pass the wiring from the control panel through
Locate the 6160RF in an area and at a height where the opening in the case back. (see the control
it is convenient for user operation. The 6160RF must panel's instructions for proper run lengths.)
be at least 10 ft from the control panel to ensure
proper operation of the RF receiver. a. If surface wiring is being used, wiring may be
Mounting and Wiring routed through the top or the bottom left-side
The 6160RF has terminal blocks for connection to breakout in the case back. The breakouts must
power and data wires. Removing the keypad's case be punched out using a screwdriver before
back provides access to the terminal blocks.
mounting the case back.
The 6160RF can be surface mounted directly to b. If desired,wires may be strain-relieved to the
walls, or to a single- or double-gang electrical box. wire tie point on the inside of the case back
Follow these steps to mount and wire the keypad: with a tie wrap (not supplied).
1. Push the two case release snaps at the bottom of 3. Mount the case back to a wall or to an electrical
the keypad with the blade of a medium box using the 25mm-long self-tapping screws
screwdriver(this will push in the release snap), supplied(mollies for drywall are not supplied).
then pull that side of the case back away. Insert 4. Connect the power and data wires from the
the screwdriver in the side of the keypad control panel to the terminals on the 6160RF as
(between the front and back case) and gently indicated in Figure 2 and Table 1.
twist to release the side locking tab. Repeat for
the other side. Refer to Figure 1 for location of the
case back release snaps and locking tabs. ❑ ❑ o O
_ � �' ���� �o
� �
��;�>
� � ❑
� 0
NOTE: o o�
TO REMOVE REAR COVER
PUSHINTHETWOMOUNTING Q �-
SNAPSLOCATEDALONGTHE
BOTTOM OFTHE KEVPAD
AND LIFT COVER UP. \ O
0 }1
mouNnNG �oc�clNG WIRING TERMINALS
RE�EASE �B (TO CONTROL PANEL) e
SNAPS e
Figure 1. Removing the Case Back Figure 2-6160RF Wiring Details
Table 1 -Wiring Table 5. Reattach the keypad to the mounted case back.
Keypad Control Panel Wire Color Attach the top of the keypad first, and then
G�(Data Out) Data In Green press the bottom section down until it snaps
- -Aux Pwr(GND) Black into place securely.
+ +Aux Pwr Red
�Y(Data In) Data Out Yellow 6. Peel off protective film on the LED panel and
install the keypad labels as required.
APPLICATION GUIDELINES FOR THE 6160RF
Use the following guidelines when planning an installation:
If... And... Then...
This is the only You want to use both • Set the keypad to a device address assigned to the desired partition.*
transceiver on the receiver and • Enable the receiver.
the system, transmitter function
on a single-partition • Program a system House ID in the control panel (this will enable the transmitter
system, function).**
• Set the wireless devices that will communicate with this 6160RF to the same
system House ID.
There is another You want to use only • Set the keypad to a device address assigned to the desired partition.*
receiver or the transmitter • Disable the receiver.
transceiver on function on a second
the system, partition, • Program a DIFFERENT House ID in the 6160RF than is programmed in the control
panel.*/**
� Set the wireless devices that will communicate with this 6160RF to the same
House ID as the 6160RF.
You want to use only • Set the keypad to a device address assigned to the Partition 1.
the transmitter • Disable the receiver.
function on a single-
partition system, • Program a House ID in the 6160RF that matches the system House ID
programmed in the control panel.*
• Set the wireless devices that will communicate with this 6160RF to the same
House ID.
Notes:
* On VISTA-40 panels and above, wireless keypads (e.g., 5804BD)can only be used on a single partition. This
partition is programmed in f"ield 1*48, and must match the partition assigned to the 6160RF. Wireless keys can
be used on more than one partition, using a House ID programmed in the 6160RF and the devices. In this case,
the wireless keys must be assigned to the same partition as the 6160RF.
�* On VISTA-20P panels, the 6160RF will use the House ID programmed in the panel for the partition to which
it is assigned. Wireless keypads can only be used on Partition l.
PROGRAMMING THE 6160RF
Refer to the following procedure to program the 6160RF:
STEP DESCRIPTION DISPLAY CHOICES
1. Enter the program mode by pressing the [1]and[3]keys simultaneously
for a few seconds within 60 seconds after applying power.
2. (Keypad Address)Enter the two-digit keypad address. Press the[='s�]key CDIYADD1PE55 = XX 00-31
to continue.
Notes: (1) Refer to the control panel's installation instructions for the
acceptable keypad addresses.
(2) On the VISTA-40 and above the 6160RF's partition assignment must
match the RF keypad partition assignment programmed in field
(1*48).
3. (Receiver Enable)Enter[1]to enable,or[0]to disable Receiver.Enable !2E[�jf��� 1= ON
the receiver if RF transmitters or wireless keypads are programmed into 0= OFF
the control and no other receivers are enabled.Press the [=i=]key to Qn �Q= fl��l
continue.
- 2 -
STEP DESCRIPTION DISPLAY CHOICES
4. (Receiver Address)If receiver is enabled,enter the two-digit receiver RFtADDJPE55=XX 00-30
address. (01-30).
Note: Refer to the control panel's installation instructions for the acceptable
receiver addresses.
Press the [='s=]key to continue.
5. (House ID)This prompt will only appear if the receiver is disabled. If the }{Q(fSE fd= x)( 00-31
receiver is enabled the 6160RF will use the House ID programmed in
the panel. Refer to Application Guidelines section when selecting a
House ID.
To program a House ID:Enter 01-31.
To disable the transmitter:Enter 00
Note: Each device that will receive status from the 6160RF must be set to the
same House ID as the 6160RF(refer to Application Guidelines section).
Press the[='s=]key to continue.
6. (Enable High Security Mode)Enter[1]to select High Security Mode. }{j�xS�Q��lT� 1= Enable
Note: If the High Security mode is enabled,the 6160RF will only recognize 0= Disable
encrypted devices. If this mode is disabled,the 6160RF will process p��jjj p�
commands both encrypted and non-encrypted devices.*
Press the[=i=]key to continue.
7. (Disable High Security Devices)Press the[='s=]key to skip this prompt (jfSf38LF f.{SdFf/r� 1=YES
and exit Program Mode. MQ jjJ_ �fs o= NO
Notes: (1) The [�k] key must be pressed several times in order to save the
programmed data.
(2) If you need to disable encrypted devices,refer to the Disabling High
Security Devices section.
� *When operating the system in High-Security mode,5804BD wireless keys will still function. If you want the system to
recognize only encrypted wireless devices,program only encrypted devices in the system.
ACTIVATING HIGH SECURITY DEVICES
This following procedure should be followed if using High-Security(encrypted) devices.
STEP DESCRIPTION
1, Follow the normal procedure for programming the device into the control panel(refer to the Installation
Instructions for the device that you are programming). Exit out of Programming Mode.
2. Put the control panel in Go/No Go Test mode. (See the Installation Guide for the panel being installed.)
g. Follow the instructions supplied with each wireless device to enroll the device in High-security mode.After each
device is enrolled the 6160RF will momentarily display"SECURITY DEVICE"along with the device number and
its serial number.
Note:The 6160RF will support a maximum of 8 devices. If you attempt to enroll additional devices the keypad will display
"EXCEEDED NUMBER""ALLOWED DEVICES".
DISABLING HIGH SECURITY DEVICES
This mode gives you the ability to disable high security on all wireless keys that have been enrolled in the
6160RF. This is particularly useful if a user loses a wireless key.
Once high-security (encrypted) devices have been disabled, they will only operate if the 6160RF is set to listen to both
� encrypted and non-encrypted devices(programming step 6,above).To completely disable the devices,they must be deleted
' from the control panel.
STEP DESCRIPTION DISPLAY CHOICES
1. After the keypad has been powered for at least 60 seconds hold rQnROORFSS=xx 00-31
down the [1] and [3] keys at the same time for 3 seconds. The
current keypad address will be displayed. (You cannot change the
keypad's address at this point.)Press the[=i=]key to continue.
2_ (Delete High Security Devices)Press the [1]key to remove all high- OJSRSLF HS DFU� 1=YES
security(encrypted)devices. Press the[=i=]key to continue. �� jTJ_y�s 0 = NO
g. If YES was selected in Step 2 the unit will display a confirm fjR��Q(f SUQ�� 1=YES
request to delete the stored high security device.Press the [1]key nd jT1_yFS 0 = NO
to accept,followed by the[=:=]key to exit the programming mode.
- 3-
TROUBLESHOOTING
The error messages listed in the following table cause the 6160RF to produce a single ding tone. The table
describes the error messages and the corrective actions.
Display Probable Cause Corrective Action
Low Bat(with Low battery in the wireless device. 1. Replace the battery if the wireless transmitter has a replaceable battery.
zone no.) 2. Replace the transmitter if the wireless transmitter does not have a
replaceable battery.
Open Ckt No data is being received from the control panel. Verify that the keypad�Y(yellow)wire is connected properiy.
Check 100 1.The control panel does not see the 6160RF 1 a.Verify that the keypad�Y(yellow)and G� (green)wires are
* Receiver,or the Receiver is not functioning. connected properly.
Check 1x�c
1 b.Verify that the control's receiver address is correct.
2.Another device on the keypad terminals is not 2. Verify the wiring connections between the control and all other devices.
communicating to the control panel.
*�=the device address of the receiver.
SPECIFICATIONS
Physical: 5-3/8"H x 7-3/8"W x 1-1/4"D Current: Standby 50mA
(137mm x 187mm x 32mm) Backlighting on and
Wiring: Refer to Table 1 Sounder on 150mA
Range: 200 ft(60.9 m)nominal Display: 2 x 16 alphanumeric supertwist LCD,backlit
Frequency: 345 MHz Sounder: Tone Generator Integrated Circuit.(fire alarm is loud pulsing tone;
burglary/audible panic alarm is continuous tone)
FOR DETAILS ON THE LIMITATIONS OF THE ENTIRE ALARM SYSTEM,REFER TO THE INSTALLATION AND SETUP GUIDE FOR THE CONTROL PANEL BEING
INSTALLED IN CONJUCTION WITH THIS DEVICE.
FCC STATEMENT&INDUSTRY CANADA STATEMENT
This device complies with Part 15 of the FCC rules and RSS210 of Industry Canada. Operation is subject to the following two conditions: (1)This device may not
cause harmful interference,and(2)This device must accept any interference received,including interference that may cause undesired operation.
Federal Communications Commission (FCC)Part 15 Statement
This equipment has been tested to FCC requirements and has been found acceptable for use.The FCC requires the following statement for your information:
This equipment generates and uses radio frequency energy and if not installed and used properly,that is,in strict accordance with the manufacturer's instructions,may
cause interference to radio and television reception.It has been type tested and found to comply with the limits for a Class B computing device in accordance with the
specifications in Part 15 of FCC Rules,which are designed to provide reasonable protection against such interterence in a residential installation.However,there is no
guarantee that interference will not occur in a particular installation.If this equipment does cause interference to radio or television reception,which can be determined
by turning the equipment off and on,the user is encouraged to try to correct the interference by one or more of the following measures:
• If using an indoor antenna,have a quality outdoor antenna installed.
• Reorient the receiving antenna until interference is reduced or eliminated.
• Move the radio or television receiver away from the receiver/control.
• Move the antenna leads away from any wire runs to the receiver/control.
• Plug the receiver/control into a different outlet so that it and the radio or television receiver are on different branch circuits
If necessary,the user should consult the dealer or an experienced radio/television technician for additional suggestions.The user or installer may find the following
booklet prepared by the Federal Communications Commission helpful:"Interference Handbook."This booklet is available from the U.S.Government Printing Office,
Washington,DC 20402.
The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User's Manual. Unauthorized changes or
modifications could void the user's authority to operate the equipment.
LIMITED WARRANTY
Honeywell International Inc.,acting through its Security&Custom Electronics business("Seller")165 Eileen Way,Syosset,New York 11791,warrants its products to be
in conformance with its own plans and specifications and to be free from defects in materials and workmanship under normal use and service for 24 months from the
date stamp control on the product or,for products not having an Ademco date stamp,for 12 months from date of original purchase unless the installation instructions or
catalog sets forth a shorter period,in which case the shorter period shall apply.Seller's obligation shall be limited to repairing or replacing,at its option,free of charge
for materials or labor,any product which is proved not in compliance with Seller's specifications or proves defective in materials or workmanship under normal use and
service.Seller shall have no obligation under this Limited Warranty or otherwise if the product is altered or improperly repaired or serviced by anyone other than Ademco
factory service.For warranty service,return product transportation prepaid,to Factory Service,165 Eileen Way,Syosset,New York 11791.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, OF MERCHANTABILITY, OR FITNESS FOR A PARTICULAR PURPOSE OR OTHERWISE, WHICH EXTEND
BEYOND THE DESCRIPTION ON THE FACE HEREOF.IN NO CASE SHALL SELLER BE LIABLE TO ANYONE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES
FOR BREACH OF THIS OR ANY OTHER WARRANTY, EXPRESS OR IMPLIED, OR UPON ANY OTHER BASIS OF LIABILITY WHATSOEVER, EVEN IF THE LOSS OR
DAMAGE IS CAUSED BY THE SELLER'S OWN NEGLIGENCE OR FAULT.
Seller does not represent that the products it sells may not be compromised or circumvented;that the products will prevent any personal injury or property loss by
burglary, robbery,fire or otherwise; or that the products will in all cases provide adequate warning or protection. Customer understands that a properly installed and
maintained alarm may only reduce the risk of a burglary, robbery,fire or other events occurring without providing an alarm,but it is not insurance or a guarantee that
such will not occur or that there will be no personal injury or property loss as a result. CONSEQUENTLY, SELLER SHALL HAVE NO LIABILITY FOR ANY PERSONAL
INJURY,PROPERTY DAMAGE OR OTHER LOSS BASED ON A CLAIM THE PRODUCT FAILED TO GIVE WARNING.HOWEVER,IF SELLER IS HELD LIABLE,WHETHER
DIRECTLY OR INDIRECTLY, FOR ANY LOSS OR DAMAGE ARISING UNDER THIS LIMITED WARRANTY OR OTHERWISE, REGARDLESS OF CAUSE OR ORIGIN,
SELLER'S MAXIMUM LIABILITY SHALL NOT IN ANY CASE EXCEED THE PURCHASE PRICE OF THE PRODUCT,WHICH SHALL BE THE COMPLETE AND EXCLUSIVE
REMEDY AGAINST SELLER.This warranty replaces any previous warranties and is the only warranty made by Seller on this product.No increase or alteration,written or
verbal,of the obligations of this Limited Warranty is authorized.
II I II II II I II I II I II III I I III II III Hone�ell 165 o yegn oaoos Ho es eti�NewYo ak111791
K0903V1 2/06 Rev.B www.honeywell.com/security
Honeywell
Piezo Dynamic Series
(PD) SIRENS
E ��
747PD
Honeywell's Piezo Dynamic (PD) WAVE2PD and 747PD The sirens feature a sleek, lightweight design, an
Sirens produce traditional "speaker" sound while drawing easy-to-wire terminal block and a hinged case cover.
1/4 the current of typical sirens. This allows multiple The WAVE2PD and 747PD Sirens are globally compliant
devices to be installed on the same alarm panel without and UL approved and ideal for residential application.
the need for additional hardware, costs and labor.
FEATURES
• Low current draw lets you add additional sirens in areas • Hinged case cover with elliptical mount holes provide
like basements, garages, hallways and more installation convenience
•Two tones to choose from: Steady and Warble • Tampered versions available to provide an added level of
• Lightweight ABS plastic case is less than half the weight Protection and meet global requirements
of standard sirens • Compatible with LYNX control panels
• Enclosed PCB to protect components • Large wiring channel provides plenty of room for wire
• Easy-to-wire terminal block eliminates the need to splice
and crimp wire
Dimensions: See reverse side for dimensional drawings and ordering information
Piezo Dynamic Series
(PD) SIRENS
SPECIFICATIONS
WAVE2PD o.ss° ",.,o"
Sound Output ,,ao�� -�
• 105dB @ 1 meter � \�
� 'C,��� 0.15�
�
CUYCeIIt DPaW � MO�NriNG � \
• 120mA � �� `��"°��s T
4.46" / � /� 3.15„
Operation Voltage ` \ �
• 12VDC � � ' ���
�. c � R������w
I
�"
� �_/
��
�3.25" I
\\�
Dimensional Drawing for WAVE2PD Siren
^i.sa�
y
�0.90'
747PD i.zs��.� o.�������
�
SOUIICI OUtpUt ��, MNONTiNG \
• 105dB @ 1 meter \ � �o�qrFO��
Current Draw ����
a.zs' ��
• 120mA ���;� � /' s.�s�
Operation Voltage �'�\� ��
• 12VDC \\\\ aEaR��Ew �,,J�,
��
\I\�\\�\
� � � ��a.2s^
- . � i
\yl
Dimensional Drawing for 747PD Siren
ORDERING
WAVE2PD Piezo Dynamic Siren
WAVE2PDT Piezo Dynamic Siren with Tamper
747PD Piezo Dynamic Siren
747PDT Piezo Dynamic Siren with Tamper
Honeywell Security&Custom Electronics Hon��Gll
Honeywell International Inc.
PO Box 9035 P�osooa
UPIEZODYN/D
Syosset, NY 11791 May 2oos
02006 Honeywell International Inc.
www.honeywell.com
Honeywell
VISTA-128BPT SERIES
PARTITIONED COMMERCIAL BURGLARY
ALARM CONTROL PANELS .�
� �� _
�_.
, �.
i i�„ . t
The VISTA-128BPT is a powerful member of the Honeywell The VISTA-128BPT and VISTA-128BPTSIA are listed for
family of commercial alarm panels, integrating burglary, CCTV residential burglary, residential fire and commercial burglary
and access control functions. Many features are available that applications(see agency listings in this document for
extend the applications of the VISTA-128BPT while simplifying more details).They are compatible with a wide range of
end-user operation. AlarmNet communications products for alarm reporting,
uploading/downloading and remote services.
FEATURES
Standard features • Zone 7 may be used for keyswitch • Group bypass
(VISTA-128BPT and VISTA-128BPTSI�: arming/disarming • Arm faulted
• Provides nine style-B hardwired zones • Integrates with WIN-PAK access . Event arming
• Supports up to 119 additional zones control systems to provide increased
using a built-in polling (V-Plex�, users, event log and scheduling • Carbon monoxide(CO)zone
multiplex) loop interface • Supports V-Plex addressable type support
• Supports up to 127 wireless zones VistaKey access control (up to eight • Expanded high-speed RS-232
using up to two 5800 series wireless doors and 250 cards) capability for third party interface
receivers (fewer if using hardwire • Easily programmed and maintained and automation
and/or polling loop zones) by Compass Windows-based • Internet upload/download
• Provides one power-limited bell circuit downloader over AlarmNet GSM and/or
deliverin 1.7Am max at 12VDC IP communicators over the panel's
9 p ( ) • Supports up to 96 programmable keypad (ECP) bus
• Provides the ability to control eight outputs
se arate artitions inde endentl , • Ringback support for AlarmNet
p p p Y • Programmable to meet SIA false communicators (confirmation of
each functioning as if it had its own alarm prevention specifications.
separate control To meet UL approval for ANSI/SIA closing report)
•Accommodates 150 user codes with CP-01-2010, order part number • 24-hour dialer test support for
seven authority levels V128BPTSIA AlarmNet devices
•Accommodates 32 keypad macro • Supports up to six touchscreen • Supports V-Plex Smart Contact
commands per system Advanced User Interface(AUI) feature for improved responsiveness
• Keeps a log of up to 512 events
devices(6272 or later) on systems with many V-Plex zones
• Supports up to 16 compatible
• Smoke detector reset at keypad •Telco line cut detection
two-wire smoke detectors on zone 1 • Quick exit
VISTA-128BPT SERIES
PARTITIONED COMMERCIAL BURGLARY ALARM CONTROL PANELS
ADDITIONAL FEATURES
Basic Hardwired Zones Wireless Expansion Eight Partitions
Provides nine style-B hardwired zones Supports up to 127 wireless zones Provides the ability to control eight
with the following characteristics: using up to two 5800 Series wireless separate areas independently, each
• EOLR supervision (optional for zones receivers (fewer if using hardwire functioning as if it had its own separate
2-8) supporting N.O. or N.C. sensors and/or polling loop zones). control. Partitioning features include:
(EOLR supervision required for fire Wireless zones have the following •A Common Lobby partition (1-8),
and UL burglary installations) characteristics: which can be programmed to arm
• Individually assignable to one of • Supervised by control panel for automatically when the last partition
eight partitions check-in signals (except certain that shares the common lobby is
• Up to 16 two-wire smoke detectors non-supervised transmitters) armed, and to disarm when the first
on zone 1 •Tamper protection for supervised Partition that shares the common
• Four-wire smoke or heat detectors transmitters
lobby is disarmed
•A Master partition (9), used strictly to
on zones 1-8 (power to four-wire • Individually assignable to one of assign keypads for the purpose of
smoke detectors must be supervised eight partitions viewing the status of all eight partitions
with an EOL device). Listed for Scheduling at the same time(master keypads)
residential fire only.
Provides the following scheduling •All zones assignable to one of
Polling Loop Expansion capabilities: eight partitions
Supports up to 119 additional zones . Open/close schedules (for control of • Keypads assignable to one of eight
using a built-in polling (V-Plex, multiplex) arming/disarming and reporting) partitions or to Master partition 9 to
loop interface. Current draw can total
up to 128mA. Polling loop zones have ' Holiday schedules (allows different view system status
time windows for open/close •Abilit to assi n rela s to one or all
the following characteristics: y g y
schedules) eight partitions
• Must use V-Plex devices
•Timed events (for activation of relays, .Ability to display fire and/or burglary
• Supervised by control panel auto-bypassing and unbypassing, and panic and/or trouble conditions
• Individually assignable to one of auto-arming and disarming, etc.) at all other partitions' keypads
eight partitions • Access schedules (for limiting system (selectable option)
• Supports VSI Module access to users by time) • Individually programmable account
• Supports 4297 Expander Module • End user output programming mode number, entry delay and exit delay
• Maximum wiring distance — (provides 20 timers for output control) by partition
12,000 feet
V-Plex Loop �.
, � - N�,� ��— . ,>�. .
`- — � 5193
41015N DT7500SN FG1625SN Glassbreak 4208EX Eight-zone 4293SN Adapters Series Smoke Detectors
Relay Module V-Plex DUAL TEC V-Plex Expander and I
Motion Sensor 4208SN Serialized Eight-zone
Remote Point Module � 5881
ECP Bus Wireless
' Receiver
. _ �
6160
710 Console ' �=�
Strobe ?
Light VISTA-1288PT
4204 �
NoCiflcatlon ` Relay
Appliances ,• Keyswitch Module
� �4s Option
� �;` 4146 _ , ��
Serial Printer PC Connection �y '�-��� I � Phone Line to Central Station
� 748
� Horn
RS232
' �� �, i �—or— --or — —
7847i GSMV iGSMV
NOTE:P/ease refer to the website(www.honeywell.com/security/hsc)for the latest product information.
VISTA-128BPT SERIES
PARTITIONED COMMERCIAL BURGLARY ALARM CONTROL PANELS
ACCESSORIES
Auxiliary Devices Passive Infrared Detectors • 5819 - Shock Sensor
• 4204 - Relay Module, four form • IS2500SN • 5827BD - Bidirectional Keypad
C contacts • DT7500SN • 5853 - Glassbreak Detector
• 5881 Series - RF Receiver supporting V-Plex(Addressable) Contacts • 5898 -Wireless DUAL TEC
5800 wireless detectors
• 6160 -Alpha Keypad/Annunciator
• 4939SN-WH Motion Sensor
• 4944SN-WH • 5800PIR-OD - Outdoor Motion Sensor
• 6220S - System Printer • 5870API -Asset Protection Device
Manual Pull Stations • 4959SN
V-Plex Glassbreak Detectors • 5800PIR/5800PIR-RES/5800PIR-COM
• 5140MPS-1 -Wireless Motion Detectors
• 5140MPS-2 • FG1625SN • 580000 (580000A- Canada) -
V-Plex (addressable) Devices VISTA Interactive Phone Module Wireless Carbon Monoxide Detector
• 4101SN Single Relay/Zone Module • 4286 VIP Module • 5800RP -Wireless Repeater
• 4190SN Remote Point Module - Optional Communicators • 5808W3 (5808W3A- Canada) -
two zones •AlarmNet Internet/Intranet Wireless Smoke Detector
• 4193SN Two-zone Serial Interface communicators and digital cellular • 5809 -Wireless Heat Detector
Module communicators Commercial Listed
• 4208EX- Eight-zone expander for Access Control Wireless Devices
ULC commercial installations •VISTAKey V-Plex(addressable) • 5817CB - Commercial UL Burglary,
• 4208SN Loop Expansion Module- Access Control Universal Contact Monitoring
eight zones •VISTAKey-SK Starter Kit Transmitter`
• 4209U Group Zoning Module- •VISTAKey-EX Expansion Kit • 5869 - Commercial UL Wireless
two/four zones Hold-up Button"
Wireless Devices • 5881 ENHC and 5883H Receivers
• 4293SN One-zone Serial • 5804 -Wireless Key
Interface Module �wnen�5ed w�tn sa8i ENHC a�aior
• 4297 Isolation/Extender Module • 5804BD - Bidirectional Key 5883H receiver.
•VSI Short/Overload Isolation Module ' 5804BDV- Bidirectional Key
with voice
• 5193SD • 5816 - Door/Window Transmitter
• 5193SDT
1
� �
� � 4190SN 4959SN 4944SN�M` � 'J�
4193SN Remote Point Module Overhead Door Contact Contact ��
IS2500SN 4208U Two-zone Serial Interface Module -
V-Plex PIR Eight-zone
Motion Sensor Expansion Module � 5808W3 VISTAKey V-Plex
5881 ENHC (5808W3A-Canada)���� Glassbreak Detectors Acc�odu entrol
Commercial Wireless Receiver Wireless . .
ECP Bus (Max Two) Smoke Detector ``t"` 5800
� Series
Wireless — 5800PIR Series � �
_ �1"." 6160 5816 � Devices Wireless PIRs ..�
Console DoorNVindow �_ '/ y � —
: �' Transmitter I \ ' 4 42�9�
- Group Zoning
�� Module ��
5869 '��l Q
Commercial UL' � � � Supports Up To
4204 Wireless Hold-up 58VCB Universal ' 16 Conventional -
' Rela Button ContactMonitoring Two-Wire ��
Y �� Smoke Detectors
- �� Module Transmitter
VISTA-128BPT SERIES
PARTITIONED COMMERCIAL BURGLARY ALARM CONTROL PANELS
SPECIFICATIONS
Agency Listed to the Electrical • Standby Time: Four hours min. with
Following Standards: •Voltage Input: From Honeywell No. 750mA aux. load using 7AH battery
• UL609 Grade A Local Mercantile 1361 Plug-In Transformer or • Circuit Protectors: PTC circuit
Premises and Mercantile Safe 1361 X10 transformer(for X-10 breakers are used on battery input to
and Vault installations)rated 16.5VAC,40 VA protect against reverse battery
• UL1610 Grades A, AA • Use 1361 CN plug-in transformer connections and on alarm sounder
Central Station for Canada output to protect against wiring faults
• UL365 Grades A, AA Police Connect •Alarm Sounder Output: (shorts). A solid state circuit breaker
10VDC-13.8VDC, 1.7 am s max., is used on auxiliary power output to
• UL985 Household Fire p protect against wiring faults(shorts).
• UL1023 Household Bur lar Alarm (UL1023, UL609 installations);
g 750mA less aux. current draw Main Dialer
California State Fire Marshall (CSFM) (UL985 installations) • Formats Supported: ADEMCO
• UL1635 - Digital Alarm •Auxiliary Power Output: 9.6VDC- Contact ID with support for four-digit
Communicator System Units 13.8VDC, 750mA max. For UL and ten-digit accounts and
• CAN/ULC - S303 installations, the accessories ADEMCO 4 + 2 Express
• CAN/ULC - S304 connected to the output must be UL • Line Seize: Double Pole
• CAN/ULC - S545 Listed, and rated to operate in the . Ringer Equivalence: 0.7B
• CAN/ULC - S1023 above voltage range Cabinet Dimensions
• Backup Battery: 12VDC, 4AH or 7AH
• For commercial burglary attack sealed-lead acid. YUASA NP4-12 12-1/2" W X 14 1/2" H X 3" D
proof requirements, use N5873V4BE (12V, 4AH)or NP7-12 (12V, 7AH)
attack proof enclosure provided in recommended
VISTA-ULKT kit
ORDERING
VISTA-128BPT Commercial Burglary Alarm Control Panel (UL Listed)
V128BPTSIA SIA Approved Enhanced Commercial Burglary Alarm Control Panel (UL Listed)
V128BPTCNKT VISTA-128BPT Commercial Burglary Alarm Control Panel with 1361 CN Transformer(Canada only)
For more information:
www.honeywel I.com/security/hsc
Automation and Control Solutions
Honeywell Security&Communications
2 Corporate Center Dr. Suite 100 Honeywell
P.O. Box 9040
Melville, NY 11747
1.800.467.5875 wsTai 2aaPTOio
April 2011
www.honeywell.com OO 2011 Honeywell International Inc.