HomeMy WebLinkAboutB13-0455 COMCHECK.pdf COMcheck Software Version 3.9.2
Interior Lighting and Power
Compliance Certificate
90.1 (2007) Standard
Section 1: Project Information
Project Type: New Construction
Project Title :Sitzmark Lodge workout room
Construction Site: Owner/Agent: Designer/Contractor:
Vail,CO AEDG
1900 Wazee Street#350
Denver,CO 80202
Section 2: Interior Lighting and Power Calculation
A B C D
Area Category Floor Area Allowed Allowed Watts
(M) Watts/ft2 (B x C)
Common Space Types:Electrical/Mechanical 19 1.5 29
Gymnasium/Exercise Center:Exercise Area 178 0.9 160
Total Allowed Watts= 189
Section 3: Interior Lighting Fixture Schedule
A B C D E
Fixture ID:Description/Lamp/Wattage Per Lamp/Ballast Lamps/ #of Fixture (C X D)
Fixture Fixtures Watt.
Common Space Types:EIectrical/Mechanical(19 sq.ft.)
Linear Fluorescent 1:F1:24"long strip:24"T8 17W:Electronic: 1 1 22 22
Gymnasium/Exercise Center:Exercise Area(178 sq.ft.)
Track lighting 1:T1:Track:Wattage based on low-voltage transformer capacity 0 0 60 75
Track lighting 2:T1:Track:Wattage based on low-voltage transformer capacity 0 0 60 40
Linear Fluorescent 2:W1:Vanity Light:22"T5 14W:Electronic: 1 1 18 18
Compact Fluorescent 1:S1:Shower:Triple 4-pin 13W:Electronic: 2 1 25 25
Total Proposed Watts= 180
Design Interior Lighting PASSES: better than code.
Section 4: Compliance Statement
Compliance Statement: The proposed lighting design represented in this document is consistent with the building plans,specifications and
other calculations submitted with this permit application.The proposed lighting system as been designed to meet the 90.1 (2007)Standard
requirements in COMcheck Version 3.9.2 and to comply with the mandato y requirem is in he Requirements Checklist.
Jeff Mullikin 10/8/13
Name-Title Signat r Date
Section 5: Post Construction Compliance Statement RE
'ST
35837
Record Drawings and Operating and Maintenance Manuals: �'.• z
p •.
L3 1. Construction documents with record drawings and operating and maintenance manuals provided to the owner.
�NALE
Project Title: Sitzmark Lodge workout room Report date: 10/08/13
Data filename:J:\2579.00-Sitzmark Changing Room\Ltg Calcs\257900EC01.cck Page 1 of 2
Lighting Designer or Contractor Name Signature Date
Project Title: Sitzmark Lodge workout room Report date: 10/08/13
Data filename:J:\2579.00-Sitzmark Changing Room\Ltg Calcs\257900ECO1.cck Page 2 of 2
fZCOMcheck Software Version 3.9.2
Inspection Checklist
Requirements: 0.0% were addressed directly in the COMcheck software
Text in the"Comments/Assumptions"column is provided by the user in the COMcheck Requirements screen. For each requirement,
the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed.Where
compliance is itemized in a separate table,a reference to that table is provided.
90.1 (2007) Plan Review Complies? Comments/Assumptions
Standard
4.2.2 Plans,specifications,and/or calculations ❑Complies
[PR4]' provide all information with which ❑Does Not Comply
compliance can be determined for the ❑Not Observable
lighting and electrical systems and ❑Not Applicable
equipment and document where exceptions
to the standard are claimed. Information
provided should include interior lighting
power calculations,wattage of bulbs and
ballasts,transformers and control devices.
8.4.1.1, Plans,specifications,and/or calculations ❑Complies
8.4.1.2 provide all information with which ❑Does Not Comply
[PR6]2 compliance can be determined for the ❑Not Observable
electrical systems and equipment and ❑Not Applicable
document where exceptions are claimed.
Feeder connectors sized in accordance
with approved plans and branch circuits
sized for maximum drop of 3%.
Additional Comments/Assumptions:
1 1 High Impact(Tier 1) 2 1 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Sitzmark Lodge workout room Report date: 10/08/13
Data filename: J:\2579.00-Sitzmark Changing Room\Ltg Calcs\257900EC01.cck Page 1 of 4
90.1 (2007) Rough-In Electrical Inspection Complies? Comments/Assumptions
Standard
9.4.1.1 ;Automatic controls to shut off all building ❑Complies
[EL1]2 lighting installed in buildings>5,000 ft2. ❑Does Not Comply
❑Not Observable
❑Not Applicable
9.4.1.2 Independent lighting controls installed per ❑Complies
[EL2]2 :approved lighting plans and all manual ❑Does Not Comply
controls readily accessible and visible to ❑Not Observable
;occupants.
_-]Not Applicable
9.4.1.4 Separate lighting control devices for specific ❑Complies
[EL4]' uses installed per approved lighting plans. ❑Does Not Comply
❑Not Observable
❑Not Applicable
9.4.2 Ballasted one and three lamp fixtures with ❑Complies
[EL5]3 >30 W/lamp have two lamp tandem wired ❑Does Not Comply
j ballasts when2 fixtures in same space ❑Not Observable
on same control. j❑Not Applicable
9.4.3 Exit signs do not exceed 5 watts per face. ❑Complies
[EL6]' ❑Does Not Comply
❑Not Observable
❑Not Applicable
9.6.2 Additional interior lighting power allowed for ❑Complies
[EL8]' special functions per the approved lighting ❑Does Not Comply
plans and is automatically controlled and ❑Not Observable
separated from general lighting. ❑Not Applicable
Additional Comments/Assumptions:
1 1 High Impact(Tier 1) 2 1 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Sitzmark Lodge workout room Report date: 10/08/13
Data filename: J:\2579.00-Sitzmark Changing Room\Ltg Calcs\257900EC01.cck Page 2 of 4
90.1 (2007) Final Inspection Complies? Comments/Assumptions
Standard
8.7.1 Furnished as-built drawings for electric ❑Complies
[FI16]3 power systems within 30 days of system ❑Does Not Comply
acceptance. ❑Not Observable
❑Not Applicable
8.7.2 Furnished O&M instructions for systems ❑Complies
[FI17]3 and equipment to the building owner or ❑Does Not Comply
designated representative. ❑Not Observable
❑Not Applicable
9.2.2.3 Interior installed lamp and fixture lighting ❑Complies See the Interior Lighting fixture schedule for values.
[FI18]' power is consistent with what is shown on ❑Does Not Comply
the approved lighting plans,demonstrating ❑Not Observable
proposed watts are less than or equal to ❑Not Applicable
allowed watts.
Additional Comments/Assumptions:
1 1 High Impact(Tier 1) 2 1 Medium Impact(Tier 2) 3 1 Low Impact(Tier 3)
Project Title: Sitzmark Lodge workout room Report date: 10/08/13
Data filename: J:\2579.00-Sitzmark Changing Room\Ltg Calcs\257900EC01.cck Page 3 of 4
Project Title: Sitzmark Lodge workout room Report 10/08/13
Data filename: J:\2579.00-Sitzmark Changing Room\Ltg Calcs\257900EC01.cck Page 4 of 4