HomeMy WebLinkAboutA13-0070 cut sheet �L�CO SIMPLEXGRINNELL 6240 Smith Road Fire & Denver, Colorado 80216 Securit y wwwsimplexqrinnell.com Simp/exG�inne// Tele: (303) 355-0500 Fax: (303) 355-0615 Fire Alarm Product Data Submittal for: Vail Valley Medical Center VVMC Elevator Upgrade 181 W Meadow Dr. Vail, CO 81658 iVtii�� i A�L°i°i i ii°oi.::�t i Ivo�+u TECHNICAL ARF?. 003n}�, LEUEL IV V'ERTIFlCATE $: 10935g / .� \•ALID THPOUGH 09/G1j15 � ; I'HE SUPhkb9�I�N ('F A NICET IV NICET �I � "iCWED F(�P. Tllf' IIJFORI�AiION CONTAINCD � CEfll7RED �', =��+r -i7[r� .,, � i r� i�1 ei ir�nei.0 9//9�3 Encore Electric 77 Metcalf, Suite 200, PO Box 8849 Avon, �O 81620 Sir»p/exG�inne// 6240 Smith Road Denver, Colorado 80401 Sales: (303) 355-0500 Service: (303) 355-0500 Fax: (303) 355-0615 PROJECT: Vail Valley Medical Center VVMC Elevator Upgrade PREPARED FOR: Encore Electric TYPE: DESCRIPTION: 4098-9714 PHOTO SENSOR 4098-9733 HEAT SENSOR 4098-9792 SENSOR BASE 2190-9163 ADDRESS. MODULE - RELAY �oSimplEx TrueAlarm Analog Sensing UL, ULC, CSFM Listed; FM Approved; TrueAlarm Analog Sensors — Photoelectric MEA (NYC) Acceptance* and Heat; Standard Bases and Accessories � TrueAlarm analog sensing provides: • Digital transmission of analog sensor values via IDNet � or MAPNET lI two-wire communications For use with the following Simplex°products: • 4100ES,4100U,4010ES,and 40]0 Series control panels; and 4008 Series control panels with reduced 1 1 feature set(refer to data sheet 54008-0001 for details) — • 4020,4100,and 4120 Series control panels,Universal Transponders,and 2120 TrueAlarm CDTs equipped 4098-9714 TrueAlarm Photoelectric for MAPNET II operation Sensor Mounted in Base Fire alarm control panel provides: • Peak value logging allowing accurate analysis of each � ' • • sensor for individual sensitivity selection • Sensitivity monitoring satisfying NFPA 72 sensitivity Digital Communication of Analog Sensing. testing requirements;automatic individual sensor TrueAlarm analog sensors provide an analog calibration check verifies sensor integrity measurement digitally communicated to the host control • Automatic environmental compensation,multi-stage panel using Simplex addressable communications.At the control panel,the data is analyzed and an average value is alarm operation, and display of sensitivity directly in determined and stored.An alarm or other abnormal percent per foot condition is determined by comparing the sensor's present • Ability to display and print detailed sensor value against its average value and time. information in plain English language Intelligent Data Evaluation.Monitoring each sensor's PhotoeleCtric smoke sensors provide: average value provides a continuously shifting reference • Seven levels of sensitivity from 0.2%to 3.7% point. This software filtering process compensates for (refer to addirional informarion on page 3) environmental factors(dust,dirt,etc.)and component Heat sensors provide: aging,providing an accurate reference for evaluating new • Fixed temperature sensing activiry.With this filtering,there is a significant reduction • Rate-of-rise temperature sensing in the probability of false or nuisance alarms caused by shifts in sensitivity,either up or down. • Utility temperature sensing • Listed to UL 521 and ULC-S530 Control Panel Selection.Peak activity per sensor is stored to assist in evaluaring specific locarions. The alarm General features: set point for each TrueAlarm sensor is determined at the • Listed to UL 268 and ULC-S529 host control panel, selectable as more or less sensitive as • Louvered smoke sensor design enhances smoke the individual application requires. capture by direcring flow to chamber; entrance areas Timed/Multi-Stage Selection. Sensor alarm set points are minimally visible when ceiling mounted can be programmed for timed automatic sensitivity • Designed for EMI compatibiliry selection(such as more sensitive at night,less sensitive • Magnetic test feature is provided during day).Control panel programming can also provide • Optional accessories include remote LED alarm multi-stage operation per sensor.For example,a 0.2% indicator and output relays level may cause a warning to prompt investigation while a Additional base reference: 2.5°/o level may initiate an alarm. • For isolator bases,refer to data sheet 54098-0025 Sensor Alarm and Trouble LED Indication.Each • For sounder bases,refer to data sheet 54098-0028 sensor base's LED pulses to indicate communications with the panel.If the control panel determines a sensor is • For photo/heat sensors,refer to data sheet S4098-0024 in alarm,or is dirry ar has some other type of trouble,the (single address)and 54098-0033 (dual address) details are annunciated at the control panel and that sensor ' m��xnd�r,��,a�o�ed eytne c,��fo�„�a st�te F�nro�r,�(csFn���,t to base's LED will be turned on steadily. During a system sect�a,�s�aa.�ortnecai�fa„�a�tnandsarerycode.seecsFrvtust��s alarm the control anel will control the LEDs such that 7272-0026:218,7271-0026231,7270-0026216,and 7300-0026217 fa allo�ble values � p arxuor oonditions ooncernir,g rreterial preserted in tnis doaamer,t.acoepted tor use—atyof an LED indicating a trouble will return to pulsing to help NewYalcDepartmentofBuildings—NEA3.5-93EPdditiaial listingsrrnybeapplicable, identify the alarmed sensors. contact your local Sirrplex product supplier for the latest status.Listirx�s and appra�als under Slrrplex Trre Reca-der Co.are the property of Tyco Rre Rotedion Raluds. S4098-0019-15 4/2013 TrueAlarm Sensor Bases and Accessories ■ - . . . TrueAlarm sensor bases contain integral addressable electronics that constantly monitor the status of the Base mounted address selection: detachable photoelectric or heat sensors. Each sensor's • Address remains with its programmed location output is digitized and transmitted to the system fire alarm • Accessible from front(DIP switch under sensor) control panel every four seconds. General features: Since TrueAlarm sensors use the same base,different • Automatic identificarion provides default sensiriviry sensor types can be easily interchanged to meet specific when substituting sensor types location requirements. This feature also allows intentional • Integral red LED far power-on(pulsing),or alarm or sensor substitution during building construction.When trouble(steady on) conditions are temporarily dusty, instead of covering the • Locking anti-tamper design mounts on standard outlet smoke sensors(causing them to be disabled),heat sensors box may be installed without reprogramming the control panel. Although tbe control panel will indicate an • Magnetically operated functional test incorrect sensar type,the heat sensor will operate at a � default sensitivity providing heat detection for building protection at that location. 4098-9792, Standard sensor base 4098-9789, Sensor base with wired connections for: � � • 2098-9808 Remote LED alarm indiCator or 4098-9822 Electrical Box Requirements:(boxes are by others) relay(unsupervised) Without relav:4"octagonal or 4"square,1-1/2"deep; 4098-9791,Sensor base with supervised relay driver single gang,2��deep output(not compatible with 2120 CDT): w�tn relav:a"octagonal or 4"square,1-1/2"deep, • Relay operation is programmable and can be manually witn i-�/2"extension ring operated from control panel a^(102 mm)Square Box a^(102 mm)Octagonal Box • Use with remote mount 2098-9737 relay surface mount�efe�ence • Also includes wired connections for remote LED alarm indicator or 4098-9822 relay �` � � � � ' U � u �J • • • • 2098-9737, Remote or local mount supervised relay: �-�i2��(38 mm) minimum box depth • DPDT contaCts for resistive/suppressed loads,power Flush mount reference,mount even with final limited Cating of 3 A@ 28 VDC;non-power limited surface,or with up to 1/4"(6.4 mm)maximum recess rating of 3 A@ 120 VAC(requires external 24 VDC ' � ;2098-9737 Relay(mounts in 4098-9822 Relay(mounts � COI� pOWei� ;base electrical box or remotely) in base electrical box) � 4098-9822, LED Annunciation Relay: ; � � ; • Activates when base LED is on steady,indicating local � ; alarm or trouble ' � � ; • DPDT contacts for resistive/suppressed loads,power � ; limited rating of 2 A@ 28 VDC;non-power limited � ; rating of 1/2 A@ 120 VAC,(requires external 24 VDC ; � COIl pOW2T� ; Relay Size: 2-1/2"X 1-1/2"X 1"(375 cubic inches) ; (64mmX38mmX25.4mm) � 4098-9832,Adapter plate: ; � , NOTE:Review total wire count,wire size,and accessories � • Required for surfaCe or semi-flush mounting to � being wired to determine required box volume. ; 4"square electrical box and for surface mounting to '---------------------------------------------% 4"octagonal box �� 6-3/8"(162 mm) � • Can be used for cosmetic retrofitting to existing 6-3/8" dlameteT'baSe pl'OdUCt - � 4098-9832 Adapter Plate,re�c uired for 2098-9808, Remote red LED Alarm ��4�� mounting to surface mounted boxes � (6.4 mm) and 4"sauare flush box Indicator: • Mounts on single gang box �. 4-7/8"(124 mm) -� ALARM (shown in illustration to right) �o �5/�s" (24 mm) p }3�m�� TrueAlarm Bases 4098-9789,-9791,&-9792 � 2 S4098-0019-15 4/2013 TrueAlarm Sensors � , . . � Sealed against rear air flow entry TrueAlarm heat sensors are self-restoring and provide rate Interchangeable mounting compensated, fixed temperature sensing, selectable with EMI/RFI shielded electronics or without rate-of-rise temperature sensing.Due to its Heat sensors: small thermal mass,the sensor accurately and quickly • Selectable rate compensated,fixed temperature measures the local temperature for analysis at the fire sensing with or without rate-of-rise operation alarm control panel. • Rated spacing distance between sensors: Rate-of-rise temperature detection is selectable at the control panel for either 15°F(8.3°C)or 20°F(11.1°C) Fixed Temp. UL&ULC FM Spacing,Either Fixed per minute. Fixed temperature sensing is independent of Setting Spacing Temperature Setting rate-of-rise sensing and programmable to operate at 135°F 60 ft x 60 ft �0 ft x 20 ft(6.1 m)for fixed 135°F(572°C)or 155°F(68°C).In a slow developing (57.2°C) (18.3 m) temperature only;RTI=Quick 5o ft x 5o ft(�5.z m)for fixed fire,the temperature may not increase rapidly enough to 155°F 4o ft x 40 ft temperature with either rate-of-rise operate the rate-of-rise feature.However,an alarm will be (ss°C) (�2.2 m) selection;RTI=ultra Fast initiated when the temperature reaches its rated fixed Smoke Sensors: temperature setting. • Photoelech-ic technology sensing TrueAlarm heat sensors can be programmed as a utility • 360°smoke entry for optimum response device to monitor for temperature extremes in the range from 32°F to 155°F(0° C to 68°C).This feature can • Built-in insect screens provide freeze warnings or alert to HVAC system problems.Refer to specific panels for availabiliry. � 1 • ' • • • - • -7/8"(124 mm) TrueAlarm photoelectric sensors use a stable,pulsed infrared LED light source and a silicon photodiode ���—�E�status indicator receiver to provide consistent and accurate low power 2-3/8" smoke sensing. Seven levels of sensitivity are available (60 mm) for each individual sensor,ranging from 0.2%to 3.7%per foot of smoke obscuration. Sensitivities of 0.2%,0.5%, and 1%are for special applications in clean areas. Standard sensitivities are 1.5%,2.0%,2.5%, and 3.7°/o. Sensitivity is selected and monitored at the fire alarm 4098-9733 Heat Sensor with Base control panel.* The sensor head design provides 360° smoke entry for WARNING: In most fires, hazardous levels of smoke optimum response to smoke from any direction. Due to its and toxic gas can build up before a heat detection photoelectric operation,air velocity is not normally a device would initiate an alarm. In cases where Life factor,except for impact on area smoke flow. Safety is a factor,the use of smoke detection is highly recommended. -. 4-7/8"(124 mm) - II��LED status indicator . � � � 2-1/8" (54 mm) Sensor locations should be determined only after careful consideration of the physical layout and contents of the area to be protected.Refer to NFPA 72,the National Fire Alarm and Signaling Code. On smooth ceilings, smoke 4098-9714 Photoelectric Sensor with Base sensor spacing of 30 ft(9.1 m)may be used as a guide.* * For detailed application information including sensitivity selection, refer to Installation Instructions 574-709. 3 S4098-0019-15 4/2013 - � � . . . . . . TrueAlarm Sensor Bases (Refer to Application Manual 574-709 and Installation Instructions 574-707 for additional information) Model Description Compatibility Mounting Requirements 4098-9792 Standard Sensor Base,no options Sensors 4098-9714 and 4098-9733 4"octagonal or 4"square box, 1-1/2"min. depth;or single gang box,2"min.depth Sensor Base with connections for Sensors 4098-9714 and 4098-9733 4"octagonal or 4"square box 4098-9789 Remote LED Alarm Indicator or 2098-9808 remote LED alarm Unsupervised Relay indicator or 4098-9822 relay Note:Box depth requirements depend on Sensors 4098-9714 and 4098-9733 total wire count and wire size,refer to Sensor Base with connections for accessories list below for reference. Supervised Remote Relay and 2098-9737 remote relay(supervised) 4098-9791** connections for Remote Alarm **NOTE:4098-9791 is NOT compatible 2098-9808 remote alarm indicator or With the 2120 CDT Indicator or Unsupervised Relay 4098-9822 relay(unsupervised) TrueAlarm Sensors Model Description Compatibility Mounting Requirements 4098-9714 Photoelectric Smoke Sensor Bases 4098-9792,4098-9789, 4098-9733 Heat Sensor and 4098-9791 Refer to base requirements TrueAlarm Sensor/Base Accessories Model Description Compatibility Mounting Requirements Remote Mounting requires 4"octagonal or 2098-9737 Supervised Relay,mounts remote For use with 4098-9791 base 4"square box, 1-1/2"minimum depth or in base electrical box Base Mounting requires 4"octagonal box, 2-1/8"deep with 1-1/2"extension ring 2098-9808 Remote Red LED Alarm Indicator Single gang box, 1-1/2"minimum depth on single gang stainless steel plate Relay,tracks base LED status Bases 4098-9789 and 4098-9791 4098-9822 (unsupervised,mounts only in base 4"octagonal box,2-1/8"deep with 1-1/2" electrical box) extension ring Required for surtace or semi-flush 4098-9832 Adapter Plate Bases 4098-9792,-9789,&-9791 mounted 4"square box and for surface mounted 4"octagonal box . - . • General Operating Specifications Communications and Sensor Supervisory Power MAPNET II or IDNet,auto-select,24-40 VDC w/data,400µA typical, 1 address per base Communications Connections Screw terminals for in/out wiring, 18 to 14 AWG(0.82 mmZ to 2.08 mm2) Remote LED Alarm Indicator Current 1 mA typical,no impact to alarm current Remote LED Alarm Indicator and Relay Connections Color coded wire leads, 18 AWG(0.82 mm2) UL Listed Temperature Range 32°to 100°F(0°to 38°C) with 4098-9733 32°to 122°F(0°to 50°C) Operating Temperature Range with 4098-9714 15°to 122°F(-9°to 50°C) Humidity Range 10 to 95%RH Smoke Sensor 4098-9714, Air velocity=0-4000 ft/min(0-1220 m/min) Ambient Ratings Photoelectric Sensor Housing Color Frost White 4098-9791 Base With Supervised Remote Relay 2098-9737(see page 2 for contact ratings) Externally Supplied Relay Coil Voltage 18-32 VDC(nominal 24 VDC) Supervisory Current 270µA,from 24 VDC supply Alarm Current with 2098-9737 Relay 28 mA,from 24 VDC supply 4098-9822 Unsupervised Relay, Requirements for Bases 4098-9789 and 4098-9791 (see page 2 for contact ratings) Externally Supplied Relay Coil Voltage 18-32 VDC(nominal 24 VDC) Supervisory Current Supplied from communications Alarm Current 13 mA from separate 24 VDC supply TYCO,SIMPLEX,and zhe product names listed ln this material are marks and/a�registered marks.Unauthorized use is strzctly pi�ohibited.NFPA 72 and Nationa7 Fire Alarm and Signaling Code ar�e trademarlrs of the Nalzona[Fire Protecfion Association(NFPA). �05 i m p I Ex Tyco Fire Protection Products• Westminster,MA•01441-0001•USA S4098-0019-15 4/2013 www.simplexgrinnell.com OO 20/3 Tyco Fire Protection Products.All righzs resc�ved.A!!spec�ificarioras ancl other ir fonnutt'on shown were current as of'docurnent revision dute and are subject to change without rzotice. ��Simplex MAPNET II° Communicating Devices UL, ULC, CSFM Listed; Zone Adapter Modules (ZAMs) FM Approved* Addressable Interface to Conventional Circuits � 0 0 MAPNET II ZAMs provide an addressable interface I „ O G to conventional fire alarm zone circuit devices** LJ I - - _ including: ° An=-� _ � �s° � • Initiating devices (Monitor ZAM) � � `�0°=°° " � � � • Notification appliance circuits (Signal ZAM) � 0 � o • Control relays (Control ZAM) � � � � � p� a e � These ZAMs are compatible with the following Simplex°fire alarm control panels when equipped with MAPNET II communications: O U • 4100/4100U Series fire alarm control panels SignaUControl ZAM • 4100 Series Universal Transponders • 4120 Series Network node fire alarm control panels O - - • 4020 Series fire alarm control panels ` _ _ - • 2120 Communicating Device Transponders � O `'�°; � ��o�roo 0 MAPNET II communications can be wired: � 0 n N m • NFPA Style 4/Class B or Style 6/Class A � O � • Style 4/Class B communications may be wired � 0 either"T"tapped or In/Out � Convenient DIP switch address selection O �J \ UL listed to Standard 864 Monitor ZAM � - . . MAPNET II zone adapter modules (ZAMs) provide � - • . � -� an addressable interface between conventional zone Control ZAMs provide addressable control functions devices and the host fire alarm control panel. such as elevator capture,HVAC control,pressurization Monitor ZAMS provide status monitoring and fan control,and damper control. The control relay supervision of an initiaring device circuit(IDC)zone and provides a DPDT contact(contact ratings are shown on are used for circuits with non-addressable detectors and page 4). for other contact closures such as waterflow and tamper switches or non-addressable manual stations.Different ' - ' ' models of Monitor ZAMs are available for two-wire IDCs Class B,or Class A,and for four-wire IDCs with Class B Communications Supplied by MAPNET II, IDC input.Each type required a separate 24 VDC input 24 to 40 VDC with data power from a listed fire alarm power supply. Power Separate 24 VDC required from listed fire alarm power supply Slgnal ZAMS supervise and operate 24 VDC notification Refer to reference diagrams on a liances, s eakers, and tele hone circuits. Ou ut Wiring Information pp p p � pages 3 and 4 capacity is up to 2 A@ 24 VDC,or 50 W of 25 VRMS speakers,or up to three simultaneously activated Wire Connections Screw terminals for in/out wiring, firefighter phones. The signa]ZAM is available for either 18 to 12 AWG wire Style Y/Class B or Style Z/Class A operation for Address Means DIP switch,8 position notificahon appliance circuits. 32° F to 120° F(0°C to 49°C) ' Tt,isproductnast�,app-ovedbytneCaiifomiastateFren�,rs�,ai(�pursua,tto Temperature Range intended for indoor operation Section 13144.1 of the Califomia F lealth and Safety Code.See CSFM Listing 73040026:182forallan�evaluESarxVoroonditiaiscorioemingmateri�presc-�itedinthis Humidity Range Up to 85% RH at 86° F(30°C) docurrerrt.It is subjed to re-e�nirration,revision,arid possible c�cellation.Pciditia� listings rrey be applicable,contact your local Sirrplex produ�supplier fa-the latest status. Listings and approvals urider Sirrplex Tme Recorder Co.are the�xoperty of Tyco Safety "` M�I'NET I I addressable cq171tanications are proteded by U.S.Patent No. Products V�strrinster. 4,796,025. S2190-0012-15 5/2010 . . . Zone Adapter Modules, Monitor ZAMs (separate 24 VDC power is required) Model Cover Type Description Supervisory Current Alarm Current 2190-9153 Surface Monitor ZAM, Class A(Style D) 2190-9154 Flush 2190-9155 Surface Monitor ZAM, Class B(Style B) 20 mA @ 24 VDC 90 mA @ 24 VDC 2190-9156 Flush 2190-9157 Surface 4-Wire Detector ZAM, Class B IDC input 2190-9158 Flush Zone Adapter Modules, Signal and Control ZAMs (separate 24 VDC power is required) Model Cover Type Description Supervisory Current Alarm Current 2190-9159 Surface Signal ZAM, Class A(Style Z) 15 mA @ 24 VDC 65 mA @ 24 VDC 2190-9160 Flush 2190-9161 Surface Signal ZAM, Class B(Style Y) 15 mA @ 24 VDC 2190-9162 Flush 40 mA @ 24 VDC 2190-9163 Surface Control Relay ZAM, DPDT Contacts 10 mA @ 24 VDC 2190-9164 Flush • � . . 4-11/16" (119 mm) Square box, 2-1/8" (54 mm) deep ��� �� �� �� �� �� / � o � Typ��ai zaM assembiy � � ° � � ° �J (� � � �� � o - -- :;�::: � � � � � �� �;o��o e o - o � � 0 � �-� �� ° ° � 4-11/16" (119 mm) o Square extension ring, sssm� �� 1-1/2 (54 mm) deep Flush cover, 5-7/16" 65implex o square (138 mm) Surface cover, 4-15/16" square (125 mm) 2 S2190-0012-15 5/2010 • • � • � . • + + 24 VDC Monitor Class B,Style B ZAM 2-Wire monitor circuit "T"Tapped + or IN/OUT MAPNET II _ wiring _ communications Shield � Monitor Monitor circuit circuit Resettable End of line Return Detector power relay Class A/Style D 4-Wire detector 2-Wire monitor circuit ZAM wiring • � • + t 24 VDC Class B/Style Y . notification appliance circuit(speakers shown for reference) �F " "T"Tapped or MAPNET II IN/OUT wiring communications Shield Signal input,audio or phone Primary � Class A/Style Z notification appliance circuit Return a Signal input,audio or phone 3 S2190-0012-15 5/2010 • • � • � . • Control ZAM .} N.C. 1 24 VDC Common 1 N.O. 1 + "T"Tapped or MAPNET II IN/OUT wiring communications - N.C.2 Shield Common 2 Controlled device N.O.2 Control Power • • � � � ' � • Application Resistive Rating Inductive Rating** Power Limited* 2 A@ 28 VDC 1 A@ 28 VDC 2A@28VDC 1 A@28VDC Non-Power Limited 1/2 A@ 120 VAC 1/2 A@ 120 VAC � DC Voltage must be from a listed Fire Alarm power supply. ** Inductive loads must be properly suppressed. Tyco is a r�egistered trademar-k of Tyco Inzernationn/Services GmbH and is used c�ncler license.Sim�ler,the Simplcr logo,and MAPNET 11 aee trademarks ofTyco International Ltd.and its affiliates und are used uncler license. �3 Simplex Tyco Safety Products Westminster• Westminster,MA•01441-0001•USA S2190-0012-15 5/2010 � www.tycosaferyproducts-usa-wm.com C 20/0 Tvco Safety Prroducts Weshninstee A!!nohts reserved.A!l spec�icarions and ather inforn�alion shown were curT�ent as of doc7�rnent revision dnte a�zd are subject to change without riotice.