Press Alt + R to read the document text or Alt + P to download or print.
This document contains no pages.
HomeMy WebLinkAboutB13-0395 PLANS APPROVEDB13-0395
RADER1
ENGINEERING • COMFORT SYSTEMSM
PO BOX 8610 • AMOR 00 816M • Telephone 970484,x7910
Fax 9705457522 • E4nsil dader@aderercjneering.com
9/17/13
Justin Nielsen
Skyline Mechanical
P.O. Box 1258
Gypsum, CO 81637
justin(&skkylinemechanical.com
RE: Vail's Front Door, Vail, CO
New Chimney Cap at Boiler Flue Chase
Justin,
It is our understanding that there is excessive ice build -up at the existing boiler flue chimney cap.
This is being caused by the fact that the cap is hemi cylindrical in shape (inverted U) and is
thereby trapping flue gases. The trapped flue gases are causing ice build -up and also corroding
the copper metal. See page 2 below for image.
It is our understanding that Skyline is proposing to replace this chimney cap at the boiler chase
with a new open top type chimney cap, as shown on page 3 below. The cap will be made
entirely of steel and will be powder coated for corrosion resistance. The proposed chimney cap
will be consistent with the other chimney caps on the building, and per the original architectural
drawings (sheet A525).
Rader Engineering approves of the proposed design. It has been our experience that an open top
chimney cap is the best method for concealing power vented boiler flues, while also allowing the
flue gases to be discharged straight vertically unimpeded into the atmosphere. We recommend
that the existing flues be extended vertically so that the top of the flue pipes are 3" higher than
the top of the chimney cap structure.
Please call with any questions.
Sincerely,
L/
Bryan J. Houle, P.E.
r0 , N . O(i F :•
46 9/17/13
3
9 . • �v
.o .� to
S70N A t- EN
RECEIVED
By DRHOADES at 1:16 pm, Sep 26, 2013
9/17/13 Vail's Front Door Page 1 of 3
Existing Chimney Cap to be Removed (note corrosion)
9/17/13 Vail's Front Door Page 2 of 3
Suggested structural frame for
Chalet Chimney cap replacement
r Existing Post X4
//,, 7-- EL n.,.
op o tom yp
Post X4
1 " Tube Steel frame
with Corrosion Resistant
powder coat finish
d Kexisting vertica of flue ' to
— Flues
shall
extend no
higher
than 1"
below the
top of the
cap.
Cap will be cladded in copper
to match existing chimneys
on the building.
Proposed Chimney Cap at Boiler Flue Chase