HomeMy WebLinkAboutA13-0073 cut sheets ���.Q SIMPLEXGRINNELL
6240 Smith Road
Fire & Denver, Colorado 80216
5ecurity
www.simplexgrinnell.com
Sim,p�►exGrinne►l Tele: (303) 355-0500
Fax: (303) 355-0615
Fire Alarm
Product Data Submittal for:
Lodge Tower
2120 U pg rade
200 Vail Road
Vail, CO 81657
Prepared for:
A K Electric
P.O. Vox 6241
Avon, Colorado 81620
Marcel
o�PDO LI�F�
�o.:�aA�,o•A sFa Proulx
'� 2013.09.23
.� 90 t
:� 44967 X;
9:, ::��. 12:02:22 -
��FSS�ONALEN���`` O4'OO'
Simpl+�x s►r►nn�►!
6240 Smith Road
Denver, Colorado 80401
Sales: (303) 355-0500
Service: (303) 355-0500
Fax: (303) 355-0615
PROJECT: 2120 Upgrade
PREPARED FOR: A K Electric
TYPE: DESCRIPTION:
4100-9620 BASIC AUDIO W/MIKE-ANALOG
4100-6052 EVENT/POINT REPORTING DACT
4100-6038 DUAL RS-232 IF CARD
4100-2300 EXPANSION BAY(PHASE 10 ONLY)
4100-1326 FLEX 50W AMP W/3 NACS-25V
4100-1294 LED/SWITCH SLIDE-IN LABEL KIT
4100-6079 SAFELINC INTERNET INTERFACE
4100-7153 INFOALARM 4100U UPGRADE
4100-1293 PANEL MOUNT PRINTER
4100-1288 64/64 LED/SWITCH CONTROLLER
4100-1280 8 SWITCH,8 RED LED MODULE
4100-1279 2"BLANK DISPLAY MODULE
4100-1252 AUDIO IF MODULE,SGL CHANNEL
4100-1241 MESSAGE EXPANSION,8 MINUTES
2081-9296 BATTERY 50AH
4100-9600 BASIC TRANSPONDER
4100-0621 ANALOG AUDIO RISER MODULE
4100-0636 BOX TO BOX HARNESS KIT
4100-0637 AUDIO BOX TO BOX HARNESS KIT
4100-0638 ADDITIONAL 24V HARNESS
4100-1248 100W NAC EXPANSION,6 CLASS B
4100-1315 100W AMP W/6 B NACS 120VAC 70V
4100-2300 EXPANSION BAY(PHASE 10 ONLY)
4100-2303 LEGACY CARD STABILIZER BRKT
4100-2320 AUDIO EXPANSION BAY
4100-5005 ZONE MODULE,8 IDC,CLASS B
4100-5101 XPS POWER,3 NACS, 120VAC
4100-5111 X SPS PWR, IDNET,3 NACS, 120V
4100-5115 XPS EXPANSION MODULE,3 NACS
2975-9446 3 BAY BB/GDOOR/DRESS PNLL PLAT
2975-9452 3 BAY BB/SDOOR/PLAT
4100-0634 POWER DISTRIBUTION MODULE 120V
4100-5128 BATTERY DIST TERM MODULE
2081-9279 BATTERY 110AH
2081-9280 BATT CAB ONLY F/2081-9279
4906-9153 SPKR/STROBE MC WHITE
4081-9008 EOL, 10K 1/2W
�oSimplEx 4100m Fire Control Panels
UL, ULC, CSFM Listed; FM Approved; Addressable Fire Detection and Control
MEA (NYC) Acceptance* Basic Panel Modules and Accessories
� — --
Master Controller(top) bay; � -d,����:�
• 32-Bit Master Controller with color-coded operator
interface including raised switches for high confidence _
feedback __----
J�� I
• Dual configurarion program CPU,convenient service port -
access, and capacity for up to 2500 addressable points -� "��� � � ��s
� �
• CPU assembly includes 2 GB dedicated compact flash ���
memory for on-site system programming and —
information storage — �
• System power supply(SPS)and charger(9 A total)with � �, �a '��' � I�� �
�imimim�mi�imimi�mimimim�
on-board:NACs,IDNet addressable device interface, ° - ��i�i iiiiiiiiiiiii��iumoiiui�mimimiiou
tlItlIIIItlINItlWtlIN�VI�I
programmable auxiliary output and alarm relay ������,,,,�,,,.,,,�.�.,
-
- -
-- — -- ----
• Available with InfoAlarm Command Center expanded ___ ____, __ -- __ _ _
content user interface(see data sheet 54100-0045) 4100ES Cabinets are Available with
• Upgrade kits are available for existing control panels One,Two or Three Bays
Standard addressable interfaces include:
• IDNet addressable device interface with 250 points that �
support TrueAlarm analog sensing and operate with CPU provides dual configuration programs:
either shielded or unshielded twisted pair wiring • Two programs allow for optimal system protection and
• Remote annunciator module support via RUI(remote commissioning efficiency with one active program and
unit interface)communications port one reserve
Optional modules include: . Downtime is reduced because the system stays running
• Building Network Interface Module(BNIC)for Ethernet during download
connectivity options(see data sheet S4100-0061) pC based programmer features:
• Addirional IDNet and MAPNET ll addressable device Convenient front panel accessed Ethernet port for quick
modules and IDNet/MAPNET II quad isolator modules � and easy download of site-specific programming
• IDNet+output module with built-in quad isolator and . Modifications can be uploaded as well as downloaded
enhanced operation for better retrofit to existing wiring for greater service flexibility
(see data sheet S4l 00-0046)
• Fire Alarm Network Interfaces,DACTs,ciry • AND,firmware enhancements are made via software
connections,and up to five(5)RS-232 ports for printers downloads to the on-board flash memory
and terminals . . .
• IP communicator compatibility 4100ES Series Fire Detection and Control Panels
• Alarm relays,auxiliary relays,additional power provide extensive installation,operator,and service features
supplies,IDC modules,NAC expansion modules with point and module capacities suitable for a wide range of
• Service modems, VESDA Air Aspiration Systems system applications.An on-board Ethernet port provides fast
interface,ASHRAE BACnet Interface,TCP/IP Bridges external system communications to expedite installation and
• LED/switch modules and panel mount printers service activity. Dedicated compact flash memory archiving
• Emergency communications systems(ECS)equipment; provides secure on-site system information storage of
8 channel digital audio or 2 channel analog audio electronic job configuration files to meet NFPA 72(National
• Battery brackets for seismic area protection(see page 2) Fire Alarm and Signaling Code)requirements.
Compatible with Simplex°remotely located Modular design.A wide variety of functional modules
4009 IDNet NAC Extenders, up to ten per IDNet are available to meet specific system requirements.
SLC Selections a11ow panels to be configured for either
4100ES and upgrade kits are UL Listed to: Stand-Alone or Networked fire control operation. InfoAlarm
• UL Std. 864,Fire Detection and Control (UOJZ),and Command Center options provide convenient expanded
Smoke Control Service(UUKL) display content(detailed on data sheet S4100-0045).
• UL Std.2017,Process Management Equipment(QVAX)
" See�5 arx16 fa product that is UL a ULC listed arid additional listing irifarrration.
• UL Std. 1076,Proprietary Alarm Units-Burglar(APOU) m�s prod�t nas�er,i��ted eytr,e cai�forrria state Fre�rsn��csFn��,r�,t to
• UL Std. 1730, Smolce Detector Monitor(UULH) s�ia,�s�aa.��tr�c�ifoR,�a�tn�,dsar�yc«�.s�csFn���tir,yy
7165-0026:251(4100ES)fa-allwaable values ancVor coriditiais corioerriing material
• ULC Std. 5527-99 presentedinthisdaxarrent.Pcceptedfause—atyofNEwYakDepartmentof&�Idings—
NEA'3.rr93E PrJditional listings rrey be applicable;contact your lod Slrrplex produd
supplier for the latest status.Listings�d apq�ovals urxier Sirrplex Tirre Re�rder Co.are
the property of Tyoo Fre Protedion Prod�s.
S4100-0031-23 6/2013
• • � - • • � - � • • '•
The Master Controller Bay(top)includes a standard • The latching dress panel(retainer)assembly easily
multi-featured system power supply,the master controller lifts off for internal access
board,and operator interface equipment. • NACs are mounted directly on power supply
assemblies providing minimized wiring loss,compact
The Expansion Bays include a Power Distribution size,and readily accessible terminations
Interface(PDI)for new 4"x 5"flat design option Packaging supports traditional 4100-style
modules and also accommodate 4100-sryle modules. � motherboard with daughter cards
The Battery Compartment(bottom)accepts two • Modules are power-limited(except as noted,such as
batteries,up to 50 Ah,to be mounted within the cabinet relay modules)
without interfering with module space. • The NEMA 1 box is ordered separately and available
for early installation
The following illustration identifies bay locations using a . Doors are available with tempered glass inserts or
three bay cabinet for reference. solid;boxes and doors are available in platinum or red
• Boxes and door/retainer assemblies are ordered
_ separately per system requirements;refer to data sheet
S4100-0037 for details
sio„� �=d
siotz -_-_ , . • • - • � -
n
s�°`3 0 -�-_—_- The followin illustration identifies the rimar functions
Master siot a °°°' 0 g p y
controuer eay �_°°� of the operator interface.
o �� Operator interface panel is directly
Mastercontrollerwith viewable and accessible(no acce\s door)
dual slot motherboard System power supply�
so s�, so, ,�. sa, � �o„
' o0 0 � _
i � o,.. ...
_ `s :'i` E i�'�iun i_ -
' ; � ,.,Mea.. - � �� )tyi
Expansion Bay 1� �°°` 0 L
�.,� �I
i ..=w�. ��_� D�I O� �� —
I �O� OI �000 O ��'
Typicalbayswith � ��.��: �� - ���---�-�-
mixed module sizes
.�, �e. � a,,. ,,.,, �e , .,,.
-- o,�
� � .:���� ������, Upload/Download Basic operator instructions Panel sounder
�expansion Bay 23 a°°E Ethernet port access are printed on the interface
=�oa� (under sliding cover) mounting plate
�° ��
� m��,r �o.� �
I
���-��� ° ° • TrueAlarm individual analog sensing with front panel
information and selection access
• "Dirty"TrueAlarm sensor maintenance alerts,service
�Battery Compartment, 111C1 Stal11S t'epOT'tS 1nCluCllilg"almOSt CI1T'1y"
� • TrueAlarm magnet test indication appears as distinct
"test abnormal"message on display when in test mode
----- • TrueAlarm sensor peak value performance report
4100ES Module Bay Reference • "Install Mode"allows grouping of multiple troubles for
uninstalled modules and devices into a single trouble
condition(typical with future phased expansion);with
• � ' • • future equipment and devices grouped into a single
• Boxes can be close-nippled;each box provides trouble,operators can more clearly identify events from
the commissioned and occupied areas
convenient stud markers for drywall thickness and . Module level ground fault searching assists installation
nail-hole knockouts for quicker mounting and service by locaring and isolating modules with
• Smooth box surfaces are provided for locally cutting grounded wiring
conduit entrance holes exactly where required . `Recurring Trouble Filtering"allows the panel to
• Cabinet assembly design has been seismic tested and is recognize,process,and log recurring intermittent
certified to IBC and CBC standards as well as to troubles(such as external wiring ground faults),but
ASCE 7-OS category D,requires 33 Ah or 50 Ah only sends a single outbound system trouble to avoid
batteries with battery bracicets as detailed on data sheet nuisance communications
52081-0019 • WALKTEST silent or audible system test performs an
automatic self-resetting test cycle
2 S4100-0031-23 6/2013
• � - • • � - •
Convenient Status Information.With the locking • Convenient and extensive operatar information is
door closed,the glass window allows viewing of the provided using a logical,menu-driven display
display, status LEDs,and available operator switches. . Multiple automatic and manual diagnostics for
Features include a two-line by 40-character,wide viewing maintenance reduction
angle(super-twist) LCD with status LEDs and switches as
shown in the illustration below. • Alarm and Trouble History Logs(up to 1250 entries for
each,2500 total events)are available for viewing from
LED indicatars describe the general category of activiry the LCD,or capable of being printed to a connected
being displayed with the LCD providing more detail.For printer,or downloaded to a service computer
the authorized user,unlocking the doar provides access to
the control switches and allows further inquiry by • Convenient PC programmer label editing
scrolling the display for additional detail. . Password access control
FlRE AL�RIIA ACK ackria�iedges a Fre Alarrn
ooridition,logs the�daiaMedge,and silences the
operator par�el and all annundator tone-alerts
SIX SYSTEM STATUS II�DICATq2 I�s ��N 2 ACK adv�edc�s a Priaity 2 Alarm
provide system status indications in addition condition,logs the adaxNriedge,and silences the
to LCD ir�fon7ation,LEDs flash to indicate the �P�"�ta-Par�and all annunaator ton�alerts
ULC SYSTEMS condition arid tt�en wf�en adviov�iedged, SUPV ACK adcnowieck�es system supervisaY
require designating remain on urrtil reset: oq�ditions,logs the adcna�ledge,and silences the
a Q�ound Fault Fre Alarm&Prioriiy 2 Alam�,red LED operator par�l and all annunaator taie-alerts
indicator Supervisory&Trouble,yellauv Lm
Alarm Silenced,yellow Lm lROUBLE ACK aclvx�n�iedges system troubles,logs
AC Povoer,green LED(on fa-norrr�al) the admovoledge,ar�d silences the ope�-ata-pariel arid
all annunaator torie-alerts
TM��� ALARM SILE]�CE causes audible notification
prrn�ide custom labeling,the top 2 X 40 LCD READOUT,LED baddighted �iances to be silenced(depenciing on par�l
two LEDs are seledable as red or during riomial oonditiais arid abr�rrrial P�J���)��ly after evaaaation is oa�rplete and
yellow,the bottom LED is operating coriditiais,provides up to 40 �ile alarrn source is being irrvestigated;rr�y allav
seledable as grcen or yellow diaracters for custom label infarr�tion ���e notification to oontin�(strobes still flashing)
FlRST ALARM DISPLAY:Operation can SYSTEM RESET resta-es contrd par�l to riorrr�l wt�-i
Custom label ir�sert ����fa-rriairitained display of first �I alarrr�ed inputs are retumed to riorrr�al
alarmuritil adaio�u�iedged
I Waterflow-East -
'�Y'=;7Eh1 I:=; Ni i�;I�AL
j Waterf� d -�n�!�:e i� • rc T!!C q.-. �•E i�,i •i•_�
�
� 1.:;,z �_ ,�.,_� i7��� i_�t� .I.��:�-'t:�..:����-' . ��.- i
�Gramd Fault - � �
� � Manual Evac � d - - - - �
� �City Disconnect
l
�
, ���
� � Elevator Recall � -���
I
� � � � �
� I i - �
; � ��
� � Almost Dirty � � �
U � GroLa chault � � � � � '��
FlVE PROGRANMABLE POIM'STATUS ADDIT10NAl_FUNCTION LCD NAVIGATION NUNERIC F�YPAD for
FUNCf10N SIMTCFES, COMROL F�YS: I�YS: COMROL: C�r�t category arid par�t
each with a yellav LED Poirit Enable arid Everrt Time F�quest Menu seledion seledion(alphabet
indicator Disable Ma-e Iriforrretion Request Vertical and characters are not used ffi
Force On a-Arm Larrp Test Fbriza�tal position this ti rr�)
Force OfF a-Disarrn seledion bi.�ltons
Retum On/Off a-
Arrr✓Disarm to Auto
Nbde
3 S4100-0031-23 6/2013
• � . � • � - - � • � - •
The 4100ES is compatible with an extensive list of Addressable device communications include operation of
remote peripheral devices including printers, TrueAlarm smoke and temperature sensors. Smoke
CRT/keyboards(up to five total), and both conventional sensors transmit an output value based on their smoke
and addressable devices including TrueAlarm analog chamber condition and the CPU maintains a current
sensors. value,peak value,and an average value for each sensor.
Status is determined by comparing the current sensor
' • • ' - • ' � ' • • value to its average value.Tracking this average value as
Overview.The 4100ES provides standard addressable a continuously shifting reference point filters out
device commLmicarions for IDNet compatible devices and environmental factors that cause shifts in sensitivity.
accepts optional modules for communications with Programmable Sensitivity of each sensor can be
MAPNET II compatible devices.Using a two wire selected at the control panel for different levels of smoke
communications circtiit,individual devices such as obscuration(shown directly in percent)or for specific
manual fire alarm stations,TrueAlarm sensors, heat detection levels. To evaluate whether the sensitivity
conventional IDC zones,and sprinkler waterflow should be revised,the peak value is stored in memory and
switches can be interfaced to the addressable controller to can be easily read and compared to the alarm threshold
communicate their identity and status. directly in percent.
Addressability allows the location and condition of the CO sensor bases combine an electrolyric CO sensing
connected device to be displayed on the operatar interface module with a TrueAlarm analog sensor to provide a
LCD and on remote system annunciatars. Additionally, single multiple sensing assembly using one system
control circuits(fans,dampers,etc.)may be individually address. The CO sensor can be enabled/disabled,used in
LED/Switch modes and custom control, and can be made
controlled and monitored with addressable devices. public for communication across a fire alarm Network.
Addressable Operation. Each addressable device on (refer to data sheet 54098-0041 for details)
the communication channel is continuously interrogated TrueAlarm heat sensors can be selected for fixed
for status condition such as:normal,off-normal,alarm, temperature detection,with or without rate-of-rise
supervisory,or trouble.Both Class B and Class A detection.Utility temperature sensing is also available,
operation are available. Sophisticated poll and response typically to provide freeze warnings or alert to HVAC
communication techniques ensure supervision integrity system problems.Readings can selected as either
and allow for"T-tapping"of the circuit for Class B Fahrenheit or Celsius.
operation. Devices with LEDs pulse the LED to indicate
receipt of a communications poll and can be turned on TrueSense Early Fire Detection.Multi-sensor
steady from the panel. 4098-9754 provides photoelectric and heat sensor data
using a single 4100ES IDNet address. The panel evaluates
IDNet Channel Capacity. The CPU bay system power smoke ac2ivity,heat activity,and their combination,to
supply(SPS)provides an IDNet signaling line circuit provide TrueSense early detection. For more details on
(SLC)that supports up to 250 addressable monitor and this operarion,refer to data sheet 54098-0024.
control points intermixed on the same pair of wires. � , � � , � � _ � _ � _
Addirional IDNet circuit modules are available for 64,
127,or 250 addressable devices. Sensor Status. TrueAlarm operation allows the control
IDNet/MAPNET II Communications wiring panel to automatically indicate when a sensor is almost
dirty,dirty,and excessively dirty. The NFPA 72
SpeCifiCations. Distances are for shielded or unshielded requirement for a test of the sensitivity range of tl�e
wire. Shielded wire may provide protection from sensors is fulfilled by the ability of TrueAlarm operation
unexpected sources of interference. to maintain the sensitiviry leve] of each sensor. CO
Wiring Specifications Sensors track their 5 year active life status providing
Size 18AVbG(0.82rm�) indicatars to assist with service planning. Indicators occur
at: 1 year,6 months,and when end of life is reached.
Preferred Shielded iv�isted pair(STP)
T� �Ceptable� Unshieldediwistedpair(UfP) Modular TrueAlarm sensors use the same base and
different sensor types(smoke or heat sensor)and can be
Farthest astanoe 126-250 Upto2500feet(762 m) easily interchanged to meet specific location requirements.
fromCa�trd Panel This allows intenrional sensor subsriturion during building
pe�-Device load up to 125 Up to 4000 ft(1219 m)
construction when conditions are temporarily dusty.
T�al VUre Length Allov�ed VUth �to 10,000 ft(3 Ivn);0.58 N F Instead of covering smoke sensors(causing them to be
'T'Tapsfa-C�assBV�iring disabled),heat sensors may be installed without
`Sorr�e applicatia�s rr�y require shielded winng.Reviewyour system reprogramming the control panel. The control panel will
with your local Sirrplex produd supplier. indicate an incorrect sensor rype,but the heat sensor will
operate at a default sensitivity to provide heat detection
for building protecrion at that locarion.
4 S4100-0031-23 6/2013
� , _ � _ System Power Supply (Continued):
• Three,3 A On-Board NACs,conventional reverse
Master Controller and Motherboard: polarity operation;rated 3 A for Special Application
• Mounts in Slot 4 of a two slot motherboard(Slots 3 and 4 appliances and 2 A for Regulated 24 DC power,with
of the Master Controller Bay)and provides one Style 4 or electronic control and overcurrent protection; selectable
Sryle 7,RUI communications channel, available at Slot 4 as Class B or Class A,and for synchronized strobe or
• RUI communications controls up to 31 devices per master SmartSync horn/strobe operation over two wires
controller(on one or multiple RUI channels); devices • NACs can be selected as auxiliary power outputs
include: MINIPLEX transponders,4603-9101 LCD derated to 2 A for continuous duty;the total auxiliary
Annunciators,4602-9101 Status Command Units(SCU), power output per SPS is limited to 5 A
4602-9102 Remote Command Units(RCU),4602 Series . Battery Charger is dual rate,temperature compensated,
LED Annunciator Panels,and 4100 Series 24 UO and and charges up to 50 Ah sealed lead-acid batteries
LED/Switch modules mounted in the battery compartment(33 Ah for single
• Up to four RUI channels are supported;use up to three bay cabinets);also is UL listed for charging up to
4100-1291 RUI expansion modules as required 110 Ah batteries mounted in an external cabinet(see
• Optional Service Modem 4100-6030 mounts onto the data sheet 52081-0012 for details)
master controller board with its own on-board connections • Battery and Charger Monitoring includes battery
• Slot 3 of the motherboard is primarily for the 4100-6078 charger status and low or depleted battery conditions;
Network Interface Board with media modules,and status information provided to the master connoller
secondarily for the 4100-6038 Dual RS-232 Board includes analog values for:battery voltage,charger
(4100-6038 is required for 2120 System connections) voltage and current,actual system voltage and current,
System Power Supply: (see page 8 for more detail) and individual NAC currents
Rating is 9 A total with "Special Application"appliances; • �A Auxiliary Power Output is selectable for detector
� 4 A total for"Regulated 24 DC"appliance power reset,door holder,or coded output operation
• Outputs are power-limited, except for the battery charger • Auxiliary Relay is selectable as N.O. or N.C.,rated 2 A
@ 32 VDC,and is programmable as a trouble relay,
• Provides system power,battery charging,auxiliary power, either normally energized or normally de-energized,or
auxiliary relay,earth detection,on-board IDNet as an auxiliary control
communications channel for 250 points,three on-board . Optional City Connect Module(4100-6031,with
NACs,and provisions for either an optional City Connect disconnect switches,or 4100-6032,without disconnect
Module or an optional Alarm Relay Module switches)can be selected for conventional dual circuit
• IDNet SLC Output provides Class B or Class A
city connections
communications for up to 250 addressable devices(as . Optional Alarm Relay Module(4100-6033)provides
described on page 4) three Form C relays that are used for Alarm,Trouble,
and Supervisory,rated 2 A resistive @ 32 VDC
. . . . .
Master Controller and Expansion Bay Selection* (Canadian models have low battery cutout)
Model Model Type and Listing Description Supv. Alarm
4100-9111 120 VAC Input UL 4100ES Master Controller Assembly with LCD and
4100-9112 English 120 VAC,Canadian ULC operator interface,9 A system power supply/battery 373 mA 470 mA
4100-9113 French charger(SPS),250 point IDNet interface,3 NACs,
4100-9211 220-240 VAC Input UL auxiliary relay,and external RUI communications interface
4100-9131 120 VAC Input UL 4100ES Master Controller Assembly,no display,no
4100-9132 English 120 VAC,Canadian ULC operator interface,9 A system power supply/battery 363 mA 425 mA
charger(SPS),250 point IDNet interface,3 NACs,
4100-9230 220-240 VAC Input UL auxiliary relay,and external RUI communications interface
4100-9121 Redundant Master Controller,two bay assembly;top bay contains LCD and operator interface,
(not ULC CPU card assembly,and 4100ES,9 A system power supply/battery charger(SPS);second bay ��g mA 937 mA
listed) contains CPU card in Slot 2, and LCD and operator interface; 120 VAC,60 Hz input;
NOTE: RUI connections require use of 4100-1291 RUI expansion modules
4100-2300 Expansion Bay Assembly;order for each required expansion bay(not required for 4100-9121)
4100-2303 Legacy Module Stabilizer Bracket, used when expansion bays have legacy slot style modules
Master Controller Upgrades for Existing 4100 Series Fire Alarm Control Panels*
Model Panel Type Includes
4100-7150 1000 pt 4100(4100+) New Master Controller and 4100ES user interface door assembly with Ethernet connection
4100-7152 512 pt 4100 Same as 4100-7150 plus includes a Universal Power Supply
4100-7158 1000 pt 4100(4100+) New Master Controller with Ethernet Connection Upgrade Kit;for 4100+without LCD and
or 4100U operator interface,or 4100U with or without LCD and operator interface
Expansion Bay Upgrade Kit for mounting 4100ES style(4"x 5"modules)in existing 4100 style panels;
4100-2301 Note:When using this kit to upgrade a 4100+transponder, a 4100-0620 Transponder Interface Card(TIC)is also
required for communications to the 4100ES module
�For InfoAlarm Command Center expanded content display products, refer to data sheet S4100-0045. (Continued on next page)
5 S4100-0031-23 6/2013
. . . . .
Master Controller Upgrades for Existing 4020 Series Fire Alarm Control Panel
Model Description
4020 Master Controller Upgrade to 4100ES; Includes New Master Controller with LCD&operator interface assembly,
4100-9833 $VDC Converter and RUI Interface in a single bay cabinet with locking glass door and retainer; mounts as an adjunct
panel close-nippled to existing 4020 cabinet;also includes 8 VDC box-to-box power and communications harness and
solid filler panel for the existing 4020 Master Controller bay
Communication Modules
Model Description Size Supv. Alarm
4100-6078 For Master Controller; mounts in Slot 3 Modular Network Interface;each requires 1 Slot 46 mA 46 mA
4100-6061 For Redundant Master Controller two media modules(below) 1 Slot 46 mA 46 mA
4100-6056 Wired Media Module Select two media cards as required; mounts on N.A. 55 mA 55 mA
4100-6057 Fiber Optic Media Module 4100-6078 or 4100-6061 N.A. 25 mA 25 mA
4100-6047 Building Network Interface Card(BNIC), refer to data sheet S4100-0061 for details 2 Blocks 291 mA 291 mA
4100-6055 Network Access Dial-in Service Modem, mounts to 4100-6078 or 4100-6061 Network N.A. 60 mA 60 mA
Interface Card, requires telephone line connection
4100-1291 Remote Unit Interface Module(RUI); up to three maximum per control panel 1 Slot 85 mA 85 mA
4100-6030 Service Port Modem, local panel access only, mounts to Master Controller Module, N.A. 70 mA 70 mA
requires telephone line connection, accesses same information as front panel port
4100-6031 City Circuit,with disconnect switches For use with SPS N.A. 20 mA 36 mA
4100-6032 Select one per Cit Circuit,w/o disconnect switches only, not RPS N.A. 20 mA 36 mA
SPS(fits on SPS) y
4100-6033 Alarm Relay,3 Form C relays, 2 A@ 32 VDC;for SPS or RPS N.A. 15 mA 37 mA
4100-6101 Physical Bridge, Class B, includes 1 modem module and 2 wired modules 1 Slot 210 mA 210 mA
4100-6102 Physical Bridge, Class X, includes 2 modem and 2 wired modules 2 Slots 300 mA 300 mA
4100-6038 Dual Port RS-232 with 2120 interface(slot module) 3 maximum of RS-232 type 1 Slot 132 mA 132 mA
4100-6046 Dual Port RS-232 standard interface(4 x 5 module) modules per panel 1 Block 60 mA 60 mA
4100-6045 Decoder Module 3 Slots 85 mA 163 mA
4100-6048 VESDA Aspiration System Interface 1 Slot 132 mA 132 mA
4100-6052 DACT, Point or Event Reporting; 1 shipped unless 4100-7908 is selected;2 max. per 1 Slot 30 mA 40 mA
system; includes 2, 2080-9047 cables, 14 ft(4.3 m)long, RJ45 plug and spade lugs
Expansion, System and Remote Power Supplies and Accessories(Canadian models have low battery cutout)
Model Voltage/Listing Description Size Supv. Alarm
4100-5101 120 VAC UL Expansion Power Supply(XPS);9 A output,3 built-in
4100-5103 120 VAC, Canadian ULC Class A/B NACs; NAC operation is same as SPS, see 2 Blocks 50 mA 50 mA
4100-5102 220-240 VAC UL page 5 for details
4100-5115 NAC Expansion Module, 3 NACs, Class A/B, mounts on XPS only N.A. 25 mA 25 mA
4100-5111 120 VAC UL Additional System Power Supply(SPS); 9 A power
4100-5112 120 VAC, Canadian ULC supply/charger with 250 point IDNet channel, 3 Class 4 Blocks 175 mA 185 mA
4100-5113 220-240 VAC UL �B NACs,add IDNet device currents separately
4100-5125 120 VAC UL Remote Power Supply(RPS); 9 A power
4100-5126 120 VAC, Canadian ULC supply/charger similar to SPS except no IDNet channel 4 Blocks 150 mA 185 mA
4100-5127 220-240 VAC UL or City Circuits;will accept one 4100-6033
4100-5152 12 VDC Power Option,2 A maximum 1 Block 1.5 A maximum
4100-0156 8 VDC Converter, required for multiple Physical Bridge Modules, 3 A maximum 1 Block included w/loads
4100-0636 Box Interconnection Harness Kit(non-audio); order one for each close-nippled cabinet
4100-0638 4100 Slot Module Additional 24 VDC Harness; need when 4100 Slot module requirements exceed 2 A from SPS
8 Zone Initiating Device Circuits* Expansion Signal Module and Options(1.5 A Class B except as noted)
Model Type Supv. Alarm Model Description Supv. Alarm
4100-5005 Class B 75 mA 195 mA 4100-5116 Converts 1 NAC in to 3 NACs out; 1 Block size 18 mA 80 mA
4100-5015 Class A 75 mA 195 mA 4100-1266 Expands 3 NACs to 6 select one; mounts 0.6 mA 60 mA
`IDC Modules are 1 Slot size 4100-1267 Converts 3 NACs to Class A on 4100-5116 0.6 mA 30 mA
Continued on next page
6 S4100-0031-23 6/2013
. . . . . � -.
Miscellaneous Accessories
Model Description
4100-1279 Single blank 2"display cover;4100-2302 provides a single plate for a full bay
4100-9856' 4100ES Canadian French Applique Kit; Simplex,4100ES, Controle Incendie
4100-9857* 4100ES English Applique Kit; Simplex,4100ES, Fire Control
4100-9858' 4100ES InfoAlarm Remote Display English Applique Kit; Simplex, Operator Interface,4100ES
4100-9859� 4100ES InfoAlarm Remote Display Canadian French Applique Kit; Simplex, Interface de I'operateur,4100ES
4100-9835 Termination and Address Label Kit(for module marking); provides additional labels for field installed modules
4100-6029 Smoke Management Application Guide; required for UUKL listing
4100-6034 Tamper Switch,one per cabinet assembly if required; monitors solid door for panels with solid door; monitors the
internal retainer panel for panels with glass door(not the glass door); has a built-in addressable IDNet IAM
Series resistor for WSO, IDCs(N.O.water flow and tamper on same circuit,wires after water flow and before tamper)
2081-9031 470 S2, 1 W, encapsulated,two 18 AWG leads(0.82 mm2), 2-1/2"L x 1-3/8"W x 1"H (64 mm x 35 mm x 25 mm)
*Note: 4100ES English Appliques are included with 4100ES Upgrade and Retrofit Kits for mounting 4100ES in 4100,2120,2001,
and Autocall back boxes so that upgrades can be easily identified as 4100ES.4100ES Applique Kits are available for
applications such as to update Remote InfoAlarm Displays connected to a panel that was upgraded to 4100ES or for an
existing 4100U when the New Master Controller is upgraded to 4100ES and only a software upgrade is required.When
required, French appliques are ordered separately.
Addressable Interface Modules (refer to location reference on pages 8 and 9)
Model Description Supv. Alarm
4100-3101 IDNet Module,250 point capacity With 250 IDNet devices, add 200 mA 250 mA
4100-3104 IDNet Module, 127 point capacity With 127 IDNet devices, add 102 mA 127 mA
4100-3105 IDNet Module,64 point capacity With 64 IDNet devices, add 51 mA 64 mA
IDNet Modules,Specifications for each capacity; Module without devices 75 mA 115 mA
Module size= 1 Block Loading per IDNet device 0.8 mA 1 mA
Model Description Supv. Alarm
MAPNET II Module, 127 point capacity,add devices Module without devices 255 mA 275 mA
4100-3102 separately; Module size=2 Slots;
Loading per MAPNET II device= 1.7 mA Fully loaded module,total 471 mA 491 mA
Isolator Module for MAPNET II or IDNet;converts a single connected SLC into four
isolated outputs selectable as Class A or Class B; up to two Isolator Modules can be
4100-3103 connected to one SLC; Module size= 1 Slot; 50 mA 50 mA
NOTE: Compatible with MAPNET II Remote Isolators only;for quad isolation with IDNet
Remote Isolators, use 4100-3107 IDNet+Module(see data sheet S4100-0046 for details)
Relay Modules; N011pOweP-Ilmit@d (for mounting in expansion bay only, refer to location reference on pages 8 and 9)
Model Description Resistive Ratings Inductive Ratings Size Supv. Alarm
4100-3202 4 DPDT w/feedback 10 A 250 VAC 10 A 250 VAC 2 Slots 15 mA 175 mA
4100-3204 4 DPDT w/feedback 2 A 30 VDC/VAC 1/2 A 30 VDC/120 VAC 1 Block 15 mA 60 mA
4100-3206 8 SPDT 3 A 30 VDC/120 VAC 1-1/2 A 30 VDC/120 VAC 1 Block 15 mA 190 mA
Current Calculation Notes:
1. To determine total supervisory current, add currents of modules in panel to base system value and all external loads powered
by panel power supplies.
2. To determine total alarm current,add currents of modules in panel to base system alarm current and add all panel NAC loads
and all external loads powered from panel power supplies.
7 S4100-0031-23 6/2013
. .
System Power Supplies(SPS) 120 VAC Models 4 A maximum @ 102 to 132 VAC, 60 Hz
Input Ex ansion Power Su lies XPS
Power p pp � � 220-240 VAC 2 A maximum @ 204 to 264 VAC, 50/60 Hz;
Remote Power Supplies(RPS) Models separate taps for 220/230/240 VAC
Power Supply Output Total Power Supply �ncluding module currents and auxiliary power outputs; Output switches
9 A total for"Special Application"appliances;4 A total for
Ratings for SPS,XPS, Output Rating ��Regulated 24 DC"power(see below for details) to battery backup
and RPS during mains AC
(nominal 28 VDC on Auxiliary Power Tap 2 A maximum failure or
AC;24 VDC on battery NACs Programmed 2 A maximum per NAC; Rated 19.1 to 31.1 VDC brownout
backup) for Auxiliary Power 5 A maximum total conditions
Special AppliCation Simplex 4901,4903,4904,and 4906 Series horns,strobes,and combination horn/strobes and speaker/strobes
Appliances (contact your Simplex product representative for compatible appliances)
Regulated 24 DC power for other UL listed appliances; use associated external synchronization modules where required
Appliances
Battery Charger Battery capacity range UL listed for battery charging of 6.2 Ah up to 110 Ah (batteries larger than 50 Ah
Ratings for SPS and require a remote battery cabinet); ULC listed for charging up to 50 Ah batteries
RPS(sealed lead-acid Charger characteristics Temperature compensated,dual rate, recharges depleted batteries within 48
batteries) and performance hours per UL Standard 864;to 70%capacity in 12 hours per ULC Standard S527
Operating Temperature 32°to 120°F(0°to 49°C)
Environmental
Operating Humidity Up to 93% RH, non-condensing @ 90° F(32°C)maximum
Additional Technical Installation Instructions 574-848
Reference Operating Instructions 579-197
. • . . . . • •• -• ••
Slot 3,one 2"card:either 4100-6078 Network Module Door thickness
with media cards or 4100-6038 Dual RS-232 4-3/4"(121 mm)
Master Controller Bay 4100-6030 Service Modem mounts o 0
only on master controller board
Two,2",or one,4"slot for :� Knockout Cabinet hei ht:
one or two modules installed I I 9
4100-6031 or 4100-6032 screw/nail 2 ba shown
per the following: � Y
City Circuit or 4100-6033 holes(for for reference)
4100-6052 DACT,Slot 1 s���� � �` Alarm Relay semi-flush
4100-6101 Physical Bridge, siotzsola 5n��" 0 mounting) 1�B59 mm)
Slot 2 � ..� �
0 2 Bay=4p"
4100-6102 Physical Bridge �
(4"module)Slots 1 and 2 �vv vv vv (1016 mm)
'Master controller *System power supply Exposed cabinet for 3 Bay=56"
4100-6048 VESDA Interface, with motherboard 1427 mm
=�o„ „a„ =,o„ o,. ,
semi-flush mounting I � )
Slot 7 or 2 :------:- o �-� o��oo�o� 1-3/8"(35 mm)
4100-5005/5015 IDC Modules, � minimum Wall board
Slot 1 or 2 - ',o,"E'� reference for
semi-flush
4100-6038 Dual RS-232, �' Su�=� mounting,
Slot 2,if Network Module is 8,o� "°" 6"stud
in Slot 3 ..��^°�° �'°�"'",
�'°°, Exposed door and
Typical Expansion Bay o cabinet for semi- Stud
�------- a o 0
(showing mixed module sizes) flush mounting alignment
6-1/8"(156 mm) markers,
Two bay cabinet minimum each side
shown without retainer 6"stud
Battery Compartment �` �4"stud
Door can be hung Door 4-3/4"
hinged left or right 24"(610 mm) (121 mm) 6-29/32"
(175 mm)
�Optional semi-flush trim kit� 11-11/16"
(296 mm)
NOTE: A system ground must be provided for Earth Detection and transient protection devices.This connection
shall be made to an approved, dedicated Earth connection per NFPA 70, Article 250, and NFPA 780.
8 S4100-0031-23 6/2013
. . . . . . . . .
sioc� sioc z sioc s sioc a sioc s sioc e sioc� sioc a Description Mounting
� � IDNet Modules 1 Block
, 4,2 A Relays 1 block
Block A sio�k c Block E eio�k c 4, 10 A Relays po er-limited 4",2 slots
8,3 A Relays 1 block
VESDA Interface 2", 1 Slot
Class B IDC 2", 1 Slot
Class A IDC 2", 1 Slot
MAPNET II Module 4",2 Slots
MAPNET II/IDNet Isolator 2", 1 Slot
, , , , Class B Physical Bridge 2", 1 Slot
eio�k a Block D Block F Block H Class X Physical Bridge 4",2 Slots
Decoder Module 6",3 Slots
C-1 � U System or Remote Power Supply Blocks E, F,G&H
ONLY
Expansion BayChassis Expansion Power Supply Blocks G&H ONLY
Size Definitions:Block=4"W x 5"H(102 mm x 127 mm)card area NAC Expansion Module On XPS ONLY
Slot=2"W x 8"H(51 mm x 203 mm)motherboard with daughter card
` • • • 11 � .
Subject Data Sheet Subject Data Sheet
Introducing the 4100ES S4100-0060 Agent Release Applications S4100-0040
4100ES Enclosures S4100-0037 Fire Alarm Network Overview S4100-0055
4100ES Control Panels with EPS+Power Supplies S4100-0100 Network Communications S4100-0056
for TrueAlert Addressable Notification
4100ES Audio and Firefighter Phone Modules S4100-0034 Network Display Unit(NDU) S4100-0036
LED/Switch Modules&Printer S4100-0032 Addressable Device Compatibility S4090-0011
Remote Annunciators S4100-0038 IDNet+Module w/Quad Isolator S4100-0046
MINIPLEX Transponders S4100-0035 Remote Battery Charger S4081-0002
Building Network Interface(BNIC) S4100-0061 TFX Interface Module S4100-0042
InfoAlarm Command Center S4100-0045 Master Clock Interface S4100-0033
Graphic I/O Modules S4100-0005 2120 BMUX Module S4100-0048
SafeLINC Internet Interface S4100-0028 Truelnsight Remote Service S4100-0063
9 S4100-0031-23 6/2013
TYCO,SIMPLEX,and the product rzame.t listed in this rnaterial are marks and/or registered marks.Unauthorized use as steictly prohibited.Macr•o.rofl a�sd Windows are tr'ademar/cs
ofMicr-osoft Corporation. VF,SDA is a trademark ofXtralis Pty I,td.NFPA 72 and National Fire A1arm Code are n�ademm�ks ofthe Narional Fire Pr�otectron Association(NFPA).
ASHRAE nndBAGxet are trademarks ofASHXAF.,American Sociery ofHeating,Refr�igeration,andAir Condrtroning Engineers.
�05 i m p I Ex Tyco Fire Protection Products• Westminster,MA•01441-0001•USA S4100-0031-23 6/2013
www.simplexgrinnell.com
OO 20/3 Tyco Fire Protec6on Products.All righzs resc�ved.A!!spec�ificarioras ancl other ir fonnutt'on shown were current as of'docurnent revision dute and are subject to change without rzotice.
��SimplEx 4100m Fire Control Panels
UL, ULC, CSFM Listed; FM Approved; /nfoAlarm T"" Command Center
MEA (NYC) Acceptance* for the 4100ES Fire Alarm Control Panel
� �
Multi-line expanded content display interface for � ' �' "" u �� ���I
Simplex°4100ES Series fire alarm control panels, �o . ��� o00
available with the following products: oo � y., ;�� o 000
• Fire alarm control panels(stand-alone or networked) O0 ��� � ' � � � �-�� ��
including Redundant CPU options(Software Revision 00 ���❑ N.Q
12 or higher is required)
• Network Display Units(NDU) supports up to 12,000 � � � � -� ��� �
points
• Remote Annunciator panels and models that mount in a InfoAlarm Command Center for Control Panel Mounting
dedicated cabinet(4100ES and 4100U control panels
support Remote InfoAlarm Command Centers
independent of host panel display type)
• Upgrade kits are available for legacy 4100(1000 pt, �� �;a ���r,c,
4100+systems)and 4100ES and 4100U standard control �'_""`�"°°"�' � �
panels � � - o
• UL listed to Standard 864 �� i� O O O O ' ��_�
InfoAlarm Command Centers provide customized .. . .
operating convenience:
• "Acrivity in System"primary display choices include:
First and Most Recent,First 5 and Most Recent,First 8,
Site Plan with activity status icons,General Alarm, or InfoAlarm Command Center in Remote Cabinet
Direct to List; selectable individually by event type
• System reports are easily viewed; logs can be read with � - . .
minimal scrolling required
• Up to six"softkeys"per screen provide functions that InfoAlarm Command Centers far 4100ES fire alarm
vary with the particular screen information aiding systems provide a large display with extended information
operators to determine how to proceed content,dual language support including 2 byte character
• Up to two languages are available per system,easily languages,and an intuitive control key interface per the
following:
selected by programmable key press(systems with . Up to 10 InfoAlarm Command Centers are supported per
IMS/GCC/NPU or 2 x 40 LCD panels or annunciators 4100ES/4100U control panel;able to allow one
require one language to be the default font) InfoAlarm Command Center to take-control and to
• International models allow customized language legends designate access levels for interfaces not in-control;LEDs
for operator keys and status LEDs can be programmed for in-control status indications
Display properties: • Menu-driven farmat conveniently prompts operators for
• 320 x 240 dot matrix(QVGA)display provides an active the next action required
area of 4.53"W x 3.4"H(115 mm x 86 mm)displaying • Key controls are provided to select the highlighted entry,
up to 854 characters using standard ASCII character font load next screen of information,or jump to top or
• Bright white LED backlighting provides efficient and bottom of activity lists
long lasting illumination;operation is selectable as . Direct point callup displays individual points
continuous or off with power fail or with no key presses alphabetically and then homes in on the logical choice as
� � � more point information is entered
• A Site Plan bitmap can be displayed for reference; icons
Displaying more information.4100ES Controls using the can be added to indicate system status
InfoAlarm Command Center provide an expanded content, . Up to 50 custom point detail messages can be generated
multi-line LCD interface that requires minimal key presses to . Date formats are either MM/DD/YY or DD/MM/YY
access detailed information. Because it is system-powered,its , Time formats are either 24 hour or 12 hour with AM/PM
detailed information is provided without requiring separate
supplementary equipment. • System Normal screen supporYs a gray scale bitmap
InfoAlarm Command Center Control Panel. By using (�'atermark)for location name, company logo, or site plan
a 12T'g0Y 2Ye1 fOY1112t 1riSteaCl Of ari 1riC11 V1CIUa1 teXt Ilrie C11Sp13y, "This product has been approved by the California State Fire Marshal(CSFM)pursuant to
Section 13144.1 of the California Health and Safety Code.See CSFM Listing 7165-0026:251
tlle L,CD pt'OV1CIeS tBXt 1rifOT'rilahOri fOT'f�laPTYl, SUpEt'V1SOT'y, Ot' for allowable values andlor conditions concerning material presented in this document.It is
Trouble.The format is flexible and able to be customized per subject to re-examination,revision,and possible cancellation.Accepted for use-City of
New York Department of Builtlings—MEA35-93E.Atltlitional listings may be applicable;
application allowing additional information to be pTesented to contact your local Simplex product supplierfor the latest status.Listings and approvals under
SUIt t}10 Sp2Clf C app11C1YlOri. Simplex Time Recorder Co.are the property of Tyco Safety Products Westminster.
S4100-0045-6
• • • • - •
NOTE: Refer to page 7 for international control panel reference information. Detailed operator instructions are on
document 579-685.
320 x 240 DOT MATRIX DISPLAY,White SIX SOFT KEYS are available when
LED backlighting provides easy viewing;
operation is programmable for key inactivity requiretl.This sample provides Menu
timeout and/or AC power fail to call up the available operations;
More Info to call up specific point
THREE PROGRAMMABLE PRIMARY"ACTIVITY IN SYSTEM" tletails,Site to call up the Site Plan
LEDs provitle custom labeling, DISPLAY OPTIONS:Choices include"First Graphic Screen,Event Time(while
8"(shown below for"Fire Alarm in System"), pressed dis la s time and date for all
the top two LEDs are selectable � p Y
as red or yellow,the third LED is "First and Most Recent,""First 5 and Most tlisplayetl events,antl CIrlExit;the
selectable as red or green Recent,""Site Plan,""General Alarm,"or following are other typical soft keys: NUMERIC KEYPAD for
"Direct to List."After the event is point Enable and Disable point category and point
ULC SYSTEMS require acknowledged,screen reverts to the Force On or Arm selection(alphabet
designating a Ground Fault sequential event list until Clr/Exit softkey is Force Off or Disarm characters are not used
indicator selectetl or after timeout(—30 seconds); Return OnlOff or at this time)
applicable to Fire Alarm,Priority 2 Alarm, Arm/Disarm to Auto Mode
System Supervisory,and System Trouble, ClExit Key duplicates
Event Time Request
Custom label insert(typical each category is intlependently selectable More Information Request the CIrlExit softkey
choices shown for reference) for primary display mode when present
� . Ground Fault ' wenu �
i � I Waterflow•East ��' i ls+ Floor Conference Room �y , _ -. �
MOKE DETECTOR FIRE RLRRM �� � �
� ls+ Floor Elevo+or Lo66v wore � �) � i
' I Watertlow-West �. 2 IJLL STRTION FIRE RLRRMI°`o -_ _ '
ls+ Floor Eos+ �
i �� ' 3 iRTERFLOW FIRE RLRRM � � � '
i Manual Evac nd F I oor E I evo+or Lo66v S�te �
� � �'MOKE DETECTOR FIRE RLRRM �� �
i - . S'rd F I oor E I evo+or Lo66v Neor Eos+ Door Event �
' CityDisconnect� MOKE DETECTOR FIRE RLRRMr�me � � i
i � �� rd Floor Mechonicol Room �-� �— �-� � �
i ° IJCT SMOKE DETECTOR FIRE RLRRM i
� DoorHolder ' a nd Floor Nor+h Corridor � � i
' � gypass MOKE DETECTOR FIRE RLRRM ��� � �O O O �
� +h Floor Elevo+or Lo66v � - i
' e MOICE DETECTOR FIRE RLRRMci�� �
i I . Drill E"'t �
� O FIRE=17 PRI2=0 SIJPV=O TRBL=O
' / SmokeSensor � � �
i
� � �Almost Dirty Check
i I
� O �anyuaye LCD NAVIGATION
' Toggle
� CONTROL:
' O �a'"PTest O O O , O Menu,Enter,Previous
item select,Next item
'----- -------------------------------------� select;PageUpand
Page Down
SEVEN PROGRAMMABLE FIRE ALARM ACK acknowletlges a Fire Alarm contlition,logs the
FUNCTION SWITCHES,each acknowledge,silences the operator panel and all annunciator tone- SIX SYSTEM STATUS INDICATOR
equipped with tlual color LED alerts,and displays sequential alarm list LEDs provide system status indications
indicators;the to six LEDs are in adtlition to LCD information,LEDs flash
p PRIORITY 2 ACK acknowledges a Priority 2 Alarm condition,logs the to indicate the condition and then when
selectable as either retl or acknowledge,silences the operator panel and all annunciator tone- acknowledgetl,remain on until reset:
yellow,the bottom LED is alerts,and displays sequential Priority 2 alarm list Fire Alarm&Priority 2 Alarm,retl LED
selectable as either red or
green;NOTE:Program the SUPV ACK acknowledges system supervisory conditions,logs the Supervisory&Trouble,yellow LED
bottom switch as"Lamp acknowletlge,silences the operator panel antl all annunciator tone- Alarm Silenced,yellow LED
TesY'for UL listed systems alerts,and displays sequential supervisory contlition list AC Power,green LED(on for normal)
TROUBLE ACK acknowledges system troubles,logs the
acknowledge,silences the operator panel antl all annunciator tone-
alerts,and displays sequential trouble list
ALARM SILENCE causes notification appliances to be deactivated,
typically after evacuation is complete antl while alarm source is being
investigated.May be programmed to silence audible notification and
allow visible notification to continue(strobes still flashing).
SYSTEM RESET restores control panel to normal when all alarmetl
inputs are returned to normal
2 S4100-0045-6
� . .
FIRST OCCURRENCES(UP TO 5)AND MOST RECENT OCCURRENCE,
ACTIVITY IN SYSTEM DISPLAY("Fire Alarm in System"screen shown for reference,
see page 2 for a First 8 Events display)
FIRST OCCURRENCE advises of the time,date,device type,and custom label of the
first occurrence of the event type displayed;the numerical count identifies the
sequence of occurrence;when selected as the primary display screen,display of first
occurrence and most recent occurrence is maintained until events are acknowledged
which brings up the event list(similar to the First 8 display);the display reverts back to
"First and Most Recent"when the Clr/Exit softkey is selected or after a time delay
SOFT KEYS in this
FONT ATTRIBUTES include: column correspond to
the panel pushbutton
Normal, Bold, Underline, Double, I:, r�, switches; programming
�, Flash On/Off, Flash OnlDim, and allows the soft keys to
appear only when the
commands for Vertical and Horizontal Placement functions are enabled
��f1U
FIR�T �C�URI�ENCE — 11:�3 AM 0��1��1�
1 orth Basemen+ — Area C
MOfCE DETECTO� FI�E AL�RM �°r�
asment S�r i nk I er�s Info
DISPLAYSIZE: � �TERFL04� FI�E AL�RM
4.53"W x 3.4"H 1�t F I ���` E I ��l�t��` L�GG�
(115 mm x 86 mm) � ���E �ETE�T�I� F I I�E �iL�iR�1 ��t�
y nd Floor� Eas+ ��rrid�r
MOfCE DETECTO� FI�E AL�RM E4�ryt
� r�d F I oor-� E I e�at�r� Lobb� Time
MOfCE DETECTO� FI�E AL�RM
MOST RECENT — 1�:�1 PM 0��1��10
17 th F I ��r� E I e�rat�r L����
M�f�E �ETE�T�� FI�E �L�R�1
Clr!
Exit
FI�E=1� PRI�=O SUP�=O T�BL=O
TALLY COUNTS list the number of activities per category of Fire Alarm
(FIRE), Primary 2 Alarm(PRI2),Supervisory(SUPV),and Trouble(TRBL)
COMMAND PROMPT advises the operator of the action required and displays local panel time
MOST RECENT advises of the time,date,device type,and custom label of
the most recent occurrence of the list shown, in this case,the Fire Alarm list
3 S4100-0045-6
.
Site Plan Bitmap.The InfoAlarm Command Center
supports a site plan monochrome bitmap image(size is
281 pixels wide by 192 pixels high)that can also display
icons indicating activity and location. Shown to the right is a
sample site plan with icons shown in each building area. For �ef4
this example,each area is showing an"A"for an initiating
device in alarm, a"WF"for waterflow occurring, and an � �F
icon indicating notificarion appliances in alarm. (Icons can be �0r�� Core 4
�i . .i { .i �
created for site specific symbology,these are for example -�- -�- -0-
Orily.� • �• f �• { �� Status
� 1�VF � 1�I�F Warehouse
Site Plan Selection and DetaiL If desired,the site plan
can be the primary display screen for system activity or can �°r�� �°i�3 For fire call
be for reference,available by selecring the"Site"softkey. ��_ -�- (s2��sss-�2sa
Depending on the facility layout,the site plan can also be a ` i` � �` For ser�rice cau
convenient location for common reference information such � 1lUF � VI�F (���l���-����
as primary call phone numbers,street address,etc. to assist
operators in their assigned response. FIRE-7 PRI2-0 SUPV-0 TRBL-0
System Normal Screen. The site plan(or another bitmap
image)can be displayed on the System Normal screen as a
grey image watermark behind the screen text. (Size and type
are the same as that for a site plan bitmap). This can be used
to identify the specific location of the 4100ES or can display
a site-specific logo or other information. (A sample is shown
on page 6.)
........................................................................................................................................................................
• - • •
LOGIN........Lo9in or Lo9ou+ of +he svs+em �
REV............5how +he 5�W rev i s i on o� +he The Main Menu screen illustration to the left
JOb or svs+em demonstrates how print/display statements appear for
status information or for prompting of user input. Other
examples of this format occur when setting time and date,
������� �������� entering a password,or identification of a status change
such as point enabling ar disabling.Use of this feature
allows the display to clearly focus the user on required
REPORT5....V i ew svs+em I 495 or rePOr+s trifOYmattOt]OT aCtlOris.
PORT..........Se I ect svstem Por+ For rePOrts
CLR
Esit
FIRE=O PRI2=0 5UPV=0 TRBL=O
........................................................................................................................................................................
• . • MENTRY 6 12:d0:04 a■ 4ED 19-MAY-10
5Y5TEM TIME�DATE INVALID OR NOT SET
The Trouble Log History screen shown to the right TROUBLE PdINT ABNORMRL
identifies the abilit to view multi le event entries with ENTRY 5 12:00:03 ❑m WED 19-MAY-10
Y P COLD START
minimal scrolling. For specific information access, TROUBLE PdINT ABNORMRL
ressin NexY'or"Previous"on the ke ad hi hli hts ENTRY 4 12:Od:d2 ❑m WED 19-MAY-id
p g yp g g CARD 3- 4120 NETWORK INTERFACE
the selected next or previous item in the list as indicated CARD MISSING�FAILED ABNORMRL
by the arrow and the bolded first line of Entry 6. ENTRY 3 12:Od:d2 am WED 19-MAY-id
COMMON TROUBLE POINT FOR NODE: 2
NO�E MISSING TROUBLE
Far access to the next or previous full screen of ENTRY 2 12:Od:dd ❑m WED 19-MAY-id
information usc the Pa e Dn or Pa e U ke s located to CARD 4- MULTI-PURP05E MONITOR CRR�
> g g P Y CARD MISSING�FAILED ABNORMRL
the right of the soft keys,each to the right of the display. ENTRY i 12:D0:00 am WED 19-MAY-10 c��r
EH�t
FIRE=O PRI2=0 SUPV=O TRBL=O
4 S4100-0045-6
� • • • � •
Below are samples of a First and Most Recent primary
display and of a General Alarm display.
Menu Menu
FIRST flLflRM
11:43 AM 05/19/10
MOKE DETECTOR RBNORMAL F I I�E �L�I�M I�
or+h Bosemen+ S�{� �1fe
�'��TE11
MdST RECEHT ALARM
12:41 PM 05f19�10
MOKE DETECTOR RBNORMAL
+h Floor Eas+ Corridor
FIRE=12 PRI2=0 5UPV=0 TRBL=O FIRE=2 PRI2=0 SUPV=O TRBL=O
First and Most Recent Primary Display Option General Alarm Primary Display Option
. � . �
CUSTOM LABEL INSERT for the NOTE:Two sets of slide-in labels are provided, UPPER LABEL INSERT allows
three programmable LEDs and for the one blank,the other in English;areas shown with custom labeling of the numeric keypad
seven programmable switches ++++ are blank for custom wordslcharacters and of the LCD navigation controls
Generic site plan shown for reference
++++ �
�
++++ � ^ .+++ ++++. ++++
++++ ++..
++++ � ^ ++++ ++++ ++++
O ++++ ��• ++++
O ++++ � ++++
++++ }��� u ++++ ++++ ++++
��
O ++++ �.. '++++
++++ ++++ ++++ ++++
v
O ++++ �_
++++ �,x �� �� �� ++++ ++++
O ++++ �
++++ ++++`'r ++++ ++++ ++++ ++++ ++++
Toggle �-� .� �— � — �
O 7� Language —.
�\i� ++++ ++++ ++++ ++++ ++++ ++++
� Lamp Test
.� ++++ ++++ �
�-------------- ---------------------------'
SWITCH PROGRAMMING EXAMPLES;for UL listed systems, LOWER LABEL INSERT allows custom labeling of the
designate the bottom switch for Lamp Test;for dual language
systems,you can program a second switch to change the language six ACK/SilencelReset switches antl labeling of their
display(text shown for reference only,slide-in labels are blank) associated LEDs
` � � • 11 � .
Data Sheet Subject Data Sheet Subject Data Sheet Subject
S4100-0031 Standard Panel Reference S4100-0035 MINIPLEX°Transponders S4100-0034 Audio/Phone Modules
S4100-0036 Network Display Unit S4081-0002 Remote Battery Charger S4100-0032 LED/Switch Modules
S4100-0038 Remote Annunciators S4100-0046 IDNet+Module w/Quad Isolator S4100-0037 Enclosure Options
5 S4100-0045-6
. . .
4100ES Master Controller with InfoAlarm Command Center(see data sheet S4100-0031 for descriptions of the 4100ES
Basic Control Panel details,standard product features,options,and reference for related fire alarm control panel products)
Model Model Type UL ULC Voltage InfoAlarm Command Center Type Master Controller Features
4100-9114 English ✓ — 9 A s stem ower
4100-9115 En lish 120 VAC, 60 Hz Master Controller Assembly; raised keys Y p
g �/ with fixed labels supply/battery charger(SPS),
4100-9116 French 250 point IDNet interface,
4100-9213 International J — 120 VAC, 60 Hz 3 NACs,auxiliary relay,and
220/240 VAC, Master Controller Assembly;flat keys external RUI communications
4100-9212 International ✓ — 50/60 Hz With inserts for custom key labels interface
4100-9122 English J — 120 VAC, 60 Hz Redundant CPU (Master Controller); One Command Center,two
raised keys with fixed labels CPU cards, and an SPS in a
two bay assembly; NOTE: For
4100-9222 International �/ _ 220/240 VAC, Redundant CPU (Master Controller);flat external RUI,use 4100-1291
50/60 Hz keys with inserts for custom key labels RUI Expansion module(s)
Upgrade Kits (see NOTE for NDU upgrades; Upgrade kit are UL and ULC listed)
Model Model Type Description NOTE
Upgrade Kit for existing 4100ES or 4100U Series Fire Alarm Control Panels;includes
4100-7153 English complete bay front assembly with InfoAlarm Command Center providing raised keys with
fixed labels;uses existing power supply and Master Controller Board(CPU card)
Upgrade Kit for existing 4100(Legacy 1000 pt,4100+systems)Series Fire Alarm NDU
Control Panels(non-4100U);includes complete bay front assembly with InfoAlarm upgrades
4100-7154 English Command Center; raised keys with fixed labels,and replacement Master Controller Board; require
uses existing power supply
4100-0640
Upgrade Kit for existing 4100ES or 4100U Series Fire Alarm Control Panels;includes Display
4100-7155 International complete bay front assembly with InfoAlarm Command Center providing flat keys with Memory
inserts for custom key labels; use for non-English language applications including French Expansion,
for Canada; uses existing power supply and Master Controller Board(CPU card) see below for
Upgrade Kit for existing 4100(Legacy 1000 pt,4100+systems)Series Fire Alarm details
4100-7156 International Control Panels(non-4100U); includes complete bay front assembly with InfoAlarm
Command Center;flat keys with inserts for custom key labels,and replacement Master
Controller Board; use for Canadian French applications; uses existing power supply
Network Display Unit(NDU) Master Controller with InfoAlarm Command Center
(NOTE: See data sheet S4100-0036 for NDU feature details and for details on SPS NAC ratings for NDU with VCC)
Model Model Type UL ULC Voltage NDU Type Master Controller Features
4100-9151 English J — Includes:4100-06401nfoAlarm
4100-9153 English 120 VAC, 60 Hz NDU (Standard, Non-Voice); Memory Expansion, Network Intertace
4100-9154 French '� raised keys with fixed labels Module(select media cards
separately),9 A SPS power
4100-9245 International J — 120 VAC, 60 Hz NDU (Standard, Non-Voice); supply/batt.charger,and external RUI;
flat keys with inserts for (NOTE: SPS IDNetT"" channel and
4100-9243 International ✓ — 220/240 VAC, 50/60 Hz custom key labels NACs are disabled)
4100-9152 English ✓ — NDU with Voice Interface Includes above features and adds:
4100-9155 English ✓ 120 VAC, 60 Hz and Control; raised keys VCC Bay with Standard CPU Module,
4100-9156 French with fixed labels Network Interface Module(select
4100-9246 International ✓ — 120 VAC, 60 Hz NDU with Voice Interface media cards separately),9 A SPS with
and Control;flat keys with 250 Point IDNet Interface, (3)3 A
4100-9244 International J — 220/240 VAC, 50/60 Hz inserts for custom key labels NACs,and ext. RUI comm. interface
Remote Annunciator with InfoAlarm Command Center(see data sheet S4100-0038 for Remote Annunciator features)
Model Model Type UL ULC InfoAlarm Command Center Type Master Controller Features
4100-9612 English ✓ ✓ Includes Expansion Bay with
With raised keys and fixed labels Basic PDI, Remote TIC module;
4100-9613 French — ✓ Remote
Annunciator Power is supplied from host
4100-9614 International ✓ — With flat keys&inserts for custom key labels control panel
4100-9607 English ✓ ✓ Includes Expansion Bay with
With raised keys and fixed labels Remote PDI, Remote TIC module;
4100-9608 French — ✓
Annunciator power supply is specified
4100-9609 International ✓ — With flat keys&inserts for custom key labels separately when configured
InfoAlarm Command Center Memory Option (may be required to be ordered separately,see description details)
Model Description
4100-0640 Display Memory Expansion Module; included with NDU systems; required for all InfoAlarm Command Centers
connected to a panel if any are using 2 byte character fonts; 6 Meg module mounts on rear of display board
(continued on next page)
6 S4100-0045-6
• � • / '•
Remote InfoAlarm Command Center Control Assembly with Cabinet for Surface Mounting
Model Number/Cabinet Color
Application Type Listing Description
Red Platinum
4100-9401 4100-9403 English UL&ULC Remote InfoAlarm Command Center with cabinet;for
surface mounting; includes mounting box and door
4100-9421 4100-9423 French/Canada ULC assembly with glass insert; uses RUI communications;
requires external 24 VDC system voltage; see illustrations
4100-9441 4100-9443 International UL below and Installation Instructions 579-687 for details
. . � . • .
o�
�� O 00�
���� S�'SiFN iS I�IQMf�I ��0�
��� ��' �����
`O l ��> '��� ��� O O O
��c��� � �>
���0 �
� �o� 0000
. • . . . � • • Es
. . � . . . .
Box and door width=20-1/2"(521 mm) Depth 2-3/4"
(70 mm)
2"(51 mm)
16"(406 mm) 3/4"(19 mm) i i�
�•�►E
RUI Communications
wiring terminals ���`=�
I I
8" Transponder
(203 mm) Interface Card see
(TIC) conduit
13-1/16"
� 24 VDC power input � � (332 mm) note
wiring terminals
NOTE: Bring wiring through back of box;do not use cabinet bottom;
refer to Instal�ation Instructions shipped with assembly
7 S4100-0045-6
. - . .
General Display Specifications
Dot Matrix Size 320 x 240
Active Display 4.53"W x 3.4"H (115 mm x 86 mm), includes header,footer,and softkey
Size Reference Area area; 5.66"diagonal measurement(144 mm)
Characters Up to 854 characters total using standard ASCII character font
Designation QVGA; one quarter of standard VGA(Video Graphics Array)display
Display Polarizer Type Transflective with rear backlight
Display Adjustment Contrast adjustment is located on the controller module
Backlight White LEDs with intensity adjustment and selectable AC power fail operation;
intensity adjustment is located on the controller module
Backlighting Operation Options On continuously; Off with AC power fail until a switch is pushed;selectable
timeout without switch activity
Control Panel Mounted InfoAlarm Command Center Current Requirements
Master Controllers(4100-9114,-9115, Supervisory 447 mA @ 24 VDC
-9116,-9212,-9213,-9222) Alarm 542 mA @ 24 VDC; backlight and tone-alert on
Redundant CPUs Supervisory 782 mA @ 24 VDC
(4100-9122,-9222) Alarm 964 mA @ 24 VDC; backlight and tone-alert on Panel currents only
Network Display Units, Non-Voice Supervisory 492 mA @ 24 VDC are shown, add
(4100-9151,-9153,-9154,-9243,-9245) Alarm 547 mA @ 24 VDC; backlight and tone-alert on external device
loading per system
Network Display Units,Voice Supervisory 912 mA @ 24 VDC requirements
(4100-9152,-9155,-9156,-9244,-9246) Alarm 989 mA @ 24 VDC; backlight and tone-alert on
4100-7153&-7155 for 4100U add 82 mA supervisory;add 127 mA for alarm
Upgrade Kits
4100-7154&-7156 for Legacy 4100+ add 235 mA supervisory; add 280 mA for alarm
Remote Annunciators with InfoAlarm Command Center, Powered from Control Panel
Voltage 19 to 33 VDC(24 VDC nominal),system supplied; requires separate wiring
Current Supervisory 186 mA @ 24 VDC
Alarm 214 mA @ 24 VDC; backlight and tone-alert on
Mounting Details; Stand-Alone Cabinet Models See page 6 for reference illustration
Type RUI (Remote Unit Interface)external annunciator communications line SLC
(signaling line circuit)
Capacity Up to 31 total remote RUI devices, including up to 10 InfoAlarm Command
4100ES Capacity, Center devices
RUI Output 4100ES: InfoAlarm Command Center, Remote Annunciators, MINIPLEX
RUI Device Transponders;4603-9101 LCD Annunciator,4602-9101 Status Command
Reference List Unit(SCU), and 4602-9102 Remote Command Unit(RCU); refer to data
sheet S4100-0031 for additional 4100ES RUI information
Data Single twisted, shielded pair, 18 AWG(0.82 mmZ)
Power 18 to 12 AWG(0.82 mm2 to 3.31 mm2)wires for 24 VDC system power
Wiring Requirements A dedicated earth ground connection to the electrical box is required for
Earth proper ESD and EMI protection;wire in accordance with NFPA 70(National
Electrical Code°)Article 250
Custom Point Detail Messages
Select"more info"softkey when investigating point detail and scroll to the
Message Location Details bottom of the information;typical messages might include contact details
(phone numbers, pager numbers, etc.)and other contact or reference
information
Number of Messages Up to 50
Character Details 120 characters;visible characters= 116; (lines 1 and 2 require one carriage
return character and one line feed character)
Message Size
Line Details 3 lines total;40 characters maximum per line; line 3 may be limited to 36
visible characters depending on characters in lines 1 and 2
Operating Temperature 32°to 120°F(0°to 49°C)
Environmental
Operating Humidity Up to 93% RH, non-condensing @ 90° F(32°C)maximum
Tyco is a registered b-ademark of Tyco lnten2ational Services GmbH and is arsed under[Lcense.Simple,r,IUNet,MINIPLFX,InfoAlarm,and zhe Simplex logo are trademarks ojTyco
Internationa/Ltd.and its affiliates and are used under license.Na[ional Electrical Code arvd NFPA are trademar�.r of the Natiorval Fir�e Protection Associa[ion.
�3S i m p I Ex Tyco Safety Products Westminster• Westminster, MA•01441-0001• USA S4100-0045-6
o www.tycosafetyproducts-usa-wm.com
C�2011 Tyco Safery Piroducts Wesdninrter.Ali nghtr reserved.All specificatzons and other information shown were current as ofdocaanent revision daze and are subject to change without notice.
�oSimplEx Fire Control Panel Accessories
UL, ULC, CSFM Listed� SafeLINC Fire Panel Internet InterFace for
Model Series 4100ES, 4010ES, and 4100U
� SafeLINC Internet
Interface main screen
SafeLINC Fire Panel Internet Interface (FPII) enables
investigation of fire alarm control panel status �
�� �
using the familiar interface of an Internet browser:
• Intuitive menu screens are refreshed automatically with ----�---
the occurrence of new events ��
• Support is for to 50 user accounts with up to five ,��
Simultaneous users Local Interne�
• Annunciation and reporting capacity up to 12,000 points connection Remote PC
—� � with Internet
• Supports either DHCP or static IP addresses � ��-- �, browser
• Compatible with Microsoft Internet Explorer(version � -°�
6.0 or higher) '
Remote status Intranet/Internet Service
• Listed to UL Standard 864 and ULC Standard S527 summary Provider Network
Security access features:
• Multiple user accounts and passwords(similar to the
host control panel) i�Loca�network
connection
• Programmable lockout on login screen prevents - �
excessive login attempts by unauthorized users
o�
Fire alarm control panel model compatibility:
• Compatible with 4100ES,4010ES;and 4100U at
revision 12.06 or higher Fire alarm
Automatic or scheduled email feature provides �:� ' �ontroi panei
selectable notification to user accounts: safeuNC ,-.-e
• Built-in email feature will notify user accounts of FPII module '�e �
individually selected status changes either automatically --�o IIqIIIIIIUIaIIpIIIIIIINIIIIIIIINIIIIQIIIIINIIII�IdII@lul
IInItlINIdIIIIINI�I�INIIIIIIIINI01nIIIIIUI�In101101101
or as scheduled
• Compatible email services include:local SMTP email
servers,ISP provided email service,and Internet email SafeLINC FPII System Connection Drawing
service (4100ES Fire Alarm Control Panel shown for reference)
• Email capacity includes addresses for the 50 user � . � �
accounts and up to 5 separate email distribution lists
with each supporting up to 20 additional email addresses Fire Alarm Control Panel System Information.
• With 4100ES,4100U,or 4010ES control,action Simplex°fire alarm control panels monitar their
messages can be sent to email distribution lists for connected devices and gather system information to
Emergency Communication System(ECS)operation describe the status of the protected buildings. This
(see details on pages 3 and 4) information is available at the panel and via accessory
• Information can be alarm,prioriry 2,supervisory, devices such as remote terminals or dial-in modems,all
trouble;or TrueAlarm Sensor Service and Status Reports requiring special equipment connections.
• Compatible pagers,cell phones,or Personal Digital Secure Internet Access. The SafeLINC Internet
Assistants can receive direct email messages ar interface provides an alternative access to system
messages forwarded from a user account information using the familiar interface of a standard
Internet browser. A remotely located fire professional can
Available information: use this access to analyze control panel status during
• Alarm,Prioriry 2 Alarm, Supervisory,and Trouble non-alarm conditions and can also use this information to
counts and status messages assist local fire responders during alarm conditions.
• Detailed point information accessible similar to that (NOTE; Secure access requires proper installation behind
available at the panel network firewalls consistent with local network security
• TrueAlarm sensor status including both status reports requirements.)
and service reports * 7fus product has bcen ap�xoved by the Califomia State Fre N}arslx�l(CSFM)pursuant to
• Alarm and Trouble log information Sedion 13144.1 of the Califania H�Ith and Safety Code.See CSFM Listing
7300.0026:0312.FM approv�l is not applic�ble fa'this product type.Pdditiax�listirx�s
On-board service PC port provides convenient rreybeapplicade;cont2ctyourlaalSirrplexprodudsupplierfa-thelateststatus.
installation setu and dia nostics �stingsa�dapprovalsurxlerSirrplexTmeRemrclerCo.arethepropertyofTycoFre
p J aoteaia,Products.
S4100-0062 8/2012
� . .
Fire Alarm Control Panel Status Count: Local PC time and remote
Fire; Priority 2; Supervisory;Trouble fire alarm control panel time
System menu for selecting History logs and
investigation detail ____ system reports access ___
� �
� '
�
�� �: -
S ' O(�7 Pb�1t17Yr1�
— ❑SafeLBJC User �
- p ppp 79:91ari�73RUC2012
�� Lnca I 7ime
p ppp 70:07am 73A1IG2072
System _a'�a_In�.FFii E.e�srx
1—'—
—_______�
' Central 5chool Distriet �
� „�s�;�� Merrjorial H'r�h Sehovl ;
� Anywtaere,�JSA �
� ,
'-��-- Hos[Fore AIBrtn Contrd PBnel-Gerreral Infr�rmatlon �
r System revisian:9.02 �
�
+ CFIG forma[:65 �
1 '
► Jo6 name:CFG1�2 �
3 Jo6 date 08-Aug-12 11:48 �--- Connected panel details
�
f Jo6 rev 16 �
i
�
AdrrgnSVadve Coniact{s) �
� PJame:admm �
�
� � Ema�l: �
f Primary Tel.555-555-5555 �
--------'
� -
ii P 11 •11 �
"� ' i'i�;: =-I DU41 I i�ueAla�-m Stet�.i� I T°�u�.cAl� �. PanelTrme
❑SafeLMClJser .! m �
❑9[iU TrereAkarmService � 70:07am73A11G2012
❑9U4 � f ..?",� . .- LocalTime
❑ppp . 70:07am 73A11G2012
� r � � ��� . r�
Systern �«�-INC FFII:Sysmm E•:Fnt:Fire E�:Fnt�_;.
Active Fire Event{s}
�° '=^'�''-' Fire events are listed for your system below.Click on the hypertext custom label to obtain detailed information about
_,�stern Sun� the oint shown.The Fire events list will be refreshed automaticall
.cnuni Se";. P Y-
�
F _,_ __. ,__. „_ ..���<.
2-1-0 YES
_:. .,. .�':[-3[I15:
PULL STATION FFEE
Emergency Contact(s�
Name:admin
Email: . .. . . ..
Prircary Tel:55�..55�..5555
Custom FAessage:Please repa�rt any p�ro�hlems to J.One
2 S4100-0062 8/2012
. . .
Model Compatible Panels Mounting Reference RS-232 Port Consumption
4100-6079 4100ES or 4100U Fire Alarm Control Mounts in Blocks A&B in an Reduces Control Panel RS-232
Panels expansion bay Bi-directional Port capacity by one
(refer to specific panel documentation
4010-9923 4010ES Fire Alarm Control Panels Requires two vertical block spaces for capacity and additional information)
. . - � � • � . •
Sample Emergency ALERT and ALL CLEAR Messages
From: System Administrator From: System Administrator
Sent: Monday,August 13,2012 1:30 PM Sent: Monday,August 13,2012 2:30 PM
To: Campus Emergency Distribution List To: Campus Emergency Distribution List
Subject: SafeLWC: Action Alert! Subject: SafeLWC: Action Alert!
HOSTILE INTRUDER ALERT!-Campus Lockdown-remain in ALL CLEAR! Emergency Situation under control.Resume
rooms.If off-campus remain off-campus until further notice. normal activities
FACP DATE/TIME..:13AUG2012 128pm FACP DATE/TIME..:13AUG2012 2:28pm
'� ---►
�
�
�
; Compatible wireless message devices receive either
; directly addressed or forwarded email messages
�
,
Email distribution � ,' Cell Phones �
` • - � '� Pagers Address selected to
receivers " R
'/i� '�� .� receive email
ern �% � � �=°--= --
us . �\ //, _ ,
User 2 (from PC or direct) �` p� Forwarded message
_ — �, ;•i
, .--�---- — �
�< � � Intranet/Internet Service �
�._ ,
user� "--- - �� MIS/IT email Provider Network — � '�
distribution lists �'�
� --------:" "���
��j'�� i� Automatically generated email is
DACT output for routing �� sent to user account list for
alarm to local fire department I! supplemental notification
�;i
TrueAlarm smoke sensors ____--_______ �� Fire Alarm Control Panel
� (4100ES shown for reference)
-.,e:,88� °B
�
To remote
Manual Emergency ------------
Message Control � � annunciators
(external or LED/Switch ,�-�
module on panel) o��
� � �
I . � � �
-a � IIIY�IIIIIItl�lllllq1111111�11111�plllll�tlllllll
!=�• I��Illll�lllll�llllll�llllll�dlllll�llllll
SafeLINC FPII module; size: '--a� , Local panel alarm
4"x 11-5/16"(102 mm x 287 mm) ___ notification appliances
3 S4100-0062 8/2012
. . - .
The SafeLINC Internet interface is normally installed into � �
a local facility network using conventional CAT 5 wiring
(or better)and configured similar to an individual
u����,��,�:
computer. The following summarizes the typical � �
requirements:
• Mount behind securiry firewalls for maximum protection P���'�4rs�:
• To automatically send emails,a simple mail transfer � �
protocol (SMTP)mail account is required �
• Each module has a unique Media Access Control (MAC)
address that will be required by the local MIS/IT
department to configure on the network
� Primary Login Screen
Anonymous Login Screen.The primary login screen � , �
(upper rigl�t)does not describe the available connection.
Unauthorized visitors that might find the SafeLINC Email Feature.User accounts include email addresses
Internet interface location would not know the purpose of to allow the receipt of automatically generated or
the screen. previously scheduled messages.Each user account can be
Selectable Login Parameters. The designated selected for the event message categories required. Email
SafeLINC FPII Administrator(s)can select the following "from"field can be customized for accurate identification.
parameters: Each user can configure email size and data format to
• Programmable login attempts before lockout; selectable receive only what is desired including formatting for SMS
from 1 to 20 with 3 as default text messages.
• Following an unsuccessful login attempt,a lockout Note: Use of email server distribution lists can assist to
period is in effect and during this time no access is notify the required recipients.
allowed; lockout time is selectable from 0 to 24 hours, Emergency Communication Messages.When
with 1 hour as default controlled from a 4100ES,4010ES,or 4100U Fire Alarm
• If desired,individual TP addresses ar address series can Control Panel(4100U at revision 12.06 or higher),the
be blocked from access custom point detail action messages(up to 50 per control
• Information is gathered about any unsuccessful attempt panel)can be programmed(at the pane])to route to selected
to login and emailed to the administratar(s) email distriburion lists.With messages similar to those
� , • - - - . . � shown on page 3,this can be part of an Emergency
� Communications System(Mass Notification).Note: All
These reports can be viewed or emailed as attachments: paint detail action messages will route to the selected lists.
• TrueAlarm sensor status reports for sensitivity
selection,device status, and dirt accumularion status; Message Forwarding. At the receiving email account,
also available is the dirty detector report messages can be forwarded by tbe local email application.
• TrueAlarm sensor service reports including details of Messages can be forwarded to another computer,cell
current status,recorded peak status; and CO sensor phone, pager, or other email compatible message
service reports including status and end of life date receiver.If desired, a user account could include an email
• TrueAlert addressable candela reports and status reports address list to allow distribution to multiple receivers
• Logs for: Fire Alarm,Priority 2 Alarm, Supervisory, without requiring forwarding and by using only one of the
and Trouble 50 available supported email addresses accounts. (Refer
. . . - .
to the message diagram on page 3.)
Compatible Internet Browser Internet Explorer 6 or above
Voltage Range 18 to 33 VDC,supplied from the host fire alarm control panel
Current,Supervisory and Alarm 145 mA maximum @ 24 VDC
LED 7 Ethernet link status indicator,green LED
Module Status LEDs LED 8 Ethernet link activity indicator, red LED
(for setup and service) Detailed status indicator,yellow LED; blinking codes provide internal diagnostics and
LED 3 details on external connections
Operating Temperature Range 32°to 120°F(0°to 49°C)
Operating Humidity Range Up to 93°/o RH, non-condensing @ 90° F(32°C)maximum
Technical Publication Reference 579-1004, Installation, Programming, and Operating Manual
TYCO,S/MPLEX,and[he product names listed ni this material are marks and/or registered marks.Unaufhorized use is sG�ictly prohibited.MicrosoJt is a trademark of Microsoft
Corporatiore in the US.and other courrtries.
�05 i m p I Ex Tyco Fire Protection Products• Westminster,MA•01441-0001•USA S4100-0062 8/2012
www.simplexgrinnell.com
�2012 Tyco Fire Protection Praducks.Ali nghts reserved.A!!speci�ications and other in%rrynafion shown were c�Arrent ns of document revision date and are subject to char�ge without notice.
��SimplEx 4100m Fire Control Panels
UL, ULC, CSFMListed; FMApproved; Addressable Fire Detection and Control
MEA (NYC) Acceptance* Emergency Voice/Alarm Communications Equipment
� --
Emergency voice/alarm communications provide:
_-----
• Alarm/evacuation signal generation with multiple � '�>
built-in tones = �-'��
� J'
• Standard or customized digital message storage and �� ,
message generation
• Automatic or manual operation
• Mass Notification o eration p ���)
P � �_�
Multiple channels are available: ➢� I� �
� , �_ :
• Analog audio systems provide dual channel operation __
• Digital audio systems provide up to eight channels over �
a single wire pair ����,�,�
l
Communications features: �0
• Up to five supervised remote microphone inputs
• Spoken voice coding from the digital message player IQ90909�09VIIIIIII�V90909�IIIIIIII�90000�9QIIIIIIVQ9V9090 — —
• Multiple digitally recorded human voice messages IIVVBODdG�IIIIIIII�V�00���IIIIIIII��00����VIIIIIIV0��d0�0 �
• Spoken WALKTESTT`'system testing** ff°�'�
• Separate evacuation,drill,and optional"All Clear" �
voice messages and tones
• Ready-to-talk microphone indicator on front panel audio
control module 4100ES Fire Alarm Control Panel with
• Local panel speaker for tone/message broadcast
Voice and Firefighter Telephone Options
verification Listed to:
• MINIPLEX�Voice Transponders are available for . UL Std. 864,Fire Detection and Control(UOJZ),and
distributed alidio
Smoke Control Service(UUKL)
Amplifiers are available with analog or digital input: . UL Std. 2017,Process Management Equipment(QVAX)
• Flex-35 (35 W)and Flex-50(50 W)amplifiers provide a
dual channel design with configurable operarion modes
** • UL Std. 1076,Proprietary Alarm Units-Burglar(APOU)
• UL Std. 1730, Smoke Detector Monitar(UULH)
• 100 W primary and backup,single channel amplifiers . ULC Std. S527-99
include a built-in power supply
• Amplifiers are available for 25 VRMS or 70.7 VRMS
output with on-board,power-limited NACs(only one � � ' '
voltage choice per systein) 4100ES Audio Systems provide voice communication,
• Built-in Temporal Pattern horn tone provides default alarm tones, and/or digitally prerecorded voice messages to
backup signal operation alert occupants of fire ar other emergency situations.
• Optional modules provide power-limited NAC expansion, Evacuation signaling may be automatically generated via
convert Class B NACs to Class A operation,and provide alarm initiated event programs or by firefighting personnel
Constant Supervision Operation for Non-Alarm Audio using the operator controls.
(NAA)applications(NAA requires additional hardware,
and software revision 11.08 or higher) 4100U Series Products Note.The audio system
Firefighter telephone systems: modules and features listed in this data sheet are both
• Master telephone can simultaneously talk with up to 6 compatible with,and listed for use with 4100U series fire
remote telephones and can be connectcd as an audio alarm control panels. Contact your local Simplex�product
input far broadcast messages supplier for details.
• Rlrig S1griS1 Ori YCTYlOtO f1T'@f gI1t0T't01CphOrie 1riC11Cat0S tllat ` See page 5 for product that is listed as UL or ULC and additional product listing details.
This protluct has been approved by the California State Fire Marshal(CSFM)pursuant to
3 C211 T0CjU0St 1S 1ri1t1atCCl ariCl 3 IlO1Cl Slgri31 1riC11Cat0S t�11t Section 13144.1 of the California Health and Safety Code.See CSFM Listing
a COl]rieCt�d Ilri�haS bCCri dCS�1�Ct�d 7165-0026:251 for allowable values andlor conditions concerning material presented in this
document.It is subject to re-examination,revision,and possible cancellation.Accepted for
• T�l�phOriO Clt'CU1tS al'e SUpeI'V1Sed fOT Operi 1rid ShOY't use—City of New York Department of Builtlings—MEA35-93E.Atltlitional listings may be
C1YCU1tS,t00 tT13riy t�lepllOriCS COririeCtECl,ariCl tll�YYlaStOY applicable;contact your local Simplex product supplier for the latest status.Listings and
telepY1011e 1S SUpet"VISOCl fOC COCC� 1I7t0gClty approvals under Simplex Time Rewrder Co.are the property of Tyco Safety Products
Westminster
• Degraded mode allows reinote telephones to remain
*` WALKTEST system test is protected under US Patent No.4,725,818.Flex-35 and Flex-50
COri170Cted t0 eaCh OtheT Iri the 0V011t Of a C0171171Uri1Cat1011S amplifier operation is protected untler U.S.Patent No.6,452,491.
�OSS
S4100-0034-11
� � • • • • � � - • • � • • •
The Audio Controller Module provides digitized alarm The Temporal Pattern is available for compatible tones
tones and digitally recorded voice messages and message (1/2 sec on, 1/2 sec off, 1/2 sec on, 1/2 sec off, 1/2 sec on,
construction,and manages both microphone inputs and other 1-1/2 sec offl to indicate evacuation. The following is a
auxiliary inputs connected to the optional Auxiliary Audio list of the standard audio tones.
Input Module. Tones and voice messages are digitally • Horn,conrinuous 500 Hz tone,primarily used for coded
recorded and stored in the audio control module's message systems or general temporal pattern signaling
memory.
• Chime,a digitally recorded mechanical chime tone,
Two versions are available: Analog and Digital. Systems normally used free-running or for coded operation
must be either analog or digital,not intermixed. One audio . gell,a digitally recarded mechanical bell sound,
control module controls the entire audio system. normally used free-running, for coded systems,or
Common audio control board features: general temporal pattern signaling
• On-board digital message memory provides up to . Fast Whoop,a quickly ascending tone
2 minutes at normal or 1 minute at high resolution • Slow Whoop,a slowly ascending tone
• Connects to oprional4-input audio input modules(two , High/Low,with high frequency of 750 Hz for 100 ms and
maximum)for a total of up to 6 microphones and 11
distinct audio inputs low frequency of 500 Hz for 400 ms
• Memory expansion is available to provide up to • Beep,500 Hz tone of 0.7 s on,0.7 s off
8 minutes or 32 minutes at normal resolution • Stutter,500 Hz tone with on and off times of 100 ms
(4 minutes or 16 minutes at high resolution) • Wail,ascends,then descends between 600 to 940 Hz
• Connections for a Master Microphone and one • GSA Tone,continuous 2000 Hz tone
Remote Microphone, compatible with standard or
noise-canceling microphones ' • • • • " • ' ' � " • •
• Master telephone to audio interface connection uses the Zone Coded Signaling is available using tones or
audio bay's Power Distribution Interface Module(PDI) spoken numbers. Spoken coded messages can be used in
• Local paneL speaker output with on-board volume control place of convenrional pulse tone coding to eliminate
• On-board download port for message loading counring and interpretation of the zone coded location.
• The microphone ready-to-talk LED is located on the For example,a fire alarm zone such as First Floor East,
front panel audio control module(see p.4)and Smoke Detector Room 23 will be Code 1123.
requires connection to a 64 LED/64 switch controller Two possible transmission schemes are:
• Audio risers,either digital or analog,may be directly
connected to 31 remote nodes;for applications requiring 1. Convenrional Zone Coded Signaling where
audio risers to more than 31 remote nodes, alternate T=Tone: T...T...TT...TTT...T...T...TT...TTT...
connecrion methods are available,contact your Simplex �• Spoken Coded Signaling:
product representative for details Code, one..one..two..three,- Code, one..one..two..three
, , � � , � � � � . � � The Audio Controller has the ability to precede spoken
codes with phrases and alert tones.As an alternative,the
Analog audio control modules are far systems that previous example could have been preceded with a chime
require one or two simultaneous channels of audio tone. The word"code"could be replaced with the phrase
information per the following feature summary. "Doctor Firestone,please dial...".
• Built-in 10 VRMS riser output eliminates the need for Preprogrammed Special Messages can be ordered.
separaYe riser amplifiers available as Class B or Class A Up to 32 minutes of special phrases and messages are
• Messages can play on one or both risers simultaneously, available to meet specific applications. The standard
with the same ar a different message Evacuation Message is: "Attention...Attention...
• Analog audio controllers are for connection to analog Attention...An emergency has been reported....All
input audio amplifiers and audio risers only occupants walk to the nearest stairway exit and walk
• On-board status LEDs assist with setup and down to your assigned re-entry floor or main lobby...Do
troubleshooting not use the elevator... Walk to the nearest stairway.... Do
� � � • • • • • �
not use the elevator.... Walk to the nearest stairway."
, Custom Message Ordering is summarized below:
Digital audio control modules are for systems that
require more than two simultaneous channels of audio Model Description
information per the following feature summary. Select when Custom Messages are required,
• Up to 8 channels of information at normal resolution are 4100-8804 choose message types from below as required
(minimum quantity of one)
available(4 channels at high resolution)on one twisted 4�00-0822 Custom Messages from Tape
wire pair Order(1)
Custom Messages from 4100-082x for
• Primary 1 Digital Audio Riser(DAR)output can be either Transcript; NOTe; Send
wircd Style 4 or Style 7;Primary 2 DAR is an identical, 4100-0823 transcript in advance to each(2)complete
separate output for Style 4 connections,typically to local Applications Engineering to messages without
verify phrase quantity spliced phrases;
MINIPLEX voice transponders or for each(50)
• Digital audio controllers are for connection to digital 4100-0824 Custom Messages from spliced phrases
input audio amplifiers and digital audio risers only Archive
2 S4100-0034-11
` � • � • � - • • � •
4100ES audio amplifiers are available as dual channel • Each Flex-35 channel is capable of up to 35 W output
models rated for 35 W(Flex-35)or 50 W(Flex-50)and as with a total of 35 W
single channel 100 W models with on-board NACs . Channels can be divided as 0 W and 35 W; 17.5 W and
(norification appliance circuits)for convenient field 17.5 W; 10 W and 25 W; or any combination that totals
wiring. Common features are summarized as follows: 35 W or less
• Analog input amplifier models are for single or dual
channel system operation � � '
• Digital input amplifier models are for multi-channel • Each Flex-50 channel is capable of up to 50 W output
system operation providing up to eight channels over a with a total output of 50 W
single twisted wire pair . Channels can be divided as 0 W and 50 W;25 W and
• Amplifiers are power-limited with models available 25 W; 10 W and 40 W;or any combination that totals
providing 25 VRMS, or 70.7 VRMS output 50 W or less
• When Non-Alarm Audio(NAA)applications(such as � . � � � �
for background music,paging,or far Mass Notification)
are required,optional Constant Supervision modules • Two Flex-35 amplifiers,or two Flex-50 amplifiers can
provide conrinued speaker zone supervision during the connect to a single Expansion Power Supply(XPS)in
page or while background music is playing;due to the the same audio expansion bay(amplifiers must be the
NAA supervision requirements,amplifiers used for same model number);XPS output is dedicated to
paging or playing background music are derated to 70% amplifier power
of alarm output rating(24.5 W,35 W,and 70 W) • Mounting for dual Flex-35 or Flex-50 amplifiers is
• Linear power output stages are traditional Class B Blocks A&B for amplifier 1,Blocics C&D for the
designs for low distortion and low EMI XPS,blocks E&F are not used,and Blocks G&H are
• An on-board 500 Hz temporal pattern horn tone on each for amplifier 2 (see page 7 for mounting reference)
amplifier provides a default backup tone � � . � � . �
• Supervision actively monitors amplifier gain in real
time,comparing output]evel to input level 100 W amplifiers provide single channel operation per
• On-board test switches can be activated to test and the following feature summary:
observe amplifier backup • Six standard on-board Class B audio NACs are each
• On-board overcurrent protection protects against rated for 2 A maximum
overloads and short circuits • 100 W amplifiers include a built-in power supply and
• Each amplifier communicates to the host CPU and use system battery backup
allows voltage and current values to be accessed from • Amplifier and power supply size requires four
the fire alarm control panel operator interface continuous blocks of expansion bay size
• A single 100 W primary amplifier or both a primary and
' � � � � a backup amplifier can be located on a single expansion
Flex-35 and Flex-50 amplifiers are a self-backup bay(refer to page 7 far bay loading)
dual channel design that provides a total of 35 W or • Redundant(backup)amplifiers interconnect directly to
50 W of audio power with the following common feature minimize wiring connections and their power is routed
summary: through the NACs of the primary amplifier
• Self-backup feature allows NACs connected to a disabled . Redundant amplifier operation can be configured as
amplifier channel to be routed to the remaining channel one-for-one or one-for-many depending on specific
with the full 35 W ar 50 W providing the single channel requirements
as selected by the fire alarm control panel programming; • DigiYal models of these amplifiers have a digital decoder
external backup amplifiers are not required module that selects the desired input channel per system
• Three standard on-board audio NACs are each rated for requirements
2 A maximum and are capable of being routed to either . Selectable reduced output levels of-12 dB or-6 dB are
desired amplifier channel available far non-emergency audio output
• Compatible power supplies include the: Expansion
Power Supply(XPS),Remote Power Supply(RPS), � ' ' � ' ' ' ' '
or System Power Supply(SPS);power supplies with . For applications requiring additional NACs,modules are
single amplifiers can provide power for other comparible available for on-board expansion and further expansion
applications within their rated output is available witl�the chassis mounted 4100-5 l 16
• Digital models of the Flex-35 and Flex-50 have a digital Expansion Si�nal Module
decoder module that selects one or two of the input . l00 W Amplifiers support optional modules tbat convert
channels as desired the six audio NACs to Class A or to inerease the Class B
• Selectable reduced output levels of-12 dB or-6 dB are audio NACs to twelve
available for non-emergency audio ouYput, selectable per • NOTE: Adding NAC expansion modules does not
channel increase amplifier power beyond the stated ratings
3 S4100-0034-11
� . . . � . . . . . . - . . . .
Ph phone Audio Spe ker
Control Control Control Circuits
oo� oo� oo� oo�
oo� oo� oo� oo�
oo� oo� oo� oo�
Push-to-Talk oo� oa° �a° �a°
switch
oo� oo� oo� oo�
oo� oo� oo� oo�
00
000 000 00 000 000
000 0�0 00 0�0
00
Master Phone 8 Switches with 8 Master Microphone 8 Switches with 8 Red
Module 4100-1270 Red LEDs, Module 4100-1243 LEDs,4100-1280
4100-1280, 2 shown
with typical labels Single Channel Audio
Control 4100-1252
� • • • • • •
4100-1252, 4100-1253, 4100-1254, 4100-1255,
Single Channel 1.5 Channel Dual Channel 3-8 Channel
�I -�
Audio Audio Audio Audio
Control Control Control Control
�omma�d Green �omma�a Green �emma�d Green �omma�d Green
A���e, �e��� �e��� ce�
r��e LED �� A n�a LED A n LED n�we LED
AIl AIl AIl � AIl —�
Speakers � Speakars � Speakers Speakers I
EVAC � EVAC � EVAC I EVAC
I I I I
i_ Red i
se�e«��a � se�e����e � se�e«�..e i LEDs Q SA��" i
evAC � Red evnc I R0d EVAC seie�cea
i �
Visible area i LEDs � LEDs i F Red
se�e«��e se�e«��e LEDs
8-1/4"H 2„W � A�e,� � A�en � i
(210 mm x 51 mm) � �
i i �
_i i �o�a� —i i
Speaker �
EVAC � '
� �
Local _ � Local � � Local � �I
Speaker � Speakar � Speaker �
E�A� A�en Green
� Green i Green � LEDs
All — All All All
sPeake,� � LEDs �aeake,� � LEDs sPaake,s i � sPeake�s �
raik � raik � raik � reik �Green
i i i i LEDs
Reatly _� Ready _� Ready _� Ready _�
Ta�lk Talh Talk Talk
Blank switches can be
programmed as required
4 S4100-0034-11
. - . � . . . . . . .
NOTE: Select systems as either analog or digital (refer to pg. 7 for mounting reference and pg. 8 for additional specifications)
Analog Emergency Voice/Alarm Communications Equipment, Constant Supervision Compatible
Model Description Details
4100-9620 Basic Analog Audio Operation with microphone,requires Includes: Expansion Bay,4100-1210 Analog Controller Board,
dedicated expansion bay Microphone Module,and Audio Expansion Bay Kit
4100-1210 Analog Controller Board only;order expansion bay and Controller board mounts in Blocks A and B
audio expansion bay kit separately
4100-1361 25 VRMS output Flex-35,35 W Amplifier,constant NAC rating=1.4 A 35 W,or 100 Includes three on-
4100-1362 70.07 VRMS output supervision compatible NAC rating=0.5 A speakers max. board Class B audio
NACs;power is
4100-1312 25 VRMS output Flex-50,50 W Amplifier,constant NAC rating=2 A 50 W,or 100 supplied from an XPS,
4100-1313 70.7 VRMS output supervision compatible NAC rating=0.707 A speakers max. RPS,or SPS*
100 W Analog Amplifiers with Power Supply, Constant Supervision Compatible
Model/Output Voltage
25 VRMS 70.7 VRMS Power Supply Input/Listing Description Details
4100-1314 4100-1315 120 VAC,60 Hz UL Includes six, Class B audio NACs;
Primary NAC ratin 100 s eakers maximum;
4100-1316 4100-1317 120 VAC,60 Hz ULC �pp W g- p ULC
Am lifier 2 A@ 25 VRMS(50 W); models
4100-1318 4100-1319 220/230/240 VAC,50/60 Hz UL p 1.414 A@ 70.7 VRMS(100 W) have low
4100-1320 4100-1321 120 VAC,60 Hz UL battery
Backup Uses the six Class B NACs of primary dropout
4100-1322 4100-1323 120 VAC,60 Hz ULC 100 W amplifier circuit
4100-1324 4100-1325 220/230/240 VAC,50/60 Hz UL Amplifier
Digital Emergency Voice/Alarm Communications Equipment, Constant Supervision Compatible
Model Description Details
4100-9621 Basic Digital Audio Operation with microphone, requires Includes: Expansion Bay,4100-1311 Digital Controller Board,
dedicated expansion bay Microphone Module,and Audio Expansion Bay Kit
4100-1311 Eight Channel Digital Controller Board only;order Controller board mounts in Blocks A and B
expansion bay and audio expansion bay kit separately
4100-1363 25 VRMS output Flex-35,35 W Amplifier,constant NAC rating=1.4 A 35 W,or 100 Includes three on-
4100-1364 70.07 VRMS output supervision compatible NAC rating=0.5 A speakers max. board Class B audio
NACs;power is
4100-1326 25 VRMS output Flex-50,50 W Amplifier,constant NAC rating=2 A 50 W,or 100 supplied from an XPS,
4100-1327 70.7 VRMS output supervision compatible NAC rating=0.707 A speakers max. RPS,or SPS*
100 W Digital Amplifiers with Power Supply, Constant Supervision Compatible
Model/Output Voltage
Power Supply Input/Listing Description Details
25 VRMS 70.7 VRMS
4100-1328 4100-1329 120 VAC,60 Hz UL Includes six,Class B audio NACs;
Primary NAC rating=100 speakers maximum; ULC
4100-1330 4100-1331 120 VAC,60 Hz ULC 100 W 2 A@ 25 VRMS(50 W); models
4100-1332 4100-1333 220/230/240 VAC,50/60 Hz UL Amplifier 1.414 A@ 70.7 VRMS(100 W) have low
4100-1334 4100-1335 120 VAC,60 Hz UL battery
Backup Uses the six Class B NACs of primary dropout
4100-1336 4100-1337 120 VAC,60 Hz ULC 100 W amplifier circuit
4100-1338 4100-1339 220/230/240 VAC,50/60 Hz UL Amplifier
Audio Options for use with either Analog or Digital Systems (see page 2 for custom message ordering)
Amplifier and Related Audio Options
Model Description Details and Mounting Reference
4100-1245 Flex-35/50 Expansion NAC Module;adds Mounts on Flex-35/50 assembly; NAC ratings= 1.5 A,35/50 W,
three Class B audio NACs Choose or 100 speakers maximum; Supv. =8.4 mA,Alarm=60 mA
one per
Flex-35/50 Class A Adapter Module;converts Mounts on Flex-35/50 assembly; NAC ratings=2 A,50 W,or
4100-1246 three on-board NACS to Class A operation amplifier 100 speakers maximum; Supv. =1 mA,Alarm=30 mA
4100-1248 100 W Amplifier Expansion NAC Module; NAC Provides six additional Class B audio NACs,mounts on 100 W
ratings= 1.5 A,50 W,or 100 speakers max. Choose amplifier assembly; Supv. = 17 mA,Alarm=60 mA
one per
4100-1249 100 W Class A Adapter Module; NAC ratings amplifier Converts six on-board NACs to Class A operation,mounts on
=2 A,50 W,or 100 speakers maximum 100 W amplifier assembly; Supv. = 1 mA,Alarm=60 mA
25 VRMS Output; NAC Constant Supervision Supv. = 10 mA
4100-1259 rating=2 A, 50 W,or 100 Adapter for three NACs; on batteries; Converts three Class B audio NACS to Class A
speakers maximum select per amplifier output Alarm=35 mA or Class B Constant Supervision NACs;mounts
70.7 VRMS Output; NAC (not compatible with Supv. =38 mA on Flex-35/50 or 100 W amplifier assembly;
4100-1260 rating=0.707 A, 50 W,or amplifier NAC expansion Alarm=70 mA use two for the six NACs on 100 W amplifiers;
100 speakers maximum modules)
'Refer to data sheet S4100-0031 for power supply details. (continued on next page)
5 S4100-0034-11
. - . � . . . . . . . . -.
Amplifier and Related Audio Options (Continued)
Model Description Details and Mounting Reference
Expansion Signal Module;three, 1.5 A Class B Converts one NAC input to three NAC outputs;selects between two inputs;
4100-5116 NACs;up to five maximum per amplifier;NAC for Flex-35/50 amplifiers only,two input NACs are required;Single Block
rating= 1.5 A,50 W,or 100 speakers maximum module mounts in expansion bay; Supv. =20 mA;Alarm=80 mA
4100-1266 Expansion Signal Module NAC Expander; NAC Expands module capacity to six,Class B NACs;
rating= 1.5 A,50 W,or 100 speakers maximum Supv. =0.84 mA;Alarm=60 mA These modules
Expansion Signal Module Class A Adapter; NAC Converts 3 Class B, NACs to Class A; Supv. = 1 mA; mount on the
4100-1267 rating= 1.5 A,50 W,or 100 speakers maximum Alarm=30 mA 4100-5116;
select one max.
Expansion Signal Module Constant Supervision Converts 3 Class B NACs to Class B or Class A Constant per 4100-5116
4100-1268 Adapter for 25 VRMS or 70.7 VRMS; NAC rating Supervision NACs; Supv. =38 mA on batteries(constant as required
= 1.4 A,50 W,or 100 speakers maximum supervision deactivated);Alarm=70 mA
4081-9018 End-of-line resistor harness for 70.7 VRMS NACs; 10 kS2, 1 W
4100-2300 Expansion Bay Hardware;order one for each expansion bay
4100-2320 Audio Bay-to-Bay Interconnection Harness Kit;order one for each audio bay addition
4100-0637 Audio Box Interconnection Harness Kit;order one for each close-nippled audio cabinet
Audio Input and Controller Options (see page 2 for custom message ordering)
Model Description Details and Mounting Reference
4100-1240 Auxiliary Audio Input Module;four additional Inputs for 10 VRMS,25 VRMS, 70.7 VRMS,line Ievel(0.707 VRMS),or
(unsupervised)inputs per module;2 maximum microphone; 1 Block; Supv.current= 10 mA,Alarm Current=50 mA
4100-1241 8 Minute Message Expansion Module Provides 8 minutes at normal resolution or 4 minutes at high Mounts to
resolution, Supv. =2 mA;Active= 17 mA audio
4100-1242 32 Minute Message Expansion Module Provides 32 minutes at normal resolution or 16 minutes at controller
high resolution; Supv. =2 mA;Active= 17 mA module
Operator Interface and Related Options
Model Description Details and Mounting Reference
Microphone Module(mike);for Fire Alarm One maximum per audio system;front panel module that Supervisory
4100-1243 Control Panels requires 2 Slots(4"),locate on expansion bay only;space current=
behind for 4100ES flat modules only 2.4 mA
Remote Microphone Module;for Remote Front panel module that requires 2 Slots(4"),locate on Active
4100-1244 Annunciator Panels expansion bay only;space behind for 4100ES flat modules current=
only;distance limited to 4000 ft(1219 m) 6 mA
4100-1252 1 Channel(audio or mike) Single Slot LED/switch modules;connects to a 4100-1288 or 4100-1289
4100-1253 1.5 Channel(audio+mike) Operator LED/switch controller in the same bay;space behind controller accepts
4100-1254 2 Channel(full audio) Interface 4100ES flat modules only(see drawings on p.4);Current=24 mA;
3-8 Channel(8 channel normal LED/Switch Additional adjacent LED/switch modules,as shown on p.4,are used as
4100-1255 res.messages,4 channels of high Modules required for specific speaker circuit selection(refer to data sheet
res.messages) S4100-0032 for LED/switch module availability)
4100-1288 64 LED/64 Switch Controller Refer to Mounts behind the LED/switch modules;has LED/switch controllers
Module with mounting plate data sheet provisions for one 4100-1289 Controller Module and their connected
4100-1289 64 LED/64 Switch Controller S4100-0032 Mounts on extra space of 4100-1288;controls modules must be in
Module without mounting plate for details additional 64 LEDs and 64 switches the same bay
Firefighter Telephone System Products
Model Description Details and Mounting Reference
Master Telephone with Control Module and Front panel module;space behind for 4100ES flat modules only;phone
4100-1270 three Class B telephone NACs,one maximum control module included,mounted on bay module mounting plate;for
per audio system;for use in Fire Alarm Control individual telephone circuit control,use LED/switch modules;
Panels only; includes one 4100-1272 Module Supv. =80 mA;in use= 140 mA+remote phones(see tab/e on page 7)
4100-1271 Remote Master Telephone Mounts in Remote Annunciator Panel only(see S4100-0038)
4100-1272 Expansion Telephone Control Module with three Expansion module for additional telephone circuits in main control or
Class B telephone NACs transponders; Supv. =80 mA;in use= 140 mA+remote phones
4100-1273 Telephone NAC Class A Adapter Module Mounts to 4100-1270 or-1272; no additional current required
Network and MINIPLEX Transponder Audio Connection Options
Model Description Details
4100-0623 Network Audio Riser Controller Module for Typically for Network nodes without an audio controller, used for NAA
control of either an analog or digital riser module applications;mounts in Block A; current=35 mA
4100-0621 Dual Channel Analog Audio Riser Accepts two separate audio signals from host;controlled by Transponder
Module Interface Module;current=25 mA when active
4100-0622 3-8 Channel Digital Audio Riser Select one, Receives and decodes digital inputs;up to eight audio channels;
Module;with NAA input mounts in current=70 mA;NAA input for 25,70.7,or 0.707 VRMS
Block B Selects a single digital audio channel and converts it to an analog line level
4100-1341 MCC(Multiple Command Center) for input to an analog 4100ES/4100U/4100 Legacy voice panel;current=
Digital Audio Riser Interface 70 mA
4100-9854 4100/4100+Legacy bay mounting kit Use to mount 4100-1341 MCC Digital Audio Riser Interface in legacy panel
4100-1258 NPU to 4100ES Audio Interconnect Module; Dual terminal block module with harnesses for connecting to the Audio
mounts in 4100ES Audio cabinet Controller and Telephone Control module(requires 1 Block)
6 S4100-0034-11
- . - . . - � - . . Remote Master Telephones mount in Remote
Annunciator Cabincts and are wircd as the only connection
Firefighter telephone systems provide two-way to a telephone circuit.By adding local LED/switch
communications for faciliries where radio modules, operation is that of the Master Telephone.
communicarions may not be available or are unreliable.
They are typically used during active firefighting Remote telephones are available cabinet mounted or
conditions,during a fire alarm investigation,or during fire far plugging into a dedicated telephone jack. Each hears a
alarm system inspection and test. ring tone when a call-in is selected and a hold tone when
placed on hold. When on hold,the remote telephones are
System Operation. Connections are made using a each separated from the talk line.
common talk line(party line)that includes a Master
Telephone and up to six reinote telephones.Remote The Telephone Interface Module provides three
telephones call into the Master by either being taken Class B(Class A option is available)telephone circuits,
off-hook or by being plugged into a telephone jack The connection for a master telephone,and a telephone riser
Master Telephone locarion receives a ring-in tone with a input. One module is supplied when selecting a Master
visible LED indicator for each telephone circuit. When Telephone.Additional telephone interface modules can be
the call is received,the operator selects the calling added as required.Telephone circuit outputs can be
telephone circuit using the assigned switch control. The programmed as remote telephones,as a Remote Master,
operator at the master location can place the original or for telephone riser operation. Telephone circuits are
telephone circuit on hold and connect to additional supervised for opens, shorts,and overload conditions. The
telephone circuits or add them to the talk line. Master Telephone is supervised for broken cord or
off-hook.
Master Telephone Operation. The Master Telephone
connects directly into a telephone interface module. A Telephone riser operation can be programmed to
Push-to-Talk(PTT)switch provides the operator with voice provide a telephone riser output that is used to
input control. Each master telephone uses local LED/switch interconnect telephone interface modules in different
modules to select telephone circuits and to silence any locarions. This output type has ring and hold tones
subsequent call-ins until selected. disabled.
Telephone CirCUit Control. A call request causes the Degraded Mode.If the telephone interface module
local call-in tone sounder and assigned telephone circuit loses communications with the host fire alarm control
LED to pulse quickly.Pushing the calling circuit's switch panel,telephone circuits off-hook are automatically
silences the local sounder and connects that circuit to the connected to the talk line allowing any telephone to talk
talk line.Activating the switch again places that circuit on to another simply by being picked up(or plugged in).
hold with a hold tone being heard at the remote telephones Master Telephone Control Current with Remote
and causing that circuit's LED to pulse slowly. Subsequent Telephones. The following table lists Master Telephone
pushes toggles from active to hold. Activating a telephone Contro] current with the addition of remote firefighter
circuit switch when no call is incoming places a request to telephones.
pickup on remote telephones equipped with local LEDs.
Master tele hones can be also be connected as an in ut to Remote 0 1 2 3 4 5 6
p p Phones
an audio controller module to allow audio system message Current(mA) 140 180 220 250 276 304 329
broadcasting without using a microphone.
. . . . . . . • .
Description Mounting
sioc� sioc z sio�s siot a siot s sioc s sioc� sioc s Audio Controller Modules Blocks A&B
n Network Riser Controller Module Block A
U � Audio Riser Modules Block B
� , , , System or Remote Power Supply Blocks E, F,G&H
Block A Block C Block E Block G ONLY
Expansion Power Supply Blocks G&H ONLY*
Flex-35 Amplifiers,2 max/bay" B�ocks E&F;C&D;
orA&B
Flex-50 Amplifiers,2 max/bay" Blocks E&F or C&D
100 W Amplifiers, 1 max/bay Blocks E, F,G&H
100 W Backup Amplifiers, 1 max. glocks A, B,C&D
per bay with primary amplifier
aio�k e Block D Block F Block H Master or Remote Phone Module Blocks A&B
Master or Remote Microphone Two vertical Blocks,
Module any location(except
� � next to telephone)
� � Telephone Module 1 Block
Expansion Bay Chassis
Expansion Signal Module 1 Block
Size Definitions: Block=4"W x 5"H(102 mm x 127 mm)card area Operator LED/Switch Modules 1 Slot
Slot=2"W x 8"H(51 mm x 203 mm)motherboard with daughter card NPU to 4100ES Audio 1 Block
Interconnect Module
'NOTE: When mounting dual Flex amplifiers on an
expansion bay,special mounting rules apply.
7 S4100-0034-11
. .
Input Power
Power Supplies;SPS, 120 VAC Models;4 A maximum @ 102 to 132 VAC,60 Hz
XPS,and RPS 220-240 VAC Models;2 A maximum @ 204 to 264 VAC,50/60 Hz;with taps for 220/230/240 VAC
100 W Amplifier Power 120 VAC Models;4 A maximum @ 102 to 132 VAC,60 Hz
Supplies 220-240 VAC Models;2 A maximum @ 204 to 264 VAC,50/60 Hz;with taps for 220/230/240 VAC
Amplifier Ratings
Built-in Tones 500 Hz horn tone operated at temporal pattern,provided when amplifiers are separated from
audio controller
Input Voltage 19 to 35 VDC from adjacent power supply
Flex-35 Amplifiers: 425 mA with power stage supervised
4100-1361 Supervisory Current $5 mA in low power mode
4100-1362 Use this value for power
4100-1363 5.5 A with continuous horn tone
4100-1364 Alarm Current supply loading
@ full output power Use this value for battery
1.64 A average,with temporal pattern horn
backup reference
Input Voltage 19 to 35 VDC from adjacent power supply
Flex-50 Amplifiers: 425 mA with power stage supervised
4100-1312 Supervisory Current $5 mA in low power mode
4100-1313 Use this value for power
4100-1326 Alarm Current 5.55 A with continuous horn tone supply loading
4100-1327
@ full output power Use this value for battery
2.27 A average,with temporal pattern horn
backup reference
100 W Am lifiers and Backu Am lifiers: 400 mA(analog);220 mA(digital)with power stage supervised
P P P Supervisory Current
4100-1314, 4100-1316, 4100-1318, 85 mA in low power mode
4100-1320,4100-1322, 4100-1324; 9.6 A with continuous horn tone
4100-1328,4100-1330,4100-1332, Alarm Current
4100-1334,4100-1336,4100-1338 @ full output power 3.8 A average,with temporal pattern horn Use this value for battery
backup reference
Total Amplifier Power per Cabinet 300 W maximum
Audio Controller Ratings
4100-9620,4100-1210 Analog=225 mA supervisory Add for local speaker in alarm: 75 mA min. volume;
Current 190 mA half volume;333 mA full volume;
Requirements 4100-9621,4100-1311 Digital-85 mA supervisory Add microphone current separately; Supv.=2.4 mA;
- Active=30 mA
Analog Riser Distance Up to 10,000 ft(3048m)total with 18 AWG(0.82 mm2)shielded twisted pair(STP)
Up to 2500 ft(762 m)from 4100-1311 Digital Controller to 4100-0622 Digital Audio Riser or
Digital Riser Distance; 18 AWG 4100-1341 MCC Digital Riser Interface;up to 2500 ft(762 m)between 4100-0622 Digital
unshielded,twisted pair(UTP)required, Audio Riser Modules or 4100-1341 MCC Digital Riser Intertaces(signal is reformatted and
except as noted(refer to Installation repeated);wire runs over 100 ft(30 m)require UTP wire
Instructions 574-844)`
*NOTE:Wire runs of 100 ft(30 m)or less require shielded twisted pair wire(STP)
Firefighter Telephone Distance Ratings
Distance 7500 ft(2286 m)distance to farthest phone, 18 AWG shielded twisted pair(STP)
Battery Charger, System and Remote Power Supply(sealed lead-acid batteries)
Battery capacity range UL listed for battery charging of 6.2 Ah up to 110 Ah(110 Ah batteries require a remote battery
cabinet); ULC listed for charging up to 50 Ah batteries
Charger characteristics and performance Temperature compensated,dual rate, recharges depleted batteries within 48 hours per UL
Standard 864,to 70/o capacity in 12 hours per ULC Standard S527
Environmental
Operating Temperature Range 32°to 120°F(0°to 49°C)
Operating Humidity Range Up to 93% RH, non-condensing @ 90°F(32°C)maximum
� • • • � 1 1 �
Subject Data Sheet Subject Data Sheet Subject Data Sheet
Basic Panel Modules S4100-0031 Network Display Unit(NDU) S4100-0036 InfoAlarmT"^ Comm.Center S4100-0045
LED/Switch Modules S4100-0032 Enclosures S4100-0037 Remote Battery Charger S4081-0002
MINIPLEX Transponders S4100-0035 Remote Annunciators S4100-0038 Remote Firefighter Phones S2084-0001
Tyco is a registered trademarlr ofTyco Irzter�national Services G�nbH and l,s used under Gcense.Sinzplex,the Simpdes logo, WAI,KTES7;MLN/Pl,F,X,and/njoAlarm are trademarks
of Tyco In[ernational L[d.and its a�filintes arid are used under license.
�m S i m p I Ex Tyco Safety Products Westminster• Westminster, MA•01441-0001• USA S4100-0034-11
www.tycosafetyproducts-usa-wm.com
�O 2011 Tyro Safery Pr�oducts Wertmins[er.All rights rese�ved.All spectfications and other info�makon shown were current as ofdocument revi.sion date ancf are subject[o change withou[nofice.
��SimplEx 4100m Fire Control Panels
UL, ULC, CSFMlisted; FMApproved; Panel Mounted LED/Switch and LED Modules,
MEA (NYC) Acceptance* LED/Switch Controllers, and Panel Mounted Printer
�
Panel mounted annunciation modules for use with
4100U/4100ES Fire Alarm Control Panels, Remote i}=u� "'"�
Annunciators, and Network Display Units (NDU): �
• Modules mount on front of panel bay providing
convenient access and high visibility p ,� `� '" �
• Panel monitors switches for user input and controls �� ,_ i:''t;
LED indicators to annunciate function status �ii�iiiiiii�iuii�ii�
• Compact 64 LED/64 switch controller modules mount �iimii�iiAii�iiQiimiioiu�iMiiunQiini
on back of LED/switch modules ' `- -- --- ' �'
LED/Switch Modules: �M��
• Raised momentary switches provide tactile feedback �� �
• Alternate action operation provides on/off functions e �
• High intensity LEDs provide clear status annunciation """ �
• Slide-in labels provide custom on-site labeling(label �
ki i r r r 1
�
t s o de ed se a ate
P Y) �
8 LED, 8 Switch Modules: r$
• One status LED per switch �
• Available as all red LEDs or all yellow LEDs
16 LED, 8 Switch Modules: 4100ES 2-Bay Fire Alarm Control Panel
• Two status LEDs per switch with Sample of Available LED/Switch Modules
• Available with two LEDs per switch as:red/yellow,
yellow/yellow,red/green,or green/yellow • '�
16 LED, 16 Switch Modules: 24 Point I/O Module for external connections:
• One status LED per switch in 2"(51 mm)module . Each point is selectable as either a switch input
• Available as all red LEDs,or 8 red and 8 yellow (momentary or maintained)or lamp/relay driver output
• Two configurarions are available, one with pluggable . Multiple switch monitoring modes are available
LEDs,refer to illustrations on page 2 and product panel mounted printer (see pages 6 and 7 for details):
selection details on page 4 • Records system events and provides 20 visible lines
24 LED, 24 Switch Modules: Listed to:
• Double slot module with one red status LED per • UL Std. 864,Fire Detection and Control(UOJZ),and
switch
Sinoke Control Service(UUKL)
HOA(Hand-Off-Auto) Switch Modules: . UL Std. 2017,Process Management Equipment
• Eight controls in a double slot module,each control �QV��
has three switches for status selection and one LED • UL Std. 1076,Proprietary Alarm Units-Burglar(APOU)
per switch position . UL Std. 1730, Smoke Detector Monitar(UULH)
• Switch selection is On/Hand,Off, and Auto . ULC Std. 5527-99
Available with three HOA Module LED Options:
• On/Hand(green LED),Off(red LED)and Auto � _ � �
(green LED)
• On/Hand(green LED),Off(red LED)and Auto Annunciation Options.4100U/4100ES fire alarmpanels
(white LED)to comply with International Building support a variety of switch input and LED status indicators
Code(IBC)requiren�ents to complement the information and controls available at tbe
• On/Hand(green LED),Off(yellow LED)and Auto operator interface. These modules provide a convenient
(green LED)for applications requiring no red LEDs interface efficiently packaged onto the front panel space of
• Availabl�with or without switch buttons labels the cabinet bay. Addirionally,the panel mounted printer can
(On,Off,Auto) conveniEntly record system status without rEquiring a
LED Modules with 8 or 16 pluggable LEDs: separately located printer.
• g LED MOdUl�haS T'0d LEDS, 16 LED mOdUle haS ' Refer to additional listing tletails on page 4.This product has been approved by the
g Ced Wlth g ye��OW California State Fire Marshal(CSFM)pursuant to Section 13144.1 of the California Health
and Safety Code.See CSFM Listing 7165-0026:251 for allowable values andlor
• ROCl,y0110W,gl'�eri,OT'b1Ue I.EDS al'G 1V111abIC lri conditions concerning material presented in this document.It is subject to re-examination,
packages of eight(8)to change color on-site per revision,and possible cancellation.Adtlitional listings may be applicable;contact your
appllC3tlOri TeC1U1T'CYY1Grit�OYCIETECI S�plYately� local Simplex°product supplier for the latest status.Listings and approvals under Simplex
Time Recorder Co.are the property of Tyco Safety Products Westminster
S4100-0032-10
� - . . • -•
Easy Interface. Switches are alternate action ON/OFF The 24 Point 1/O Module is selectable for input switch
(depending on programming selecrion)using a tactile feel, type and supervision type. Outputs are selectable for
raised rubber button. High efficiency LEDs provide clear steady on or pulsing to drive remotely connected relays,
status annunciarion readily visible through the glass door. incandescent lamps,or LEDs.
Selectable Functions. Switch functions,LED status
indications,and printer output is selected when the
control panel CPU is customized for site specific
requirements. Slide-in labels are locally printed to
indicate the exact function of the LEDs and switches.
� . . �
LED/Switch Modules LED Modules
- - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - -- - - - - - - - , - - - - - - - - - - - - - - - -
� Label insert � � �
i � � Primary i i � i
i function label � i �
i �
i i .
Additional
_ _ _ _ __ ; function labels
ConVOI Fan Fa
CUSfOfT1 __ _ _ _ _ �n Off
label area ' Designates area
Switches i�, East � I-for each column of
\ Wing � switches and LEDs
� LEDs West �
�� Wing
South �
' Wing
Visible area
8-1/4"H, -, rvortn \Switch
2^N/ - - Wing
(210 mm
x 51 mm) �� Annex
LEDs
1 �� Garage �
. sasement �
Boiler
Room
8 Switches 76 Switches 8 Switches 16 Switches 8 LEDs:
with 16 LEDs: with 16 LEDs: with 8 LEDs: with 16 LEDs: 4100-1276,R
4100-1282,R/Y 4100-1300,R/Y 4100-1280,R 4100-1278,R-Y (pluggable LEDs)
4100-1283,Y/Y (pluggable LEDs) 4100-1281,Y 4100-1285,R
4100-1284,R/G 16 LEDs:
4100-1296,G/Y 4100-1277,R/Y
LED Color Legend:Red,Yellow,Green; (pluggable LEDs)
R/Y=Red on top,Yellow on bottom;
R-Y=Red on left,Yellow on right
2 S4100-0032-10
• � • � � � • • � -
24 Stiuitches,24 LEDS HOA Modules,S Controls
(3 switches each],24 LEDs
—� �Label insert� �
One switch per Primary function labels
c«,tra,oNoff
Custam �
label area
i LED(On)
i
� LED(df�
i
' LED(Auto)
i
i
i
� � LED Color Legend:
i Red LEDs
� Green,Red,White,Yellaw;
i —
GIRIG=Grcen an,Red off,
Green auto
Visible area GIRIW=Green on,Red off,
8-114"H,2"W White auto
{21 Q mm x 51 mm) GlYIG=Green an,Yellow
off,Green auto
i-
One switch i
per iunctian i
i
4100_1287 HOA Modules,GlRIG LEDs:
470a1286,wiih labeled switches as shanrn
410Q1295,with unlabeled switches(not shawn)
HOA Modules for IBC Applications,GlRIW LEDs:
410Q1275,with labeled switches as shawn
470a1299,wiih unlabeled switches(not shown)
HOA Modules,GlYIG LEDs:
470a1302,wiih labeled switches as shanrn
470a1307,wiih unlabeled switches(not shown)
3 S4100-0032-10
� • • • • � •. • -• • • • •
LED/Switch Modules, General Purpose (LED/switch controller and label kit is ordered separately)
Model LEDs per Switch LED Color(s) Custom Label Area LED Quantity Switch Quantity
4100-1280 One Red
Per module and per switch 8 8
4100-1281 One Yellow
4100-1282 Two Red on top,Yellow on bottom
4100-1283 Two Yellow on top and bottom
Per module and per switch 16 8
4100-1284 Two Red on top, Green on bottom
4100-1296 Two Green on top,Yellow on bottom
4100-1285 One Red One per column of 8
LED/switch pairs(see
4100-1278 One 8 Red on left, 8 Yellow on right illustration on page 2) 16 16
4100-1300' One W�th pluggable LEDs;shipped Per module and per
Red on top,Yellow on bottom LED/switch pair
4100-1287 One Red Per module and per switch 24 24
''UL, ULC,and CSFM listed only.
LED Only Modules and LED Kits (LED/switch controller and label kit is ordered separately)
Model Description
4100-1276 Eight(8)LED Module with Red LEDs;custom label area per
module and per LED
LEDs are pluggable;select LED kits as required to
Sixteen (16)LED Module; Red LED on top and Yellow LED change LED color
4100-1277 on bottom at each position; custom label area per module
and per LED pair
4100-9843 Yellow
4100-9844 Green Kits of 8 LEDs;order as required for modules with pluggable LEDs to change LED color on-site per
application requirement;compatible with LED Modules 4100-1276,4100-1277, and 4100-1300
4100-9845 Red (glue is typically used for Ancillary Device status indication per ULC S527)
4100-9855 Blue
LED/Switch Modules, HOA(Hand-Off-Auto)with Green/Red/Green LEDs
(LED/switch controller and label kit is ordered separately)
Model Operation Switch Function(Location) LED Description
Eight function HOA(On,Off,Auto)Control Module with On(top) Green LED
4100-1286 labeled switches;custom label area per module and per Off(middle) Red LED
LED/switch set Auto(bottom) Green LED
4100-1295 Eight function HOA(On,Off,Auto)Control Module, same as 4100-1286 except switches are unlabeled
LED/Switch Modules, HOA(Hand-Off-Auto)with Green/Red/White LEDs for IBC Applications
(LED/switch controller and label kit is ordered separately)
Model Operation Switch Function(Location) LED Description
Eight function HOA(On,Off,Auto)Control Module with On(top) Green LED
4100-1275 �abeled switches; LED colors meet International Building Off(middle) Red LED
Code(IBC)requirements; custom label area per module
and per LED/switch set Auto(bottom) White LED
4100-1299 Eight function HOA(On,Off,Auto)Control Module, same as 4100-1275 except switches are unlabeled
LED/Switch Modules, HOA(Hand-Off-Auto)with Green/Yellow/Green LEDs
(LED/switch controller and label kit is ordered separately)
Model Operation Switch Function(Location) LED Description
Eight function HOA(On,Off,Auto)Control Module with On(top) Green LED
4100-1302`� labeled switches;for applications requiring no red LEDs; Off(middle) Yellow LED
custom label area per module and per LED/switch set Auto(bottom) Green LED
4100-1301** Eight function HOA(On, Off,Auto)Control Module, same as 4100-1302 except switches are unlabeled
`�UL, ULC,and CSFM listed only.
Continued on next page
4 S4100-0032-10
� • • • • � • 'I
LED/Switch Controller Modules and Accessories
Model Description
64 LED/64 Switch Controller Module with mounting plate;controls up to 64 LEDs
4100-1288 and interfaces to up to 64 switches; mounts behind the LED/switch modules and NOTE: LED/switch controllers
has provisions for one 4100-1289 Controller Module and their connected modules
64 LED/64 Switch Controller Module without mounting plate; mounts on extra must be in the same bay.
4100-1289 space of 4100-1288;controls an additional 64 LEDs and 64 switches
4100-0636 Harness Kit, Power and Communications One of each is required per 4100-1288 that is
located in the same bay as two Flex-35/50
4100-0641 Harness Kit,26 Position Flex Cable, 14-1/2"(368 mm)long amplifiers and an SPS
4100-1290 24 Point I/O Module for external connections,select each point as either input or output;
2"(51 mm)wide, 1 Slot
4100-1294 LED/Switch Module Slide-in Labels, required when LED/switch or LED only modules are present;
order one per cabinet
4100-1279 Single blank 2"display cover;order as required (8 fill a bay front);two maximum in a row between LED/switch
modules
Panel Mounted Printer(refer to pages 6 and 7 for printer details)
Model Description
4100-1293 Panel Mount Thermal Printhead Printer,supplied with one roll of paper
4190-9803 Replacement Paper for 4100-1293 Printer,one roll
� • • • • • • - •
(For additional LED/Switch Module informarion,refer to Installation Instructions 574-843)
64 LED/64 Switch Controller Modules (4100-1288 and 4100-1289)
Input Voltage 19 to 33 VDC,from control panel
Current, No LEDs On 20 mA @ 24 VDC
Current,All 64 LEDs On 210 mA @ 24 VDC(approx. 3 mA/LED)
Mounting Reference Bracket of 4100-1288 attaches to the back of the LED/switch modules
Controllers per Bay Maximum of two per bay;for control of LED/switch modules within that bay only
Bay Location Reference Slots 1 &2 or Slots 3&4; mounts onto the back of the LED/switch modules
Clearance Behind Controller Module Space accepts low profile 4100U/4100ES modules only
24 Point I/O Module (4100-1290)
Module Current Supervisory=34 mA;Alarm=75 mA(add output currents separately)
Switch Input Details Momentary or maintained,2 or 3 position; max.distance is 2500 ft(762 m)or 65 f2
Output Current 150 mA @ 24 VDC per point; inrush current is limited for use with incandescent bulbs
Output Details Diode suppress relay loads at the coil; max. distance is 600 ft (183 m)or 2 f2
General Specifications
Operating Temperature Range 32°to 120°F(0°to 49°C)
Operating Humidity Range Up to 93% RH, non-condensing @ 90° F(32°C)maximum
� � • • �
Subject Data Sheet Subject Data Sheet
4100ES Basic Panel Modules and Accessories S4100-0031 Network Display Unit(NDU) S4100-0036
4100ES Audio/Phone Modules S4100-0034 Enclosure Reference S4100-0037
MINIPLEX°Transponders S4100-0035 Remote Annunciators S4100-0038
5 S4100-0032-10
• • - 11 ' • � -
- Access latches
oa l
I�I
- -
� �� �
�iiiuii�wiiiium°10ii�iwiuuuiii Hinged printer assembly:
5-1/2"W x 7-1/2"H
— ---- (140 mm x 191 mm)
- EXpOSeC�p2p@f 2f2a: FIREALARMFIRSTFLOORELECTRICAL
CLOSET
2-3�8��W X 4��H LOCATION EL�1-B 72:37:15 09 FEB 10
(60 mm x 102 mm) LOWBATTERYTROUBLETRANSPONDERI7
12:4726 09 FEB 10
SYSTEM RESETIN PROGRESS
14:1223 09 FEB 10
SYSTEM RESET COMPLETE
14:13�02 09 FEB 10
LOGIN
n zs zz os Fee io Multi-color status LED:
PnsswoROnccePreo Green=Power On
nzazs os Fee io Green/Yellow=Paper Low
sENSORia-soisne�eo Yellow=Pape�Out
19:15:09 09 FEB 10
SENSOR 13-9 ENABLED
19:19:03 09 FEB 10
LOGOU7
19:33:02 09 FEB 10
LOGIN
� Control switch provides
ON,OFF,Feed,and
Manual Test Mode
���������
6 S4100-0032-10
. .
(For addirional printer information,refer to Installation Instructions 579-249)
Electrical &Communications
Input Voltage 19 to 33 VDC,from control panel
Standby 125 mA @ 24 VDC
Current
Printing 800 mA @ 24 VDC
Communications RS-232,9600 baud,from control panel RS-232 module
Print Characteristics
Print Format Fixed thermal printhead producing black characters
Characters 11 x 28 dot matrix;alarm information printed in bold
Paper Format 40 columns;6 lines per inch;20 lines visible; paper is wound onto top take-up reel,
paper can be manually unwound from take-up reel and rewound using Feed switch
Paper Speed 1.33 in/sec maximum
Print Speed 312 cps
Sound Output 55 dB maximum,with cabinet door open
Paper(one roll included)
Type and Size Thermal; 2.35"wide, 160 ft long(60 mm x 49 m)
Replacement Paper 4190-9803, 1 roll
Mounting Specifications
Bay Location Reference Requires 3 expansion bay slots,can be located as required
Clearance Behind Printer Space accepts low profile 4100U/4100ES modules only
Environmental Specifications
Operating Temperature Range 32°to 120°F(0°to 49°C)
Operating Humidity Range Up to 93% RH, non-condensing @ 90° F(32°C)maximum
7 S4100-0032-10
Tyco is a registered trademark of�Tyco Inkernational Services GmbH and is used under license.Simplex,tlae Simplex logo,and MIN/PLEX are trademarks of Tyco Internadonal
Lld.and its afftliates and are used under license.
�m S i m p I Ex Tyco Safety Products Westminster• Westminster, MA•01441-0001• USA S4100-0032-10
www.tycosafetyproducts-usa-wm.com
�O 2011 Tyco Safery Products Westminster.All rights rese�ved.All specificatio�is and other�informa6ori shown were current as of document revision date and are suhject to cha�nge wi[hou[no[zce.
�oSi m plEx �`.�H ID�yq� 4100ES Fire Control Panels
UL, ULC, CSFM Listed; io�o2 Addressable Fire Detection and Control
FMApproved * r�F'cp'�` MINIPLEX Transponders
� MINIPLEX
4100ES Series MINIPLEX transponders allow transponder
remotely located initiating and notification IDNet addressable Addressable strobes
funCtiOnS: devices on IDNAC SLC
• Transponder operation is available as standard or with
local mode operation � ��� ��� (� (�
• Communications with the host fire alarm control panel
use the Remote Unit Interface(RUI/RUI+)format � �
Initiating functions include: : �_
• Addressable device support including TrueAlarm Audio NAC : ��� �oca�mode
analog sensor compatibility . contro�ler
• Conventional initiating device circuit(IDC)support ;
Notification functions include: �
----- - ,
• Addressable strobe and horn norification using �
enhanced power delivery IDNAC SLCs ���:���:
• Emergency voice/alarm communications �
• Conventional DC notification appliance circuits(NACs) i
Local mode operation provides: ��,
�
• Defat�lt local initiating and notification operation in the � °
event of a communications loss with the host control panel
• Enabling of an optional Local Mode Controller with a
local alarm sounder,LED status indicators,and ��„��i�i�i����
keyswitch enabled control switches I�imio�enmi�iunwmm�i�oiM
• Support for IDNet addressable devices,addressable and
conventional notification appliances,and default output -- ---
tones from local amplifiers 4100ES Fire Alarm Control Panel
Optional modules include: w�tn vo�ce cor,troi
• Digital or Analog audio riser modules for connection to
system audio signals Typical 4100ES MINIPLEX System One-Line Drawing
• Digital or analog input audio amplifiers with integral
on-board NACs . • .
• Power supplies with or without battery chargers 4100ES MINIPLEX transponders connect to a host
• City Connect modules and RS-232 ports far printers or 4100ES Fire Alarm Control Panel using Simplex°remote
maintenance terminals unit interface(RUI)communications.At the transponder,
• Alarm relays,auxiliary relays,additional IDC modules, RUI communications are received by the transponder
and NAC expansion modules interface module and translated into the same internal
Cabinets are equipped with solid doors (beige or communications format that is used in the host control
red)and in one,two, or three bay sizes panel.
Listed to: Remotely located modules.With RUI
• UL Std. 864,Fire Detection and Control (UOJZ),and communicarions,the transponder can remotely provide
Smoke Control Service(UUKL) the same initiating and notificarion functions that occur at
• UL Std.2017,Process Management Equipment(QVAX) the host control panel without requiring multiple long
• UL Std. 1076,Proprietary Alarm Units-Burglar(APOU) distance wiring runs. Connections to the host panel are
• UL Std. 1730, Smolce Detector Monitar(UULH) low current communicarions and audio wiring with
distances up to 2500 ft(762 m).
• ULC Std. S527-99
Additional Reference.Refer to document S4100-0100
� seepa�esaand5fa-proa�,cttr,at�siis�eaasu�oru�c.7r,isp-oduar,as�eer,�prwedby and the other documents listed on page 3 for additional
tr,ec,��t«„�ast�teF��,�i���,��Mtos�t�«,�a�aa.�o�tr,ec,��tor„�a�tn informationconcerningtheextensiveinitiatingand
a�,dsare�'coae.seec��s�",���s�°°2�:02��faa�i°"'a�e`�uesa�t'a�c�a't'°"s notificarion features of the 4100ES fire alarm control
ca�cerning rreteri�p'esented in this doa iment.PrJditional listings rrey be applic�ble;oaitact
your local Sirrplex produd supplier for the latest status.Listirgs and approvals undex Sirrplex panels.
Tirr�Reoorder Co.are the property of Tyco Fre Protection Products.
S4100-0103-1 5/2013
• • � - • • • • • - • • � • - • • '•
Transponder model 4100-9600 includes a bay Notification Operation.Fire alarm conditions reported
assembly,a power distribution interface module(PDI),a against a fire alarm point rype within a transponder in
Basic Transponder Interface Module,and an interconnect local mode will cause all notification appliance circuits in
barness. Communications with the host fire alarm control that transponder to:
panel are via a Remote Unit Interface(RUI)connection . Sound a general alarm temporal pattern horn tone
that allows for up to 2500 ft(762 m)distance. RUI can . Activate visible notification appliance circuits
communicate with up to a total of 31 remote devices and
can be either Style 4 or Style 7 communications. Local Mode Module Support.Local mode operation
provides support for the following 4100ES modules:
Transponder model 4100-9601 substitutes a Local
Mode Transponder Module for the Basic Transponder • Enhanced Power Supplies(EPS+/EPS)including
Module. on-board IDNAC SLCs
• IDNet 1+addressable device circuits,including those
Optional Expansion Bays each include a PDI and on-board the EPS+,IDNet 1+expansion modules,and
accept a variety of optional modules(refer to list starting the Quad IDNet Isolator Module
on page 4). . Expansion Power Supplies(XPS)including on-board
The Battery Compal'tment(bottom)accepts two NACs and expansion signal modules,operated at a
batteries,up to 50 Ah,that can be mounted within the temporal pattern
cabinet. Battery mounting does not interfere with . 4100ES amplifiers will provide their on-board horn tones
available module space. A power supply with battery (500 Hz)at a temporal pattern through their on-board
charger is required for each battery set. amplifier NACs
• � • ' - • • Firefighter Telephone control modules in local mode
• Modules are power-limited(except as noted,such as Local Mode Operation Module Exclusion. Modules
relay modules) not listed above but that are listed as compatible with
MINIPLEX transponders per this document, do not
• Enclosure are available for one,two,or three bay sizes interfere with local mode operation but are not supported
or for cabinet rack mounting during local mode operation.
• Boxes and solid doors are available in beige or red
(ordered separately) � ' � � � � �
• Up to eight close-nippled cabinets can be connected at OperatiOn.During local mode operation,an optional
one transponder location(close-nippled is mounted Local Mode Controller will indicate status(see illustration
within 20 ft(6 m)and with interconnecting wiring below)and can be enabled using a keyswitch to perform
enclosed in conduit) local alarm silence or reset.If alarms occurring during local
Refer to document 54100-0037 for enclosure details mode are reset using a Local Mode Controller,upon
� restoration of communications,those alarms will not be
. . . . - . . • . - . . sent to the master controller.If alarms are sti11 present
upon restorarion of communications,then the alarm
Default Stand-Alone Operation. In the event of a condition will be reported and host fire alarm control panel
communications loss with the host fire alarm control programmed alarm funcrions will occur.When
panel,mode14100-9601 MINIPLEX Local Mode communications are re-established,the local mode
Transponders provide fire alarm response default transponder restores automatically.
operation for its connected devices and appliances per the
following. Mounting.Local Mode Controllers are mounted on
three-gang plates,are available in beige or red,and for
Input Operation.During local mode operation, either flush or semi-flush mounting. (See page 7 for
TrueAlarm initiating devices connected to the transponder details).
will cause an alarm at their least sensitive alarm threshold. �
• Photoelectric sensors will alarm at 3.7%/ft smoke d � �
obsCUration Fire Alarm Local Mode Controller
• Ionization sensors will alarm at 1.3%/ft obscuration ^'a.m
• Heat sensors will alarm at a fixed temperature of 135°F • •• s^e�e,
(57°C) �o�a,
� � Mode
• TrueAlarm device LEDs will be activated to indicate a """e
�,.,\�.' POner
device in alarm
f3 Simplex See Operating Instruction 579-343
�� �> ��
Local Mode Controller Module
2 S4100-0103-1 5/2013
. . . � . .
�
.. . . . . . . . . . ..
� � . .
Seventh floor � o : :
: Legend:
� � MINIPLEX transponder
� Addressable strobes
� : on IDNAC SLC
Slxth flool' , ��;r
� IT� •
� Speaker NAC
�
. : �,:E
� � • • � TrueAlarm sensors
and IDNeUMAPNET II
Fifth floor � : : � addressable circuits
. . Audio riser wiring,
: : twisted pair
� � . . RUI communications
o �..: . .
� pairng,twisted,shielded
Fourth floor • •
� I�� MINIPLEX transponder
Third floor � o � — . —
: �� f�
. �I
-- � � :
Second floor � o �
: - a
• �
. . . . . . . . . � :e���� --
Illllqlllllllllllplllllllllllltllltllllllllllllllllllllllllllllllllll
ItlllqlltllllullqlllulllllllqUqllnlllllllllllllllllllllllllllll
4100ES Fire Alarm Control Panel
with Voice Control
First floor
� • • • 1 1 �
Subject Data Sheet Subject Data Sheet
MINIPLEX Transponders for conventional S4100-0035 Basic Panel Modules and Accessories S4100-0100
(non-addressable)notification applications Network Display Unit(NDU) S4100-0102
Enclosures S4100-0037 Remote Annunciators S4100-0038
LED/Switch Modules S4100-0032 Remote Battery Charger S4081-0002
4100ES Audio/Phone Modules S4100-0034 Addressable Device Compatibility S4090-0011
IDNet+Module with Quad Isolator S4100-0046
3 S4100-0103-1 5/2013
. . . - . . .
Transponder Type
Model Description Supv. Alarm
4100-9600 Basic Transponder, includes bay equipment with power distribution interface,and 4100-0620 Basic 87 mA 87 mA
Transponder Interface Module mounted in Block A
4100-9601 Local Mode Transponder,includes bay equipment with power distribution interface,and normal 87 mA 87 mA
4100-0625 Local Mode Transponder Interface Module mounted in Block A in local mode 112 mA 112 mA
Local Mode Controller Selection
Model Description Supv. Alarm
4601-9108 Flush mount Red with white Local Mode Controller,3-gang plate mounted; normal 12 mA 12 mA
4601-9109 Surface mount lettering flush mount requires a 1 '/2'(38 mm)deep
4601-9110 Flush mount Beige with black 3-gang box;surface mount controllers include a
4601-9111 Surface mount lettering matching mounting box;see p.7 for details in local mode 20 mA 60 mA
Communication Modules
Model Description Size Supv. Alarm
4100-6031 City Circuit,with disconnect switches N.A. 20 mA 36 mA
4100-6032 Select one per Cit Circuit,without disconnect switches N.A. 20 mA 36 mA
EPS+or EPS y
4100-6033 Alarm Relay,3 Form C relays,2 A@ 32 VDC N.A. 15 mA 37 mA
4100-6038 Dual RS-232 Interface 1 Slot 132 mA 132 mA
4100-6045 Decoder Module 3 Slots 85 mA 163 mA
4100-6048 VESDA Aspiration System Interface 1 Slot 132 mA 132 mA
4100-9816 Master Clock Interface Module with one standard RS-232 port(see S4100-0033) 1 Slot 132 mA 132 mA
Enhanced and Expansion Power Supplies and Accessories (see specification details on page 6)
Model Voltage/Listing Description Size Supv. Alarm
4100-5311 120 VAC UL& Enhanced Power Supply(EPS+);9 A Enhanced Power 217 mA 480 mA
ULC Supply/battery charger with 250 point IDNet 1+interface, 4 Blocks
3 Class B IDNAC SLCs,and RUI+isolated output Right with 200 IDNet
4100-5313 220-240 VAC UL communications interface; 120 VAC model has selectable low Side devices and 20
battery cutout device LEDs in alarm
4100-5325 120 VAC UL& Enhanced Power Supply(EPS);9 A Enhanced Power 4 Blocks
ULC Supply/battery charger with 3 Class B IDNAC SLCs,and Right 125 mA 220 mA
RUI+isolated output communications interface; 120 VAC
4100-5327 220-240 VAC UL model has selectable low battery cutout Side
Dual Class A IDNAC Isolator(DCAI),converts a single Class B IDNAC SLC input to two
Class A or two Class B SLC outputs; provides short circuit isolation between each Class A
4100-6103 or B output circuit;connect up to two DCAI modules per IDNAC SLC input up to a 1 Block 6.5 mA 6.5 mA
maximum of 6 DCAI modules per EPS;each isolated output SLC used requires one IDNAC
address;the total current remains controlled by the Class B input source SLC at 3 A
maximum
Model Voltage/Listing Description Size Supv. Alarm
4100-5101 120 VAC UL Expansion Power Supply(XPS);9 A output,3 built-in
Class A/B NACs,rated 3 A for Special Application
4100-5103 120 VAC,Canadian ULC appliances(2 A for Regulated DC); NACs can be selected 2 Blocks 50 mA 50 mA
as auxiliary power outputs,derated to 2 A for continuous
4100-5102 220-240 VAC UL duty,total per XPS is 5 A;4100-5103 has low battery cutout
4100-5115 NAC Expansion Module,3 NACs,Class A/B,mounts on XPS only N.A. 25 mA 25 mA
4100-5152 12 VDC Power Option,2 A maximum 1 Block 1.5 A maximum
4100-0636 Box Interconnection Harness Kit(non-audio);order one for each close-nippled cabinet
Miscellaneous Options and Accessories
Model Description
4100-1290 24 Point I/O Module for external connections,select each point as either a switch input(momentary or maintained)or an
output(for lamp/LED/relay);requires 1 Slot(refer to data sheet S4100-0032 for additional information)
4100-0632 Terminal Block Utility Module with 2, 16 position terminal blocks on 4"x 5"single block,for of up to 12 AWG wire(3.31 mm2)
4100-0633 Door Tamper Switch,connects into Transponder Intertace Module,one per cabinet assembly if required
4100-0634 120 VAC
4100-0635 220/230/240 VAC Power Distribution Module(PDM)select per system voltage;one required per box
4100-9837 Green LED Power-on Indicator Kit, required for ULC listing of MINIPLEX transponder;mounts on solid door knockout
Series resistor for WSO, IDCs(N.O.water flow and tamper on same circuit,wires after water flow and before tamper)470 f2,
2081-9031 1 W,encapsulated,two 18 AWG leads(0.82 mm2),2'/z"L x 1 '/8'W x 1"H(64 mm x 35 mm x 25 mm)
*Standard power supply NACs can provide synchronized strobe or SmartSync,two-wire operation. Continued on next page
4 S4100-0103-1 5/2013
. . . - . . . � -.
Audio Riser Modules
Model Description Size Supv. Alarm
4100-0621 Dual Channel Analog Audio Riser Module;accepts one or two separate audio signals from 1 Block 0 mA 15 mA
host control panel;mounts in Block B,is controlled by Transponder Interface Module
4100-0622 3-8 Channel Digital Audio Riser Module;similar to analog module,except receives and 1 Block 70 mA 70 mA
decodes a digital input signal with up to eight audio channels;with Non-Alarm Audio input
Analog Emergency Voice/Alarm Communications Equipment, Constant Supervision Compatible*
Model Description Details
4100-1361 25 VRMS output Flex-35,35 W Amplifier,constant Includes three on-board NAC rating=1.4 A 35 W,or 100
4100-1362 70.07 VRMS output supervision compatible Class B audio NACs; NAC rating=0.5 A speakers
4100-1312 25 VRMS output Flex-50,50 W Amplifier,constant power is supplied from NAC rating=2 A 50 W,or 100
4100-1313 70.7 VRMS output supervision compatible an EPS+, EPS,or XPS NAC rating-0.707 A speakers
100 W Analog Amplifiers with Power Supply, Constant Supervision Compatible
Model/Output Voltage
25 VRMS 70.7 VRMS Power Supply Input/Listing Description Details
4100-1314 4100-1315 120 VAC,60 Hz UL Includes six,Class B audio NACs;
Primary NAC rating=50 W or 100 speakers ULC
4100-1316 4100-1317 120 VAC,60 Hz ULC 100 W
Am lifier maximum;2 A@ 25 VRMS; models
4100-1318 4100-1319 220/230/240 VAC,50/60 Hz UL p 1.4 A 70.7 VRMS have low
4100-1320 4100-1321 120 VAC,60 Hz UL battery
Backup Uses the six Class B NACs of primary dropout
4100-1322 4100-1323 120 VAC,60 Hz ULC 100 W amplifier circuit
4100-1324 4100-1325 220/230/240 VAC,50/60 Hz UL Amplifier
Digital Emergency Voice/Alarm Communications Equipment*
Model Description Details
4100-1363 25 VRMS output Flex-35,35 W Amplifier,constant Includes three on-board NAC rating=1.4 A 35 W,or 100
4100-1364 70.07 VRMS output supervision compatible Class B audio NACs; NAC rating=0.5 A speakers
4100-1326 25 VRMS output Flex-50,50 W Amplifier,constant Power is supplied from NAC rating=2 A 50 W,or 100
4100-1327 70.7 VRMS output supervision compatible an EPS+, EPS,or XPS NAC rating=0.707 A speakers
100 W Digital Amplifiers with Power Supply, Constant Supervision Compatible
Model/Output Voltage
25 VRMS 70.7 VRMS Power Supply Input/Listing Description Details
4100-1328 4100-1329 120 VAC,60 Hz UL Includes six,Class B audio NACs;
Primary NAC rating=50 W or 100 speakers ULC
4100-1330 4100-1331 120 VAC,60 Hz ULC 100 W
Am lifier maximum;2 A@ 25 VRMS; models
4100-1332 4100-1333 220/230/240 VAC,50/60 Hz UL p 1.4 A 70.7 VRMS have low
4100-1334 4100-1335 120 VAC,60 Hz UL battery
Backup Uses the six Class B NACs of primary dropout
4100-1336 4100-1337 120 VAC,60 Hz ULC 100 W
Am lifier amplifier circuit
4100-1338 4100-1339 220/230/240 VAC,50/60 Hz UL P
Options for use with either Analog or Digital Amplifiers
Model Description Details and Mounting Reference
4100-1245 Flex-35/50 Expansion NAC Module;adds three Mounts on Flex-35/50 assembly;NAC ratings= 1.5 A,35/50 W,
Class B audio NACs Choose or 100 speakers maximum; Supv=8 mA,Alarm=60 mA
one per
4100-1246 Flex-35/50 Class A Adapter Module;converts amplifier Mounts on Flex-35/50 assembly;NAC ratings=2 A,50 W,or
three on-board NACS to Class A operation 100 speakers maximum; Supv=10 mA,Alarm=30 mA
4100-1248 100 W Amplifier Expansion NAC Module; NAC Provides six additional Class B audio NACs,mounts on 100 W
ratings=1.5 A,50 W,or 100 speakers max. Choose amplifier assembly; Supv= 17 mA,Alarm=60 mA
one per
4100-1249 100 W Class A Adapter Module; NAC ratings= amplifier Converts six on-board NACs to Class A operation,mounts on
2 A,50 W,or 100 speakers max. 100 W amplifier assembly;Supv= 1 mA,Alarm=60 mA
25 VRMS Output; NAC Constant Supervision Adapter Supv= 10 mA
4100-1259 rating=2 A,50 W,or for three NACs;select per on batteries; Converts three Class B audio NACS to
100 speakers max. amplifier output;not Alarm=35 mA Class A or Class B Constant Supervision
70.7 VRMS Output;NAC compatible with amplifier NAC Supv=38 mA NACs;mounts on Flex-35/50 or 100 W
g= ex ansion modules; amplifier assembly; use two for the six NACs
4100-1260 ratin 0.707 A,50 W, p on 6atteries; on 100 W amplifiers
or 100 speakers max. deactivated when on batteries Alarm=70 mA
Firefighters Telephone Options*
Model Description Size Supv. In Use
4100-1272 Expansion Telephone Control Module with three Class B telephone NACS;required when 1 Block 80 mA 130 mA
telephone circuits are mounted in transponder;
4100-1273 Telephone Class A Adapter Module; mounts on 4100-1272; no additional current required
`Refer to document S4100-0034 for additional audio information. Continued on next page
5 S4100-0103-1 5/2013
. . . - . . . � -.
Audio Expansion Signal Module and Options
Model Description Details and Mounting Reference
Expansion Signal Module;three, 1.5 A Class B NACs for Converts one NAC input to three NAC outputs;selects between two
4100-5116 Audio applications; up to five maximum per amplifier; inputs;for Flex-35/50 amplifiers only,two input NACs are required;
NAC rating= 1.5 A,50 W,or 100 speakers maximum Single Block module mounts in expansion bay;
Supv=20 mA;Alarm=80 mA
4100-1266 Expansion Signal Module NAC Expander; NAC rating= Expands module capacity to six,Class B NACs; These modules
1.5 A,50 W,or 100 speakers max. Supv=0.84 mA;Alarm=60 mA mount on the
4100-1267 Expansion Signal Module Class A Adapter;NAC rating= Converts 3 Class B, NACs to Class A; 4100-5116;
1.5 A,50 W,or 100 speakers maximum Supv=0 mA;Alarm=30 mA select one
Expansion Signal Module Constant Supervision Adapter; NAC rating= 1.4 A,50 W,or 100 speakers max.; max. per
4100-1268 Converts 3 Class B NACs to Constant Supervision Supv=38 mA on batteries(constant supervision 4100-5116 as
Class B or Class A NACs;for 25 or 70.7 VRMS audio deactivated);Alarm=70 mA required
General Audio Options
Model Description
4081-9018 End-of-line resistor harness for 70.7 VRMS NACs; 10 kS2, 1 W
4100-2320 Audio Bay-to-Bay Interconnection Harness Kit;order one for each audio bay addition
4100-0637 Audio Box Interconnection Harness Kit;order one for each close-nippled audio cabinet
Addressable Interface Modules
Model Description Supv. Alarm
With 250 IDNet devices,and 20 device LEDs in alarm 292 mA 510 mA
4100-3108 IDNet 1+Module,250 point capacity with Module without devices 92 mA 115 mA
isolated output, 1 block
Loading per IDNet device(no LEDs on) 0.8 mA 1 mA
Quad IDNet Isolator Module;converts a single connected SLC into four isolated outputs selectable as
4100-3107 Class A or Class B, provides advanced diagnostics for use with retrofit wiring;dual horizontal block 75 mA 115 mA
module;(see data sheet S4100-0046 for additional details)
NOTE:This module is compatible with IDNet Remote Isolators
Relay Modules; Nonpower-Limited
Model Description Resistive Ratings Inductive Ratings Size Supv. Alarm
4100-3202 4 DPDT w/feedback 10 A 250 VAC 10 A 250 VAC 2 Slots 15 mA 175 mA
4100-3204 4 DPDT w/feedback 2 A 30 VDC/VAC '/z A 30 VDC/120 VAC 1 Block 15 mA 60 mA
4100-3206 8 SPDT 3 A 30 VDC/120 VAC 1 '/2 A 30 VDC/120 VAC 1 Block 15 mA 190 mA
Current Calculation Notes:
1. For total supervisory current,add panel module currents to base system value and add all external panel-powered loads.
2. For total alarm current,add panel module currents to base system alarm current and add all panel SLC/NAC loads and all external
loads powered from panel power supplies.
• •
120 VAC Models 4.6 A maximum @ 102 to 132 VAC,50/60 Hz
Enhanced Power Supplies,
EPS/EPS+ 220-240 VAC Models 2•3 A maximum @ 204 to 264 VAC,50/60 Hz;
separate taps for 220/230/240 VAC
Input Power
120 VAC Models 4 A maximum @ 102 to 132 VAC,60 Hz
Expansion Power Supply(XPS)
100 W Amplifiers 220-240 VAC Models 2 A maximum @ 204 to 264 VAC, 50/60 Hz;
separate taps for 220/230/240 VAC
Total Power Supply Including module currents and auxiliary power outputs;9 A
Power Supply Output Output Rating total for"Special Application"appliances
Ratings for EPS/EPS+ IDNAC Output Voltage Regulated 29 VRMS
Output switches to
Auxiliary Power Tap 2 A maximum battery backup
Total Power Su I 9 A total includin module currents and auxilia ower during mains AC
Power Supply Output pp y g ry p
Ratings for XPS Output Rating outputs failure or brownout
conditions
(nominal 28 VDC on AC; Auxiliary Power Tap 2 A maximum
24 VDC on battery NACs Programmed 2 A maximum per NAC; Rated 19.1 to 31.1 VDC
backup) for Auxiliary Power 5 A maximum total
Compatible Special Application Appliances Simplex TrueAlert ES and TrueAlert addressable notification appliances;contact your
Simplex product representative for compatible appliances
Battery Charger Battery capacity range UL listed for battery charging of 6.2 Ah up to 115 Ah(batteries larger than 50 Ah
Ratings for EPS/EPS+ require a remote battery cabinet); ULC listed for charging up to 50 Ah batteries
(sealed lead-acid Charger characteristics Temperature compensated,dual rate, recharges depleted batteries within 48 hours per
batteries) and performance UL Standard 864,to 70%capacity in 12 hours per ULC Standard S527
Operating Temp. Range 32°to 120°F(0°to 49°C)
Environmental
Operating Humidity Range Up to 93%RH,non-condensing @ 90°F(32°C)maximum
Installation Instruction Reference 574-844,Transponder Interface Cards 579-343, Local Mode Controller
6 S4100-0103-1 5/2013
• • • - • • � -
Matching box is supplied with surface mount models
4601-9109(red)and 4601-9111 (beige);for semi-flush models 4601-9108
(red)and 4601-9110(beige), use a 1-1/2"(38 mm)minimum depth, 3-gang box
Box dimensions,6-1/2"(165 mm) 1"(25.4 mm)
into box
� � �
Fire Alarm Local Mode Controller
Alarm O
• .
��-
� .� � � Alarm
Silenced 4-1/2" 4-5/8"
(114 mm) O (117 mm)
Local
Mode
• Active
� Power O
On
£;Simplex See Operating Instruction 579-343
� � �
1-3/4"
�Local Mode Controller dimensions,6-3/8"(162 mm)-► �(44 mm)�
Local Mode Controller to Transponder Wiring:
1. Wire close-nippled to transponder, maximum distance=20 ft(6.1 m).
2. Nine wires required:24 VDC(2),one per LED indicator(4), and one per switch(3).
3. Wire size, 18 AWG (0.82 mm2).
• . • • • • . • •
Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7 Slot 8
U U
Block A Block C Block E Block G
Size Definitions:
1 Block=4"W x 5.65" H (102 mm x 144 mm); (often
called 4 x 5 modules)
1 Slot=2"W x 11.3" H (51 mm x 287 mm),typically a
motherboard with daughter card
Block B Block D Block F Block H
U U
Expansion BayChassis
7 S4100-0103-1 5/2013
. .
Front view, box outline without door Side view with door attached
Doorthickness o o �
4-3/4"(121 mm)
3 Bay height=
56"(1422 mm)
Knockout screw/nail holes
(for semi-flush mounting)
o a
Exposed cabinet for
2 Bay height= semi-flush mounting
40"(1016 mm) 1-3/8"(35 mm)
minimum Wall board reference
for semi-flush
mounting, 6"stud
1 Bay height= I
22"(559 mm) J
Exposed door and cabinet
Doors can be hinged left or right for semi-flush mounting
6-1/8"(156 mm)minimum Stud alignment
markers, each side
Optional semi-flush 6"stud I
trim kit reference 4"stud j
� c
24"(610 mm)
� I �6-29/32"
(175 mm)
11-11/16"
(296 mm)
NOTE: A system ground must be provided for Earth Detection and transient protection devices.This connection
shall be made to an approved, dedicated Earth connection per NFPA 70, Article 250, and NFPA 780.
TYCO,SIMPLEX,and the product names listed ln this material ar�e marks and/or�registered marks.Unauthorized use is strictly prohibited f/ESD�1 is a h�ademark ofXn�alis Pty Ltd.
�05 i m p I Ex Tyco Fire Protection Products• Westminster,MA•01441-0001•USA S4100-0103-1 5/2013
www.simplexgrinnell.com
�2013 Tyco Fire Protection Praducks.Ali nghts reserved.A!!speci�ications and other in%rrynafion shown were c�Arrent ns of document revision date and are subject to char�ge without notice.
�oSimplEx 4100m Fire Control Panels
UL, ULC, CSFM Listed; FM Approved; Cabinet Reference; Boxes, Doors,
MEA (NYC) Acceptance* Dress Panels, Rack Mounting, and Accessories
�
4100ES Box and door options:
-- - -- --
• Boxes are available sized for one,two,or three ��� �Q
equipment bays,each with a battery bay located at the ���,,,�,,,�,�
bottom -°��`°`��`�°
• Colors include plarinum or red
Doors are glass front with modular dress panels,or 4100ES One Bay Cabinets
• solid
- - - ---
, -
• Models are available with box and door combined for = ,H
single package shipping,or packaged separately ,
• Enclosures are NEMA 1 rated � � Q
• Refer to individua14100ES data sheets for product _ ;�;�
��.
application listings(see list on page 2) �� ��' ���
Door and dress panel selection is coordinated �����
--
with cabinet function: -__— ___-
• Glass doors with modular dress panels provide 4100ES Two Bay Cabinets
visibility of annunciation and interface modules for _
Control Panels,Network Display Units(NDU),and - � �—
Remote Annunciators _p:r.;�5
• Solid doors are for MINIPLEX Transponders and I�
utiliry function cabinets where module visibility is not
required
4100ES Enclosure details:
� °
• Latching dress panels easily lift off for interna] access �'
I
• Smooth box surfaces are provided for locally cutting
m��ammmmrem I
conduit entrance holes exactly where required u�n�mmmmm
• Alignment markers are provided at the top and bottom
of each box side for 6"(152 mm)or 4"(102 mm)wall —
studs
4100ES Three Bay Cabinets
• Knockout screw/nail holes are supplied for semi-flush
mounting
Upright cabinet rack packaging reference:
• For use with Bud Industries Inc. special cabinet rack
model number 45964
• Refer to page 2 for cabinet rack listing � . °`""
4009 TPS (TrueAlert Addressable Power Supply) 'i
cabinet assemblies: i .
• Cabinet assemblies are available for remote mounting i '„�°
of the TrueAlert addressable power supply(TPS) �
• Refer to page 2 far listings information Qoo9TPs
` Fa4100ESone,�,o,andthreebaycabinets�nithassodatedequiprrerrt:Produdsare 4009 TPS Cabinet
listed by the Califomia State Fre Marstx�(CSFN�pursuant to Section 13144.1 of the �, Assem bly(not to sca le)
Califomia H�Ith arid SaFety Code.See CSFM Listing 716:r0026251 fa-allwaaae �
valu�arxya-�nditions caiceming rraterial presented in this documerrt.It is subjed to
re-e�rrination,revision,arxl possible car�lation.P�ted for use—Glty of NewYaic .
Department of Buildings—NFA'3,�r93E.Additional listir�rray be applicable,oontact
yourla�Slrrple�Ppndudsupplierfathelateststatus.Listirx,}sandapprovalsimder Cabinet Rack Enclosure
Sirrplen Tme Recorder Co.are the property of Tyco Fre Protecfion Prod��cts.
(shown with door open)
S4100-00 37-10 10/2011
. . • •.•- • � • • .
Combined Box and Door Selection (select if box and door are to be shipped together)
Description Platinum 1 Bay Platinum 2 Bay Platinum 3 Bay Red 1 Bay Red 2 Bay Red 3 Bay
Box with Glass Door and Dress Panel 2975-9444 2975-9445 2975-9446 2975-9441 2975-9442 2975-9443
Box with Solid Door 2975-9450 2975-9451 2975-9452 2975-9447 2975-9448 2975-9449
Model Color Description Details
4009 TPS Includes box with door and mounting plate, input terminal block,and wiring harnesses;
2975-9230 Beige Cabinet Separately Order.4100 Series TPS(4100-5120 for US,4100-5121 for Canada,4100-5122,
Assembly for 240 VAC for international use),4009-9813 Interface Card,and batteries(12.7 Ah maximum
remote TrueAlert for cabinet mounting); refer to page 3,to data sheets S4100-0031 and S4009-0003, and
2975-9229 Red Power Supply instructions 579-875 for additional details[Listin s: ETL Listed to UL864&ULCS527;
(TPS)mounting CSFM listed under 7300-0026:0368; FM Approved;NYC Fire Dept.acceptance]
Separate Box and Door Selection (select if boxes and doors are required to be shipped separately)
Description Platinum 1 Bay Platinum 2 Bay Platinum 3 Bay Red 1 Bay Red 2 Bay Red 3 Bay
Box 2975-9438 2975-9439 2975-9440 2975-9407 2975-9408 2975-9409
Glass Doorand Dress Panel 4100-2104 4100-2105 4100-2106 4100-2124 4100-2125 4100-2126
Solid Door 4100-2114 4100-2115 4100-2116 4100-2134 4100-2135 4100-2136
Cabinet Rack Mounting (refer to page 4 for additional details)
Model Description #45964 Listings
#45964, Special upright cabinet rack for 4100ES; 19"(483 mm)E.I.A.; UL and ULC listed only as of document revision
from Bud gray texture; includes front polycarbonate door and rear date; cabinets are listed with the Simplex
Industries Inc. louvered door, both keyed with Simplex"B"keys 4100ES product line
4100-2140 Master Controller Rack Mount Kit,one required per master controller Master Controller and Option Bays
each require 9 Rack Units; 15.75"
4100-2145 Option Bay Rack Mounting Kit, one required per expansion bay height(400 mm)
4100-2144 Power Distribution Module(PDM)Rack Mount Kit,order PDM separately per system voltage, one required per
cabinet rack
Power Distribution Modules (Not required for 4009 TPS Cabinets 2975-9229 and 2975-9230)
Model Voltage Description
4100-0634 120 VAC Power Distribution Module(PDM); select per system voltage;
4100-0635 220/230/240 VAC one required per 4100ES box or cabinet rack
Miscellaneous Accessories
Model Description
4100-9856 Canadian French Applique Kit,for 1, 2,or 3 bay sizes
4100-9857 4100ES Applique Retrofit Kit,for 1,2,or 3 bay sizes; use to identify 4100ES features when new door is not used;
included with Master Controller Upgrade kits as detailed on data sheet S4100-0031
4100-9835 Termination and Address Label Kit,for module marking NOTE: One kit is supplied for each cabinet; order this
if required for additional field module installation
4100-9837 Green LED Power-on Indicator Kit, required for ULC Mounts using knockout provided in solid door
listing of MINIPLEX transponder
2975-9813 Platinum semi-flush box trim 1-7/16"(37 mm)wide,four corners and trim pieces for
2975-9812 Red semi-flush box trim top, bottom,and sides
Battery Reference
Model Capacity Model Capacity Battery Notes
2081-9272 6.2 Ah 2081-9287 25 Ah 1. Sealed lead-acid batteries, 12 VDC each;two required per
2081-9274 10 Ah 2081-9276 33 Ah battery location.
2081-9288 12.7 Ah 2081-9296 50 Ah 2• Battery selection is required if batteries are internal.
3. Select one size per battery set
2081-9275 18 Ah 4. Refer to data sheet S2081-0006 for batter details.
Battery Accessories
Model Description
4100-0650 Battery Shelf, required for 50 Ah batteries
4100-5128 Battery Distribution Terminal Block, mounts to side of box, required for all close-nippled cabinets unless cabinet
receives all power from power supplies and batteries located in the adjacent cabinet
' • � • � .
Subject Data Sheet Subject Data Sheet
4100ES Basic Panel Modules and Accessories S4100-0031 Network Dis la Unit NDU S4100-0036
LED/Switch Modules S4100-0032 Remote Annunciators S4100-0038
4100ES Audio/Phone Modules S4100-0034 InfoAlarm Command Center S4100-0045
MINIPLEX Transponders S4100-0035 Remote Battery Char er S4081-0002
2 S4100-0037-10 10/2011
. - . . .
Front view,box outline without door Side view with door attached
NOTE:
Door thickness o �
A system ground must be 4-3/4°(121 mm)
provided for Earth Detection 3 Bay height=
and transient protection 56��(�a22 mm)
devices.This connection
shall be made to an Knockout screw/nail holes
approved,dedicated Earth (for semi-flush mounting)
connection per NFPA 70,
Article 250,and NFPA 780. ����
For additional installation
information refer to � -
Installation Instructions
579-117. Exposed cabinet for
2 Bay height= semi-flush mounting
40"(1016 mm) 1-3/8"(35 mm)
minimum Wall board reference
for semi-flush
mounting,6"stud
_�;�
1 Bay height=
22"(559 mm)
Exposed door and cabinet
Doors can be hinged left or right for semi-flush mounting
— 6-1/8"(156 mm)minimum Stud alignment
markers,each side
Optional semi-flush �6"stud
trim kit reference r4"stud
�
I•� 24"(610 mm) �6-29/32"
(175 mm)
11-11/16"
(296 mm)
11 ' � •
�Box width 16-1/8"(410 mm)� �B�x depth=�
7"(178 mm)
�13-5/8"(346 mm)�
TrueAlert Addressable Power Supply �
mounts here:
4100-5120, 120 VAC,US
4100-5121, 120 VAC,Canada
4100-5122,220-240 VAC,50/60 Hz, �
International 4009-9813 0
Transponder 16"
panel size= Interface Card Knockouts are (406 mm)
13"W x 9"H(330 mm x 229 mm) (TIC)mounts located on top
AC power LED o here and both sides
�
�
--------------�'- �--; �
Battery Area, 1217 Ah maximum,
AC input No conduit or wiring in this area Door shown
terminal block o ; � o for reference
3 S4100-0037-10 10/2011
. . . . -
s�
�
� I
�� , �
.�.
_ . �
— _ �
s�
�
�
� —
, ,
�
—
_ - - �....�
. � .�.� ;
.�.
� � i -��
�
, � —
I� � i
E
Front View Side View Rear View
. . . - . • . • • • • .•• • •-
Type Upright cabinet rack for exclusive use with Simplex 4100ES Fire Alarm Products
Supplier Order from Bud Industries Inc. (www.budind.com)
Model Number 45964
Height 69-7/8"(1775 mm)
Outside Dimensions Width 24-1/16"(611 mm)
Depth 22" (559 mm)
Color Gray texture
Panel Space Width 19" E.I.A. (483 mm)
Front Door Surface mount with 1/8"thick(3.18 mm)smoke gray polycarbonate, locked with
Simplex"B" key, hinged on left of cabinet
Rear poor Ventilated top and bottom, locked with Simplex"B"key
Sides Side panels are removable from the inside for rack-to-rack mounting
Bottom Pan attached for battery mounting
Levelers Includes 4 stem levelers on bottom
TYCO,SIMPLEX,and the product names listec!rn this maXeria!are marlrs and/or register�ed mar/rs.(J�aauthorized use is sdrictly prohibited.
�05 i m p I Ex Tyco Fire Protection Products• Westminster,MA•01441-0001•USA S4100-0037-10 10/2011
www.simplexgrinnell.com
OO 20//Tyco Fire Protection Products.All righzs resc�ved.A!!spec�ificarioras ancl other ir fonnutt'on shown were current as of'docurnent revision dute and are subject to change without rzotice.
�oSimplEx Fire Alarm Control Panel Accessories
Listings* System Batteries, Sealed Lead-Acid; with Applications
Reference for Battery Cabinets, and Battery Cabinets with Charger
� J
---
Rechargeable, sealed lead-acid batteries: -- --
• Lead-calcium grid structure with immobilized _
electrolyte in absorbent separator �0000 _ „�
o�ooa
• Low maintenance with no need to add water
• Low self-discharge characteristics
• One-piece,high impact polystyrene cell cover with high
reliabiliry dua] seal construction
• UL 924 recognized pressure relief valves � ;@�•
Available in a variety of capacities:
• Batteries for internal mounring range from 6.2 Ah up to �
50 Ah,depending on control panel cabinet size
• Larger batteries, up to ll 0 Ah,mount in external battery
cabinets with models available with internal chargers
Battery cabinets with chargers:
• Battery cabinets with charger communicate with their
connected fire alarm control panel and are available for
4100ES/4010ES/4100U Series and 4010 Series panels __ _
� _ � . Compatible Sealed Lead-Acid Batteries can be
Installed Inside Fire Alarm Control Panel Cabinets
Simplex°rechargeable sealed-lead acid batteries provide
reliable and repeatable discharge and recharge
characteristics for use in fire alarm and other systems �
applications. They are designed with immobilized
electrolyte in an absorbent separator, allowing them to
provide rated capacity on the first cycle.
Because of their sealed construction,packaging is allowed
within the system electronics enclosure(see illustration
on page 2).When this is applicable,the quantity of
system cabinets and the battery wiring distances are both
minimized.Where required,external battery cabinets can Remote Battery Cabinets are Available for
be close-nippled to the control panel to house larger Larger Battery Requirements
batteries with battery chargers available in some battery
cabinet sizes.
� � • -�
Charging. These batteries are intended to be used with Shipping. Sealed lead-acid batteries are shipped via
compatible Simplex battery chargers. ground or sea transportation only. They are not shipped
via air.
Series Connections. These batteries are required to be
connected in series to produce 24 V system voltage. Disposal. Battery chemicals and materials can be
Battery sets must be of idenrical voltage,model number, recycled. Refer to information shipped with the battery or
appearance,and approximately the same date of on its case.Return to the battery manufacturer or to a
manufacture for proper operaYion. similarly qualified battery processing facility for proper
disposal.
Testing.Battery capacity testing is recommended to be
performed by using a sealed lead-acid battery tester � �{�-to details on page 4 and to the referer�ced individual product data
designed to withdraw a minimum of battery charge. The sheets fa-ageaicy�isting status of battery cabinets and ct,argers.TI-ie batteries
preferred tester applies a variety of amplitude and detailed in this cloa.iment rreet the requirerrents of UL,ULC,and Fac#ay
duration controlled test pulses that compares terminal Mutual for use with respective equipment battery chargers as listed on page 3.
voltage against those predicted for the specific battery �tad Your local Sirrplex product supp�ier fa-proper battery seledia,per
size. (Testing is available through your local Simplex systemrequire���ts.ListingsandapprovalsunderSirrplexTimeReca-der
product supplier.) Co.are the prc�erly of Tyco Fre Protedion Produds.
S2081-0006-20 1/2012
. .
Actual appearance will vary with battery size.
Sealed outer cover
Quick connect or post type terminal Vent hole
(type varies with battery size)� Potting material,black for
negative,red for positive
0 0 (polarity is also clearly
� marked with+and-)
�
Pressure relief valve
Innercover
Absorbent separator used
to immobilize electrolyte
Semi-permeable
Lead-calcium grids membrane separator
Cell group
Cell case(high impact
polystyrene)
• •
Capacity @ 20 Hour Height with Approximate
Battery Model Discharge Rate Width" Depth" Terminals Weight*
2081-9272 6.2 Ah 6-1/8"(156 mm) 2-5/8"(67 mm) 4"(102 mm) 5.75 Ibs(2.6 kg)
2081-9274 10 Ah 6"(153 mm) 4-1/16"(103 mm) 4"(102 mm) 9.2 Ibs(4.2 kg)
2081-9288 12.7 Ah 6"(153 mm) 4"(102 mm) 4"(102 mm) 9 Ibs(4.1 kg)
2081-9275 18 Ah 7-1/4"(184 mm) 3-3/8"(86 mm) 6-5/8"(168 mm) 14.3 Ibs(6.5 kg)
2081-9287 25 Ah 6-5/8"(168 mm) 5"(127 mm) 7"(178 mm) 19.4 Ibs(8.8 kg)
2081-9271
(rectangular case, 33 Ah 12-1/2"(318 mm) 3-3/8"(86 mm) 7-1/16"(179 mm) 26.6 Ibs(12.1 kg)
typically for service)
2081-9276
("square"case, 33 Ah 7-3/4"(197 mm) 5-1/4"(133 mm) 6-3/4"(171 mm) 26.5 Ibs(12 kg)
use for new)
2081-9296 50 Ah 9"(229 mm) 5-1/2"(140 mm) 8-7/8"(225 mm) 41.8 Ibs(19 kg)
2081-9279 110 Ah 11-3/16"(284 mm) 10-1/2"(267 mm) 9"(230 mm) 82 Lbs(37 kg)
� Dimensions and weight are per battery and are for reference only. Exact size may vary. Refer to the tables on page 3 for
mounting compatibility.These batteries are 12 V each and series connected for 24 V system use.
NOTE: When wired in series for 24 V output,these batteries are to be of identical voltage,appearance,model number,and
approximately the same date of manufacture.
• •
Nominal Voltage Rating 12 Volts per battery
Discharge Rating 20 Hour Rate
Typical Charge/Discharge Cycles 100 to 150
Preferred Charge Temperature Range 60° F to 90° F(15.6°C to 32.2°C)
2 S2081-0006-20 1/2012
. . . . . � . . . .
NOTE: Refer to individual fire alarm control panel product data sheets for additional battery application information
Simplex Control Panel Model Series(see legend and notes below)
Battery Capacity
Model 4006& 4009 4100ES/ 4100&4120 4020
4003EC 4004R 4005 4008 (all models) 4010 4010ES 4100U (2,4 or 6-Unit) (2,4 or 6-Unit)
2081-9272 6.2 Ah ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
2081-9274 10 Ah �/ ./ �/ �/ �/ ./ �/ �/ �/ ./
2081-9288 12.7 Ah ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
2081-9275 18 Ah Ext Note 3 J Ext Ext Note 2 �/ �/ ./ ,/
2081-9287 25 Ah Ext Note 3 Ext Ext NA ✓ ✓ ✓ ✓ Ext
2081-9271 33 Ah Ext Note 3 Ext NA NA Note 3 �/ �/ Ext Note 4
rectangular
2081-9276 33 Ah Ext Note 3 Ext NA NA Note 3 ✓ ✓ ✓ Ext
"square"
2081-9296 50 Ah NA Note 3 NA NA NA Note 3 Note 6 2 or 3 bay Ext Ext
2081-9279 110 Ah Requires external battery cabinet,compatible with 4100ES,4010ES,4100,and 4120 Series only
✓ =Can be placed in the respective equipment cabinet
Ext=External battery cabinet is required, refer to selection chart on page 4
NA=Not applicable/not compatible
NOTES:
1. These batteries meet the requirements of UL, ULC,and Factory Mutual for use with respective equipment battery chargers
listed above. Contact your local Simplex product supplier for proper battery selection per system requirements.
2. 4010 Cabinets will accommodate 2081-9275, 18 Ah batteries, but will not allow bottom entry conduit.
3. Use 4081 series companion cabinet and charger, refer to page 4.
4. 4020 Cabinets will accommodate 2081-9271,33 Ah batteries, but will not allow bottom entry conduit.
5. Some control panel models are listed for battery replacement reference only.
6. For 2 bay international applications only,50 Ah batteries will fit in the cabinet.
. . . • . •
Battery Cabinets without Chargers (connects to charger in panel)
Battery
Cabinet Panel Compatibility 2081-9275 2081-9287 2081-9271 2081-9276 2081-9296 2081-9279
18 Ah* 25 Ah Rectangular 33 Ah Square 33 Ah 50 Ah 110 Ah
2081-9280 4100ES,4010ES, NA NA NA NA NA ✓
4100U, and 4100+
2081-9281 multiple �/ �/ ✓ J ✓ NA
2081-9282
4009-9801 multiple ✓ ✓"* NA NA NA NA
4009-9802 multiple ✓ NA ✓ NA NA NA
Battery Cabinets with Chargers
2081-9275 2081-9287 2081-9271 2081-9276 2081-9296 2081-9279
Cabinet Panel Compatibility 18 Ah* 25 Ah Rectangular 33 Ah Square 33 Ah 50 Ah 110 Ah
4081-9301 4004R and 4010 J ./ ✓ J J NA
4081-9302
4081-9306 4100ES,4010ES, NA NA NA NA �/ J
4081-9308 and 4100U
*Batteries smaller than those listed are normally mounted in the product cabinet
"25 Ah capacity was effective as of 7/2005.
✓=Can be placed in the respective equipment cabinet
NA=Not applicable/not compatible
3 S2081-0006-20 1/2012
. . .
Battery Cabinets Without Chargers; Shallow Design with Front Door
Model Color Listings Description Dimensions
2081-9281 Beige UL and 2'Unit,4100 style cabinet without charger;with locking 25-3/4"W x 20-3/4"H x 6-3/4"D
FM solid door and battery shelf, primarily for use with 50 Ah (654 mm x 527 mm x 171 mm)
2081-9282 Red batteries
4003-9860 Beige Multiple Intended for use with 4003EC systems,for up to 33 Ah 9-1/2"H x 24"W x 9"D
batteries(refer to 4003EC data sheet S4003-0002) (241 mm x 610 mm x 229 mm)
4009-9801' Beige UL and For up to 25 Ah External battery cabinet without charger, 16-1/4"W x 13-1/2"H x 5-3/4"D
FM batteries' with locking solid door and battery (413 mm x 343 mm x 146 mm)*
For up to 33 Ah harness;for close-nippled mounting to 25-3/4"W x 20-3/4"H x 4-1/8"D
4009-9802 Beige UL batteries fire alarm control panel cabinet (654 mm x 527 mm x 105 mm)
*Depth increased for 25 Ah batteries effective 7/2005.
Chargers for use with 4010 Fire Alarm Control Panels and 4004R Suppression Release Systems
(refer to data sheet S4081-0001)
Model Color Input Voltage Description Dimensions
4081-9301 Beige Battery cabinet with charger for the 4010 and
4004R fire alarm control panel;for up to 50 Ah
120 VAC batteries;with front door 22-1/2"W x16-3/4"H x 8-3/8"D
4081-9302 Red
Listings include:UL, ULC, FM, CSFM, and MEA �572 mm x 425 mm x 213 mm)
(NYC), see data sheet for details
Battery Cabinet Without Charger for 110 Ah Batteries; for use with compatible panel mounted chargers
(refer to data sheet S2081-0012)
Model& Color Cabinet Description Compatible Charger Description Dimensions
Listings Chargers
4010-9xxx 4010ES Main System Supply
Series (MSS)
4100-9xxx 4100ES/4100U System Power
Series Supplies(SPS)
Battery cabinet for 4100-5111
2081-9279, 110 Ah 4100-5112 4100ES/4100U Additional SPS
2081-9280 batteries; includes 4100-5113
Listings Red $0 A battery fuse, 4100-5125 4100ES/4100U Remote Power 26-1/2"W x 12"H x 12"D
include:UL terminals and 4100-5126 Supply(RPS) (673 mm x 305 mm x 305 mm)
and CSFM battery connection 4100-5127
cables; see data 4100-5120
sheet for details 4100-5121 4100ES/4100U TrueAlert
4100-5122 Addressable Power Supply(TPS)
4100-0104
4100-0114 4100 Legacy power supplies
4100-0124
4100ES/4010ES/4100U Compatible Battery Cabinet With Charger for 110 Ah Batteries (for ULC listed systems
and for other applications unable to use panel mounted power supply charger; referto data sheet S4081-0002)
Model Color Input Voltage Description Dimensions
Battery cabinet with charger for up to 110 Ah
4081-9306 Red 120 VAC batteries;
NOTE: Required for ULC listed charging of 27-7/8"W x 13-1/2"H x 14-5/8"D
220/230/240 VAC, 110 Ah batteries;Listings include:UL, ULC, FM, (708 mm x 343 mm x 371 mm)
4081-9308 Red multi-tapped CSFM, and MEA (NYC), see data sheet for
details
4100-9837 Green LED Power-on Indicator Kit, required for ULC listing,mounts above access panel using knockout provided
TYCO,SIMPLEX,and zhe product names Iisted in this material are marks and/a��-egistered marks.Unauthorized use is strictly pi�ohibited.
�oSim plEx Tyco Fire Protection Products• Westminster,MA•01441-0001•USA S2081-0006-20 1/2012
www.simplexgrinnell.com
OO 20/2 Tyco Fire Protection Products.All righzs resc�ved.A!!spec�ificarioras ancl other ir fonnutt'on shown were current as of'docurnent revision dute and are subject to change without rzotice.
��Simplex TrueAlert° Multi-Candela Notification Appliances
UL, ULC, CSFM Listed; FM Approved; Visible Notification Appliances with Speaker
MEA (NYC) Acceptance* and Multi-Candela Strobe; Non-Addressable
�
Speaker/visible (S/V) notification appliances with I,III ,...,,,�,, ,S,m�,e%
multi-tapped speaker and multi-tapped high
intensity xenon strobe with synchronized flash: ��
• Rugged,high impact,flame retardant thermoplastic � �,
g g � ___
ousm s are avai a e or wa or cei m mount �� - _— ,
• Operation is compatible with ADA requirements(refer to ��� ����
important wall mount installation information on page 4)
___ _— —
Wall mount S/V features: ' ' • •
• Housings are available in red or white with clear lens ° °
with contrasting white or red"FIRE"lettering _
• Covers are available separately to convert housing color �� � � �:�
Ceiling mount S/V features:
• Housing is white with clear lens
• Red"FIRE"lettering is printed on two sides
Audible notification appliance (speaker): �-�
• High quality voice and tone reproduction with taps for F==`\\��
1/4, 1/2, 1,or 2 W,at 25 or 70.7 VRMS � � �
• Capacitor input for connection to supervised notification �
appliance circuits �`
• Speakers are wired separately from strobe wiring
• UL listed to Standard 1480 �
Visible notification appliance (strobe): '�
• 24 VDC xenon strobe; intensity is selectable as 15,30, Wall and Ceiling Mount S/Vs
75,or 110 candela with visible selection jumper secured
behind strobe housing � - . .
• Strobes are activated from NACs selected to provide Multi-Candela TrueAlert S/Vs with speaker and
Simplex°strobe synchronization signals or from SynChrOnized Strobe provide convenient installation
separate strobe Synchronization Modules that are to standard electrical boxes with extensions. The
available for Class B or Class A operation** enclosure designs are both impact and vandal resistant
• Regulated circuit design ensures consistent flash output and provide a convenient strobe intensity selection. Since
and provides controlled inrush current each model can be selected for strobe intensity output,
• UL listed to Standard l 971 on-site model inventory is minimized and changes
Options for wall mounted S/Vs: encountered during construction can be easily
accommodated.
• Red or white adapters to cover surface mounted
electrical boxes Wall mount S/V housings are a one-piece assembly
• Red adapter for mounting to Simplex 2975-9145 boxes (including lens)that mounts to a 4"square electrical box
• Red wire guard with extension(see details on page 4). The cover can be
quickly removed(a tool is required)and covers are
available separately for color conversion.
Ceiling mount SNs also install using 4"electrical
' �ertopayezfa-iis�r,gs�atuso�w�regu�-ds.Tr,�sp�duar,as�eer,app�-ovedbytr,e boxes with an extension(see details on page 4).
Califania State Fre N}arshal(CSFN�pursuant to Sedion 13144.1 of the Califomia Health
and Safety Caie.See CSFM Listing 7320-0026:247 for allw�rable values arid/or a�riditiais
conoeming rr�terial presented in this doaamerrt.It is subjed to re-exarrination,revision, • • - •
arid possible carxellation.Pccepted for use—(Sty of NewYaic Departrrent of Buildirx�s—
NEA35-93E.Pdditior�al listirx,}s rrey be applicable;c�r,taa ya,r i«�sr,p�eX aod��ct During installation,a selection plug at the back of the
supplierfa-thelateststatus.Listir83saidapprovalsunderSirrplexTirreRecorderCo.ae housin determines the desired strobe intensit An
tne�o�y o�Tyo�s��y Frod�cs v�tm�t�. g Y•
'�`SirrpeXt�w�v�,irestronesyr,d,ra,iZatia,operatia,ispr�ectednyu.s.patentNos. attached flag with black letters on a highly visible yellow
s,�,asz;a,ass,s2o;s,�a�,�sa;and s,�xt,�s�. background allows the selected intensity to be seen at the
side of the strobe lens.
S4906-0003-6 2/2010
. - . . . - . . - � . . . .
Multiple Strobes.When multiple strobes and their Proper selection of visible notification is dependent on
reflections can be seen from one location, synchronized occupancy, location, local codes,and proper applications
flashes reduce the probability of photo-sensitive reactions of: the National Fire Alarm Code(NFPA 72),ANSI
as well as the annoyance and possible distraction of Al 17.1;the appropriate model building code: BOCA,
random flashing.The multi-candela strobes of these S/Vs ICBO,or SBCCI;and the application guidelines of the
are acrivated by NACs that provide the Simplex Americans with Disabilities Act(ADA).
synchronization format. For additional information,refer
to data sheet 54905-0003.
. . .
Wall Mount Multi-Candela S/Vs
Model Housing "FIRE" Description Housing Dimensions with Lens
Color Lettering
4906-9151 Red White Multi-tapped Speaker with Multi-Candela 7-1/4" H x 5"W x 2-5/8"D
Synchronized Strobe;strobe intensity selectable (184 mm x 127 mm x 67 mm)
4906-9153 White Red as: 15, 30, 75, or 110 candela
Ceiling Mount Multi-Candela S/V
Model Housing "FIRE" Description Dimensions
Color Lettering
Housing=7-1/2"(191 mm)
Multi-tapped Speaker with Multi-Candela diameter, 1/2"(13 mm)deep
4906-9154 White Red Synchronized Strobe;strobe intensity selectable Strobe lens protrusion=2-5/8"
as: 15, 30, 75, or 110 candela (67 mm)above speaker housing
Depth into box=2-3/4"(70 mm)
Wall Mount S/V Adapters
Model Description Dimensions
4905-9946 Surface mount red adapter skirt Required when mounting to surface 7-3/4"H x 5-3/8"W x 3-3/16"D
mounted electrical box,4"square, (197 mm x 137 mm x 81 mm)
4905-9947 Surface mount white adapter skirt 1-1/2"deep with 1-1/2"deep extension depth with S/V=5-7/8"(149 mm)
4905-9903 Adapter Plate, red, required to mount S/V on 2975-9145 8-5/16" H x 5-3/4"W x 0.060"Thick
(211 mmx146mmx1.5mm)
2975-9145 Mounting box, red,for surface or flush mount, requires adapter plate 7-7/8"H x 5-1/8"W x 2-3/4"D
4905-9903(this box may be available for retrofit applications) (200 mm x 130 mm x 70 mm)
Wall Mount S/V Replacement Covers
Model Description Dimensions
4905-9996 Red S/V cover with white"FIRE"lettering 7-1/4"H x 5"W x 1-3/8"D
4905-9997 White S/V cover with red"FIRE"lettering (184 mm x 127 mm x 35 mm)
Synchronized Flash Control Modules
Model Description Dimensions
4905-9914* Synchronized Flash Module, Class B Epoxy encapsulated with in/out
(Style Y)operation 18 AWG(0.82 mm2)wire leads, 1-3/8"W x 2-7/16"L x 13/16"H
4905-9922* Synchronized Flash Module,Class A rated for 2 A NAC, requires 5 mA (35 mm x 62 mm x 20 mm)
(Style Z)operation for power
Wall Mount S/V Wire Guard
Model Description Dimensions
4905-9998 Wire guard with mounting plate, red,compatible with surface and semi-flush 8-3/8"H x 6-1/16"W x 3-1/4"D
boxes(UL listed by Space Age Electronics Inc.) (213 mm x 154 mm x 79 mm)
Ceiling Mount Tile Bridge
Model Description Dimensions
2905-9946 Tile Bridge See diagram on page 4
'Refer to data sheet S4905-0003 for additional flash control module information
2 S4906-0003-6 2/2010
. - . .
Common Specifications
Environmental;Temperature and Humidity 32°to 122°F(0°to 50°C); 10%to 93%,non-condensing at 100°F(38°C)
Connections Terminal blocks for 18 AWG to 12 AWG(0.82 mmZ to 3.31 mmz);two wires per
terminal for in/out wiring
Speaker Specifications
Input Voltage 25 or 70.7 VRMS,see Note 1 below
Power Taps 1/4, 1/2, 1,and 2 W
Fire Alarm 400 to 4000 Hz
Frequency Response
General Signaling 125 to 12 kHz
Wattage Tap 1/4 W 1/2 W 1 W 2 W
Speaker Output Ratings Reverberant Chamber,
@ 10 ft(3 m) UL 1480Test �6 dBA 79 dBA 82 dBA 85 dBA
(see Note 1 below) Anechoic Chamber, 87 dBA 90 dBA 93 dBA 96 dBA
1 kHz Input,On-Axis
Strobe Specifications
UL Listed Rating Regulated 24 VDC;see Note 2 below
Rated Voltage Range
ULC Listed Rating 20 VDC to 30 VDC per ULC S526-M878
Flash Rate and Synchronized NAC Loading 1 Hz;with up to 35 synchronized strobes maximum per NAC
Housing Dimensions(with lens) 7-1/4"H x 5"W x 2-5/8"D(184 mm x 127 mm x 67 mm)
Maximum RMS Current Rating per 75 cd 30 cd 75 cd 110 cd
Wall Strobe Setting(see Note 3 below) 60 mA 94 mA 186 mA 252 mA
Mount
Reference RMS Currents at 18 VDC 53 mA 84 mA 165 mA 224 mA
other voltages 24 VDC 40 mA 63 mA 124 mA 168 mA
Housing Dimensions Speaker housing=7-1/2"(191 mm)diameter, 1/2"deep(13 mm); lens protrusion
above speaker housing=2-5/8"(67 mm);depth into box=2-3/4"(70 mm)
Ceiling Maximum RMS Current Rating per 15 cd 30 cd 75 cd 110 cd
Mount Strobe Setting(see Note 3 below) 75 mA 125 mA 233 mA 316 mA
Reference RMS Currents at 18 VDC 67 mA 111 mA 207 mA 281 mA
other voltages 24 VDC 50 mA 83 mA 155 mA 211 mA
NOTES:
1. Speakers are for connection to conventional fire alarm audio circuits.Anechoic speaker output ratings are typically more representative
of actual installed sound output.
2. "Regulated 24 VDC"refers to the voltage range of 16 to 33 VDC per UL Standard 1971, Signaling Devices forthe Hearing Impaired,
changes effective May 1,2004.This voltage range is the absolute operating range.Operation outside of this range may cause
permanent damage to the appliance. Please note that 16 VDC is the lowest operating voltage that is allowed at the last appliance on
the NAC under worst case conditions.
3. The maximum RMS strobe current listed is the device nameplate rating.Strobe designs are constant wattage and the maximum RMS
current rating occurs at the lowest allowable operating voltage.(RMS is root mean square and refers to the effective value of a varying
current waveform.)
• � •
85
--� �
M 84
'Y 83
0
R 82
m
� 81 � � �
; $O I
N
J
� 79
�
N �$ I
N
a`
v �� I i
c
� �6 _ " -
v°� _ �'
�s
90 80 70 60 50 40 30 20 10 0 10 20 30 40 50 60 70 80 90
Angular Displacement(Degrees)on Horizontal Axis
-2kHz 4kHz
3 S4906-0003-6 2/2010
� • • • • � - � •
:_
O ��� i �� T e Bnd4e +
� � 1/2"(13 mm) ��
O O �� 4"(102 mm)square, 1-1/2"
O (38 mm)deep box with 1-1/2" 0.024"thick sheet
0 � extension(by others) metal,folded with
1/2" lip each side
. I 3-3/4"(95 mm)square
� cutout,centered on plate
Wiring input terminals and �
speaker tap selection are 23-11/16"
� accessible from rear of (602 mm)
� � � speaker housing
I �
I
1/4"diameter(6
� i � mm)holes,4 places
- � Strobe intensity i
�- i viewing slot i
N �
� Intensity selection plug, I 6-11/16"
I accessible only from rear of lens � � (170 mm)
� housing;factory setting is 15 cd � �I
�-----------------------I
�13-3/8"(340 mm)�
• •
IMPORTANT!INSTALLATION
�� MOUNTING HEIGHT REFERENCE
i� Mounting to 2975-9145 Box �� �� Standard Electrical Box Mounting i
� � � 4"(102 mm)square box,1-1/2" ; 2975-9145
2975-9145 Box�_ � ; (38 mm)deep,with a 4"square box ; box outline� 4"square box outline
� � � extension,1-1/2"deep,by others ;
� � � � �� ' �
�
i 0 i � � �� �� �� i 4"(102 m m)
i i � L� L� �� i
i � � � � i ��__
i �
i ii I � � �
' � ' ' �" � \ �I i 82"(2.1 m) 1-1/2"(38 mm)
i l i r o � I o J r � minimum
4905-9903 �� � � � � ��� � J i NFPA 72 requires that the
Adaptef PIaYe � ��-;'� � � I � � i 78-1/2"(2 m) entire lens be not less than
i
/�� I � o �� � minimum 80"and not greater than 96"
� `� �I above the finished floor.
O / R ° ���� J �
' _ i
I ��� ' �� i
i
i �
i __ ______________________''
i—
U � Wiring input terminals and Surface Mounting Reference
°°°°m`�°�°° �� speaker tap selection are Showing Optional Wire Guard
accessible from rear
� ' Surface mount conduit and
o Speaker assembly box shown for reference
Strobe assembly _
_ _ 4"(102 mm)square box
---,---
, , ,
�� � � profile,1-1/2"(38 mm)
� O deep with 1-1/2"extension � �
� � ---�---
�.-- Optiona14905-9998 �
__ Intensity selection Wire Guard I
Transparent p�ug,accessible only
housin and from rear of housing; 75
Removable cover g factory setting is�5 cd gN
(tool required) lens assembly
Strobe intensity
�'c � n � viewing slot Surface mount adapter skirt,3-3/16"(81 mm)
�f-' �� deep,required for this mounting method:
4905-9946,Red;4905-9947,White(conduit
knockouts are provided on all four sides)
Tyco is a regisCered h�ademark of Tyeo International Services GMBHand is used under license.Simplex,the Simplex logo,and TrueAlert are trademarkr of Tyco Internationa!
L(d.and iGr affiliates and are used aender license.NFPA 72 and National L'ire Alarm Code are register�ed tr'ademarks of the National Fir�e Protection Association(NFPA).
�3 Simplex Tyco Safety Products Westminster• Westminster,MA•01441-0001•USA S4906-0003-6 2/2010
� www.tycosaferyproducts-usa-wm.com
C 20/0 Tvco Safety Prroducts Weshninstee A!!nohts reserved.A!l spec�icarions and ather inforn�alion shown were curT�ent as of doc7�rnent revision dnte a�zd are subject to change without riotice.
��Simplex System Accessories
UL Listed* 4081 Series End-of-Line
Resistor Harnesses
�
For use as Class B end-of-line resistor:
• Connect these resistor harnesses where
end-of-line resistors are required at remote
locations to monitor wiring continuity
• Refer to specific circuit specifications for
end-of-line resistor requirements
UL Listed to Standard 864
' . . • —9-1/2"
(241 mm)
Model Reference Description**
Number
4081-9001 733-892 2.2 kS2, 1/2 W
4081-9002 733-893 3.3 kS2, 1 W
4081-9003 733-896 4.7 kS2, 1/2 W
4081-9004 733-886 6.8 kS2, 1/2 W
4081-9005 733-984 1.8 kS2, 1/2 W
4081-9006 733-890 560 52, 1 W
4081-9007 733-891 1.2 kS2, 1 W
4081-9008 733-894 10 kS2, 1/2 W
4081-9009 733-912 20 S2, 1 W
4081-9010 733-973 1 kS2, 1 W
4081-9011 733-974 100 S2, 1/2 W
4081-9012 733-985 22 kS2, 1/2 W Typical 4081 Series Resistor Harness Assembly
4081-9013 734-086 4.99 kS�, 1/2 W, ± 1% (full size except for lead length)
4081-9014 734-092 2.4 kS2, 1/2 W
4081-9015 734-093 1.5 kS2, 1/2 W
4081-9016 734-149 150 kS2, 1/2 W � . , ,
4081-9017 734-171 3.9 kS2, 1 W
4081-9018 734-168 10 kS2, 1 W Overall Length Approximately 9-1/2" (241 mm)
�'±5%tolerance except as noted. Wire Length 7"(178 mm)± 1" (25 mm)
Wire Size 18 AWG (0.82 mmZ)
Insulation 600 V, black
Leads Stripped 0.5"(13 mm);tinned
Resistor Resistor leads are crimped to wires
Attachment and covered with heat shrink tubing
'This product was not approved by ULC,FM,MEA(NYC),or CSFM as of document revision
date.Additional listings may be applicable,contact your local Simplex0 product supplier for
the latest status.Listings and approvals under Simplex Time Recorder Co.are the property
of Tyco Safety Products Westminster.
S4081-0003 7/2004
Tyco,Simpler,and the Sim�ler logo a�-e trademarks ofTvco lnternational Services AG or its affiliates in the U.S.and/or other coi�ntries.
f3Simplex Tyco Safety Products Westminster• Westminster, MA•01441-0001•USA S4081-0003 7/2004
� www.tycosafetyproducts-usa-wm.com
OO 2004 Tyco Safety Products Weshnrnstee Al!nghts reserved.All spec�ca6ons and otlzer informa6on shown were current us of doeument revision date und are.subject to change without notice.