HomeMy WebLinkAboutF13-0049 specs Bulletin 006 Rev. F
Model RFC30 (SIN RA0611) °J
� C� Model RFC43 (SIN RA0612) �
Model RFC49 (SIN RA0616) �
Residential Flat Concealed �
Sprinklers ;,
A Residential Flat Concealed ; �, � � ' -
..�
Sprinklerengineered fora minimum -- �•: '
design density of 0.05 gpm/ft2 with �� � ��
r
low GPM requirements. �
Features
,
1. Very low water flow requirements.
2. '/2" (13mm) Total adjustment. � , f
3. Thread-On/Thread-Off or Push-On/Thread
Off cover attachment option. }
4. Smooth aesthetic ceiling profile.
5. Available in brass, chrome and black plated
or painted finishes.
Listings & Approval
1. Listed by Underwriters Laboratories, and �
certified by UL for Canada (cULus) ` � ��
2. NYC MEA 258-93-E
UL Listing Categories
Residential Automatic Sprinklers
UL Guide Number
VKKW
Product Description
Model RFC30, RFC43 and RFC49 Concealed Residen- the most dependable fire protection available, an automat-
tial Sprinklers are fast response residential fusible solder ic sprinkler system.
link automatic sprinklers. Residential sprinklers differ from The RFC30, RFC43 and RFC49 are UL Listed Residential
standard sprinklers primarily in their response time and Sprinklers to be installed in the residential portions of any
water distribution patterns. occupancy in accordance with NFPA 13, 13R, & 13D.
Model RFC30, RFC43 and RFC49 sprinklers discharge The RFC30, RFC43 and RFC49 can reduce the need for
water in a hemispherical pattern below the sprinkler de- precise cutting of drop nipples. The threaded cover plate
flector. Residential distribution patterns are higher and assembly can be adjusted without tools to fit accurately
generally contain a finer droplet size than standard sprin- against the ceiling. The fire protection system need not be
kler patterns. shut down to adjust or remove the cover plate assembly.
The combination of speed of operation and high dis- Application and Installation
charge pattern required for residential sprinklers has dem- The RFC30, RFC43 and RFC49, for residential installa-
onstrated, in fire testing, an ability for controlling residen- tions, use a 165°F(74°C)fusible solder link in a tuning fork
tial fires, and thereby providing significant evacuation time style sprinkler frame with a drop-down deflector. This as-
for occupants. sembly is recessed into the ceiling and concealed by a flat
The RFC30, RFC43 and RFC49 Sprinklers provide the cover plate. The cover plate is attached to the skirt, using
best form of fire protection by combining an attractive ap- 135°F (57°C) ordinary temperature classification solder.
pearance and '/2" (13mm) of cover adjustment for ease of When the ceiling temperature rises, the solder holding
installation. The small diameter cover plate is easily and the cover plate releases the cover allowing the deflector
positively attached and blends into the ceiling, concealing to drop into position and exposing the sprinkler inside to
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
ceiling temperature. The subsequent operation of the sol- OF THE SPRINKLER/CUP ASSEMBLY. MODEL RFC30,
der link opens the waterway and causes the deflector to RFC43 AND RFC49 CONCEALED SPRINKLERS MUST
drop into position to distribute the discharging water in a BE INSTALLED ONLY WITH 135°F RATED COVERS.
hemispherical pattern below the sprinkler deflector. Any Note: A leak tight'/2" NPT(R1/2) sprinkler joint can be ob-
adjustment of thread engagement between the cover tained with a torque of 8-18 ft-Ibs (10,8- 24,4 N-m). Do not
plate and cup will assure that the drop-down deflector is tighten sprinklers over maximum recommended torque. It
properly located below the ceiling. The residential distri- may cause leakage or impairment of the sprinklers.
bution pattern contains a finer droplet size than a standard Cover assemblies provide up to '/z" (13mm) of adjust-
sprinkler, and the pattern produces significantly higher ment. Turn the cover clockwise until the flange is in con-
wall wetting. tact with the ceiling. For the push-on/thread-off option, the
After a 25/g inch diameter hole is cut in the ceiling, the cover assembly is pushed onto the cup and final adjust-
sprinkler is to be installed with the Model FC Wrench. ment is made by turning the cover clockwise until the skirt
When installing a sprinkler, the wrench is first positioned flange makes full contact with the ceiling. Cover removal
into the sprinkler/cup assembly and around the hexagonal requires turning in the counter-clockwise direction.
body of the sprinkler frame. The Wrench must bottom out In ceilings that have a plenum space above the sprinkler,
against the cup in order to ensure proper, safe installation. the plenum space may have neutral or negative pressur-
The sprinkler is then tightened into the pipe fitting. When ization but must not be positively pressurized. Inspect all
inserting or removing the wrench from the sprinkler/cup sprinklers after installation to ensure that the gap between
assembly, care should be taken to prevent damage to the cover plate and ceiling and the 4 slots in the cup are
the sprinkler. DO NOT WRENCH ON ANY OTHER PART all open and free from any air flow impediment.
Temperature Rating
Sprinkler Cover Plate Max.Ambient Temp.
165°F/74°C 135°F/57°C 100°F/38°C
Installation Data: RFC30 (SIN RA0611)
Thread Sprinkler Maximum Minimum Minimum Required
Distance to Distance between Sprinkler Discharge
Size K Factor Spacing N►all s rinklers
inch (mm) ft. (m) p Flow Press.
ft.(m) ft. (m) gpm (Lpm) psi (bar)
'/z"(15mm) 3.0 12 x 12(3.6x3.6) 6(1.83) 8(2.43) 9(34.1) 9.0(0.62)
'/z"(15mm) 3.0 14 x 14(4.3x4.3) 7(2.13) 8(2.43) 10(37.8) 11 (0.76)
Note: 1 bar= 100 Kpa
Installation Data: RFC43 (SIN RA0612)
Thread Sprinkler Maximum Minimum Minimum Required
Size K Factor Spacing Distance to Distance between Sprinkler Discharge
inch (mm) ft. (m)
Wall sprinklers Flow Press.
ft. (m) ft. (m) gpm (Lpm) psi (bar)
Y2"(15mm) 4.3 12 x 12(3.6x3.6) 6(1.83) 8(2.43) 12(45) 7.8(0.54)
Yz"(15mm) 4.3 14 x 14(4.3x4.3) 7(213) 8(2.43) 13(49) 9.1 (0.63)
Yz"(15mm) 4.3 16 x 16(4.9x4.9) 8(243) 8(2.43) 13(49) 9.1 (0.63)
Y2"(15mm) 4.3 18 x 18(5.5x5.5) 9(2.74) 8(2.43) 18(68) 17.5(1.21)
Y2"(15mm) 4.3 20 x 20(6.Ox6.0) 10(3.05) 8(2.43) 21 (79) 23.8(1.64)
Note: 1 bar= 100 Kpa
Installation Data: RFC49 (RA0616)
Maximum Minimum Minimum Required
Thread Sprinkler Distance to Distance between Sprinkler Discharge
Size K Factor Spacing Wall s rinklers
inch (mm) ft. (m) p Flow Press.
ft. (m) ft. (m) gpm (Lpm) psi (bar)
'/z"(15mm) 4.9 12 x 12(3.6x3.6) 6(1.83) 8(2.43) 13(49) 7.0(0.48)
'/z"(15mm) 4.9 14 x 14(4.3x4.3) 7(2.13) 8(2.43) 13(49) 7.0(0.48)
'h"(15mm) 4.9 16 x 16(4.9x4.9) 8(2.43) 8(2.43) 13(49) 7.0(0.48)
'/z"(15mm) 4.9 18 x 18(5.5x5.5) 9(2.74) 8(2.43) 17(64.3) 12.0(0.83)
'/z"(15mm) 4.9 20 x 20(6.Ox6.0) 10(3.05) 8(2.43) 20(757) 16.7(1.14)
Note: 1 bar= 100 Kpa
FOR SLOPED CEILING APPLICATIONS SEE RASCO BULLETIN 035.
2.
Maintenance
Model RFC30, RFC43 and RFC49 Concealed Sprinklers consist of a brass cover plate and copper alloy retainer
should be inspected quarterly and the sprinkler system flange allowing a'/z" cover plate adjustment. Any secure
maintained in accordance with NFPA 25. Do not clean engagement between the cover plate and the cup will
sprinklers with soap and water, ammonia or any other assure that the drop-down deflector is properly located
cleaning fluids. Remove dust by using a soft brush or gen- below the ceiling. A plastic protective cap shall be
tle vacuuming. Remove any sprinkler cover plate assem- provided and factory installed inside the sprinkler cup
bly which has been painted (other than factory applied)or to protect the drop-down sprinkler deflector from dam-
damaged in any way. A stock of spare sprinklers should age, which could occur during construction before the
be maintained to allow quick replacement of damaged or cover plate is installed. Standard cover finish: [Chrome]
operated sprinklers. Prior to installation, sprinklers should [White] [Specialty—specify]. Residential concealed
be maintained in the original cartons and packaging until sprinklers shall be Reliable Model RFC30, SIN RA0611
used to minimize the potential for damage to sprinklers (Bulletin 006), Model RFC43, SIN FiA0612 (Bulletin 006)
that would cause improper operation or non-operation. or Model RFC49, SIN RA0616 (Bulletin 006).
Model RFC30, RFC43 and RFC49 Residential Ordering Information Cover Plate Finishes�'�
SpeCify: Standard Finishes
Concealed Sprinkler Specification 1. Sprinkler Model
S rinklers shall be cULus Listed low flow residential con- 2. Cover Plate Finish Chrome
cealed sprinklers with drop-down deflector and adjust- 3. Thread-On or White
able flat cover plate engineered for a minimum design Push-On Feature Special Application
density of 0.05 gpm/ftz. Sprinkler frame and deflector Finishes
shall be of bronze frame construction having a'/2" NPT Bright Brass
thread. Thermal element shall consist of an approved Black Plating
black- ainted ber Ilium-nickel fusible solder link with Black Paint
p y Off White
symmetric lever mechanism, maintaining a Teflon-coated Satin Chrome
Belleville spring washer and machined brass cap water �'�Other colors and finishes avail-
seal assembly containing no plastic parts. Sprinkler able. Consult factory for details.
K-factor shall be nominal 3.0 (44), 4.3 (62.4), and 4.91 Note: Paint or any other coatings
5 � 3 � applied over the factory finish will
(70) having a /,6', /$" and /,6" orifice. Temperature rating void all approvals and warran-
shall be Ordinary 165°F(74°C); cover plate temperature ties.
rating to be 135°F(57°C). Cover plate assembly shall
�' x �/2'� REOUaNc
r�E� orz E�r�ow I
��—�--��__ –
------- --"," --- —
--��� t �,�— -
_ g°[66.55mm� ����
s,� � � ,�o�E,N ��,,.,N� � ��
_�� (58.42mm� 0/A � �
CUP — �
i
2°(50.8rnm] MAX. �
FP.CE OF F177/NG �
�������,� TO FACE OF CEILING
� ������� DlMtNSION
�������
iiiii.i,
iiiiiii�
CE/L/NG � iiiiiii �
2°(12JOmm]MAX. I ��
COVER ADJUS7MEN7 �"(4.96mm] �����
CCP COVER PLATE �°(8427mm] D/A_
ASSEME3L Y
SPRINKLER ooeFCOia
COI/ER PL�TE: 1/2„ �12.7mm� %DJUSTMEIVT
3.
Rel iable . . . For Com lete Protect I O n
p
Reliable offers a wide selection of sprinkler components. Following are some of the many
precision-made Reliable products that guard life and property from fire around the clock.
• Automatic sprinklers • Deluge valves
• Flush automatic sprinklers • Detector check valves
• Recessed automatic sprinklers • Check valves
• Concealed automatic sprinklers • Electrical system
• Adjustable automatic sprinklers • Sprinkler emergency cabinets
• Dry automatic sprinklers • Sprinkler wrenches
• Intermediate level sprinklers • Sprinkler escutcheons and guards
• Open sprinklers • Inspectors test connections
• Spray nozzles • Sight drains
• Alarm valves • Ball drips and drum drips
• Retarding chambers • Control valve seals
• Dry pipe valves • Air maintenance devices
• Accelerators for dry pipe valves • Air compressors
• Mechanical sprinkler alarms • Pressure gaugesldentification signs
• Electrical sprinkler alarm switches • Fire department connection
• Water flow detectors
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association,Factory
Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Productsmanufactured and distributed by Reliable have been protecting life and property for over 90 years,and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States,Canada and foreign countries.
Manufactured by
The Reliable Automatic Sprinkler Co., Inc. � Recyclea
� Q (800)431-1588 Sales Offices Paper
� '� � (800)848-6051 Sales Fax Revision lines indicate updated or new data.
(914)829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address EG.Pr�r,tea�r,u.s.A o2/11 P/N 9gsss�o2si
Bulletin 176�e�A
�
� Model F1 �
Residential Sprinklers for �
Design Density of .10 gpm/ft2 �
D
Model F1 Res Sprinklers engineered for the lowest flows
to meet the minimum design density of.05 gpm/f�
Types: � �, •
1. F1 Res 49 Pendent - �`�'' .� ;J' "�'��
2. F1 Res 49 Recessed Pendent/F1 � �`-�,,. ��F,��
3. F1 Res 49 Recessed Pendent/FP �'"`-_��.
4. F1 Res 49 CCP Pendent -
5. F1 Res 58 Pendent F1 Res 49,58&76 F1 Res 49,58&76
6. F1 Res 58 Recessed Pendent/F1 Recessed Pendent/F1 Recessed Pendent/FP
7. F1 Res 58 Recessed Pendent/FP
8. F1 Res 58 CCP Pendent
9. F1 Res 44 & 58 HSW `
10. F1 Res 44 & 58 HSW Recessed HSW/F2 °r1�i
11. F1 Res 44 SWC �"���-��
12. F1 Res 76 Pendent ��f a ; �
13. F1 Res 76 Recessed Pendent/F1
14. F1 Res 76 Recessed Pendent/FP
15. F1 Res 76 CCP Pendent F1 Res 49, 58&76 F1 Res 44&58
CCP Pendent Recessed HSW/F2
Listings &Approvals
1. Listed by Underwriters Laboratories Inc. and �
UL Certified for Canada (cULus) . �
I 2. NYC MEA 258-93-E �
UL Listing Category
Residential Automatic Sprinkler -
UL Guide Number
VKKW F1 Res 44 SWC
Patents
US Patent No. 6,516,893 applies to the
Model F1 Res 49 & 58 Pendent Sprinklers
Product Description Technical Data:
Model F1 Res Pendent sprinklers (Figs. 1, 2, 3 & 4) • Thermal Sensor: Nominal 3mm glass-bulb
combine excellent durability, high sensitivity glass-bulb • Sprinkler Frame : Brass Casting
and low profile decorative design. • Sprinklers' Pressure Rating : 175 psi
The 3mm glass-bulb pendent sprinklers permit the Factory Hydrostatically Tested to 500 psi
efficient use of residential water supplies for sprinkler • Thread Size: '/2" NPT(R1/2)
coverage in residential fire protection design. • K�actor.4.9(Acival)-F1 Fies 49 Pender�t Spnnlder
The low flow F1 Res sprinklers are specially 5.8(F�tual)-F1 Res58Pendent&HSWSpnnl�der
engineered for fast thermal response to meet the 7.6(Actual)-F1 Res 76 Pendent Sprinkler
sensitive fire protection application needs of the latest 4.4(Actual)-F1 Res 44 HSW Sprinkler i
residential market standards (UL 1626 Standard *). • Density: Minimum 0.10 gpm/ft2
Upon fire conditions, rising heat causes a sprinkler's
heat-sensitive glass-bulb to shatter, releasing the
waterway for water flow onto the deflector, evenly
distributing the discharged water to control a fire.
* Effective date 7/12/02 I
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Application
Model F1 Res Sprinklers are used for Residential Fire Example No. 1
Protection according to UL 1626 Standard*. Be sure Room Size= 12 ft x 20 ft (3.6 m x 6.1 m)
that orifice size, temperature rating, deflector style and Coverage Area= 12 x 20 = 240 ft2(22.3 m2)
sprinkler type are in accordance with the latest Flow @ 0.10 gpm/ft2 density= 240 x 0.10 = 24 gpm
published standards of The National Fire Protection Using an F1 Res 49 Pendent Sprinkler, K=4.9
Association or the approving authority having Pressure- (24/4.9)2 = 24 psi (1.65 bar)
jurisdiction. The baseline flow for a 20 ft x 20 ft (6.1 m x 6.1 m)
When using F1 Residential Sprinklers for systems covera2qe area using the baseline density of 0.05
design to NFPA 13D or NFPA 13R, use listed area of gpm/ft will be 20 gpm C� 16.7 psi (75.7 L/min C� 1.14
coverage and minimum flow and pressure requirements bar). Therefore,the minimum flow required is 24 gpm @
shown in Bulletin 135. 24 psi (90.8 L/min C� 1.65 bar).
For systems designed to NFPA 13, use information in
this bulletin.The number of design sprinklers shall be the Example No. 2
most hydraulically demanding sprinklers as required by Room Size- 8 ft x 20 ft (2.4 m x 6.1 m)
NFPA 13. Flows and pressures can not be below the - 2 2
baseline flows and pressurers. Coverage Area= 8 2 20 = 160 ft (14.9 m )
NFPA 13 Flow @ 0.10 gpm/ft density= 160 x 0.10 = 16 gpm
Using an F1 Res 49 Pendent Sprinkler, K=4.9
For residential sprinkler systems designed to NFPA 13, Pressure- (16/4.9)2 = 10.7 psi (0.74 bar)
a minimum density of 0.1 gpm/ft must be provided over The baseline flow for a 20 ft x 20 ft (6.1 m x 6.1 m)
the "design area" that includes the four(4) hydraulically covera2ge area using the baseline density of 0.05
most demanding sprinklers for the actual coverage gpm/ft will be 20 gpm C 16.7 psi (75.7 L/min C 1.14
areas being protected by the 4 sprinklers. The minimum bar). Therefore,the minimum flow required is 20 gpm @
required discharge from each of the four most 16.7 psi (75,7 L/min @ 1.14 bar).
hydraulically demanding sprinklers shall be the �reater
of the following:
1.The flow rates given in the Reliable Residential Example No. 3
Sprinkler Technical Bulletins referenced in Table A Room Size= 10 ft x 16 ft (3.0 m x 4.91 m)
for NFPA 13D and 13R as a function of temperature Coverage Area= 10 x 16 = 160 ft2(14.9 m2)
rating and maximum allowable coverage area (for Flow C 0.10 gpm/ft2 density= 160 x 0.10 = 16 gpm
actual coverage areas less than or between those Using an F1 Res 76 Pendent Sprinkler, K=7.6
indicated in the respective technical bulletin, it is The baseline flow for a 16 ft x 16 ft coverage area is 21
required to use the minimum required flow for the gpm @ 7.6 psi (79.5 L/min @ 0.52 bar). Therefore, the
next largest coverage area); or minimum flow and pressure is 21 gpm @ 7.6 psi (79.5
2.A minimum discharge density of 0.1 gpm/ft2 L/min @ 0.52 bar).
applied over the"design area"consisting of the four
most hydraulically demanding sprinklers for the Example No. 4
actual coverage areas being protected by the four Room Size- 14 ft x 18 ft (4.3 m x 5.5 m)
sprinklers. The maximum dimension of the actual Coverage Area- 14 x 18 - 252 ft2(23.6 m2)
coverage area cannot be any greater than the 2
maximum coverage area indicated in the technical Flow @ 0.10 gpm/ft density= 252 x 0.10 = 25.2 gpm
bulletins referenced in Table A. (94.6 L/min)
Design Note: Using the AS - S x L method to Using an F1 Res 76 Pendent Sprinkler, K=7.6
determine the sprinkler protection area of coverag Pressure= (252/7.6) = 11 psi (0.76 bar)
in accordance with NFPA 13, apply the 0.1 gpm/ft� The baseline flow and pressure of an 18 ft x 18 ft
density to this area to determine the minimum coverage area is 21 gpm @ 7.6 psi (79.5 L/min @ 0.52
required flow. Compare this flow to the minimum bar). Therefore, the minimum flow and pressure is 25.2
0.05 gpm/ft2 cULus Listed flow for the appropriate gpm @ 11 psi (94.6 L/min C� 0.76 bar).
coverage area in the technical bulletin for the
specific residential sprinkler. If the flow stated in the In general residential sprinklers req uire
technical bulletin is less than the calculated 0.1 flows and pressures as listed for D.05
gpm/ft2 density flow required, the .1 d�nsity flow densities to achieve the proper spray pattern
must then be used in the equation Q=K�/P, solving so the flows and pressures at 0.05 density are
for P, to establish the minimum required pressure the baseline flows and pressures. Flows and
using the sprinkler K-factor. Note: In many cases pressures below the listed 0.05 denSity shall
the listed flow of individual residential sprinklers� not be used.
may exceed the required minimum 0.05 gpm/ft
density. Reliable has available residential sprinklers
with larger K-factors (K=5.8 and K=7.6) that will
provide lower pressure demands for 0.1 gpm/ft2
densities in NFPA 13 residential applications.
2.
Installation
Models F1 Res sprinklers are to be installed as use only the Model GFR2 Sprinkler wrench. Use of
shown. Model F1, F2 and FP Escutcheons, illustrated wrenches other than those specified may damage
herewith,are the only recessed escutcheons to be used these sprinklers.
with Model F1 Res sprinklers. Use of any other Note:A`leak tight"sprinkler joint can be obtained with
recessed escutcheon will void all approvals and the following torque:
warranties. For installing Model F1 Res Pendent • 3/4" NPT (R3/4)— 14-20 ft-Ibs (19 - 27.1 N-m)
sprinklers use only the Model D sprinkler Wrench; for . '/2" NPT (R1/2)—8-18 ft-Ibs (10.8—24.4 N-m)
installing Models F1 Res Recessed Pendent, CCP Do not tighten sprinklers over maximum
sprinklers use only the Model GFR2 sprinkler wrench; recommended torque. It may cause leakage or
for installing Model F1 Res recessed HSW sprinklers impairment of the sprinklers.
• Model F1 Res 49, 58 & 76
• Model F1 Res 49, 58 & 76 Pendent Recessed Pendent/ F1/F2
-�::
�����
,,�� `. � ' '���'��
:. ''� � ;�►
� ��
_ �� � _
� , / 1�'
��`� �_ .��_ -
=_� �,.�� .--_
__y v �„
F1 escutcheon, /" (19mm) adjustment
Note: See escutcheon table for dimensions.
z,i4-���o�c o,�_
�s�zmm�
� � � '�;9zmm�A.
— _�— _
_ = =_ � � �
— �— - � �I: � _
I � t �9"X I/2"RFOUCEF
I NRN COLWR UIJIIL I
TIGHi AG//NST SPRINKLER
WRENCN BO55 � 'I �
FACE PF FITTING i0
� CEILING DIMENSIOfJ�
�p��j� s/i 6—�5/>s(F�escurcHFON)
��� .s/�o—>r/>6(F2 escurcvFON)
O�SV� ao�usrMeNr ���°��
_i-- �,
I �
r/a,.
� [3.em.,�)
q,.
I
�
135FG03 i35tco2,a ��'�32 D1A�
[�zan,n]
Fig. 1 Fig. 2
3.
Technical Data: F1 Res 49 Pendent and Recessed Pendent
Escutcheon�, F1 or F2, Data:
Nominal Sprinkler Max. M� Actual Sprinkler Adjustment <<q�� Face of fitting to
Thread Orifice Temp. p��u� Ambient K Length Type Inch(mm) Inch(mm) ceiling
Size Inch Ratin �i Tem . Inch Inch mm
Factor
(mm) �F �C (bar) �F �C (mm) 3 Min.=3�n� (19.1) 3 ,5
F1 /,(19.0) /e- /s(Q.7-24.0)
Max.=1'�:"�38.1)
%"NPT ����(11) 155 68 175(12) 100 38 4.9 2.25(57) ,;,�„
(R%) 175 79 150 66 F2 % (12.7) Min.= ,6 (23.8) / _,� (4.7- 17.4)
� Max.=1%"(38.1) 16 ,s
*Note: Escutcheons F1 or F2 may be used with
Model F1 Res 49&58 Recessed Pendent Sprinkler
**Baseline flows and pressures for 0.05 density
Deflector-to-ceiling *Deflector-to-ceiling
Maximum 1" (25mm)to 4" (100mm) Ma�cimum 4" (100mm)to 8" (203mm)
Max. Sprinkler Sprinkler Max. Sprinkler Sprinkler
Flow Pressure Flow Pressure
Spacing m L m si bar ldentification Spacing m L m si bar ldentification
ft m gp � p � p � � Number SIN ft m gp � p � p � � Number SIN
i 12 x 12(3.6x3.6) 13(49) 7.0(0.48) 12 x 12(3.6x3.6) 15(57) 9.4 (0.65)
I 14 x 14(4.3x4.3) 13(49� 7.0(0.48� 14 x 14(4.3x4.3) 16(60.5) 10.6(0.73)
16 x 16(4.9x4.9) 13(49) 7.0(0.48) R3516 16 x 16(4.9x4.9) 17(64.3) 12.0(0.83) R3516
18 x 18(5.5x5.5) 17(64.3) 12.0(0.83) 18 x 18(5.5x5.5) 19(72) _ 15.0(1.0)
I 20 x 20(6.1x6.1) 20(75.7) 167(1.14) 20 x 20(6.1x6.1) 22(83.2) 20.2(1.4)
*Note: The F1 Res 49 pendent and recessed pendent
residential sprinklers can be installed per NFPA 13 in
beamed ceilings meeting the following criteria:
1. Maximum beam depth = 7" (178mm)
2. Beam spacing at or greaterthan 7.5 ft.(2.3m)on center.
Technical Data: F1 Res 58 Pendent and Recessed Pendent
Nominal Sprinkler M�, Max. Sprinkler
Thread Orifice Temp. Pressure �bient K Length
Size Inch Ratin pSi Temp. Factor Inch
(mm) °F °C (bar) �F �� (mm)
'/z'NPT /���13� 155 68 175(12) 100 38 5.8 2.25(57)
(RYz) 175 79 150 66
**Baseline flows and pressures for 0.05 density
Max. Sprinkler Flow Pressure Ceiling-ta Sprinkler
Spacing Deflector ldentification
ft m JPm(Lpm) psi(bar) Inch mm Number SIN
12 x 12(3.6x3.6) 16(61) 7.6(0.53) I
14 x 14(4.3x4.3) 16(61) 7.6(0.53) I
16 x 16(4.9x4.9) 16(61) 7.6(0.53) �25- 00) R3513
18 x 18(5.5x5.5) 19(72) 10.8(0.75)
20 x 20(6.1x6.1) 22(83.3) 14.4(1.0) I
**Calculate for a.10 density but in no case
go below the baseline flows & pressures
4.
Technical Data: F1 Res 76 Pendent and Recessed Pendent
Nominal �n�' M�c. � Sprin{der-
Thread Orifice T� Press�.re �� K Ler�glh
Size Inch � psi T Fac.tor Irxh
(mm) �F �� (bar) �F �� (mm)
%"NPT „ 155 68 100 38 Adjustment °°q°° Face offitting to
�R34� /2"(13.5) 175 79 175(12) 150 66 �6 2.25(57) Type Inch(mm) Inch(mm) �iling
* F� %(i9.o) MaX % (sa�.i� .
Inch�mm)
Baseline flows and pressures for 0.05 density , -- 3i6-'i6�4.7-24.0)
F2 %(12J) Min.='%6"(23.8) %g-'%s(4.7-17.4)
Max.Sprinkler Sprinkler Max.=1y��(38.1)
Flow Pressure
Spacing Identification
ft m 9pm(Lpm) psi(bar) Number SIN
12 x 12(3.6x3.6) 21 7.6(0.53)
I 14 x 14(4.3x4.3) _ 21 7.6(0.53)
16 x 16(4.9x4.9) 21 7.6(0.53) R7618 *Calculate for a .10 density but in no case
18 x 18(5.5x5.5) 21 7.6(0.53) go below the baseline flows & pressures
I 20 x 20(6.1 x6.1) I 23 _ 9.2(0.63)
• Model F1 Res 49, 58 & 76 • Model F1 Res 49, 58 & 76
CCP Pendent Recessed Pendent/ FP
, -- - -
-. „.___
r.i1. ��@�L—���,.�o". .
� �'f ,I
�i � � � :
, �
.� �
FP push-on/thread-off
escutcheon
2 5/8°(66Jmm� 0/!J. 2 5/a"oia.[ae.�mmJ
HOLE IN CEILING
2 5/is" niA. rfo�E iN rciuNc
�58Jmm� z s/re"oia.
GUP ---�---� l5a.�mmJ
___"._}"�� .'"! / CUP
,,;_.�....�<_____"�__, I � �
�`� ;' � 1'x 1/2'" REDUCER I= _=———I
. ........._....__: ----
Technical Data: F1 Res 49 CCP Pendent and Recessed Pendent / FP
- CCP Options Data:
Nominal ��d�' � M�c. � nlde�- "A" "B"
Thread OrfiCe Temp. � p�,�� Ambiei�t F( � CoverAdjustment CCP Height
Size Inch ��J � psi T� Factor Irich Inch mm Inch mm
(mm) �� �� �� "g (bar) � oF � o� � (mm) %(12.7) '%(24)
1iz��NPT , ,� � z.z5 %(4.�) � %(19)
����?� /6 (11) 155 68 135 57 175(12) 100 38 4.9 �57�
*Baseline flows and pressures for 0.05 density FP Data "A":
Max.Sprinkler Sprinkler FP Position ��A��
Flow Pressure Inch mm
Spacing Identification ( ) -
ft m 9pm(Lpm) psi(bar) Number SIN Max. Recessed �16(11)
12 x 12(3.6x3.6) 13(49) 7.0(0.48) Min. Recessed 'S/16(24)
14 x 14(4.3x4.3) 13(49) 7.0(0.48) Note: Sprinklers shown in Fig. 3 and Fig. 4 are not
16 x 16(4.9x4.9) 14(53) 8.2(0.56) R3516 suitable for installation in ceilings which have
18 x 18(5.5x5.5) 18(68.1) 13.5(0.93) positive pressure in the space above.
20 x 20(6.1 x6.1) 20(75.7) 16.7(1.14)
Technical Data: F1 Res 58 CCP Pendent and Recessed Pendent/FP
Nominal ��' � Max. � Sprinlde�-
Thread Orifice T� � Pressure �rt K Lerx,�U�
Size Inch ��J � psi T�p• Facbor Uich
(mm) oF o� oF o� (bar) oF o� ��)
�R�2� Y2"(13) 155 68 135 57 175(12) 100 38 5.8 2.25(57)
*Baseline flows and pressures for 0.05 density
Max.Sprinkler Sprinkler
Flow Pressure
Spacing Identification
ft m 9pm(Lpm) psi(bar) Number SIN
12 x 12(3.6x3.6) 16(61) 7.6(0.53)
14 x 14(4.3x4.3) 16(61) 7.6(0.53)
16 x 16(4.9x4.9) 16(61) 7.6(0.53) R3513
18 x 18(5.5x5.5) 19(72) 10.8(0.75)
20 x 20(6.1x6.1) 22(83.3) 14.4(1.0)
Technical Data: F1 Res 76 CCP Pendent and Recessed Pendent/FP
Nominal �n�d�' �� M�c. � Spririlder
Thread Orifice T� T Pre�are �rt K Lengtl�
Size Inch ��J �' psi T�p• Facton c�h
�mm) oF o� oF o� � oF o� ��)
3/4'NPT �%z" 155 68 135 57 175(12) 100 38 �6 2.25
(R3/4) (13.5) 175 79 150 66 (57)
*Baseline flows and pressures for 0.05 density
Max.Sprinkler Sprinkler
Flow Pressure
Spacing Identification
ft m 9pm(Lpm) psi(bar) Number SIN
12 x 12(3.6x3.6) 21 7.6(0.53)
14 x 14(4.3x4.3) 21 7.6(0.53)
16 x 16(4.9x4.9) 21 7.6(0.53) R7618 *Calculate for a .10 density but in no case
18 x 18(5.5x5.5) 22 8.4(0.58)
go below the baseline flows & pressures
20 x 20(6.1 x6.1) 25 10.8(0.74)
6.
• Model F1 Res 44 & 58 HSW • Model F1 Res 44 & 58
Recessed HSW/F2
_ _.�-�, �1 i� C`�.��
���. .. .fi� V���,� I ���, ,y. �
� ;�� 4�� '� '�J
'' - � �, a.
�:�.. ;
,�` , �
F2 escutcheon, /" (13mm)
adjustment
Technical Data: F1 Res 44 HSW & HSW/F2
Escutcheon, F2, Data:
Nominal �n� Max. � Sprinkler Adjustment Face of Fitting
Thr�d Orifice T� Pressi.re a�'rt K L�englh Ty� Inch mm to wall
Sme Inch ��J psi T�'�p• Facbor Inch � � Inch mm
(mm) � � (bar) � � � (mm) F2 %_(13) _�s-"/,6(4.7-17.4)
'/z'NPT /���10� 155 68 175(12) 100 38 4.4 2.45(62)
(Rh) 175 , 79 150 66
*Baseline flows and pressures for 0.05 density
<<A„
Mau.Sprinkler Ceiling-ta SprinklerTemp. Flow pressure Sprinkler
Spacing Deflector Rating 9pm psi(bar) Identification
��m� Inch mm F( C) (Lpm) Number(SIN)
12 x 12(3.6x3.6) 155(68) 175(79) 12(45.4) 7.5(0.52)
14 x 14(4.3x4.3) 155(68) 175(79) 14(53.0) 10.2(0.71)
16 x 16(4.9x4.9) 4_g 155(68) 175(79) 16(60.6) 13.3(0.92)
16 x 18(4.9x5.5� (101-152) 155(68) 175(79� 18(68.1) 16.8(1.16)
18 x 18(5.5x5.5) 155(68) 175(79) 19(72.0) 18.7(1.29)
16 x 20(4.9x6.1) 155(68) 175(79) 23(87.1) 27.4(1.89) R3531
I 12 x 12(3.6x3.6) 155(68) 175(79) 14(53.0) 10.2(0.71)
14 x 14(4.3x4.3) 155(68) 175(79) 16(60.6) 13.3(0.92)
� 16 x 16(4.9x4.9) 6-12 155(68) 175(79) 17(64.4) 15.0(1.04)
(152-305)
16 x 18(4,9x5.5) 155�68) � 175(79) 20(75.7) 20.7(1.43)
I 16 x 20(4,9x6.1) � , 155(68) 175(79) 23(87.1) 27.4(1.89)
*Calculate for a .10 density but in no case
go below the baseline flows& pressures
7.
• Model F1 Res 44 SWC
�
4"to 12•,
� [701.60mm 70
� 1 7/4"'(37.75mm)Mox�mum 304.80mmJ
Fa[e 0/Fiffing PUSH ON COVER, THEN
7o Woll D�mens�on TURN TO ADJUST UNTIL
� �� �� TIGHT AGAINSr WALL.
� r' 1"X i/2'"Reducer i
` �
Recommended �1 ii' `�
� Woll Hole 2 5/16" � �
z s/a• [ss.�a,,,,�,)�I � _ _ -�--
[66.68mmJ DIO. 3 5/16"
i , (84.14mmJ
Dia. `Iiii�----
`�. I ; "� � � Dla.
� i r�l
I
TURN COLLAR UNTIL
TIGNT AGAlNST SPRINKLER � z��32..
WRENCH BOSS. `J
(42.07mm)
]35FGOl -� 1�2���12.70mm�
Adjustment
F1 RES 44 SWC
Fig. 5
Technical Data: F1 Res 44 SWC
Nominal ��' �.T� Max. � Sprir�lder
Thread Orifice T�p• Raati �� Arrd�ientT K �
Sme Inch � � psi �� Facfion c�h
(mm) � � � � (bar) � � (mm)
���RN�T �"(10) 155 68 135 57 175(12) 100 38 4.4 2.45(62)
*Baseline flows and pressures for 0.05 density
Mau.Sprinkler A�� Flow Sprinkler
Spacing Ceiling-to- gpm Pressure �dentification
��m� Deflector ��pm� psi(bar) Number(SIN)
Inch mm
12 x 12(3.6x3.6) 13(49.2) 8.7(0.60)
14 x 14 4.3x4.3 14 53.0 10.2 0.71
16 x 16�4.9x4.9) (101-1�52) 17(64.3) 15.0(1.1)
16 x 18(4.9x5.5) 19(71.8) 18.7(1.13)
16 x 20(4.9x6.1) 23(87.1) 27.4(1.89) R3531
12 x 12(3.6x3.6) 14(52.9) 10.2(0.71)
14 x 14(4.3x4.3) 6-12 15(56.7) 11.7(0.81)
16 x 16(4.9x4.9) (152-305) 18(68.1) 16.8(1.16)
16 x 18(4.9x5.5) 20(75.6) 20.7(1.43)
*Calculate for a .10 density but in no case
go below the baseline flows & pressures
8.
Technical Data: F1 Res 58 HSW & HSW/F2
Escutcheon, F2, Data:
Nominal Sprinkler Max. M�• Sprinkler Adjustment Face of Fitting
Thread Orifice Temp. pressure �bient K Length Ty� Inch mm to wall
Size Inch Ratin psi Tem . Factor Inch � � Inch mm
(mm) �F �C (bar) �F �C (mm) F2 %(13) %s-'%s(4.7-17.4)
'/z'NPT /���13) 155 68 175(12) 100 38 5.8 2.45(62)
(R/z) 175 79 150 66
*Baseline flows and pressures for 0.05 density
Mau.Sprinkler ��'4�� SprinklerTemp. Flow Sprinkler
Spacing Ceiling-ta Rating gpm P�ssure Identification
��m� Deflector �F(°C) (Lpm) psi(bar) Number(SIN)
Inch mm
12 x 12(3.6x3.6) 155(68) 175(79) 16(60.6) 7.6(0.53)
14 x 14(4.3x4.3) 155(68) 175(79) 18(68.2� 9.7(0.67)
16 x 16(4.9x4.9) (101-1�52) 155(68) 175(79) 21 (79.5) 13.2(0.91)
16 x 18(4.9x5.5) 155(68) 175(79) 25(94.7) 18.6(1.28)
16 x 20(4.9x6.1) 155(68) 175(79) 29(109.8) 25(1.73) R3533
12 x 12(3.6x3.6) 155(68) 175(79) 22(83.3) 14.4(1.0)
14 x 14(4.3x4.3) 6_12 155(68) 175(79) 22(83.3) 14.4(1.0)
16 x 16(4.9x4.9) (152-305) 155(68) 175 79 26 98.4 20.1 (1.39
16 x 18(4.9x5.5) 155(68) I 175(79) 31 (117.4) 28.6(1.97)
*Calculate for a .10 density but in no case
go below the baseline flows& pressures
Finishes�'�
Standard Finishes Ordering Information
Specify:
S rinkler F1, F2, FP Escutcheons 1. Sprinkler Model
Bronze Brass
Chrome Plated Bright Chrome Plated 2. Sprinkler Type
White Polyester Coated White Painted 3. Temperature Rating
_ _ Special Application Finishes 4. Sprinkler Finish
S rinkler F1, F2, Escutcheons
Bright Brass Bright Brass 5. Escutcheon Finish
Black Plated Black Plated
Black Paint Black Paint
Off White Off White
Satin Chrome Satin Chrome
"'Other finishes and colors are available on special order.
Consult factory for details.
9.
Maintenance
Model F1 Res 49, F1 Res 58 & F1 Res 76 Sprinklers Model F1 Res 49 & 58 Recessed Pendent/F1,
should be inspected quarterly, and the sprinkler system Model F1 Res 49 & 58 Recessed Pendent/F2,
maintained in accordance with NFPA 25, 13, 13D, and Model F1 Res 49 & 58 Recessed Pendent/FP
13R. Do not clean sprinkler with soap and water,Ammonia Sprinklers shall be [cULus Listed] [New York City MEA
or any other cleaning fluids. Remove dust by using a soft Approved (258-93-E)] low flow residential recessed
brush or gentle vacuuming. Remove any sprinkler which pendent sprinklers engine red to provide a minimum
has been painted(other than factory applied)or damaged design densiry of 0.10 gpm/ft�over the listed coverage area.
in any way. A stock of spare sprinklers should be Listed flows as specified by the manufacturer's technical
maintained to allow quick replacement of damaged or data sheets are to be used. Residential sprinklers shall be
operated sprinklers. Prior to installation, sprinklers should installed in conformance with the manufacturer's installation
remain in the original cartons and packaging until used. guidelines and the applicable installation standard. Where
This will minimize the potential for damage to sprinklers that pendent residential sprinklers are installed under sloped
could cause improper operation or non-operation. ceilings having a pitch of up to [4/12] [8/12], the sprinklers
shall be listed for such use. Deflector-to-ceiling distance
listing shall be 1" to 8" maximum. Sprinkler frame and
Model F1 RES 49 Residential deflector shall be of bronze frame construction having a'h"
Sprinkler Specifications NPT thread. Water seal assembly shall consist of a
Teflon-coated Belleville spring washer and top-loaded
extruded cup with 3 mm glass bulb containing no plastic
Model F1 Res 49 & 58 Pendent parts, and having a temperature rating of [155°F (68°C)]
Sprinklers shall be [cULus Listed] [New York City MEA L175°F(79°C)]. Sprinklers shall have a nominal K-factor of
Approved (258-93-E)] low flow residential pendent 4.9 (70). Standard finish: [Bronze] [Chrome-plated] [White
sprinklers engineered to provide a minimum design Polyester] [Special finish—specify]. Recessed escutcheon
I density of 0.10 gpm/ft2 over the listed coverage area. assembly shall be a steel, two-piece escutcheon [with '/2"
Listed flows as specified by the manufacturer's technical adjustment(Model F2)] [with 3/4" adjustment(Model F1)] [of
data sheets are to be used. Residential sprinklers shall be push-on and thread off design with '/2" adjustment (Model
installed in conformance with the manufacturer's FP)]. Standard finish shall be [brass][bright chrome] [white
installation guidelines and the applicable installation painted]. Residential recessed pendent sprinklers shall be
standard. Where pendent residential sprinklers are Reliable [Model F1 Res 49 & 58 Recessed Pendent/F1]
installed under sloped ceilings having a pitch of up to[4/12] [Model F1 Res 49 & 58 Recessed Pendent/F2] [Model F1
[8/12], the sprinklers shall be listed for such use. Res 49 & 58 Recessed Pendent/FP] SIN R3516 & R3513
Deflector-to-ceiling distance listing shall be 1" to 8" (Bulletin 135).
maximum.Sprinkler frame and deflector shall be of bronze Model F1 Res 49&58 CCP Pendent(Concealed)
frame construction having a '/z" NPT thread. Water seal Sprinklers shall be[cULus Listed] [New York City MEA
assembly shall consist of a Teflon-coated Belleville spring A roved 258-93-E low flow residential concealed
washer and top-loaded extruded cup with 3 mm glass bulb sprp klers engineere)d to provide a minimum design
containing no plastic parts, and having a temperature density of 0.10 gpm/ft2 over the listed coverage area. I
rating of [155°F (68°C)] [175°F (79°C)]. Sprinklers shall Listed flows as specified by the manufacturer's technical
have a nominal K-factor of 4.9 & 5.8. Standard finish: data sheets are to be used. Residential sprinklers shall
[Bronze][Chrome-plated][White Polyester][Special finish— be installed in conformance with the manufacturer's
specify]. Residential pendent sprinklers shall be Reliable installation guidelines and the applicable installation
Model F1 Res 49&58,SIN R3516&R3513(Bulletin 135). standard. Where pendent residential sprinklers are
installed under sloped ceilings having a pitch of up to
[4/12] [8/12], the sprinklers shall be listed for such use.
Sprinkler frame and deflector shall be of bronze frame
construction having a '/2" NPT thread. Water seal
assembly shall consist of a Teflon-coated Belleville
spring washer and top-loaded extruded cup with 3 mm
glass bulb containing no plastic parts, and having a
temperature rating of 155°F (68°C). Cover plate
assembly shall consist of a brass cover plate and copper
alloy retainer flange. Method of attaching the cover plate
to the sprinkler cup shall be a push-on and thread-off
design allowing a '/2" cover plate adjustment. Cover
plate temperature rating shall be 135°F(57°C). A plastic
protective cap shall be provided and factory installed
inside the sprinkler cup to protect the sprinkler from
damage, which could occur during construction before
the cover plate is installed. Standard cover plate finish:
[White] [Custom Color— specify]. ]. Concealed pendent
sprinklers shall be Reliable Model F1 Res 49 & 58 CCP,
SIN R3516 & R3513 (Bulletin 135).
10.
Model F1 Res 44 & 58 Horizontal Sidewall Model F1 Res 76 Recessed Pendent/F1,
Sprinkler Model F1 Res 76 Recessed Pendent/F2,
Sprinklers shall be [cULus Listed] [New York City MEA Model F1 Res 76 Recessed Pendent/FP
Approved (258-93-E)] low flow residential horizontal Sprinklers shall be [cULus Listed] low flow residential
sidewall sprinklers engineered to provide a minimum recessed pendent sprinklers engineere�d to provide a
I design density of 0.10 gpm/ft2 over the listed coverage minimum design density of 0.10 gpm/ft over the listed I
area. Listed flows as specified by the manufacturer's coverage area. Listed flows as specified by the
technical data sheets are to be used. Residential manufacturer's technical data sheets are to be used.
sprinklers shall be installed in conformance with the Residential sprinklers shall be installed in conformance
manufacturer's installation guidelines and the applicable with the manufacturer's installation guidelines and the
installation standard. Where horizontal sidewall applicable installation standard. Sprinkler frame and
residential sprinklers are installed under sloped ceilings deflector shall be of bronze frame construction having a
having a pitch of up to [4/12] [8/12], the sprinklers shall 3/4" NPT thread. Water seal assembly shall consist of a
be listed for such use. Sprinkler frame and deflector shall Teflon-coated Belleville spring washer and machined
be of bronze frame construction having a'/2" NPT thread. cup with 3 mm glass bulb containing no plastic parts,and
Water seal assembly shall consist of a Teflon-coated having a temperature rating of [155°F (68°C)] [175°F
Belleville spring washer and top-loaded extruded cup (79°C)]. Sprinklers shall have a nominal K-factor of 7.6.
with 3 mm glass bulb containing no plastic parts, and Standard finish: [Bronze] [Chrome-plated] [White
having a temperature rating of [155°F (68°C)] [175°F Polyester] [Special finish— specify]. Recessed
(79°C)]. Sprinklers shall have a nominal K-factor of 5.8. escutcheon assembly shall be a steel, two-piece
Standard finish: [Bronze] [Chrome-plated] [White escutcheon [with '/2" adjustment (Model F2)] [with 3/4"
Polyester] [Special finish—specify]. Residential horizontal adjustment(Model F1)] [of push-on and thread off design
sidewall sprinklers shall be Reliable Model F1 Res 58, with '/2" adjustment(Model FP)]. Standard finish shall be
SIN R3513 (Bulletin 135). [brass][bright chrome] [white painted]. Residential
recessed pendent sprinklers shall be Reliable [Model F1
Model F1 Res 44 & 58 Recessed Res 76 Recessed Pendent/F1] [Model F1 Res 76
Horizontal Sidewall S rinkler Recessed Pendent/F2] [Model F1 Res 76 Recessed
p Pendent/FP] SIN R7618 (Bulletin 135).
Use description for the Model F1 Res 58 horizontal
sidewall sprinkler with the following modifications:
Replace "horizontal sidewall sprinkler" with "recessed Model F1 Res 76 CCP Pendent (Concealed)
horizontal sprinkler." Add: Recessed escutcheon Sprinklers shall be [cULus Listed] low flow residential
assembly shall be a steel,two-piece escutcheon with'/2" concealed sprinklers engin�ered to provide a minimum
adjustment (Model F2). Standard finish shall be designdensityof0.10gpm/ft overthelistedcoveragearea. I
[brass][bright chrome] [white painted] [Special finish— Listed flows as specified by the manufacturer's technical
specify]. Residential recessed horizontal sidewall data sheets are to be used. Residential sprinklers shall be
sprinklers shall be Reliable Model F1 Res 58/F2, SIN installed in conformance with the manufacturer's installation
R3513 (Bulletin 135). guidelines and the applicable installation standard.
Sprinkler frame and deflector shall be of bronze frame
Model F1 Res 76 Pendent construction having a 3/4" NPT thread. Water seal assembly
Sprinklers shall be [cULus Listed] low flow residential shall consist of a Teflon-coated Belleville spring washer and
pendent sprinklers engine red to provide a minimum machined cup with 3 mm glass bulb containing no plastic
design density of 0.10 gpm/ft�over the listed coverage area. parts, and having a temperature rating of 155 F (68 C).
Listed flows as specified by the manufacturer's technical Cover plate assembly shall consist of a brass cover plate
data sheets are to be used. Residential sprinklers shall be and copper alloy retainer flange. Method of attaching the
installed in conformance with the manufacturer's installation cover plate to the sprinkler cup shall be a push-on and
guidelines and the applicable installation standard. thread-off design allowing a /2" cover plate adjustment.
Sprinkler frame and deflector shall be of bronze frame Cover plate temperature rating shall be 135°F (57°C). A
construction having a 3/4" NPT thread. Water seal assembly plastic protective cap shall be provided and factory installed
shall consist of a Teflon-coated Belleville spring washer and inside the sprinkler cup to protect the sprinkler from
machined cup with 3 mm glass bulb containing no plastic damage,which could occur during construction before the
parts, and having a temperature rating of [155°F (68°C)] �over plate is insta�lled�]tlndard cover plate finishp[White]
[175°F(79°C)]. Sprinklers shall have a nominal K-factor of Custom Color— s eci Concealed endent s rinklers
7.6. Standard finish: [Bronze] [Chrome-plated] [White shall be Reliable Model F1 Res 76 CCP,SIN R7618(Bulletin
Polyester] [Special finish— specify]. Residential pendent 135).
sprinklers shall be Reliable Model F1 Res 76, SIN R7618
(Bulletin 135).
11.
Reliable . . . For Complete Protection
Reliable offers a wide selection of sprinkler components. Following are some of the many
precision-made Reliable products that guard life and property from fire around the clock.
• Automatic sprinklers • Deluge valves
• Flush automatic sprinklers • Detector check valves
• Recessed automatic sprinklers • Check valves
• Concealed automatic sprinklers • Electrical system
• Adjustable automatic sprinklers • Sprinkler emergency cabinets
• Dry automatic sprinklers • Sprinkler wrenches
• Intermediate level sprinklers • Sprinkler escutcheons and guards
• Open sprinklers • Inspectors test connections
• Spray nozzles • Sight drains
• Alarm valves • Ball drips and drum drips
• Retarding chambers • Control valve seals
• Dry pipe valves • Air maintenance devices
• Accelerators for dry pipe valves • Air compressors
• Mechanical sprinkler alarms • Pressure gauges
• Electrical sprinkler alarm switches • Identification signs
• Water flow detectors • Fire department connection
The equipment presented In this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association,Factory Mutual Research
Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances,whenever applicable.
Products manufactured and distributed by RELIABLE have been protecting life and properry for over 80 years,and are installed and serviced by the most highly qualified and reputable
sprinkler contractors located throughout the United States,Canada and foreign countries.
Manufactured by
4 The Reliable Automatic Sprinkler Co., Inc.
(800)431-1588 Sales Offices Rec cled
� � (800)848-6051 Sales Fax �Paper
� (914)829-2042 Corporate Offices Revision lines indicate updated or new data.
www.rellablesprinkleccom Internet Address EG.Printed in U.S.A.05/08 P/N 9999970322
TABLE 2c. Dimensions and Physical Characteristics of Copper Tube:TYPE M
Nominal Dimensions, inches Calculatetl Values(based on nominal dimensions)
Nominal or Cross Weight Weight Contents of Tube
Standard Outsitle Inside Wall Sectional of Tube Only, ofTube&Water, per linear ft
Size,inches Diameter Diameter Thickness Area of Bore, pounds pounds Cu ft Gal
s inches perlinearft perlinearft
'/e .500 .450 .025 .159 .145 .214 .00110 .00826
'/z .625 .569 .028 .254 .204 .314 .00176 .0132
'/4 .875 .811 .032 .517 .328 .551 .00359 .0269
1 1.125 1.055 .035 .874 .465 .843 .00607 .0454
1'/4 1.375 1.291 .042 1.31 .682 1.25 .00910 .0681
1'/z 1.625 1.527 .049 1.83 .940 1.73 .0127 .0951
2 2.125 2.009 .058 3.17 1.46 2.83 .0220 .165
2'/� 2.625 2.495 .065 4.89 2.03 4.14 .0340 .254
3 3.125 2.981 .072 6.98 2.68 5.70 .0485 .363
3'/� 3.625 3.459 .083 9.40 3.58 7.64 .0653 .488
4 4.125 3.935 .095 12.2 4.66 9.83 .0847 .634
5 5.125 4.907 .109 18.9 6.66 14.8 .131 .982
6 6.125 5.881 .122 27.2 8.92 20.7 .189 1.41
8 8.125 7.785 .170 47.6 16.5 37.1 .331 2.47
10 10.125 9.701 .212 73.9 25.6 57.5 .513 3.84
12 12.125 11.617 .254 106 36.7 82.5 .736 5.51
TABLE 2d. Dimensions and Physical Characteristics of Copper Tube: DMV(Drain, Waste and Vent)
Nominal Dimensions,inches Calculatetl Values(based on nominal tlimensions)
Nominal or Cross Weight Weight Contents of Tube
Standartl Outside Inside Wall Sectional of Tube Only, of Tube&Water, per linear ft
Size,inches Diameter Diameter Thickness Area of Bore, pountls pounds
s inches perlinearft perlinearft Cuft Gal
1'/4 1.375 1.295 .040 1.32 .650 1.22 .00917 .0686
1'/� 1.625 1.541 .042 1.87 .809 1.62 .0130 .0971
2 2.125 2.041 .042 3.27 1.07 2.48 .0227 .170
3 3.125 3.030 .045 7.21 1.69 4.81 .0501 .375
4 4.125 4.009 .058 11.6 2.87 7.88 .0806 .603
5 5.125 4.981 .072 19.5 4.43 12.9 .135 1.01
6 6.125 5.959 .083 27.9 6.10 18.2 .194 1.45
8 8.125 7.907 .109 49.1 10.6 31.8 .341 2.55
22
TABLE 7. Pressure Loss in Fittings and Valves Expressed as Equivalent Length of Tube, feet
Nominal Fittings Valves
or Stantlartl EII 90°Tee Coupling
Standard Side Straight
Size, in g0° 45° Branch Run Ball Gate Btfly Check
3/a .5 - 1.5 - - - - - 1.5
Yz 1 .5 2 - - - - - 2
5/B 1.5 .5 2 - - - - - 2.5
3/4 2 .5 3 - - - - - 3
1 2.5 1 4.5 - - .5 - - 4.5
1'/4 3 1 5.5 .5 .5 .5 5.5
1'/z 4 1.5 7 .5 .5 .5 6.5
2 5.5 2 9 .5 .5 .5 .5 7.5 9
2'/z 7 2.5 12 .5 .5 - 1 10 11.5
3 9 3.5 15 1 1 - 1.5 15.5 14.5
3'/z 9 3.5 14 1 1 - 2 - 12.5
4 12.5 5 21 1 1 - 2 16 18.5
5 16 6 27 1.5 1.5 - 3 11.5 23.5
6 19 7 34 2 2 - 3.5 13.5 26.5
8 29 11 50 3 3 - 5 12.5 39
NOTES: Allowances are for streamlined solderetl fittings and recessed threaded fittings.
For threaded fittings,double the allowances shown in the table.
The equivalent lengths presented above are based upon a C factor of 150 in the Hazen-Williams
friction loss formula.The lengths shown are rountletl to the nearest half foot.
32
FIGURE 5. Selected Pressure Fittings
ADAPTERS
O �
O 0
FTGxM FTGxF CxC
Adapter Adapter Union
O
O �
O
� � O
C x M C x F C x C x F
Adapter Adapter Tee
ELBOWS
� �
O
O
O O �
C x C � x C C x C x C
45° Elbow 9Q° -1bow Tee
OO
OO
OO
z0
�O �O
FTG x C FTG x C C x FTG x C
a5° Elbow 90°Elbow Tee
COUPLINGS
OO
i0
CxC CxC CxC CxC
Roll Stop Staked Stop No Stop Reducing
GENERAL NOTES: (a) Fittings are designated by size in the order: 1x2x3(b) Fitting tlesigns antl drawings are for illustration only.
36
,�■► �!'' � " `' ii► �'�1'
� � �� � � � �
Schedule-10/Schedule-40 - ABFII
Submittal Data Sheet
� Fully Listed and FM Approved Sprinkler Pipe -� �
NPS Nominal I.D. Wt. Wt.(H20 Filled) CRR
When you specify Schedule-10/Schedule-40-ABFII sprinkler pipe from Allied Tube& �n;mm in;mm Lbs/Ft;kg/m Lbs/Ft;kg/m -
Conduit,you get UL listed and FM approved products.Although these products do not t" 1.049 1.680 z.o5 �
require separate approvals,Schedule-10/Schedule-40-ABFII gives you the extra quality 25 26.6 z.5 3.05 -
assurance you demand.Our Sch-10(1-1/4"-8") pipe and Sch-40(1"-2-1/2") pipe t�/4" 1.380 z.z�o 2.93 �
have passed the same thorough lab testing as our other listed pipe products,and receive 3z 35.1 4.36 4.36 -
periodic mill inspections from both UL and FM agents to ensure consistent quality. �'/z" 1.610 z.�zo 3.61 �
40 40.9 4.0 5.37 -
�' GaIVa111Z2C1 Plpe Schedule-10/Schedule-40-ABFII product can be "hot-dip" Z" z.o6� 3.650 5.13 �
galvanized to meet FM requirements. 50 52.5 5.4 7.63 -
2'/z" 2.469 5J90 7.86 1
� Superior Coating our advanced formula mill coating offers a clean,durable 65 6z.� a.6 11.73 -
surface that is also paintready for custom color applications without special preparation.
� .- .
The internal surface of all black Fire Sprinkler pipe up to 4.5000" in diameter shall be NPS Nominal I.D. .Wt. Wt.(H20 Filled) cRR
coated with Allied Tube &Conduit Antibacterial Formula "ABF". i,,;mm i,,;mm Lbs/Ft;kg/m Lbs/Ft;kg/m -
1'/4" 1.442 1.810 2.525 7.0955
! American MadeAb�e to meet"BuyAmerican" requirements,and is available 3z 36.6 z.7 3.75 -
through distributors in the USA, Canada, Mexico and Latin America. ��/�" �.6sz z.oso 3.04 5.6570
40 42.7 3.1 4.52 -
�' SpeCIflCat10115 & ApprOVaIS Schedule-10-ABFII pipe is in compliance Z�� z.�5� z.54o 4.zZ 4.5827
with ASTM A135,Type E Grade A, and NFPA 13.Schedule-40-ABFII pipe is in compliance 50 54.8 3.9 S.ZS -
with ASTM A135/A795,Type E Grade A,and NFPA 13. Both pipe products have a working Z��z^ 2.635 3.530 5.89 3.5196
pressure rating of 300 psi maximum and also meet the stringent requirement for the 65 66.9 5.3 s.77 -
following tests:Welded Outlets, Hydrostatic Pressure, Side Wall Rupture,Vibration Test. 3" 3.z6o 4.330 7.94 2.5550
75 82.8 6.4 11.82 -
4" 4.260 5.610 11.78 1.6020
100 108.2 8.3 17.53 -
5" 5.295 7.77 17.33 1.4874
125 134.5 11.56 25.80 -
6" 6.357 9.290 23.03 1.0251
150 161.5 13.8 34.27 -
8" 8.249 16.490 40.15 1.8365
200 209.5 24.5 59.75 -
�L c �L ��
�PPa�rEo
Project: Sprinkler Contractor: Date:
Engineer: Specification Reference: System Type:
Locations: Comments:
/���III�� Customer Service (800) 88Z-5543 Fax: (800) 659-7730 www.alliedtube-sprinkler.com
�T� • 16100 S Lathrop Ave. • 11350 Norcom Rd. •2525 N Z7th Ave. •600 Dean Sievers Place
TUBE & CONDUIT° Harvey,IL 60426 Philadelphia,PA 19154 Phoenix,AZ 85009 Morrisville,PA 19067
A PART O=�atkore
002011 Atkore International,Inc.All Rights Reserved. STP-S5-4-1111
�lTTI1V�S c��s�r ��+�rv
SU�IVIITTAL SHEET C99.1
! � ! �?r��isrr�rr n{.5far f i�e Prrxlrrrr.s
r N' -
-1-- ,
! ! � -
-",i�-� i
� -�--- � !��c�� �J� •��M r �- �- �
� , _ _ , �
� �JSTF.C1 tJSFU F�P�Rt?1£EG
t
� � � � � � i � • � � .
MC}MINAI. IT�f4A MA,X. d1MEh4SIQNS YNEIGHT NOMIMtiAL I7'EM MAX. DIAAEMSI�i�lS � IN��GHT
SIZE C�DE WO�I�KING ' EACH SIZE �CaDE Wt7RF{3NG EACH
(IhlGkl� # P.S.I. A B PiEC'� (INCHJ # R.S.I. A B PIEGE
1 GB9�DQ33 306 1.50 '[.50 0.95 1 CT333 3�0 1.5d 1.50 1.21
1114 CB9U444 30U 1.75 `1.75 1.34 1114 CT444 340 1.75 1.75 1.87
1112 �B9fl455 39U 1.94 1.9d '1.8D 1112 CT555 3QU 1.94 1.94 2.51
2 CS90fl86 30�} 2.25 2.25 Z.��U � C7fi68 3Q0 Z.25 �i.26 3.96
�,d
� �'
.�_��_.�I '�� ,
,,` �
, ��:.:-`
{
, ,
. � ' ! i � . � 1 ' : �
NC]MiNAL 17�M MIA7C. aIMEN5IL�N WEIGHT NO�VIINAL ITEM MAX. ❑IM�N51C7NS WEIG�4T
51ZE CQ�E WdRKING' EAGM SIZ� GO�]E WC]RKING �ACH
41NC4�� # P.5.1. A PIE�E (iNCHJ # P.S.I. A 6 PIECE
17C112 CFtC031 3D0 1.76 f}.52 1 �B45f133 3[!U 1.12 1.12 0.84
1X314 CFtC032 3fl0 1.7Q (1.84 11l4 CB45U44 3(�� 1.?9 '�.29 3.4i1
11f� C845fl5S 304 1.43 1.d3 1.$U
2 C�45�fifi 344 1.fi8 9.68 ?.79
f�! k f ._ '_�._
��-+ � �� A
� -
, - ,
! � � � � � � . � �� � !
NC1h+f1NAL {TEI'� MA7�. DIN1EN51C3NS YUEfGHT hNf)MINAL ITEM MA}C. DIMEh1SIt7N WEIGHT
SI� CflDE W�RKING EAGM SVZE C[JQ€ WORKI�NG EJ1CH
{INC#i} # P.S.I. A B RIECE (1NCH} # P.S.1. A PIECE
1X1I2 C894431 300 1_2fi 1.36 U.64 'EJ2 CPL�Q7 3�0 tl.94 0.1Q
1X3l4 CB9Q�32 3C?6 1.3F 1.45 [l.87 314 CP�t7�� 300 1.C11 {}.17
11{4X,11� CB9�Ofl4ti 340 1.34 '[.53 [5.9fi 'I CP�.{1�3 300 1.25 {].28
11{4?C314 G690U42 344 1.45 "i.6� 1.13 11f4 CPLUOd 34?6 1.36 �1.44
11fdX1 G630U43 3U0 1.58 1.fi7 1.'ifi 11f2 CPL005 344 i.45 U.G2
11l2XT CB9t70'�3 3(]0 1.65 1.8Q 1.5i 2 C�'�.�Ofi 34(1 '�.56 (}.91
11l25C1714 C�90054 340 'f.82 1.88 1.fi2
27S9f2 CS9[}6�i1 300 4.49 1.88 2.iF6
�x�ra casaasz saa �.�p �.s7 2_0� �,��mitted by:
27C� CB94Ufi3 34a 7.73 2.Q2 2.1U �ate:
2X111d CB9{1D64 300 1.91] 2.1a 2.30
2}(11f2 CB9DQ65 3DD 2.U2 2.9E, 2.fi0
- - pP�aravec� hy:
IJate:
For inst�llatian �n the __ project
$y; �corrtractor
4018 WFSTHflLLC)W PARKWAY H[]USTC7N,TF?CAS 77082
T(}LL FREE.8t38-�3+6l-STAR,T�L: 2&[-558-34U0,�'�k�:2�S1:558-90Ua
�������'rJ � , ,C�►►SrI� I K�7�"+d
SLIBMI`T I�"�.L �4�IErT [.99.I�
! ! a I�iti�r`tiifirr rrj",Slar 1"i�ar�l'rodut'fs
� � ■ �
NC?MINAL ITEI4! MAX. QiMENS147NS WEVGHT
SIZE CDDE WQRKING EACH
�tNCH} # P.S.I. A B C PIECE
���� '6}Lfi3(1!2 C7331 3�i1 1.�8 1.26 1.36 D.95
� 't?4?X3f4 C'�332 34d 1.37 1.37 t.45 1.10
_ � iX1f2X1 CT3'�3 3[Fd 1_5{7 1.36 1.SU 1.48
+ fiX3fd�1 CT323 3{FO 1.5{f 1.43 ti.SU 1.18
� _ I I 1X1iC1114 C�'33d 30� 1.67 1,67 'Y.58 '1,52
I , - 1X1X11f2 ��335 _ 3Q0 1.8Q 1.80 1.55 1.73
I _ _� 'S tl4XiX1I2 CT431 3�Ff1 1.3d 1.28 1.53 1.�7
11I4X17i314 CT�32 30Q 1.45 9.37 1,6� 1.38
11f4x1X1 CTd3$ 30p 1.58 '�.�0 1.5'7 9.47
1 �14X1X1 1f4 CT�34 �00 1.T5 °I.67 1,75 7.8D
711dX'�X11lT GT436 3QU 1.SEt 1.80 1.82 2.05
7 'il4K1 114X112 CT4d1 300 1.34 1.34 1.53 7.37
'! 'EI�K1 114}C3ld �T442 3U4 1.4a 9.d� 1.62 1.54
�� �I ���� 1 1J4X1 1F4X1 �7443 30U 1.5$ 1.58 1.67 1.65
� "'�" 1 114X9 1l4X1 '112 CT445 30� 1.68 1.88 't.82 ?.2'I
� 1114X11fdJi2 ' CT4d6 300 2.10 2.iQ 1.9U Z.SS
�ISTE� ��SE� APPRraVE� 11f2X1�C1�2 CT531 3�IQ "1.47 1.34 1.6fi 1.d1
11f2�(1X31a CT5�2 304 1.52 �.3a �.a5 �.s3
1 't12%1X9 CT533 3{�d 1.65 1.50 1.80 � 4.65
1 11Z3[4l(4 9!d C3�53d 34� 1.82 1_67 9.88 2.44
1 112X'�X 1 'I f 2 �lf�35 3�D 1.94 1.80 9.94 2.30
C:A5T 1R{3'tii TI[REAdED C+'�TTI'Vr'S 5T'�C1FZC'r1Tl{]I]V: � �j2]�1 1f4Xif2 C�'541 �{}11 1.41 �.,3d �.68 1.58
1 �f3�1 1141i314 C�Sd� 30� 1.5? 1.45 1.7� 1.72
1112X11l+1K1 C�`543 3�60 1.65 1,5$ °1.$0 1.85
;�5T11�1 ri-126 All cast iron scr�wed fitticig,s meet ore.xceeds 1 712?(7 1ldX2 CT546 3if0 2.ifi 2.10 2.02 2.80
materials canfi7rn7ing te�r'15"1'M A-12b. 1 1l2X1 if2X1P2 CT551 3�i0 1.41 1.4'� i.65 1.7�6
1 112X1 'If2X31A CT552 3�1[I 1.52 1.52 1.TS 1.87
1 112Jt7 '1f27(1 GT553 34U 'F.�65 1.�55 1.8U 1.94
}1�ISlIA,S1+4�E t31G.4('LA55 125 CasL ir�n Lhreaded lillings { ���xq 1!2}C1 114 CT5,54 3{}0 1.82 1.82 1.88 2.29
d'smensinns Lo���onnto ANS[f,45TM 816.�C'LASS 125. 1 1123f1 if2X2 CTS56 3�4 2.16 2.16 2,02 3.2$
2X'1x2 GT&3fi 3{!(1 �.25 � 2�02 2.25 3.40
2X1 9l4x2 C'P646 3�Q0 2.25 I 2.10 2.25 2.80
A;VSi1.�.51�'[F, I�1.20.1 �11! cast iron thccaded tik[g���;s ZX1 qf25C1l2 CT&51 3(f4 4.49 1.d�1 1.88 2.f19
are NA'I'stan�ar�l acsni�rming lo ANSll'ASME f�i.2�.1 ��1 'tl�x3lb CT652 3t1{! 1.60 1.52 i.97 2.4U
2X1112?(1 CT653 34U 1,7� 1.65 2.f?� 2.54
��9 1F2X'! if4 Cl'fi54 3{�Fi 1.9f� 1.82 2.10 2.85
2Xi 1I2�1 'Sf2 CT655 30fl 1.49 1.d1 7.88 2.24
2X1112X2 C'f65fi 30df 2.25 2,18 2.�5 3.75
2]C2X112 CT661 3Q0 1d�9 4.49 1.88 2.60
27L2X314 �T662 300 1.fiD 1.60 fi.97 2.71
2Xi2X1 C7663 300 1,?3 1.73 2.02 2.97
2x2X� 1F4 GTS54 300 i.�C? 1.�0 2.iG� 3.32
�xax� �rz crsss 3no z.o� �.a2 z.�s �.a2
' 1 ' /
' '` � ` � N41'VIINAL lTEM MAX. I]IM�NSI�hIS WEIGHT
i l. *�`'°"I� Ci7L}� V1fdRi(ING EACH
��r ' {iNCH'} # P.S.�. ,q B PI�CE
C I
' � 1 GiC033 300 1.5Q fi.50 1.54
� - + 1 1C4 CX044 30Q 1.7 a '#.75 2,d4
I i if2 CX065 3�U `l.'9A '1.9A 3.'10
a ---' �
T - 2 �X466 3�Q0 2.25 3.25 4.Oa
-- ----, i:-.:
_ �t- ,-, 1 1fGX1 �CX443 340 1.58 9.67 2.05
71l2X1 CXfY53 3(]L} 1.65 1.8q 2.dfl
2X1 CXQfi3 300 �t.73 2.�1z 2,7$
4418 WESTH�LL�IW FARKWA4' I-IOL�ST�N,TEXAS 77(182
T�LL FR�E: 888-861-STAR,TEL: 281-558-3U�OU,FAX: 2S1-558-9f}QO
THREADED FiTTIJ�I�S
sr���.�x
�`�'A1��1�`I�'TIN�G,�
A Divisio,�of Star Fipe Products,I,.P.
I�EM SIZE LIST QLIANTITY YV�IGH'� GART�NS
CC��E INCH PRiCE CARTUN PLT. CARTON PL'I'. �L.�.
Pl�l1G ��
c��aai ��z �.�� �aoa a�,oao s� s.aoa da
- cP�oa2 sra 1.28 6��D 24.c��a �02 �,aaa aa
cP�oa� T 1.28 30D �2,000 7a z,sa� aa
__� GP1��44 1 't!4 2.C1$ 18f3 7,2�� 75 3,Q�4 - 48
==—=� GPLOU� 1 112 2.93 'l4�Q 5,5i�0 87 3.48g �S
— GRLCld36 2 3.43 80 3,Z�DCl fi4 2,56f7 48
IGRDSS CI
CXD33 1 13.45 42 1,fi8� 48 1,92t� 48
� CXCJ44 1 114 18.97 22 � 880 50 2,�170 48
C�55 1112 25,73 17 680 41 1,640 48
c�ss z s4.as �� �za �� �,aao 4s
CXf743 ') 114X1 114X1X1 27.(]8 2$ 1,120 5fl �,O�fl 48
�Kp53 11l2X111�X9X1 25.07 18 �2� 51 2,d4€] 48
- � C?(D63 2X2}(1]C9 34.32 16 64� 42 1,58t] 48
IBIJLL HEA�TEE Cl
CT334 iX1?C71l�3 9,41 $2 },�680 52 2,484 A8
r
CT335 'lX1Xt 1!2 '�3,55 34 1,36(J 52 2,fl$� 4$
CT435 1 '�F4X1x1 1I2 �4.�54 27 1,295 55 2��4Q 48
� GT445 1 1�4X7 `�14X'I 11� 74,�4 �4 950 48 1,924 48
CTi446 11«X1114X2 2Q.2t] �2C1 8QL7 46 1,844 48
�-�-` CT546 11f2X11l4X� 22.2$ 17 58C] 4� 1,84� 48
CTa55 11f2�(1112X2 'i5.5'� 17 68(l 47 1,880 48
GQUPLiNG C71
�� I L3CLQ33 1 3.65 144 5,72d 75 3,60�4 48
� aCLQ44 1114 4.fi8 90 4,320 72 3,45� AS
LQCL055 1 �12 fi.26 56 2,688 59 2.832 48
❑GLQ66 2 9.22 3B 1,72� 6S 3,12[3 d8
�CAP Cll
r_- --- •I [}CP003 � �,SQ �04 9.fi4Q �4 3,�72 48
� DCP004 1114 3,22 134 6,244 55 3,12[] 48
��.
L}CPO{}5 11l2 4,42 95 4,6�8 65 3,120 A8
�7CPQ4� 2 6.5J 72 3,456 75 3,6�30 48
N[JTE; C]M �9�DER5 RECEIL+ED F�R THREAQED PRQCIUCTS If� L�SS THAhI GARTUN QUANTITIES, 1JVE
RESERVE TNE RIGHTT{3 A6JUSTTC] THE NE)Cf CART01� QUANTiTY ABCIV� �`NE NUfNBER CJF PI�CES
SH4WN C3N THE (7RDER.
T�i: ��c��o� �s�-�o��, {�s�� s�s-3oon, �a�: ��sl} ss�-s�ouo
pa��e 20
_;:•� :.. � • � . � • �
,�I�' �� FM U�C vds LPCB ��
SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS vNOCo
STYLE 75
f� .:�
Style 75 is available where moderate pressures are expected or weight � _
i'''�,
considerations are a factor. Up to 50% lighter in weight than the Style 77, -
the Style 75 coupling is recommended for service up to 500psi/3450kPa °
depending on size. Housings are cast in two identical pieces in all sizes.
Hot-dip galvanized and special coatings are available for all sizes.
The Victaulic standard flexible coupling offering for grade "EHP° or°T°gaskets is —
the Style 177 installation-ready flexible coupling. For all available sizes,the Style
177 is the standard flexible coupling Victaulic supplies in North America for piping
systems using Grade "EHP"or"T"gaskets. Contact Victaulic for further details.
Exaggerated for clariry
MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A-536,grade 65-45-12. Ductile iron conforming to ASTM
A-395,grade 65-45-15, is available upon special request.
Housing Coating: Orange enamel.
• Optional: Hot dipped galvanized and others.
Gasket: (specify choice�)
• Grade"E" EPDM
EPDM (Green color code). Temperature range—30°F to+230°F/-34°C to+110°C.
Recommended for hot water service within the specified temperature range plus a variety
of dilute acids,oil-free air and many chemical services. UL classified in accordance with
ANSI/NSF 61 for cold+86°F/+30°C and hot+180°F/+82°C potable water service. NOT
RECOMMENDED FOR PETROLEUM SERVICES.
• Grade"T" nitrile
Nitrile(Orange color code). Temperature range—20°F to+180°F/-29°C to+82°C.
Recommended for petroleum products, air with oil vapors,vegetable and mineral oils within
the specified temperature range; except hot, dry air over+140°F/+60°C and water over
+150°F/+66°C. NOT RECOMMENDED FOR HOT WATER SERVICES.
� Services listed are General Service Recommendations only. It should be noted that there are
services for which these gaskets are not recommended. Reference should always be made to
the latest Victaulic Gasket Selection Guide for specific gasket service recommendations and for a
listing of services which are not recommended.
NOTE Additional gasket styles are available.Contact Victaulic for details.
Bolts/Nuts: Heat-treated plated carbon steel,trackhead meeting the physical and chemical
requirements of ASTM A-449 and physical requirements of ASTM A-183.
JOB/OWNER CONTRACTOR ENGINEER
System No. Submitted By Spec Sect Para
Location Date Approved
Date
www.victaulic.com
�ctaul�cc
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.OO 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED..
�r�.r°:.:�.+uw '�iL�� c'.a'�. ie��Gi.+�Wu�� O�■0�
� � ���(.
STYLE 75
DIMENSIONS
�� �
1 1315 500 680 0-0.06 0.57 238 427 1 J7 13
25 33.4 3450 30Z5 0-16 ��-43' 48 �-3�exz 61 108 45 0.6
1 Ya 1.660 500 1080 0-0.06 0.45 2.68 4.61 1.77 1.4
32 42.2 3450 4805 0-1.6 2�-10' 38 2 �e X� 68 117 45 0.6
1 Yz 1.900 500 1420 0-0.06 0.40 Z91 4.82 1 J7 15
40 483 3450 6320 0-1.6 � -56 33 Z �e X 2 74 12Z 45 0.6
Z 2375 500 2Z15 0-0.06 032 3.43 S.Z2 1.88 17
50 603 3450 9560 0-1.6 � -31 26 Z 3�8 X 2 87 133 48 0.8
2'/z 2875 500 3245 0-0.06 Q26 3.88 5.68 1.88 1,9
65 73.0 3450 14440 0-1.6 ��-1 S 22 2-3/a x 2 98 144 48 0.9
3.000 500 3535 0-0.06 0.26 4.00 5.90 1.88 1.9
76.1 mm 76.1 3450 15730 0-1.6 � �Z 22 Z �e X z 102 150 48 0.9
3 3.500 500 4800 0-0.06 Q22 450 7.00 1.88 2.9
80 88.9 3450 21360 0-1.6 � � 18 � ��X��� 114 178 48 13
3 Yz 4.000 500 6300 0-0.06 0.19 5.00 750 1.88 Z9
90 101.6 3450 28035 0-1.6 � -54 16 �-��x���4 1 Z7 191 48 13
4 4500 500 7950 0-0.13 034 5.80 8.03 2.13 4.1
100 1 143 3450 35380 0-3.2 1°-36 28 Z-'�2 X Z'�4 147 204 54 1.9
4250 450 6380 0-0.13 035 555 7.79 213 37
108.0 m m 108.0 3100 28395 0-3.Z 1°-41' 29 Z-12 x 70.0 141 198 54 17
4 Yz 5.000 450 8820 0-0.13 0.25 6.13 9.43 2.13 55
120 127.0 3100 39250 0-3.Z 1°-26 21 2-%s x 3 Yn �56 240 54 25
5 5563 450 10935 0-0.13 027 6.88 10.07 2.13 5.8
125 1413 3100 48660 0-32 1°-18' 23 2-s/s x 3 Ya ��5 256 54 2.6
5.250 450 9735 0-0.13 0.28 6.55 937 Z13 6.0
133.Omm 133.0 3100 43325 0-3.2 1°-Zl' 24 2-16x82.5 �66 238 54 2J
5500 450 10665 0-0.13 028 6.80 959 2.13 63
139J m m 139.7 3100 47460 0-3.2 � �8 24 Z-�B X 3�� 173 244 54 29
152.4mm 6.000 450 12735 0-0.13 �o_�Z, 0.21 Z_s/ex3Ya 738 10.48 1.88 6.2
15Z4 3100 56670 0-3.2 18 187 266 48 28
6 6.625 450 15525 0-0.13 0.23 8.00 1 1.07 2.13 7.0
150 1683 3100 69085 0-3.2 � -5 1 S �-�e X 3�4 203 �81 54 3.2
6250 450 13500 0-0.13 Q24 7.63 10.49 2.13 6.8
159.0 mm 159.0 3100 61405 0-3.2 ��-9' ZQ 2-16 x 82.5 194 266 54 3.1
8 8.625 450 26280 0-0.13 0°-50' ��8 2-3/n x 4'/n 1034 13.97 232 12.4
200 219.1 3100 116945 0-3.Z 14 263 355 59 5.6
� Working Pressure and End Load are total,from all internal and external loads,based on standard weight(ANSI)steel pipe,standard roll or cut grooved in
accordance with Victaulic specifications.Contact Victaulic for performance on other pipe.
WARNING:FOR ONE TIME RELD TEST ONLY,the Maximum Joint Working Pressure may be increased to 1 1/2 times the figures shown.
t Allowable Pipe End Separation and Deflection figures show the maximum nominal range of movement available at each joint for standard roll grooved
pipe Figures for standard cut grooved pipe may be doubled.These figures are maximums;for design and installation purposes these figures should be
reduced by:50%for 3/4-3 1/2'%20-90 mm;25%for 4"/100 mm and larger.
@ Number of bolts required equals number of housing segments.
Metric thread size bolts are available(color coded gold)for all coupling sizes upon request.Contact Victaulic for details.
F Y� I�Z�I
�X -
www.victaulic.com
�ctaul�c�
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.OO 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED..
_,:.. :•• � . � � • �
�n�
STYLE 75
WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for tletails.
NOTE This product shall be manufactured by Victaulic or to Victaulic specifications. All
products to be installed in accordance with current Victaulic installation/assembly
instructions.Victaulic reserves the right to change product specifications,designs
and standard equipment without notice and without incurring obligations.
INSTALLATION Reference should always be made to the I-100 Victaulic Field Installation Handbook for the product
you are installing. Handbooks are included with each shipment of Victaulic products for complete
installation and assembly data, and are available in PDF format on our website at www.victaulic.com.
For complete contact information,visit www.victaulic.com
06.05 1470 REV M UPDATED 2/2011 �Ct'c�UIIC�
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.OO 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED.
_;:.� :•. � � � �
U� FM U�C vas LPCB
�y_ � � _ .� m.. �_ .�. a _sm�_
'- SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS
Victaulic offers a broad line of fittings in sizes through 24"/600mm in a variety of straight and -
reducing styles. Most stantlard fittings are cast of durable ductile iron to precise tolerances.
Victaulic standard fittings pressure ratings conform to the ratings of Victaulic Style 77 couplings.
AII fittings are supplied with grooves to permit fast insta�lation without field preparation.The grooved
tlesign permits flexibility for easy alignment. These fittings are not intended for use with Victaulic
couplings for plain end pipe(refer to Section 14.04 for fittings auailable for plain end applications).
Fittings are provided in various materials including ductile iron,steel or segmentally welded steel N0.20 TEE
tlepending on styles and size. Fittings are painted orange enamel with a galvanized finish available
as an option,contact Victaulic for details. -
Victaulic fittings are designed specifically for use in grooved piping systems. Fittings are provided ;
grooved conforming to stantlartl steel pipe outside diameters.When connecting wafer or lug-type
butterfly valves directiy to Victaulic fittings with 741 or 743 Vio-Flange°adapters,check disc �
i
clearance dimensions with I.D.dimension of fitting.
Note:The following Victaulic fittings are VdS approved: No.10 90°Elbow, No.l l 45°Elbow, No.20 �
Tee and No.60 Cap.
Note:The following Victaulic fittings are LPCB approved: No.10 90°Elbow, No.l l 45°Elbow, No.12 NO.10 ELBOW
22'/z°Elbow, No.13 111/n°Elbow, No.30 45°Lateral, No.30-R Reducing Lateral, No.100 Long
Radius Elbow, No.110 Long Radius Elbow, No.20 Tee, No.35 Cross, No.60 Cap, No25 Reducing
Tee, No.33 True Wye, No.50 Concentric Reducer, No.51 Eccentric Reducer and No.29M Tee with
Threaded Branch.
Advanced Groove System-For 14-24"/350-600 mm piping systems,Victaulic now offers the
Advanced Groove System(AGS). Refer to Section 20.05 for AGS fitting details.
Stainless Steel-Grooved end fittings are available in Schedule 10 Type 316 stainless steel(Schedule
5,40 and Type 304 available as an option)in various sizes. Fitting center-to-end dimensions will vary
depentling upon type and schedule. Refer to Section 17.04 antl 17.16 for details.
�-= Aluminum-Grooved end fittings are available in aluminum alloy 356 T6, in sizes from
1-8"/25-200 mm. Refer to Section 21.03 or contact Victaulic for details.
Fabricated Steel-A full range of fabricated segemtnally weided steel or full flow grooved end fittings
are available refer to section 07.04.
Fabricated Steel with AGS Vic-Rings-A full range of full flow fabricated fittings with Vic-Rings are also
available.
AGS—ADVANCED GROOVE SYSTEM
ALTERNATE STYLES Extra Heavy EndSeal°"ES"Fittings-EndSeal fittings are available in 2-12"/50-300mm for use
with°ES°grooved pipe and HP-70ES EndSeal couplings. "ES"fittings are painted black for easy
Y� identification. EndSeal(and standard)fittings may be easily internally coated(by others)for severe
service requirements.Always specify"ES EndSeal fittings"when ordering.See Section 07.03 for
information on EndSeal fittings.
^� � Fittings Machined for Rubber or Urethane Lining(MRL)-For severe abrasive services,Victaulic
fittings may be rubber or urethane lined(by others). Lining may be inside diameter/end(abrasion
resistance)or wrap-around(corrosion and/or abrasion)machined. Refer to Section 25.03 or contact
Victaulic for specific details.
i
Note: Fittings are available with a variety of coatings upon request such as hot dip galvanized,epoxy,
glass lined and others.
JOB/OWNER CONTRACTOR ENGINEER
System No. Submitted By Spec Sect Para
Location Date Approved
Date
www.victaulic.com
�ctaul�c`
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.OO 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED.
a5 v��d �u .,..... �
CARBON STEEL PIPE-GROOVED FITTI�,`,;:` O�.O�
Grooved End Fittings
MATERIAL SPECIFICATIONS Fitting: Ductile iron conforming to ASTM A-536, grade 65-45-12. Ductile iron conforming to ASTM
A-395, grade 65-45-15, is available upon special request.
• Or: Segmentally welded steel as shown under nipples
Nipples: (adapter, swaged & hose)
• 3/a—4"/20— 100 mm: Carbon steel, Schedule 40,conforming to ASTM A-53, Type F
• 5—6"/125— 150 mm: Carbon steel, Schedule 40,conforming to ASTM A-53,Type E or S, Gr. B
• 8— 12"/200—300 mm: Carbon steel, Schedule 30 or 40, conforming to ASTM A-53, Type E or S,
G r. B
Flanged Adapter Nipples: (Nipple—see above)
• Class 125 Flange: Cast iron conforming to ANSI B-16.1
• Class 150 Flange: Carbon steel conforming to ANSI B-16.5, raised or flat face
• Class 300 Flange: Carbon steel conforming to ANSI B-16.5, raised or flat face
Fitting Coatings: Orange enamel
• Optional: Hot dip galvanized and others.Some fittings supplied electroplated as standard—see
product specifications.
Flanged Adapter Nipple Coating: None(Unfinished)
• Optional: Orange enamel, hot dip galvanized and others.
www.victaulic.com
�ctaul�c'
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.OO 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED.
fid.'J1 � .�,s
CARBON STEEL PIPE-GROOVED FITTING;`' O�.O�
Grooved End Fittings
FLOW DATA The chart expresses the frictional resistance of various Victaulic fittings as equivalent feet of straight
pipe. Fittings not listed can be estimated from the data given,for example,a 22'/z°elbow is
(FriCtional ResistanCe) approximately one-half the resistance oi a 45°elbow.Values of mid-sizes can be ini�erpolated.
� .
1 1315 1.7 Q8 4J 1]
25 33J OS 0.2 13 OS
2 2375 3.5 2.5 L8 1.1 8.5 3.5
50 603 1.1 0.8 0.5 03 2.6 1.1
76.1 mm 3.000 43 2.1 10.8 43
76.1 13 0.7 33 13
3 3.500 5.0 3.8 z.6 1.6 13.0 5.0
80 88.9 1.5 12 0.8 OS 4.0 1.5
108.0 mm 4.250 6.4 3.2 153 6.4
108.0 2.0 0.9 4J 2.0
4 4.500 6.8 5.0 3 4 2.1 16.0 6.8
100 1143 2.1 15 1.0 0.6 4.9 2.1
133.0 mm 5.250 8.1 4.1 20.0 8.1
133.0 25 12 6.2 2.5
139J mm 5.500 8.5 4.Z 21.0 8.5
139J 7.6 13 6.4 ?.6
5 5.563 8.5 4.2 21.0 8.5
125 1413 ?.6 13 6.4 2.6
159.0 mm 6.Z50 9.4 4.9 25.0 9.6
159.0 2.9 1.5 Z6 2.9
165.1 mm 6.500 9.6 5.0 25.0 10.0
165.1 2.9 1.5 Z6 3.0
6 6.6Z5 10.0 7.5 5.0 3.0 25.0 10.0
150 1683 3.0 23 1.5 0.9 Z6 3.0
S 8.625 13.0 9.8 6.5 4.0 33.0 13.0
200 219.1 4.0 3.0 2.0 12 10.1 4.0
10 10J50 17.0 12.0 83 5.0 41.0 17.0
250 273.0 52 3J 2.5 1.5 12.5 52
12 12J50 20.0 14.5 10.0 6.0 50.0 20.0
300 323.9 6.1 4.4 3.0 1.8 15.Z 6.1
14 14.000 24.5§ 15.8 18.5§ 11.0 70.0 23.0
350 355.6 J5 4.8 5.6 3.4 213 7.0
16 16.000 28.0§ iS.O 21.0§ 13.0 50.0 27.0
400 406.4 85 55 64 4.0 Z44 8.2
18 18.000 31.0§ 20.0 23.5§ 14.0 90.0 30.0
450 457.0 95 6.1 7.2 43 D.4 9.1
20 20.000 34.0§ 225 25.5§ 16.0 100.0 33.0
800 508.0 '04 6.9 7.8 4.9 30.5 10.1
24 �4.000 42.0� 27.0 29.5§ 19.0 120.0 40.0
600 610.0 128 8.2 9.0 58 36.6 12.Z
#Contact Victaulic for details.
#For roll grooved systems,Victaulic offers the Advanced Groove System(AGS).For pricing and availability
of cut groove fittings in this size,contact your nearest Victaulic sales office.
§Fitting flow data for 14 24"/350 600 mm size No.10 and No.11 Elbows is based on fittings for Style 07
and 77 couplings.For flow data on AGS fittings(No.W10 and No.W11 Elbows),refer to submittal 20.05.
Note:All fittings are ductile iron unless otherwise noted with an"sw"or"s".
S-Carbon Steel Direct Roll Groove(OGS)
SW=Carbon Steel Segmentally Welded
www.victaulic.com
�ctaul�c°
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.OO 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED.
ri�v a, .,,..,..
CARBON STEEL PIPE-GROOVED FITTI�,`,;:` O�.O�
Grooved End Fittings
DIMENSIONS
Elbows
N0. 10 90°Elbow
N0. 11 45°Elbow �
N0. 12 221/z°Elbow E to E
N0. 13 111/a°Elbow � �-c to E�
N0. 100 90°Long Radius
N0. 110 45°Long Radius i�c to e i N0.12 GSNK c co E\
I >., � ,�
CtoE � � ��
�
� - + - � CtoE, CtoE I
`jE � � � �
N0.10 N0.11 N0.12 N0.13 N0.100 N0.110
� �� �
. . � . � .
- •�• .. , . . . ,�. . . , .
'/a 1.050 2.25 0.5 L50 0.5 1.63 sw 138sw 250sw 0.4 1.81 sw 03
20 26.9 57 02 38 0.2 41 35 64 O.z 46 0.1
1 1315 z.25 Q6 175 0.6 325 0.6 138sw 03 2.88sw 0.6 2.25sw OS
25 337 57 03 44 03 83 03 35 0.1 73 03 57 0.2
lYa 1.660 2J5 1.0 1J5 0.9 1J5 0.8 138sw 0.5 325sw 1.1 238sw OJ
32 42.4 70 0.5 44 0.4 44 0.4 35 0.2 83 0.5 60 03
1'fz 1.900 2J5 1.2 1J5 0.9 1J5 0.8 138sw 0.5 3.63sw 2.2 250sw 13
40 483 70 0.5 44 0.4 44 0.4 35 0.2 9z 1.0 64 0.6
� 2375 3.25 1.8 2.00 13 3 75 @ 1 4 138 1.0 438 2.5 2J5 1.8
50 603 83 0.8 51 0.6 95 0.6 35 0.5 i l l 1.1 70 0.8
2'h 2.875 3J5 3.2 2.z5 Z.2 4.00@ 23 L50 1.1 513 34 3.00 2.8
65 73.0 95 15 57 1.0 102 1.0 38 0.5 130 15 76 13
76.1 mm 3000 3J5 3J 2.25 3.4 Z.24 1.50
76.1 95 1.7 57 1.5 57 38
3 3.500 4.25 4.5 Z50 3.1 4.50@ 3.1 150 2.1 5.88 6.0 338 4.9
80 88.9 108 2.0 64 1.4 114 1.4 38 1.0 149 2.7 86 2.2
3'/z 4.000 4.50 5.6 2J5 43 ZSO sw 4.0 175sw 2J
90 101.6 114 2.5 70 2.0 64 1.8 44 1.2
4 4 500 5.00 7.1 3.00 5.6 2.88 5.6 1 J5 3.6 7.50 123 4.00 73
100 1143 127 3.2 76 25 73 25 44 1.6 191 5.6 102 33
108.0 mm 4250 5.00 11.0 3.00 5.6
108.0 127 5.0 76 25
4Yz 5.000 5.25 sw 10.0 3.13 sw 6.0 3.SOsw 6.6 1.88sw 4.2
120 127.0 133 4.5 79 2J 89 3.0 48 1.9
5 5563 5.50 i l J 325 83 2.88sw 7.8 Z.00sw 5.0 9.25 sw 18.2 4.88 sw 14.8
125 1413 140 53 83 3.8 73 3.5 51 2.2 235 83 124 6.7
133.0 mm 5.250 5.50 11.7 3.Z5 83
133.0 140 5.3 83 3.8
139J mm 5.500 5.50 11J 3.Z5 83 2.87 2.00
139J 140 53 83 3.8 73 51
6 6.6Z5 6.50 17.2 3.50 10.5 625 @ 1 z2 2.00 7.0 10J5 30.4 5.50 17.4
150 1683 165 7.8 89 4.9 159 5.5 51 32 273 13.8 140 7.9
159.0 mm 6.Z50 6.50 18.6 3.50 10.8
159.0 165 8.4 89 4.9
165.1 mm 6500 6.50 15.5 3.50 9.8 3.13 114 2.00 74 lOJSsw 29.0 S.SOsw 19.0
165.1 165 7.0 89 4.4 79 5.2 51 3.4 273 13.2 140 8.6
@ Gooseneck design•end to end dimension fittings in this size-contact your nearest Victaulic sales office
t Chinese standard sizes
Note:All fittings are ductile iron unless otherwise noted with an"sw"or"s"
S=Carbon Steel Direct Roll Groove (OGS)
SW=Carbon Steel Segmentally Welded
www.victaulic.com
�ctaul�c'
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.OO 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED.
fit.;il - .,,s
CARBON STEEL PIPE-GROOVED FITTING;`' O�.O�
Grooved End Fittings
� �-�toE-�
EtoE
� c to E� ' � i r�
N0.12 GSNK C to E
C to E� � •�
�- + - � CtoE � i
� �� � � �, ctaE_
t�E � � � � -��
N0.10 N0.11 N0.12 N0.13 N0.100 N0.110
� �� �
� � . � . �
- •�• .� , . . . ,�. . . , .
8 8675 J7 7�i9 4J5 70= IiSC? ?00 %00 IOJ 14%5 e�60 iJ5 360
200 2191 197 13-6 108 93 197 yl 51 4.6 362 30-0 184 163
10 1OJ50 9.00 633 4J5 375 438sw 30.0 J_.13 11.8 15.00 107.0 6.75 570
250 273.0 229 28J 121 17.0 lll 13.6 54 53 381 485 159 25.9
12 12J50 10.00 74.0 5.25 66J 4.88sw 40.0 2.25 293 18.00 156.0 7.50 90.0
300 323.9 254 33.6 133 303 124 18.1 57 133 457 70.8 191 40.8
14 N 14.000 14.00 136.0 5J5 65.0 S.00sw 46.0 3.SOsw 32.0 Z1.00 s 164.0 8.75 s 82.0
350 355.6 355.6 61.7 146 29.5 127 20.9 89 14.5 533 74.4 222 3Z2
377.0mm t �4.843 14.84 1493 6.15 82.0
377.0 376.9 67.7 156.2 37.2
16� 16.000 16.00 171.0 6.63 88.0 S.00sw 58.0 4.00sw 42.0 24.00 s 210.0 10.00 s 100.0
400 406.4 406.4 77.6 168 39.9 127 263 102 19.1 610 953 254 45.4
426.Omm t �6J72 16J7 198.6 6.95 1013
426.0 426,0 90.1 1765 45.9
18# 18.000 18.00 228.0 7.46 108.0 S.SOsw 65.0 450sw 532 27.00 s 273.0 1 L25 s 135.0
450 457.0 4572 103.4 189 50.0 140 295 114 24.1 686 123.8 286 612
480Omm t 18.898 18.90 291.0 783 141J
480.0 480.0 132.0 198.8 643
ZO it 70.000 z0.00 298.0 828 138.0 6.00sw 78.6 S.00sw 65.0 3Q00 s 343.0 1Z.50 s 174.0
500 508.0 508.0 135.2 210 62.6 152 36.0 127 29.5 762 155.6 318 78.9
530.Omm t Z0.866 Z0.87 355.0 8.64 V9.0
530.0 530.0 161.0 219.4 81.2
Z4 t{ Z4.000 24.00 438.0 9.94 221.0 7.00sw 140.0 6.00sw 60.0 36.00 s 516.0 15.00 s Z51.0
600 610.0 609.6 1987 252 100.2 178 63.5 152 27.2 914 234.1 381 113.9
630.0 mm t Z4.803 Z4.80 545.0 10.27 255 2
630.0 630.0 247.2 261.0 115J
14-24 AGS" For AGS fitting information,see publication 20.05
350-600 v
@ Gooseneck design(GSNK),end-to-end dimension fittings in this size,contact your nearest Victaulic sales office.
#For roll grooved systems,Victaulic offers the Advanced Groove System(AGS).For pricing and availability of cut groove fittings in this size,contact your
nearest Victaulic sales offlce.
t Chinese standard sizes
Note:All fittings are ductile iron unless otherwise noted with an"sw"or"s"
S=Carbon Steel Direct Roll Groove(OGS)
SW-Carbon Steel Segmentally Welded
www.victaulic.com
�ctaul�c°
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.OO 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED.
ri�v a, �.,...
CARBON STEEL PIPE-GROOVED FITTI�,`,;:` O�.O�
Grooved End Fittings
Reducing Base Support Elbow �toF-� �toE�,
NO. R-lOG Grv. x Grv. � ° ° � °I°
N0. R-lOF Grv. x Flange � I
o � � I _y
�- - � H - - H
-� �-� � ,� f
B Dla, B Dia.
N0.R-lOG N0.R-lOF
�
UI ci:�:: I. �.�!`�,�:��:� .. ,,.'':�,J� II i:.`��,:�;: Il I _. I I r,-�.:',
6 4 9.00 t25 1.50 19.0 33.0
150 x 100 229 3Z 38 8.6 15.0
5 9.00 1.50 1.50 23.0 38.0
125 229 38 38 10.4 172
8 6 10.50 2.13 L50 33.0 52.0
200 x 150 267 54 38 15.0 23.6
10 8 12.00 2.40 150 61.0 88.0
250 X 200 305 61 38 27J 39.9
Note:All fittings are ductile iron unless otherwise noted with an"sw"or"s"�
S=Carbon Steel Direct Roll Groove(OGS)
SW=Carbon Steel Segmentally Welded
www.victaulic.com
�ctaul�c'
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.OO 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED.
fit.Jl v .�,�
CARBON STEEL PIPE-GROOVED FITTING;`' O�.O�
Grooved End Fittings
Adapter Elbow �to
r-�E-�
N0. 18 90°Adapter Elbow I Cto�
GE
N0. 19 45°Adapter Elbow I ,r�
� - �
C to
TE C to
1 1�
N0. 18 N0.19
,�.
%a 1 050 2.25 L25 O S 150 1.50 OS
20 26.9 57 57 Q2 38 38 Q2
1 1315 2.25 225 OS
25 33J 57 57 Q2
1 Ya 1.660 275 275 09
32 42.4 70 70 0.4
1 Yz 1.900 2.75 �.75 1.1 1.75 1.75 0.9
40 483 70 70 OS 44 44 0.4
Z 2375 325 425 25
50 603 83 108 1.1
2'/z 2875 3.75 3J5 3.0 225 2.25 23
65 73.0 95 95 1.4 57 57 1.0
3 3500 425 6.00 5.8 250 425 5.0
80 88.9 108 152 2.6 64 lOS 23
3%z 4.000 450 625 8.0 525 525 8.8
90 101.6 114 159 3.6 133 133 4.0
6 6b25 650 650 17.6 3.50 3.50 1ZJ
150 1683 165 165 8.0 89 89 5.8
@ Available with British Standard Pipe Threads specify'BSP"dearly on order�
Note:All fittings are ductile iron unless otherwise noted with an°sw"or"s"
5=Carbon Steel Direct Roll Groove(OGS)
SW=Carbon Steel Segmentally Welded
www.victaulic.com
�ctaul�c°
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.OO 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED.
ri�v e;
CARBON STEEL PIPE-GROOVED FITTI�,`,;:` O�.O�
Grooved End Fittings
Tees, Crosses and True Wyes ,t�toE
� cco�� --�E
N0. 20 Tee �. �ta�yl � -.�
N0. 35 Cross �i �
N0. 33 True Wye --+ - � �I � � - -
� I
N0. 29M Tee with I � �- -
+
Threaded Branch tE SE ctoTE
� i �
N0.20 NO 35 N0.33 N0.29M
�
3/a 1_O50 225 Q6 225 09 2.25 2.00 OJ 225 225sw 0-6
20 26.9 51 03 5/ 0.4 57 51 03 51 51 03
1 1315 2.25 1.0 2.25 13 2.25 2.25 1.1 2.25 2.25 1.0
25 337 57 OS 57 0.6 57 57 0.5 57 57 OS
1'/a 1.660 2.75 15 2.75 2.1 2.75 250 1.5 2.75 275 1 S
32 42.4 70 0.7 70 1.0 70 64 0.7 70 70 0.7
1�h 1.900 2.75 2.0 2.75 25 2.75 2J5 1.8 2J5 2.75 2.0
40 483 70 0.9 70 1.1 70 70 0.8 70 70 0.9
2 2375 3.25 3.0 325 3.8 3.25 2J5 ?.5 3.25 4.25 3.00
50 603 83 1.4 83 1.7 83 70 1.1 83 108 1.4
2'fz 2.875 3J5 43 3J5 6.1 3J5 3.00 43 375 3J5 43
65 73.0 95 2.0 95 2.8 95 76 2.0 95 95 2.0
76.1 mm 3.000 3J5 5.2 3J5 3J5 sw 5.2
76.1 95 2.4 95 95 2.4
3 3500 4.25 6.8 4.�5 105 4Z5 3.25 6.1 4,25 6.00 6.8
80 889 108 3.0 108 4.8 108 83 2.8 108 152 3.1
3'/z 4.000 4.SOsw 7.9 4.50 11.5 4.50 3.50 9.6 450 450sw 7.9
90 101.6 114 3.6 114 5.2 114 89 4.4 114 114 73.6
108.0 mm 4250 5.00 15.5 5.00 5.00 sw 15.5
108.0 127 7.0 127 127 7.0
4 4.500 5.00 11.9 5.00 15.8 5.00 3J5 10.0 5.00 725 11.9
100 ll43 127 5.4 127 7.2 127 95 45 127 184 5.4
4 Yz 5.000 5.25 sw 15.0 5.25 18.5 5.25 5.25 sw 15.0
120 12Z0 133 6.8 133 8.4 133 133 6.8
133.0 mm 5250 5.50 17.8 5.50 5.50 sw 17.8
133.0 140 8.1 140 140 8.1
139Jmm 5.500 5.50 17.8 5.50 S.SOsw 17.8
1397 140 8.1 140 140 8.1
5 5563 5.50 V.8 550 20.0 5.50 4.00 15.0 550 550 sw 17.8
125 1413 140 8.1 140 9.1 140 102 6.8 140 140 8.1
159.Omm h250 6.50 27.1 650 650sw 27.1
159.0 165 123 165 165 123
165.1 mm �500 6.50 22.0 650 28.0 650 650sw 22.0
165.1 165 10.0 165 12.7 165 165 10.0
6 6.625 6.50 25.7 6.50 28.0 6.50 4.50 223 6.50 6.SOsw 25.7
150 1683 165 11.7 165 12.7 165 114 10.1 165 165 11.7
8 8.625 7.75 47.6 7.75 48.0 7.75 6.00 36.0 7.75 7.75 sw 47.6
200 219.1 197 21.6 197 21.8 197 152 163 197 197 21.6
10 10.750 9.00 99.0 9.00 iJ_1.5 9.00 650 699 9.00 9.00sw 73.0
250 D3.0 229 44.9 229 55.1 229 155 317 229 229 33.1
12 12J50 10.00 133.0 10.00 110.0 10.00 7.00 80.0 10.00 10.00sw 99.0
300 3239 254 603 254 499 254 V8 363 254 254 44.9
Note:All fittings are ductile iron unless otherwise noted with an"sw"or's"�
S=Carbon Steel Direct Roll Groove(OGS)
SW=Carbon Steel Segmentally Welded
www.victaulic.com
�ctaul�c'
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.OO 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED.
fid.'J1 ti .�,s
CARBON STEEL PIPE-GROOVED FITTING;`' O�.O�
Grooved End Fittings
Tees, Crosses and True Wyes ,r�toE �,,
N0. 20 Tee � C ro�E c co
tCtoE�I � � GE �
N0. 35 Cross j � �
N0. 33 True Wye -+ - - � I � �' � - -
N0. 29M Tee with I � t �Cto
Threaded Branch ctoTE
E - yE �
N0.20 NO 35 N0.33 N0.29M
� c
141� I')00 1 '�ns�N 14i0 11.00 1980 11.00 T�0 1>4.7 li l)Os�v '1(1C I��S.O
350 3556 2/9 65.8 2/9 89S 2i9 1J1 60is 279 279 (i5.8
377.Omm 14.000 11.50 145.0
355.6 292 65.8
16N 16.000 12.00sw 186.0 12.00 250.0 12.00 8.00 167.0 12.00sw 1200 156.0
400 406.4 305 84.4 305 113.4 305 203 75.7 305 305 84.4
426.Ommt �h000 13.00 186.0
406.4 300 84.4
18V4 18.000 1550sw 260.0 15.50 350.0 1550 850 234.0 1550sw 1550 ���g
450 4570 394 117.9 394 158.8 394 216 106.1 394 394
480.Ommt 18000 14.57 256.0
457.0 370 116J
20# 20.000 V.25 sw 336.0 17.25 452.0 17.25 9.00 281.0 17.25 sw 1 Z25 336.0
500 508.0 438 152.4 438 205.0 438 229 1275 438 438 152.4
530.Omm t Z0.000 1539sw 339.0
508.0 391 153.8
24# 24.000 20.00 sw 592.0 20.00 795.0 20.00 10.00 523.0 20.00 sw 20.00 592.0
600 610.0 508 268.5 508 360.6 508 254 23Z2 508 508 2685
630.0 mm t �4.000 1737 sw 473.0 _
610.0 441 214.5
14-Z4 ,qG$° For AGS fitting information,see publication 20.05
350-600 v
#For roll grooved systems,Victaulic offers the Advanced Groove System(AGS).For pricing and availability of cut groove fittings in this size,contact your
nearest Victaulic sales office.
t Chinese standard sizes
Note:All fittings are ductile iron unless otherwise noted with an"sw"or"s"
5=Carbon Steel Direct Roll Groove(OGS)
SW=Carbon Steel Segmentally Welded
www.victaulic.com
�ctaul�c°
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.OO 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED.
ri�v a, �.,.�
CARBON STEEL PIPE-GROOVED FITTI�,`,;:` O�.O�
Grooved End Fittings
Reducing Tee r �t�E� ,� �toE� �F �toE� ,� �t°E�
N0. 25 Grooved Branch I � � ____ _ �
N0. 29T Threaded Branch � � � � � � �
� c i�� c ,�, c
co to co co
i E E :
1 y
N0.25 N0.29T N0.25-SW N0.29T-SW
1 1 3/a Z.255w Z245w 1.0 4 4 P/a S.00sw S.00sw 96
25 X X 20 57 57 OS 100 X 100 X 32 127 127 4.4
1 Ya 1 Ya 1 275sw 275sw 13 1 Yz 5.00 5.00 10.2
32 X 32 X 25 70 70 0.6 40 127 127 4.6
Pk P/z 3/a 2.75sw 275sw 15 2 5.00 5.00 11.2
40 X 40 X 20 70 70 0.7 50 127 127 5.1
1 2JSsw 2.75sw 15 2Yz 5.00 5.00 11.4
25 70 70 OJ 65 127 12l 52
P/a 2.755w 2755w 1.7 3 5.00 5.00 11.6
32 70 70 0.8 80 127 127 53
� 2 3/a 3.25 3.25 2.5 5 5 1 S.SOsw SSOsw 14.0
50 x 50 X 20 83 83 1.1 125 X 125 X 25 140 140 6.4
1 3.25 3.25 2J lYz SSOsw S.SOsw 143
ZS 83 83 L2 40 140 140 65
1Y4 3.25sw 3.25sw 1.8 2 SSOsw SSOsw 145
32 83 83 0.8 50 140 140 6.6
1 Yz 3.?_5 3.25 sw 3.0 2'h 550 550 sw 15.2
40 83 83 1.4 65 140 140 6.9
2Yz 2Yz 3/a 3JSsw 375sw 3.9 3 550 S.SOsw 16.6
65 X 65 X 20 95 95 1.8 80 140 140 7.5
1 3J5 3JSsw 3.8 4 550 S.SOsw 16J
25 95 95 1.7 100 140 140 7.6
lYn 375sw 375sw 4.2 6 6 1 650sw 650sw 73.0
32 95 95 1.7 150 X 150 X 25 165 165 10.4
1 Yz 375 3.75 3.9 1 Yz 650sw 6.SOsw 24.0
40 95 95 1.8 40 165 165 10.9
2 3J5 3JSsw 4.5 Z 6.50 6.50 Z1.6
50 95 95 2.0 50 165 165 9.8
3 3 3/a 4.25 sw 4.25 sw 57 2 Y� 6.50 6.50 21 4
80 x 80 X 20 108 108 2.6 65 165 165 11]
1 425 425 6.1 14-24 AGS�"For AGS fitting information,see publication 20.05
75 108 108 J_.8 350-600 v
t�in a.25 sw 4.25 sw S o +Contact Victaulic for details.
32 108 108 3.6
t�/� 4.z5 4.25 sw 6.5 Note:All fittings are duccile iron unless otherwise noted with an°sw"or"s"
40 108 108 2.9 S-Carbon Steel Direct Roll Groove(OGS)
z 4.z5 4.zs sw 6.z SW=Carbon Steel Segmentally Welded
50 108 108 2.8
IMPORTANT NOTE:
2Yz 4.25 4.ZSsw 6.4
65 108 108 �.9 No.29TThreaded Outlet Reducing Tees are supplied NPT and are available
4 4 3/� s.0osw S.oOsw g.o with British Standard threads.For British Standard specify'BSP"dearly
100 " 100 " z0 1z7 1z7 3.6 on order.
1 5.00 5.00 7.8
ZS 1Z7 127 3.5
www.victaulic.com
�ctaul�c'
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.OO 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED.
Ei,'.J1 ., .,,s
CARBON STEEL PIPE-GROOVED FITTING;`' O�.O�
Grooved End Fittings
Reducing Tee ,. �toE� ��-�toE� �F �toE� �� �toE�
N0. 25 Grooved Branch �
� - - � � � ,� � - - �
N0. 29T Threaded Branch � � � c C
to to lo to
E E E - E
r y � L
N0.25 N0.29T N0.25-SW N0.29T-SW
6 6 3 6.50 650 26.5 12 12 1 1000sw 1QOOsw 770
150 X 150 X 80 165 165 12.0 300 X 300 X 2S Z54 Z54 34.9
4 650 650 25.0 2 10.0(�sw 10.00sw 80.0
100 165 165 113 50 254 254 363
5 650 650 23.2 2'/z 10.00sw 10.00sw 78.0
125 165 165 105 65 254 254 35.4
6Yz 6'/z 3 6.50 650sw 24.0 3 10.00sw 10.00sw 82.0
165.1 X 165.1 X 80 165 165 10.9 SO 254 254 37.2
4 6.50 6.SOsw 25.0 4 t0.00sw 10.00sw 80.0
100 165 165 113 100 254 254 363
8 8 P/z 7.75sw 7JSsw 33.0 5 10.00sw 10.00sw 75.0
200 X 200 X 40 197 197 15.0 125 254 254 34.0
2 7.75sw 7.75sw 335 6 10.00sw 10.00sw 75.0
50 197 197 15.2 150 254 254 34.0
2Yz 7JSsw 7JSsw 39.0 8 10.00sw 10.00sw 80.0
65 197 197 177 200 254 254 363
3 7.75sw 775sw 33.6 10 10.00sw 10.00sw 84.0
80 197 197 152 250 254 254 38.1
4 7J5 775 41.8 N 14 14 4 11.00sw 11.00sw 102.0
100 197 197 19.0 350 x 350 X 100 279 279 463
5 7J5 sw 7J5 sw 34.0 6 11.00 sw 11.00 sw 108.2
125 197 197 15.4 150 D9 279 49.1
6 7J5 7J5 423 8 11.00 11.00 llZ.O
150 197 197 19.2 200 279 279 50.8
165.1 ���5 sw 7J5 sw 48.0 10 11.00 11.00 12Q0
197 197 21.8 300 279 279 54.4
10 10 1'/� 9.00 9.00 620 12 11.00 11.00 129.1
250 X 250 X 40 229 229 28.1 300 279 279 58.6
2 9.00sw 9.00sw 62.0 #16 16 4 13Q0
50 229 229 28.1 400 X 400 x 100 + + 59.0
Z Yz 9.00 sw 9.00 sw 62.4 14-24
65 229 Z29 283 350-600 v For AGS fitting information,see publication 20.05
3 9.00sw 9.00sw 60.0 +Contact Victaullc for details.
80 Z29 229 27.2
4 9.00sw 9.00sw 6i.o Note:All fittings are ductile iron unless otherwise noted with an°sw"or°s"
�00 229 229 2Z� S=Carbon Steel Direct Roll Groove(OGS)
5 9.00sw 9.00sw 52.o SW=Carbon Steel Segmentally Welded
i25 �7_9 �?9 23.6 �MPORTANT NOTE:
6 9.00sw 9.00sw 59.0
�50 229 �79 Z6.8 No.29T Threaded Outlet Reducing Tees are supplied NPT and are available
a 9.00sw 9.00sw 64.� with Brltish Standard threads.For Brltish Standard specify'BSP"dearly
200 229 229 293 on order.
#For roll grooved systems,Victaulic offers the Advanced Groove System(AGS).
For pricing and availability of cut groove fittings in this size,contact your
nearest Victaulic sales office.
www.victaulic.com
�ctaul�c°
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.OO 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED.
ri�v' l; �.s.'.;i .s
CARBON STEEL PIPE-GROOVED FITTI�,`,;:` O�.O�
Grooved End Fittings
Reducing Tee ,��toE� �� �toE�
N0. 25 Grooved Branch �
N0. 29T Threaded Branch � � � �
c C
to to
E F
� .
N0.25 N0.29T
A 16 16 6 12 00 sw 12.00 sw 1335 #20 ZO 16 1/25 288-6
400 X 400 x 1S0 305 305 60.6 500 X 500 400 438 13Q9
8 12.00 1200 145.0 18 17,25 297.0
200 305 305 65.8 450 438 1;4J
10 12.00 12.00 1495 N 24 24 8 20.00 20.00 340.0
250 305 305 67.8 600 X 600 X 200 508 508 154.2
12 12.00 12.00 154.0 10 20.00 20.00 343.9
300 305 305 699 250 508 508 156.0
14 12.00 sw 167.0 12 20.00 20.00 352.8
350 305 75.8 300 508 508 160.0
8 18 18 4 1550sw 15.50 sw 194.0 14§ 20.00 360.0
450 X 450 X 100 394 394 88.0 350 508 1633
6 i550sw i550sw 200.0 16 20.00 378.0
150 394 394 90.7 400 SOS 1715
8 1550sw 1550sw 202.0 18§ 20.00 380.0
200 394 394 91.6 450 508 172.4
10 1550 15.50 212.0 20 20.00 _ 373.0
250 394 394 96.2 500 508 169.2
12 1550 15.50 272.6 14-24 qG$'�For AGS fitting information,see publication 20.05
300 394 394 101.0 350-600 v
14 15.50 730.1 +Contact Victaulic for details.
350 394 104.4
�6 ts.so z4z6 Note:All fittings are ductile iron unless otherwise noted with an°sw"or"s"
400 394 1123 S-Carbon Steel Direct Roll Groove(OGS)
u 20 20 6 i7.25 »25 z4o.o SW=Carbon Steel Segmentally Welded
500 X 500 X 150 438 438 108.9
8 iZ25 17.25 Z44.o IMPORTANT NOTE:
200 438 43a ��o� No.29TThreaded Outlet Reducing Tees are supplled NPT and are available
10 t7.25 �7.25 z56.o with British Standard threads.For British Standard specify'BSP"dearly
250 438 438 116� onorder.
�2 i7.25 �z25 z64.o #For roll grooved rystems,Victaulic offers the Advanced Groove System(AGS).
300 438 438 p98 For pricing and availability of cut groove fittings in this size,contact your
14 i7.�5 z75.o nearest Vlctaulic sales office.
350 43� - tz4.� §Cast fitting avallable.Contact Victaulic for details.
www.victaulic.com
�ctaul�c'
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.OO 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED.
Ei,'.J1 �. .,,s
CARBON STEEL PIPE-GROOVED FITTING;`' O�.O�
Grooved End Fittings
Bullhead Tee �to Bull Plug
�EOR-�
N0. 2l N0. 61 �.- E to E ���
?
c to �
EOB
y
NO.21
N0.61
5 5 S 7J5 5.50 28J
x x 2 2_3/5 400 23
125 125 Z00 197 140 13.0 50 603 102 1.1
6 6 8 7J5 6.50 37.5
x x 2Y� 2.875 5.00 3.0
150 150 200 197 165 17.0 65 73.0 lZ7 1.4
NoTe:All fittings are ducTile iron unless otherwise noted with an"sw°or"s"� 3 3500 6.00 45
5=Carbon Steel Direct Roll Groove(OGS) 80 88.9 152 �.0
SW=Carbon Steel Se mentall Welded 4 asoo Zoo �5
9 Y 100 1143 178 3.4
5 5563 8.00 12.0
125 1413 203 5.4
6 6.625 10.00 17.0
150 1683 254 7J
IMPORTANT NOTES:
Steel dish caps available through 24"/600 mm,contact Victaulic.
No.61 Bull Plugs should be used in vacuum service with Style 72 or 750 couplings
Note:All fittings are ductile iron unless otherwise noted with an"sw"or"s"
S=Carbon Steel Direct Roll Groove(OGS)
SW=Carbon Steel Segmentally Welded
www.victaulic.com
�ctaul�c°
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.OO 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED.
ri�v �a. ".0 �
CARBON STEEL PIPE-GROOVED FITTI�,`,;:` O�.O�
Grooved End Fittings
45° Lateral � I
NO. 30 C to �
�E i �
i
�
� I� o�
C to I �'�
SE . �� ��
N0.30
� �
��� �'�_ 4 ..I �3 �
i 5 a i� 5;�� a t p :: j
w � i�, u_` `� .� �i> >1 " � l„� .
�; t t� � i c' m
3/a 1.050 450 2.00 1.0 6 6.625 14.00 450 43.6
20 26.9 ll4 51 OS 150 1683 356 114 19.8
1 1315 5.00 2.25 1.7 8 8.625 18.00 6.00 72.0
25 33J 1D 57 0.8 Z00 219.1 457 152 32J
1�/a 1.660 575 250 25(d) 10 10.750 2050 650 105.0
32 424 146 64 1.1 250 273.0 521 165 47.6
1 Y� 1.900 6.25 2.75 3.5 12 12J50 23.00 7.00 165.0
40 483 159 70 1.6 300 323.9 584 V8 74.8
2 2375 7.00 2.75 4.6(d) 14# 14.000 2650 750 276.0
50 603 178 70 2.1 350 355.6 673 191 125.2
2Y� 2.875 7J5 3.00 9.0 16#I 16.000 29.00 8.00 344.2
65 73.0 197 76 94.1 400 406.4 737 203 156.1
76.1 mm 3.000 8.50 3.25 11.0 18# 18.000 32.00 850 429.0
76.1 216 83 5.0 450 457.0 813 216 194.6
3 3500 850 3.25 llJ(d) 20# 20.000 35.00 9.00 500.0
80 88.9 216 83 5.4 500 508.0 889 229 226.8
3 Y� 4.000 10.00 350 17.8 24# 24.000 40.00 10.00 715.0
90 101.6 254 89 8.1 600 610.0 1016 254 3243
4 4500 1050 3.75 22.2(d) 14-24 AG$'" For AGS fitting information,see publication 20.05
100 ll 43 267 95 10.1 350-600 v
5 5.563 �2.50 4.00 21.8 #For roll grooved systems,Victaulic offers the Advanced Groove System
125 1413 318 102 9.9
(AGS).For pricing and availability of cut groove fittings in thls size,contact
6.500 14.00 4.50 43.6
165.1 mm 165.1 356 114 �qg your nearest Victaulic sales offlce.
Note:All fittings are segmentally welded steel unless otherwise noted with
a(d)for ducTile iron.
www.victaulic.com
�ctaul�c'
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.OO 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED.
V'i.�iJb --� ,�.
CARBON STEEL PIPE-GROOVED FITTING;`' O�.O�
Grooved End Fittings
45° Reducing Lateral
N0. 30-R � �
c to j ��
LE � / �,
l i �.`�'
- �o
C to L
S E �r'
0
N0.30-R
:� • c� •
3 3 2 8.50 325 9.8 #lA 14 4 26.50 7.50 172.0
80 X SO X 50 216 83 4.4 350 X 350 X 100 673 191 78.0
2'/� 850 3.25 9.8 6 2650 7.50 187.0
65 216 83 4.4 150 673 191 84.8
4 4 2 10.50 3J5 10.0 8 2650 7.50 205.8
100 X 100 X 50 267 95 4.5 Z00 673 191 93.4
2Yz 1050 375 10.0 10 2650 750 235.0
65 267 95 45 250 673 191 106.6
3 1050 3J5 183 12 26.50 7.50 250.0
80 267 95 83 300 673 191 113.4
5 5 2 1Z50 4.00 24.0 #16 16 6 29.00 8.00 215.0
125 X 125 X 50 318 102 10.9 400 X 400 X 150 737 203 97.5
3 1250 4.00 27.0 8 29.00 8.00 2525
80 318 102 2122 200 737 203 1145
4 12.50 4.00 Z6.5 10 29.00 8.00 265.0
100 318 102 12.0 250 737 203 12Q2
6 6 3 14.00 4.50 37.0 12 29.00 8.00 295.0
150 x 150 X 80 356 114 16.8 300 737 203 133.8
4 14.00 4.50 36.0 14 29.00 8.00 305.0
100 356 114 163 350 737 203 1383
5 14.00 4.50 44J #18 1S 6 32.00 850 274.0
125 356 114 203 450 X 450 X 150 813 216 1243
8 8 4 18.00 6.00 62.0 8 32.00 8.50 275.0
200 x 200 X 100 457 152 28.1 200 813 216 1247
5 18.00 6.00 75.5 12 32.00 8.50 347.0
125 457 152 34.2 300 813 Z16 157.4
6 18.00 6.00 82.0 14 32.00 8.50 350.0
150 457 152 3Z2 350 813 216 158.8
10 10 4 Z0.50 6.50 104.8 16 32.00 8.50 36Z.0
250 x 250 X 100 521 165 147.5 400 813 z16 164.2
5 ZOSO 6.50 99.0 #20 20 12 35.00 9.00 415.0
125 521 165 44.9 500 X 500 X 300 889 229 188.2
6 7_OSO 6.50 105.8 14 35.00 9.00 420.0
150 521 165 48.0 350 889 229 1905
8 20.50 6.50 118.0 16 35.00 9.00 425.0
Z00 521 165 53.5 400 889 2�9 192.8
12 12 5 23.00 7.00 122.0 #24 24 16 40.00 10.00 425.0
300 X 300 X 125 584 178 553 600 X 600 X 400 1016 254 192.8
6 23.00 Z00 13Z0 20 4Q00 10.00 570.0
150 584 178 62.1 600 1016 254 258.6
8 23.00 7.00 147.0 14-24 qG$'For AGS fitting information,see publication 20.05
200 584 178 66J 350-600 v
10 23.00 7.00 167.0
250 584 178 75.g # For roll grooved systems,Victaulic offers the Advanced Groove System
(AGS).For pricing and availability of cut groove fittings in Yhis size,contact
your nearest Vlctaulic sales office.
Note:All fittings are segmentally welded steel unless otherwise noted a(d)
for ductile iron.
www.victaulic.com
�ctaul�c°
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.OO 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED.
ii��' �a. ,..,..� �
CARBON STEEL PIPE-GROOVED FITTI�,`,;:` O�.O�
Grooved End Fittings
Tee Wye
NO. 32 � I / - �
H � �
/ E�
';�='- �
�_ � _ __
�
�
I� E�
N0.32
2 2 2 2J5 7.00 9.00 4.63 6.4 5 5 5 400 12.50 16.13 10.00 48.0
50 X 50 X 50 70 178 229 118 Z.9 125 X 125 X 125 102 318 410 254 21.8
2'/z 2Yz 2Yz 3.00 7J5 10.50 5J5 11.5 6 6 6 4.50 14.00 18.25 11.50 60.5
65 x 65 X 65 76 197 Z67 146 5.Z 150 X 150 X 150 114 356 464 Z9Z 274
3 3 3 3.25 850 11.50 6.50 143 8 S 8 6.00 18.00 23.25 15.25 127.1
80 X 80 X 80 83 �16 292 165 6.5 200 X 200 X 200 152 457 591 387 57J
3'/z 3Yz 3Yz 3.25 10.00 13.00 7J5 22.9 10 10 10 6.50 2Q50 27.25 18.00 190.0
90 x 90 X 90 89 254 330 197 10.4 250 X 250 X 250 165 521 692 457 186.2
4 4 4 3J5 10.50 13.63 8.13 26.0 12 12 12 7.00 23.00 31.00 20.50 240.0
100 X 100 X 100 95 267 346 207 11.8 300 X 300 X 300 178 584 787 521 108.9
Note:All fittings are ductile iron unless otherwise noted with an"sw"or"s"
S=Carbon Steel Direct Roll Groove(OGS)
SW=Carbon Steel Segmentally Welded
www.victaulic.com
�ctaul�c'
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.OO 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED.
V'i.�iJb � ,�.
CARBON STEEL PIPE-GROOVED FITTING;`' O�.O�
Grooved End Fittings
Adapter Nipple
�-EtaE-� �- EtoE-�
N0. 40 Grv. x Thd. � �
N0. 42 Grv. x Bev.
N0.43 Grv. x Grv.
N0.40' N0.43
�-ETOE-�
�
N 0 47_
.� .� .� .�
3/a 1.050 3.00 03 6 6,625 6.00 95
20 26.9 76 0.1 150 1683 152 43
1 1315 3.00 0.4 8 8.625 6.00 14.2
25 33J 76 0.2 200 219.1 152 6.4
P/a 1.660 4.00 0.8 10 10.750 8.00 27.0
32 42.4 102 0.4 250 273.0 203 12.2
P/� 1.900 4.00 0.9 17 1JJ50 8.00 33.0
40 483 102 0.4 300 323.9 203 15.0
2 2375 4.00 �.2 *Available with British Standard Pipe Threads,specify'BSP"dearly on order.
50 603 102 OS
IMPORTANT NOTES:
2Yz 2.875 4.00 1.9
65 73.0 102 09 For pump package nipples with 1'/z°/40mm hole cut to receive Style 923
3 3500 4.0o Z,5 Vic Let or Style 924 Vic O Well request special No.40,42 or 43 nipples
80 88.9 �02 i.t and specify No.40-H,42-H or 43-H on order.NOTE 4-12"/100-300 mm
3v� 4.000 4.0o Z.� diameter-8"/200mm minimum length required.
90 101.6 i02 0.9 #For roll grooved systems,Victaulic offers the Advanced Groove System
4 4.soo 6.0o ss (AGS).For prlcing and availability of cut groove fittings in this size,contact
100 u43 �52 2.5 your nearest Vlctaulic sales office.
s 5563 6.00 �.4 Note:All fittings are ductile iron unless otherwise noted with an"sw"or"s"
�25 1413 152 3�4 S=Carbon Steel Direct Roll Groove(OGS)
SW=Carbon Steel Segmentally Welded
www.victaulic.com
�ctaul�c°
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.OO 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED.
ri�v a, ..,.� ,
CARBON STEEL PIPE-GROOVED FITTI�,`,;:` O�.O�
Grooved End Fittings
Cap �T
NO. 60 ���
\
N0.60
.� .�
_ II �I�I�
'/� 1.050 0.88 0.2 6 0.675 1.00 6.1
20 26.9 22 0.1 150 1683 25 2.8
1 1315 0.88 03 8 8.625 1.19 13.1
25 33.7 22 0.1 200 219.1 30 5.9
1 Ya 1.660 0.88 03 10 10J50 1.25 J_1.0
32 42.4 22 0.1 250 273.0 32 95
P/z 1.900 0.88 QS 12 12J50 1.Z5 35.6
40 483 22 0.2 300 323.9 32 16.2
z 2375 0.88 Q6 14#(s) 14.000 9.50 �
50 603 22 03 350 355.6 241
2 Yz 2.875 0.88 1.0 16#(s) 16.000 10.00 „
65 73.0 22 OS 400 406.4 254
76.1 mm 3.000 0.88 L2 18 N(s) 18.000 11.00 „
76.1 22 0.5 450 457.0 279
3 3.500 0.88 L2 20 ik(s) 20.000 12.00 ,
80 88.9 22 0.5 500 508.0 305
3 Yz 4.000 0.88 2.5 24#(s) 24.000 1350 ,
90 101.6 22 1.1 600 610.0 343
108.0 mm 4.Z50 1.00 23 14--24 qGS" For AGS fitting information,see publication 20.05
108.0 25 1.0 350-600 v
4 4.500 1.00 2.5
100 �143 z5 1.1 IMPORTANT NOTES:
�33.omm 5.250 �.o0 4s *Steel dish caps available through 24'Y600mm,contact Victaulic.
133.0 25 Z.o No.60 cap is not suitable for use in vacuum service with Style 72 or 750 couplings.
�39.�mm ssoo too 4.5 No.61 bull plugs should be used,see pg.35.
139J 25 2.0
#For roll grooved systems,Victaulic offers the Advanced Groove System
5 5.563 1.00 4.6
�25 �4t3 zs �_� (AGS).For pricing and availability of cut groove fittings in this size,contacY
6.z50 1.00 6.8 Your nearest Victaulic sales offlce.
�59.omm �s�.o zs 3.i Note:All fittings are ductile iron unless otherwise noted with an°sw"or"s"
165.1 mm 6.500 1.00 7.3 S=Carbon Steel Direct Roll Groove(OGS)
�65.i zs 33 SW=Carbon Steel Segmentally Welded
www.victaulic.com
�ctaul�c'
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.OO 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED.
Ei,.Jb _c „s
CARBON STEEL PIPE-GROOVED FITTING;`' O�.O�
Grooved End Fittings
Flanged Adapter Nipple �� EtoE� �� EtoE-. �- EtoE-. i� EtoE� �- EzoE-�
N0. 41 ANSI Class 125(Cast Iron)
N0. 45F ANSI Class 150 Flat Face
N0.45R ANSI Class 150 Raised Face
N0.46F ANSI Class 300 Flat Face
N0.46R ANSI Class 300 Raised Face
N0.41 N0.45F N0.45R N0.46F N0.46R
� ' ��
i.0�0 3 3 Z3 3 33
ZO 26.9 76 76 1.0 76 1 S
1 1315 3 2.5 3 2J 3 3.9
25 33J 76 1.1 76 L2 76 1.8
lYa 1.660 4 3.0 4 33 4 4.8
32 42.4 102 1.4 102 LS 102 2.2
P/z 1.900 4 35 4 3.9 4 6.9
40 483 102 1.6 102 1.8 102 3.1
2 2375 4 5.5 4 6.2 4 8.2
50 603 102 2.5 102 2.8 102 3.7
ZYz 2.875 4 8.0 4 99 4 11.9
65 73.0 102 3.6 lOZ 4.5 102 5.4
3 3.500 4 9.5 4 ll.4 4 16.5
80 88.9 lOZ 43 lOZ 5.2 lOZ 7.5
3�/z 4.00 4 12.0 4 15.1 4 20.1
90 101.6 102 5.4 102 6.8 102 9.1
4 4500 6 16.7 6 18.4 6 27.4
100 1143 152 7.6 152 83 152 12.4
5 5563 6 21.5 6 213 6 353
125 1413 152 9.8 152 9J 152 16.0
6 6.625 6 26.5 6 27.5 6 47.5
150 1683 152 12.0 152 12.5 152 21.5
8 8.625 6 39.0 6 413 6 703
200 219.1 152 17J 152 18.8 152 31.9
10 10.750 8 57.0 8 59.8 8 100.8
250 273.0 203 259 203 27.1 203 45J
12 12J50 8 41.0 8 88.2 8 1462
300 3Z39 203 18.6 203 40.0 Z03 663
14# 14.000 8 8 8
350 355.6 203 203 + 203 +
16# 16.000 8 8 8
400 406A 203 203 + 203 +
18# 18.000 8 8 8
450 457.0 203 203 + 203 +
7_0# 20.000 8 8 8
500 508.0 203 203 � 203 +
24 7t 24.000 8 8 8
600 610.0 203 z03 + 203 +
350-600 v For AGS fitting information,see publication 20.05
IMPORTANT NOTES:
+Contact Vlctaulic for details.
Flanged adapter nipples are supplied with standard rolled grooves.
Standard cut grooves or machining for rubber lining are optionally available Contact Victaulic for details.
#For roll grooved systems,Victaulic offers the Advanced Groove System(AGS).For pricing and availability of cut groove fittings in this size,contact your
nearest Victaulic sales office.
Note:All fittings are ductile iron unless otherwise noted with an"sw"or"s"
S=Carbon Steel Direct Roll Groove(OGS)
SW=Carbon Steel Segmentally Welded
www.victaulic.com
�ctaul�c°
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.OO 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED.
ri�v a. ....�, �
CARBON STEEL PIPE-GROOVED FITTI�,`,;:` O�.O�
Grooved End Fittings
Swaged Nipple
N0. 53 Grv. x Grv. Etot � r- EtoE�
N0. 54 Grv. x Thd.
N0. 55 Thd. x Grv. � �
N0.53 N0.55
r- EtaE�
IIII
N0.54
. i� k
, .; ,-.
� :� '
ai:�
_ '��' ���..
2 1 650 ZO 4 3 9.00 7.5
50 X 25 165 0.9 100 X 80 229 3.4
P/a 650 2.0 3'/z 9.00 7.5
32 165 0.9 90 229 3.4
1'/z 650 2.0 5 2 11.00 115
40 165 0.9 125 X 50 279 5.2
2'/z 1 7.00 3.0 3 11.00 113
65 X 25 178 1.4 80 279 5.1
1 Ya 7.00 3.0 4 11.00 11.5
32 178 1.4 100 279 5.2
1 Yz 7.00 3.0 6 1 1 Z.00 17.0
40 178 1.4 150 X 25 305 7J
2 7.00 3.0 1 Ya 12.00 17.0
50 17S 1.4 32 305 7J
3 x 1 8.00 45 P/z 12.00 1 Z2
80 25 203 2.0 40 305 7.8
1 Ya 8.00 4.5 2 12.00 17.4
32 Z03 2.0 50 305 7.9
1 Y� 8.00 4.4 2 Yz 12.00 17.4
40 203 2.0 65 305 7.9
2 8.00 4.5 3 1290 11.4
50 203 2.0 80 305 7.9
2Y� 8.00 4.5 3Yz 12.00 17.4
65 203 20 90 305 7.9
3 Yz 3 8.00 6.8 4 12.00 175
90 X 80 203 3.1 100 305 7.9
4 1 9.00 75 4 Yz 12.00 175
100 X 25 229 3.4 120 305 7.9
1 Ya 9.00 75 5 12.00 175
32 229 3.4 125 305 7.9
1 Yz 9.00 75 8 6 20.0
40 229 3.4 200 X 150 + 9.1
2 9.00 75 +Contact Victaulic for details.
so 229 3.4 Note:All fittings are ductile iron unless otherwise noted with an"sw"or"s"
4 2vz 9.00 7�5 S=Carbon Steel Direct Roll Groove(OGS)
100 X 65 229 3.4
SW=Carbon Steel Segmentally Welded
www.victaulic.com
�ctaul�c'
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.OO 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED.
fid.'J1 �-l. .�,s
CARBON STEEL PIPE-GROOVED FITTING;`' O�.O�
Grooved End Fittings
Female Threaded Adapter Hose Nipple
N0. 80 E to� N0. 48
EtoE- -.�
�
�
N0.80 N0. 4S
:�
'/ 1.050 Z00 1.0 1.050 3.12 0.3
20 26.9 51 OS 20 26.9 79 01
1 1315 2.06 1.0 1 1315 338 0.4
25 33J 52 0.5 25 33J 86 Q2
1 Ya 1.660 231(sw) LS 1%a 1.660 3.88 0.6
32 42.4 59 OJ 32 42.4 98 03
1'/z 1.900 Z31(sw) LS 1 Yz 1.900 3.88 0.8
40 483 59 OJ 40 483 98 0.4
2 2375 �.50 1.4 2 2375 4.50 1.1
50 603 64 0.6 50 603 114 0.5
2Yz 2.875 2J5 LS 2Yz 2.875 538 2.0
65 73.0 70 OJ 65 73.0 137 0.9
3 3.500 2J5 �9 3 3.500 5J5 3.2
80 88.9 70 13 80 88.9 146 LS
4 4.500 3.25 45 4 4.500 7.00 4.9
100 1143 83 2.0 100 1143 178 Z2
Note:All fiCtin s are ductile iron unless otherwise noted with an°sw"or"s"� 5 ss63 s.�s s.o
g 125 1413 Z22 3.6
5=Carbon Steel Direct Roll Groove(OGS) 6 6.625 10.12 143
SW=Carbon Steel Segmentally Welded �so �6s3 zs� 6.5
IMPORTANT NOTE: 8 8.625 11.88 Z4.7
200 219.1 302 lt2
Available with British SYandard Pipe threads,specify'BSP"dearly on order. �o io75o tzso 40.1
Z50 273.0 31S 18.2
12 1ZJ50 14.50 62.0
300 323.9 368 25.1
Note:All fittings are ductile iron unless otherwise noted with an"sw"or"s"
S=Carbon Steel Direct Roll Groove(OGS)
SW=Carbon Steel Segmentally Welded
www.victaulic.com
�ctaul�c°
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.OO 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED.
ri�v a, .�,.� .
CARBON STEEL PIPE-GROOVED FITTI�,`,;:` O�.O�
Grooved End Fittings
Concentric/Eccentric Reducer
N0. 50 Concentric E
N0. 51 Eccentric r t°�"� I�E co E->I I�-E co E I
�IF E to E-> � �
Fabricated Steel Fabrir,ated Steel
N0.50 N0.�l No.50 No.51
� �
I
1 Ya 3/4 1.9 3Yz 3 250 2.0 9.SOsw 7.0
32 X 20 + 0.9 90 X 80 64 09 241 3.2
1 1.9 4 1 3.00 3.0 13.00sw 6.5
25 + 0.9 100 X 25 76 1.4 330 2.9
P/z 3/a L4 1 Ya 4.6
40 X 20 + 0.6 32 + 2.1
1 2.50 0.8 8.SOsw 45 P/z 3.00sw 2.6 10.00sw 8.1
ZS 64 0.4 Z16 2.0 40 76 L2 254 3J
lYa 250 1.0 2 3.00 2.4 4.00 33
32 64 QS 50 76 1.1 102 1.5
2 3/a 250 0.9 9.00sw Z.0 2Yz 3.00 2J 4.00 3.4
50 X 20 64 03 229 0.9 65 76 L2 102 15
1 2.50 OJ 9.00 sw 23 3 3.00 3.2 4.00 3.5
25 64 03 229 1.0 80 76 1.4 102 1.6
l Ya 250 L2 9.00sw ��.6 3Yz 3.00 2.9 10.00sw 8.0
32 64 OS 229 2.1 90 76 13 254 3.6
l Yz 350 1.0 350 1.1 5 2 11.00sw 9.0 11.00sw 5.2
40 89 OS 89 OS 125 X 50 279 4.1 279 2.4
ZYz 3/a 13 33 2Yz 4.00 43 11.00sw 10.8
65 X 20 + 0.6 + 1.5 65 102 2.0 279 4.9
1 2.50 1.1 9.50 3.5 3 4.00 55 11.00sw il.i
ZS 64 OS Z41 1.6 80 102 25 279 5.0
1'/a 3.50 33 350 1.4 4 350 43 5.00 1Z0
32 89 15 89 °� 100 89 1.9 127 5.4
1Yz 250 3.6 950sw 3J 6 1 4.00 5.0 1150sw 145
40 64 1.6 241 1 J 150 X 25 102 23 292 6.6
2 250 3.9 350 43 P/z 55
50 64 1.8 89 2.0 40 � 2 5 � �
3 3/a 15 45 2 4.00 6.6 1150 sw 145
80 X 20 + OJ + Z.0 50 102 3.0 292 6.6
1 250 13 950sw 4.S 2Yz 4.00 6.4 ll50sw 14.2
25 241 0.6 241 2.2 65 102 29 292 6.4
1'/a 250 1.4 4.8 3 4.00 6.4 5.50 15.0
32 64 0.6 { 2.Z 80 102 29 140 6.8
lYz 250 5.1 950sw 5.1 4 4.00 6.5 550 17.0
40 64 23 241 23 100 102 2.9 140 7J
2 2.50 1.6 3.50 6.0 5 4.00 6.4 5.50 17.0
50 64 OJ 89 2J 125 102 2.9 140 7J
2Yz 250 1.8 3.50 7.0 8 2Yz 16.00 7.9 12.00sw 26J
65 64 0.8 89 3.Z 200 X 65 406 3.6 305 11.8
76.1 2�50 2.1 3 5.00 93 12.00sw 22.0
64 1.0 80 127 42 305 10.0
Note:All fittings are ductile iron unless otherwise noted with an"sw"or"s"
S=Carbon Steel Direct Roll Groove(OGS)
SW=Carbon Steel Segmentally Welded
www.victaulic.com
�ctaul�c'
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.OO 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED.
fit.;ii ct „�
CARBON STEEL PIPE-GROOVED FITTING;`' O�.O�
Grooved End Fittings
Concentric/Eccentric Reducer
N0. 50 Concentric t
�[oE� I<-EtoE�l �-ETOE�
N0. 51 Eccentric < E to E � � �
L11�1J
Fabricaled Steel Fahricaled Sleal
N0.50 NO_5l No.50 No_5]
� .�
8 � 5.00 10.�1 1Z.00sw 23.0 �1& x 12 1500 91 0 15.00 91.0
200 X 100 127 4.8 305 10.4 450 300 381 413 3£31 4�13
5 5.00 11.6 12.00sw Z3.0 14 15.00 91.0 15.00 91.0
125 127 5.2 305 10.4 350 381 413 381 413
6 5.00 11.9 6.00 24.0 16 15.00 91.0 15.00 91.0
150 127 5.4 152 10.9 400 381 413 381 413
10 4 6.00 19J 13.00 sw 32.0 #20 10 20.00 110.0 20.00 177.0
250 X 100 152 8.9 330 14.5 500 X 250 508 49.9 SOS 803
5 343 34.6 12 20.00 120.0 20.00 120.0
1Z5 + 15.6 + 15J 300 508 54A 508 54.4
6 6.00 20.0 13.00 sw 36.9 14 20.00 149.0 20.00 149.0
150 152 9.1 330 16J 350 508 67.9 508 67.9
8 6.00 22.0 7.00 21.6 16 20.00 120.0 20.00 120.0
200 152 10.0 178 9.8 400 508 54.4 508 54.4
12 4 44.0 14.00sw 48.0 18 20.00 136.0 Z0.00 136.0
300 X 100 + 20.0 356 21.8 450 508 61J 508 61J
6 7.00 24.6 14.00sw 50.0 #24 10 20.00 142.0 20.00 142.0
150 178 lt2 356 22J 600 X 250 508 64.4 508 64.4
8 7.00 52.0 14.00sw 535 12 20.00 150.0 z0.00 150.0
200 178 23.6 356 243 300 508 68.0 SOS 68.0
10 7.00 39.0 14.00sw 57.0 14 20.00 1620 20.00 1620
250 178 17J 356 Z5.9 350 508 73.5 SOS 735
#14 6 13.00 65.0 13.00 60.0 16 20.00 162.0 20.00 1620
350 X 150 330 Z9.5 330 27.� 400 508 735 508 735
8 13.00 65.0 13.00 60.0 18 20.00 162.0 20.00 1620
200 330 29.5 330 �7.2 450 508 73.5 SU8 735
10 13.00 66.0 13.00 65.0 20 20.00 151.0 20.00 190.0
250 330 29.9 330 29.5 500 508 685 508 86.Z
12 13.00 65.0 13.00 66.0 350-600 v For AGS fitting information,see publication 20.05
300 330 30.8 330 29.9
#16 8 14.00 73.0 14.00 73.0
400 X 200 356 33.1 355 33.1 + Contact Victaulic for details.
10§ 14.00 73.0 14.00 73.0 � Available with male threaded small end No.52.
Z5o 356 33.1 355 33.1 Note:All fittings are ductile iron unless otherwise noted with an"sw"or°s"�
12 14.00 73.0 14.00 73.0 S=Carbon Steel Direct Roll Groove(OGS)
300 356 33.1 355 33.1 SW=CaYbOn Steel Segmentdlly Welded
14 14.00 73.0 14.00 73.0
350 356 33.1 355 33.1 IMPORTANT NOTE:
#�a �o �s.00 9to �s.00 9to Steel eccentric reducers available through 30'Y750mm,contactVictaulic for
450 X 250 381 413 381 413 dimensions.
#For roll grooved rystems,Victaulic offers the Advanced Groove System
(AGS).For prlcing and availability of cut groove fittings in this size,contact
your nearest Victaulic sales office.
§Cast fitting available for JIS size.Contact Victaulic for details.
www.victaulic.com
�ctaul�c°
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.OO 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED.
ri�v a, v,..a �
CARBON STEEL PIPE-GROOVED FITTI�,`,;:` O�.O�
Grooved End Fittings
Small Threaded Reducer
N0. 52 E E
�toF�I �toF�I
II
N0.52 N0.52F
� pi ai f i; -+' I r -..E. . �
9j � ,S �
-�^� ,. 1. _ �_ ... , ..
lYz 1 250 0.8 4 2% 3.00 2.6
40 X 25 64 0.4 100 X 65 76 L2
P/a 250 0.9 3 3.00 25
32 64 0.4 80 76 1.1
2 3/a 250 0.9 108 x AZ.A 76.2 13 76.2 132
50 X 20 64 0.4 483 76Z 13 76Z 135
1 2.50 OJ 60 76.2 139
25 64 03 11�1�3 x 47,4 76.2 13 76.J_ 130
1'/a 2.50 1.2 483 76.2 13 76.2 134
32 64 OS 60 76.2 1.40
1 Yz 2.50 1.0 5 4 45
40 64 0.5 125 X 100 + 2.0
2 Y� 1 2.50 1.1 133 x 60 1143 217
65 X 25 64 0.5 139 x 60 1143 ?.?6
1'/4 250(sw) 1.2 6 1 4.00 55
32 64 0.5 150 X 25 102 25
1'/a 250(sw) 13 2 4.00 5J
40 64 0.6 50 102 2.6
2 3.00 14 2Yz 4.00 5.8
50 76 0.6 65 102 2.6
76.1 x 483 63.5 0.8 635 OJ7 3 4.00 5.8
60 63.5 0.85 80 102 2 6
3
80 X 20 +(sw) O7 100 +(sw) �.9 - -
1 2.50 13 5 2.0
25 64 0.6 125 -�-�SW� 0.9 - -
1'/a 2.50 15 159 x 4Z 4 1143 2.2 1143 2.45
32 64 OJ 483 1143 2.2 1143 2.51
1 Ya 250(sw) 15 60 1143 Z.60
40 64 OJ 165.1 x 424 101.6 2.4 101.6 290
2 250 1 S 483 101.6 Z.6 101.6 2.95
50 64 OJ 60 101.6 3.00
2 Yz 2.50 2.4 8 2 16.00 15
65 64 1.1 200 X 50 406 OJ
88.9 x 42.4 63.5 0.9 635 0.82 2�/z 16.00 1]
483 635 0.9 63.5 0.85 65 406 0.8
60 63.5 0.89
4 1 3.0o Z3 + Contact Victaulic for details.
�oo X zs 76 1.o Note:All fittings are ductile iron unless oTherwise noted with an"sw"or"s"
1 Vz 3.0o Z_7 S=Carbon Steel Direct Roll Groove(OGS)
40 �6 1.z SW=Carbon Steel Segmentally Welded
z 3.0o z.6 IMPORTANT NOTE:
50 76 1.�
Avallable with British Standard Pipe Threads,specify"BSP"dearly on order
www.victaulic.com
�ctaul�c'
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.OO 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED.
fit.;ii c-; „s
_,:.� :.. � � � �
�..�.r;�i..�... �.�� �u W�+��W.�:�
INSTALLATION Reference should always be made to the I-100 Victaulic Field Instailation Handbook for the product you
are installing. Handbooks are included with each shipment of Victaulic products for complete
installation and assembly data,and are available in PDF format on our website at www.victaulic.com.
WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details.
NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be
installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the
right to change product specifications,designs and standard equipment without notice and without
incurring obligations.
UPDATED 12/2011
07.01 1449 REV Q I�.tc�V�I C.�
VICTAULIC IS A REGISTERED TRA�EMARK OF VICTAULIC COMPANY.OO 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED.
�;.✓i
�M I F�� 1 DIELECTRIC NIPPLES
Specification: MIFAB`�Series MI-DE (specify size and connection type) galvanized steel dielectric nipples with plastic liner,
designed and tested for use at temperatures up to +225 degrees F and for pressures up to 425 PSI.
Function: Used to protect the plumbing system through the steel to plastic design that provided a dielectric waterway in all
potable water and appropriate HVAC applications. Dissimilar metals are separated in the waterway eliminating the local galvanic
cell. The metal to metal connection design maintains external electrical continuity to prevent stray current corrosion.
GALVANIZED STEEL
NIPPLE
PLASTIC LINER
- �,
_ � ,y '�
�
`z . �. - -�' ,
:�Y
� �� ,
�'
�„,
.
� �
MODEL NIPPLE NIPPLE CONNECTION
NUMBER LENGTH DIAMETER TYPE
MI-DETT-50 _ 3" (76) 1/2" (13) THREADED X THREADED
MI-DETT-75 3" 76 3/4" 19 THREADED X THREADED
MI-DETT-100 4" (102) 1" (25)_ THREADED XTHREADED
MI-DETT-125 4" 102 1 1/4" 32 THREADED XTHREADED
MI-DETT-150 4" (102) 1 1/2" (38) THREADED XTHREADED
MI-DETT-200 4" 102 2" 52 THREADED X THREADED
MI-DETT-250 _ � 6" (152) 21/2" (65) THREADED XTHREADED
MI-DEGT-100 4" 102 1" 25 GROOVED XTHREADED
MI-DEGT-125 4" 102 1 1/4" 32 GROOVED XTHREADED
MI-DEGT-150 4" 102 1 1/2" 38 GROOVED XTHREADED
MI-DEGT-200 4" 102 2" 52 GROOVED X THREADED
MI-DEGT-250 6" 152 21/2" 65 GROOVED XTHREADED
MI-DEGG-200 4" 102 2" 52 GROOVED X GROOVED
MI-DEGG-250 6" 152 2 1/2" 65 GROOVED X GROOVED
Job Name Page No:
Section No: Contractor
Schedule No: Purchase Order No:
MIFAB reserves the right to make changes in material and design without�mmal notice and obligation. USA:1-800-465-2736 www.mifab.COm CAN:1-800-387-3880
Page CI10 A
� 0�
�
514
OFFSET � --
C.P.V.C. - STEEL - COPPER #905/#906 •�'
� :
HANGER �� '
�
;
���� �
f"
. ,
, r
, ;
�
l
� ������ �
�
Hanger/Restrainer o
SIZE-3/4"thru 2"pipe.
MATERIAL-Carbon Steel.
FINISH- Mil. Galvanized.. �
LISTINGS-
c u�us EX 4231,EX 2551
PATENT-No.6,648,278. � o Stabilize-only
FUNCTION-Use on C.P.V.C.,Copper or Steel pipc.
Hanger and restrainer on top,bottom or side position. � ������� a����� � � �°���������
INSTALLATION- Per N.F.P.A 13, 13R and 13D on
top,bottom or side of beam. Space by pipe type.
On 3/8"wood web use#906 backing nuts. - see drawing.
Snap over pipe tl�en squeeze strap back allowing pipe to slide freely.
On copper-insulate pipe.
FASTENERS-UL Listed per NFPA 13
in WOOD:
CPVC pipe-#905 screw-no pre-drill. Hanger,xesrrainer
Copper pipe- #905 screw- no pre-drill. and suppon
Steel pipe- 1/4"xl l/2"lag screw- no pre-drill. � ���
in STEEL:
CPVC pipe- 1/�}" or#1�}Tek Screw.
Copper pipe- 1/4" or#14 Tek Screw.
Stee]pipe- 1/4" or#14 Tek Screw.
FEATURES
* 1 1/2" Offset.
* 3/4" and 1"pipe size have common center-line.
* Leg design produces superior strength.
* Offset edge eliminates abrasion. � stabili2e-only
* Required AFCON#905 screw has 5/]6" hex head- included �
ORDERING-Part#and pipe size. 1
AFCON#906 sold separately.
OS/03
• • ' •
0
o . .. � ' • ' • � � • � ' •
° ��v��r APPLICATION
Designed for installation on potable water lines to protect
'��'�� , against both backsiphonage and backpressure of contami-
nated water into the potable water supply.Assembly shall
�`; rovide rotection where a otential health hazard exists.
� P p p
FEATURES STANDARDS COMPLIANCE
Sizes: ❑ 3/4" ❑ 1" ❑ 1 1/4" ❑ 1 1/2" ❑ 2" ASSEO Listed 1013
IAPMOO Listed
Maximum working water pressure 175 PSI ULO Classified(less shut-offvalves orwith OS&Yvalves)
Maximum working water temperature 180°F C-ULO Classified
Hydrostatic test pressure 350 PSI CSAO Certified
End connections Threaded ANSI B1.20.1 AWWA Compliant C511
Approved by the Foundation for Cross Connection
OPTIONS Control and Hydraulic Research at the University of
(Suffixes can be combined) Southern California
NYC MEA425-89-M VOL 3
❑ - with full port QT ball valves (standard) MATERIALS
❑ L - less ball valves Main valve body Cast Bronze ASTM B 584
❑ U - with union ball valves Access covers Cast Bronze ASTM B 584
❑ MS - with integral relief valve monitor switch Fasteners Stainless Steel, 300 Series
❑ P - for reclaimed water systems
❑ S - with bronze "Y"type strainer Elastomers Silicone (FDAApproved)
❑ BMS - with battery operated monitor switch Buna Nitrile (FDAApproved)
❑ FDC - with fire hydrant connection; 2" only Polymers Noryl , NSF Listed
❑ TCU - with test cocks up Springs Stainless steel, 300 series
❑ V - with union swivel elbows (3/4" & 1")
❑ SE - with street elbows
❑ FT - with integral male 45° flare SAE test fitting ��� ��%
E � �
ACCESSORIES - - � � / II II � / �II
❑ Air gap (Model AG) o o �'
❑ Repair kit (rubber only) F o � o
❑ Thermal expansion tank (Model XT) 1 _ o o.
❑ Soft seated check valve (Model 40XL) p I � B
❑ Shock arrester(Model 1250) A
❑ QT-SET Quick Test Fitting Set
❑ Ball valve handle locks �
❑ Test Cock Lock (Model TCL24) Relief Valve discharge port:
3/4"- 1" - 0.63 sq. in.
DIMENSIONS &WEIGHTS (do not include pkg.) 1 1/4"-2" - 1.19 sq. in.
DIMENSIONS(approximate) WEIGHT
MODEL LESS WITH
SIZE A A UNION B LESS BALL C D E F G BALL BALL
BALLVALVES VALVES VALVES VALVES
in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm Ibs kg Ibs. kg
3/4 20 12 305 13 3/4 349 7 3/4 197 2 1/8 54 3 76 3 1/2 89 5 127 16 1/8 410 10 4.5 12 5.5
1 25 13 330 14 1/2 368 7 3/4 197 2 1/8 54 3 76 3 1/2 89 5 127 17 3/8 441 10 4.5 14 6.4
1 1/4 32 17 432 18 13/16 478 10 15/16 278 2 3/4 70 3 1/2 89 5 127 6 3/4 171 22 9/16 573 22 10 28 12.7
1 1/2 40 17 3/8 441 19 3/8 492 10 15/16 278 2 3/4 70 3 1/2 89 5 127 6 3/4 171 24 1/16 611 22 10 28 12.7
2 50 18 1/2 470 20 1/2 521 10 15/16 278 2 3/4 70 3 1/2 89 5 127 6 3/4 171 26 1/2 673 22 10 34 15.4
�• •
Page 1 of 2 WILKINS a Zurn company, 1747 Commerce Way, Paso Robles,CA 93446 Phone:805/238-7100 Fax:805/238-5766
In Canada:ZURN INDUSTRIES LIMITED,3544 Nashua Dr., Mississauga,Ontario L4V 1L2 Phone:905/405-8272 Fax:905/405-1292
Product Support Help Line: 1-877-BACKFLOW(1-877-222-5356) • Website:http://www.zurn.com
FLOW CHARACTERISTICS
MODEL 975XL 3/4", 1", 1 1l4", 1 1/2" &2" (STANDARD& METRIC)
FLOW RATES(I/s)
� 1.26 2.52 3.8 5.0 3.2 6.3 9.5 12.6 15.8 �
Q
�v2° 137 =
� 20 3/4"(20mm) 1"(25mm) 20 1 1/4"(32mm) (40m �
0 15 �5 _ 2���somm) 103 �
J —
_.. .. .. . . _
W W
� �� 10 69 v�i
� �
w
a
a 5 0 20 40 60 80 5 0 50 100 150 200 250 5
FLOW RATES(GPM)
O Rated Flow(Established by approval agencies)
Capacity thru Schedule 40 Pipe
TYPICAL INSTALLATION Pipe size 5 ft/sec 7.5 ft/sec 10 ft/sec 15 ft/sec
1/8" 1 1 2 3
Local codes shall govern installation requirements. To be 1/4" 2 2 3 5
installed in accordance with the manufacturers'instructions 3/8" 3 4 6 9
and the latest edition of the Uniform Plumbing Code.Unless
otherwise specified, the assembly shall be mounted at a 1/2" 5 7 9 14
minimum of 12" (305mm)and a maximum of 30" (762mm) 3/4" 8 12 17 25
above adequate drains with sufficient side clearance for 1" 13 20 27 40
testing and maintenance. The installation shall be made 1 1/4" 23 35 47 70
so that no part of the unit can be submerged. 1 1/2" 32 48 63 95
2" 52 78 105 167
CENTRAL
STATION
ALARM PROTECTIVE
PANEL eNCLOSURE � ii e-ii ��� i ii
/ — —
BATTERY
MONITOR ��
SWITCH* 12"MIN
12"M�N. 30"MAX
30"MAX. OPTIONAL AIR GAP
WATER METER
AIR GAP DRAIN�
FITTING
° > o = _
m ° ° � ' �
° ii ii ii ii
� ° DIRECTION OF FLOW �
FLOOR� D
FLOOR DRAIN� INLET SHUT-OFF
DIRECTION OF FLOW �
INDOOR INSTALLATION OUTDOOR INSTALLATION
(�Shown w/optional BMS)
SPECIFICATIONS
The Reduced Pressure Principle Backflow Preventer shall be ASSEO Listed 1013, rated to 180°F and supplied with
full port ball valves. The main body and access covers shall be bronze (ASTM B 584), the seat ring and all internal
polymers shall be NSFO Listed NorylT"' and the seat disc elastomers shall be silicone. The first and second checks
shall be accessible for maintenance without removing the relief valve or the entire device from the line. If installed
indoors, the installation shall be supplied with an air gap adapter and integral monitor switch. The Reduced Pressure
Principle Backflow Preventer shall be a WILKINS Model 975XL.
WILKINS a Zurn company, 1747 Commerce Way,Paso Robles,CA 93446 Phone:805/238-7100 Fax:805/238-5766
IN CANADA:ZURN INDUSTRIES LIMITED,3544 Nashua Dr.,Mississauga,Ontario L4V 1 L2 Phone:905/405-8272 Fax:905/405-1292
Product Support Help Line: 1-877-BACKFLOW(1-877-222-5356) • Website:http://www.zurn.com
Page 2 of 2
■ � : � •
. � �
Technical Services: Tel: (800)381-9312/Fax: (800)791-5500
i 1'
• ' ""�\
_ �
� r . - _ ti ' - _- f
The Tyco� 2 thru 8 inch (DN50 thru � g �, ' . - �` ���
DN200) Model PRV-1 Pressure Re- -� � �'� - � �5
ducing Valves are factory assembled � , �, ', ' �' '� + � - �D
and fully trimmed valve arrangements � �
for pressure control. They are used on ,'��" � �,� `"'
water filled pipe where it is necessary � • � —
to reduce a higher inlet pressure to -� -
a lower delivery pressure under static .� � �--
and/or residual flowing conditions.The
PRV-1 is intended to automatically _- � � � ;
maintain the outlet "set pressure"
(static and residual) within a close r � �3y—��
range, regardless of fluctuations in the
higher pressure inlet line or varying
flow rates.
The PRV-1 is provided with a factory NORTH AMERICA
outlet "set pressure" of 125 psi (8,6 Available Body Styles, End Connections&Sizes
bar); however it may be field set to a
nominal outlet "set pressure" of 80 to Nominal Valve Size
225 psi (5,5 to 15,5 bar) per its FM BOdy End Connection
Approval or 80 to 150 psi (5,5 to 10,3 Style 2 Inch 3 Inch 4 Inch 6 Inch 8 Inch
bar) per its UL Listing. (�NSo) (DN80) (DN100) (DN150) (DN200)
Thread x Thread � N/A N/A N/A N/A
Typical applications are as follows: �ioae Groove x Groove • • • • N/A
I i Within the main header(Ref. Figure Flange x Flange N/a N/a • • •
1) supplying wet pipe, dry pipe, del-
uge, or preaction system risers, � =Available N/A=NotAvailable
and/or a standpipe system supply-
ing hose connections. SOUTH AMERICA, CENTRAL AMERICA&EASTERN HEMISPHERE
i i As part of a sectional floor control Available Body Styles, End Connections&Sizes
assembly (Ref. Figure 2) supplying
sprinkler systems, and/or hose sta- Nominal Valve Size
tiOnS. Style End Connection Z Inch 3 Inch 4 Inch 6 Inch 8 Inch
Fe8fiU1'eS 81'e 8S fOIIOWS: (DN50) (DN80) (DN100) (DN150) (DN200)
I I C8f1 be IIlSt811ed Ill ally OYI2nt8t1011. Thread x Thread � � N/A N/A N/A
i i Eliminates any required bleeding of Globe Groove x Groove • • • • N/a
trapped air from the diaphragm — -
chamber during installation. Fian9e x Fian9e tv/a, • • • •
i i Globe or angle pattern. Tnread x Tnreaa • • N/A N/A N/A
I I Accurate pressure control. qngle Groove x Groove • • • • N/A
i i Standard nylon coated internal and
extefllal. Flange x Flange N/A � � � N/A
(continued)
� =Available N/A=Not Available
n One piece, one moving part dia- wET PiPE DRY PIPE
phl"8g1T1. SPRINKLER SPRINKLER
RISER �' ' RISER
u In-line service.
MAIN MAIN
I I One pilot valve sub-assembly pro- DRaIN
vides for any outlet "set pressure", - DRAIN
i.e., 80 to 225 psi (5,5 to 15,5 bar). MAIN �
CONTROL
WARNING PRV-1 VALVE RELIEF CO T�ROL HOSE
The Model PRV-1 Pressure Reducing MAIN \ — va�vE VALVE STATIONS
Valves described herein must be in- HEADER
stalled and maintained in compliance
with this document, as well as with the
applicable standards of the National PRV-1
Fire Protection Association,in addition i
to the standards of any other authori-
ties having jurisdiction. Failure to do
so may impair the performance of
these devices.
The owner is responsible for maintain- F/GURE 1
ing their fire protection system and de- TYPICAL MA/N HEADER APPLICATION
vices in proper operating condition.
The insfalling contractor or sprinkler
manufacturer should be contacted
with any questions.
Due to the flow regulating charac-
teristic of this device, its impact on
system hydraulics should be carefully
considered, especially when retrofit-
ted into existing systems.
�.� ���� :���,_� �� .
Downsfream pressure adjustment - RELIEF VALVE
is only to be performed by experi-
enced personnel who understand
the impact of adjusting the down- ~
stream pressure and who take full PRV-1
responsibility of the readjustment � A SPRINK�ERS
from the factory setting. The Pilot SECTIONAL \
Valve is provided with a Tamper Cap, CHECK �
which upon removal for purposes of FLOOR �� VALVE RISER
downstream adjustment will provide CONTROL SECTIONAL MANIFOLD
an indication that the PRV-1 may have HOSE CONTRO� OR
been altered from its factory setting. VALVE VALVE ZONE
" CHECK
� �
RELIEF VALVE
~ Z
PRV-1
SPRINKLERS
SECTIONAL li, CHECK
FLOOR '�� VALVE
CONTROL SECTIONAL
HOSE CONTROL
VALVE VALVE
� �'
FIGURE 2
TYP/CAL SECTIONAL FLOOR CONTROL APPUCAT/ON
VALVE PARTS � DIAPHRAGM
OUTLET CHAMBER
NO. DESCRIPTION QTY. RefertoKit PRESSURE \ ; 3
1 Valve Body ........... 1 NR GAUGE 2
2 Diaphragm ........... 1 (a) ° I �
3 Handhole Cover ....... 1 NR �\ � 4,5,6
4 Flat Washer, �/ / �
2 Inch Valve,M12 ......4 CH �
3&4 Inch Valves,M16 ..4 CH
6&8 Inch Valves,M16 ..8 CH $
5 Hex Bolt, � � �8
2 Inch Valve,M12 x 35 ..4 CH �
3&4 Inch Valves, �
/, /�,
M16 x 55 .............4 CH 11� �/" /
6 Inch Valve,M16 x 45 ..8 CH
8 Inch Valve,M16 x 55 ..8 CH . � . _ INLET
6 Hex Nut,M16, DOWNSTREAM PRESSURE
4 Inch Valve Only.......4 CH OUTLET CAVITY– GAUGE
7 Pilot Valve ............ 1 (b) �
8 Water Pressure Gauge ..2 (c)
9 Strainer .............. 1 (d) PRESSURE —� �
10 Pressure Sensor Insert .. 1 (e) SENSOR�NSERT L► L� UPSTREAM
11 Tubing and Fittings ..... 1 (f) (SEE DETAIL) INLET
CAVITY
REPLACEMENT PARTS
NO. DESCRIPTION P/N
STRAINER �
(a) Diaphragm, (SEE DETAIL) �
Fits Either Body Style,
Includes Item 2 only: GLOBE BODY STYLE
2 Inch Valves ............. 92-570-2-011
3 lnch Valves ............. 92-570-2-012 INTERIOR INTERIOR
4 Inch Valves ............. 92-570-2-013
6 Inch Valves ............. 92-570-2-014 OF OUTLET VALVE OF INLET VALVE
8 Inch Valves .......... .. 92-570-2-015 CAVITY CAVITY
SENSOR \ BODY BODY
(b) PilotValve ............... 92-570-2-200 INLETFACES + y
(c) Water Pressure Gauge ..... 92-570-2-201 TO TO
(d) Strainer: DOWNSTREAM �� TRIM TRIM
2,3,&4 Inch Valves ....... 92-570-2-202 � �
6&8 Inch Valves.......... 92-570-2-209 10 9
(e) Pressure Sensor Insert:
2 Inch Valve.............. 92-570-2-203 PRESSURE SENSOR STRAINER
3 Inch Valve.............. 92-570-2-204 INSERT DETAIL DETAIL
4 Inch Valve.............. 92-570-2-205
6 Inch Valve.............. 92-570-2-206 DIAPHRAGM
8 Inch Valve.............. 92-570-2-207 OUTLET
(f) Tubing and Fitting Kit, PRESSURE 7 CHAMBER
Excludes Items 7,8,9,and 10 GAUGE �
Globe Style Valve: � ��
2 Inch Valve.............. 92-570-3-001 \, ° 3
3 Inch Valve.............. 92-570-3-002 � 2
4 Inch Valve.............. 92-570-3-003
6 Inch Valve.............. 92-570-3-004
8 Inch Valve.............. 92-570-3-005 � � 4,5,6
Angle Style Valve: �
8
2 Inch Valve.............. 92-571-3-001 � �
3 Inch Valve.............. 92-571-3-002 � �
4 Inch Valve.............. 92-571-3-003
6 Inch Valve.... ..... 92-571-3-004 11� �/' / , $
NOTES:
1. NR-Not Replaceable DOWNSTREAM '� INLET
2. CH-Common Hardware OUTLET CAVITY—_ _y PRESSURE
GAUGE
PRESSURE — L�
SENSORINSERT
DOWNSTREAM DOWNSTREAM (SEE DETAIL) � �
OUTLET FLOW OUTLET FLOW , �
� � DIAPHRAGM � � �
O 0 O O TAB IS ORIENTED /�� \ � ��
0 o PERPENDICULAR TO ' \
O 0 O O OUTLET FLOW STRAINER UPSTREAM
(SEE DETAIL) INLET CAVITY
GLOBE ANGLE ANGLE BODY STYLE
F/GURE 3
MODEL PRV-1 PRESSURE REDUC/NG VALVE
—ASSEMBLY—
Factory Outlet "Set Pressure": End Connections:
125 psi (8,6 bar) Threaded end connections are avail-
Field Outlet "Set Pressure" Range: able NPT threaded or threaded per
ISO 7/1. Flanged end connections
Approvals: 80 to 225 psi (5,5 to 15,5 bar)per its are available drilled per Table A.
FM Approval, or 80 to 150 psi (5,5 to Grooved end connections are per in-
UL Listed. FM Approved. 10,3 bar) per its UL Listing dustry standard groove specifica-
The UL Listing is based on Pressure Loss With Inlet Pressure tions.
[i Installation requirements refer- Above "Set Pressure" Construction (Ref. Figure 3):
enced in the Standard for Installa- The inlet pressure minus the outlet Body. Rilsan* blue coated ductile
tion of Sprinkler Systems, NFPA "set pressure" equals pressure loss. iron per ASTM A536-77, Grade 65-
13, or the Standard for Installation For example:assumimg that the inlet 45-12.
of Standpipe and Hose Valves, flowing pressure is 225 psi(15,5 bar) Handhole Cover. Rilsan* blue
NFPA 14, as applicable. and the field outlet "set pressure" is coated ductile iron per ASTM A536-
u Inspection, testing, and mainte- 130 psi (9,0 bar), the pressure loss 77, Grade 65-45-12.
nance requirements referenced in is 95 psi (6,5 bar).
the Standard for Inspection, Test- Pressure Loss with Inlet Pressure Diaphragm. Nylon fabric reinforced,
ing, and Maintenance of Water- Below "Set Pressure" natural rubber per ASTM D2000.
Based Fire Protection Systems, Refer to Graphs A thru E. (These Diaphragm Cover Fasteners. Gal-
NFPA 25. graphs are a requirement of UL and vanized carbon steel.
I I The Model PRV-1 being field setto should be used as reference only.) Pilot Valve. Brass and stainless
provide the required outlet pres- Rated Flowing Range: steel with nylon fabric reinforced,
sures and flows for the given appli- natural rubber per ASTM D2000 dia-
cation. 2 inch (DN50): 0 to 250 GPM phragm.
u The Model PRV-1 being tested af- �0 to 946 LPM) Strainer. Brass and stainless steel.
ter installation in accordance with 3 inch (DN80): 0 to 550 GPM pressure Gauges. 2-1/2 inch (65
NFPA 13 and/or NFPA 14 as appli- (0 to 2080 LPM) mm) diameter, stainless steel case,
cable. 4 inch (DN100): 0 to 1000 GPM 0 to 350 psi (25 bar).
I I The Model PRV-1 being tested pe- (0 to 3785 LPM) Tube, Fittings, and Needle Valve.
riodically thereafter in accordance 6 inch (DN150): 0 to 2200 GPM Copper, brass, and stainless steel.
with NFPA 25. (0 to 8325 LPM)
*Rilsan is a registered trademark of
Maximum Inlet Pressure: 8 inch (DN200): 0 to 4000 GPM ATOFINA Chemicals, Inc. (The Ril-
250 psi (17,2 bar) (0 to 15140 LPM) san coating is a polyamide (Nylon
11)coating.)
Flange Drilling Specification
Nominal Dimensions in Inches and(mm)
Nominal ANSI B16.1 ' ISO 7005-2 ISO 7005-2 JIS B 2210 AS 2129
Valve (Class 125) (PN10)Z (PN16)3 (10K) (Table E)
Size
Dim. Dim. Qty. Dim. Dim. Qty. Dim. Dim. Qty. Dim. Dim. Qty. Dim. Dim. Qty.
A B N A B N A B N A B N A B N
31nch 6.00 0.75 6.30 0.75 5.90 0.59 5.75 0.71
(DN80) (152,4) (19,0) 4 (160,0) (19,0) $ (150,0) (15,0) $ (146,0) (18,0) 4
41nch 7.50 0.75 $ ISO 005-2 ��09 0.75 8 6.89 0.59 $ 7.00 0.71 $
(DN100) (190,5) (19,0) (PN16) (180,0) (19,0) (175,0) (15,0) (178,0) (18,0)
61nch 9.50 0.88 9.45 0.91 9.45 0.75 9.25 0.87
(DN150) (241,3) (22,2) $ (240,0) (23,0) $ (240,0) (19,0) $ (235,0) (22,0) $
81nch 11.75 0.88 $ 11.61 0.91 8 11.61 0.91 12 11.42 0.75 12 11.50 0.87 $
(DN200) (298,5) (22,2) (295,0) (23,0) (295,0) (23,0) (290,0) (19,0) (292,0) (22,0)
'Same drilling as for ANSI 616.5(Class 150)and ANSI 616.42(Class 150). Dim.A Qty.N
Z Same drilling as for BS 4504 Section 3.2(PN10)and DIN 2532(PN10). Bolt Circle—� % Number of
3 Same drilling as for BS 4504 Section 3.2(PN16)and DIN 2532(PN16). Diameter � � ��� Bolt Holes
,o—o�
o ���
i
Dim.B '
u ��
Bolt Hole�� �o—u�
Diameter
TABLE A
D/MENS/ONAL SPECIFICATION FOR SELECTION OF FLANGE DRILLING
TAMPER ADJUSTING
CAP ��_ � SCREW
OUTLET
PRESSURE LOCKNUT
GAUGE �
� P I LOT
-- VALVE NEEDLE VALVE
C� � (FACTORY SET,
� REGULATING DIAPHRAGM DO NOT READJUST)
SPRING CHAMBER �
� - /
♦ EXIT FLOW SUPPLY
Gc
LINE
/ �
� INLET
PRESSURE
PILOT � GAUGE
VALVE SYSTEM
SEAT WATER
SUPPLY C�
PRESSURE
OUTLET CAVITY INLET CAVITY ♦
SENSWG � �,
LIN E
,
I I ��
INTERIOR � INTERIOR
VALVE OF OUTLET � � � VALVE OF WLET
BODY CAVITY SENS R � � BODY CAVITY
� INLET FACES PRV-1 PRV-1 �
�� " UPSTREAM DIAPHRAGM SEAT � i ��
i i ��
TO � TO �
TRIM PRESSURE TRIM STRAINER
SENSORINSERT
FIGURE 4
MODEL PRV-1 PRESSURE REDUCING VALVE
—OPERAT/ON—
low the "set pressure° of the spring, [1 As the flow demand continues down-
exit flow from the Diaphragm Chamber stream of the PRV-1 and the "set
through the Pilot Valve to the PRV-1 pressure" is met, the Pilot Valve
With reference to Figure 4,the system outlet cavity resumes and pressure in Seat closes. As the Pilot Valve Seat
water supply pressure from the inlet the Diaphragm Chamber decreases. closes to reduce the opening, pres-
cavity of the PRV-1 enters the Dia- sure is trapped in the Diaphragm
phragm Chamber through a Strainer The regulated flow through the Pilot Chamber at a point that allows the
and Needle Valve. The factory set Valve decreases and increases the Diaphragm to remain lifted from the
Needle Valve provides the required pressure in the diaphragm chamber to PRV-1 Seat to retain the down-
orifice size for the supply line to the sufficiently open and close the PRV-1, stream "set pressure".
Diaphragm Chamber to optimize per- as required, to regulate the down-
formance. stream "set pressure°. I I Should the downstream pressure
The operation sequence is as follows: start to fall below the"set pressure",
Exitflowfrom the Diaphragm Chamber the Pilot Valve Seat re-opens to al-
through the Pilot Valve is controlled by i�When there is no flow demand low for a decrease in pressure in the
a regulating spring that is factory set, downstream of the PRV-1, the Diaphragm Chamber to allow the
and subsequently field adjustable, to PRV-1 Seat is closed and the Pilot PRV-1 to open further and then once
the desired downstream"set pressure" Valve Seat is closed. With the Pilot again establish the downstream"set
that is to be maintained.A sensing line Valve Seat closed, pressure is pressure".
connects the outlet of the Pilot Valve trapped in the Diaphragm Chamber
to the system piping downstream of to seat the Diaphragm and the I 1 When the downstream pressure is at
the PRV-1 via the Pressure Sensor PRV-1 remains closed. or above the "set pressure" and as-
Insert in the outlet cavity. suming there is a flow demand
�When there is a flow demand down- downstream of the PRV-1, the Pilot
When the downstream pressure rises stream of the PRV-1 and the PRV-1 Valve Seat is closed to trap a suffi-
above the"set pressure"of the spring, outlet pressure drops below the"set cient pressure in the Diaphragm
exit flow from the Diaphragm Chamber pressure,the Pilot Valve Seat opens Chamber to allow the PRV-1 to re-
through the Pilot Valve to the PRV-1 to relieve pressure from the Dia- main open to provide the "set pres-
outlet cavity is stopped and pressure phragm Chamber allowing the sure".
increases in the Diaphragm Chamber. PRV-1 to open.
When downstream pressure falls be-
facilitate a flow test at the sprinkler or multiple hose valves, as required,
system demand. will be necessary to simulate hose
stream demand.
For the purposes of the following in-
The following items must be consid- struction, the opening of a "flow test
ered and applied accordingly for an valve" simulates either the sprinkler
installation that will be using the Model demand or hose stream demand, as
PRV-1 Pressure Reducing Valve: The Tyco�Model PRV-1 Pressure Re- applicable. The sprinkler demand or
ducing Valve must be installed with the hose stream demand must be at least
i i The PRV-1 may be installed verti- flow arrow located on the Diaphragm 50 GPM (190 LPM) for 2 to 6 inch
cally or horizontally and in any orien- Cover pointing in the intended direc- (DN50 to DN150) valves and at least
tation without affecting its operating tion offlow.Installation dimensions are 100 GPM (380 LPM) for 8 inch
efficiency. When planning the posi- provided in Figures 5 and 6. (DN200) valves.
tioning of the PRV-1, it is recom-
mended that consideration be given Before the PRV-1 is installed, pipe There is no need to vent any trapped
to the viewing of the pressure lines should be flushed of all chips, air from the Diaphragm Chamber.
gauges. Consideration should also scale and foreign matter.Care must be Filling The System:
be given to positioning the PRV-1 so exercised to assure that the trim is not
that the diaphragm cover is facing damaged during installation. Do Not Step 1. Verify that downstream drain
up.With the cover facing up,internal Lift The Valve By Its Trim. valves are closed and that there are no
access is more easily achieved. leaks.
NOTES Step 2.Partially open a valve or valves
n The PRV-1 must be in an area that The inlet and outlet connections must at the end of the system (e.g., an in-
is easily accessible for maintenance be made based on the direction offlow
purposes, not subject to freezing arrow provided on the handhole cover. spector's test connection on a wet pipe
tem eratures, and not sub'ect to system)to allow trapped air to escape
p 1 The valve cannot operate if connected When filling the system.
physical damage. backwards.
Step 3. Slowly and partially open the
I I The valve is designed forfresh water po not alter the trim. Altering the trim Water supply control valve feeding the
service. When corrosive atmos- may render the valve ineffective and pRV-1.
pheres and/or contaminated water impair the system operation.
supplies are present, it is the Step 4. After the system fills with
owner's responsibility to verify com- water, close the valve or valves that
patibility with the pressure reducing had been partially opened in Step 2.
valve, pilot valve, and trim. Step 5. Completely open the main
I i The difference between the water water supply control valve feeding the
supply pressure and the desired out- PRV-1.
let (downstream) pressure must be Downstream Pressure Adjustment:
25 psi (1,7 bar)or greater per its FM Steps 1 through 12 are to be per-
Approval or 50 psi (3,4 bar) or formed when placing the Model PRV-1 Step 6. Remove the Tamper Cap from
greater per its UL Listing.The differ- Pressure Reducing Valve in service. the Pilot Valve by first loosening its set
ential maintains accuracy control of screw and then unscrewing the Tam-
the discharging pressure over the WARN/NG per Cap.
full rated flowing range. Downstream pressure adjustment
is only to be performed by experi- Step 7. Open the "flow test valve" to
i i Cavitation may occur when the inlet enced personnel who understand simulate either the desired sprinkler
pressure is greater than twice the the impact of adjusting the down- demand or hose stream demand.
"set pressure". For this case, the stream pressure and who take full
pressure should be reduced in two responsibility of the readjustment NOTE
steps by using two PRV-1's in se- from the factory setting. The Pilot Ifsurging flow occurs,attempt to bleed
ries. Valve is provided with a Tamper Cap, trapped air from the system via the
which upon removal for purposes of inspector's test valve and any other
i i When reducing pressure for a sprin- downstream adjusfinent will provide valve that can vent trapped air.
kler system,a relief valve of not less
than 1/2 inch (DN15)in size shall be an indication thatthe PRV-1 mayhave Step 8. Loosen the locknut on the ad-
located downstream of the PRV-1. been altered from the factory setting. justing screw of the Pilot Valve.
The relief valve shall be set at a Adjustment of the Needle Valve is Step 9. Turn the adjusting screw
pressure equal to the lowest pres- factory set and must not be altered. clockwise to increase outlet pressure
sure rated component downstream The Needle Valve is provided with a or counterclockwise to decrease outlet
of the PRV-1. NOTE;FMApproval is tamperindication, which upon removal pressure.
based on the use of the 1/2 inch, for purposes of any adjustment will Step 10. After achieving the desired
Watts Regulator, Series 530C Pres- provide an indication that the PRV-1 performance, tighten the locknut on
sure Relief Valve. may have been altered from fhe fac-
i i When reducing pressure for a sprin- tory setting. the adjusting screw.
kler system, a listed indicating valve Step 11. Close the "flow test valve".
shall be provided on the inlet side of NOTES Observe the outlet pressure gauge
the PRV-1. Per the requirements of NFPA 13, a and compare to the required "set
means shall be provided downstream pressure". If the required "set pres-
i i When reducing pressure for a sprin- of the PRV-1 to simulate the sprinkler sure" is not achieved, repeat Step 8
kler system, means shall be pro- system demand. In the case of hose and proceed accordingly.
vided downstream of the PRV-1 to stations, the opening of a hose valve
Step 12. Replace the Tamper Cap and first be obtained from the proper
tighten its set screw. authorities and all personnel who may
The pressure reducing valve is now be affected by this decision must be
set for service. notified.
The Model PRV-1 Pressure Reducing products manufactured by Tyco Fire&
NOTES Valve requires no lubrication, packing guilding Products (TFBP) are war-
Due to the spring tolerance within the or preventative maintenance; how- ranted solely to the original Buyer for
Pilot Valve, it may be necessary to ever, replacement of the diaphragm ten (10)years against defects in mate-
alternate back and forth between re- every five years is recommended. rial and workmanship when paid for
sidual and static conditions to achieve Flow Tests. Flow tests per NFPA are and properly installed and maintained
the desired "set pressure"for both re- required every five years, at which under normal use and service. This
sidual and static conditions. point the outlet pressure is compared warranty will expire ten (10) years
After any downstream pressure ad- to previous tests. If necessary the from date of shipment by TFBP. No
justment, the following items are to be PRV-1 can be readjusted following the warranty is given for products or com-
recorded on a tag attached to the Placing The Valve In Service section. ponents manufactured by companies
valve: If the desired pressure cannot be not affiliated by ownership with TFBP
- Valve installation location achieved, the Diaphragm and/or Pilot or for products and components which
Valve should be replaced. have been subject to misuse,improper
-Inlet static pressure Diaphragm Replacement. Prior to re- installation, corrosion, or which have
not been installed, maintained, modi-
- Outlet static pressure placing the Diaphragm, the PRV-1 fied or repaired in accordance with ap-
-Inlet residual pressure must be taken out of service and com- plicable Standards of the National Fire
pletely drained. With reference to Fig- protection Association, and/or the
- Outlet residual pressure ure 3, the Diaphragm Tab is oriented standards of any other Authorities
-Intended outlet flow perpendicular to the outlet flow. When Having Jurisdiction. Materials found
reinstalling the Diaphragm Cover, the by TFBP to be defective shall be either
The tag is not to be removed until after Diaphragm Cover Fasteners must be repaired or replaced, at TFBP's sole
the system has been accepted by the uniformly and securely tightened option. TFBP neither assumes, nor
Authority Having Jurisdiction. It is rec- using a cross-draw sequence. After authorizes any person to assume for it,
ommended that the tag not be re- tightening, double check to make cer- any other obligation in connection with
moved even after acceptance by the tain that all of the Diaphragm Cover the sale of products or parts of prod-
Authority Having Jurisdiction unless fasteners are securely tightened. ucts.TFBP shall not be responsible for
another means of record keeping is pilot Valve Replacement. Prior to re- sprinkler system design errors or inac-
maintained. moving the Pilot Valve, the PRV-1 curate or incomplete information sup-
must be taken out of service and com- plied by Buyer or Buyer's repre-
pletely drained.When installing the re- sentatives.
placement Pilot Valve,the trim compo- In no event shall TFBP be liable, in
nents must be replaced exactly as they contract, tort, strict liability or under
were. After reinstalling the Pilot Valve any other legal theory, for incidental,
and before returning the PRV-1 into indirect,special or consequential dam-
service, completely unscrew the Ad- ages, including but not limited to labor
justing Stem of the replacement Pilot charges, regardless of whether TFBP
Inspection, testing, and maintenance Valve so as to obtain a minimum outlet vvas informed about the possibility of
must be performed in accordance with "set pressure". Then proceed to use such damages, and in no event shall
the requirements ofthe NFPA,and any the instructions under Placing The TFBP's liability exceed an amount
impairment must be immediately cor- Valve In Service section to place the equal to the sales price.
rected. PRV-1 in service.
The foregoing warranty is made in lieu
The owner is responsible for the in- NOTES of any and all other warranties. ex-
spection, testing, and maintenance of The Pilot Valve is not field repairable. press or implied. including warranties
their fire protection system and de- Attempting to repair the Pilot Valve of inerchantability and fitness for a par-
vices in compliance with this docu- may render the valve ineffective and ticular purpose.
ment, as well as with the applicable impair the system operation.
standards of any authorities having ju- This limited warranty sets forth the ex-
risdiction. The installing contractor or Completely unscrewing the Adjusting clusive remedy for claims based on
product manufacturer should be con- Stem of the replacement Pilot Valve failure of or defect in products, materi-
tacted relative to any questions. will help to avoid an accidental over als or components, whether the claim
Automatic sprinkler systems should be Pressurization of the system piping is made in contract, tort, strict liability
ins ected,tested,and maintained b a Prior to achieving the desired "set or any other legal theory.
p y pressure". This warranty will apply to the full ex-
qualified Inspection Service in accord-
ance with local requirements and/or tent permitted by law.The invalidity, in
national codes. whole or part, of any portion of this
warranty will not affect the remainder.
NOTE
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls,permission to shut down the
affected fire protection systems must
Thread x Thread End Connections
Nominal Nominal Installation Dimensions in Inches and(mm) Weight
Valve Ibs.
Sizes A B C D E F k
9
2" 7.51 1.49 7.32 6.41 8.18 2.36 15.2
(DN50) (191) (38) (186) (163) (208) (60) (6,9)
3" 11.14 1.77 8.19 7.48 9.25 3.93 30.6
DN80 283 45 208 190 235 100 13,9
�
Groove x Groove End Connections � � F
Nominal Nominal Installation Dimensions in Inches and(mm) Weight �
Valve Ibs. E
Sizes A B C D E F k �
2" 7.51 1.49 7.32 6.41 8.18 2.36 15.2 �
(DN50) (191) (38) (186) (163) (208) (60) (6,9)
3" 11.14 1.77 8.19 7.48 9.25 3.93 30.6 � � �
(DN80� (2831 _(45) (208) (190) �235) (100� (13,9)
4" 13.62 4.37 8.70 7.91 9.68 4.52 45.2 C
(DN100) (346) (111) (221) (201) (246) (115) (20,5) �
6" 17.79 3.30 9.88 6.73 11.49 5.90 118.0 �
DN150 452 84 251 171 292 150 53,5
G� �
Flange x Flange End Connections g
Nominal Nominal Installation Dimensions in Inches and(mm) Weight � A _ �
Valve
Sizes A B C D E F Ibs.
k
3" 11.14 3.93 8.19 7.48 9.25 3.93 46.3
(DN80) (283) (100) (208) (190) (235) (100) (21,0)
4" 12.00 2.24 8.70 7.91 9.68 4.52 65.0
(DN100) (305) (57) (221) (201) (246) (115) (29,5)
6" 15.98 5.59 9.88 6.73 11.49 5.90 118.0
(DN150) (406) (142) (251) (171) (292) (150) (53,5)
8" 18.50 6.69 11.14 7.16 12.55 6.96 166.5
DN200 470 170 283 182 319 177 75,5
FIGURE 5
MODEL PRV-1 PRESSURE REDUC/NG VALVE
-GLOBE STYLE INSTALLAT/ON D/MENSIONS-
Thread x Thread End Connections
Nominal Nominal Installation Dimensions in Inches and(mm) Weight
Valve Ibs.
Sizes A B C D E F G k
2" 3.54 3.18 7.32 6.41 8.18 2.40 2.40 15.9
(DN50) (90) (81) (186) (163) (208) (61) (61) (7,2)
3" 6.06 4.52 8.19 7.48 9.25 3.93 3.93 34.1
DN80 154 115 208 190 235 100 100 15,5
Groove x Groove End Connections 1
O O F
Nominal Nominal Installation Dimensions in Inches and(mm) Weight
Valve Ibs. f
Sizes A B C D E F G k
E
2" 3.54 3.18 7.32 6.41 8.18 2.40 2.40 15.9 � I
(DN50) (90) (81) (186) (163) (208) (61) (61) (7,2) I
3" 6.06 4.52 8.19 7.48 9.25 3.93 3.93 34.1
(DN80) (154) (115) (208) (190) (235) (100) (100) (15,5) D � � �G
4" 6.33 4.56 8.70 7.91 9.68 4.52 4.52 44.0 C
(DN100) (161) (116) (221) (201) (246) (115) (115) (19,9) �
6" 8.89 6.69 9.88 6.73 11.49 5.90 5.90 89.3
DN150 226 170 251 171 292 150 150 40,5 �
�
Flange x Flange End Connections
B
Nominal Nominal Installation Dimensions in Inches and(mm) Weight
Valve �
Sizes A B C D E F G Ibs. � ��A
k
3" 6.06 4.52 8.19 7.48 9.25 3.93 3.93 35.1
(DN80) (154) (115) (208) (190) (235) (100) (100) (15,9)
_ _ _ .
4" 6.33 4.56 8.70 7.91 9.68 4.52 4.52 67.3
(DN100) (161) (116) (221) (201) (246) (115) (115) (30,5)
6" 8.89 6.69 9.88 6.73 11.49 5.90 5.90 1162
DN150 226 170 251 171 292 150 150 52,7
F/GURE 6
MODEL PRV-1 PRESSURE REDUCING VALVE
-ANGLE STYLE/NSTALLAT/ON D/MENS/ONS-
1 PSI=0,06895 BAR 1 GPM=3,785 LPM
140
a 130 A=70 PSI INLET PRESSURE
�' B=50 PSI INLET PRESSURE
v 120
z
w 110
�
� 100
�
� 90
�
w
� 80
�
O ��
�
� 60 A
�
z
W 50
�
� 40 B
cn - -
� 30
�
w 20
J
� 10
O
0
0 25 50 75 100 125 150 175 200 225 250
FLOW RATE�N GALLONS PER MINUTE(GPM)
GRAPH A-1
2 INCH(DN50)PRESSURE REDUC/NG VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD/NLET PRESSURE FALL BELOW A SET PRESSURE OF 80 PSI
(This graph is a requirement of UL and should be used as reference only.)
1 PSI=0,06895 BAR 1 GPM=3,785 LPM
140
� 130 A= 140 PSI INLET PRESSURE
�- - - B=100 PSI INLET PRESSURE
U �2� A C=50 PSI INLET PRESSURE
z
W 110
� -
� 100
C�
� 90 B
�
w
a 80
�
Z 70
� —
� 60
z
w 50
�
� 40
cn C
� 30
d
W 20
J
� 10
O
0
0 25 50 75 100 125 150 175 200 225 250
FLOW RATE IN GALLONS PER MINUTE(GPM)
GRAPH A-2
2 INCH(DN50)PRESSURE REDUC/NG VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 150 PSI
(This graph is a requirement of UL and should be used as reference only.)
1 PSI=0,06895 BAR 1 GPM=3,785 LPM
140
a 130 A=70 PSI INLET PRESSURE
-- B=50 PSI INLET PRESSURE
U 120
z
W 110
�
� 100
C�
� 90
� _
w
a 80
�
z ��
�
a 60
z A
W 50
�
� 40
cn --
W 30 B
�
a
W 20
J
� 10
O
0
0 50 100 150 200 250 300 350 400 450 500 550
FLOW RATE IN GALLONS PER M�NUTE(GPM)
GRAPH B-1
3 INCH(DN80)PRESSURE REDUC/NG VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD/NLET PRESSURE FALL BELOW A SET PRESSURE OF 80 PSI
(This graph is a requirement of UL and should be used as reference only.)
1 PSI=0,06895 BAR 1 GPM=3,785 LPM
140
� 130 A= 140 PSI INLET PRESSURE
B= 100 PSI INLET PRESSURE
U �2� A C=50 PSI INLET PRESSURE
z
W 110
�
� 100
C7
� 90 g
�
w
� 80
�
z 70
�
a 60
z
w 50
�
� 40
� C
� 30
a
W 20
J
� 10
O
0
0 50 100 150 200 250 300 350 400 450 500 550
FLOW RATE IN GALLONS PER M�NUTE(GPM)
GRAPH B-2
3 INCH(DN80)PRESSURE REDUC/NG VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 150 PSI
(This graph is a requirement of UL and should be used as reference only.)
1 PSI=0,06895 BAR 1 GPM=3,785 LPM
140
a 130 A=70 PSI INLET PRESSURE
-- B=50 PSI INLET PRESSURE
U 120
z
W 110
�
� 100
C�
� 90
�
w
a 80
�
Z 70
�
� 60 A
a
z
W 50
�
� 40 g
�
cn —
� 30
a
W 20
J
� 10
O
0
0 100 200 300 400 500 600 700 800 900 1000
FLOW RATE IN GALLONS PER M�NUTE(GPM)
GRAPH C-1
4/NCH(DN100)PRESSURE REDUC/NG VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD/NLET PRESSURE FALL BELOW A SET PRESSURE OF 80 PSI
(This graph is a requirement of UL and should be used as reference only.)
1 PSI=0,06895 BAR 1 GPM=3,785 LPM
140
� 130 A
U 120
z
W ��p A= 140 PSI INLET PRESSURE
� B= 100 PSI INLET PRESSURE
� 100 C=50 PSI INLET PRESSURE
C7 B
� 90
�
w
� 80
�
z 70
�
a 60
z
w 50
� 40 C
�
� 30
a
W 20
J
� 10
O
0
0 100 200 300 400 500 600 700 800 900 1000
FLOW RATE IN GALLONS PER M�NUTE(GPM)
GRAPH G2
4/NCH(DN100)PRESSURE REDUC/NG VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 150 PSI
(This graph is a requirement of UL and should be used as reference only.)
1 PSI=0,06895 BAR 1 GPM=3,785 LPM
140
a 130 A=70 PSI INLET PRESSURE
-- B=50 PSI INLET PRESSURE
U 120
z
W 110
�
� 100
C�
� 90
�
w
a 80
�
Z 70
�
a 60
z A
W 50
�
� 40
cn B —
� 30
a
W 20
J
� 10
O
0
0 250 500 750 1000 1250 1500 1750 2000 2250 2500
FLOW RATE IN GALLONS PER M�NUTE(GPM)
GRAPH D-1
6/NCH(DN150)PRESSURE REDUC/NG VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD/NLET PRESSURE FALL BELOW A SET PRESSURE OF 80 PSI
(This graph is a requirement of UL and should be used as reference only.)
1 PSI=0,06895 BAR 1 GPM=3,785 LPM
140
� 130 A= 140 PSI INLET PRESSURE
B= 100 PSI INLET PRESSURE
U �2� A C=50 PSI INLET PRESSURE
z
W 110
�
� 100
C7
� 90 B
�
w
� 80
�
z 70
�
a 60
z
w 50
�
� 40
� C
� 30
a
W 20
J
� 10
O
0
0 250 500 750 1000 1250 1500 1750 2000 2250 2500
FLOW RATE IN GALLONS PER M�NUTE(GPM)
GRAPH D-2
6/NCH(DN150)PRESSURE REDUC/NG VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 150 PSI
(This graph is a requirement of UL and should be used as reference only.)
1 PSI=0,06895 BAR 1 GPM=3,785 LPM
140
a 130 A=70 PSI INLET PRESSURE
-- B=50 PSI INLET PRESSURE
U 120
z
W 110
�
� 100
C�
� 90
�
w
a 80
� .
Z 70
� A
a 60
z
W 50
�
� 40 B
cn - -
_
� 30
a
W 20
J
� 10
O
0
0 500 1000 1500 2000 2500 3000 3500 4000
FLOW RATE IN GALLONS PER M�NUTE(GPM)
GRAPH E-1
8/NCH(DN200)PRESSURE REDUC/NG VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD/NLET PRESSURE FALL BELOW A SET PRESSURE OF 80 PSI
(This graph is a requirement of UL and should be used as reference only.)
1 PSI=0,06895 BAR 1 GPM=3,785 LPM
140
� 130 A A= 140 PSI INLET PRESSURE
-- B= 100 PSI INLET PRESSURE
U �2� C=50 PSI INLET PRESSURE
z
W 110
�
� 100
C7
� 90 B
�
w
� 80
�
z 70
�
a 60
z
w 50
�
� 40 C
�
� 30
a
W 20
J
� 10
O
0
0 500 1000 1500 2000 2500 3000 3500 4000
FLOW RATE IN GALLONS PER M�NUTE(GPM)
GRAPH E-2
8/NCH(DN200)PRESSURE REDUC/NG VALVE
OUTLET PRESSURE VERSES FLOW
SHOULD INLET PRESSURE FALL BELOW A SET PRESSURE OF 150 PSI
(This graph is a requirement of UL and should be used as reference only.)
Pressure Reducing Valve:
Specify: Globe Type, (specify size),
125 psi Outlet "Set Pressure"with(T
x T, G x G, or F x F) Connection, P/N
(specify from below). Pressure Reducing Valve:
P/N's for GLOBE BODY STYLE Specify: (Globe or Angle)Type, (spec-
AVAILABLE IN AMERICAS ify size), 125 psi Outlet"Set Pressure"
with (specify) Connection (and for
2 Inch T x T flanged valves specify flange drilling),
NPT................ P/N 52-570-8-060 P�N (specify from complete listing on
2 Inch G x G Page 16).
2.37 inch(60,3 mm)
Groove O.D........... P/N 52-570-8-920 f I VaIV2 Typ2 & SIZ@
(Globe, 2, 3, 4, 6, or 8 Inch)
3 Inch G x G (Angle, 2, 3, 4, or 6 Inch
3.50 inch(88,9 mm)
�roo�e o.o.. ........ Pirv 5z-5�o-a-szz �1 125 psi Outlet"Set Pressure"
Pressure
4 Inch G x G I I Connection Type
4.50 inch(114,3 mm) Threaded, Grooved, Flan ed
Groove O.D. ......... P/N 52-570-8-923 � g �
4 Inch F x F For threaded, specify NPT or ISO
ANSI Flange......... P/N 52-570-8-023
6 Inch G x G For grooved, specify O.D. Pipe Size
s.sz�r,cn��ss,s mm) -2 inch (DN50):
Groove O.D. ......... P/N 52-570-8-925 2,gg inch (60,3 mm) O.D.
6 Inch F x F
ANSI Flange. ........ P/N 52-570-8-025 - 3 IIICh (DN80�:
8 Inch F x F 3.50 inch (88,9 mm) O.D.
ANSI Flange......... P/N 52-570-8-026 -4 IIICh ��N�0��:
Pressure Relief Valve: 4.50 inch (114,3 mm) O.D.
Specify: 1/2 inch (DN15) Watts Regu- -6 inch (DN150):
lator, Series 530C Pressure Relief 6.62 inch (168,3 mm) O.D. or
Valve for use downstream of a PRV-1 6.50 inch (165,1 mm) O.D.
being used for reducing pressure in _g inch (DN200):
sprinkler system, P/N 92-570-2-208. g.62 inch (219,1 mm) O.D.
Replacement Valve Parts: For flanged, specify flange drilling
Specify: (description) for use with per
(specify) size Model PRV-1 Pressure
Reducing Valve, P/N (see Figure 3). -ANSI B16-1 (Class 125)
- ISO 7005-2 (PN16)
- ISO 7005-2 (PN10),
8 inch valve only
-JIS B2210 (10K)
-AS 2129 (Table E)
NOTES
Refer to Table A for flange drilling di-
mensional specifications.
Pressure Relief Valve:
Specify: 1/2 inch (DN15) Watts Regu-
lator, Series 530C Pressure Relief
Valve for use downstream of a PRV-1
being used for reducing pressure in
sprinkler system, P/N 92-570-2-208.
Replacement Valve Parts:
Specify: (description) for use with
(specify) size Model PRV-1 Pressure
Reducing Valve, P/N (see Figure 3).
P/N's for GLOBE BODY STYLE P/N's for ANGLE BODY STYLE
21nchTxT 21nchTxT
NPT................ P/N 52-570-8-060 NPT................ P/N 52-571-8-060
21nchTxT 21nchTxT
ISO ................ P/N 52-570-8-160 ISO................ P/N 52-571-8-160
21nchGxG 21nchGxG
2.37 inch(60,3 mm) 2.37 inch(60,3 mm)
Groove O.D........... P/N 52-570-8-920 Groove O.D.. ........ P/N 52-571-8-920
31nchTxT 31nchTxT
NPT................ P/N 52-570-8-062 NPT................ P/N 52-571-8-062
31nchTxT 31nchTxT
ISO ................ P/N 52-570-8-162 ISO................ P/N 52-571-8-162
31nchGxG 31nchGxG
3.50 inch(88,9 mm) 3.50 inch(88,9 mm)
Groove O.D.. ........ P/N 52-570-8-922 Groove O.D.......... P/N 52-571-8-922
3 Inch F x F 3 Inch F x F
ANSI Flange......... P/N 52-570-8-022 ANSI Flange......... P/N 52-571-8-022
31nchFxF 31nchFxF
ISO(PN16)Flange.... P/N 52-570-8-112 ISO(PN16)Flange ... P/N 52-571-8-112
3 Inch F x F 3 Inch F x F
JIS Flange........... P/N 52-570-8-722 JIS Flange .......... P/N 52-571-8-722
3 Inch F x F 3 Inch F x F
AS Flange........... P/N 52-570-8-522 AS Flange........... P/N 52-571-8-522
41nchGxG 41nchGxG
4.50 inch(114,3 mm) 4.50 inch(114,3 mm)
Groove O.D. ......... P/N 52-570-8-923 Groove O.D. ........ P/N 52-571-8-923
41nchFxF 41nchFxF
ANSI Flange......... P/N 52-570-8-023 ANSI Flange ........ P/N 52-571-8-023
41nchFxF 41nchFxF
ISO(PN16)Flange.... P/N 52-570-8-113 ISO(PN16)Flange ... P/N 52-571-8-113
4 Inch F x F 4 Inch F x F
JIS Flange........... P/N 52-570-8-723 JIS Flange .......... P/N 52-571-8-723
41nchFxF 41nchFxF
AS Flange........... P/N 52-570-8-523 AS Flange........... P/N 52-571-8-523
61nchGxG 61nchGxG
6.62 inch(168,3 mm) 6.62 inch(168,3 mm)
Groove O.D. ......... P/N 52-570-8-925 Groove O.D. ........ P/N 52-571-8-925
61nchGxG 61nchGxG
6.50 inch(165,1 mm) 6.50 inch(165,1 mm)
Groove O.D. ......... P/N 52-570-8-945 Groove O.D. ........ P/N 52-571-8-945
6 Inch F x F 6 Inch F x F
ANSI Flange......... P/N 52-570-8-025 ANSI Flange ........ P/N 52-571-8-025
61nchFxF 61nchFxF
ISO(PN16)Flange.... P/N 52-570-8-115 ISO(PN16)Flange ... P/N 52-571-8-115
61nchFxF 61nchFxF
JIS Flange........... P/N 52-570-8-725 JIS Flange .......... P/N 52-571-8-725
6 Inch F x F 6 Inch F x F
AS Flange........... P/N 52-570-8-525 AS Flange........... P/N 52-571-8-525
81nchFxF
ANSI Flange......... P/N 52-570-8-026
8 Inch F x F
ISO(PN10)Flange.... P/N 52-570-8-116
81nchFxF
ISO(PN16)Flange.... P/N 52-570-8-126
SlnchFxF
JIS Flange........... P/N 52-570-8-726
8 Inch F x F
AS Flange........... P/N 52-570-8-526
O 2007 TYCO FIRE 8�BUILDING PRODUCTS,451 North Cannon Avenue, Lansdale, Pennsylvania 19446
_ � . . .
• • � • • � �
300 PSI WWP Bronze Ball Valves Dezincification
Fire Protection Valve • Two-Piece Body • Chrome Plated Ball • Resistant
Blowout-Proof Stem • Reinforced PTFE Seats
300 PSI/20J Bar Non-Shock Cold Water
�:- �
�
CONFORMS TO MSS SP-110 • UL LISTEDt •
FM APPROVEDt r -
I�,� �
MATERIAL LIST y
PART SPECIFICATION �
1. Handle Nut Zinc Plated Steel KT-585-��-U�
2. Hantlle Zinc Plated Steel Clear Chromate ,/a"_1"Full Port
with Plastisol Grip Threaded
3. Threaded Pack Gland Brass ASTM B16
4. Packing PTFE KT-580-70-UL
5. Stem Silicon Bronze ASTM B371 Alloy C69430 1'/a"_3"Standard Port
or ASTM B99 Alloy C65100 Threaded
6. Thrust Washer Reinforced PTFE
7. Ball Brass ASTM B124 Alloy C37700 or ASTM
B16 Alloy C36000 with Hard Chrome Plate C�
8. Seat Aing(2) Aeinforced PTFE
9. Body Cast Red Bronze ASTM B584 Alloy C84400 �
10. Body End Piece Cast Red Bronze ASTM B584 Alloy C84400 3 �
Ya"and 3/a"size only has A304 stainless steel grounding washec 2
5 I 4 � B
�-L/
7
-- + --
,,; "-�% p
e �A s
�o
KT-585-70-UL
Full Port
DIMENSIONS-WEIGHTS-QUANTITIES NPT x NPT
KT-585-70-UL Dimensions
Size A B C D Port Weight Box Master KT-580-70-UL
In. mm. In. mm. In. mm. In. mm. In. mm. Lbs. Kg. Qty. Ctn.Qty. Stantlard Port
NPT x NPT
'/a 8 2.00 51 1.75 44 5.00 127 38 10 45 20 10 100
3/a 10 2.00 51 1.75 44 5.00 127 38 10 45 20 10 100
Yz 15 2.44 62 1.88 48 5.19 132 50 13 64 29 10 100
3/a 20 2.94 75 2.25 57 625 159 75 19 1.33 60 5 50
1 25 3.34 85 2.38 59 6.44 164 1.00 25 1.79 81 5 20
KT-580-70-UL Dimensions
Size A B C D Port Weiaht Box Master
In. mm. In. mm. In. mm. In. mm. In. mm. Lbs. Kg. Qty. Ctn.Qty.
1'/a 32 3.94 100 2.63 67 6J5 171 1.00 25 2.17 99 5 20
1 Yz 40 4.31 110 3.00 76 8.91 228 125 32 327 1.49 5 20
2 50 4.63 117 3.25 83 9.06 230 1.50 38 5.09 2.31 5 10
2'/2 65 5.84 148 3.53 90 9.66 245 2.00 51 8.25 3.79 2 6
3 80 7.09 202 4.41 112 11.53 293 2.50 64 15.65 7.11 1 4
t UL Listed,FM Approved for trim and drain use(UL Subject 285)-Sizes Ya"thru 2".
FM UL
APPROVED
NBCO INC.WORLD HEADQUAATERS•1516 MIDDLEBURY ST.•ELKHAAT,IN 46516-4740•USA•PH:1.800.234.0227 m
TECH SERVICES PH:1.888.446.4226•FAX:1.888.336.4226•INTERNATIONAL OFRCE PH:+1.574295.3327•FAX:+1.574.295.3455
www.nibco.com
� .- . . .
• • � • • , ,
200 PSI WWP Bronze Check Valves Dezincification
Fire Protection Valve � Horizontal Swing • Rubber Disc Resistant
200 PSI/13.8 Bar Non-Shock Cold Water
��
��. � ��
. � � � ��
. �
CONFORMS TO MSS SP-80 ��
_ ..
- ��'
MATERIAL LIST
PART SPECIFICATION KT 403-W
1. Bonnet Bronze ASTM B62 Threaded
or B584 Alloy C84400
2. Body Bronze ASTM B62
or 6584 Alloy C84400
3. Hinge Pin Bronze ASTM B140 Alloy C31400
or B134 Alloy C23000
4. Disc Hanger Bronze ASTM B62
5. Hanger Nut Bronze ASTM B97 Alloy C65500
or Brass ASTM B16
6. Disc Holder Bronze ASTM B62
7. Seat Disc Nitrile(W) �
PTFE(Y�# 3 �
Brass ASTM B16 s '
8. Seat Disc Nut , �
or B97 Alloy C65500
9. Hinge Pin Plug Branze ASTM B140 Alloy C32000 � �
(Not Shown) B
*10. Seat Disc Washer Stainless Steel ' � � �
*Sizes 3/a".7".1'/a"and 1'/z"only. 8
#2Yz'and 3"size only.
10
�\�
�- A -�
DIMENSIONS-WEIGHTS-QUANTITIES KT-403-W
Dimensions NPTx NPT
Size A B Weight Box Master.
In. mm. In. mm. In. mm. Lbs. Kg. Qty. Ctn.Qty.
'/z 15 2.44 62 1.69 43 58 26 10 50
3/a 20 2.94 75 1.88 48 92 42 10 50
1 25 3.56 90 2.31 59 1.55 70 5 30
1'/a 32 4.19 106 2.69 68 2.32 1.05 5 20
1'/z 40 4.50 114 2.94 75 3.00 1.36 2 10
2 50 5.25 133 3.81 97 4.87 2.21 2 10
2'/z 65 8.00 203 5.06 129 11.48 522 1 5
3 80 925 235 6.25 159 17.53 7.97 1 4
Sizes 2�/z'and 3"supplied as T-433-Y with PTFE seat disc.
NIBCO check valves may be installed in 6oth horizontal and vertical
lines with upward flow or in any intermediate position.
WARNING-Valve must be installed downstream of receiver tank if
used in line with reciprocating air compressor.
mNIBCO INC.WORLD HEADQUARTERS•1516 MIDDLEBURY ST.•ELKHART,IN 46516-4740•USA•PH:1.800234.0227
� TECH SERVICES PH:1.888.446A226•FAX:1.888336A226•WTERNATIONAL OFRCE PH:+1.574295.3327•FAX:+1.5742953455
www.nibco.com
�L � , � � FM
I , .
a�,y
_ �p'� •'J T..R �
t� 4
� �
f �
'��
r-
, '
.-�..•�.�-� ,�p� '��� -
� .--�.: ��T��[�f��!�i� � � ��� ,�� �
. �
_ � _. . _.,,_� � _
�_� ��, ,,��R .�,;s�.
� .� ,
a
❑
❑
a
❑
❑
visit us
on the Internet
at
- . . . .
10/00
�� F M
MODEL 1000 300 PSI
, A
� o
3�4�� ��� � ��4�� � ��2�� 2��
PLAN VIEW FRONT VIEW/VERTICAL INSTALLATION
� A� 1 fROM BRANCH
I � GAUGE INLET
B � PROVIDED
�D�- --- - - — �
TO DRAIN I �—� QO
� �
C � OO
I � I I STREET EL DRAIN
+ ����
FRONT VIEW/HORIZONTAL INSTALLATION i TO DRAIN
� , �
'' E —�� ORPEPEL ��
i �
� . ,�y
� �s� TO DRAIN 1
F
� '-` �� ���� RIGHT HAND/STRAIGHT INSTALLATION
�- H�-- - - � C� � -
_
TO DRAW � � O
G
1 � °
�
ORIFICE SIZE J
AVAILABLE - s/s, 7/16, 1/2, 17/32, ELO(5/8)*, ESFR(3/4)* �
DIMENSIONS- INCHES
SIZE A B C D E F G H
• MATERIAL LIST
PART: MATERIAL:
HANDLE STEEL
STEM ROD BRASS
BALL C.P.BRONZE
BODY BRONZE
VALVE SEAT IMPREGNATED TEFLON
INDICATOR PLATE STEEL
HANDLE LOCK SPRING STEEL
• . : •�• .
• .
UL LISTING EX4019
JOB NAME:
ARCHITECT:
ENGINEER:
MADE IN U.S.A. CONTRACTOR:
PFOR SMALL PIPE VSR—S
PO�� VANE TYPE WATERFLOW
� The Symbol of Protection ALARM SWITCH WITH RETARD
- UL,ULC,CSFM Listed and NYMEAAccepted
Service Pressure: Up to 300 PSI(20,7 BAR)
Flow Sensitivity Range for Signal: 4-10 GPM(15-38 LPM)UL
Maximum Surge: 18 FPS(5,5 m/s)
Enclosure: Die-cast,red enamel finish
Cover held in place with tamper resistant screws
Contact RaNngs: Two sets of SPDT(Form C)
- ]0.0 Ainps at 125/250 VAC
' �._ °� ��^ 2.0 Amps at 30 VDC Resistive
� l OmAmps min.at 24 VDC
_�'�" Conduit Entrances:Two openings provided for i/2"conduit.
� Individual switch compartments suitable for
dissimilar voltages.
Usage: Listed plastic,copper and schedule 40 iron pipe.
Fits pipe sizes- 1°(25mm), 1 ]/4°(32min), 1 1/2°(38mm)
� �,+ and 2"(SOmm)
Stock No. ll44440 Note: 12 paddles are fiirnished with each unit,one far each pipe
size of thrcadcd and swcatTEE,onc for 1"(25inm)CPVC,
one for 1°(25mm)CPVC(Central),one for 1"threaded Nibco
CPVC,and one for 1 ]/2°(38mm)threaded(Japan).
�W�R���� Environmental Specifications:
• NEMA-4/IP54 RaYed enclosure suitable far indoor or outdoar
Installation must be perfoined by qualified personnel and in use with factory installed gasket and dic-cast housing when used
accardance witl�all national and local codes and ordinances. with appropriate conduit fitting.
Shock hazard. Disconnect power source before scrvicing. • Temperature range:40°F to 120°F,(4,5°C to 49°C)UL
Serious injury or death could result. Service Use:
Risk of explosion. Not for use in hazardous locations. Serious Automatic Sprinkler NFPA-13
injury ar death could result. One or two family dwelling NFPA-13D
Residential occupancy up to four stories NFPA-]3R
National Firc Alarm Codc NFPA-72
Optional:Cover Tamper Switch Kit,Stock No.0090148
(See Fig.7 for terminations)
Replaceable Components:Retard/Switch Assembly,stock no. 1029030
The Model VSR-S is a vane type waterflow switch for use on wet Installation
sprinkler systems that use 1°(25mm), 1'/4"(32mm), 1'/z°(38mm)or 2" These devices may be mounted in horizontal or vertical pipe. On
(SOmm)pipe size.The unit may also be used as a sectional waterf3ow horizontal pipe they should be installed on the top side of the pipe where
dctectar on large systems. they will be accessible.i`he units should not be installed within 6°(15 cm)
The unit contains two single pole double throw snap action switches and of a valve,drain or fitting which changes the direction of the watertiow.
an adjustable, instantly recycling pneumatic retard. The switches are Select the proper paddle for thc pipe size and type of TEE used see Fig.
actuated when a flow of 10 gallons per minute(38 LPM)or more occurs 1 for instructions on changing paddle.The unit has a 1"NPT bushing
downstream of the dcvice.The flow condition must exist for a period of far threading into a non-corrosive TEE.See Fig.2 for proper TEE size,
time necessary to overcome the selected retard period. type and installation.Use no more than three wraps of teflon tape.
Enclosure Screw the device into the TEE fitting as shown in Fig.2.Care must be
The VSR-S switches and retard device are endosed in a general purpose, taken to properly orient the device for the direction of waterfiow.
die-cast housing.Thc cover is held in place with two tamper resistant The vane must not rub the inside of the TEE or bind in any way.The
screws which require a spccial kcy for removal.A field installable cover stem should move freely when operated by hand.
tamper switch is available as an option which may be used to indicate The device can also be used in copper or plastic pipe installations with
tmauthorized removal of the cover. See bulletin number 5401103 for the proper adapters so that the specified TEE fitting may be installed
installation instructions of this switch. on the pipe run.
Note:Do not leave cover off for an extcndcd period of time.
Potter Electric Signal Company,LLC•2081 Craig Road,St Lo�iis,MO,63146-4161•Phone:800-325-3936/Canada 888-882-1833•www.pottersignal.com
PRINTLD IN USA MPG.#5401206-R�V G PAG�1 OF 3
12/08
PFOR SMALL PIPE VSR—S
PO�� VANE TYPE WATERFLOW
� The Symbol of Protection ALARM SWITCH WITH RETARD
Fig. 1 Fig.2
FI..OW q,�MM
ReYa1'd Ad�uStment uo No'r�Envr:covee or-H Fok exreNOe�Pseioo oe�riMe �����h..�nrri�ox.
The time delay is factory set at 30 f 10 seconds. covea7nMPeR sw�TC„ �
The delay can be adjustedby rotating the retard —
adjustmcnt knob from 0 to the max setting(60-
I � ��t�,� / I
90 seconds).The time delay should be set at the I
minimum required to prevent false alanns. _-1__— w�,",
� ���A � Screw the device into the tee fitting as shown.
�� Care must be taken to properly arient the
o'R"T`°"°� M�u�r 5� device for the direction of waterflow.On sweat
WATERFLOW ARROW O�
� aus���NC ro�N�TS — tees,no threaded bushings,inserts,or adaptcrs
M DIIiCCTION OF
wn�����r�ow °� F�� are permitted,unless they comply with the
dimensions listed in the chart below.
, � '��"rT Im artant-The de th to the insidc bottom of
THREADED p p
F�TT�NC oN the tee should have the following dimensions:
ALL SIZiS �
AWARNING
R�N OY THETEH Approximatc Dcpth Raquircmcnl
MAY BE
There are 12 paddles fiut�ished wtth each�u�it. Tr�Reaoeooa T��s�z� Th«aded sw�a� cevc
5 W L:A'1'PIPL
One for each size of threaded,sweat or plastic —�� i°x r�x i�� z vie�� i 3i4�� z�ne��
�iaecT�on or
TE�as described in Fig.2.These paddles have wnTexr�ow i i ia°x i va°��° z�n a° z�n fi° wn
raised lettering that shows the pipe size and type �w��K����A i i ir�x i i iz°x i�� z i vi 6° z i ia�� Nin
of TEE that they a��e to be used with.The proper r�x z^x��� a����� z 3ra� Nia
paddlemustbeused.Thepaddlemustbeproperly snoWn W�th oPt�o��al co�e�ramPe� sW,t�h x;t.
attached(see drawing)and the screw tl�at l�olds AWARNING
Tl"le pad�e 1nUSt bG scclll"Cly 11�T]Y�nGCl. Do not use inore than three
wra}�s of teflon tape.
Fig.3 Switch Terminal Connections Clamping Plate Terminal Fig.7 Cover Tamper Switch Wiring
(Shown wifli covcr in placc)
�'�` AWARNING
„�
�,�
�� An uninsulated secrion of a single conductor should not be looped
� around the terminal and serve as two separate connections.The wire + + +
�o,�� pw�„y��, must be severed,thereby providing supervision of the connection in
a`s` the event that the wire become dislodged from under the terminal. C N.O. N C.
Failure to sever the wire may render the device inoperable risking (�'HT) (R�D) (sLK)
severe property damage and loss of life. oW�,�xR�o��R�
Fig.4 Typical Electrical Connections Fig.5 Fig.6
To remove knockouts: Breakoutthinsectionofcoverwhenwiring
� � aE�L NF�TRA�FA�O12 Place screwdriver at edge of both switches from one conduit entrance.
knockouts,not in the center.
POSITNE DC OR
j HOT AC /
) 7
� �
_ /
S
i n WA"I'L.RF�C.OWZ()h'FOh'
OO �IRC FAnLL �\
- ��
Notes: �
1. The Model VSR-S has two switches, one can be used to operate a F��
central station,proprietary or remote signaling unit,while the other
is used to operate a local audible or visual annunciator.
2. For supervised circuits see"Switch Terminal Connections"drawing r_
and caution note(Fig.3).
PRINT�D IN USA MPG.#5401206-R�V G PAGE 2 OP 3
12/08
PFOR SMALL PIPE VSR—S
PO�� VANE TYPE WATERFLOW
� The Symbol of Protection ALARM SWITCH WITH RETARD
Testing Removal
The frequency of inspection and testing for the Model VSR-S and its • To prevent accidental water damage,all control valves should
associated protective monitoring system should be in accordance with be shut tight and the system completely drained before watertiow
applicable NFPA Codes and Standards and/or the authority having detectors are removed or replaced.
jurisdiction(manufacturer reconvnends quarterly or more frequently.) • Turn off electrical power to the detectar,then disconnect wiring.
Aninspector'stestvalve(usuallylocatedattheendofthemostremotebranch • Use a wrench on the flats of the bushing.Turn the switch
line)should always be used for test purposes.lf there are no provisions for counterclockwise to disengage the pipe tUreads.
testing the operation of the flow detection device on the system,application • Gently lift with your fingers,roll the vane so it will fit through the
of thc VSR-S is not recommendcd ar advisable. holc while continuing to lift the waterflow detector.
A nvnimum flow of 10 gpm(38 Lpm)is required to activate this device. • Lift detector clear of pipe.
� P�ease advise the person responsible far testing of the A CAUTI O N
fire protection system that this system mustbe tested in accordance with
the testing instructions. Waterflowswitchesthataremonitoringwetpipesprinklersysteins
Maintenance shall not be used as the sole initiating device to discharge AFFF,
Inspect detectors monthly for leaks. If leaks are found, replace the deluge,orchenlical suppression systems.Watert3ow switches used
detecYor.The VSR-S waterftow switch should provide years of trouble- for this application may result in unintended discharges caused
free service.The retard and switch assembly are easily field replaceable. by surges,trapped air,or shart retard timcs.
In the unlikely event that either component does not perform properly,
please order replacement retard switch assembly stock#1029030.There
is no maintenance required,only periodic testing and inspection.
Mounting Dimensions
3.50" 5.56"
GROUND SCREWS (89.0 mm) (1412 mm)
p - - 2.00"
'�' � (50.8mm)
)1 i �� �
�
2.34"
(59.4 mm)
�_ i
4.89"
". 'fl' (523 mm)
� O: � F�Ow
0 1"-11 1/2 NPT
�jl_I :
DWGR 1206-5
PRINTLD IN USA MPG.#5401206-R�V G PAG�3 OF 3
12/08
RBVS
P PO�� UNIVERSAL BALL
� The Symbol of Protection VALVE SWITCH
�—�--� UL and cUL Listed,FM,CSFM Approved
Dimensions: (incLuding mounting clamps)
���n� Large Clamps 6°L x 5"W x 5.2"H
— 15,2 cm L x 12,7 cm W x 13,2 cm H
�� "`"�'��� � Small Clamps: 6"L x 4"W x 5.2"H
15,2 cm L x I 0,2 cm W x 13,2 cm H
Weight: With Large Clamps: 13.6 oz.(386,9 g.)
� �� With Small Cla�nps: 11.0 oz.(311,2 g.)
^` t� �'�'� � '� Enclosure: Non-CorrosiveCompositeMaterial
� Environmental Limitations:
� • NEMA 4 rated enclosure when proper electrical
fittings are used.(TP67)
- • Teroperature range:-40°F to 150°F(-40°C to 65°C)
W�i • Not for use in hazardous locations
Housing Cover Tamper: Activated by housing cover removal
US Patent No.6,945,509 (SYodc No. 1000035 only)
Contact Ratings:
SPDT Contacts: l0A at 125/250 VAC
RBVS Stock No. 1000040(w/o Cover Tamper) 2A at 30 VDC
RBVS-T Stock No. 1000035(w/Cover Tamper) SPDT Cover Tamper: 3A at 250 VAC
General installation On Lever Handle(See Fig.2)
The Model RBVS is desi�ed to monitor tl�e fully open position of a ball valve �. Select clamps aud clamping bolts based upon pipe/valve size,see Table 1.
installed in a sprinkler system.The unit will fit on most ball valves installed on 2 Insert rubber clamp grippers into clamps,see Fig.2.
back-flow-preventers and alarm trim lines of dry,alann,and deluge sprinkler 3. Place one clamp on top of pipe/ball valve near the valve handle and
valves.Tl�e swiYCh operates if the ball valve I�andle is moved from tlle open insert clamping bolts tlu-ough it.
position.However,the switch does not track the position of the handle or ball. 4. Place other clamp over clamping bolts from beneath the installation and
When the ball valve handle is in the open position,a spring-loaded switch button thread hex nuts onto thc clamping bolts,but do not fully tighten,(be sure
will contact the valve handle.When the I�andle is moved from the open position, I�ex nuts seatproperly in clamp hex recesses).(NOTE:Soine installations
this switch button extends to the tripped position,and the RBVS contacts change inay require one of the mounting bolts to be inserted from the bottom of
state,therebyo�eningorclosingacircuit.Acovertam�erswitchisavailableand the brackets and then trimmed to allow the extension bracket to clear.
is activaYed by thc removal of thc RBVS housing covcr.If an attempt is made See Fig.4)
to reinove the RBVS by the removal of the momlting brackets,the unit will be 5. Attach extension bracket(if necessary to use for positioning)to top clamp
set into the tripped mode by this action. using'/4-20 X 3/d'Hex bolt aud washer,but do not fully tighten.
The RBVS can bc mountcd to the hex portion of the ball valve or back-flow- 6. Attach°L"bracket(RBVS switch enclosure is loosely attad�ed to°L"
preventer or to the adjoining pipe via two clamps.The RB V S is shipped with two bracket)to extension braeket using'/4-20 X 3/4"Hex bolt and washer,but
sets of mounting clamps to accommodate various pipe and valve sizes,refer to do not fully tighten.
Table I.An"L"shaped and offset bracket for mounting the switch enclosure and �� Be sure ball valve is in the fully open position.
8. Slide loosely assembled RBVS switch encloslue to a position that permits
an extension bracket add to the mounting flexiUility of the RBVS.See°Typical the switch button to contact thc valve handle approximately I" from its
Mounting Diagram"and"lnstallation and Operation"on following page. inside end.See Fig.1 for approximate location.C�rt and remove the plastic
Tesfing coating froin the ball valve handle to allow the RBVS switch button to
The RBVS and its associated protective monitoring system should be tested contact(and be activated by)the metal of the handle.
in accordance with applicable NFPA codes and standards and/or the authority 9. Tighten clamping screws alternately to an eventua130 in-Ibs.(minimum)
having jurisdiction(manufacturer recommends quarterly or more frequently). of torque.
10. MainYain position of switch endosure over valve handle and secure bolt
Fig1 Internal Components that holds the extension bracket to the clamping assembly. It may be
NoRMn��v oPEN necessary to elose valve to access this bolt.
11. Position"L"bracket so that it contacts the back edge of the valve handle,and
NORMALLY CLOSED seciue its bolt.It may be necessary to close valve to access this bolt.
coMMON � 12. Wilh lhe ac[uator fuIly retracted,position RBVS switch enclosure to
� contact the valve handle squarely,see Fig. 1.
srRAiN REUEF � � 13. With RBVS switch enclosure held squarely in contactwith valve handle,
SWITCH euTroN securely tighten the two tamper resistant screws on the backside of the
BLACK - N.O. ° LOCATION ellC10SUT'e.
COVER RED - N.C.
TAMPER yyH17E - GOM ON HANDLE 14. C'IOSO a11C1 Op017 T.Y10 V3IV0 YO VePlfy OpeT3Y1011.T}le a.Ch1aY0Y SYIOUI(1 eaSl�y
�� retracl when the valve handle is in the open position.
15. Fully open the valve.
Mourvr so 16. Remove the cover and wire main switch and tam er switch if a licable.
SWITCH BUTTON PLASTIC COATING p pp
IS APPROX. 1" FROM REMOVED FROM CaT'efl.11ly TOUYe Yc'llllpel'SWIYCII W1T'eS tI1T'OU�TI]Sh'8ll1 T'ellef CI13T1T12I lll SWIYCII
HANDLE INSIDE END BALL VALVE HANDLE eriClOSill'e.FUIIy Se3t YY10 W1T'eS IlltO Ylle t70tYOTT1 Of YZle CI1311R01.S0e F1�T.1.
w SWITCH suTTON 17. Re lace RBVS switch enclosure cover and securel h hten cover screw.
DWG //1086-1 CONTACT AREA P Y g
Potter Electric Signal Company,LLC•208]Craig Road,St.Louis,MO,63146-4161•Phone:800-325-3936/Canada 888-882-1833•www.pottersignal.com
PRINTLD IN USA MPQ#5401086-RGV U PAG�1 OF 2
5/08
RBVS
P PO�� UNIVERSAL BALL
� The Symbol of Protection VALVE SWITCH
Fig.2 Typical Mounting Diagram Table 1 Clamp Sizing
� �ENCrH Pipe Valve/Size Clamp Clamping Bolts
6"
swircN 1/2"to 3/4"(12,5 to 19min) Small 10-32 x 2 1/2
� Ervc�osuRE � 1"to 2"(25 to SOmm) Large 1/4-20 x 4"
�
°L" BRACKET
� HEIGHT Switch Terminal Connections,Clamping Plate Terminal
0 5.2.'
EXT. BRACKET
(IF NECESSARY) I `�c°���C A CAUTI O N
� �� An uninsulated section ofsingle conductor
CLAMPS O � should not Ue looped around the temilnal
�d and serve as two seperatf;connections.The
C�AMP o���°� °V�'0'�"�' wire must be severcd,thereby providing
GRiPPERS supervision ofthe connection in the event
W I DTH
4" (SMALL� that the wirc becomcs dislodged from
DwG #1086-2 5° (LARGE) under the terminal.
Typical Electrical Connections
LOCAL CIRCUIT
TRANSFORMER OR BATTERY POWER STYLE D (CLASS A) SUPERVISED LOOP STYLE B (CLASS 6) SUPERVISED CIRCUIT
�Ny.c-.
° SIGNALING COM. CDM, i0 N.C.
N.O. DEVICE N.O. N.O. CONTROL COM. END-OF-LWE RESISTOR
UNIT N 4
N.C. � N.C. /� DWG. k1086-4
Tamper Switch ConnecYions Fig.3
COVER TAMPER & RBVS CONNECTED COVER TAMPER & RBVS WIRED swrtcH cmc�osuae
TO THE SAME ZONE ON THE FACP TO SEPERATE ZONES
COVEft
TAMPER �
COM. N.O.COM. � OFFSEi BRACKET
COM. N.O. COM.
FACP COVER EOLR N.C.
TAMPER FA�P EOLR FpC�EOLR �
N 0.
OwG.a1086-5 � �
Installation on Tee Handle(See F+ig.3) � �� �
1. Select clamps and clamping bolts based upon pipe/valve size,see Table 1. ` ef�c�E� �
2. Inscrt rubber clamp grippers into clamps,See Fig.3.
3. Place one damp on top of pipe/ball valve near the valve handle and °`"��s
insert clamping bolts through it �
4. Place other clamp over clamping bo(ts from beneath the installation �aP E� ow�
Niaes-3
and thread hex nuts onto the clamping bolts,but do not fully tighten,
(be surc hcx nuts seat properly in clamp hex recesses).
5. Loosely attach °L" bracket to the 'bffset" bracket and "offset"
bracket to the RBVS housing. Fig.4
6. Be sure ball valve is in the fully open position.
7. Slide loosely assembled RBVS switch enclosure to a position that RBVS �
permits the switch button to contact the valve handle approximately � ,,�, �
1/2"from the end ofthe handle.Cut andremove the plastic coating
from the ball valve handle to allow the RBVS switch button to contact
(and be activated by)the metal of the handle. �
8. Tighten clamping screws alternately and YQ-20 X 3/4"bolt to 30 in-lbs. a
�llll111ll1Ull1�Of tOTClUG. SOMC I�STALLATIONS MAY
9. With the valve handle fully open, slide the RBVS l�ousing down cnosemreaFeaFNCp.
until the switcl�operates plus 1/8 inch.Tighten the screws holding BcTweeN MouNT��c eo�Tn��
OFFSFT BRACKFT.INSTAI.L BOLT
the RBVS to the"offset"bracket. FaoM soTTOM nN�reim ns �'iP�
l0.Remove the RBVS switeh enclosure eover. N�:�:���a�,�ocow�zF:c�:
11. Close and open thc valve to verify operation. The actuator should
easily retract up when the valve handle is in the open position.
12.Fully open the valve.
13.Wire main switch and tamper switch(if applicable).Carefully route
tamper switch wires through strain relief channel in switch enclosure.
Fully scat the wires into the bottom of the channel.See Fig. 1. owc�:iox�-e
14.Replace RBVS switch enclosure cover and securely tighten cover screw.
PRINTCD IN USA MPG.#5401086-RLV U PAGE 2 OP 2
5/08
WHEELOCK
PPO�� SERIES MT AND MT STROBE
� The Symbol ofProtection MULTITONE ELECTRONIC SIGNALS
Wheelock's MT and MT Strobe Series Multitone Electronic Signals offer a choice of eight(8)nationally and internationally
recognized alerting sounds: Horn,Bell,March Time Horn,Code-3 Tone,Code-3 Horn,Slow Whoop,Siren or Hi/Lo Tone.
Wheelock's Code-3 horn and tone patterns are engineered to comply with NFPA/ANSI Temporal Pattern specifications
without requiring additional coding means. With MT and MT Strobe Signals, one alarm appliance meets most of your
signaling needs. Wheelock's MT and MT Strobe Signals are UL Listed, FM, CSFM and NYMEA Approved.
Features
• One alarm appliance with (8) eight selective signals to
provide superior sound penetration for various ambient `
and wall conditions with two field selectable sound output 1����C'� � �
levels. � �
• Code-3 Horn and Tone meet NFPA/ANSI/ISO temporal i
pattern for standard emergency evacuation signaling. � �
• Audible and strobe can operate from a single signaling � �}
circuit. r�
• Designed to meet orexceed NFPA/ANSI Standards and � �
ADA Accessibility Guidelines. 110 VAC model does not _
meet ADA requirements. '
• Lowcurrentdrawwithlowtemperaturecompensationto
reduce power consumption and wiring costs.
• Low cost installation via standard electrical boxes.
Attractive flush or surface mounting options available. MT-24-�5�sw-FR SHOwtv
MT-121575W-FR MT 12/24 MT-24-1575W-FR* MT4-115-WH-VFR
(Strobe/Horn) (Horn) (Strobe/Horn) Indoor (Strobe/Horn)
Model Stock No. 1610921 Stock No. 1610914 Stock No. 1610915 Stock No. 1610216
Mounting Options** Mounting Options** Mounting Options** Mounting Options**
D,E,F,L,M,O,P,R D,E,F,L,M,O,P,R D,E,F,L,M,O,P,R D,E,J,K,N,O,R
dBA and Current Ratings
Average Current Ratings(Amps) dBA Reverberant Ratings dBA Anechoic Ratings
Per UL 464
Tone @ 24VDC @ 12VDC @ 24VDC @ 12VDC @ 12 and 24VDC
HI STD HI STD HI STD HI STD HI STD
Horn 0.038 0.024 0.095 0.019 92 87 90 77 99 93
Bell 0.019 0.012 0.030 0.010 86 80 85 69 92 87
March Time Horn 0.038 0.024 0.095 0.019 89 84 89 74 99 93
Code-3 Horn 0.038 0.024 0.095 0.019 88 83 88 73 99 93
Code-3 Tone 0.027 0.016 0.057 0.014 85 80 84 70 95 90
Slow Whoop 0.047 0.025 0.095 0.024 90 89 89 75 99 94
Siren 0.034 0.022 0.078 0.019 89 84 89 75 98 93
Hi/Lo 0.020 0.013 0.042 0.011 86 81 86 71 93 88
* For outdoor installation use MTWP-2475W-FR with IOB-R backbox.
** See next page for mounting options.
Potter Electric Signal Company•2081 Craig Road,St.Louis,MO,63146-4161 •Phone:800-325-3936/Canada 888-882-1833•www.pottersignal.com
PRINTED IN USA MKT.#8850002-REV H PAGE 1 OF 2
2/03
WHEELOCK
PPO�� SERIES MT AND MT STROBE
� The Symbol ofProtection MULTITONE ELECTRONIC SIGNALS
MOUNTING ACCESSORIES
(D)4"SQUARE,FLUSH(BO) (E)4"SQUARE,DEEP,FLUSH(BO) (F)DOUBLE-GANG,FLUSH(BO)
O o �p 0/
/
0 p 0 � 0 0 O
0 0�� p ��O � 0 1 0�
��oDo a0 /o�o � 0 0 o I
0
MAXIMUMNUMBEROFGONOUGTORS MAXIMUMNUMBEROFCONOUCTORS MAXIMUMNUMBEROFGONDUGTORS
AWG.#18 AWG.p16 AWG.#14 AWG.#12 AWG.#18 AWG.pt6 AWG.#14 AWG.#12 AWG.#18 AWG.Kt6 AWG.#14 AWG.Nt2
4 A 4 4 8 8 8 4 4 4 4 4
(J)BB BACKBOX (K)WBB WEATHER RESISTANT BACKBOX (L)ISP SURFACE ADAPTER
(OrderCode:2830) (OrderCode:2959) (Order Code:5306)
Standard steel backbox with knockouts for Sturdy die-casthousing,threaded conduithole Indooruse.
interior surface mounting,concealed conduit and knockout for outdoor applications.It is
mounting or semi-flush applications. It is painted to match the signal.
painted to match the signal.
,-�n w
�.a,.--I �-un— .�n 1�'—
�-ue
00
O
Oo0 >� � ,�� I �-•�
,.,,.
Op O O � I'"I� 79/�2 �.w � •-aia
o0 , ,. I
,T� �
o� .,:aa� �.n� � ._v�
„�:�.-�
MAXIMUMNUMBEROFGONOUGTORS MAXIMUMNUMBEROFCONDUCTORS MAXIMUMNUMBEROFCONDUCTORS
AWG.#18 AWG.W16 AWG.#14 AWG.pt2 AWG.#18 AWG.ki6 AWG.#14 AWG.#12 AWG.#18 AWG.pt6 AWG.#14 AWG.#t2
4 4 4 4 4 4 4 4 8 8 8 4
(0)RP-R RETROFIT PLATE (R)SFP SEMI-FLUSH PLATE (M)10B BACKBOX
(OrderCode:5042) (OrderCode:2957) (Order Code:5046)
Stamped aluminum surface wall plate which For surface mounting MT products.
mounts behind the basic unit and serves to
cover recessed backboxes in semi-flush �
�'^ mounting applications.It is painted to match o -�- � 'I
'-'^� �I—"�'� the signal.
� ��a vr
I �y�� �Il�f/�[ a-T/Y- 00%c1Y�OW)
}�Y�f f-i/�b
Y!/! }L!W
���Y6 O Te o o+
1-M � O �
I O e �
� � � O � O 1-fA
>�.vn— }c o c+
MAXIMUM NUMBER OF CONDUCTORS
��i. ����,1-i AWG.#18 AWG.k16 AWG.#14 AWG.#12
8 B 8 4
MOUNTING NOTES
CAUTION:The mounting options figures show the maximum numberoffield wires(conductors)that can enterthe backbox used with each mounting option.Ifthese limits are
exceeded,there may be insufficient space in the backbox to accommodate the field wires and stresses from the wires could damage the product.
Although the limits shown for each mounting option comply with the National Electrical code(NEC),Wheelock recommends use of the largest backbox option and the use of
approved stranded field wires whenever possible,to provide additional wiring room for easy installation and minimum stress on the product from wiring.
CAUTION:Check that the installed product will have sufficient clearance and wiring room prior to installing backboxes and conduit,especially if sheathed multiconductor cable
or 3/4"conduit fittings are used.
1. Mounting hardware for each mounting option is supplied.
2. Conduit entrancestothe backbox should be selected to provide sufficientwiring clearanceforthe installed product.When extension rings are required,conduit should enter
through the backbox,not the extension ring.Use Steel City#53151(1-1/2"deep)or#53171(2-1/8"deep)extension rings(as noted in the mounting options)or equivalent
with the same cut-out area.
3. When terminating field wires,do not use more lead length than required.Excess lead length could result in insufficient wiring space for the appliance.
4. Use care and proper techniques to position the field wires in the backbox so that they use minimum space and produce minimum stress on the product.This is especially
important for stiff,heavy gauge wires and wires with thick insulation or sheathing.
5. Do not pass additional wires(used for other than the appliance)through the backbox.Such additional wires could result in insufficient wiring space for the appliance.
PRINTED IN USA MKT.#8850002-REV H PAGE 2 OF 2
2/03
• • ' ■
. ..
. . •. • .
� APPLICATION
Designed for installation on potable water lines between the
backflow preventer or pressure reducing valve and the water
heater to protect against water thermal expansion. When
system pressure increases,water enters the tank's bladder
which expands into the pre-charged air chamber, keeping
system pressure below the relief valve setting.
�
STANDARDS COMPLIANCE
FEATURES • IAPMOOListed UPC
Sizes (liters): ❑ 8 ❑ 18 ❑ 32 ❑ 50V • NSFO Listed �
❑ 75V ❑ 120V ❑ 165V ❑ 320V
(V=vertical,free-standing)
Maximum working water pressure 150 PSI MATERIALS
End connections Threaded NPT
ANSI B1.20.1 Outer shell High Grade Steel
Precharge(adjustable) 40 PSI Coatings Epoxy finish(outer shell)
Connection Brass (sizes: 8 thru 32)
5 yearwarranty Stainless Steel (sizes: 50V thru 320V)
Bladder Butyl Rubber(FDA approved)
ACCESSORIES
❑ BR4 - water pressure reducing valve
❑ TP1100A - temperature&pressure relief valve
❑ P1000A - pressurereliefvalve
❑ 975XL - reduced pressure backflow preventer
NOTE: Model WXTP tanks are certified to NSF Standard
61 cold, but are suitable for temperatures up to 200°F.
DIMENSIONS&WEIGHTS(do not include pkg.)
.. .
Page 1 of 2 �
� SIZING CHART �
I
Based upon 100° F temperature rise(40° F to 140° F) X=multiple tanks required(contact your WILKINS Rep)
TYPICAL INSTALLATION
Local codes shall govern installation requirements. Unless otherwise specified, the assembly shall be mounted on the cold
water supply and at least 18"from the cold water inlet to the heater. Note: If incoming water pressure is above 40 psi, the
precharge pressure of the expansion tank should be adjusted to equal the incoming water pressure,not to exceed 80 psi.
MODEL WXTP INSTALLATION MODEL WXTP INSTALLATION"V"SERIES
SPECIFICATIONS
The Water Thermal Expansion Tank shall be IAPMOO and NSFO Listed. The outer shell shall be high grade steel
with exterior coating. The bladder shall be FDA approved butyl rubber and prevent water from contact with shell
interior.The assembly shall incorporate a shrader valve for adjustable air precharge and a lead free bronze system
connection.The Water Thermal Expansion Tank shall be a WILKINS Model WXTP.
Page 2 of 2
WILKINS a Zurn Company, 1747 Commerce Way, Paso Robles, CA 93446 Phone:805/238-7100 Fax:805/238-5766
IN CANADA:ZURN INDUSTRIES LIMITED,3544 Nashua Dr., Mississauga,Ontario L4V 1L2 Phone:905/405-8272 Fax:905/405-1292
Product Support Help Line: 1-877-BACKFLOW (1-877-222-5356) • Website: http://www.zurn.com
GUARDIAN
FIREEQUIPMENT,�n,c. DETAIL AND SUBMITTAL SHEET
MIAMI, FL
Ph.800.327.6584•Fax 800.827.3869
• 111 � • • •
Project/Location: Date:
Architect/Engineer:
Contractor:
DAppropriate Selection
Used as auxiliary connections through which the fire department can pump
water to supplement existing water supplies. Provides 250 GPM flow (mini- ���=°N�pp�e P,ate
(by others)� O
mum), per 2'/z" inlet. �
Swivel ia ° ��
Inlet
Single- inlet connections incorporate a straight-thru, non-clappered de- �
Plug 3�` 4'/d'
sign with female NPT outlets.
sooz
Two and three-wav inlet connections feature brass bodies (angle or
straight pattern), with integral drop-clapper inlets and female NPT outlets. z,,,,or3.. �3��=�o�4'/a'Dia.
Nipple—a Plate
(by others) _ ����
Standard components, all connections: sW;�e,� � �
Female hose thread swivel inlets, plugs with chains and identification '"'e` I I
plate. Cast brass construction, standard. P'�g� 3,= I�,"�I
6014/6015
. - . .
•�- � ❑ 6002 ❑ 601� ❑ 6015 ❑6016 ❑6017 z��z"or s° —3vz°or 4��8°�ia.
Nipple� Plate
• �'/z� Z��z" 3„ 2��z,� 3" �by others) �
- �'/z" 2�/z° 2�/p" 2'/2" 2�/z" Swivel� o � �„
Inlet �
4'/2' O.D. 7"O.D. 7"O.D. 7"SQ 7"SQ
Plug� 3'/1' �7"�
Indentification Plate Lettering:AUTO SPKR
6016/6017
. . . .
•�-
A A C�
• • ' . ��- ' C � ..�'"_._�� � �
• B � B � �
❑6024 Back 4"x 2'/z"x 2'/z° 2 115/8" 7'/8" --- 75/8" �– �
❑6025 Bottom 4"X 2'/z"X 2'/z" 2 12'/e° 6'/a„ 7'/s" 75/s„ 2vz'NiPP�e �-Y svz'�ia.
(by others) -�� Plate �
❑6026 Top 4"x 2'/z°'x 2'/z" 2 12'/s" 6'/a" 7'/s" 75/s" swi�e�,.=o o � _� T
Inlet �- (� � 9"
❑6027 Back 6"x 2'/z"x 2'/2" 2 115/8" 7'/8" --- 75/8" Plug� s�i�� � d
❑6028 Bottom 6"X 2'/z"X 2'/z" 2 12'/s° 75/a" 7'/e° 75/a" � I f! �
❑6029 Top 6"x 2'/2"x 2'/2" 2 12'/8„ 8„ 9„ 7„ 15
❑6034 Back 4"x 2'/z"x 2'/z"x 2'/�° 3 173/a" 6'/e" --- g5�8�° 6024-6029
❑6037 Back 6°x 2'/z"x 2�/2"x 2�/Z" 3 173/a° 6'/8" --- 65/8„
❑6038 Bottom 6"x 2'/�"x 2'/Z°x 2'/z° 3 173/8° 75/8„ 7,/e° 65/8°
A A C �
❑6039 Top 6"x 2'/z"x 2'/z"x 2'/z" 3 173/8° 75/8" 7'/a° 65/8° ��' � � � � ��
Indentification Plate Lettering �� �
2Yz"Nipple�
❑AUTO SPKR ❑AUTO SPKR&STANDPIPE (byomer5) � P�ate 3'�='o�a.
Swivel A J �
❑STANDPIPE ❑DRY STANDPIPE �n�et�z u � (� � � s"
Plug 3'/z" � ��
� ---�+�—-{- D
Optional Finish:❑-B Polished Brass Threads: z3"�
❑-C Rough Chrome Plated ❑NST 6034-6039
❑-D Polished Chrome Plated ❑Other
Contact factory for current listings and approvals