HomeMy WebLinkAboutB13-0451 ELECTRICAL PLANS APPROVEDELECTRICAL SPECIFICATIONS GENERAL REQUIREMENTS DRAWINGS ARE DIAGRAMMATIC AND DO NOT INDICATE ALL FITTINGS, JUNCTION BOXES, ETC. REQUIRED. PROVIDE ALL REQUIRED EQUIPMENT, CONDUIT, FITTINGS, WIRING, BOXES, ETC. FOR A COMPLETE AND OPERATIONAL INSTALLATION. WORK AND EQUIPMENT SHALL COMPLY WITH STATE AND LOCALLY ADOPTED CODES AND STANDARDS, INCLUDING THE NATIONAL ELECTRICAL CODE (NEC), INTERNATIONAL CODES (I-CODES), AND LOCAL AMENDMENTS. ANYTHING DRAWN OR SPECIFIED SHALL NOT BE CONSTRUED TO CONFLICT WITH STATE AND LOCALLY ADOPTED CODES AND STANDARDS, INCLUDING THE NATIONAL ELECTRICAL CODE, WHICH GOVERNS THE INSTALLATION OF ANY ELECTRICAL WORK. ITEMS SHALL NOT BE INSTALLED IN CONFLICT WITH THE NEC. RESOLVE ANY AND ALL CONFLICTS PRIOR TO INSTALLATION. BECOME THOROUGHLY ACQUAINTED WITH THE CONDITIONS UNDER WHICH WORK IS TO BE PERFORMED. EXAMINE ALL SERVICES, EQUIPMENT, AND EXISTING CONDITIONS, WHICH THIS WORK IS IN ANY WAY DEPENDENT UPON, AND BRING ANY DISCREPANCIES OR OMISSIONS FOUND IN THE DRAWINGS TO THE ELECTRICAL ENGINEER'S ATTENTION PRIOR TO SUBMITTING BID. THE LOCATION OF OUTLETS AND EQUIPMENT SHOWN ON THE DRAWINGS ARE APPROXIMATE. THE ARCHITECT AND ENGINEER SHALL HAVE THE RIGHT TO ADJUST THE LOCATION OF OUTLETS OR FIXTURES, WITHIN 10' OF THE SPECIFIED LOCATION, BEFORE THEY ARE INSTALLED AND WITHOUT ADDITIONAL COST. PROVIDE DRAWINGS TO LOCAL BUILDING AUTHORITY AND OBTAIN A PERMIT PRIOR TO STARTING ANY WORK. NOTIFY ELECTRICAL ENGINEER OF ANY CHANGES REQUESTED BY THE LOCAL BUILDING AUTHORITY IMMEDIATELY AND PRIOR TO STARTING WORK. VERIFY AND COMPLY WITH UTILITY COMPANY REQUIREMENTS. PROVIDE METERING, CONNECTION CABINETS, CT CABINETS, AND TRANSFORMER AND CONNECTION CABINET PADS PER LOCAL UTILITY COMPANY REQUIREMENTS. PROVIDE A REDLINED AS-BUILT SET OF ELECTRICAL DRAWINGS TO OWNER UPON COMPLETION OF WORK. ELECTRICAL WORK SHOWN LIGHT OR MARKED "E" IS EXISTING, SHOWN DARK IS NEW, AND SHOWN DASHED IS EXISTING TO BE REMOVED OR RELOCATED UNLESS OTHERWISE INDICATED. DASHING MAY ALSO INDICATE UNDER FLOOR OR UNDER GROUND CONDUIT. IF UNCLEAR, CONTACT ELECTRICAL ENGINEER FOR CLARIFICATION. EQUIPMENT, WIRING, AND DEVICES SHOWN ARE NEW UNLESS OTHERWISE NOTED. MAINTAIN CIRCUITING TO EXISTING EQUIPMENT AND DEVICES TO REMAIN. INSTALL EQUIPMENT AND DEVICES PER THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. NOTIFY ELECTRICAL ENGINEER, PRIOR TO INSTALLING EQUIPMENT AND DEVICES, IF MANUFACTURER'S INSTALLATION INSTRUCTIONS CONFLICT WITH ELECTRICAL INFORMATION ON THE THESE DRAWINGS. ELECTRICALLY OPERATED EQUIPMENT SHOWN ON PLANS, AND NOT CIRCUITED ON THE ELECTRICAL PLANS, WILL REQUIRE ELECTRICAL SERVICE. CONTACT ELECTRICAL ENGINEER FOR CONNECTION REQUIREMENTS AND CLARIFICATION PRIOR TO BID. THE COST FOR THIS WORK SHALL BE INCLUDED IN THE BID. PROVIDE HANGERS AND SUPPORTS TO ADEQUATELY AND SECURELY SUPPORT ELECTRICAL SYSTEM COMPONENTS IN A NEAT AND WORKMANLIKE MANNER. MAINTAIN THE FIRE RATING OF THE ASSEMBLY (CEILING, WALL, OR FLOOR) IN WHICH EQUIPMENT, WIRING, AND DEVICES ARE TO BE INSTALLED. SUBMITTALS AND SUBSTITUTIONS PROVIDE PRODUCT DATA SHEETS AND SHOP DRAWINGS FOR EQUIPMENT, FIXTURES, AND DEVICES TO ELECTRICAL ENGINEER PRIOR TO PURCHASING. REVIEW, STAMP AND INITIAL ALL ELECTRICAL SUBMITTALS AND SHOP DRAWINGS CERTIFYING THAT THE SUBMITTALS HAVE BEEN REVIEWED PRIOR TO SUBMITTING TO ELECTRICAL ENGINEER FOR REVIEW. EQUIPMENT AND FIXTURES SPECIFIED REPRESENT REQUIRED QUALITY AND PERFORMANCE. PROVIDE PRODUCT DATA SHEETS AND SHOP DRAWING OF PROPOSED SUBSTITUTIONS TO SPECIFIED EQUIPMENT TO ELECTRICAL ENGINEER FOR REVIEW. ELECTRICAL ENGINEER SHALL DETERMINE THE ACCEPTABILITY OF SUBSTITUTIONS TO SPECIFIED EQUIPMENT. REVIEW, STAMP AND INITIALED ALL ELECTRICAL SUBMITTALS AND SHOP DRAWINGS CERTIFYING THAT SUBMITTALS HAVE BEEN REVIEWED PRIOR TO SUBMITTING TO ELECTRICAL ENGINEER FOR REVIEW. SUBMITTALS AND SHOP DRAWINGS ARE TO INCLUDE THE FOLLOWING: KEY TO PLAN DESIGNATIONS, MANUFACTURER, MODEL NUMBER, DATA SHEETS, QUANTITIES, COLORS, LABELS, DIMENSIONS, INSTALLATION INSTRUCTIONS, AND ANY ADDITIONAL INFORMATION REQUIRED TO DETERMINE IF THE PRODUCT MEETS THE DESIGN INTENT. CONSTRUCTION PHASE REVIEW REQUIREMENTS INSTALL POWER, LIGHTING, COMMUNICATIONS AND SPECIAL SYSTEM (FIRE ALARM, SECURITY, BUILDING AUTOMATION, ETC) BOXES PRIOR TO RUNNING CABLE OR CONDUIT TO BOXES. ARRANGE FOR OWNER, ARCHITECT, AND ENGINEER TO REVIEW BOX LOCATIONS PRIOR TO RUNNING CABLE OR CONDUIT TO BOXES. ADJUST BOXES AS DIRECTED BY OWNER, ARCHITECT, AND ENGINEER. REQUESTS FOR MODIFICATIONS TO THE CONTRACT (CHANGE ORDERS) REQUESTS BY CONTRACTOR FOR ADDITION OR REDUCTION TO THE CONTRACT AMOUNT SHALL BE ACCOMPANIED BY THE FOLLOWING FOR EVALUATION BY THE OWNER AND ENGINEER: 1.ORIGIN AND DATE OF CLAIM 2.QUANTITIES OF PRODUCTS, LABOR, AND EQUIPMENT 3.DOLLAR AMOUNT OF TAXES, OVERHEAD, AND PROFIT 4.JUSTIFICATION FOR ANY CHANGE IN CONTRACT TIME 5.CREDIT AMOUNT FOR DELETIONS (WITH DOCUMENTATION) 6.DATES AND TIMES OF WORK PERFORMED, AND BY WHOM 7.TIME RECORDS AND WAGE RATES PAID 8.INVOICES AND RECEIPTS FOR PRODUCTS AND EQUIPMENT SUBMIT ALL DOCUMENTATION TO ENGINEER AND OWNER, AND OBTAIN WRITTEN APPROVAL PRIOR TO STARTING ANY WORK THAT AFFECTS THE CONTRACT AMOUNT OR COMPLETION DATE. EXISTING CONDITIONS THESE DRAWINGS CONTAIN INFORMATION REGARDING EXISTING CONDITIONS. THIS INFORMATION WAS COMPILED FROM EXISTING DRAWINGS OR CASUAL FIELD OBSERVATIONS. IN SOME CASES, ASSUMPTIONS WERE MADE WHEN FIELD OBSERVATIONS OR EXISTING DRAWINGS DID NOT PROVIDE NECESSARY INFORMATION (I.E. LOCKED DISCONNECTS, NO WIRE SIZE INDICATED, NAMEPLATE DATA MISSING, INACCURATE AS-BUILT DRAWINGS, ETC.). EXISTING CONDITIONS SHALL BE VERIFIED AND ALLOWED FOR PRIOR TO BID AND CONSTRUCTION. NOTIFY THE ELECTRICAL ENGINEER OF ANY DISCREPANCIES WITH THESE DRAWINGS IMMEDIATELY AND PRIOR TO COMMENCING ANY FURTHER WORK. COORDINATION THE ELECTRICAL DRAWINGS ARE ONLY ONE PART OF A COMPLETE SET OF CONSTRUCTION DOCUMENTS. EXAMINE THE ARCHITECTURAL, MECHANICAL, AND PLUMBING DRAWINGS PRIOR SUBMITTING BID AND STARTING WORK TO DETERMINE THE FULL EXTENT OF ELECTRICAL WORK REQUIRED. COORDINATE WORK WITH OTHER TRADES PRIOR TO ROUGH-IN. COORDINATION SHALL INCLUDE REVIEWING THE ARCHITECTURAL, MECHANICAL, PLUMBING, ETC. DRAWINGS AND SHOP DRAWINGS PRIOR TO BID AND CONSTRUCTION. OBTAIN AND REVIEW SHOP DRAWINGS, PRODUCT DATA, MANUFACTURER'S WIRING DIAGRAMS AND MANUFACTURER'S INSTRUCTIONS FOR EQUIPMENT PROVIDED BY OTHERS. THE FINAL LOCATION OF EQUIPMENT SHALL BE COORDINATED IN THE FIELD, PRIOR TO ROUGH-IN, TO MEET APPLICABLE LOCATION, HEIGHT AND CLEARANCE REQUIREMENTS. DEMOLITION DISCONNECT WIRING TO EQUIPMENT, DEVICES, AND FIXTURES TO BE REMOVED. REMOVE EQUIPMENT, WIRING, DEVICES AND CONDUIT NOT BEING USED. FIELD VERIFY EXISTING CONDITIONS TO DETERMINE EXTENT OF DEMOLITION WORK. REFERENCE ARCHITECTURAL, MECHANICAL, AND ELECTRICAL PLANS FOR ADDITIONAL INFORMATION. MAINTAIN THE ELECTRICAL SERVICE TO EXISTING EQUIPMENT AND DEVICES TO REMAIN. MAINTAINING EXISTING SERVICES MAINTAIN THE ELECTRICAL SERVICE TO EXISTING TENANTS AND AREAS. ANY SERVICE DISCONTINUITY SHALL BE COORDINATED AND APPROVED BY OWNER AND TENANTS PRIOR TO OUTAGE. IF REQUIRED, PROVIDE TEMPORARY POWER DURING OUTAGE. WIRING AND CONDUIT NEW WIRING SHALL BE THHN/THWNƒ&,NSULATED COPPER UNLESS OTHERWISE NOTED. ALUMINUM CONDUCTORS SHALL BE XHHW-2, INSULATED COMPACT STRAND. THE CONDUCTORS FOR 15A AND 20A BRANCH CIRCUITS SHALL BE #12 THHN/THWN-2, ƒ& INSULATED COPPER. $%5$1&+&,5&8,76,1':(//,1*81,760$<%(7++17+:1ƒ&,168/$7('&233(5 BRANCH-CIRCUIT CONDUCTORS GREATER THAN 20A SHALL BE AS INDICATED ON PLANS OR REQUIRED PER CODE. CONDUCTOR INSULATION SHALL BE COLOR CODED AS FOLLOWS: 9‘3+$6($%/$&.3+$6(%5(' 7+(0$;,080180%(52)&21'8&7256,1$&21'8,7)25$‘6<67(06+$//%(7:2 $‘%‘  NOT INCLUDING NEUTRAL AND EQUIPMENT GROUNDING CONDUCTORS UNLESS OTHERWISE INDICATED. CONDUIT SIZE SHALL BE BASED UPON NEC CHAPTER 9 AND ANNEX C. MORE THAN 3 CURRENT-CARRYING CONDUCTORS MAY BE INSTALLED IN A RACEWAY IF THE APPROPRIATE AMPACITY-DERATING FACTORS ARE APPLIED. PROVIDE A DEDICATED NEUTRAL FOR EACH LINE-TO-NEUTRAL CIRCUIT UNLESS A MULTI-POLE BREAKER, WHICH DISCONNECTS ALL PHASE CONDUCTORS THAT SHARE A NEUTRAL, IS PROVIDED (LISTED BREAKER-TIES ARE PERMITTED). PROVIDE AN INSULATED EQUIPMENT GROUNDING CONDUCTOR WITH ALL FEEDERS AND BRANCH-CIRCUIT WIRING. INCREASE CONDUIT SIZE AS REQUIRED TO ACCOMMODATE EQUIPMENT GROUNDING CONDUCTOR. IN FINISHED AREAS, WHERE CONDUIT AND CABLE CAN NOT BE CONCEALED IN WALLS OR CEILINGS (I.E. EXISTING MASONRY CONSTRUCTION), PROVIDE WIREMOLD OR EQUAL SURFACE MOUNTED RACEWAY AS APPROVED BY ARCHITECT OR ENGINEER. THE TYPE OF CONDUIT SHALL BE AS FOLLOWS FOR ALL FEEDERS AND BRANCH CIRCUITS, UNLESS OTHERWISE SPECIFIED OR REQUIRED. REFERENCE THE NEC FOR ADDITIONAL APPLICATION REQUIREMENTS. APPLICATION TYPE OF CONDUIT IN CONCRETE OR MASONRY EMT, GRC OR PVC OUTDOORS (ABOVE GRADE)EMT OR GRC BRANCH CIRCUITS (EXPOSED) EMT OR GRC BRANCH CIRCUITS (CONCEALED) MC CABLE OR EMT SUPPLY TO DISTRIBUTION PANELS EMT OR GRC UNDERGROUND PVC SCHED. 40 OR 80 AS REQ'D OVERHEAD SERVICE ENTRANCE GRC (2" MIN) SER AND NM CABLE MAY BE USED IN RESIDENTIAL PROJECTS WHERE PERMITTED BY THE NEC. ALL CONDUITS AND CABLES PASSING THROUGH RATED WALLS, FLOORS OR CEILINGS SHALL BE FIRE STOPPED WITH APPROVED FIRE BARRIER CAULK. INSTALL CAULK PER MANUFACTURE'S INSTRUCTIONS AND MAINTAIN THE RATING OF THE WALL, FLOOR, OR CEILING BEING PENETRATED. DEVICES DEVICE AND FACEPLATE COLOR SHALL BE AS SPECIFIED BY THE ARCHITECT OR TO MATCH EXISTING. COORDINATE FACEPLATE AND DEVICE COLORS WITH ARCHITECT, INTERIOR DESIGNER AND OWNER PRIOR TO PURCHASING AND INSTALLING DEVICES AND FACEPLATES. PROVIDE RESIDENTIAL GRADE SWITCHES AND RECEPTACLES. PROVIDE DEVICES AS INDICATED BELOW: DEVICE MANUFACTURER MODEL NUMBER INCANDESCENT DIMMER LUTRON NOVA SERIES PROVIDE TAMPER-RESISTANT RECEPTACLES IN DWELLING UNITS. PROVIDE GFI PROTECTION FOR 120V, 15A AND 20A RECEPTACLES INSTALLED IN THE FOLLOWING DWELLING UNIT LOCATIONS: BATHROOMS; GARAGES; OUTDOORS; CRAWL SPACES; UNFINISHED SPACES; KITCHENS (WHERE RECEPTACLES SERVE COUNTERTOP SURFACES); LAUNDRY, UTILITY, AND WET-BAR SINKS (WITHIN 6' OF OUTSIDE EDGE OF SINK); AND LOCATIONS INDICATED ON POWER PLAN. PROVIDE WEATHER-RESISTANT RECEPTACLES FOR RECEPTACLES INSTALLED IN DAMP OR WET LOCATIONS. PROVIDE HUBBELL RECEPTACLES WITH THE APPROPRIATE NEMA CONFIGURATION FOR RECEPTACLES SHOWN ON THE ELECTRICAL PLAN. PROVIDE 6' CORD AND PLUG FOR SPECIAL-PURPOSE RECEPTACLES IF EQUIPMENT TO BE INSTALLED IS NOT SUPPLIED WITH A CORD AND PLUG. PROVIDE WIRING DEVICES AS MANUFACTURED BY HUBBELL, PASS AND SEYMOUR, LEVITION, WATT-STOPPER, LUTRON OR EQUAL. COORDINATE MOUNTING HEIGHTS OF SWITCHES, RECEPTACLES, PHONE OUTLETS, DATA OUTLETS, TV OUTLETS, AND LIGHT FIXTURES WITH ARCHITECTURAL DRAWINGS. THE MOUNTING HEIGHT FOR DEVICES SHALL BE AS INDICATED BELOW, UNLESS OTHERWISE NOTED. MOUNTING HEIGHTS ARE TO CENTER OF DEVICE, UNLESS OTHERWISE NOTED. MATCH MOUNTING HEIGHT OF EXISTING DEVICES IF APPLICABLE. GENERAL RECEPTACLES (RESIDENTIAL) @12" AFF ABOVE COUNTER RECEPTACLES AND SWITCHES @ 2" ABOVE COUNTER OR BACKSPLASH TO BOTTOM OF DEVICE (COORDINATE WITH ARCHITECT) GARAGE OUTLETS @ 48" AFF TV OUTLETS (RESIDENTIAL) @ 12" AFF DATA/PHONE OUTLETS (RESIDENTIAL) @ 12" AFF PROVIDE "IN-USE" WEATHERPROOF COVER FOR EXTERIOR RECEPTACLES. COMPLY WITH ADA STANDARDS FOR MOUNTING HEIGHTS AND LOCATIONS. DEVICES IN THE SAME LOCATION AND AT THE SAME MOUNTING HEIGHT SHALL BE MOUNTED UNDER A COMMON WALL PLATE. DISTRIBUTION EQUIPMENT PROVIDE DISTRIBUTION PANELS, DISCONNECTS, CONTACTORS, ETC. OF VOLTAGE, AMPERAGE, PHASE, AND SHORT-CIRCUIT RATINGS AS INDICATED ON PLANS. PROVIDE A LISTED BREAKER-TIE OR MULTI-POLE BREAKER FOR EACH MULTIWIRE (SHARED NEUTRAL) BRANCH CIRCUIT. PROVIDE DISTRIBUTION EQUIPMENT AS MANUFACTURED BY AMERICAN MIDWEST POWER, SQUARE D, ELECTRO-MECHANICAL INDUSTRIES, CUTLER-HAMMER, SIEMENS, ERICKSON ELECTRIC, GE OR METRON. THE MOUNTING HEIGHT FOR DISTRIBUTION EQUIPMENT SHALL BE AS INDICATED BELOW, UNLESS OTHERWISE NOTED. PANELS/LOADCENTERS - 6' AFF MAX TO CENTER OF TOP HANDLE DISCONNECT SWITCHES - 6'-6" AFF MAX TO CENTER OF HANDLE PROVIDE A TYPED PANEL SCHEDULE WITH LOAD DESCRIPTIONS FOR PANELS AFFECTED BY THIS PROJECT. PROVIDE A PHENOLIC LABEL ON EACH NEW OR RENAMED PANEL INDICATING THE PANEL NAME. LIGHTING OWNER TO PROVIDE LUMINAIRE SPECIFICATIONS. NOTIFY ELECTRICAL ENGINEER OF ANY DISCREPANCIES WITH THESE DRAWINGS. MAKE CONNECTIONS TO LIGHT FIXTURES USING BUILDING WIRE WITH INSULATION SUITABLE FOR TEMPERATURE CONDITIONS WITHIN THE LUMINAIRE. MAINTAIN THE FIRE RATING OF THE ASSEMBLY (CEILING OR WALL) IN WHICH LIGHT FIXTURES ARE TO BE INSTALLED. PROVIDE FIRE-RATED FIXTURES OR PROVIDE BOX AROUND FIXTURES AS MANUFACTURED BY TENMAT, EZ BARRIER OR EQUAL. BRANCH-CIRCUIT WIRING SCHEDULE (UNLESS OTHERWISE NOTED) 15 A #12 AWG #12 AWG #12 AWG 1/2" 20 A #12 AWG #12 AWG #12 AWG 1/2" 25 A #10 AWG #10 AWG #10 AWG 1/2" 30 A #10 AWG #10 AWG #10 AWG 1/2" 35 A #8 AWG #8 AWG #10 AWG 3/4" 40 A #8 AWG #8 AWG #10 AWG 3/4" 45 A #6 AWG #6 AWG #10 AWG 1" 50 A #6 AWG #6 AWG #10 AWG 1" 60 A #4 AWG #4 AWG #10 AWG 1 1/4" 70 A #4 AWG #4 AWG #8 AWG 1 1/4" 80 A #3 AWG #3 AWG #8 AWG 1 1/4" 90 A #2 AWG #2 AWG #8 AWG 1 1/2" 100 A #1 AWG #1 AWG #8 AWG 1 1/2" NOTES: 1.FOR MOTOR LOADS, USE MCA (MINIMUM CIRCUIT AMPACITY) TO SIZE PHASE AND NEUTRAL CONDUCTORS AND USE MOCP (MAXIMUM OVER-CURRENT PROTECTIVE DEVICE) TO SIZE EQUIPMENT GROUNDING CONDUCTOR. 2.INCREASE PHASE, NEUTRAL, AND EQUIPMENT GROUNDING CONDUCTOR SIZES BY 1 STANDARD CONDUCTOR SIZE PER EACH 75' OF CONDUCTOR LENGTH. INCREASE CONDUIT SIZE ACCORDINGLY. A A PROVIDE CLEAR SPACE EQUAL TO THE WIDTH OF EQUIPMENT OR 30", WHICHEVER IS GREATER. B PROVIDE THE FOLLOWING CLEAR SPACE IN FRONT OF EQUIPMENT: 3' FOR 0-150 L-G VOLTAGE AND 4' FOR 151-600 L-G VOLTAGE. C PROVIDE CLEAR SPACE, FOR THE WIDTH OF THE EQUIPMENT, FROM GRADE, FLOOR OR PLATFORM TO A HEIGHT OF 6-1/2' OR THE HEIGHT OF THE EQUIPMENT, WHICHEVER IS GREATER. D THE SPACE EQUAL TO THE WIDTH AND DEPTH OF THE EQUIPMENT AND EXTENDING FROM THE FLOOR TO A HEIGHT OF 6' ABOVE THE EQUIPMENT OR TO THE STRUCTURAL CEILING, WHICHEVER IS LOWER, SHALL BE DEDICATED TO THE ELECTRICAL INSTALLATION - NO PIPING, DUCTS, LEAK PROTECTION APPARATUS, OR OTHER EQUIPMENT FOREIGN TO THE ELECTRICAL INSTALLATION SHALL BE LOCATED IN THIS ZONE. SUSPENDED CEILINGS WITH REMOVABLE PANELS SHALL BE PERMITTED WITHIN THE 6' ZONE. SPRINKLER PROTECTION SHALL BE PERMITTED FOR THE DEDICATED SPACE WHERE THE PIPING COMPLIES WITH THIS SECTION. A DROPPED, SUSPENDED, OR SIMILAR CEILING THAT DOES NOT ADD STRENGTH TO THE BUILDING STRUCTURE SHALL NOT BE CONSIDERED A STRUCTURAL CEILING. E THE AREA ABOVE THE DEDICATED SPACE SHALL BE PERMITTED TO CONTAIN FOREIGN SYSTEMS, PROVIDED PROTECTION IS INSTALLED TO AVOID DAMAGE TO THE ELECTRICAL EQUIPMENT FROM CONDENSATION, LEAKS, OR BREAKS IN SUCH FOREIGN SYSTEMS. B C D D E E CLEAR SPACE/WORKING SPACE ABOUT ELECTRICAL EQUIPMENT THE FINAL LOCATION OF EQUIPMENT SHALL BE COORDINATED IN THE FIELD, PRIOR TO ROUGH-IN, TO MEET APPLICABLE LOCATION, HEIGHT AND CLEARANCE REQUIREMENTS. THE ELECTRICAL CONTRACTOR SHALL STOP WORK IMMEDIATELY, AND ADVISE OTHERS TO STOP WORK IF THERE IS A CONFLICT WITH THE ELECTRICAL CLEARANCE AND WORK SPACE REQUIREMENTS PER THE ABOVE INFORMATION AND THE NEC. D FRONT VIEW OF EQUIPMENT SIDE VIEW OF EQUIPMENT M VC S S M Project Number Date Drawn by Checked by E1 REVISIONS CLIENT: No.Description Date JEFF GATES 13367 10/9/13 BEK BEK VA I L R A C Q U E T C L U B BU I L D I N G 1 1 , U N I T 1 46 5 0 V A I L R A C Q U E T C L U B D R I V E VA I L , C O 8 1 6 5 7 NOT ISSUED FOR CONSTRUCTION UNLESS SIGNED THROUGH THE SEAL IN BLUE INK OR DIGITALLY SIGNED BY BRYAN KAZIN. LIMITED TO ELECTRICAL. 36628 10/9/13 By David Rhoades at 4:33 pm, Oct 09, 2013 B13-0451 WH AC GFI +72" AC GFI AC GFI AC GFI +30" GFIL1 REF DW DISP MW FP CONVERT PANEL INTO JUNCTION BOX AC GFI SS SS WP GFI UC UC UC L17 (UNIT 17 PANEL) PANEL AMPERAGE 100 MAIN BREAKER MLO PANEL VOLTAGE 240/120 BREAKER AIC RATING (MIN)10,000 DESCRIPTION BREAKER CIRCUIT NUMBER PHASE CIRCUIT NUMBER BREAKER DESCRIPTION GENERAL LTG & RECEPTS 15A1P/AFC 1 A 2 20A1P/AFC WATER HEATER GENERAL LTG & RECEPTS 15A1P/AFC 3 B 4 20A1P/AFC BATHROOM RECEPTACLE REFRIGERATOR 20A1P 5 A 6 DISHWASHER 20A1P 7 B 8 DISPOSAL 20A1P 9 A 10 SMALL APPLIANCE 20A1P/AFC 11 B 12 SMALL APPLIANCE 20A1P/AFC 13 A 14 HOOD/MICROWAVE 20A1P 15 B 16 17 A 18 19 B 20 21 A 22 23 B 24 PANEL L1 PANEL L1 (3 #2 AL, 1 #6 AL G)SER OR 1 1/4"C (100A) UNIT 17 LOAD CALCULATION LOAD DESCRIPTION LOAD QUANTITY TOTAL LOAD GENERAL LIGHTING AND RECEPTACLES 3.0VA/ft^2 500ft^2 1.5kVA SMALL APPLIANCE 1.5kVA 2 3.0kVA DISPOSAL 0.9kVA 1 0.9kVA DISHWASHER 1.2kVA 1 1.2kVA RANGE (GAS RANGE)0.5kVA 1 0.5kVA MICROWAVE 1.5kVA 1 1.5kVA WATER HEATER/BOILER (GAS)1.0kVA 1 1.0kVA FIRE PLACE 0.0kVA 0 0.0kVA 0.0kVA 0 0.0kVA -0.0kVA 0 0.0kVA TOTAL 9.6kVA FIRST 10kVA @ 100%10.0kVA REMAINDER @ 40%0.0kVA -0.0kVA 0 0.0kVA -0.0kVA 0 0.0kVA -0.0kVA 0 0.0kVA TOTAL LOAD 10.0kVA TOTAL AMPERAGE @ 208V ‘48A METER CENTER LOAD CALCULATION LOAD DESCRIPTION LOAD QUANTITY TOTAL LOAD GENERAL LIGHTING AND RECEPTACLES 3.0VA/ft^2 12000ft^2 36.0kVA SMALL APPLIANCE 1.5kVA 48 72.0kVA -0.0kVA 0 0.0kVA -0.0kVA 0 0.0kVA TOTAL 108.0kVA 1ST 3000VA @ 100%3.0kVA 3,000VA TO 120,000VA @ 35%36.8kVA OVER 120,000VA @ 25%0.0kVA DISPOSAL @ 75%0.9kVA 24 16.2kVA DISHWASHER @ 75%1.2kVA 24 21.6kVA MICROWAVE @ 75%1.5kVA 24 27.0kVA WATER HEATER/BOILER (GAS) @ 75%1.0kVA 24 18.0kVA HOUSE PANEL 25.0kVA TOTAL LOAD 147.6kVA TOTAL AMPERAGE @ 208V ‘410A 150kVA 9‘:6(&21'$5< UTILITY CO. TRANSFORMER FAULT CURRENT CALCULATIONS (END OF CONDUCTOR) LOCATION DESCRIPTION STARTING ISC MINIMUM CONDUCTOR LENGTH PHASE MULTIPLIER VOLTAGE # OF CONDUCTOR SETS C VALUE ISC END @ METER CENTER 14,400 15 1.73 208 3 20,867 13,998 @ PANEL L17 13,998 30 1.73 208 1 3,729 7,228 800A METER CENTER 9‘:,1387 9‘:287387 CONVERT PANEL INTO JUNCTION BOX 3 PARTIAL ONE-LINE DIAGRAM NOT TO SCALE NOTES: 1.EQUIPMENT, WIRING, AND DEVICES SHOWN LIGHT ARE EXISTING, SHOWN DARK ARE NEW, AND SHOWN HATCHED ARE EXISTING TO BE REMOVED UNLESS OTHERWISE NOTED. 2.NEW WIRING SHALL BE THHN/THWN-2 INSULATED COPPER UNLESS OTHERWISE NOTED. 1 POWER PLAN SCALE: 1/4" = 1'-0" (APPROX)2 LIGHTING PLAN SCALE: 1/4" = 1'-0" (APPROX) Project Number Date Drawn by Checked by E2 REVISIONS CLIENT: No.Description Date JEFF GATES 13367 10/9/13 BEK BEK VA I L R A C Q U E T C L U B BU I L D I N G 1 1 , U N I T 1 46 5 0 V A I L R A C Q U E T C L U B D R I V E VA I L , C O 8 1 6 5 7 NOT ISSUED FOR CONSTRUCTION UNLESS SIGNED THROUGH THE SEAL IN BLUE INK OR DIGITALLY SIGNED BY BRYAN KAZIN. LIMITED TO ELECTRICAL. 36628 10/9/13