HomeMy WebLinkAboutB13-0451 ELECTRICAL PLANS APPROVEDELECTRICAL SPECIFICATIONS
GENERAL REQUIREMENTS
DRAWINGS ARE DIAGRAMMATIC AND DO NOT INDICATE ALL FITTINGS, JUNCTION BOXES, ETC.
REQUIRED. PROVIDE ALL REQUIRED EQUIPMENT, CONDUIT, FITTINGS, WIRING, BOXES, ETC. FOR A
COMPLETE AND OPERATIONAL INSTALLATION.
WORK AND EQUIPMENT SHALL COMPLY WITH STATE AND LOCALLY ADOPTED CODES AND
STANDARDS, INCLUDING THE NATIONAL ELECTRICAL CODE (NEC), INTERNATIONAL CODES
(I-CODES), AND LOCAL AMENDMENTS.
ANYTHING DRAWN OR SPECIFIED SHALL NOT BE CONSTRUED TO CONFLICT WITH STATE AND
LOCALLY ADOPTED CODES AND STANDARDS, INCLUDING THE NATIONAL ELECTRICAL CODE, WHICH
GOVERNS THE INSTALLATION OF ANY ELECTRICAL WORK. ITEMS SHALL NOT BE INSTALLED IN
CONFLICT WITH THE NEC. RESOLVE ANY AND ALL CONFLICTS PRIOR TO INSTALLATION.
BECOME THOROUGHLY ACQUAINTED WITH THE CONDITIONS UNDER WHICH WORK IS TO BE
PERFORMED. EXAMINE ALL SERVICES, EQUIPMENT, AND EXISTING CONDITIONS, WHICH THIS WORK
IS IN ANY WAY DEPENDENT UPON, AND BRING ANY DISCREPANCIES OR OMISSIONS FOUND IN THE
DRAWINGS TO THE ELECTRICAL ENGINEER'S ATTENTION PRIOR TO SUBMITTING BID.
THE LOCATION OF OUTLETS AND EQUIPMENT SHOWN ON THE DRAWINGS ARE APPROXIMATE. THE
ARCHITECT AND ENGINEER SHALL HAVE THE RIGHT TO ADJUST THE LOCATION OF OUTLETS OR
FIXTURES, WITHIN 10' OF THE SPECIFIED LOCATION, BEFORE THEY ARE INSTALLED AND WITHOUT
ADDITIONAL COST.
PROVIDE DRAWINGS TO LOCAL BUILDING AUTHORITY AND OBTAIN A PERMIT PRIOR TO STARTING
ANY WORK.
NOTIFY ELECTRICAL ENGINEER OF ANY CHANGES REQUESTED BY THE LOCAL BUILDING AUTHORITY
IMMEDIATELY AND PRIOR TO STARTING WORK.
VERIFY AND COMPLY WITH UTILITY COMPANY REQUIREMENTS. PROVIDE METERING, CONNECTION
CABINETS, CT CABINETS, AND TRANSFORMER AND CONNECTION CABINET PADS PER LOCAL UTILITY
COMPANY REQUIREMENTS.
PROVIDE A REDLINED AS-BUILT SET OF ELECTRICAL DRAWINGS TO OWNER UPON COMPLETION OF
WORK.
ELECTRICAL WORK SHOWN LIGHT OR MARKED "E" IS EXISTING, SHOWN DARK IS NEW, AND SHOWN
DASHED IS EXISTING TO BE REMOVED OR RELOCATED UNLESS OTHERWISE INDICATED. DASHING
MAY ALSO INDICATE UNDER FLOOR OR UNDER GROUND CONDUIT. IF UNCLEAR, CONTACT
ELECTRICAL ENGINEER FOR CLARIFICATION.
EQUIPMENT, WIRING, AND DEVICES SHOWN ARE NEW UNLESS OTHERWISE NOTED.
MAINTAIN CIRCUITING TO EXISTING EQUIPMENT AND DEVICES TO REMAIN.
INSTALL EQUIPMENT AND DEVICES PER THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.
NOTIFY ELECTRICAL ENGINEER, PRIOR TO INSTALLING EQUIPMENT AND DEVICES, IF
MANUFACTURER'S INSTALLATION INSTRUCTIONS CONFLICT WITH ELECTRICAL INFORMATION ON
THE THESE DRAWINGS.
ELECTRICALLY OPERATED EQUIPMENT SHOWN ON PLANS, AND NOT CIRCUITED ON THE
ELECTRICAL PLANS, WILL REQUIRE ELECTRICAL SERVICE. CONTACT ELECTRICAL ENGINEER FOR
CONNECTION REQUIREMENTS AND CLARIFICATION PRIOR TO BID. THE COST FOR THIS WORK SHALL
BE INCLUDED IN THE BID.
PROVIDE HANGERS AND SUPPORTS TO ADEQUATELY AND SECURELY SUPPORT ELECTRICAL
SYSTEM COMPONENTS IN A NEAT AND WORKMANLIKE MANNER.
MAINTAIN THE FIRE RATING OF THE ASSEMBLY (CEILING, WALL, OR FLOOR) IN WHICH EQUIPMENT,
WIRING, AND DEVICES ARE TO BE INSTALLED.
SUBMITTALS AND SUBSTITUTIONS
PROVIDE PRODUCT DATA SHEETS AND SHOP DRAWINGS FOR EQUIPMENT, FIXTURES, AND DEVICES
TO ELECTRICAL ENGINEER PRIOR TO PURCHASING. REVIEW, STAMP AND INITIAL ALL ELECTRICAL
SUBMITTALS AND SHOP DRAWINGS CERTIFYING THAT THE SUBMITTALS HAVE BEEN REVIEWED
PRIOR TO SUBMITTING TO ELECTRICAL ENGINEER FOR REVIEW.
EQUIPMENT AND FIXTURES SPECIFIED REPRESENT REQUIRED QUALITY AND PERFORMANCE.
PROVIDE PRODUCT DATA SHEETS AND SHOP DRAWING OF PROPOSED SUBSTITUTIONS TO
SPECIFIED EQUIPMENT TO ELECTRICAL ENGINEER FOR REVIEW. ELECTRICAL ENGINEER SHALL
DETERMINE THE ACCEPTABILITY OF SUBSTITUTIONS TO SPECIFIED EQUIPMENT. REVIEW, STAMP
AND INITIALED ALL ELECTRICAL SUBMITTALS AND SHOP DRAWINGS CERTIFYING THAT SUBMITTALS
HAVE BEEN REVIEWED PRIOR TO SUBMITTING TO ELECTRICAL ENGINEER FOR REVIEW.
SUBMITTALS AND SHOP DRAWINGS ARE TO INCLUDE THE FOLLOWING: KEY TO PLAN DESIGNATIONS,
MANUFACTURER, MODEL NUMBER, DATA SHEETS, QUANTITIES, COLORS, LABELS, DIMENSIONS,
INSTALLATION INSTRUCTIONS, AND ANY ADDITIONAL INFORMATION REQUIRED TO DETERMINE IF
THE PRODUCT MEETS THE DESIGN INTENT.
CONSTRUCTION PHASE REVIEW REQUIREMENTS
INSTALL POWER, LIGHTING, COMMUNICATIONS AND SPECIAL SYSTEM (FIRE ALARM, SECURITY,
BUILDING AUTOMATION, ETC) BOXES PRIOR TO RUNNING CABLE OR CONDUIT TO BOXES. ARRANGE
FOR OWNER, ARCHITECT, AND ENGINEER TO REVIEW BOX LOCATIONS PRIOR TO RUNNING CABLE
OR CONDUIT TO BOXES. ADJUST BOXES AS DIRECTED BY OWNER, ARCHITECT, AND ENGINEER.
REQUESTS FOR MODIFICATIONS TO THE CONTRACT (CHANGE ORDERS)
REQUESTS BY CONTRACTOR FOR ADDITION OR REDUCTION TO THE CONTRACT AMOUNT SHALL BE
ACCOMPANIED BY THE FOLLOWING FOR EVALUATION BY THE OWNER AND ENGINEER:
1.ORIGIN AND DATE OF CLAIM
2.QUANTITIES OF PRODUCTS, LABOR, AND EQUIPMENT
3.DOLLAR AMOUNT OF TAXES, OVERHEAD, AND PROFIT
4.JUSTIFICATION FOR ANY CHANGE IN CONTRACT TIME
5.CREDIT AMOUNT FOR DELETIONS (WITH DOCUMENTATION)
6.DATES AND TIMES OF WORK PERFORMED, AND BY WHOM
7.TIME RECORDS AND WAGE RATES PAID
8.INVOICES AND RECEIPTS FOR PRODUCTS AND EQUIPMENT
SUBMIT ALL DOCUMENTATION TO ENGINEER AND OWNER, AND OBTAIN WRITTEN APPROVAL PRIOR
TO STARTING ANY WORK THAT AFFECTS THE CONTRACT AMOUNT OR COMPLETION DATE.
EXISTING CONDITIONS
THESE DRAWINGS CONTAIN INFORMATION REGARDING EXISTING CONDITIONS. THIS INFORMATION
WAS COMPILED FROM EXISTING DRAWINGS OR CASUAL FIELD OBSERVATIONS. IN SOME CASES,
ASSUMPTIONS WERE MADE WHEN FIELD OBSERVATIONS OR EXISTING DRAWINGS DID NOT
PROVIDE NECESSARY INFORMATION (I.E. LOCKED DISCONNECTS, NO WIRE SIZE INDICATED,
NAMEPLATE DATA MISSING, INACCURATE AS-BUILT DRAWINGS, ETC.).
EXISTING CONDITIONS SHALL BE VERIFIED AND ALLOWED FOR PRIOR TO BID AND CONSTRUCTION.
NOTIFY THE ELECTRICAL ENGINEER OF ANY DISCREPANCIES WITH THESE DRAWINGS IMMEDIATELY
AND PRIOR TO COMMENCING ANY FURTHER WORK.
COORDINATION
THE ELECTRICAL DRAWINGS ARE ONLY ONE PART OF A COMPLETE SET OF CONSTRUCTION
DOCUMENTS. EXAMINE THE ARCHITECTURAL, MECHANICAL, AND PLUMBING DRAWINGS PRIOR
SUBMITTING BID AND STARTING WORK TO DETERMINE THE FULL EXTENT OF ELECTRICAL WORK
REQUIRED.
COORDINATE WORK WITH OTHER TRADES PRIOR TO ROUGH-IN. COORDINATION SHALL INCLUDE
REVIEWING THE ARCHITECTURAL, MECHANICAL, PLUMBING, ETC. DRAWINGS AND SHOP DRAWINGS
PRIOR TO BID AND CONSTRUCTION.
OBTAIN AND REVIEW SHOP DRAWINGS, PRODUCT DATA, MANUFACTURER'S WIRING DIAGRAMS AND
MANUFACTURER'S INSTRUCTIONS FOR EQUIPMENT PROVIDED BY OTHERS.
THE FINAL LOCATION OF EQUIPMENT SHALL BE COORDINATED IN THE FIELD, PRIOR TO ROUGH-IN,
TO MEET APPLICABLE LOCATION, HEIGHT AND CLEARANCE REQUIREMENTS.
DEMOLITION
DISCONNECT WIRING TO EQUIPMENT, DEVICES, AND FIXTURES TO BE REMOVED. REMOVE
EQUIPMENT, WIRING, DEVICES AND CONDUIT NOT BEING USED. FIELD VERIFY EXISTING
CONDITIONS TO DETERMINE EXTENT OF DEMOLITION WORK. REFERENCE ARCHITECTURAL,
MECHANICAL, AND ELECTRICAL PLANS FOR ADDITIONAL INFORMATION.
MAINTAIN THE ELECTRICAL SERVICE TO EXISTING EQUIPMENT AND DEVICES TO REMAIN.
MAINTAINING EXISTING SERVICES
MAINTAIN THE ELECTRICAL SERVICE TO EXISTING TENANTS AND AREAS. ANY SERVICE
DISCONTINUITY SHALL BE COORDINATED AND APPROVED BY OWNER AND TENANTS PRIOR TO
OUTAGE. IF REQUIRED, PROVIDE TEMPORARY POWER DURING OUTAGE.
WIRING AND CONDUIT
NEW WIRING SHALL BE THHN/THWN&,NSULATED COPPER UNLESS OTHERWISE NOTED.
ALUMINUM CONDUCTORS SHALL BE XHHW-2, INSULATED COMPACT STRAND.
THE CONDUCTORS FOR 15A AND 20A BRANCH CIRCUITS SHALL BE #12 THHN/THWN-2, &
INSULATED COPPER.
$%5$1&+&,5&8,76,1':(//,1*81,760$<%(7++17+:1&,168/$7('&233(5
BRANCH-CIRCUIT CONDUCTORS GREATER THAN 20A SHALL BE AS INDICATED ON PLANS OR
REQUIRED PER CODE.
CONDUCTOR INSULATION SHALL BE COLOR CODED AS FOLLOWS:
93+$6($%/$&.3+$6(%5('
7+(0$;,080180%(52)&21'8&7256,1$&21'8,7)25$6<67(06+$//%(7:2$%
NOT INCLUDING NEUTRAL AND EQUIPMENT GROUNDING CONDUCTORS UNLESS OTHERWISE
INDICATED. CONDUIT SIZE SHALL BE BASED UPON NEC CHAPTER 9 AND ANNEX C. MORE THAN 3
CURRENT-CARRYING CONDUCTORS MAY BE INSTALLED IN A RACEWAY IF THE APPROPRIATE
AMPACITY-DERATING FACTORS ARE APPLIED.
PROVIDE A DEDICATED NEUTRAL FOR EACH LINE-TO-NEUTRAL CIRCUIT UNLESS A MULTI-POLE
BREAKER, WHICH DISCONNECTS ALL PHASE CONDUCTORS THAT SHARE A NEUTRAL, IS PROVIDED
(LISTED BREAKER-TIES ARE PERMITTED).
PROVIDE AN INSULATED EQUIPMENT GROUNDING CONDUCTOR WITH ALL FEEDERS AND
BRANCH-CIRCUIT WIRING.
INCREASE CONDUIT SIZE AS REQUIRED TO ACCOMMODATE EQUIPMENT GROUNDING CONDUCTOR.
IN FINISHED AREAS, WHERE CONDUIT AND CABLE CAN NOT BE CONCEALED IN WALLS OR CEILINGS
(I.E. EXISTING MASONRY CONSTRUCTION), PROVIDE WIREMOLD OR EQUAL SURFACE MOUNTED
RACEWAY AS APPROVED BY ARCHITECT OR ENGINEER.
THE TYPE OF CONDUIT SHALL BE AS FOLLOWS FOR ALL FEEDERS AND BRANCH CIRCUITS, UNLESS
OTHERWISE SPECIFIED OR REQUIRED. REFERENCE THE NEC FOR ADDITIONAL APPLICATION
REQUIREMENTS.
APPLICATION TYPE OF CONDUIT
IN CONCRETE OR MASONRY EMT, GRC OR PVC
OUTDOORS (ABOVE GRADE)EMT OR GRC
BRANCH CIRCUITS (EXPOSED) EMT OR GRC
BRANCH CIRCUITS (CONCEALED) MC CABLE OR EMT
SUPPLY TO DISTRIBUTION PANELS EMT OR GRC
UNDERGROUND PVC SCHED. 40 OR
80 AS REQ'D
OVERHEAD SERVICE ENTRANCE GRC (2" MIN)
SER AND NM CABLE MAY BE USED IN RESIDENTIAL PROJECTS WHERE PERMITTED BY THE NEC.
ALL CONDUITS AND CABLES PASSING THROUGH RATED WALLS, FLOORS OR CEILINGS SHALL BE
FIRE STOPPED WITH APPROVED FIRE BARRIER CAULK. INSTALL CAULK PER MANUFACTURE'S
INSTRUCTIONS AND MAINTAIN THE RATING OF THE WALL, FLOOR, OR CEILING BEING PENETRATED.
DEVICES
DEVICE AND FACEPLATE COLOR SHALL BE AS SPECIFIED BY THE ARCHITECT OR TO MATCH
EXISTING. COORDINATE FACEPLATE AND DEVICE COLORS WITH ARCHITECT, INTERIOR DESIGNER
AND OWNER PRIOR TO PURCHASING AND INSTALLING DEVICES AND FACEPLATES.
PROVIDE RESIDENTIAL GRADE SWITCHES AND RECEPTACLES.
PROVIDE DEVICES AS INDICATED BELOW:
DEVICE MANUFACTURER MODEL NUMBER
INCANDESCENT DIMMER LUTRON NOVA SERIES
PROVIDE TAMPER-RESISTANT RECEPTACLES IN DWELLING UNITS.
PROVIDE GFI PROTECTION FOR 120V, 15A AND 20A RECEPTACLES INSTALLED IN THE FOLLOWING
DWELLING UNIT LOCATIONS: BATHROOMS; GARAGES; OUTDOORS; CRAWL SPACES; UNFINISHED
SPACES; KITCHENS (WHERE RECEPTACLES SERVE COUNTERTOP SURFACES); LAUNDRY, UTILITY,
AND WET-BAR SINKS (WITHIN 6' OF OUTSIDE EDGE OF SINK); AND LOCATIONS INDICATED ON POWER
PLAN.
PROVIDE WEATHER-RESISTANT RECEPTACLES FOR RECEPTACLES INSTALLED IN DAMP OR WET
LOCATIONS.
PROVIDE HUBBELL RECEPTACLES WITH THE APPROPRIATE NEMA CONFIGURATION FOR
RECEPTACLES SHOWN ON THE ELECTRICAL PLAN.
PROVIDE 6' CORD AND PLUG FOR SPECIAL-PURPOSE RECEPTACLES IF EQUIPMENT TO BE
INSTALLED IS NOT SUPPLIED WITH A CORD AND PLUG.
PROVIDE WIRING DEVICES AS MANUFACTURED BY HUBBELL, PASS AND SEYMOUR, LEVITION,
WATT-STOPPER, LUTRON OR EQUAL.
COORDINATE MOUNTING HEIGHTS OF SWITCHES, RECEPTACLES, PHONE OUTLETS, DATA OUTLETS,
TV OUTLETS, AND LIGHT FIXTURES WITH ARCHITECTURAL DRAWINGS.
THE MOUNTING HEIGHT FOR DEVICES SHALL BE AS INDICATED BELOW, UNLESS OTHERWISE
NOTED. MOUNTING HEIGHTS ARE TO CENTER OF DEVICE, UNLESS OTHERWISE NOTED. MATCH
MOUNTING HEIGHT OF EXISTING DEVICES IF APPLICABLE.
GENERAL RECEPTACLES (RESIDENTIAL) @12" AFF
ABOVE COUNTER RECEPTACLES AND SWITCHES @ 2" ABOVE
COUNTER OR BACKSPLASH TO BOTTOM OF DEVICE
(COORDINATE WITH ARCHITECT)
GARAGE OUTLETS @ 48" AFF
TV OUTLETS (RESIDENTIAL) @ 12" AFF
DATA/PHONE OUTLETS (RESIDENTIAL) @ 12" AFF
PROVIDE "IN-USE" WEATHERPROOF COVER FOR EXTERIOR RECEPTACLES.
COMPLY WITH ADA STANDARDS FOR MOUNTING HEIGHTS AND LOCATIONS.
DEVICES IN THE SAME LOCATION AND AT THE SAME MOUNTING HEIGHT SHALL BE MOUNTED UNDER
A COMMON WALL PLATE.
DISTRIBUTION EQUIPMENT
PROVIDE DISTRIBUTION PANELS, DISCONNECTS, CONTACTORS, ETC. OF VOLTAGE, AMPERAGE,
PHASE, AND SHORT-CIRCUIT RATINGS AS INDICATED ON PLANS.
PROVIDE A LISTED BREAKER-TIE OR MULTI-POLE BREAKER FOR EACH MULTIWIRE (SHARED
NEUTRAL) BRANCH CIRCUIT.
PROVIDE DISTRIBUTION EQUIPMENT AS MANUFACTURED BY AMERICAN MIDWEST POWER,
SQUARE D, ELECTRO-MECHANICAL INDUSTRIES, CUTLER-HAMMER, SIEMENS, ERICKSON ELECTRIC,
GE OR METRON.
THE MOUNTING HEIGHT FOR DISTRIBUTION EQUIPMENT SHALL BE AS INDICATED BELOW, UNLESS
OTHERWISE NOTED.
PANELS/LOADCENTERS - 6' AFF MAX TO CENTER OF TOP HANDLE
DISCONNECT SWITCHES - 6'-6" AFF MAX TO CENTER OF HANDLE
PROVIDE A TYPED PANEL SCHEDULE WITH LOAD DESCRIPTIONS FOR PANELS AFFECTED BY THIS
PROJECT.
PROVIDE A PHENOLIC LABEL ON EACH NEW OR RENAMED PANEL INDICATING THE PANEL NAME.
LIGHTING
OWNER TO PROVIDE LUMINAIRE SPECIFICATIONS. NOTIFY ELECTRICAL ENGINEER OF ANY
DISCREPANCIES WITH THESE DRAWINGS.
MAKE CONNECTIONS TO LIGHT FIXTURES USING BUILDING WIRE WITH INSULATION SUITABLE FOR
TEMPERATURE CONDITIONS WITHIN THE LUMINAIRE.
MAINTAIN THE FIRE RATING OF THE ASSEMBLY (CEILING OR WALL) IN WHICH LIGHT FIXTURES ARE
TO BE INSTALLED. PROVIDE FIRE-RATED FIXTURES OR PROVIDE BOX AROUND FIXTURES AS
MANUFACTURED BY TENMAT, EZ BARRIER OR EQUAL.
BRANCH-CIRCUIT WIRING SCHEDULE
(UNLESS OTHERWISE NOTED)
15 A #12 AWG #12 AWG #12 AWG 1/2"
20 A #12 AWG #12 AWG #12 AWG 1/2"
25 A #10 AWG #10 AWG #10 AWG 1/2"
30 A #10 AWG #10 AWG #10 AWG 1/2"
35 A #8 AWG #8 AWG #10 AWG 3/4"
40 A #8 AWG #8 AWG #10 AWG 3/4"
45 A #6 AWG #6 AWG #10 AWG 1"
50 A #6 AWG #6 AWG #10 AWG 1"
60 A #4 AWG #4 AWG #10 AWG 1 1/4"
70 A #4 AWG #4 AWG #8 AWG 1 1/4"
80 A #3 AWG #3 AWG #8 AWG 1 1/4"
90 A #2 AWG #2 AWG #8 AWG 1 1/2"
100 A #1 AWG #1 AWG #8 AWG 1 1/2"
NOTES:
1.FOR MOTOR LOADS, USE MCA (MINIMUM CIRCUIT
AMPACITY) TO SIZE PHASE AND NEUTRAL
CONDUCTORS AND USE MOCP (MAXIMUM
OVER-CURRENT PROTECTIVE DEVICE) TO SIZE
EQUIPMENT GROUNDING CONDUCTOR.
2.INCREASE PHASE, NEUTRAL, AND EQUIPMENT
GROUNDING CONDUCTOR SIZES BY 1 STANDARD
CONDUCTOR SIZE PER EACH 75' OF CONDUCTOR
LENGTH. INCREASE CONDUIT SIZE ACCORDINGLY.
A
A PROVIDE CLEAR SPACE EQUAL TO THE WIDTH OF
EQUIPMENT OR 30", WHICHEVER IS GREATER.
B PROVIDE THE FOLLOWING CLEAR SPACE IN FRONT OF
EQUIPMENT: 3' FOR 0-150 L-G VOLTAGE AND 4' FOR 151-600
L-G VOLTAGE.
C PROVIDE CLEAR SPACE, FOR THE WIDTH OF THE
EQUIPMENT, FROM GRADE, FLOOR OR PLATFORM TO A
HEIGHT OF 6-1/2' OR THE HEIGHT OF THE EQUIPMENT,
WHICHEVER IS GREATER.
D THE SPACE EQUAL TO THE WIDTH AND DEPTH OF THE
EQUIPMENT AND EXTENDING FROM THE FLOOR TO A
HEIGHT OF 6' ABOVE THE EQUIPMENT OR TO THE
STRUCTURAL CEILING, WHICHEVER IS LOWER, SHALL BE
DEDICATED TO THE ELECTRICAL INSTALLATION - NO
PIPING, DUCTS, LEAK PROTECTION APPARATUS, OR
OTHER EQUIPMENT FOREIGN TO THE ELECTRICAL
INSTALLATION SHALL BE LOCATED IN THIS ZONE.
SUSPENDED CEILINGS WITH REMOVABLE PANELS SHALL
BE PERMITTED WITHIN THE 6' ZONE.
SPRINKLER PROTECTION SHALL BE PERMITTED FOR THE
DEDICATED SPACE WHERE THE PIPING COMPLIES WITH
THIS SECTION. A DROPPED, SUSPENDED, OR SIMILAR
CEILING THAT DOES NOT ADD STRENGTH TO THE BUILDING
STRUCTURE SHALL NOT BE CONSIDERED A STRUCTURAL
CEILING.
E THE AREA ABOVE THE DEDICATED SPACE SHALL BE
PERMITTED TO CONTAIN FOREIGN SYSTEMS, PROVIDED
PROTECTION IS INSTALLED TO AVOID DAMAGE TO THE
ELECTRICAL EQUIPMENT FROM CONDENSATION, LEAKS,
OR BREAKS IN SUCH FOREIGN SYSTEMS.
B
C
D D
E E
CLEAR SPACE/WORKING SPACE ABOUT
ELECTRICAL EQUIPMENT
THE FINAL LOCATION OF EQUIPMENT SHALL BE COORDINATED
IN THE FIELD, PRIOR TO ROUGH-IN, TO MEET APPLICABLE
LOCATION, HEIGHT AND CLEARANCE REQUIREMENTS.
THE ELECTRICAL CONTRACTOR SHALL STOP WORK
IMMEDIATELY, AND ADVISE OTHERS TO STOP WORK IF THERE
IS A CONFLICT WITH THE ELECTRICAL CLEARANCE AND WORK
SPACE REQUIREMENTS PER THE ABOVE INFORMATION AND
THE NEC.
D
FRONT VIEW
OF EQUIPMENT SIDE VIEW OF
EQUIPMENT
M
VC
S
S
M
Project Number
Date
Drawn by
Checked by
E1
REVISIONS
CLIENT:
No.Description Date
JEFF GATES
13367
10/9/13
BEK
BEK
VA
I
L
R
A
C
Q
U
E
T
C
L
U
B
BU
I
L
D
I
N
G
1
1
,
U
N
I
T
1
46
5
0
V
A
I
L
R
A
C
Q
U
E
T
C
L
U
B
D
R
I
V
E
VA
I
L
,
C
O
8
1
6
5
7
NOT ISSUED FOR CONSTRUCTION UNLESS
SIGNED THROUGH THE SEAL IN BLUE INK OR
DIGITALLY SIGNED BY BRYAN KAZIN.
LIMITED TO ELECTRICAL.
36628
10/9/13
By David Rhoades at 4:33 pm, Oct 09, 2013
B13-0451
WH
AC
GFI
+72"
AC
GFI
AC
GFI
AC
GFI
+30"
GFIL1
REF DW DISP
MW
FP
CONVERT PANEL
INTO JUNCTION BOX
AC
GFI
SS
SS
WP
GFI
UC UC
UC
L17 (UNIT 17 PANEL)
PANEL AMPERAGE 100
MAIN BREAKER MLO
PANEL VOLTAGE 240/120
BREAKER AIC RATING (MIN)10,000
DESCRIPTION BREAKER CIRCUIT
NUMBER PHASE CIRCUIT
NUMBER BREAKER DESCRIPTION
GENERAL LTG & RECEPTS 15A1P/AFC 1 A 2 20A1P/AFC WATER HEATER
GENERAL LTG & RECEPTS 15A1P/AFC 3 B 4 20A1P/AFC BATHROOM RECEPTACLE
REFRIGERATOR 20A1P 5 A 6
DISHWASHER 20A1P 7 B 8
DISPOSAL 20A1P 9 A 10
SMALL APPLIANCE 20A1P/AFC 11 B 12
SMALL APPLIANCE 20A1P/AFC 13 A 14
HOOD/MICROWAVE 20A1P 15 B 16
17 A 18
19 B 20
21 A 22
23 B 24
PANEL
L1
PANEL
L1
(3 #2 AL, 1 #6 AL G)SER OR 1 1/4"C
(100A)
UNIT 17 LOAD CALCULATION
LOAD DESCRIPTION LOAD QUANTITY TOTAL LOAD
GENERAL LIGHTING AND RECEPTACLES 3.0VA/ft^2 500ft^2 1.5kVA
SMALL APPLIANCE 1.5kVA 2 3.0kVA
DISPOSAL 0.9kVA 1 0.9kVA
DISHWASHER 1.2kVA 1 1.2kVA
RANGE (GAS RANGE)0.5kVA 1 0.5kVA
MICROWAVE 1.5kVA 1 1.5kVA
WATER HEATER/BOILER (GAS)1.0kVA 1 1.0kVA
FIRE PLACE 0.0kVA 0 0.0kVA
0.0kVA 0 0.0kVA
-0.0kVA 0 0.0kVA
TOTAL 9.6kVA
FIRST 10kVA @ 100%10.0kVA
REMAINDER @ 40%0.0kVA
-0.0kVA 0 0.0kVA
-0.0kVA 0 0.0kVA
-0.0kVA 0 0.0kVA
TOTAL LOAD 10.0kVA
TOTAL AMPERAGE @ 208V 48A
METER CENTER LOAD CALCULATION
LOAD DESCRIPTION LOAD QUANTITY TOTAL LOAD
GENERAL LIGHTING AND RECEPTACLES 3.0VA/ft^2 12000ft^2 36.0kVA
SMALL APPLIANCE 1.5kVA 48 72.0kVA
-0.0kVA 0 0.0kVA
-0.0kVA 0 0.0kVA
TOTAL 108.0kVA
1ST 3000VA @ 100%3.0kVA
3,000VA TO 120,000VA @ 35%36.8kVA
OVER 120,000VA @ 25%0.0kVA
DISPOSAL @ 75%0.9kVA 24 16.2kVA
DISHWASHER @ 75%1.2kVA 24 21.6kVA
MICROWAVE @ 75%1.5kVA 24 27.0kVA
WATER HEATER/BOILER (GAS) @ 75%1.0kVA 24 18.0kVA
HOUSE PANEL 25.0kVA
TOTAL LOAD 147.6kVA
TOTAL AMPERAGE @ 208V 410A
150kVA
9:6(&21'$5<
UTILITY CO. TRANSFORMER
FAULT CURRENT CALCULATIONS (END OF CONDUCTOR)
LOCATION DESCRIPTION STARTING ISC
MINIMUM
CONDUCTOR
LENGTH
PHASE
MULTIPLIER VOLTAGE
# OF
CONDUCTOR
SETS
C VALUE ISC END
@ METER CENTER 14,400 15 1.73 208 3 20,867 13,998
@ PANEL L17 13,998 30 1.73 208 1 3,729 7,228
800A METER CENTER
9:,1387
9:287387
CONVERT PANEL INTO
JUNCTION BOX
3 PARTIAL ONE-LINE DIAGRAM
NOT TO SCALE
NOTES:
1.EQUIPMENT, WIRING, AND DEVICES SHOWN LIGHT ARE EXISTING,
SHOWN DARK ARE NEW, AND SHOWN HATCHED ARE EXISTING TO
BE REMOVED UNLESS OTHERWISE NOTED.
2.NEW WIRING SHALL BE THHN/THWN-2 INSULATED COPPER
UNLESS OTHERWISE NOTED.
1 POWER PLAN
SCALE: 1/4" = 1'-0" (APPROX)2 LIGHTING PLAN
SCALE: 1/4" = 1'-0" (APPROX)
Project Number
Date
Drawn by
Checked by
E2
REVISIONS
CLIENT:
No.Description Date
JEFF GATES
13367
10/9/13
BEK
BEK
VA
I
L
R
A
C
Q
U
E
T
C
L
U
B
BU
I
L
D
I
N
G
1
1
,
U
N
I
T
1
46
5
0
V
A
I
L
R
A
C
Q
U
E
T
C
L
U
B
D
R
I
V
E
VA
I
L
,
C
O
8
1
6
5
7
NOT ISSUED FOR CONSTRUCTION UNLESS
SIGNED THROUGH THE SEAL IN BLUE INK OR
DIGITALLY SIGNED BY BRYAN KAZIN.
LIMITED TO ELECTRICAL.
36628
10/9/13