Loading...
HomeMy WebLinkAboutB13-0502 ComCheck approved COMcheck Software Version 3.9.1 Interior Lighting Compliance Certificate 2012 IECC Section 1: Project Information Project Type:Alteration Project Title:Quality Group TI Construction Site: OwnedAgent: Designer/Contractor: Vail,CO WMC Section 2: Interior Lighting and Power Calculation A B C D Area Category Floor Area Allowed Allowed Watts (ft2) Watts/ft2 (B x C) Common Space Types:Office—enclosed 430 1.1 473 Common Space Types:Office—open plan 215 1 215 Common Space Types:Conference/Meeting/Multipurpose 215 1.2 258 Total Allowed Watts= 946 Section 3: Interior Lighting Fixture Schedule A B C D E Fixture ID:Description/Lamp/Wattage Per Lamp/Ballast Lampsl #of Fixture (C X D) Fixture Fixtures Watt. Common Space Types:Office—enclosed(430 sq.ft.) Linear Fluorescent 1:Other/Dimming 2 8 60 480 Common Space Types:Office—open plan(215 sq.ft.) __.y: Linear Fluorescent 2:Other/Dimming 2 4 60 240 Common Space Types:Conference/Meeting/Multipurpose(215 sq.ft.) Linear Fluorescent 3:Other/Dimming 2 3 60 180 Total Proposed Watts= 900 Section 4: Requirements Checklist Lighting Wattage: � 1. Total proposed watts must be less than or equal to total allowed watts. Allowed Wattage:946 Proposed Wattage:900 Complies:YES Mandatory Requirements: � 2. Dwelling units(complete independent living facilities)within commercial buildings are not required to comply with interior lighting requirements of this code provided that>=75 percent of the permanently installed fixtures other than low voltage lighting contain only high efficacy lamps. � 3. Manual Controls:Each enclosed space has manual lighting control.Remotely located manual controls are labelled for area of service and indicate on/off status. Exception(s): � Security/emergency areas with 24-hour operation. � Stairwayslcorridors that are means of egress. � ' - � 4. Light Reduction Controls:Each space required to have a manual control also allows for reducing the connected lighting load by at least 50 percent by either controlling all luminaires,dual switching of altemate rows of luminaires,altemate luminaires,or alternate lamps, switching the middle lamp luminaires independently of other lamps,or switching each luminaire or each lamp. Project Title: Quality Group TI Report date: 11/04/13 Data filename: Untitled.cck Page 1 of 2 Exception(s): � Only one luminaire(lamp<100 W)in space. ❑ An occupant-sensing device controls the area. ❑ The area is a corridor,equipmenUstore rooms,restrooms,public lobby,elec./mech.room, or sleeping unit. ❑ Areas that use<0.6 Watts/sq.ft. ❑ Daylight spaces having automatic daylighting controls. � 5. Automatic time switching controls are installed and have an override switching device.The override switching device allows for<=2 hour operation cycle within spaces<=5000 sq.ft.,manual operation,and is readily accessible and located where the operation of the connected lights are visible or communicated to the switch. Exception(s): ❑ Sleeping units,patient care areas;and spa�es where automatic shutoff would endanger safety or security or where lighting is intended for 24hour operation. � Emergency egress lighting. ❑ Spaces where lighting is controlled with o�cupancy sensors. � Malls,arcades,auditoriums, single tenant retail spaces, industrial facilities and arenas that are<=20,000 sq.ft.are permitted exceed the 2-hour operation cycle limit when a captive key device override switch is installed. � 6. Occupant sensors are installed in the following spaces and automatically turn lighting off within 30 minutes of all occupants leaving the space:Classrooms,conferenceJmeeting/training rooms,employee lunch and break rooms,private offices,storagefjanitorial rooms, restrooms,and other spaces<=300 sq.ft.Automatic-on sensors set power on <50 percent power. Exception(s): � Full power automatio-on controls are permitted where manual-on operation would endanger the safety or security of the room or building occupants. � 7. Daylight zones have either individual lighting controls independent from that of the general area lighting that are either manual or automatic and serve zones<=2,500 sq.ft.Zones under skylights more than 15 feet from the perimeter have lighting controls separate from daylight zones adjacent to vertical fenestration. Exception(s): ❑ Contiguous daylight zones spanning no more than two orientations are allowed to be controlled by a single controlling device. ❑ Daylight spaces enclosed by walls or ceiling height partitions and containing two or fewer light fixtures are not required to have a separate switch for general area lighting. � 8. Automatic daylight zone controls are capable of reducing power to<35 percent using continuous dimming ballasts and daylight-sensing controls OR,are capable of automatic power redu�tion using step-dimming multi-level switching and daylight-sensing controls having at least two control channels per zone and at least one control step in the 50-70 percent range and another<=35 percent of design power. � 9. Medical task lighting or art/history display lighting claimed to be exempt from compliance has a control device independent of the control of the nonexempt lighting. � 10. Separate control device for display/accent lighting,case lighting,task lighting,nonvisual lighting,under-shelflcabinent lighting,lighting for sale,and demonstration lighting. � 11. Hotel/motel sleeping units and guest suites have control device(s)at the entry door that control all permanent luminaires and switched receptacles. � 12. Exit signs 5 Watts or less per sign. � 13.Tandem wired one-lamp and three-lamp ballasted luminaires(No single-lamp ballasts). Exception(s): � Electronic high-frequency ballasts. ❑ Luminaires not on same switch. ❑ Recessed luminaires 10 ft.apart or surface/pendant not continuous. � Luminaires on emergency circuits. . . Section 5: Compliance Statement Compliance Statement: The proposed lighting alteration project represented in this document is cons'tstent with the building plans, specifications and other calculations submitted with this permit application.The proposed lighting alteration project has been designed to meet the 2012 IECC,Chapter 8,requirements in COMcheck Version 3.9.1 and to comply with the mandatory requirements in the Requirements Checklist. r �i ]-��[OM - ���J� Name-Title Signature Date Project Title: Quality Group TI RepoR date: 11/04/13 Data filename: Untitled.cck Page 2 of 2