HomeMy WebLinkAboutA13-0081 Stamped approved scope of work letterAcme Alarm Company PO Box 883 Rifle, CO 81650 Phone 970-625-3398 Fax 970-625-0870 "We Set The Standards for Security!" 11/14/13 Sonnenalp North Building Vail, CO Overview: The Sonnenalp North Building 1st Floor is performing a tenant finish to provide offices for administration including reservations. There are currently heat detectors and pull stations installed in the area. Initiating devices will need to be relocated and changed to smoke detectors to provide adequate coverage for the space. Additional smoke detectors shall be added to meet code requirements. Notification circuits will be added to provide voice notification and visual notification. Documentation: See attached cut sheet for the Apollo smoke detectors and Wheelock horn strobes Scope and Sequence: • Revise spacing of the smoke detectors in the new office area. • Add eight additional smoke detectors due to new walls, offices, and hallway. • Relocate two pull stations. • Add five ceiling mount speaker strobes and one ceiling strobe to office areas and hallway. • Test new and relocated devices per NFPA 72 requirements. • Final Inspection with Vail Fire and Emergency Services. Reconstruction Phase: • All wiring shall be installed according to NEC70 and NFPA 72 standards. • Installation shall be overseen by NICET certified personnel. • Current fire control panel location shall be utilized. Timeline: • Move current devices and wire new devices 2 Days • Install new devices 1 Day • Program device labels and test devices 4 Hours • Final Test and Inspection 1 hour Clint Bartels NICET 104519 Fire Alarm Systems Level IV Acme Alarm Company Inc. 303 CR 265  Rifle, CO 81650 970.625.3398 tel 970.625.0870 fax clint@acmealarm.com