HomeMy WebLinkAboutA13-0081 Cut Sheet '�``' XP95-P
_ Gam�ll
� FIRE COI+JTROL
INSTRUMENTS
by HDne�well
Description Photoelectric Smoke Sensor
The Gamewell-FCI XP95-P analog addressable photoelec- _
tric sensor operates with the Gamewell-FCI analog addres- �-`
sable Fire Alarm Control Panels (FACPs). The � .�,�� y ,
photoelectric sensor digitally transmits its address and the - � .:' �- �-� �
chamber's analog values to the FACP for analysis. The �'
photoelectric sensor is distinguished by the clear status _�. ��� �
��
LED, which flashes red briefly when the device is polled d
and turns on continuously when the device is in alarm. � � �
�
Operation e1. �~'� Rr�� 3
The XP95-P photoelectric sensor constantly monitors its � ,�. . _ � �
sensing chamber and its internal electronics. The results • �
are then reported along with the unit's address through the XP95-P
integral communications electronics located in the sensor
head. The XP95 photoelectric sensor utilizes a patented
smoke chamber and infrared smoke sensing design. The Features
infrared emitter generates a burst of light every second, or �
in response to direct interrogation.
• Compatible with the Gamewell-FCI 600 Series analog
In clean air, the photo diode receives no light from the addressable control panels
emitter because of the arrangement of the chamber. When • Fits 4.0" (10.16 cm)or 6.0"(15.24 cm) ultra-low-profile
smoke enters the chamber, it scatters light from the emitter E-Z fit bases
onto the photo diode receptor in proportion to smoke char- • Audible alarm sounder base
acteristics and density. As the smoke content in the cham- • Four-wire relay base
ber increases, the signal from the photo diode receptor • Address is stored in the sensor base
increases. This information is processed and conditioned • Address is set by XPert addressing card
by an on-board, advanced-technology ASIC and digitally • Two-color status LED
transmitted to the FACP. • Infrared smoke sensing design
• Continuous communications
Trouble and Alarm conditions of the XP95 sensors are . Optional remote LED
actually determined at the control panel. The status infor-
mation of each sensor is analyzed for off-normal conditions
by the FACP. If the sensor reports a condition that matches
its programmed trouble signature,the FACP will detect that
the sensor is in trouble and will follow its programmed I
response sequence. If the status reported matches the
alarm signature, the FACP will follow the programmed An ISO 9000-2000 Company
alarm response for the specific device in alarm. When a SIGNALING
sensor is in alarm,the integral LED in the sensor's housing �
will light continuously. � FM MEA
LISTED Approved
� 51795 APPROVED 149-99-E
GAMEWELL-FCI
12 Clintonville Road, Northford,CT 06472-1610 USA•Tel:(203)484-7161 •Fax:(203)484-7118
Specifications are for information only,are not intended for installation purposes,and are subject to change without notice.No responsibility is assumed by Gamewell-FCI for their use.
02007 by Honeywell International Inc. All rights reserved. WWW.g8Y1'IeW@II-fCI.COPTI CS-2054 Rev.a1 page 1 of 2
Operation (Continued) Ordering Information
The XP95-P photoelectric device is connected to a two- Model DesCription
wire SLC carrying both data and a 17 to 28 VDC supply XP95-P Photoelectric sensor, analog
voltage, and is insensitive to loop connection polarity. A addressable (55000-650)
remote LED indicator may be connected. The device is XP95-B4 4.0"(10.16 cm)mounting base with
compatible with point-or group-addressable relay and XPert addressing card (45681-2101)
sounder bases. XP95-B6R4 6.0"(15.24 cm)relay base
(four-wire)with XPert addressing card
Engineer's Specifications XP95-B6SNDR 6.0"(15.24 cm)mounting base with XPert
addressing card and audible alarm
The contractor shall furnish and install, where indicated on sounder in the base
the plans, photoelectric smoke sensors with one of the 71112 Additional blank XPert addressing cards
several addressable mounting base options available. The 30203 Remote LED (24 V)on single gang
combination sensor head and twist-lock mounting base plate
shall be UL Listed and UL Listed as compatible with the
Gamewell-FCI 600 Series analog addressable fire alarm
control panels. The base shall permit free interchange of
sensor heads without requiring any additional wiring or
additional programming of the head or base. The smoke
sensor shall contain an integral LED that shall latch in
when the unit goes into alarm. RF suppression techniques
shall be employed to minimize false alarms. The photo-
electric smoke sensor shall be the Gamewell-FCI model
XP95-P.
Specifications
Standby Current: 340 �aA
Alarm LED Current: 0.00434 A
Remote Alarm
Output: 0.004 A@ 5 VDC
Temperature Range: 32°F to 140°F (0° C to 60° C)
Relative Humidity: (non-condensing)0%to 95%
Recommended
Spacing: Meets the 30 ft. (9.1 m)spacing
guidelines in NFPA 72 Chapter 2.
However,this spacing is based on
ideal conditions and is to be used
as a layout guide only.Appropriate
installation-specific engineering is
required.
GAMEWELL-FCI
12 Clintonville Road, Northford,CT 06472-1610 USA•Tel:(203)484-7161 •Fax:(203)484-7118
CS-2054 Rev.a1 page 2 of 2 www.gamewell-fci.com