HomeMy WebLinkAboutB13-0488 CR1 BEAUDIN GANZE LETTER.pdf "DEALIDIN
r/)
October 18,2010 D [E C '-�' a r AN
eonsultiing engineers. me
SEP
Mr.Bob Lazier
Tivoli Lodge TOWN OF VAIL
386 Hanson Ranch Road
Vail,CO 81657
RE: Tivoli Lodge 5th Floor Guest Room Addition
Project#8961.00
Dear Bob-
As requested, BGCE has reviewed the existing plumbing and power infrastructure at the Tivoli Lodge
with regard to supporting the proposed build-out of an 870 square foot hotel guest room. We understand
this is a rentable guest room and is not considered a dwelling unit as defined by Town of Vail adopted
building codes. Our review indicates the existing building infrastructure should be capable of supporting
the proposed guest room. Specific systems findings and recommendations follow.
PLUMBING SYSTEMS
Assuming original plumbing riser construction was completed similar to the design intent
(majority of the riser components are concealed behind existing finishes),the plumbing risers in
the immediate vicinity of the proposed guestroom should support the waste,vent,hot water, and
cold water needs. No natural gas load in this guestroom is anticipated
We recommend extending a 4"waste line to either of the adjacent ri�er� labeled "8" and 15"can
the 2007 BGCE design drawings. Horizontal piping should slope, at minimum. 1/8"per foot
slope to the new bathroom fixture group and coffee/bar sink.
We recommend extending a 3/4"hot water and 3/4"cold water piping from the riser labeled"15"
pm the 2007 BGCE design drawings. Piping should be insulated in accordance with the 2009
IECC. Also, we recommend accessible isolation valves be provided within this new guest room
to isolate all new cold/hot water fixtures from a single location.
We recommend extending a 2-1/2"vent pipe from either of the adjacent risers labeled"8"and
"15"to serve the new fixture group.
Please see the attached plan sketch from the original construction documents indicating the
approximate locations of these risers. Note, at the time of this review. risers which would be
located in the middle of the living space have been relocated to be accommodated within adjacent I If
walls.
A:N
MECHANICAL SYSTEMS F
It is our understanding a heating only system consisting of electric baseboard is desired. The AV
calculated heat loss for the guest hotel room is approximately 9,900btu/h. This calculated heat `T
loss does not factor in any heat transfer from the adjacent portions of the building which we I k
understand are often sufficient to keep the existing guest room space at a reasonable temperature. 1
Since this passive heat gain is not reliably predictable and is not controllable by the guest room
occupants. To offset this calculated heat loss we recommend an electric resistance baseboard
with a total heat output of 2.900 watts be provided within the guest room. To maximize occupant
79(:hahC l 111'IM AC:'01 P O Pox$i;iw avne7 CO 816 20.p A/0 949 6108 'HAIL
ALBUQUERQUE DENVER FORT COLLINS LAKE TAHOE SACRAMENTO VAIL
WWW bece com
Mr. Bob Lazier
Tivoli Lodge
Tivoli Lodge 5`i'Floor Guest Room Addition
October 18.2010
Page 2
space comfort we recommend a majority of this baseboard heat be distributed adjacent to the
window wall as allowable by the architecture and interior furnishings systems. We also suggest a
small length of baseboard be provided in the bathroom and be equipped with its own thermostat
control.
We understand code ventilation for the main volume of the guest room will be provided via
operable windows.
For bathroom ventilation,we recommend providing a cabinet exhaust fan capable of achieving a
minimum of 50 cfm at the developed static pressure(dependent on duct sizing and routing).
Note,this bath ventilation system should be installed to minimize or eliminate need to penetrate
any fire rated construction assemblies. In the event ventilation systems do penetrate fire
assemblies, proper opening protection must be provided.
ELECTRICAL
The overall building electrical service has sufficient capacity to accommodate the proposed guest
room. Furthermore,there is sufficient capacity and spare circuits in Panel"5A" located adjacent
to the proposed guest room. The anticipated guest room loads and general device layout are
indicated on the attached sketch and the attached anticipated panel schedule.A master switch
located at the room entry to control lighting and switched receptacles will be required per 2009
IECC as adopted by Town of Vail. Lighting fixtures will be specified by the Owner.
SMOKE DETECTION/FIRE ALARM SYSTEM/FIRE SUPPRESSION
Smoke Detection/Fire Alarm and fire suppression are by others and are not within this scope of
work.
The above information is intended to respond to the building departments request for systems
infrastructure capacity verification. The actual design of these new systems is the responsibility of the
design/build contractor. It is also a design/build contractor's responsibility to inform BGCC if the
recommendations included in thi 1 er are not achievable. If you have any questions or comments
please call.
.r,91;i�1ii9fpn
Sincerely, '
C.
Dan Koelliker,PE 6
Vice President
DJK:jrb
111...
4 r
S\BGProleats•.8961 00 Tivoli Lodge 5th Floor Guest Room Addiuon,Correspondence\BGCE\896I OOGLOIDK docx �
///J www bece com