HomeMy WebLinkAboutAtrium A 92B Exhaust EXHAUST METHOD (Per IBC Section 909.8) AXISYMMETRIC PLUMES (Equations based on NFPA 92B -2005 Edition) NFPA 92B - Eq. 6.2.1.1c: - Z <_ ZL The Calculations are based upon the following: Q = 5000.00 BTU/Sec Q�= 3500.00 BTU/Sec Z = 6.00 Feet Z� = 13.94 Feet (0.533 Q�2�5 - Limiting Flame Height- NFPA 92B Eq. 6.2.1.1a) Elevation = 8150.00 Feet Smoke Temp = 250.00 °F Since Z <_Z�, The following formula from NFPA 92B Section 6.2.1 will be used. Therefore: Mp= �.�ZO8Q�3/5 Z Mp= 0.0208 ( 3500.00 )3�5* ( 6.00 ) Mp= 16.70 Ibs/sec From NFPA 92B Eq. 6.4: V = 60 Mp/p p = Density of air. The density used in these calculations has been adjusted to the project's elevation and smoke layer temperature of: 8150 feet above sea level and corrected for a smoke layer temperature of: 250 ° F 0.043 adjusted density (Ibs/ft3) V = 60 ( 16.70 ) / ( 0.043 ) V = 23,190 cfm (Required smoke control exhaust rate)