EQUIPMENT SUBMITTAL
CO Worldwide www,tyco-fire.com
Contacts
RAP/D RESPONSE Series LFII Residential Sprinklers
4.9 K-factor Flat-Plate Concealed Pendent
Wet Pipe and Dry Pipe Systems
General tial fires and to improve the chance for
occupants to escape or be evacuated.
Description The Series LFII Residential Flat-Plate _�
The TYCO RAPID RESPONSE Series Concealed Pendent Sprinklers are �
LFII Residential Flat-Plate Concealed shipped with a Disposable Protective l �
Cap.The Protective Cap protects the r �-��_
Pendent Sprinklers(TY2524)are decora- sprinkler during ceiling installation or ,� �� `?
tive,fast response,fusible solder sprin- finish.After ceiling installation is com- L ��-- �
klers designed for use in residential oc- plete, the Protective Cap is removed ! - ��- .�
cupancies such as homes,apartments, and the Cover Plate/Retainer Assem-
dormitories,and hotels. bly is installed. Removing the Protec-
The Cover Plate/Retainer Assembly con- tive Cap is required for proper sprinkler
ceals the sprinkler operating compo- performance.
nents above the ceiling.The flat profile Dry Pipe System Application
of the Cover Plate provides the optimum The Series LFII Residential Flat-Plate The owner is res onsible for maintain-
aesthetically appealing sprinkler design. Concealed Pendent Sprinkler offers a ing their fire protection system and de-
Additionally,the concealed design of the laboratory approved option for design- vices in proper operating condition. The
Series LFII Residential Flat-Plate Con- ing dry pipe residential sprinkler sys- installing contractor or sprinkler manu-
cealed Pendent Sprinklers provides 1/2 tems, whereas, most residential sprin- facturer should be contacted with any
inch(12,7 mm)vertical adjustment.This
adjustment provides a measure of flex- klers are laboratory approved for wet questions.
ibility when cutting fixed sprinkler drops. systems only.
The Series LFII Residential Flat-Plate Through extensive testing, it has been Sprinkler
Concealed Pendent Sprinklers are in- determined that the number of design
tended for use in the following systems: sprinklers(hydraulic design area)for the /dentification
Series LFII Residential Flat-Plate Con-
• wet and dry pipe residential sprin- cealed Sprinklers(TY2524)need not be Number (SIN)
kler systems for one- and two-fam- increased over the number of design
ily dwellings and mobile homes per sprinklers(hydraulic design area)speci- TY2524
NFPA 13D fied for wet pipe sprinkler systems, as
• wet and dry pipe residential sprin- is customary for density/area sprinkler
kler systems for residential occu- systems designed per NFPA 13, 13D,
pancies up to and including four sto- or 13R.
ries in height per NFPA 13R Consequently,the Series LFII Residen-
• wet and dry pipe sprinkler systems tial Flat-Plate Concealed Sprinklers
for the residential portions of any (TY2524)offer the features of non-wa-
occupancy per NFPA 13 ter filled pipe in addition to not having to
increase the number of design sprinklers
The Series LFII Residential Sprinklers (hydraulic design area)for systems de-
have been designed with heat sensitiv- signed to NFPA 13, 13D, or 13R. Non-
ity and water distribution characteristics water filled pipe will permit options for
proven to help in the control of residen- areas sensitive to freezing.
IMPORTANT �
Always refer to Technical Data The Series LFII Residential Flat-Plate
Sheet TFP700 for the "INSTALLER Concealed Pendent Sprinklers(TY2524)
WARNING" that provides cautions described herein must be installed and
with respect to handling and instal- maintained in compliance with this doc-
lation of sprinkler systems and com- ument and the applicable standards of
ponents. Improper handling and in- the National Fire Protection Association,
stallation can permanently damage in addition to the standards of any au-
a sprinkler system or its components thorities having jurisdiction. Failure to
and cause the sprinkler to fail to do so may impair the performance of
operate in a fire situation or cause it these devices.
to operate prematurely.
Page 1 of 6 APRIL 2013 TFP443
TFP443
Page 2 of 6
BODY SEALING WRENCH
(1/2" NP� ASSEMBLY RECESS
/
CAP � SPRINKLER
WRENCHING
AREA
SADDLE
�y PUSH WRENCH
SUPPORT �`� COMPRESSION IN TO ENSURE
CUP WITH �7 � SCREW ENGAGEMENT
ROLL FORMED WITH SPRINKLER
THREADS WRENCHING AREA
LEVER FIGURE 2
� W-TYPE 18
GUIDE I I SPRINKLER WRENCH
PIN
I �i �i �i �i I SOLDER LINK
i i ELEMENT
GUIDE PW I I I I i I
HOUSING � � � �
ii ii
i � __ � � DEFLECTOR
� � �-J� ` _ � � � i (OPERATED
DEFLECTOR I� - �--- - POSITION)
I SPRWKLER/SUPPORT CUP I
�
ASSEMBLY
THREAD INTO I I RETAINER
SUPPORT WITH THREAD
CUP UNTIL DIMPLES
MOUNTING O 0
SURFACE IS
FLUSH WITH
CEILING EJECTION
SPRING
�
SOLDER J COVER PLATE/RETAINER COVER
TAB ASSEMBLY PLATE
FIGURE 1
RAPID RESPONSE SERIES LFII RESIDENTIAL
FLAT-PLATE CONCEALED PENDENT SPRINKLER(TY2524)
2-1/2" DIA. SPRINKLER-
(63,5 mm) 1/2" (12,7 mm) FACE OF SUPPORT CUP
1/2��
THREADED SPRINKLER ASSEMBLY
NPT ADJUSTMENT FITTING
\ ' OPERATED
SPRINKLER
\
1-7/8"±1/4" - COVER JJ
(47,6 mm PLATE SS
RETAINER
I 1/8"GAP ±6,4 mm)
(3,2 mm)
J 1 � � 1
COVER- SPRINKLER- � 7/8"(22,2 mm)
RETAINER SUPPORT CUP 3�1� SOURFACE 1-1/8" (28,6 mm)
ASSEMBLY ASSEMBLY �4$mm� \ t
3-3/16" DIA. DISPOSABLE DEFLECTOR IN
(81,0 mm) TIP PROTECTIVE CAP OPERATED POSITION
FIGURE 3
RAPID RESPONSE SERIES LFII RESIDENTIAL FLAT-PLATE(TY2524)
INSTALLATION DIMENSIONS/PROTECTIVE CAP/ACTIVATED DEFLECTOR
TFP443
Page3of6
Technical Design The number of "design sprinklers"
specified in NFPA 13 for wet pipe sys-
Data Criteria tems is to be applied when designing
dry pipe systems.
Approvals The TYCO RAPID RESPONSE Series Dry Pipe System Water Delivery
UL and C-UL Listed LFII Residential Flat-Plate Concealed When using the Series LFII Residential
The TYCO RAPID RESPONSE Series Pendent Sprinklers (TY2524) are UL Flat-Plate Concealed Pendent Sprinklers
and C-UL Listed for installation in ac- TY2524 in dr i e s rinkler s stems,
LFII Residential Flat-Plate Concealed cordance with this section: � � y p p p y
Pendent Sprinklers are only listed with the time for water delivery must not ex-
the Series LFII Concealed Cover Plates Residential Sprinkler Design Guide ceed 15 seconds for the most remote
having a factory-applied finish. When conditions exist that are outside operating sprinkler.
For details on approvals,refer to the De- the scope of the provided criteria, re- Obstruction to Water Distribution.
sign Criteria section. fer to the Residential Sprinkler Design Sprinklers are to be located in accor-
Guide TFP490 for the manufacturer's dance with the obstruction rules of
Maximum Working Pressure recommendations that may be accept- NFPA 13D, 13R, and 13 as applicable
175 psi (12,1 bar) able to the authority having jurisdiction. for residential sprinklers as well as with
Discharge Coefficient System Type the obstruction criteria described within
K=4.9 GPM/psi'�z(70,6 LPM/bar1z) Per the UL Listing,wet pipe and dry pipe the Technical Data Sheet TFP490.
systems may be utilized. Per the C-UL Operational Sensitivity
Temperature Rating Listing, only wet pipe systems may be
Sprinkler: 160°F(71°C) utilized. Install sprinklers relative to the ceiling
Cover Plate: 139°F(59°C) mounting surface as shown in Figure 3.
Refer to Technical Data Sheet TFP485
Vertical Adjustment about the use of Residential Sprinklers The Series LFII Residential Flat-Plate
1/2 inch (12,7 mm) in residential dry pipe systems. Concealed Pendent Sprinklers must
not be used in applications where the
Finishes Ceiling Types air pressure above the ceiling is greater
Refer to the Ordering Procedure section. Smooth flat horizontal, or beamed, or than that below. Down drafts through
sloped, in accordance with the 2013 the Support Cup can delay sprinkler op-
Physical Characteristics Edition of NFPA 13D, 13R or 13 as eration in a fire situation.
Cover Plate/Retainer Assembly: applicable.
Cover Plate . . . . . . . . . . . . . Copper Sprinkler Spacing
Ejection Spring . . . . Stainless Steel Hydraulic Design The minimum spacing between sprin-
Retainer . . . . . . . . . . . . . . . . Brass (NFPA 13D and 13R) klers is 8 feet (2,4 m). The maximum
For systems designed to NFPA 13D or spacing between sprinklers cannot ex-
Sprinkler/Support Cup Assembly: NFPA 13R,the minimum required sprin- ceed the length of the coverage area
Body . . . . . . . . . . . . . . . . . . . Brass kler flow rate are given in Tables A and (Table A)being hydraulically calculated
Cap . . . . . . . . . . . . . . . . . . . Bronze g as a function of temperature rating (e.g.,a maximum of 12 feet for a 12 ft.x
Saddle. . . . . . . . . . . . . . . . . . Brass and the maximum allowable coverage 12 ft. coverage area or 20 feet for a 20
Sealing Assembly . . . . . . .Beryllium areas.The sprinkler flow rate is the mini- ft.x 20 ft. coverage area.)
Nickel w/TEFLON mum required discharge from each of
Soldered Link Halves . . . . . . Nickel the total number of"design sprinklers"
Lever . . . . . . . . . . . . . . . . . . Bronze as specified in NFPA 13D or NFPA 13R.
Compression Screw . . . . . . . Brass The number of"design sprinklers"spec-
Deflector . . . . . . . . . . . . . . . Bronze ified in NFPA 13D and 13R for wet pipe
Guide Pin Housing. . . . . . . . Bronze systems is to be applied when designing
Guide Pins . . . . . . . . . . . . . Bronze dry pipe systems.
Support Cup . . . . . . . . . . . . . . Steel
Hydraulic Design
Operation (NFPA 13)
For systems designed to NFPA 13,the
When exposed to heat from a fire,the number of design sprinklers is to be
Cover Plate,which is normally soldered the four most hydraulically demanding
to the Retainer at three points,falls away sprinklers.The minimum required dis-
to expose the Sprinkler/Support Cup As- charge from each of the four sprinklers
sembly.At this point,the Deflector,sup- is to be the greater of the following:
ported by the Guide Pins, drops down
to its operated position. •The flow rates given in Tables A and
B as a function of temperature rating
The Solder Link Element of the Sprinkler/ and the maximum allowable cover-
Support Cup Assembly is comprised of age area
two link halves that are soldered togeth- .A minimum discharge of 0.1 gpm/ft2.
er with a thin layer of solder. When the over the "design area" comprised of
rated temperature is reached,the sol- the four most hydraulically demand-
der melts and the two link halves sepa- ing sprinklers for the actual coverage
rate, allowing the sprinkler to activate areas being protected by the four
and flow water. sprinklers
TFP443
Page 4 of 6
WET PIPE SYSTEM
Minimum Flow and Residual Pressure�b,°�
Maximum Maximum
Coverage Spacing Ordinary Temp Rating
Area 160°F(71°C)
Ft.x Ft. Ft' Deflector to Installation Minimum
(m x m) (m) Flow Pressure Ceiling Type Spacing
GPM PSI Ft.
(L/min) (bar) (m�
12 x 12 12 13 7.0 Smooth
(3,7 x 3,7) (3,7) (49,2) (0,48) Ceilings 7/8 to
14 x 14 14 13 �� 1-1/8 inches.
(4,3 x 4,3) (4,3) 49,2) (0,48) Beamed
Ceilings per
16 x 16 16 13 �•� NFPA 13D Concealed $
(4,9 x 4,9) (4,9) (49,2) (0,48) 13R,or 13 �2'4�
18 x 18 18 17 �2,0 Installed in
(5,5 x 5,5) (5,5) (64,3) (0,83) beam 7/8 to
1-1/8 inches
20 x 20 20 20 16.7 below bottom
(6,1 x 6,1) (6,1) (75,7) (1,15) of beam
(a) For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest
coverage area for which Hydraulic Design section under the Design Criteria are stated.
(b) The Minimum Flow requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pres-
sures are calculated using the nominal K-factor.Refer to"Hydraulic Design"in the Design Criteria section for details.
(c) For NFPA 13 residential applications,the greater of 0.1 gpm/ft.2 over the design area or the flow in accordance with the
criteria in this table must be used.
TABLE A
WET PIPE SYSTEM
SERIES LFII RESIDENTIAL FLAT-PLATE CONCEALED PENDENT SPRINKLER(TY2524)
NFPA 13D, 13R,AND 13 HYDRAULIC DESIGN CRITERIA
DRY PIPE SYSTEM
Maximum Minimum Flowand Residual Pressure�b>
Coverage Maximum
Area�a> Spacing Ordinary Temp Rating
Ft.x Ft.
Ft. 160°F(71°C) Deflectorto Installation Minimum
(m x m) �m) Flow Pressure Ceiling Type Spacing
GPM PSI Ft.
(L/min) (bar) (m)
12 x 12 12 15 9.4 Smooth
(3,7 x 3,7) (3,7) (56,8) (0,65) Ceilings 7/8 to
14 x 14 14 15 9 4 1-1/8 inches.
(4,3 x 4,3) (4,3) (56,8) (0,65) Beamed
Ceilings per
16 x 16 16 16 10,7 NFPA 13D Concealed $
(4,9 x 4,9) (4,9) (60,6) (0,74) 13R,or 13 �2'4�
18 x 18 18 17 12.0 Installed in
(5,5 x 5,5) (5,5) (64,3) (0,83) beam 7/8 to
1-1/8 inches
20 x 20 20 21 18,4 below bottom
(6,1 x 6,1) (6,1) (79,5) (1,27) of beam
(a) For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest
coverage area for which Hydraulic Design section under the Design Criteria are stated.
(b) The Minimum Flow requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual
pressures are calculated using the nominal K-factor.Refer to"Hydraulic Design"in the Design Criteria section for details.
(c) For NFPA 13 residential applications,the greater of 0.1 gpm/ft.z over the design area or the flow in accordance with the
criteria in this table must be used.
TABLE B
DRY PIPE SYSTEM
SERIES LFII RESIDENTIAL FLAT-PLATE CONCEALED PENDENT SPRINKLER(TY2524)
NFPA 13D, 13R,AND 13 HYDRAULIC DESIGN CRITERIA
CO Worldwide www,tyco-fire.com
Contacts
RAP►D RESPONSE Series LFII Residential Sprinklers
4.9 K-factor Pendent
Wet Pipe and Dry Pipe Systems
General Escutcheon reduces the accuracy to
which the pipe drops to the sprinklers
Description must be cut. ___
The TYCO RAPID RESPONSE Series The Series LFII Residential Sprinklers � �
have been designed with heat sensi-
LFII Residential Pendent and Recessed tivity and water distribution charac- +�
Pendent Sprinklers(TY2234)are deco- teristics proven to help in the control `� ��' �
rative, fast response, frangible bulb of residential fires and to improve the �
sprinklers designed for use in residen- chance for occupants to escape or be
tial occupancies such as homes, apart- evacuated.
ments, dormitories, and hotels. When "
aesthetics and optimized flow charac- Dry Pipe System Application '
teristics are the major consideration, The Series LFII Residential Pendent '
the Series LFII Residential Sprinklers and Recessed Pendent Sprinklers
(TY2234)should be the first choice. offers a laboratory approved option for
The Series LFII Residential Sprinklers designing dry pipe residential sprinkler
are intended for use in the following systems, whereas, most residential The owner is responsible for main-
scenarios: sprinklers are laboratory approved for taining their fire protection system and
wet systems only. devices in proper operating condition.
• wet and dry pipe residential sprin- Through extensive testing, it has been The installing contractor or sprinkler
kler systems for one-and two-family determined that the number of design manufacturer should be contacted with
dwellings and mobile homes per sprinklers (hydraulic design area) for any questions.
NFPA 13D the Series LFII Residential Pendent and
• wet and dry pipe residential sprinkler Recessed Pendent Sprinklers(TY2234) Sprinkler
systems for residential occupancies need not be increased over the number
p g 9 P � Y J /dentification
u to and includin four stories in of desi n s rinklers h draulic desi n
height per NFPA 13R area)as specified for wet pipe sprinkler Number (SIN)
systems, as is accustomed for density/
• wet and dry pipe sprinkler systems area sprinkler systems designed per
for the residential portions of any NFPA 13. TY2234
occupancy per NFPA 13
Consequently, the Series LFII
The recessed version of the Series Residential Sprinklers offer the features
LFII Residential Sprinklers is intended of non-water filled pipe in addition to
for use in areas with finished ceilings. not having to increase the number of
It employs a two-piece Style 20 design sprinklers (hydraulic design
Recessed Escutcheon.The Recessed area) for systems designed to NFPA
Escutcheon provides 1/4 inch (6,4 13, 13D, or 13R. Non-water filled pipe
mm) of recessed adjustment or up to �nrill permit options for areas sensitive
1/2 inch (12,7 mm) of total adjustment to freezing.
from the flush ceiling position. The
adjustment provided by the Recessed �
•
The Series LFII Residential Pendent and
Recessed Pendent Sprinklers(TY2234)
IMPORTANT described herein must be installed and
Always refer to Technical Data maintained in compliance with this
Sheet TFP700 for the "INSTALLER document and the applicable stan-
WARNING" that provides cautions dards of the National Fire Protection
with respect to handling and instal- Association, in addition to the standards
lation of sprinkler systems and of any authorities having jurisdiction.
components. Improper handling and Failure to do so may impair the perfor-
installation can permanently damage mance of these devices.
a sprinkler system or its compo-
nents and cause the sprinkler to fail to
operate in a fire situation or cause it
to operate prematurely.
Page 1 of 6 APRIL 2013 TFP400
TFP400
Page2of6
7/16"(11,1 mm) ESCUTCHEON
1/2"
Components: NOMINAL NPT PLATE SEATING 2-7/8" DIA. _
1 - Frame MAKE-IN SURFACE (73,0 mm)
2 - Button �
3 - Sealing Assembly 1 �
4 - Bulb
5 - Compression 2 �
Screw 2-1�4��
6 - Deflector* 3 p A (57,2 mm)
4 1-5/8"
(41,3 mm) WRENCH STYLE 20
RECESSED
*Temperature 5 � F�ATS ESCUTCHEON
rating is *
indicated on 6
Deflector.
CROSS SECTION PENDENT RECESSED PENDENT
FIGURE 1
RAPID RESPONSE SERIES LFII RESIDENTIAL
PENDENT AND RECESSED PENDENT SPRINKLERS(TY2234J
2-7/8" DIA.
(73,0 mm)
7/16±1/8" 1/2"(12,7 mm)
(11,1±3,2 mm) 2_��4" DIA. 1/4" (6,4 mm) / WRENCH RECESS
FACE OF ~ �57,2 mm) ~ � (END "A" USED
SPRINKLER MOUNTING FOR TY2234)
FITTING PLATE
FIGURE 3
� W-TYPE 6
SPRINKLER WRENCH
� p I
MOUNTING WRENCH
SURFACE 1�$" RECESS
(3,2 mm)
1-3/8" (34,9 mm) �
CLOSURE TY2234
1-1/8" (28,6 mm)
FIGURE 2
STYLE 20 RECESSED ESCUTCHEON FOR USE WITH THE
RAPID RESPONSE SERIES LFII RESIDENTIAL PENDENT SPRINKLER
(TY2234) PUSH WRENCH
IN TO ENSURE
Technical Temperature Rating ENGAGEMENT
155°F(68°C)or 175°F(79°C) WITH SPRINKLER
Data Finishes WRENCHING AREA
Natural Brass FIGURE 4
Approvals Pure or Signal White W-TYPE 7 RECESSED
UL Listed for use with wet pipe and Chrome Plated SPRINKLER WRENCH
dry pipe systems Physical Characteristics
C-UL Listed for use only with wet pipe Frame . . . . . . . . . . . . . . . . . . . . Brass
systems Button . . . . . . . . . . . . . . . . . . .Copper
NSF Certified to NSF/ANSI 61 Sealing Assembly . . . . . . . . Beryllium
Nickel w/TEFLON
For details on these approvals, refer Bulb(3 mm). . . . . . . . . . . . . . . . Glass
to the Design Criteria section. Compression Screw . . . . . . . . Bronze
Maximum Working Pressure Deflector . . . . . . . . . . . . . . . . . Bronze
175 psi (12,1 bar) Ejection Spring . . . . . .Stainless Steel
Discharge Coefficient
K=4.9 GPM/psi1i2(70,6 LPM/bar1i2)
TFP400
Page3of6
Operation Hydraulic Design /nstallation
(NFPA 13)
The glass bulb contains a fluid that For systems designed to NFPA 13, The TYCO RAPID RESPONSE
expands when exposed to heat.When the number of design sprinklers is Series LFII Residential Pendent
the rated temperature is reached, the to be the four most hydraulically and Recessed Pendent Sprinklers
fluid expands sufficiently to shatter the demanding sprinklers. The minimum (TY2234) must be installed in accor-
glass bulb, allowing the sprinkler to required discharge from each of the dance with this section:
activate and flow water. four sprinklers is to be the greater of
the following: General Instructions
Design • The flow rates given in Tables A Do not install any bulb type sprin-
or B as a function of temperature kler if the bulb is cracked or there is a
Criteria rating and the maximum allowable loss of liquid from the bulb. With the
coverage area. sprinkler held horizontally, a small air
The TYCO RAPID RESPONSE bubble should be present. The diam-
Series LFII Residential Pendent ' A minimum discharge of 0.1 gpm/ft2 eter of the air bubble is approximately
and Recessed Pendent Sprinklers over the "design area" comprised 1/16 inch (1,6 mm).
(TY2234) are UL and C-UL Listed for of the four most hydraulically
installation in accordance with this demanding sprinklers for actual A leak-tight 1/2 inch NPT sprinkler
section. coverage areas protected by the joint should be obtained by applying
four sprinklers. a minimum-to-maximum torque of 7
Residential Sprinkler Design Guide The number of "design sprinklers" to 14 ft.-Ibs. (9,5 to 19,0 Nm). Higher
When conditions exist that are specified in NFPA 13 for wet pipe levels of torque can distort the sprin-
outside the scope of the provided systems is to be applied when kler Inlet with consequent leakage or
criteria, refer to the Residential designing dry pipe systems. impairment of the sprinkler.
Sprinkler Design Guide TFP490 for po not attempt to compensate
the manufacturer's recommendations Dry Pipe System Water Delivery for insufficient adjustment in an
that may be acceptable to the local When using the Series LFII Residential Escutcheon Plate by under- or over-
authority having jurisdiction. Sprinklers(TY2234) in dry pipe sprin- tightening the sprinkler. Re-adjust the
kler systems, the time for water position of the sprinkler fitting to suit.
System Types delivery must not exceed 15 seconds
Per the UL Listing, wet pipe and dry for the most remote operating Series LFII Residential Pendent
pipe systems may be utilized. Per the sprinkler. Sprinklers
C-UL Listing, only wet pipe systems The Series LFII Residential Pendent
may be utilized. Obstruction to Water Distribution Sprinklers must be installed in accor-
Refer to Technical Data Sheet TFP485 Sprinklers are to be located in accor- dance with the following instructions.
for the use of residential sprinklers in dance with the obstruction rules Step 1. Install pendent sprinklers in
residential dry pipe systems. of NFPA 13D, 13R, and 13 as appli- the pendent position with the deflector
cable for residential sprinklers as parallel to the ceiling.
Ceiling Types well as with the obstruction criteria
Smooth flat horizontal, or beamed, or described within the Technical Data Step 2. With pipe thread sealant
sloped, in accordance with the 2013 Sheet TFP490. applied to the pipe threads, hand-
Edition of NFPA 13D, 13R, or 13 as tighten the sprinkler into the sprinkler
applicable. Operational Sensitivity fitting.
Sprinklers are to be installed with a Step 3. Tighten the sprinkler into
Hydraulic Design deflector-to-ceiling distance of 1-1/4 to the sprinkler fitting using only the
(NFPA 13D and 13R) 4 inches. W-Type 6 Sprinkler Wrench (Figure
For systems designed to NFPA 3). With reference to Figure 1, apply
13D or NFPA 13R, the minimum Sprinkler Spacing the W-Type 6 Sprinkler Wrench to the
required sprinkler flow rates are The minimum spacing between sprin- wrench flats.
given in Tables A and B as a func- klers is 8 feet (2,4 m). The maximum
tion of temperature rating and the spacing between sprinklers cannot Series LFII Residential Recessed
maximum allowable coverage areas. exceed the length of the coverage Pendent Sprinklers
The sprinkler flow rate is the minimum area(Table A or B) being hydraulically The Series LFII Residential Recessed
required discharge from each of the calculated(e.g., maximum 12 feet for a Pendent Sprinklers must be installed
total number of"design sprinklers"as 12 ft. x 12 ft. coverage area, or 20 feet in accordance with the following
specified in NFPA 13D or NFPA 13R. for a 20 ft. x 20 ft. coverage area). instructions.
The number of "design sprinklers"
specified in NFPA 13D and 13R for wet Step A. Install recessed pendent
pipe systems is to be applied when sprinklers in the pendent position with
designing dry pipe systems. the deflector parallel to the ceiling.
Step B. After installing the Style 20
Mounting Plate over the sprinkler
threads and with pipe thread sealant
applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
fitting.
(Continued on Page 5)
TFP400
Page4of6
WET PIPE SYSTEM
Minimum Flow and Residual Pressure�b,°)
Cove a e ordinary Temp.Ratiny Intermediate Temp.Rating
Area�9 155°F(68°C) 175°F(79°C) Minimum
Deflector to Installation Spacing
Ft.x Ft. Flow Pressure Flow Pressure Ceiling Type Ft.
(m x m) GPM PSI GPM PSI (rn)
(L/min) (bar) (L/min) (bar)
12 x 12 13 7.0 13 7.0 Smooth
(3,7 x 3,7) (49,2) (0,48) (49,2) (0,48) Ceilings
14x14 13 7.0 13 �p 1-1/4to
(4,3 x 4,3) (49,2) (0,48) (49,2) (0,48) 4 inches Recessed
Beamed using Style 20
16 x 16 13 7.0 13 7•0 Ceilings per Escutcheon or 8
(4,9 x 4,9) (49,2) (0,48) (49,2) (0,48) NFPA 13D non-recessed (2,4)
18 x 1S 17 12.0 17 12.0 or 13R pe13R oA 13D
(5,5 x 5,5) (64,3) (0,83) (64,3) (0,83) 1-1/4 to 1-3/4
inches below
20 x 20 20 16.7 20 16.7 bottom of
(6,1 x 6,1) (75,7) (1,15) (75,7) (1,15) beam.
(a) For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage
area for which hydraulic design criteria are stated.
(b) Requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using
the nominal K-factor.Refer to Hydraulic Design under the Design Criteria section.
(c) For NFPA 13 residential applications,the greater of 0.1 gpm/ft2 over the design area of the flow in accordance with the criteria in
this table must be used.
TABLE A
WET PIPE SYSTEM
SERIES LFII RESIDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS(TY2234)
NFPA 13D, 13R,AND 13 HYDRAULIC DESIGN CRITERIA
DRY PIPE SYSTEM
Maximum Minimum Flow and Residual Pressure�b,��
Coverage Ordinary Temp.Rating Intermediate Temp.Rating
Area�a� 155°F(68°C) 175°F(79°C) Minimum
Ft.x Ft. Deflector to Installation Spacing
(m x m) Flow Pressure Flow Pressure Ceiling Type Ft.
GPM PSI GPM PSI (m)
(L/min) (bar) (L/min) (bar)
12 x 12 13 7.0 13 7.0 Smooth
(3,7 x 3,7) (49,2) (0,48) (49,2) (0,48) Ceilings
14x14 14 8.2 14 82 1-1/4to
(4,3 x 4,3) (53,0) (0,57) (53,0) (0,57) 4�nches Recessed
Beamed using Style 20
16 x 16 15 9.4 15 9•4 Ceilings per Escutcheon or 8
(4,9 x 4,9) (56,8) (0,65) (56,8) (0,65) NFPA 13D non-recessed (2,4)
or 13R Per NFPA 13D,
18x18 18 13.5 18 13.5 13R,or13
(5,5 x 5,5) (68,1) (0,93) (68,1) (0,93) 1-1/4 to 1-3/4
inches below
20 x 20 21 18.4 21 18.4 bottom of
(6,1 x 6,1) (79,5) (1,27) (79,5) (1,27) beam.
(a) For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage
area for which hydraulic design criteria are stated.
(b) Requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using
the nominal K-factor.Refer to Hydraulic Design under the Design Criteria section.
(c) For NFPA 13 residential applications,the greater of 0.1 gpm/ft2 over the design area of the flow in accordance with the criteria in
this table must be used.
TABLE B
DRY PIPE SYSTEM
SERIES LFII RESIDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS(TY2234)
NFPA 13D, 13R,AND 13 HYDRAULIC DESIGN CRITERIA
TFP400
Page5of6
Step C. Tighten the sprinkler into the The owner is responsible for the
sprinkler fitting using only the W-Type 7 inspection, testing, and mainte-
Recessed Sprinkler Wrench (Figure 4). nance of their fire protection system
With reference to Figure 1, apply the and devices in compliance with this
W-Type 7 Recessed Sprinkler Wrench document, as well as with the appli-
to the sprinkler wrench flats. cable standards of the National Fire
Step D. After the ceiling has been Protection Association (e.g., NFPA
installed or the finish coat has been 25), in addition to the standards of any
applied, slide on the Style 20 Closure authorities having jurisdiction. Contact
over the Series LFII Residential the installing contractor or sprinkler
Sprinkler and push the Closure over the manufacturer regarding any questions.
Mounting Plate until its flange comes in Automatic sprinkler systems are
contact with the ceiling. recommended to be inspected,
tested, and maintained by a qualified
Care and Inspection Service in accordance with
local requirements and/or national
Maintenance codes.
The TYCO RAPID RESPONSE Series Orderin
LFII Residential Pendent and Recessed �
Pendent Sprinklers(TY2234) must be procedure
maintained and serviced in accordance
with this section: Contact your local distributor for
Before closing a fire protection system availability. When placing an order,
main control valve for maintenance indicate the full product name and Part
work on the fire protection system that Number(P/N).
it controls, permission to shut down Sprinkler Assembly
the affected fire protection system Specify: Series LFII (TY2234), K=4.9,
must be obtained from the proper Residential Pendent Sprinkler,
authorities and notify all personnel (specify)temperature rating, (specify)
who may be affected by this action. finish, P/N (specify).
Absence of the outer piece of an 155°F�ss°c)
escutcheon, which is used to cover Natural Brass..............P/N 51-201-1-155
a clearance hole, can delay sprinkler Pure White(RAL 9010)'......P/N 51-201-3-155
OpGfatl011 111 a fIYG SltUatlOil. Signal White(RAL 9003).....P/N 51-201-4-155
Chrome Plated.............P/N 51-201-9-155
The owner must assure that the i�s°F(�s°c)
sprinklers are not used for hanging Natural Brass..............P/N 51-201-1-175
any objects and that the sprinklers Pure White(RAL 9010)'......P/N 51-201-3-175
are only cleaned by means of gently Signal White(RAL 9003) .....P/N 51-201-4-175
dusting with a feather duster; Oth@Y- Chrome Plated.............P/N 51-201-9-175
WIS6, non-operation Iil the event Of `Eastern Hemisphere sales only.
a fire or inadvertent operation may
result. Recessed Escutcheon
Sprinklers which are found to be Specify: Style 20 Recessed
leaking or exhibiting visible signs of Escutcheon with (specify')finish, P/N
corrosion must be replaced. (specify").
Automatic sprinklers must never be �Refer to Technical Data Sheet
painted, plated, coated, or other- TFP770.
wise altered after leaving the factory. Sprinkler Wrench
Modified sprinklers must be replaced. Specify: W-Type 6 Sprinkler Wrench,
Sprinklers that have been exposed to P/N 56-000-6-387.
corrosive products of combustion, but
have not operated, should be replaced Specify: W-Type 7 Sprinkler Wrench,
if they cannot be completely cleaned P/N 56-850-4-001.
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers - before,
during, and after installation.
Sprinklers damaged by dropping,
striking, wrench twist/slippage, or the
like, must be replaced. Also, replace
any sprinkler that has a cracked bulb
or that has lost liquid from its bulb.
(Ref. Installation Section.)
CO Worldwide www,tyco-fire.com
Contacts
RAPID RESPONSE Series LFII Residential Sprinklers
4.4 K-factor Horizontal Sidewall
Wet Pipe Systems
General The Series LFII Residential Sprinklers
has been designed with heat sensitivity
Description and water distribution characteristics
proven to help in the control of residen-
The TYCO RAPID RESPONSE Series tial fires and to improve the chance for f
LFII Residential Horizontal Sidewall occupants to escape or be evacuated. ►� "�
Sprinklers (TY2334) are decorative, '
fast re �nse. frangible bulb sorin- � �
klers � s�yr , fr u �n ;� �n� The Series LFII Residential Horizontal L �
occu� icie �u� � ho^-��� apr - Sidewall Sprinklers(TY2334)described
ments, u�rr���,.,� :, a��u ��„ce��. ����an herein must be installed and maintained
aesthetics and .,�cimized flow charac- in compliance with this document and
teristics are the major consideration, with the applicable standards of the
the Series LFII Residential Sprinklers National Fire Protection Association, in
(TY2334)should be the first choice. addition to the standards of any author-
The Series LFII Residential Sprinklers ities having jurisdiction. Failure to do so
are intended for use in the following may impair the performance of these �'�,
scenarios: devices. �'
• wet pipe residential sprinkler systems The owner is responsible for main- �
for one-and two-family dwellings and taining their fire protection system and -�: -
mobile homes per NFPA 13D devices in proper operating condition. l�
The installing contractor or sprinkler ��
• wet pipe residential sprinkler systems manufacturer should be contacted with e�'`"""
for residential occupancies up to and any questions.
including four stories in height per
NFPA 13R S rinkler
• wet pipe sprinkler systems for the p Technical
residential portions of any occupancy /dentification Data
per NFPA 13
The recessed version of the Series Number (S/N) Approvals
LFII Residential Sprinklers is intended UL and C-UL Listed
for use in areas with finished walls. TY2334 NSF Certified to NSF/ANSI 61
It employs a two-piece Style 20 For details on approvals, refer to the
Recessed Escutcheon.The Recessed
Escutcheon provides 1/4 inch(6,4 mm) Design Criteria section.
of recessed adjustment or up to 1/2 inch Maximum Working Pressure
(12,7 mm)of total adjustment from the Maximum 175 psi (12,1 bar)
flush mounting surface position. The
adjustment provided by the Recessed Discharge Coefficient
Escutcheon reduces the accuracy to K=4.4 GPM/psi��2(63,4 LPM/bar1i2)
which the pipe nipples to the sprinklers
must be cut. Temperature Rating
155°F(68°C)or 175°F(79°C)
IMPORTANT
Always refer to Technical Data Finishes
Sheet TFP700 for the "INSTALLER Natural Brass
WARNING" that provides cautions Signal White
with respect to handling and Chrome Plated
installation of sprinkler systems and Physical Characteristics
components. Improper handling and Frame. . . . . . . . . . . . . . . . . . . . Brass
installation can permanently damage Button. . . . . . . . . . . . . . . . . . . Bronze
a sprinklersystem orits components Sealing Assembly. . . . . . . . .Beryllium
and cause the sprinkler to fail to Nickel w/TEFLON
operafe in a fire situation or cause it Bulb . . . . . . . . . . . . . . . . .3 mm Glass
to operate prematurely. Compression Screw. . . . . . . . Bronze
Deflector. . . . . . . . . . . . . . . . . Copper
Page 1 of 6 APRIL 2013 TFP412
TFP412
Page2of6
Components: WRENCH
1 - Frame FLATS �/RENCH
2 - Button � F�,4TS
3 - Sealing TOP-OF- �
Assembly DEFLECTOR 1/2" NPT
4 - Bulb
5 - Compression 7/16" (11,1 mm)
Screw � NOMINAL 2-7/8" DIA.
6 - Deflector* � 6* 5 4 2 MAKE-IN (73,0 mm)
*Temperature rating _ CENTERLWE
is indicated on top f OF WATERWAY
of Deflector. ��1g�� 1 STYLE 20
RECESSED
(11,1 mm) 1_��2„ � ESCUTCHEON
END-OF- �(38,1 mm)~ ESCUTCHEON
DEFLECTOR 2-1/8" � PLATE SEATING
BOSS (54,0 mm) SURFACE RECESSED
FIGURE 1
RAPID RESPONSE SERIES LFII RESIDENTIAL HORIZONTAL SIDEWALL
AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS(TY2334)
7/16±1/8"
~(11,1±3,2 mm)
MOUNTING FACE OF / WRENCH RECESS
SURFACE SPRINKLER (END"A" USED
FITTING / FOR TY2334)
TOP-OF- CLOSURE
DEFLECTOR } FIGURE 3
� TY2334 I W-TYPE 6
2-7/8" DIA. SPRINKLER WRENCH
(73,0 mm)
2-1/4" DIA. WRENCH
� (57,2 mm) RECESS
7/16" �
(11,1 mm)
MOUNTING �
PLATE
END-OF-
DEFLECTOR 1/8" �
BOSS (3,2 mm)
PUSH WRENCH
1-1/4" (31,8 mm) 1/2"(12,7 mm) IN TO ENSURE
1" (25,4 mm) 1/4" (6,4 mm) ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 2
STYLE 20 RECESSED ESCUTCHEON FIGURE 4
FOR USE WITH THE RAPID RESPONSE SERIES LFII W-TYPE 7 RECESSED
RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER(TY2334) SPRINKLER WRENCH
TFP412
Page3of6
Oneration Obstruction to Water Distribution Step 2. With pipe thread sealant
/" Sprinklers are to be located in accor- applied to the pipe threads, hand
The glass bulb contains a fluid that dance with the obstruction rules of tighten the sprinkler into the sprinkler
expands when exposed to heat. When NFPA 13D, 13R, and 13 as applicable fitting.
the rated temperature is reached, the for residential sprinklers as well as with Step 3. Tighten the sprinkler into
fluid expands sufficiently to shatter the obstruction criteria described within the sprinkler fitting using only the
the glass bulb allowing the sprinkler to the Technical Data Sheet TFP490. W_Type 6 Sprinkler Wrench (Ref.
activate and flow water. Operational Sensitivity Figure 3). With reference to Figure 1,
The sprinklers are to be installed the W-Type 6 Sprinkler Wrench is to be
Design with an end of defector-boss to wall applied to the wrench flats.
� � distance of 1-1/8 to 6 inches. Series LFII Residential Recessed
Cr�ter�a In addition the top-of-deflector-to- Horizontal Sidewall Sprinklers
ceiling distance is to be within the The Series LFII Recessed Horizontal
The TYCO RAPID RESPONSE Series range(Ref.Table A) being hydraulically Sidewall Sprinklers must be installed
LFII (TY2334) Residential Horizontal calculated. in accordance with the following
Sidewall Sprinklers are UL and C-UL instructions.
Listed for installation in accordance Sprinkler Spacing
with this section. The minimum spacing between sprin- Step A. Recessed horizontal side-
klers is 8 feet (2,4 m). The maximum `^�all sprinklers are to be installed in the
Residential Sprinkler Design Guide horizontal position with their center-
When conditions exist that are outside spacing between sprinklers cannot line of waterway perpendicular to the
the scope of the provided criteria, refer exceed the width of the coverage area back wall and parallel to the ceiling.The
to the Residential Sprinkler Design �Ref.Table A)being hydraulically calcu- Word "TOP" on the Deflector is to face
Guide TFP490 for the manufacturer's lated(e.g., maximum 12 feet for a 12 ft. towards the ceiling.
recommendations that may be accept- x 12 ft. coverage area, or 16 feet for a
able to the local authority having 16 ft.x 20 ft. coverage area). Step B. After installing the Style 20
jurisdiction. � Mounting Plate over the sprinkler
Installat�on threads and with pipe thread sealant
System Type applied to the pipe threads, hand
Only wet pipe systems may be utilized. The TYCO RAPID RESPONSE Series tighten the sprinkler into the sprinkler
LFII (TY2334) Residential Horizontal fitting.
Ceiling Type Sidewall Sprinklers must be installed in Step C. Tighten the sprinkler into the
Smooth flat horizontal, or beamed, or accordance with this section. sprinkler fitting using only the W-Type
sloped, in accordance with the 2013 7 Recessed Sprinkler Wrench (Ref.
Edition of NFPA 13D, 13R, or 13 as General Instructions
applicable. Do not install any bulb-type sprinkler if Figure 4).With reference to Figure 1,the
the bulb is cracked or there is a loss of W-Type 7 Recessed Sprinkler Wrench
Hydraulic Design liquid from the bulb. With the sprinkler is to be applied to the sprinkler wrench
(NFPA 13D and 13R) held horizontally, a small air bubble flats.
For systems designed to NFPA 13D should be present.The diameter of the Step D. After the wall has been
or NFPA 13R, the minimum required air bubble is approximately 1/16 inch installed or the finish coat has been
sprinkler flow rate are given in Table (1,6 mm). applied, slide on the Style 20 Closure
A as a function of temperature rating A leak-tight 1/2 inch NPT sprinkler over the Series LFII Sprinkler and push
and the maximum allowable coverage joint should be obtained by applying a the Closure over the Mounting Plate
areas. The sprinkler flow rate is the minimum to maximum torque of 7 to 14 until its flange comes in contact with
minimum required discharge from ft.-Ibs. (9,5 to 19,0 Nm). Higher levels the wall.
each of the total number of "design of torque can distort the sprinkler Inlet
sprinklers"as specified in NFPA 13D or With consequent leakage or impairment
NFPA 13R. of the sprinkler.
Hydraulic Design Do not attempt to compensate for
(NFPA 13) insufficient adjustment in the sprinkler
For systems designed to NFPA 13, by under- or over-tightening the
the number of design sprinklers is sprinkler. Re-adjust the position of the
to be the four most hydraulically sprinkler fitting to suit.
demanding sprinklers. The minimum Series LFII Residential Horizontal
required discharge from each of the Sidewall Sprinklers
four sprinklers is to be the greater of The Series LFII Horizontal Sidewall
the following: Sprinklers must be installed in accor-
• The flow rates given in Table A as a dance with the following instructions.
function of temperature rating and the Step 1. Horizontal sidewall sprin-
maximum allowable coverage area. klers are to be installed in the hori-
• A minimum discharge of 0.1 zontal position with their centerline of
gpm/ft2 over the "design area" waterway perpendicular to the back
comprised of the four most hydrau- wall and parallel to the ceiling. The
lically demanding sprinklers for word "TOP" on the Deflector is to face
the actual coverage areas being towards the ceiling with the front edge
protected by the four sprinklers. of the Deflector parallel to the ceiling.
TFP412
Page4of6
WET PIPE SYSTEM
Max.Coverage Max. Minimum Flow and Residual Pressure�b,�1
Area�a1 Spacing prdinary Temp.Rating Intermediate Temp.Rating
Width x Length(d1 Ft. 155°F(68°C) 175°F(79°C) Minimum
Ft.x Ft. �m� Flow Pressure Flow Pressure Deflector to Installation Spacing
(m x m) GPM PSI GPM ps� Ceiling Type Ft.
(L/min) (bar) (L/min) (bar) �m)
12 x 12 12 13 8.7 13 8.7
(3,7 x 3,7) (3,7) (49,2) (0,60) (49,2) (0,60)
14 x 14 14 14 10.1 14 10.1
(4,3 x 4,3) (4,3) (53,0) (0,70) (53,0) (0,70)
16 x 16 16 16 13.2 16 13.2
(4,9 x 4,9) (4,9) (60,6) (0,91) (60,6) (0,91)
16 x 18 16 19 18.6 19 18.6 4 to
(4,9 x 5,5) (4,9) (71,9) (1,28) (71,9) (1,28) 6 inches
16 x 20 16 23 27.3 23 27.3
(4,9 x 6,1) �4�9) �8��1) �1�$$) �8��1) �1�$$)
18 x 18 18 23 27.3 23 27.3
(5,5 x 5,5) �5,5) �8�,1) �1,$$) �8�,1) �1,$$)
18 x 20 18 26 34.9 26 34.9 Recessed
(5,5 x 6,1) (5,5) (98,4) (2,41) (98,4) (2,41) Escu�tchteon2or 8
12 x 12 12 13 8.7 13 8.7 non-recessed (2,4)
(3,7 x 3,7) (3,7) (49,2) (0,60) (49,2) (0,60) per NFPA 13D,
13R,or 13
14 x 14 14 14 10.1 14 10.1
(4,3 x 4,3) (4,3) (53,0) (0,70) (53,0) (0,70)
16 x 16 16 17 14.9 17 14.9
(4,9 x 4,9) (4,9) (64,3) (1,03) (64,3) (1,03)
16 x 18 16 20 20.7 20 20.7 6 to
(4,9 x 5,5) (4,9) (75,7) (1,43) (75,7) (1,43) 12 inches
16 x 20 16 23 27.3 23 27.3
(4,9 x 6,1) (4�9) (87,1) (�,88) (87,�) (1,88)
18 x 18 18 23 27.3 23 27.3
(5,5 x 5,5) (5,5) (87,1) (1,88) (87,1) (1,88)
18 x 20 18 26 34.9 26 34.9
(5,5 x 6,1) (5,5) (98,4) (2,41) (98,4) (2,41)
(a) For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which
hydraulic design criteria are stated.
(b) Requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K-
factor.Refer to Hydraulic Design under the Design Criteria section.
(c) For NFPA 13 residential applications,the greater of 0.1 gpm/ft2 over the design area or the flow in accordance with the criteria in this table must be
used.
(d) The Width x Length dimension refers to the Width(backwall where the sprinkler is located)times the Length(horizontal throw of sprinkler).
TABLE A
WET PIPE SYSTEMS
SERIES LFII(TY2334)RESIDENTIAL HORIZONTAL SIDEWALL
AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS
NFPA 13D, 13R AND 13 WET PIPE HYDRAULIC DESIGN CRITERIA
NIBCO . . .
�:� ,� �� - - �'`��,; -
�,
■ ■ ■
All of the advantages found in copper as a metal have been capitalized to the utmost in the manufacture of NIBCO Fittings. Because
of the accuracy of construction and design,copper plumbing is more efficient and less expensive.
NIBCO manufactures nine general types of fittings:Wrot Pressure; Cast Pressure;Wrot Drainage; Cast Drainage; Flanges; Flared
Tube;Threaded Bronze; Insert Fittings for PEX; Barbed Insert Fittings for Polybutylene. Each has its particular place and use and each
offers its own advantages when used for the proper service requirement.
ALLOY AND FINISH NIBCO Fittings are made from highest quality raw materials available—Cast Fittings are made from Copper
Alloy C84400 which consists of 81% Copper,7% Lead,3%Tin,and 9%Zinc per ASTM Specification B584.Wrot Copper Fittings are
made from commercially pure copper mill products per ASTM Specifications B75 Alloy C12200.
NIBCO fittings are produced to meet requirements of applicable standards wherever practicable.
NIBCO brand wrot and cast fittings are manufactured in the U.S.A. and Mexico.The manufacturing plants at Stuarts Draft,VA,
Nacogtloches,TX and Reynosa, Mexico are registered to ISO 9002 quality standards.
Following is suggested phrasing to be incorporated in your specifications or bills of material for
Copper Tube Fittings.
x WROT SOLDER JOINT FITTINGS—"Wrot Solder Joint Fittings shall be produced to one of the following specifications:
1. Material and workmanship shall be in accordance with ASME/ANSI B16.22;Wrought Copper and Copper Alloy Solder Joint
Pressure Fittings."
2. The dimensional, material and workmanship shall dimensions of Federal Specifications WW-F-406 or
meet the requirements of MSS SP-104;Wrought ASME Std. B16.24.
Copper Solder Joint Pressure Fittings." CLASS 125—Material,workmanship and
3. The dimensional, material and workmanship of dimensions of flanges shall be in accordance with
5"-12"copper fittings shall meet the requirements MSS SP-106.
of MSS SP-109 "Welded Fabricated Copper Solder CAST BRONZE THREADED FITTINGS—
Joint Pressure Fittings."" "Cast Bronze Threaded Fittings shall be in accordance
4. Certified to ANSI/NSF 61. with ANSI/ASME B16.15."
CAST COPPER ALLOY SOLDER JOINT FITTINGS POLYBUTYLENE COPPEA INSEAT TYPE VALVES AND
—"Cast Copper Alloy Solder Joint Fittings shall be in FITTINGS—"Wrot Copper Insert Fittings shall be
accordance with ANSI Std. B16.18." manufactured per the following specifications:
WROT DRAINAGE FITTINGS—"Wrot Drainage MSS SP-103 or ASTM F1380."
Fittings shall be in accordance with ASME/ANSI Std. NIBCO Copper Tube Fittings are all produced to above
B16.29." Standards.To simplify,write your specifications to
CAST COPPER ALLOY SOLDEA JOINT DRAINAGE read: "Copper Tube Fittings to be in accordance with
FITTINGS—"Cast Copper Alloy Solder Joint Drainage specifications as outlined in NIBCO Catalog c-cf-0602."
Fittings shall be in accortlance with ASME Std. WROT COPPER MEDICAL MEDICAL GAS SYSTEM
B16.23." COMPONENTS—Wrot copper fittings that are to be
CAST COPPER ALLOY FLARED TUBE FITTINGS—"Cast installed in medical gas applications shall be prepared
Copper Alloy Flared Tube Fittings shall be in accor- in accordance with NFPA 99, Health Care Facilities
dance with ASME/ANSI Std. B16.26. Gas and Vacuum Systems and the Compressed
Gas Association, Pamphlet G4.1. Packaging shall
CAST COPPER ALLOY FLANGES AND FLANGED be adequately protective and include labeling that
FITTINGS— identifies the preparer and states that the product
CLASS 150—Cast Copper Alloy Flanges and has been cleaned antl bagged for oxygen or med gas
Flanged Fittings shall meet the requirements service.
of MSS SP-106 and/or the workmanship and For technical information and dimensions refer to the
engineering section contained in this catalog.
� NIBCO INC.WORLD HEADQUARTERS•1516 MID�LEBURY ST•ELKHART,IN 46516-4740•USA•PH:1.800234.0227
� TECH SERVICES PH:1.888.446A226•FAX:1.888234.0557•INTERNATIONAL OFFICE PH:+1.574295.3327•FAX:+1.574295.3455
www.nibco.com
NIBCO . . .
�:� � �� - - �;`��,-, _ ,
ADAPTERS
�i� �� � ` �i
'.��� � - :�
X 603 703 703-2
Adapter C x F-Wrot Adapter C x F- Cast Fitting Adapter Ftg x F- Cast
� � � � � �
� � ,
1/8 0.03 13/sz 1/4 x 1/2 0.13 27/az 1/2 x 1/4 0.11 1'/sz
1/8 x 1/4 0.03 '/z 1/2 x 1 0.30 1 3/4 x 1/2 0.12 19/,s
1/4 0.03 5/s 3/4 x 1 1/4 0.55 1'/s 1 x 3/4 0.38 131/3z
1/4 x 3/8 0.05 21/sz 3/4 x 3/8 0.17 3/a 1 x 1/Z 0.15 1'/,s
3/8 0.04 "/,s 1 x 1 1/2 0.68 13/sz 21/2 1.65 215/,s
3/8 x 1/2 0.09 �s/az 1 1/4 x 1 0.27 31/az 3 2.47 3'/4
3/8 x 1/4 0.03 9/,s 1 1/4 x 3/4 0.29 3/a
1/2 0.09 27/az 1 1/2 x 2 OJ8 1'/az
1/2 x 3/4 0.14 1 1 1/2 x 1 0.37 25/az �„r yy
1/2 x 3/8 0.04 "/az 1 1/2 x 1 1/4 0.47 1'/4
1/2 x 1/4 0.05 '/z 2 x 1 1/4 OJ6 �'/az �'��� �"��-
5/8 x 3/4 0.12 29/az 2 1/2 1.62 13/s . ��� �
5/8 x 1/2 0.11 3/a 3 2.34 1'/z �++' �
3/4 0.15 29/az 4 4.05 1 g/is
3/4 x 1 021 1�/e
3/4 x 1/2 0.10 5/e
1 024 31�3� 703-5 Special
1 x 1 1/4 o.zs 25�3� �i� Drop Adapter C x F- Cast
1 x 3/4 0.19 /az ,� " ����' ,,� �
1 x 1/2 024 5/e � � �
�I
1 1/4 0.33 13/az ,;:�y � 1/2 0.16 3/a
11/4x11/2 0.40 1�/a 3/4 0.24 31/s2
1 1/4 x 1 027 31�32 603.-2
� ��2 0.44 ���$ Fitting Adapter Ftg x F-Wrot �
1 1/2 x 2 0.50 1'/az ••� �
2 0.63 13/az � _ -
2 x 1 1/2 0.74 13/,s 1/4 0.03 13/sz
21/2 1.13 - 3/8 0.06 13/�s
3 1.94 - 1/2 0.09 1'/,s �
1/2 x 3/8 0.05 1'/4
3/4 0.13 1"/�s "
1 0.27 2'/3z 703-5B
1 1/4 0.31 2�/e Drop Adapter C x F- Cast
11/2 0.43 ZS/is
2 0.61 2"/sz ''' '
�
1/2 0.15 3/a
Consult price sheet for Made to Order items and
for minimum order quantities.
NIBCO INC.WORLD HEADQUARTERS•1516 MID�LEBURY ST•ELKHART,IN 46516-4740•USA•PH:1.800234.0227
�i TECH SERVICES PH:1.888.446A226•FAX:1.888234.0557•INTERNATIONAL OFFICE PH:+1.574295.3327•FAX:+1.574295.3455
www.nibco.com
N 1 BCO . . .
�:� � � �. - - �����,t�a -
.
CAPS COUPLINGS
, �
� � �
3 x 2 1/2 0.98 '/z
3 x 2 1.06 15/is
I, � 3 x 1 1/2 0.92 1'/sz
� 31/2 x 3 1.52 '/z
6�� X 4 x 31/2 2.12 '9/sz
4 x 3 1.92 Z'/sz
x 617 Reducing Coupling C x C -Wrot 4x21/2 �.�� �
Tube Cap C-Wrot •••� � � 4X2 1.92 ���4
••� � � 5 x 4 3.50 331�32
� 1/8 x 3/16 O.D. 0.01 5/3z 5 x 3 3.18 �15�32
1/8 0.01 '/sz 5/16 O.D.x 1/8 0.01 3/�6 5 x 21/2 3.50 13/is
1/4 0.01 3/az 1/4 x 5/16 O.D. 0.01 3/�6 5 x 2 3.09 2'/az
3/8 0.01 3/az 1/4 x 1/8 0.01 3/�s 6 x 5 5.70 1'/s
1/2 0.02 3/az 3/8 x 1/4 0.02 3/�6 6 x 4 5.24 1'/z
5/8 0.03 '/a 3/8 x 5/16 O.D. 0.01 '/4 6 x 3 5.04 2
3/4 0.04 �/a 3/8 x 1/8 0.01 '/4 6 x 21/2 5.13 2'/a
1 0.07 5/az 1/2 x 3/8 0.03 3/�s 6 x 2 4.89 2'/z
1 1/4 0.10 3/az 1/2 x 1/4 0.02 �/4 8 x 6 13.06 �19�32
1 1/2 0.16 '/a 1/2 x 1/8 0.03 "/3z 8 x 4 12.22 2'g/az
2 0.27 5/az 5/8 x 1/2 0.05 3/�6 8 x 3 11.79 33/az
21/2 0.50 �/az 5/8 x 3/8 0.04 "/32 8 x 21/2 12.64 33/s
3 OJS �/az 5/8 x 1/4 0.03 13/sz
4 1.66 '/a 3/4 x 5/8 0.07 3/is
3/4 x 1/2 0.06 9/az I �
3/4 x 3/8 0.06 3/a
3/4 x 1/4 0.05 "/sz
1 x 3/4 0.11 "/az
1 x 5/8 0.09 3/a
1 x 1/2 0.10 "/s2
1 x3/8 0.10 13�3Z 600-RS X
1 1/4x 1 0.16 5�,6 Coupling with Rolled Tube Stop
��� 11/4x3/4 0.18 ��/3z � X � -WfOt
Tube Cap C - Cast 11/4x5/8 0.18 5�8 "1 �
��� � 1 1/4 x 1/2 0.14 �/is �
� 1 1/Z x 1 1/4 0.23 5/is 1/8 O.D. 0.01 '/�s
5 5.48 �/�e 1 1/Z x 1 0.22 s/is 3/16 O.D. 0.01 3/az
6 9.07 "/3z 1 1/Z x 3/4 0.20 3/a 1/8 0.01 �/is
1 1/2 x 1/2 0.19 '/z 5/16 O.D. 0.01 3/sz
2 x 1 1/2 0.41 g/�s 1/4 0.01 �/�s
;= 2 x 1 1/4 0.35 �'/�s 3/8 0.01 3/az
2 x 1 0.37 �/�s 1/2 0.03 3/sz
2 x 3/4 0.34 ��/3z 5/8 0.04 3/sz
2 x 1/2 0.35 23/sz 3/4 0.06 3/sz
21/Z x 2 0.59 g/is 7/8 0.09 3/az
2 1/Z x 1 1/2 0.65 "/i s 1 0.11 3/sz
717-D 2 1/2 x 1 1/4 0.65 13/is 1 1/4 0 16 '/a
Drain Cap - Cast 21/Zx 1 0.73 29�3z � vz o.z3 ��8
�
� � Cantinues. Z 0.41 �/s
21/2 0.65 �/s
1/2 0.06 Z�/az 3 0.93 '/s
31/2 1.45 5/sz
4 1.93 �/3z
Consult price sheet for Made to Order items and
for minimum order quantities.
NIBCO INC.WORLD HEADQUARTERS•1516 MID�LEBURY ST•ELKHART,IN 46516-4740•USA•PH:1.800234.0227 �
TECH SERVICES PH:1.888.446A226•FAX:1.888234.0557•INTERNATIONAL OFFICE PH:+1.574295.3327•FAX:+1.574295.3455 �
www.nibco.com
NIBCO . . .
�:� � �� - - �;`��,-, _ ,
ELBOWS continued
' �(�4
706-2 707 607-LT
45° Fitting Elbow Ftg x C - Cast 90°Elbow- Close Rough 90° Elbow- Long Radius
�
• •�•� � � � CxC - Cast CxC -Wrot
•� � � � •� � � �
4 4.31 3��/sa 15/is � �
1 1/4 x 1 0.42 15/s 1'S/sz 3/16 0.D. 0.01 '3/sz '3/sz
11/4x3/4 0.34 9/�s 13/is 1/8 0.01 13/sz 13/sz
1 1/4 x 1/2 0.28 15/sz �'/az 5/16 O.D. 0.02 9/�s 9/�s
1 1/2 x 1 0.54 "/�s 1 1/4 0.02 "/sz "/sz
1 1/2 x 3/4 0.42 19/sz 3'/sz 1/4 x 1/8 0.01 '9/sz '/z
�'`'. / � 1 1/2 x 1/2 0.40 5�e zs�s2 3/8 0.04 23/sz z3/sz
- 2 x 1 1/4 0.8 6 '/a 1'/a 1/2 0.0 8 '/s '/a
���•' ' 2 x 1 0.78 3/a 1�/a 1/2 x 3/8 0.06 13/is 13/�s
2 x 3/4 0.69 5/a 1'/a 1/2 x 1/4 0.03 ZS/sz Z'/sz
6�� 2 1/2 x 2 2.16 13/is �g�32 5/8 0.10 13/sz 13/sz
9�° Elbow- Close Rough 3x21/2 2.26 1"/,s 1'/z 5/8x1/2 0.09 1'/�s 1'/is
C X C -WCOt 3 x 2 2.68 13/a 19/is 3/4 0.16 1'/a 1'/a
•i � � �
4 x 3 5.18 129/sz 2'S/sz 3/4 x 5/8 0.13 1'/a 13/sz
� 3/4 x 1/2 0.10 1'/a 1'/is
1/8 0.01 ''/a2 13/sz �"'�'' 7/8 0.28 1�s/32 119/a2
1/4 0.02 9/sz g/sz 1 0.28 1'/�s 1'/is
3/8 0.03 �/2 �h 1 x 3/4 0.20 1'/a 1'/a
1/2 0.04 3/e 3/a - 1 x 5/8 0.15 113/sz 13/sz
1/2 x 3/8 0.04 g/is Z�/az � 1 1/4 0.42 1'/a 1'/a
3/4 0.10 »/az ��/3z � 1 1/4 x 1 0.33 125/a2 1�/z
3/4 x 5/8 0.12 29/s2 �/a 1 1/2 0.66 2'/a 2'/a
3/4 x 1/2 0.10 ��/sz 3/n 2 1.23 215/is 215/�s
1 0.21 23/az 23/az 607-I � 21/2 1.96 3"/is 3"/�s
1 x3/4 0.16 23/sz 5�8 �O°Elbow- s 2.93 4'/az 4'/sz
1 1/4 0.31 1�/s2 1�/sz Intermediate Radius C x C 4 5.95 5'/a 5'/a
1 1/4 x 1 0.31 15/s 115/sz -�/COt
1 1/2 0.46 1�/az 1�/s2 ,,� � � �
1 1/2 x 1 1/4 0.35 15/s2 13/az '
2 0.84 1�/z 1�/z 1/2 0.06 19/sz �s/sz
2 x 1 1/2 0.58 1�/is 1'/a 5/8 0.09 '/e '/s
21/2 1.41 127/s2 1z7/sz 3/4 0.14 13/�s 3/is
3 2.07 23/s2 23/az 1 0.24 1'/�s 1'/is
3 1/2 2.94 Z3�8 23/a
4 4.23 225�32 zZ5�32
5 7J4 2�/a 2�/e
6 10.95 3�/�s 3�/�s
8 29.50 423/s2 4z3/sz
Consult price sheet for Made to Ortler items and
for minimum order quantities.
m NIBCO INC.WORLD HEADQUARTERS•1516 MID�LEBURY ST•ELKHART,IN 46516-4740•USA•PH:1.800234.0227
TECH SERVICES PH:1.888.446A226•FAX:1.888234.0557•INTERNATIONAL OFFICE PH:+1.574295.3327•FAX:+1.574295.3455
www.nibco.com
N 1 BCO . . .
�: � �; e ���„t�a _ ,
ELBOWS continued FITTING REDUCERS
,
� ,
�,� 4 x 3 1/2 2.09 25/s
��� � � � �� 4 x 3 Z.00 3'/az
� � �'`�; ' 4 x 2 1/2 1.56 3'/az
I� � 4 x 2 1 J6 313/sz
� ,,: __;_�,�' _
5 x 4 3.30 39/is
5 x 3 2.97 4'/�e
5x21/2 3.30 4��/az
���-6 6��-2 X 5x2 2.88 4��/is
90°Union Elbow C x C - Cast Fitting Reducer Ftg x C -Wrot 6X5 5.56 n3�,6
., , , ., , 6 x 4 5.09 4g/�e
' ' 6 x 3 4.67 5'/�s
3/8 0.17 ��/az 5/is 1/4 x 1/8 0.01 ��/a� 6 x 2 1/2 4.47 5��/sz
1/2 0.24 1 �/i s 3/8 x 1/4 0.01 �9/az 6 x 2 � 4.51 5�s/az
3/4 0.39 ����32 9/is 3/8 x 1/8 0.01 25/sz 8 x 6 12.33 515/sz
1 0.64 1Z1/sz 23/sz 1/2 x 3/8 0.03 "/is 8 x 5 10.35 515/is
1 1/4 1.07 ��g�32 23/sz 1/2 x 1/4 0.02 25/sz 8 x 4 11.10 6'/�s
5/8 x 1/2 0.04 �/e 8 x 3 10.63 615/is
5/8 x 3/8 0.04 31/sz 8 x 2 1/2 11.41 73/�e
5/8 x 1/4 0.03 1�/sz 8 x 2 10.86 7�/�s
� 3/4 x 5/8 0.06 31/sz
3/4 x 1/2 o.os ���8 F LA N G E S -
3/4 x 3/8 0.05 1'/s C LA S S 125
3/4 x 1/4 0.05 13/sz
1 x 3/4 0.10 1�/az
..:,.���.
1 x 5/8 0.09 13/e q��`
708 1x1/2 0.09 1�/a
90°Flanged Sink Elbow 1 x3/8 0 os �g�3Z
C X F- CaSt 1 1/4 x 1 0.15 15/�s
1 1/4 x 3/4 0.16 1�/z
� � � � � 1 1/4 x 1/2 0.13 13/s
1/2 0.20 '/a �/is 13/a 1 1/2 x 1 1/4 0.23 113/sz
- 1 1/2 x 1 0.21 15/a
1 1/2 x 3/4 0.20 1�/e
11/2x1/2 0.16 �19�32
2 x 1 1/2 0.40 131/az
Z x 1 1/4 0.34 23/az 741
zX� 0.35 �27�3Z Companion Flange C - Cast
2 x 3/4 0.35 127/az
2x1/Z 0.34 131/az � �•�� � � � �
21/2 x 2 0.65 131/az 1/2 Q55 '/s 3'/z 3/�s 2�/a
21/2 x 1 1/2 0.65 23�8 3/4 0J1 '/s 3'/a 3/is Z3�4
21/2 x 1 1/4 0.60 z�/3z 1 1.26 '/a 4'/a '/4 3'/a
21/2 x 1 OJ8 2g/sz 1 1/4 1.42 '/a 45/a '/a 3'/z
]64 3x21/2 1.03 2'/4 11/2 1.82 '/a 5 5/is 3'/a
g�° Double Elbow 3x2 0.99 2g/is 2 276 '/s 6 3/e 43�4
� X � X C - �aSt 3 x 1 1/2 0.81 219/az 21/2 4 29 '/e 7 3/s 5'/z
3 x 1 1/4 1.29 3�/a 3 5.26 '/a 7�/z �/is 6
...� � � � 31/2 x 3 1.48 2"/az
' 4 7.60 '/a 9 '/is 7�/z
1 x 3/4 x 3/4 0.33 3/4 ��/yz Continues... 5 9.04 �/s 10 �/is 8�/2
6 12.68 '/a 11 '/z 9'/z
Consult price sheet for Made to Order items and ruore:o�m a=r�bescoPto Fia�9e Fa�e
for minimum order quantities.
NIBCO INC.WORLD HEADQUARTERS•1516 MID�LEBURY ST•ELKHART,IN 46516-4740•USA•PH:1.800234.0227 m
TECH SERVICES PH:1.888.446A226•FAX:1.888234.0557•INTERNATIONAL OFFICE PH:+1.574295.3327•FAX:+1.574295.3455
www.nibco.com
NIBCO . . .
�:� � �� - - �;`��,-, _ ,
TEES continued
�
�a �„�'`. _
_ ._.m`.��r;
� r �
NOTE:Tee sizes are read Run x Run x Outlet.
611 X �� � � •� � �
Tee C x C x C -Wrot continued � �
� � �
� 2 1.30 1 g/32 19/sz 1�/32 3 3.15 1�/s 1'/a 2'/sz
1 x 1/2 x 1 029 "/�s 1 21/3z 2 x 2 x 21/2 2.34 2 2 1z1/sz 3 x 3 x 2 1/2 3.55 1z9/sz 129/sz Z3�8
1 x 1/2 x 3/4 027 g/is 13/16 s�4 2 x 2 x 1 1/Z 1.17 1�/a 1'/a 123/sz 3 x 3 x 2 3.19 115/sz 115/sz 13'/az
1 x 1/2 x 1/2 0.22 'S/az 25�32 23/az 2 x 2 x 1 1/4 1.12 9/sz g/sz 1�/s 3 x 3 x 1 1/2 3.08 1'S/sz 1'S/az 29/sz
1 1/4 0.43 13/is 3/is 13/is Z x 2 x 1 0.90 27/sz z7/sz 1�/a 3 x 3 x 1 1/4 3.10 115/sz 115/sz 2'/is
1 1/4 x 1 1/4 x 2 1.13 130/az 130/az 13/az 2 x 2 x 3/4 0.88 19/sz �s/sz 1�/a 3 x 3 x 1 2.12 �'/az �'/az 13�/az
1 1/4 x 1 1/4 x 1 1/2 0.60 13/ts 13/ts 29/az Z x 2 x 1/2 1.17 1'/a 1'/a 2�/a 3 x 3 x 3/4 2.39 27/az 27/sz 23/is
1 1/4 x 1 1/4 x 1 0.45 25/az 25�32 29/az z x 1 1/2 x 2 1.16 1 g/sz 1�/a 1��/sz 3 x 3 x 1/2 1.82 z7/az z7/sz 23/s
1 1/4 x 1 1/4 x 3/4 0.37 21/az 21/sz 3/a 2 x 1 1/2 x 1 1/2 1.15 1�/4 13/a 1 z3/az 3 x 2 1/2 x 3 3.08 1'/s 23/s �31�32
1 1/4 x 1 1/4 x 1/2 0.30 '/z 'h 25/sz 2 x 1 1/2 x 1 1/4 1.15 �/sz 13/a 1��/s2 3 x 2 1/2 x 2 1/2 3.12 1 z9/sz Z"/sz 25/sz
1 1/4 x 1 1/4 x 3/8 0.34 23/az 23�32 29/az Z x 1 1/2 x 3/4 0.83 z1/sz �5/is 1�/32 3 x 2 1/2 x 2 228 1'S/sz 1 z7/sz 131/az
11/4x1x11/4 0.43 13/is 1�/az 13/�s 2x11/2x1/2 1.12 1�/a 125/sz 2�/a 3x2x3 3.62 1z9/sz2"/az115/is
1 1/4 x 1 x 1 0.47 25/az �/s �s/az 2 x 1 1/4 x 2 1.58 19/az 1�5/az 1 s/sz 3 x 2 x 2 1/2 3.56 1�g/a2 2s/i s 25/i s
1 1/4 x 1 x 3/4 0.35 21/az 25/az �/a 2 x 1 1/4 x 1 1/2 1.16 1�/4 131/az 123/s2 3 x 2 x 2 322 115/sz 13�/sz 13�/az
1 1/4 x 1 x 1/2 0.30 �/z 5/e 29/az 2 x 1 1/4 x 1 1/4 1.19 'S/�s 1"/sz 1'�/sz 3 x 1 1/2 x 3 3.13 129/sz 2Z5/sz 23/sz
1 1/4 x 3/4 x 1 1/4 0.42 '3/i s �1�8 '3/�s 2 x 1 1/4 x 1 0.90 27/sz 19/sz 1��/sz 3 x 1 1/4 x 3 3.63 1 z9/sz 2z5/az 1'S/i s
1 1/4 x 3/4 x 1 0.45 25/az 1'/az 29/az Z x 1 1/4 x 3/4 0.85 z1/sz 1 1$/z� 3 x 1 x 3 3.20 131/sz Z'g/sz 23/is
1 1/4 x 3/4 x 3/4 0.37 ��/az 15/is �/a 2 x 1 x 2 1.11 1�/a 125/az 1�/a 3 x 3/4 x 3 3.55 131/a2 2�s/sz 23/is
1 1/4 x 3/4 x 1/2 0.30 '/z 3/a 29/az 2 x 1 x 1 0.89 z7/sz 19/sz 1'�/s2 3 1/2 520 2"/sz 2"/sz 2"/az
1 1/4 x 1/2 x 1 1/4 0.41 13/is 1�/az 13/is 2 x 3/4 x 2 1.15 1g/sz Z3�16 1�/a 4 8.12 213/sz 213/az 2"/sz
1 1/2 0.61 31/az 31/az �s/az 2 x 1/2 x 2 1.15 19/az 23/a 1�/4 4 x 4 x 3 6.70 2�/sz 2'/az 2�'/az
1 1/2 x 1 1/2 x 2 1.11 125/az 125/az 13/az 21/2 2.40 15/a 15/a 15/s 4 x 4 x 2 1/2 6.65 2'/s2 2'/az 35/az
1 1/2 x 1 1/2 x 1 1/4 0.62 �s/az �s/az 1'/is 2 1/2 x 2 1/2 x 2 1.97 15/�s 15/is 1��/sz 4 x 4 x 2 5.82 1's/az 115/s2 2'/is
1 1/2 x 1 1/2 x 1 0.55 ��/�e '�/is �/a 2 1/2 x 2 1/2 x 1 1/2 1.53 13/sz 13/sz 1��/sz 4 x 4 x 1 1/2 3.94 1"/az 1��/az 2�'/a2
�> >> > 2 1/2 x 2 1/2 x 1 1/4 1 J2 13/32 13/sz 1 Z�/az 4 x 4 x 1 1/4 4.04 1"/sz 1"/sz 229/sz
1 1/2 x 1 1/2 x 3/4 0.45 /is /is 1 /sz Z5 Z5 ii 4 x 4 x 1 3.72 1 1 29/is
1 1/2 x 1 1/2 x 1/2 0.40 '/z '/z 1'/sz z 1/2 x 2 1/2 x 1 1.34 /sz /sz 1 /is
1 1/2 x 1 1/4 x 1 1/2 0.62 1�/sz 13/�s �s/az 21/2 x 21/2 x 3/4 1.34 25/sz 25/sz 113/�s 4 x 4 x 3/4 3.70 1 1 2"/is
31 3 31 2 1/2 x 2 1/2 x 1/2 1.34 Z5�32 Z5�32 2��8 4 x 3 x 4 �.�5 ZZ5�32 3��32 2���32
1 1/2 x 1 1/4 x 1 1/4 0.62 /az 1 /az /az Zi 3 zi 4 x 3 x 3 5.03 2'/sz Z15/sz 215/sz
1 1/2 x 1 1/4 x 1 0.51 25/az 1 1�/sz Z 1/2 x 2 x 21/2 1.99 1 /sz 2/sz 1 /az
1 1/2 x 1 1/4 x 3/4 0.49 ��/�s 13/is 1'/az 2 1/2 x 2 x Z 1.95 1'�/sz 15/a 123/sz 4 x 3 x 2 1/2 5.04 2�/s2 215/sz 2�s/az
1 1/2 x 1 1/4 x 1/2 0.41 '/z 25�32 1'/sz Z 1/2 x 2 x 1 1/2 1.57 13/sz 213/sz 1z�/s2 4 x 3 x 2 5.87 1'S/sz 13'/sz 2'/is
1 1/2 x 1 x 1 1/2 0.59 1�/az 1"/az 29/az z 1/2 x 2 x 1 1/4 1.57 13/sz 1'g/sz 1 z7/sz 4 x 2 1/2 x 4 7.19 2z5/sz 3'S/az 2Z'/sz
1 1/2 x 1 x 1 1/4 0.63 29/az 1�/s 1'/is Z 1/2 x 2 x 1 1.40 z5/sz 19/sz 13/a 4 x 2 x 4 7.08 225/sz 319/sz 227/sz
1 1/2 x 1 x 1 0.54 25/3z 1�/�s 1�/sz z 1/2 x 2 x 3/4 1.35 25/sz 19/sz 1 Z�/sz Continued on next page.
1 1/2 x 1 x 3/4 0.44 �'/ie 31/sz 15/is 2 1/2 x 1 1/2 x 1 1/2 1 J6 13/sz 113/sz 13/s
1 1/2 x 1 x 1/2 0.39 '/z 25�32 1'/sz z 1/2 x 1 1/4 x 2 1/2 2.40 1z1/sz Z�/�s 1z1/sz
1 1/2 x 3/4 x 1 1/2 0.62 1'/az 1�/is 1�/is Z 1/2 x 1 x 2 1/2 2.04 121/sz 2z3/az 1Z�/az
11/2x3/4x11/4 0.58 �s/az 1��/az 1'/is 21/2x3/4x21/2 2.00 1��/sz2"/�s1��/az
1 1/2 x 3/4 x 1 0.54 25/az 1�/a 1'/sz Z 1/2 x 1/2 x Z 1/2 2.46 1�/z 2�/sz 1�/z
1 1/2 x 3/4 x 3/4 0.47 ��/�s �3�32 29/3z Continues...
1 1/2 x 3/4 x 1/2 0.39 �/z 29/sz 31/az Consult price sheet for Made to Order items and
1 1/2 x 1/2 x 1 1/2 0.62 1'/az 113/az 3'/az for minimum order quantities.
Continues...
NIBCO INC.WORLD HEADQUARTERS•1516 MID�LEBURY ST•ELKHART,IN 46516-4740•USA•PH:1.800234.0227
: TECH SERVICES PH:1.888.446A226•FAX:1.888234.0557•INTERNATIONAL OFFICE PH:+1.574295.3327•FAX:+1.574295.3455
www.nibco.com
N 1 BCO . . .
�: � �; e ���„t�a _ ,
Co e r Wate r Tu be �ont�nued
pp
� � � � � � � � �
TYPE"M" Hard Drawn Only: 20-ft.(6.1 m)Straight Lengths
Usage: For general purpose plumbing,heating and
drainage installations.
Tolerances Hard Drawn
(Hard Drawn Only)
Outside Tubing OD Nominal Wall Weight Bursting Safe Working
Nominal Diameter Thickness Per Foot PressureA Pressuree
WaterTube Min. Max.
Size(In Inches) Inch (mm� Inch (mm) Inch (mm� Inch (mm) Lb (kg) psi (bars) psi �bars)
1/4 D.375 (9.53) 0.373 (9.47) 0.376 (9.55) N/A N/A N/A N/A N/A N/A N/A N/A
3/8 0.500 (12J0) 0.497 (12.62) 0.501 (12J3) 0.025 (0.64) 0.145 (0.07) N/A N/A 855 �59�
1/2 0.625 (15.88� 0.622 (15.80) 0.626 (15.90) 0.028 (OJ1) 0.204 (0.09) 6135 (423) 741 (51)
5/8 OJ50 (19.05� OJ47 (18.97) OJ51 (19.08) N/A N/A N/A N/A N/A N/A N/A N/A
3/4 0.875 (2223) 0.872 (22.15) 0.876 (2225) 0.032 (0.81� 0.328 (0.15) 4717 (325) 611 �42�
1 1.125 (28.58) 1.122 (28.50� 1.127 (28.63) 0.035 (0.89) 0.465 (021) 3865 (266) 506 (35)
11/4 1.375 (34.93� 1.372 (34.85) 1.377 (34.98) 0.042 (1.07) 0.682 (0.31) 3875 (267) 507 (35)
11/2 L625 �4128� 1.621 (41.17) 1.627 (41.33) 0.049 (124) 0.940 (0.43) 3550 (245) 497 �34�
2 2.125 (53.98) 2.121 (53.87� 2.127 (54.03) 0.058 (1.47) 1.460 (0.66) 2935 (202) 448 (31)
21/2 2.625 (66.68) 2.621 (66.57) 2.627 (66J3) 0.065 (1.65) 2.030 (0.92) 2800 (193) 411 (28)
3 3.125 (79.38) 3.121 (79.27� 3.127 (79.43) 0.072 (1.831 2.680 (L22) 2665 (184) 380 (26)
31/2 3.625 �92.08� 3.621 (91.97) 3.627 �92.13) 0.083 (2.11) 3.580 (1.62) N/A N/A 378 �26�
4 4.125 (104.78) 4.121 (104.67) 4.127 (104.83) 0.095 (2.41) 4.660 (2.11) 2215 (153� 377 �26�
5 5.125 (130.18) 5.121 (130.07) 5.127 (13023) 0.109 (2.77) 6.660 (3.02) 2490 (172) 349 (24)
6 6.125 (155.58� 6.121 (155.47) 6.127 (155.63) 0.122 (3.10) 8.920 (4.05) 2000 (138) 328 (23)
8 8.125 (206.38) 8.119 (20622) 8.127 (206.43) 0.170 (4.32) 16.500 (7.48) 2285 (158) 344 �24�
10 10.125 (257.18) 10.119 (257.02) 10.127 (25723) 0212 (5.38) 25.600 (11.61� N/A N/A 344 �24�
12 12.125 (307.98) 12.119 (307.82) 12.127 (308.03) 0.254 (6.45) 36J00 (16.65) N/A N/A 345 (24)
Note:Information and data contained in these charts,as taken from ASTM Specifications B 88.
Aated intemal pressure for copper water tube based on the strength of the tube alone and
applicable to systems using suitable mechanical joints.
aBased on actual la6oratory test data provided by Copper Development Association,Inc.
�Based upon 150°F(65.6°C)with an allowable stress of 9500 psi 1668 kPa�.
U.S.customary units in this document are the standard;the metric units are provided for
reference only.The values statetl in each system are not exact equivalents.
NIBCO INC.WORLD HEADQUARTERS•1516 MID�LEBURY ST•ELKHART,IN 46516-4740•USA•PH:1.800234.0227
TECH SERVICES PH:1.888.446A226•FAX:1.888234.0557•INTERNATIONAL OFFICE PH:+1.574295.3327•FAX:+1.574295.3455 ��
www.nibco.com
N 1 BCO . . .
�: � �; e ���„t�a _ ,
Co e r Wate r Tu be �ont�nued
pp
� • � � � � � � � � � � �
Commercially Available Lengths
Tube Type Color Code Standard Application Nominal or Standard Sizes Drawn Annealed
Type K Green ASTM B 88 Domestic Water Service Distri6ution Straight Lengths: '/a-inch to 8-inch 20 ft.(6.1 m) 20 ft.(6.1 m)
Fire Protection 10-inch 18 ft(5.5m) 18 ft.(5.5m)
Solar 12-inch 12 ft(3Jm) 12 ft(3Jm)
Fuel/Fuel Oil Coils: '/4-inch to 1-inch — 60 ft(18.3m)
HVAC — 100 ft(30.5m)
Snow Melting P/4-inch&1'/z-inch — 60 ft(18.3m)
2-inch — 40 ft�12.2m)
— 45 ft(13Jm)
Type L Blue ASTM B 88 Domestic Water Service Distribution Straight Lengths: '/n-inch to 10-inch 20 ft(6.1 m) 20 ft.(6.1 m)
Fire Protection 12-inch 18 ft.(5.5m) 18 ft.(5.5m)
Solar
Fuel/Fuel Oil
Natural Gas Coils: '/4-inch to 1-inch — 60 ft.(18.3m)
Liquified Petroleum(LP)Gas — 100 ft.(30.5m)
HVAC 1'/4-inch&1'/z-inch — 60 ft(18.3m)
Snow Melting 2-inch — 40 ft(12.2m)
— 45 ft(13Jm)
X Type M Red ASTM B 88 Domestic Water Service Distribution Straight Lengths: '/u-inch to 12-inch 20 ft.(6.1 m) N/A
Fire Protection
Solar
Fuel/Fuel Oil
HVAC
Snow Melting
DWV Yellow ASTM B 306 Drain Straight Lengths: 1'/4-inch to 8-inch 20 ft(6.1 m) N/A
Waste
Vent
HVAC
Solar
ACR Blue ASTM B 280 Air Conditioning Straight Lengths: '/a-inch to 4'/e-inch 20 ft(6.1 m) 20 ft(6.1 m�'
Refrigeration
Natural Gas Coils: '/e-inch to 15/e-inch — 50 ft(15.3m�'
Liquified Petroleum(lP)Gas
OXY Type K ASTM B 819 Medical Gas Straight Lengths: '/a-inch to 8-inch 20 ft(6.1 m) N/A
MED Green
OXY/MED
OXY/ACR Type L
ACA/MED Blue
Type G Yellow ASTM B 837 Natural Gas Straight Lengths: 3/e-inch to P/e-inch 12 ft.(3Jm) 12 ft(3Jm�'
Liquified Petroleum(LP�Gas 20 ft.(6.1 m) 20 ft(6.1 m�'
Coils: '/e-inch to'/a-inch — 60 ft.(18.3m�'
— 100 ft.(30.5m�'
'Available as special order only.
U.S.customary units in this document are the standard;the metric units are provided for
reference only.The values statetl in each system are not exact equivalents.
NIBCO INC.WORLD HEADQUARTERS•1516 MID�LEBURY ST•ELKHART,IN 46516-4740•USA•PH:1.800234.0227
TECH SERVICES PH:1.888.446A226•FAX:1.888234.0557•INTERNATIONAL OFFICE PH:+1.574295.3327•FAX:+1.574295.3455 :
www.nibco.com
� � . . f• t• t•
�
. � . � �, — � • 11
Fig. 20 - Standard Pipe Strap
Fig. 20S - Flush Mount Pipe Strap
Data Table for Fig. 20S
Size Range— 1/2" thru 8" pipe
Material — Carbon Steel Dimensions •Weights
Function — Recommended for supporting pipe P�pe q B C D Hole Max. Rec. Approx.
Sizes Size Load Lbs. Wt./100
with fittings vertically or horizontally to walls or 1/2 4�/8 5/16 2�/8 3/4 7/16 410 21
ceiling. Fig. 20S will support pipe flush with 3/4 45/,6 7/16 3 15/16 7/16 410 24
mounting surface. 1 49/,6 9/16 33/8 1�/8 7/16 410 26
Approvals — Conforms to Federal Specification 1'/4 415/,6 11/16 33/4 1'/z 7/16 410 30
WW-H-171 E, Type 26 and Manufacturers 1�/z 53/,6 13/16 4�/4 15/8 7/16 410 33
Standardization Society SP-69, Type 26. 2 53/4 1�/,6 43/4 2�/4 7/16 410 38
2'/z 6'/4 19/,6 5'/, 23/, 7/16 610 102
Finish — Plain 3 6�/8 15/8 5�/8 33/8 7/16 610 118
Note—Available in Electro-Galvanized and HDG 3�/z 73/8 1�/8 63/8 3�/8 7/16 610 130
finish or Stainless Steel materials. 4 83/8 2�/8 7 43/8 9/16 725 159
Order By— Figure number, pipe size, material 5 9�/,6 25/8 7'/8 53/8 9/16 725 191
and finish 6 10�/� 33/,6 8'/8 6�/,6 9/16 725 234
8 14 4'/, 11'/Z 83/8 11/16 900 446
Data Table for Fig. 20
Dimensions •Weights ��.��
Pipe Hole Max. Rec. Approx. _ __ �
Sizes p` B C D Size Load Lbs. Wt./100 �`� =�d
1/2 3'/8 3/4 3'/,6 15/3z 7/16 410 16 ' '�`� �'�� �
3/4 4 13/16 3'/8 15/,6 7/16 410 21 '' � C ��• �
1 49/,6 7/8 3'/8 1 VZ 7/16 410 26 ,#� -�. �` a
1'/, 415/,6 1 3'/, 1'/8 7/16 410 30 �--��'� �•- -'`'�
1
1'/2 53/,s 13/,6 4'/, 2'/8 7/16 410 33 '��-.� �'.
2 53/a 1'/,6 4'/4 25/8 7/16 410 38 ^,. "`--� � �
�
2'/z 6'/4 1"/,6 5'/, 3'/8 7/16 610 102 �-`� �'
3 6'/a 2 5'/8 33/, 7/16 610 118
3'/z 73I8 2'/4 6'/8 4'/4 7/16 610 130 �-
4 83/8 2'/z 7 43/, 9/16 725 159 ., ',5I4
5 9'/,6 3'/,6 7'/8 5"/,6 9/16 725 191 �`°;��.._���
6 10'/z 35/s 8'/8 6'/8 9/16 725 234 �`-
8 14 45/8 11'/z 9 11/16 900 446
Fig. 21 - "Tin Strap"
Size Range— 1/2" thru 2" pipe _
Material — Carbon Steel ` t� �
Function — Light duty strap that attaches pipe or copper
tubing to horizontal or vertical structure. �--�����'�
I �
Finish — Pre-Galvanized � ,r'� �
Note—Available with felt lining, order TOLCOT"' Fig. 21 F. a � ' �
Order By— Figure number and pipe size �
�:..:.
G �
����
�-�.�-
� MainCffice/ManufacturingFacility•1375S�rrpsonAve.•(brore,CA 92879•Fh: 909.737.5599•Fax 909.737.0330
• CUstomer Servi ce•800.786.5266
www.tolco.com
� TOLCO
a brand of NIBCO Revision 5/24/2001
F� Fig. 200
��� "Trimline"Adjustable Band Hanger
Size Range— 1/2 thru 8 inch pipe.
Material—Carbon Steel, Mil. Galvanized to G-90
specifications.
Function— For fire sprinkler and other general piping �
purposes. Knurled swivel nut design permits hanger �� �'�
adjustment after installation. ;' �
Features �' B !�� B %� ��
• (1/2 thru 2 inch) Flared edges ease installation for all ;� %�
pipe types and protect CPVC plastic pipe from q A
abrasion. Captured design keeps adjusting nut from
separating with hanger. Hanger is easily installed
around pipe.
• (2-1/2 thru 8 inch) Spring tension on nut holds it
securely in hanger before installation. Adjusting nut is
easily removed.
1/2 THRU 2 INCH PIPE 2 1/2 THRU 8 INCH PIPE
Approvals— Underwriters' Laboratories Listed (1/2"
thru 8") in the U.S. (UL) and Canada (cUL)for steel
and CPVC plastic pipe and Factory Mutual
Engineering Approved (3/4"thru 8"). Conforms to
Federal Specifications WW-H-171 E, Type 10, and �r
Manufacturers Standardization Society SP-69, type 10. �
Maximum Temperature-650°F. i;l
Finish— Mil. Galvanized, for Stainless Steel materials �
order TOLCOT"' Fig. 200WON.
OrderBy— Figure number and pipe size.
+
p Rod Size Max. Rec. Approx.
Pi e Size Inch Metric* B Load bs. Wt./100
1/2 3/8 8mm or 10mm 3-1/8 2-5/8 400 11
3/4 3/8 8mm or 10mm 3-1/8 2-1/2 400 11
1 3/8 8mm or 10mm 3-3/8 2-5/8 400 12
1-1/4 3/8 8mm or 10mm 3-3/4 2-7/8 400 13
1-1/2 3/8 8mm or 10mm 3-7/8 2-7/8 400 14
2 3/8 8mm or 10mm 4-1/2 3 400 15
2-1/2 3/8 10mm 5-5/8 4-1/8 600 27
3 3/8 10mm 5-7/8 4 600 29
3-1/2 3/8 10mm 7-3/8 5-1/4 600 34
4 3/8 10mm 7-3/8 5 1000 35
5 1/2 12mm 9-1/8 6-1/4 1250 66
6 1/2 12mm 10-1/8 6-3/4 1250 73
8 1/2 12mm 13-1/8 8-3/4 1250 136
*Order Fig. 200M
Main Office/Manufacturing Facility•1375 Sampson Ave.• Corona,CA 92870• Ph: 909.737.5599• Fax: 909.737.0330 �
Distribution Center• 8790 Fruitridge Road• Sacramento,CA 95826• Ph: 916.388.7800• Fax: 916.388.1401
Manufacturing Facility•4851 Homestead Road,Bldg.118• Houston,TX 77028• Ph: 713.672.0058• Fax: 713.672.0074
www.tolco.com
0
i • � • � •
� � � � • • • � �' • � • �- � ��� . � �
�
Not less than 2"nominal width — PCOdUCt F@BfUC@S •
(1-1/2")up to 3-112"pipe;not less than ���—�
s���2-vz°�nom'�oai W�atn a��a s°p�pe � j •No pre-drilling required.
_ . ._ .. �► �
– / RoorJosi � ,,
( Minimum 2-112"from bottom for , •Quick to install using the Sammy
branch lines.Minimum 3"from
" Nut Driver with an 18V cordless
� bottomformainllnes.Exception-This dfl���dflVOf.
requirement shall not apply to 2"or
/ thicker nailing strips resting on top of
/ steel beams. •Saves time from traditional
, � methods.
•Reduces installation cost. �
�� •Made in the U.S.A. •
li �� -
-- �� � ..
� � �
r---
--� . ��
^� �j,'%
— /
/
:� ���
�
� � � •
1l4" 8018957 SWG 100 11A x 1" 622 (Fir) 25 125
1/4" 8019957 SWG 200 114 x 2" 1725 (Fir) 25 125
°�= 3/8" 8020957 SWG 10 114 x 1" 622 (Fir) 300 25 125 �
����, 318" 8021957 SW�20 114 x 2" 1725 (Fir) 1050 25 125
�� 3/S" 8073925 SWG 20-SS 114 x 2" 1725 (Fir) 850 25 125
#14 SW Red O� 3/8" 8022925 SWG 25-380 3l8 x 2-112" 2249 (Fir) 1500 25 125
Nut Driver 3/8" 8023925 SWG 30 114 x 3" 1884 (Fir) 25 125
Part#8114910
•' • -
1.Insert the appropriate nut driver into a 3/8"or 1/2"portable drill. 1.Insert the appropriate nut driver into a 3/8"or 1/2"portable drill.
�
2.Insert the SAMMYS into the#14(black)nut driver(p/n 8113910).Drill 2.Insert the SAMMYS into the#14SW(red)nut driver(p/n 8114910).With drill
should be in a vertical position. unit in a horizontal position and at a right angle to the structural member,
begin installation. �
3.Push the face of the nut driver tight to the member.When the
nut driver spins freely on the SAMMYS,stop drill and remove. 3.When the nut driver spins free on the SAMMYS,stop the drill and
remove.
4.The SAMMYS is now ready to receive 1/4';3/8", 1/2°or metric
all thread rod,bolt stock.(The 1/2"requires the#14SW red nut driver) 4.The unit is now ready to receive 1/4",3/8"or metric all thread rod or
bolt stock.
Note:When installing DSTR,follow the above instructions,
then add retainer nut and torque to 20 foot Ibs.for maximum Note:When installing SWDR,follow the above instructions,then add retainer nut
pullout in purlin steel, and torque to 20 foot Ibs.for maximum pullout in purlin steel. -
� � z
"v,� 3's c
�� (�' _ �,� � –���- �
• 7 1
„' i
�
SPECIAL NUT DRNER SYSTEM:The nut tlrivers were designed with a unique spin-off feature which provides a fast and safe installation each time.When the face of the driver comes into
contact with the material you are installing into,continue drilling until nut driver spins free.Installation is then complete.Warranty requires the use of the appropriate nut driver for installations.
� � . � � • • :11 : �
� � . . f• t• t•
�
. � . � �, — � • 11
Fig. 98 - Rod Stiffener ��,i
� =;
,=-;
Size Range — Secures 3/8" thru 7/8" hanger rod �=i
��=�_�_�-.
Material — Carbon Steel � ' �;=; � �:._
,�'!r�� i i::;'' r::.:
Function — Secures channel to hanger rod for vertical seismic bracing. �
,4� ���
Finish — Electro Galvanized <�.�,��.�!���.., ',,
Note—Available m HDG finish or Stainless Steel matenals. � �� `� � '� � �
Order By— Figure number - ,
', ,
I �
Fig. 99 - All Thread Rod Cut to Length
Size Range — Secures 3/8" thru 7/8" rod in Dimensions •Weights
1" increments Rod Max. Rec. Load Lbs.
Material —Carbon Steel Size For Service Temps
Maximum Temperature—750°F 650°F 750°F
Finish — Plain 3/8 610 540
1/2 1130 1010
Note—Available in Electro-Galvanized and 5/8 1810 1610
HDG finish or Stainless Steel materials. 3/4 2��0 2420
Order By— Figure number, rod diameter, rod �l$ 3��0 3360
length and finish
Fig. 100 - All Thread Rod Full Lengths
Size Range — Secures 3/8" thru 7/8" rod in
10' lengths
Material —Carbon Steel
�;�;
Maximum Temperature— 750°F �° •�`����
Finish — Plain � ����{: �
Note—Available in Electro-Galvanized and ��� '!r`,r
��(�f t�'`�f:��,';�..
HDG finish or Stainless Steel materials. �� '1 r`��. _
�.
Order B Fi ure number, rod diameter �� F'�f'���
and finish g �����{``-�
�,f,{_��r
}�y�
l f!"f��
Dimensions •Weights ��s-:
�,,r�;.
Max Rec. Load Lbs. r��
Rod For Service Temps Approx. ��,��
Size 650°F 750°F Wt./100
1/4 240 215 12
3/8 610 540 29
1/2 1130 1010 53
5/8 1810 1610 84
3/4 2710 2420 123
7/8 3770 3360 169
1 4960 4420 222
1'/, 8000 7140 360
1'/z 11630 10370 510
MainCffice/ManufacturingFacility•1375S�rrpsonAve.•(brore,CA 92879•Fh: 909.737.5599•Fax 909.737.0330
•� CUstomer Servi ce•800.786.5266
www.tolco.com
ES-F-860S
� • FEBCO�
Series 860 - � �� �� �
� � __ - � �:�
Reduced Pressure Zone Assemblies � � ��� � ' �
� -- r ��'�a s�
� �
. � _ �.. .
Size: '/z" - 2" (15mm - 50mm) `� � _
Series 860 '�;�'.
The FEBCO Series 860 Reduced Pressure Zone Assemblies are designed
for use in health-hazard applications.
End Connections—NPT ANSI/ASME B1.20.1 Capacity
Pressure—Temperature kP2 25 v2�(15mm)
Max.Working Pressure: 175psi(12.1 bar) y �sa zo
HydrostaticTest Press: 350psi(24.1 bar) J '03 'S
i 69 10
Temperature Range: 32°F to 140°F(0°C to 60°C) 3a 5
0 3 6 9 12 15 18 gpm
Materials 0 11 22 34 45 57 681pm
Valve Body: Bronze kPa Ps� 3/;��2omm)
Elastomers: Silicone nz z5
Springs: Stainless Steel �as zo
103 15
Models = ss ,o
34 5
• Wye-Strainer 0 5 10 15 20 25 30 gpm
0 19 38 57 76 95 114 Ipm
Approvals— Standards kPa Ps� ���(25mm)
172 25
• ANSI/AWWA Conformance(C511) „ ias zo
• Approved by the Foundation for Cross-Connection Control and Hydraulic J io3 i5
Research at the University of Southern California. � ss io
34 5
0 10 20 30 40 50 60 gpm
�SJ�+ S P� 0 38 76 114 151 190 227 Ipm
1013 B64.4 kPa ps' 1'/a"132mm)
172 25
Typical Installation N ,3$ zo
103 15
= 69 10
Series 860'/z"-2"(15-50mm) 34 5
Outdoor Installation o zo ao so so ioo 120 gpm
0 76 151 227 304 379 454 Ipm
1 kPa psi 1�/z'(40mm)
12"(300mm)Minimum »Z 25
Clearance „ �3a 2o
� to Fixed Structure � ios i5
e e a
I ss io
�\ o b 1 0 �� 1 34 5
� 1 0 20 40 60 80 100 120gpm
0 76 151 227 304 379 4541pm
kPa psi Z"(50mm)
F�°w � � nz z5
6"Min.(150mm) „ isa za
J 103 15
i 69 10
IMPORTANT:INQUIRE WITH GOVERNING AUTHORITIES 3a 5
FOR LOCAL INSTALLATION REQUIREMENTS o so so so �20 �50 180 gpm
0 114 227 342 454 570 681 Ipm
Job Name Contractor
Job Location Approval
Engineer Contractor's P.O. No.
Approval Representative
FEBCO product specifications in U.S.customary units and metric are approximate and are provided for reference only. For precise mea-
surements,please contact FEBCO. FEBCO reserves the right to change or modify product design,construction,specifications,or materials
without prior notice and without incurring any obligation to make such changes and modifications on FEBCO products previously or subse-
quently sold.
Series 860 / Size: '/z" - 2" (15mm - 50mm)
11 2 6.1 8 2.2 6 7 ITEM DESCRIPTION MATERIALS
1 Body Bronze
1.2 Tailpiece Bronze
@ 1.4 0-Ring Silicone
pe 8 _ � 2 Cover Bronze
= 2.2 0-Ring Silicone
; - - 3 Seat Noryl°
3.1 0-Ring Siiicone
� 4 Poppet Noryl°
5 Seat Disc Siiicone Rubber
_ _ 5.1 Disc Retainer Noryl°
5.2 Rnd HD Screw Phillips, 18-8 SS
; 6 Spring SS
E � 6.1 Spring SS
5.2 3 5.1 5 6 1.4 4 � Guide Noryl°
8 Retainer Spacer Noryl°
3.1 9 BaII Valve Bronze
9.1 BaII Valve Bronze
11 Test Cock Bronze
12 Seat Ring-RV Noryl°
____________________________A.______________________________________ 12.1 Gasket Ring-RV Silicone Rubber
g 1 21 60 61 1.2 g.1 13 Spring-RV SS
14 Seat Disc-RV Silicone Rubber/SS
15 Diaphragm-RV Rubber/Fabric
� + + - 16 Outer Diaphragm-RV Rubber/Fabric
� 0 17 Small Piston-RV Noryl°
17.1 Rnd HD Screw Phillips, 18-8 SS
+ + + � 172 Washer 18-8 SS
173 Hex Nut 18-8 SS
� 18 Cylinder-RV Brass
B ° ° 18.1 Slip Ring-Cylinder Acetal
; � � - 18.2 Siide(Plug) Nylon
19 Cover-RV Bronze
21 20 0-Ring Silicone
21 Hex HD Capscrew 18-8 SS
22 Large Piston-RV Noryl°
Relief Valve Assembly Check Assembly 23 Guide-RV Noryl°
60 Identification Plate Brass
e.i 5 a � 61 Drive Screw Stick SS
zo �.�
,�., n.2 ,�.s 52 Note:The gap drain is not designed to catch the maximum discharge pos-
'$' '` sible from the relief valve.The installation of FEBCO air gap with the drain
,8.2 23 line terminating above a floor drain will handle any normal discharge or nui-
' ;�. � �,?,>> � �� sance spitting through the relief valve. However,floor drain size may need
18 � 14 to be designed to prevent water damage caused by a catastrophic failure
\ a (s.i) s s., condition. Do not reduce the size of the drain line from the air gap fitting.
17 �6 19 18.1 15 22 13 �
Dimensions-Weights
Size:'/z"-2" (15-50mm)
SIZE(DN) DIMENSIONS WEIGHT
A B C D E
in. mm in. mm in. mm in. mm in. mm in. mm Ibs. kgs.
%z 15 10 254 1Yz 38 1Yz 38 3'/a 79 3'/z 89 5.6 2.5
3/n 20 103/a 273 1Yz 38 1Yz 38 3'/a 79 3Yz 89 5.8 2.6
1 25 12%z 318 1'/a 48 15/a 41 33/a 86 35/s 92 9.2 4.2
1Yn 32 15'/s 403 3 76 2Yz 64 4'/a 108 55/s 143 20.2 9.2
1Yz 40 163/s 416 3 76 2Yz 64 4Ya 108 55/a 143 20.6 9.4
2 50 175/s 450 3'/z 89 2Yz 64 4'/a 108 55/a 143 24.8 11.3
Note:Dimensions are nominal.Allowances must be made for normal manufacturing tolerances.
: •
FEBCO
��V% � 9001-2000
� CERTIFIED
A Watts Water Technologies Company USA: 4381 N.Brawley•Ste.102•Fresno,CA•93722•Tel.(559)441-5300•Fax:(559)441-5301 •www.FEBCOonline.com
Canada: 5435 North Service Rd.•Burlington,ONT. •L7L 5H7•Tel.(905)332-4090•Fax:(905)332-7068• www.FEBCOonline.ca
ES-F-860S 0814 O 2009 FEBCO
0
• • - 11
o . ..
-. ..
-. .
� r__.
.� �
.
� APPLICATION
;�:; Designed for installation on potable water lines to reduce
- high inlet pressure to a lower outlet pressure. The high
" �� :� " flow capacity makes this device most suitable for industrial
� ari �-��_.
�,_ _ , } �k� water lines and commercial irrigation systems. The direct
– acting integral by-pass design prevents buildup of exces-
FEATURES sive system pressure caused by thermal expansion. The
Sizes: 1/2" 3/4" 1" 1 1/4" balanced piston design enables the regulator to react in a
1 1/2" 2" 2 1/2" 3" smooth and responsive manner to changes in system flow
Maximum working water pressure 300 psi demand, while at the same time, providing protection from
Maximum working water temperature 140° F inlet pressure changes.
Reduced pressure range 25 psi to 75 psi STANDARDS COMPLIANCE
Factory preset (field set 2 1/2" & 3") 50 psi
Threaded connections (FNPT) ANSI B1.20.1 ASSEO Listed 1003 (1/2" thru 2 1/2" )
Copper connections (FC) ANSI B 16.22 p IAPMOO Listed (1/2"thru 2" )
CPVC tailpiece: Max. hot water temp. 140°F @ 100 psi
Cold water rated temp. 73.4°F @ 400 psi City of Los Angeles Approved (1/2"thru 2 1/2")
OPTIONS (Suffixes can be combined) CSAO Certified (1/2"thru 2")
- standard with single union FNPT inlet x FNPT
outlet(1/2"thru 2")and less union (21/2"&3") MATERIALS
C - copper sweat connection (1/2"thru 2") Main valve body Cast bronze ASTM B 584
HR - 75 psi to 125 psi spring range, factory set Access covers Cast bronze ASTM B 584
at 85 psi (field set 2 1/2" & 3") Brass ASTM B 16
HLR - 10 psi to 125 psi spring range, factory set Fasteners Stainless steel, 300 series
at 50 psi Stem & plunger Cast bronze ASTM B 584
HTSTSC- 180°F inaximum temp, stainless steel trim, Brass ASTM B 16
spring, sealed cage Elastomers Buna Nitrile (FDA approved)
L - less integral by-pass check valve (3/4"-2") EPDM (FDA approved)
LPV - 180°F inaximum temp with 10 psi to 35 psi Cap gaskets Natural vulcanized fibre
spring range, factory set at 20 psi Acetal (DelrinT"' 500), NSF Listed
LPC - 140°F inaximum temp with 10 psi to 35 psi Springs Oil tempered wire,ASTM A 229
spring range, factory set at 20 psi Seat Stainless steel, 300 series
SC - sealed cage bell housing and stainless steel p
adjustment screw
SW - made for salt water service
YSBR - with bronze "Y" strainer on inlet
510 - 400 psi inlet rating and 75 psi to 125 psi
spring range, factory set at 85 psi
(field set 2 1/2" & 3") B
P - tapped and plugged for gauge
CPVC - CPVC tailpiece connection (3/4"-1") � �
ACCESSORIES � � � W�LKINS
Repair kit (rubber only) � �soo�
DIMENSIONS &WEIGHTS (do not include pkg.) A—��
SIZE DIMENSIONS(approximate) WEIGHT
CONNECTIONS A B C D
in. mm in. mm in. mm in. mm in. mm Ibs. kg.
1/2 15 SINGLE UNION 4 1/2 108 6 152 1 5/8 41 2 3/4 70 3 1.5
3/4 20 SINGLE UNION 4 5/8 118 6 152 1 1/8 29 2 3/4 70 4 2.0
1 25 SINGLE UNION 5 1/8 130 6 7/8 175 1 5/8 41 3 5/16 84 6 3.0
1 1/4 32 SINGLE UNION 6 5/16 160 7 1/4 184 1 3/4 45 4 102 7 3.0
1 1/2 40 SINGLE UNION 8 5/16 211 10 254 1 7/8 48 5 127 14 6.5
2 50 SINGLE UNION 9 1/2 241 10 3/4 273 2 1/8 54 6 1/2 165 20 9.0
2 1/2 65 LESS UNION 10 254 14 1/2 368 3 76 8 203 28 12.5
3 80 LESS UNION 11 1/8 283 16 406 3 1/2 89 8 203 44 20.0
�• •
- i�
Page 1 of 2 WILKINS a Zurn company, 1747 Commerce Way, Paso Robles,CA 93446 Phone:805/238-7100 Fax:805/238-5766
In Canada:ZURN INDUSTRIES LIMITED,3544 Nashua Dr.,Mississauga,Ontario L4V 1L2 Phone:905/405-8272 Fax:9051405-1292
Product Support Help Line: 1-877-BACKFLOW(1-877-222-5356) • Website: http://www.zurn.com
FLOW CHARACTERISTICS
MODEL 500 1/2"THRU 3" (STANDARD &METRIC)
FLOW RATES(I/s)
3.2 6.3 9.5 12.6 15.8 18.9
20 138
,--. 1/2" . 3/4" 1" 1 1/4" 1 1/2" 2" 2 1/2„ 3" -
� ,�5 75mm , (20mm 25mm 32mm 40mm SOmm 65mm SOmm 104
N �
a Q
LL 10 69 �
0 0
� 5 35 �
� 0 . a
0 50 100 150 200 250 300
"Flow curves are based on a FLOW RATES(GPM)
50 psi pressure differential"
TYPICAL INSTALLATION
Local codes shall govern installation requirements. Unless otherwise specified, the assembly shall be mounted in ac-
cordance with the manufacturers' instructions and the latest edition of the Uniform Plumbing Code. The assembly shall
be installed with sufficient side clearance for testing and maintenance. The Model 500 may be installed in any position.
If installed in a pit or vault, specify the "SC" sealed cage option. Multiple installations are recommend for wide demand
variations or where the desired pressure reduction is more than 4 to 1 (i.e.: 200 psi inlet reduced to 50 psi outlet).
CAUTION:Anytime a reducing valve is adjusted, a pressure gauge must be used downstream to verify correct pressure
setting. Do not bottom adjustment bolt on bell housing.
- � ��M��J�
_ � ���_���_���-���-
o iii-u�-�i�=ri
°�-_�! � ui=il=iTi=il-
MODEL 975XL2 0 �HI�'
cnuce---- � III�II�I���I�
RPZ BACKFLOW PREVENTER oPnoNn�arzessurze -- o III-111-1�'
I PROTECTIVE I o
MODEL850�� -
I =��'s>< ENCLOSURE sHUr-oFFVn�ve
II 0 �`� II II I
I �
_ = I OPTIONAL �f �� " �.. , _
I ° � I - I PRESSUREGAUGE �
I + I .
— �F j
MODEL DUXL � �' �!I�
DIELECTRIC UNION I 12"MIN. — I
I = 30"Max. _ � VERTICAL INSTALLATION
I I MODEL 500 TO HANDLE LOW
DEMANDS(SET @ 65 PSI) �
—
<?1VV�l� � � �i�� � �I I I °' _� I II��
lll��III�Ilf I�II'�I :=1I1=1 111=I11�Ilf
-1II-1II- III-1I 'III-III -1II-1II-
'=1 I I-1 I I I-1 I!- =1 I I-1 I I I-1 I 1='
'=111i �III: -111, iilll=�'
DIRECTION OF FLOW �
TYPICAL INSTALLATION
C �oos�
MODEL SOOFC TO HANDLE DIRECTION OF FLOW—�„
HIGH DEMANDS(SET @ 55 PSI)
BATTERY INSTALLATION
SPECIFICATIONS
The Pressure Reducing Valve shall consist of a bronze body and bell housing, a separate access cover for the plunger
and a bolt to adjust the downstream pressure. The bronze bell housing and access cap shall be threaded to the body
and shall not require the use of ferrous screws. The assembly shall be of the balanced piston design and shall reduce
pressure in both flow and no-flow conditions.The assembly shall be accessible for maintenance without having to remove
the body from the line. The Pressure Reducing Valve shall be a WILKINS Model 500.
WILKINS a Zurn company, 1747 Commerce Way,Paso Robles,CA 93446 Phone:805/238-7100 Fax:805/238-5766
IN CANADA:ZURN INDUSTRIES LIMITED,3544 Nashua Dr.,Mississauga,Ontario L4V 1 L2 Phone:905/405-8272 Fax:905/405-1292
Product Support Help Line: 1-877-BACKFLOW(1-877-222-5356) • Website:http://www.zurn.com
Page 2 of 2
� i • I �
� � �
, � o
. . . . . . .
• • .
� 0 � �
�
� a� ,_, � �
_�� ��
: �
� � � L ��
("
.
.. _ . �� .., � �1
9i:a:c �fl��
_ _ .. '_. ��'
__ _ �
s�,k.A��'n"4"�'��'.'F•�` tm+
_�yr�—'�"`��
• The AGF Manufacturing Inc. Model 1011A TESTnNDRAIN°matches all the features and benefits of our Model
1000 by providing both the test function and the express drain function in a multistory installation for a wet fire
sprinkler system, with the added feature of an integral Model 7000 Pressure Relief Valve with drainage piping.
• The Model 1011A complies with the requirements of NFPA-13 that stipulate a pressure relief valve be installed
on all gridded systems and downstream of all pressure reducing valves (see reverse).
• The Model 1011A TESTaNDRA1N° is a compact single handle ball valve which includes a tamper resistant
test orifice and integral tamper resistant sight glasses, and is 300 PSI rated.
• Available in a full range of sizes from 3/a" to 2" NPT and BSPT, with all specifiable orifice sizes 3/s" (2.8K), '/,s"
(4.21�, �/z" (5.6K), "/sz" (8.OK), 5/a" (11.2K, ELO), 3/a" (14.OK, ESFR), and K25 as required by NFPA 13, 2007 Edi-
tion (see reverse).
• The included UVFM Model 7000 Pressure Relief Valve features a flushing handle and is factory rated for 175
PSI. Other pressure settings are available and may be substituted.
• Designed to relieve excess system pressure caused by surges or temperature changes as well as solve the dif-
ficult problem of providing the relief valve with a convenient drainage-piping outlet.
• Shipped with relief valve and bypass drain ports plugged to expedite pressure testing the system.
• A locking kit is available and can be ordered with the valve to provide vandal resistance or prevent uninten-
tional alarm activation.
• Repair kits including (1) adapter gasket, (1) ball, (2)valve seats, (1) stem packing, and (1) stem washer are avail-
able for all TESTaNDRA1N°valves. Valve and orifice size must be specified when ordering.
NOTE: It is important to note that the pressure rating of the relief valve indicates an operating range of pressure for both opening and
closing of the valve. Standard relief valves are required to OPEN in a range of pressure between 90%and 105%of their rating.The valves
are required to CLOSE at a pressure above 80%of that rating.The relief valve should be installed where it is easily accessible for main-
tenance. Care should be taken that the relief valve CANNOT be isolated from the system when the system is operational.A relief valve
should NEVER have a shutoff valve or a plug downstream of its outlet.
� ' . • ' . 1 1 ' 1 1 . •
TESTANDRAIN is a registered trademark of AGF Manufacturing Inc. CS1011A 10/09
FOR SMALL PIPE VS R'S F
PPO�� VANE TYPE WATERFLOW
� The Symbol of Protection ALARM SWITCH WITH RETARD
UL,ULC,CSFM Listed and NYMEAAccepted,CE Marked
Service Pressure: Up to 250 PSI (17,2 BAR)
Minimum Flow Rate for Alarm: 8-10 GPM(30-38 Lpm)
�� ��% Maximum Surge: 18 FPS (10 m/s)
p�� , Enclosure: Die-cast, red enamel finish
�,_,.=:- Cover held in place with tamper resistant screws
Contact Ratings: Two sets of SPDT(Form C)
�� 15.0 Amps at 125/250 VAC
2.0 Amps at 30 VDC
Conduit Entrances: Two knockouts provided for 1/2"conduit.
� Usage: Listed plastic, copper and schedule 40 iron pipe.
Fits pipe sizes - 1" (25mm), 1 1/4" (32mm), 1 1/2"
(38mm) and 2" (50mm)
� °' Note: 12 paddles are furnished with each unit, one for
�
�,,. ;
= each pipe size of threaded and sweat TEE, one for 1"
` �, ,-' (25mm) CPVC, one for 1" (25mm) CPVC (Central),
- 4��_ ' '' ' one for 1 1/2" (38mm) polybutylene and one for 1 1/2"
` (38mm) threaded (Japan).
(CTS-Copper tubing size)
� � Environmental Specifications:
— • Suitable for indoor or outdoor use with factory installed
gasket and die-cast housing.
• NEMA 4/IP55 rated enclosure-use with appropriate conduit
fitting.
• Temperature range: 40° F to 120° F,4,5° C to 49° C)
Caution: This device is not intended for applications in
explosive environments.
Service Use:
StockNo.1113000 Automatic Sprinkler NFPA-13
U.S. Pat. No.3921989, Canadian Pat. No. 1009680 One or two family dwelling NFPA-13D
Residential occupancy up to four stories NFPA-13R
Other Patents Pending National Fire Alarm Code NFPA-72
Optional: Cover Tamper Switch Kit, Stock No. 0090018
The Model VSR-SF is a vane type waterflow switch for use on wet waterflow.
sprinkler systems that use 1" (25mm), 1 1/4" (32mm), 1 1/2" The vane must not rub the inside of the TEE or bind in any way.
(38mm) or 2" (50mm) pipe size. The unit may also be used as The stem should move freely when operated by hand.
a sectional waterflow detector on large systems.
The device can also be used in copper or plastic pipe installa-
The unit contains two single pole double throw snap action tions with the proper adapters so that the specified TEE fitting
switches and an adjustable, instantly recycling pneumatic re- may be installed on the pipe run.
tard.The switches are actuated when a flow of 8-10 gallons per
minute (30-38 Lpm) or more occurs downstream of the device. INSPECTIONANDTESTING: Checktheoperationoftheunitby
The flow condition must exist for a period of time necessary to opening the inspector's test valve at the end of the sprinkler line
overcome the selected retard period. or the drain and test connection,if an inspector's test valve is not
provided.
INSTALLATION: These devices may be mounted in horizontal
or vertical pipe. On horizontal pipe they should be installed on If there are no provisions for testing the operation of the flow
the top side of the pipe where they will be accessible. The units detection device on the system,application of the VSR-SF is not
should not be installed within 6"(15cm)of a valve,drain or fitting recommended or advisable
which changes the direction of the waterflow. The unit has a 1" The frequency of the inspection and testing and its associated
NPT bushing for threading into a non-corrosive TEE. See Fig. protective monitoring system should be in accordance with the
2 for proper TEE size, type and installation. applicable NFPA Codes and Standards and/or authority having
Screw the device into the TEE fitting as shown in Fig. 2. Care Jurisdiction (manufacturer recommends quarterly or more fre-
must be taken to properly orient the device for the direction of quently).
Potter Electric Signal Company•2081 Craig Road,St.Louis,MO,63146-4161 •Phone:800-325-3936/Canada 888-882-1833•www.pottersignal.com
PRINTED IN USA MKT.#8800003-REV X PAGE 1 OF 2
MFG.#5400802-12/01
FOR SMALL PIPE VS R�S F
PPO�� VANE TYPE WATERFLOW
� The Symbol of Protection ALARM SWITCH WITH RETARD
FIG. 1 0o NoT LEAVE COVER FIG. 2
pFF FOR E%TENOEO
Retard Adjustment: PER�oo oF r�Me
To change time, turn knob ��
(either direction) for desired / FLOW
y 1 11/16��APPROX.
time delay. Use the minimum Q (4,3mIm)
amount of retard necessary to MouNT so (REO)ENC�OM. �
prevent false alarms. A "B" ARROw ON
BUSHING (BLACK) N.C.
setting is usually adequate for POINTS IN —
this. Factory set at"B��. DIR�ATERFLOW � �� �
//� 1"NPT I \ DEPTH / I
�/n THREAOEO
�'\ FITTING ON
ALL SIZES
OIRECTION OF
WATER FLOW RUN OF THE
^ iEE MAY BE — — — — —
THRE40E0 OR
\"\ SWEAT TYPE
�1 i
DIRECTION oa nl �� Screw the device into the tee fitting as shown.Care must be taken to
wATERFLOw \\ properly orient the device for the direction of waterflow.On sweat tees,no
DWG. q737-31 � threaded bushings,inserts,or adapters are permitted,unless they comply
owc. peo2-ao with the dimensions listed in the chart below.
Important: Important-The depth to the inside bottom of the tee should have the
There are 12 paddles fur- caunoN:
TO PREVENT LEAKAGE APPLY TfFLON TAPE SEALANT following dimensions:
nished with each unit. One for TO MALE THREADS ONLY. DO NOT USE ANY OTHER
each size of threaded,sweat or TYPE OF LU6RiCnNT OR SEaIANT. APPROXIMATE DEPTH REOUIREMENT
plastic TEE as described Ill TEE SIZE THREADED SWEAT CTS, POLYBUTYLENE CPVC
Fig. 2. These paddles have APPRO%. RETARD SETTINGS ��r, sEC.�
raised lettering that shows the o n e c o e ��� * �" x �" z i/ie" i s/a" N�n z �/ie"
i e size and t e of TEE that ° 10-zs zo-ao 3s-ss so-�o 60-90 > >/4" x i i/a" x i" z �/ie" z 7/16" N/A N/n
P P YP i i�z" x i i/z" x i" z ii/ie" z i�a" z i/z" N/n
they are to be used with. The z" x z" xi" 3 3/16" 2 3/4" N/A N/n
proper paddle must be USeC�. DWG. {j735-33
The paddle must be properly
attached (see drawing) and
the screw that holds the pad-
dle must be securely tight-
ened.
SWITCH TERMINAL CONNECTIONS CLAMPING PLATETERMINAL
FIG. 3
��N�o�"'"G CAUTION:
� An uninsulated section of a single conductor should not be looped around
the terminal and serve as two separate connections. The wire must be
�s severed, thereby providing supervision of the connection in the event that
o�rG�N DwG. N923-3 the wire becomes dislodged from under the terminal.
FIG. 4 TYPICALELECTRICALCONNECTIONS FIG. 5
NoTES: To remove knockouts: Place
LOCAL BELL TRANSFORMER CLA55 8(STYLE B) 1. The model VSR-SF has two screwdriver at edge of knock-
OR BATTERY POwERED END-OF-LINE RESISTOR CKT.(SEE NOTE) $WltCrle$,one can be used to QUts, not in the center.
COM. COM.
OPEN ON ALARM OPEN ON CLOSE ON operate a central station�
CLOSE ON ALARM EOL
N.O. ALARM A��M RESISTOR proprietary or remote signal- �~�
Nc "o° "c ing unit, while the other is
used to operate a local au-
SIGNAUNG DEVICE SUPERVISEO LOOP(SEE NOTEJ
coM. dible or visual annunciator.
TYPICAL SWITCH ACTION TO ADD�L
COM. FROM OPEN ON CLOSE ON 2. For supervised C�rC.u�t$ $ee
OPEN ON CLOSE ON CONTROL A�RM ALARM DEVICES
f! oR RETURN "Switch Terminal Connec-
ALARM �a ALARM PANEL N.O.o y�N.C. TO CONTROL
N.O.�� N.C. �\ tions" drawing and caution
DwG. {�761-15 note(Fig.3). ° o
O � O
O
APPLICATION WARNING!
Due to the possibility of unintended discharges caused by pressure surges, trapped air, or short retard times,waterflow switches
that are monitoring wet pipe sprinkler systems should not be used as the sole initiating device to discharge AFFF, deluge, or
chemical suppression systems.
PRINTED IN USA MKT.#8800003-REV X PAGE 2 OF 2
MFG.#5400802-12/01
RBVS
P PO�� UNIVERSAL BALL
� The Symbol of Protection VALVE SWITCH
—��� UL and cUL Listed,FM,CSFM Approved
Dimensions: (including mounting clamps)
�s�R� Large Clamps: 6°L x 5"W x 5.2°H
- �— 15,2 cm L x 12,7 cm W x 13,2 cm H
_...
�`�' "''��" � Small Clamps: 6°L x 4"W x 5.2"H
I 5,2 cm L x I 0,2 cm W x 13,2 cm H
� Weight: With Large Clamps: 13.6 oz.(386,9 g.)
�� � - With Small Clamps: 11.0 oz.(311,2 g.)
'� �9 �' '� Enclosure: Non-Corrosive Compositc Material
, ', Environmental Limitations:
� • NEMA 4 rated enelosure when proper electrical
�i fittings are used.(IP67)
- • Temperahue range:-40°F to 150°F(-40°C to 65°C)
�!� • Not for use in hazardous locations
Housing Cover Tamper: Activated by housing cover removal
US Patent No.6,945,509 (Stock No. 1000035 only)
Contact Ratings:
SPDT Contacts: l0A at 125/250 VAC
RBVS Stock No. 1000040(w/o Cover Tamper) 2A at 30 VDC
RBVS-T Stock No. 1000035(w/Cover Tamper) SPDT Cover Tamper: 3A at 250 VAC
General installation On Lever Handle(See Fig.2)
The Model RBVS is designed to monitor tl�e fully open position of a ball valve �, Select clamps and clamping bolts based upon pipe/valve size,see Table 1.
installed iu a sprinkler system.The unit will fit on most ball valves installed on 2 Insert rubber clamp grippers into clamps,see Fig.2.
back-flow-preventers and alarm trim lines of dry,alarm,and deluge sprinkler 3. Place one clamp on top of pipe/ball valve near the valve handle and
valves.The switch operates if the ball valve I�andle is moved from the open insert clamping bolts through it.
position.However,the switch does not track the position of the handle or ball. 4. Place other clamp over clamping bolts from beneath the installation and
When the ball valve handle is in the open position,a spring-loaded switch button thread hex nuts onto thc clamping bolts,Uut do not fully tighten,(be sure
will contact the valve handle.When the I�andle is moved from d�e open position, hex nuts seat properly in clamp hex recesscs).(NOTE:Some installations
this switch button extends to the tripped position,and the RBVS contacts change may require one of the mounting bolts to be inserted from the bottom of
state,thereby opening or dosing a circuit.A covertamper switcl�is available and the brackets and then trimmed to allow the extension bracket to elear.
is activated by the removal of the RBVS housing cover.If an attempt is made See Fig.4)
to remove the RBVS by the removal of the moimting brackets,the unit will be 5. Attach extension bracket(if necessary to use for positioning)to top clamp
set into the tripped mode Uy this action. using'/4-20 X 3/d'Hex bolt aud washer,but do not fully tighten.
The RBVS can be mounted to the hex portion of the ball valve or back-flow- 6. Attach°L"brackct(RBVS switch enclosure is looscly attachcd to°L"
preventerorto the adjoining pipe via two clamps.The RBVS is shippedwith two bracket)to extension brad<et using%4-20 X 3/4°Hex bolt and washer,but
sets of mounting clamps to accommodate various pipe and vabe sizes,refer to do not fully tighten.
Table l.An°L"shaped and offset bracket for mounting tl�e switch endosure and �� Be sure ball valve is in the fully open position.
8. Slide loose]y assembled RBV S switch encloslu-e to a position that permits
an exte»sion bracket add to tl�e mounting flexibility of the RBVS.See"Typical �e switch button to contact the valve handlc approximately I" from its
Mounting Diagram"and"installation and Operation"on following page. inside end.See Fig.1 for approximate location.Cut and remove Yhe plastic
Testing coating from the ball valve handle to allow the RBVS switch button to
The RBVS and its associated protective monitoring system should be tested contact(and be activated by)tl�e metal of the handle.
in accordance with applicable NFPA codes and standards and/or the authority 9. Tighten clamping screws alternately to an eventua130 in-Ibs.(miniinum)
having jurisdiction(manufacturer recommends quarterly or inore frequently). of torque.
10. Maintain position of switch enclosure ovcr valve handle and secure bolt
Fig1 Internal Components that holds the axtension bracket to the clamping assembly. It may be
NoRMn��v oPEN necessary to close valve to access this bolt.
ll. Position"L"bracket so that it contacts the back edge of the valve handle,and
NORMALLY CLOSED seciue its bolt.lt may be necessary to close valve to access this bolt.
coMMON � 12. With the actuator fully retracted,position RBVS switch enclosure to
� contact the valve handle squarely,see Fig. 1.
STRAW REUEF � � 13. With RBVS switch enclosure held squarely in contact with valve handlc,
swircH euTroN securely tighten the two tamper resistant screws on the backside of the
BLACK - N.O. ° LOCATION enclosure.
COVER RED - N.C.
TAMPER yyHITE - GOM ON HANDLE 14. (,'lOSO 3llC1 O�JOR Y110 ValVO YO Vel'1�OpeI'3YlOY1.T11e 3CYLlatOT'S110U1d 08Slly
�o retract when the valve handle is in the open position.
15. Fully open the valve.
Mourvr so 16. Remove the cover and wirc main switch and tam �,r switch if a licaUle.
SWITCH BUTTON PLASTIC COATING p pp
IS APPROX. 1" FROM REMOVED FROM �YefU��}'YOUYe Y1111p01'SW1YCIl Wtl'05 tlltOUfT}]SYC21T1 I'0�70t CIl81lT1eI lil SW1YC}1
HANDLE INSIDE END BALL VALVE HANDLE eriClOSlll'2.FUIIy Se3t t110 W1T2S 1Rt0 tlle�701tOTT1 Of tlle Cllalll101.S0e Fl�.1.
W SWITCH BUTTON 17. Re laCO RBVS SWItCIl 0riC10SUT0 COVOT 1llC1 SOCLll'el Yl Y8II COVeT SCTOW.
DWG //1086-1 CONTACT AREA P Y �
Potter Electric Signal Company,LLC•208]Craig Road,St.Louis,MO,63146-4161•Phone:800-325-3936/Canada 888-882-1833•www.pottersignal.com
PRINTLD IN USA MPQ#5401086-RGV U PAG�1 OF 2
5/08
RBVS
P PO�� UNIVERSAL BALL
� The Symbol of Protection VALVE SWITCH
Fig.2 Typical Mounting Diagram Table 1 Clamp Sizing
� �ENCrH Pipe Valve/Size Clamp Clamping Bolts
6"
SwircN 1/2"to 3/4"(12,5 to 19mm) Small 10-32 x 2 1/2
� Ervc�osuRE � 1"to 2"(25 to SOmm) Large 1/4-20 x 4"
�
°L" BRACKET
� HEIGHT Switch Terminal Connections,Clamping Plate Terminal
0 5.2.'
EXT. BRACKET
(IF NECESSARY) � �CO���� A CAUTI O N
CLAMPS O �� Anuninsulatedsectionofsingleconductor
should not Ue looped around the terminal
�d and serve as two seperatf;connections.The
C�AMP o���o� °"'0"'''' wire must be severcd,thereby providing
GRiPPERS supervision ofthe connection in the event
W I DTH
4" (SMALL� that the wirc becomcs dislodged from
DWG #1086-2 5° (LARGE) under the terminal.
Typical Electrical Connections
LOCAL CIRCUIT
TRANSFORMER OR BATTERY POWER STYLE D (CLASS A) SUPERVISED LOOP STYLE B (CLASS 6) SUPERVISED CIRCUIT
�Ny.c-.
° SIGNALING COM. CDM, i0 N.C.
N.O. DEVICE N.O. N.O. CONTROL COM. END-OF-LWE RESISTOR
UNIT N 4
N.C. � N.C. /� DWG. k1086-4
Tamper Switch Connections Fig.3
COVER TAMPER & RBVS CONNECTED COVER TAMPER & RBVS WIRED swrtcH cmc�osuae
TO THE SAME ZONE ON THE FACP TO SEPERATE ZONES
COVEft
TAMPER �
COM. N.O.COM. � OFFSEi BRACKET
COM. N.O. COM.
FACP COVER EOLR N.C.
TAMPER FA�P EOLR FpC�EOLR �
N 0.
OwG.a1086-5 � �
Installation on Tee Handle(See F+ig.3) � �� �
1. Select clamps and clamping bolts based upon pipe/valve size,see Table 1. ` ef�c�E� �
2. Insert rubber clamp grippers into clamps,Sec Fig.3.
3. Place one clamp on top ofpipe/ball valve near the valve handle and °`"��s
insert clamping bolts through it �
4. Place other clamp over clamping bolts fiom beneath the installation �aP E� ow�
Niaes-3
and thread hex nuts onto tl�e clamping bolts,but do not fully tighten,
(be sure hex nuts seat properly in clamp hex recesses).
5. Loosely attach °L" bracket to the 'bffset" bracket and "offset" Fig.4
brackEt to thc RBVS housing.
6. Be sure ball valve is in the fully open position.
7. Slide loosely assembled RBVS switch enclosure to a position that Ravs �
permits the switch button to contact the valve handle approximately � ,,�
1/2"from the end of the handle.Cut and remove the plastic coating �
from thc ball valve handle to allow thc RBV S switch button to contact
(and be activated by)the metal of the handle. �
8. Tighten clamping screws alternately and'/4-20 X 3/4"bolt to 30 in-lbs. a
(ininimum)of torque. some insrn��nT�o��s Mav
9. With tl�e valve handle fully open, slide the RBVS housing down cnosF iNrFaFeaFNCa
until the switch operates plus 1/8 inch.Tighten the screws holding BcTweeN MouNT��c eocTn��
OFFSFT RRACKFT.INSTAI,L BOLT
YIlO RBVS YO Y�70��O�SOY��b71C�C0t. PROMBOTTOMANDTRIMAS �'�P�
10.Remove the RBVS switch enclosure cover. Nrr:��eo rocoaizeci:
11. Close and open the valve to verify operation. The actuator should
easily retract up when the valve handle is in the open position.
12.Fully open the valve.
13.Wire�main switch and tamper switch(if applicable).Carefully route
tamper switch wires through strain relief channel in switch enclosure.
Fully seat the wires into the bottom of the channel.See Fig. 1. �wcu�oxb-e
l 4.Replace RBVS switch enclosure cover and securely tighten cover screw.
PRINTCD IN USA MPG.#5401086-RLV U PAGE 2 OP 2
5/08
ii • I �
� � � � � 1
� � � � � � � �
�� �
DIMENSIONS MODEL 'IO1'IA - FRONT VIEW
Orifice Size Available:3/s", �/ie", '/z", '�/s2", ELO(5/s")*, ESFR(3/a")�, &K25`" R A�
SIZE A B C D E F G H E --� �WLET
3 "
�9�16�� 11�2�� 23�16�� 35�g" 33�g" 113�16�� 49�16�� 63�8�� TO • � � �,
/4 (191 mm) (37.5 mm) (57 mm) (93 mm) (86 mm) (46 mm) (117 mm) (162.5 mm) DR� �
1 79/�s" 1�/z" 23/i s" 35/s" 33/a" 113�16�� 49/i s" 63/s" H � _° I o
(191 mm) (37.5 mm) (57 mm) (93 mm) (86 mm) (46 mm) (117 mm) (162.5 mm)
1�/a" 715/is" 1>>/is" 29/1s" 4�/a" 35/s" 115/�s" 59/is" 5�/2"
(201 mm) (43 mm) (65 mm) (108 mm) (91 mm) (51 mm) (141 mm) (192 mm)
11/z" 815/is" 113/�s" 3�/a" 5�/is" 3�/s" 25/a" 8�/a" 10�/a" MODEL 1O1'IA - PLAN VIEW
(227 mm) (45 mm) (81.5 mm) (127 mm) (99 mm) (67 mm) (207 mm) (274 mm)
2n $15�16�� 113�16�� .���4�� 5��16�� .3��8u `L5�8�� $��4�� 1���8�� �A�
(227 mm) (45 mm) (81.5 mm) (127 mm) (99 mm) (67 mm) (207 mm) (274 mm) �-�
`Available on 1�/a" to 2" size units only �'Available on 1�/z" and 2" size units only To 1 y �
DRAIN I
THE MODEL 1O11A PROVIDES ALL OF THE FOLLOWING... �—�I t
From the 2007 Edition of NFPA 13 1 � �
Chapter 8.16.2.4.1' Provisions shall be made to properly drain all parts of the system. �
Chapter 8.16.2.4.2 Drain connections, interior sectional or floor control valve(s)-
&8.16.2.4.3 shall be provided with a drain connection having a minimum size
as shown in Table 8.16.2.4.2. MATERIALS
Chapter 8.16.2.4.4 Drains shall discharge outside or to a drain capable of handling Handle: Steel
the flow of the drain. Stem: Rod Brass
Chapter A.8.17.4.2 (Wet Pipe System)test connection is permitted to terminate into Ball: C.P. Brass
a drain capable of accepting full flow... using an approved sight Body: Bronze
test connection containing a smooth bore corrosion-resistant Valve Seat: Impregnated Teflon°
orifice giving a flow equivalent to one sprinkler... Indicator Plate: Steel
Chapter 8.17.4.2.2 The test connection valve shall be readily accessible. Relief Valve: Bronze
Chapter 8.17.4.2.4 shall be permitted to be installed in any location... downstream Bypass Fittings: Brass
of the waterFlow alarm. Bypass Tubing: Nylobraid
Chapter 8.17.4.3.1 (Dry Pipe System)a trip test connection not less than 1" in
diameter,terminating in a smooth bore corrosion-resistant orifice, A►PFROVALS
to provide a flow equivalent to one sprinkler... UL and ULC Listed: (EX4019
Chapter 8.17.4.3.2 The trip test connection... with a shutoff valve and plug not less &EX4533)
than 1", at least one of which shall be brass. FM Approved
Chapter 7.1.2 -a gridded wet pipe system shall be provided with a relief valve NYC-BSA No. 720-87-SM
set to operate at 175 PSI or 10 PSI in excess of the maximum
system pressure,whichever is greater.
Chapter 8.16.1.2.3` A relief valve of not less than ih" in size shall be provided on the �,
discharge side of the pressure-reducing valve set to operate at a �
pressure not exceeding 175 PSI.
Chapter A.8.16.1.2.3 -consideration should be given to piping the discharge from the ��1�
(pressure reliefl valve MADE IN U.S.A.
� . • . .
AGF Manufacturing Inc. Job Name:
100 Quaker Lane, Malvern, PA 19355
, Phone:610-240-4900 Architect:
Fax:610-240-4906 Engineer:
www.testandrain.com
Contractor:
United Brass Works,Inc. -Item#Model 50-2",Model 50 Lift Check Valve http://ubw.thomasnet.com/printitem/fire-protection-products-lift-check-v...
United Brass Works, Inc.
714 South Main Street
Randleman, NC 27317 USA
Phone: 336-498-2661
Fax: 336-498-4267
To I I-free: 800-334-3035
Email: sales@ubw.com
Website: http://www.ubw.com
All Categories> Fire Protection Valves&Products>Fire Protection Products-Lift Check Valves>Model 50 Lift Check
Valve>Item#Model 50-2"
Item# Model 50 -2", Model 50 Lift Check Valve
Spring Loaded Lift Check
Complies with MSS-SP-80-97
400 WOG at 180° Max
100% Pressure Tested
Threaded Ends
Soft Disc
Integral Seat
"Contains lead. Not for use in water systems intended for human consumption`
Equipped with 24S disc for water service,
Not recommended for steam.
�—•a,
, , V ��::
�,.���_`� ;��.,���{ a �, �
7 � ���� ��,{��
��
, i; ��,'��a`°�,`��.�':..
..°��,_ :;�� _ w��;
t
. I1►fl�r�� Ir� �?.�.�►.
larger image
larqer imaqe
Specifications • Material List
Specifications
Size 2 in
A-Total Length 5.88 in
B-Height 3.25 in
Ship Weight 9.00 Ib
Quantity per Carton 1
Valve Type Check Valve
200 psi
Pressure Class 400 WOG
200 WSP
1 of 2 5/14/2012 11:55 AM
United Brass Works,Inc. -Item#Model 50-2",Model 50 Lift Check Valve http://ubw.thomasnet.com/printitem/fire-protection-products-lift-check-v...
End Connection Threaded
Gas
Application Oil
Steam
Water
Bonnet Type Union
UL Listed No
FM Approved No
MEA Approved No
MSS Compliant Yes
Canadian Registration No
Pressing Machine Part No
Material List
1'V��,`�'�1�IA�L LI��T' ��
j� � p� ti� p � � 1
`tiCl. I�E�+�'RIP�I�\ !�L�T�R�.-'�. ,
A 4
� B�tu�et�h�t�,;�„_i �°`� Bi�:�ss 6 ° � ° �
Saiub�t�Ttit(1 �.._ -,.,� B�ni�e �� o ;,��� �
o , v
�
i �15��t7���C7'�1 -��'3 a�•� �1':155 � � � ♦ �'` ��`.; ti
` Disc Holdei°[1"—;") Br`o��zz II� L �'� I i i ii�
��` , 3
.��" ��,�. � : i�iill�r�
3 Saft D�S� Bi�«� .� �, � i�
�
�Ilj�f�lll�
Dise Holdei�h'ait(`.•+.,_ l l,a..) i,i i i i i i n
� PtT'�44
I��s�i-iolci�r�xet(1'..'�`—3"} E3r���zz I '� � /
S $mdy' B�`c��ize �'
C S�n�itrs St:�isil��s�t�el .,�
T Cauidt(°.,i`°—'�:') Br�sS
' Cn�dc(�.._.�.,� B�-o1��
��
2 of 2 5/14/2012 11:55 AM
United Brass Works,Inc. -Item#Model 125SUL- 1",Model 125SUL... http://ubw.thomasnet.com/printitem/fire-protection-products-globe-valv...
United Brass Works, Inc.
714 South Main Street
Randleman, NC 27317 USA
Phone: 336-498-2661
Fax: 336-498-4267
To I I-free: 800-334-3035
Email: sales@ubw.com
Website: http://www.ubw.com
All Categories> Fire Protection Valves&Products>Fire Protection Products-Globe Valves>Model 125SUL Globe
Valve>Item#Model 125SUL-1"
Item# Model 125SUL- 1", Model 125SUL Globe Valve
Soft Disc
UL Listed for Fire Sprinkler Service at 250 WOG
200 WOG at 180° Max
100% Pressure Tested
Threaded Ends
Integral Seat
Rising Stem
Swivel Disc Holder
*Contains lead. Not for use in water systems intended for human consumption�
. , . - - �
� �.�,
I -- �
� �
I � 4.- -
__ '+�.f'"-.
_ -� - I1�I�c�� In T1.�.�i
larger imaqe
larqer image
Specifications � Material List
Specifications
Size 1 in
A-Total Length 2.97 in
C-Height Closed 4.25 in
B-Diameter 2.75 in
Ship Weight 1.76 Ib
Quantity Unit Pack 6
Quantity per Case 36
Valve Type Globe Valve
125 psi
Pressure Class 200 WOG
125 WSP
1 of 2 10/29/20ll 3:01 PM
United Brass Works,Inc. -Item#Model 125SUL- 1",Model 125SUL... http://ubw.thomasnet.com/printitem/fire-protection-products-globe-valv...
End Connection Threaded
Gas
Application Oil
Water
Stem Type Rising
Bonnet Type Screwed
UL Listed Yes
FM Approved No
MEA Approved No
MSS Compliant No
Canadian Registration No
Pressing Machine Part No
Material List
�����r�,���1 �� '� � �L��
� �o�R �
r
���. i�i�a��.�i i���i��� ��:��rr:��.k�. . .:.;�� ��-�
_ ��i',L .~4.Y: �...4:. .
�� F{�r�.l k3'Ir��� .s � I.���t•1i1,�: Ir+�w � �—s
i
.#� �'s�ki�rt; �ui � �I<r��:
� �'x�ara ��r,i�hihe�1�n-�s�*.
�.. - . ... . � .���r _
��i+rn � I 3 ���,� �ri�.k m�,`.
� 13�,q rkt a I�:� �a.! I�n:'�n�t " �
t� �ieii'�:�°1"r��c' :ti��€n. Hr�r� G�' _ �
En
! ?� 1:7i� l���u•i:'� r .-•,
�
_ �,
� �
?d li��s� 1#rti�rr.t �
�':���- _
��
2 of 2 10/29/20ll 3:01 PM
� � � � � � ' � , � � • �
SINGLE INLET
An inlet connection with 250 G.P.M. minimum inlet capacity
��� � � to supplement the fire protection water supply. Provides ��li ���� .
�� � -�,
.__ . �� unobstructed water supply. Flush round design enhances �'�.. � ,�a
r , appearance and provides unobstructed passage. . �:�ti�
i e �
fi , �. '��-' �
�� ' �. �:`�'
s-. �,{�'
��k�` � �9 , ��:�� STANDARD EQUIPMENT: Cast Brass round plate with double ���., �� g��;�•
� � ��:,
�� � � �, female adapter; plug and chain; branding as selected. ��� - y .,
.��'• �`2� s�'� '*. �1ti �£�1-..
SPECIFY THREAD AND BRANDING. ��''��-�'
�� .
>;a
� BRANDING: "Standpipe", "Auto Spkr." �
,7F
_, t.i�l
FINISH: Cast Brass
Figure No. 6341 Figure No. 6342
OPTIONAL FINISH: PB-Polished Brass
PC-Polished Chrome
Round Plate
Figure No. Size
6341 2 1/2 X 2 1/2
6342 3 X 2 1/2
6343 3 X 3
RESI DENTIAL FI RE DEPT . CON N ECTI ON
An inlet connection to supplement the water supply to a
� •'' � ����- residential sprinkler system.
:�R °r
�`k;���.. -�:'�,�;
T�
��� �-�`� Rya�, ,' STANDARD EQUIPMENT: 1 1/2" cast brass round plate
, ., �� �. i assembly with integral pin lug swivel inlet. Hose thread inlet
'=+'�� �' ����` swivel, 1 1/2" NPT female outlet on back of plate. Cast brass
,k h
, ^���� �'�:�F plug and brass chain. Overall outside Diameter 4 3/8".
i , SPECIFY THREAD AND BRANDING.
� � U/L LISTED.
���'` BRANDING: "Auto Spkr."
.�
FINISH: Cast Brass
Figure No. 6345
OPTIONAL FINISH: PB-Polished Brass
PC-Polished Chrome
Page 6-12
\
N;`;.AMTROLN°.'�,
� " �
:,
--' �
FIRE-X-TROL R
FPT Series, Fire Protection Expansion Tanks (ASME)
175 PSIG Working Pressure
SYSTEM CONNECTION In-Line Models
B CHARGING
VALVE
Model Tank A B Sys. Ship
No. Vol. Hei ht Diameter Conn. Wt.
Lit. Gal. mm ins. mm ins. ins. kg Ibs.
nnooe�s: FPT-5-C 15 2.1 264 103�a 254 10 3ia NPTF 9.5 21
A FPT-5-C FPT-12-C 24 6.4 397 155�s 305 12 3ia NPTF 15.4 36
FPT-12-C
Stand Models
Motlel Tank A B C Sys. Ship
SYSTEM CONNECTION No. Vol. Height Diameter Dim. Conn. Wt.
B
CHARGING Lit. Gal. mm ins. mm ins. mm ins. ins. kg 16s.
VALVE FPT-20V-C 30 8.0 495 191iz 305 12 273 103�4 3�a NPTF 23.6 52
FPT-30V-C 53 14.0 486 191�s 419 16��a 324 123�4 3ia NPTF 44 97
nnooe�s: FPT-42V-C 66 17.5 616 24��a 419 16�ia 324 123�4 3�a NPTF 52.7 116
FPT-20V-C FPT-60V-C 95 25.0 838 33 419 16�ia 324 123�4 3�a NPTF 70 154
FPT-30V C
A FPT-42V C FPT-70V-C 129 34.0 1054 41��z 419 16�ia 324 123�4 3�a NPTF 90 197
FPT-60V-C FPT-80V-C 200 53.0 908 353�4 610 24 406 16 11�aNPTF 114 251
FPT-70V C FPT-120V-C 250 66.0 1111 433�a 610 24 406 16 1�ia NPTF 127.6 281
FPT-180V-C 292 77.0 1235 485�s 610 24 406 16 11/a NPTF 160.3 353
FPT-210V-C 341 90.0 1410 551�2 610 24 406 16 11ia NPTF 173.4 382
Constructed per ASME Code Section VIII, Division 1.
`— � � All dimensions and weights are approximate.
Maximum Operating Conditions
B CHARGING o 0 0 0 �
VALVE Operating Temperature -20 F(-29 C)to 200 F(93 C)
Working Pressure 175 PSIG (12 bar) o `
MODE�S: Specifications
FPT-80V C Description Standard Construction
A FPT-120V-C Stantlard Factory Pre-charge 25 PSIG (1.7 bar)
FPT-180V-C System Connection Stainless Steel
FPT-210V-C Diaphragm Material High-Performance Rubber Compound
Liner Material Polypropylene
_ Shell Steel
SYSTE"" –�– – Coating FPT Red
CONNECTION
I'' � ''I Fluid Compatibility With or Without Antifreeze Per NFPA 13
Job Name Contractor
Location Contractor P.O. No.
Sales Representative
Model No. Ordered
Engineer
Rev.03/06 18
Submittal data sheets can ONLYbe ordered as a"Submittal Data Sheet Pack",using MC#4400. They are not available to order on an indi-
vidual basis,however each data sheet is available on the Amtrol Web Site and can be downloaded and printed for use as needed.
Expansion Chamber Sizing
Step 1
L = Change in Antifreeze Solution Volume 0.690
Sv = Volume of System 20
DI = Density of solution at lowest temp 1.050
Dh = Density of solution at highest temp 1.015
Densities are listed at NFPA 13 2002 Figure 7.5.2.5(b)
Step 2
Vec = Minimum required volume (gal) of expansion chamber 3.1
PO = Pre-charge pressure of chamber 122
P1 = Static pressure on supply side of backflow 125
P2 = Maximum allowable system working pressure 175
TO = Temperature of chamber air at pre-charge 75
T1 = Lowest expected temperature of air in tank 60
T2 = Highest expected temperature of air in tank 80
L = Result of step 1 0.690
Notes:
All pressures and temperatures absolute (psia and rankin)
psia = measured + 15 psi
rankin = temperature + 460