HomeMy WebLinkAboutA13-0085 Specs o a ro�ect a ues:
Project Name: Christiana Standby Hours: 24
�� Project ID: Alarm Mins:�5
Prepared By: Brad Wolniak Derating Factor: 1.2
: 1 . . Date: 11/15/2013 Voltage Drop Warning
� � � Threshold%: 10
Panel ID: 5820XL Model: 5820XL Add.Fire Alarm Control Panel Max NAC Current: 3.0 Amps
Location: Lower Level Mechanical Volts: 24 VDC Max Panel Current: 6.0 Amps
Current Draw Wire AWG Ohms Per Length(ft) Actual Volts @ o
Ckt.# Circuit Name Qty Standb Alarm &T e 1000 Ft. One-Wa Ohms EOL ��Drop
5820XL 5820XL CTRL Panel 1 0.215 0.385
SK Photo,Phato-T 59 0.016 0.016
SK Fire-CO 47 0.014 0.014
SK Heat,Heat-HT 19 0.005 0.005
SK Heat ROR 0.000 0.000
SK Beam,Beam-T 0.000 0.000
SK Duct 0.000 0.000
SK Acclimate 0.000 0.000
SK Control 0.000 0.000
SK Control-6 0.000 0.000
SK Relaymon 0.000 0.000
SK Monitor, Minimon 32 0.012 0.012
SK Monitor-2 0.000 0.000
SK Monitor-10 0.000 0.000
SK Pull-SA,Pull-DA 0.000 0.000
SK Rela 5 0.001 0.001
SK Rela -6 0.000 0.000
SK Zone 0.000 0.000
SK Zone-6 0.000 0.000
SK Isolator Module 0.000 0.000
SSB22461 Isolator Base 0.000 0.000
B200SR Sounder Base 85 0.060 0.060
SSB224R6 Rela Base 0.000 0.000
SSRTS151 Ma netic Remote Test 0.000 0.000
SSRTS151KEY Ke Activated Test 0.000 0.000
SSRA100Z Remote LED 0.000 0.000
5815XL SLC Loop Expander 1 0.055 0.055
5860 LCD Remote Annunc 1 0.020 0.025
5824 Serial/Parallel Module 0.000 0.000
5496 Power Ex ander 0.000 0.000
5895XL Power Expander 0.000 0.000
5865-4 LED Annunciator 4G 0.000 0.000
5865-3 LED Annunciator 3G 0.000 0.000
5880 LED Driver Module 0.000 0.000
5883 Rela Module 0.000 0.000
PGM-I/O#1 Aux Power Circuit 0.042 1.470 #14 Solid 2.52 200 1.01 18.92 7.26%
PGM-I/O#2 Notification Appl Circuit 0.043 1.505 #14 Solid 2.52 200 1.01 18.88 7.44%
PGM-I/O#3 Notification A I Circuit 0.000 0.531 #14 Solid 2.52 200 1.01 19.86 2.62%
PGM-I/O#4 Notification Appl Circuit 0.000 0.254 #14 5olid 2.52 200 1.01 20.14 1.26%
PGM-I/O#5 Notification A I Circuit 0.000 0.777 #14 Solid 2.52 200 1.01 19.62 3.84%
PGM-I/O#6 Notification Appl Circuit 0.000 0.177 #14 Solid 2.52 200 1.01 20.22 0.87%
Total Standb Current Am s 0.483 5.287 Total Alarm Current Am s
Standb Time In Hours 24 0.083 Alarm Time In Minutes/60 5 Mins
Total Standb AH Re uired 11.590 0.441 Total Alarm AH Re uired
Total Combined AH Required 12.03 Command Shortcuts
Multi I B The Deratin Factor 1.20
Minimum Batte AmpHours Required 14.44 Configure Circuits Print Page
CEILING SPECIFICATIONS:
All ceilings are flat and 10' or less with the exception of: