Loading...
HomeMy WebLinkAboutA13-0085 Specs o a ro�ect a ues: Project Name: Christiana Standby Hours: 24 �� Project ID: Alarm Mins:�5 Prepared By: Brad Wolniak Derating Factor: 1.2 : 1 . . Date: 11/15/2013 Voltage Drop Warning � � � Threshold%: 10 Panel ID: 5820XL Model: 5820XL Add.Fire Alarm Control Panel Max NAC Current: 3.0 Amps Location: Lower Level Mechanical Volts: 24 VDC Max Panel Current: 6.0 Amps Current Draw Wire AWG Ohms Per Length(ft) Actual Volts @ o Ckt.# Circuit Name Qty Standb Alarm &T e 1000 Ft. One-Wa Ohms EOL ��Drop 5820XL 5820XL CTRL Panel 1 0.215 0.385 SK Photo,Phato-T 59 0.016 0.016 SK Fire-CO 47 0.014 0.014 SK Heat,Heat-HT 19 0.005 0.005 SK Heat ROR 0.000 0.000 SK Beam,Beam-T 0.000 0.000 SK Duct 0.000 0.000 SK Acclimate 0.000 0.000 SK Control 0.000 0.000 SK Control-6 0.000 0.000 SK Relaymon 0.000 0.000 SK Monitor, Minimon 32 0.012 0.012 SK Monitor-2 0.000 0.000 SK Monitor-10 0.000 0.000 SK Pull-SA,Pull-DA 0.000 0.000 SK Rela 5 0.001 0.001 SK Rela -6 0.000 0.000 SK Zone 0.000 0.000 SK Zone-6 0.000 0.000 SK Isolator Module 0.000 0.000 SSB22461 Isolator Base 0.000 0.000 B200SR Sounder Base 85 0.060 0.060 SSB224R6 Rela Base 0.000 0.000 SSRTS151 Ma netic Remote Test 0.000 0.000 SSRTS151KEY Ke Activated Test 0.000 0.000 SSRA100Z Remote LED 0.000 0.000 5815XL SLC Loop Expander 1 0.055 0.055 5860 LCD Remote Annunc 1 0.020 0.025 5824 Serial/Parallel Module 0.000 0.000 5496 Power Ex ander 0.000 0.000 5895XL Power Expander 0.000 0.000 5865-4 LED Annunciator 4G 0.000 0.000 5865-3 LED Annunciator 3G 0.000 0.000 5880 LED Driver Module 0.000 0.000 5883 Rela Module 0.000 0.000 PGM-I/O#1 Aux Power Circuit 0.042 1.470 #14 Solid 2.52 200 1.01 18.92 7.26% PGM-I/O#2 Notification Appl Circuit 0.043 1.505 #14 Solid 2.52 200 1.01 18.88 7.44% PGM-I/O#3 Notification A I Circuit 0.000 0.531 #14 Solid 2.52 200 1.01 19.86 2.62% PGM-I/O#4 Notification Appl Circuit 0.000 0.254 #14 5olid 2.52 200 1.01 20.14 1.26% PGM-I/O#5 Notification A I Circuit 0.000 0.777 #14 Solid 2.52 200 1.01 19.62 3.84% PGM-I/O#6 Notification Appl Circuit 0.000 0.177 #14 Solid 2.52 200 1.01 20.22 0.87% Total Standb Current Am s 0.483 5.287 Total Alarm Current Am s Standb Time In Hours 24 0.083 Alarm Time In Minutes/60 5 Mins Total Standb AH Re uired 11.590 0.441 Total Alarm AH Re uired Total Combined AH Required 12.03 Command Shortcuts Multi I B The Deratin Factor 1.20 Minimum Batte AmpHours Required 14.44 Configure Circuits Print Page CEILING SPECIFICATIONS: All ceilings are flat and 10' or less with the exception of: Certain penthouse ceilings have peaked ceilings