HomeMy WebLinkAboutA13-0086 Ademco Battery Calc--625 Forest Rdversion 1.061 (6/21/2013) Honeywell Security Battery & Power Budget Calculator © 2003 Honeywell International Inc. All Rights Reserved Select Panel from pulldown list: Selected Panel NOT Comm'l Fire Rated Calculated Current Draw Power Budget Grayed-out device(s) are not supported by selected panel KEYPADS/INTERFACES 6128 6128RF 6137 6139/6139R 6148 6149EX 6150 6150RF 6150V 6150RF 6160/6160CR 6160CR-2 6160PX 6160RF 6160V 6164US 6165EX 6270 6271C 6271CV 6271V 6272CV 6272CSV 6272CBV 6460S 6460W 8132iPK (Symphony) FSA-8 Fire Zone Annunciator FSA-24 Fire Zone Annunciator Add'l Keypd (Enter # and Currents) Add'l Keypd (Enter # and Currents) 2 WIRE & 4 WIRE SMOKE DETECTORS (except Vplex Polling Loop detectors) 2 wire smoke detector (zone powered) 2 wire smoke detector (zone powered) 2 wire smoke detector (zone powered) 2 wire smoke detector (zone powered) ESL 449 CST SYS CO1224TR CO Detectors SYS5603 135 Fixed Heat Detectors 12V 4 wire Smoke ( Qnt'y & Currents) MULTI-POWER DEVICES 4208U [powered by polling loop] 4208U [powered by panel aux power] 4208U [powered externally] 4208SN [powered by polling loop] 4208SN [powered by panel aux power] 4208SN [powered externally] 4208SNF [powered by polling loop] 4208SNF [powered by panel aux power] 4208SNF [powered externally] 4208SNF (Class B to A Zone Converter) 4209U Grouped Zone Mux. Module 4209U [powered externally] 4297 Polling Loop Extender Add'l Device (enter quant. & currents) Add'l Device (enter quant. & currents) AUXILIARY POWERED DEVICES PS24 24 volt Power Supply Module 4100SM (no more than one per system) 4204: Enter no. of relays used 4204CF:Enter no. of relays used 4285 Voice Module 4286 with warning speakers 5140DLM Backup Dialer Module 5800RP wireless repeater module 5800TM wireless xmtr module 5881EN receiver 5883 hi-security receiver UVS-QM VA8200 Panel Linking Module VA8201 Alpha Pager Module Add'l Device (enter quant. & currents) Add'l Device (enter quant. & currents) Communicators 7845GSM/7845i-GSM 7845i/7845i-ENT GSMCF/iGSMCF Fire Communicator Vista-GSM/Vista-GSMCN (Vista-21iP only) 7847i/7847i-E Internet Communicator Add'l Device (enter quant. & currents) Add'l Device (enter quant. & currents) PIR Motion Detectors (non Vplex) IS215T IS215TCE IS2260/IS2260T IS2460 IS2500LT IS2535/IS2535T IS2560/IS2560T IS2560TC IS310/IS320 Request to Exit (RTE) 997 Ceiling Mount PIR 998 Wall Mount PIR Motion Detctrs (enter quant. & currents) Motion Detctrs (enter quant. & currents) Motion Detctrs (enter quant. & currents) Motion Detctrs (enter quant. & currents) Dual Tech Motion Detectors (non Vplex) DT-515 DT-6100STC DT-7235T DT-7435/DT-7435C DT-7450/DT-7450MIC DT-7550 Motion Detctrs (enter quant. & currents) Motion Detctrs (enter quant. & currents) Motion Detctrs (enter quant. & currents) Motion Detctrs (enter quant. & currents) grayed-out devices are not supported by selected panel POLLING LOOP DEVICES 4101SN Single Output Relay Module 4190SN Two Zone SIM 4190WH 4191SN-WH 4192CP 4192SD Photoelectric Smoke Det. 4192SDT 4193SN Two Zone SIM 4194 Contact 4196 4209U 4275EX Dual PIR 4275EX-SN Dual PIR 4278EX-SN DT7500SN 4293SN 4939SN WH/BR/GY Surf Mt. Cntct. 4944SN Recessed Contact 4945SN-WH 4959SN Overhead Door Contact 5192SD Smoke Detector 5192SDT Smoke w/ Heat 5193SD Smoke Detector 5193SDT Smoke w/ Heat 998MX PIR IS2500SN PIR FG-1625SN Glass Break Detector Quest2260SN Vplex-VSI Short Isolator Vistakey Add'l VPlex (enter qnt'y & current) Add'l Vplex (enter qnt'y & current) 12V NOTIFICATION DEVICES ON BELL OUTPUT #1 SYS-MHW SYS-P2RK Enter device name, quant., & current Enter device name, quant., & current Enter device name, quant., & current 12V NOTIFICATION DEVICES ON BELL OUTPUT #2 (IF USED) Enter device name, quant., & current Enter device name, quant., & current Enter device name, quant., & current Enter device name, quant., & current Enter device name, quant., & current 12V AUX POWER AND BELL CIRCUIT WIRE RUN DATA Panel Aux Power Wire Run (twin lead) Panel Bell 1 Wire Run (twin lead) Panel Bell 2 Wire Run (twin lead) PS24 Power Supply Battery & Power Budget Calculator © 2003 Honeywell International Inc. All Rights Reserved Selected Panel NOT Comm'l Fire Rated Equivalent panel load @ 24V (converted to 12VDC from 24V full-wave) Power Budget 24V NOTIFICATION APPLIANCES Enter Device Names & Specifications 24V Notification Appliance 24V Notification Appliance 24V Notification Appliance 24V Notification Appliance 24V Notification Appliance 24V Notification Appliance 24V Notification Appliance 24V Notification Appliance 24V Notification Appliance 24V Notification Appliance 24V Notification Appliance 24V Notification Appliance 24V Notification Appliance 24V Notification Appliance 24V Notification Appliance 24V Notification Appliance 24V BELL CIRCUIT WIRE RUN DATA PS24 Output A Wire Run (twin lead) PS24 Output B Wire Run (twin lead) Facility Information Location: Account #: Model: Engineer: Date: SELECTED PANEL MAXIMUM OUTPUT RATINGS Polling Loop (mA) 128 40.5 87.5 Current OK Enter Quantity 0 0 0 0 0 0 0 0 0 0 2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Power Overdraw if highlighted Enter Quantity 0 0 0 0 14 9 4 0 Enter Quantity 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Power Overdraw if highlighted Enter Quantity 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Power Overdraw if highlighted Enter Quantity 0 0 0 0 0 0 0 27 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Polling Loop Overdraw if highlighted! Add 4297 Devices (row 41) Enter Quantity 4 1 0 0 0 Bell #1 Power Overdraw if highlighed! Enter Quantity 0 0 0 0 0 Bell #2 Power Overdraw if highlighed! Units PS24 POWER SUPPLY MODULE, MAXIMUM CAPACITIES Panel 12V Standby (mA) 455.778 0 455.778 Enter Quantity 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Units 625 Forest Rd ADE 128BPE George Sharer 12/08/2013 Standby Auxiliary Power (mA) 750 165.278 584.722 Current OK How many powered externally? 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 How many powered externally? 0 0 0 0 How many powered externally? 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 How many powered externally? 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 How many powered by 4297? 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 How many powered externally? 0 0 0 0 0 How many powered externally? 0 0 0 0 0 Wire Gauge(AWG) Panel 12V Alarm (mA) 746.626 0 746.626 Which PS24 Output? 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Wire Gauge(AWG) Alarm Auxiliary Power (mA) 1000 375.92 624.08 Current OK Standby (aux pwr) 30 60 40 40 30 40 40 80 60 80 45 45 40 50 60 55 40 180 159 159 137 180 180 180 40 40 350 35 35 0 0 Standby (aux pwr) Two-wire smoke detector current is built into the panel budgets. These fields are included to help you create a complete equipment list. The line below indicates if number of detectors exceeds panel capacity, or if the selected panel does not support 2-wire smoke detectors. Quantity of 2 Wire Smoke Detectors OK for selected panel! 0.007 0.02 0 0 Standby (aux pwr) 0 28 28 0 33 33 0 40 40 40 110 110 178 0 0 Standby (aux pwr) 50 25 40 80 160 220 5 80 20 60 80 75 88 165 0 0 10 10 10 10 75 0 0 7 18 4 9 25 20 20 25 35 12 13 0 0 0 0 20 35 20 30 35 40 0 0 0 0 Standby (aux pwr) Standby (aux pwr) Standby (aux pwr) Output A Standby (mA) 570 0 570 Device Standby Load (MA) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Panel Standby (mA) 250 Alarm Current (Aux) 45 120 85 100 55 60 70 105 160 105 150 160 165 150 190 210 70 280 230 230 210 305 305 305 150 150 400 65 130 0 0 Alarm Current (Aux) 0.04 0.04 0 0 Alarm Current (Aux) 0 28 28 0 33 33 0 40 40 40 110 110 178 0 0 Alarm Current (Aux) 100 25 40 80 160 300 15 80 20 60 80 110 88 165 0 0 10 10 10 10 75 0 0 7 18 4 9 25 20 20 25 35 12 13 0 0 0 0 20 35 20 30 35 40 0 0 0 0 Alarm Current (Aux) Alarm Current (Aux) 0.013 0.154 0 0 0 Alarm Current (Aux) 0 0 0 0 0 Ohms per 1000 ft 5.08 8.08 8.08 Output A Alarm (mA) 1700 0 1700 Device Alarm Load (MA) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Ohms per 1000 ft 0 0 Panel Alarm (mA) 330 Calculated Bell Draw Bell Power Budget External Bell Power Req'd (mA): Polling Loop Polling Loop Polling Loop 27.3 0.6 0.6 33.6 0.6 0.6 33.6 0.6 0.6 0 15.5 15.5 0 0 Polling Loop Polling Loop 7 2 2 0.5 0.4 0.4 0.4 1.5 1 1 15.5 1 1 1 2.6 1 1 1 0.5 0.5 1.2 1.2 1.2 1.2 1 1.6 1 6 5 2 0 0 Polling Loop Polling Loop Alarm Current Draw (mA) 375.92 0.206 0 Use TWO identical batteries w/ this AH capacity Output B Standby (mA) 570 0 570 Total Alarm Current Draw (mA) 0 0 Bell #1 Output (mA) 1700 0.206 1699.794 Current OK 0 Total Polling Loop Total Polling Loop Total Polling Loop 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Total Polling Loop Total Polling Loop 0 0 0 0 0 0 0 40.5 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Total Polling Loop Total Polling Loop Run Length 300 300 0 Output B Alarm (mA) 1700 0 1700 Current OK Subtotal A Standby 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Run Length 0 0 Enter Standby and Alarm Times Battery Standby (hours): Alarm Duration (minutes): Recommended Battery Capacity OK for 48-Hr Recharge Bell #2 Output (if used; mA) NA 0 Not Used Total Standby Current 0 0 0 0 0 0 0 0 0 0 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Panel Max Output Exceeded if highlighted Total Standby Current 0.098 0.18 0 0 Total Standby Current 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Panel Max Output Exceeded if highlighted Total Standby Current 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 75 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Panel Max Output Exceeded if highlighted Total Standby Current Panel Max Output Exceeded if highlighted Total Standby Current Panel Max Output Exceeded if highlighted Total Standby Current Panel Max Output Exceeded if highlighted Actual Resistance (twin leads) 3.048 4.848 0 Standby/Alarm Durations (from top) Battery Standby (hours): Alarm Duration (minutes): Required Capacity (AH) Recommended Battery Capacity OK for 48-Hr Recharge PS24 PC Board (mA) 40 40 0 Subtotal A Alarm 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Actual Resistance (twin leads) 0 0 Recommended Battery (AH) Maximum Panel Standby Output 750 Total Standby 205.778 Standby Budget 544.222 Current OK Total Alarm Current 0 0 0 0 0 0 0 0 0 0 300 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Total Alarm Current 0.56 0.36 0 0 Total Alarm Current 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Total Alarm Current 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 75 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Total Alarm Current Total Sounder Current from Panel Bell #1 0.052 0.154 0 0 0 Total Sounder Current from Panel Bell #2 0 0 0 0 0 Voltage At EOL 10.85419584 11.999001312 12 Maximum Total Standby Output 610 Total Standby 40 Standby Budget 570 Current OK Subtotal B Standby 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Voltage At EOL 24 24 24 5 13.8323435666667 Maximum Panel Alarm Output 1700 Total Alarm 416.626 Alarm Budget 1283.374 Current OK Ext. UL Power Req'd (mA): Total External Current Required 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Total External Current Required 0 0 0 0 Total External Current Required 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Total External Current Required 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Total External Current Required Total Sounder Current (external) 0 0 0 0 0 Total Sounder Current (external) 0 0 0 0 0 Voltage Drop (Percent) 9.54836800000001 8.32239999999729E-03 0 24 5 1.15533333333333 7 7 Maximum Total Alarm Output 4180 Total Alarm 40 Alarm Budget 4140 Current OK Subtotal B Alarm 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Voltage Drop (Percent) 0 0 Battery Contigency Factor Max Battery Supported by Panel 17.2 0 Modifiers (LEDs, etc.) False False False True False False False False False False Modifiers (LEDs, etc.) False False False False False False False False False False False Max. Battery Capacity 34.4 34.4 3 All Keypads? 1 True -16 False True True False False False False False False Unit Selection 1 1 1 4 Unit Selection False Output Selection 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Unit Selection 1 1 False 1 SN Vplex? 1 False 1 True AUI Support? 1 False Commercial Fire Rated 0 False Polling Loop Support 1 False No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 Battery Contingency (normally 1.1 (10%), 1.2 (20%), or 1,4 (40%). This value is carried to Battery Capacity calculation (in cell Calculator!J6), and is used to compensate for the way a lead-acid battery changes over time. Select one of the two methods for calculating this below, and copy the appropriate cell into B20. Contingency Factor: This code adds a combo-box selector to the Calculator page, which will enable the user to select battery contingency factors of 10%, 20%, or 40%. This code is here in case customer feedback indicates that they want battery contingency as a manual selection. To implement, copy the combo box to the calculator page, and copy cell D26 to B20. Number 1 2 3 Line Drop Calculations 1 2 3 4 5 6 7 8 9 10 11 12 13 Panel <Select Panel> Vista-32FB 5110XM 5140XM Vista-100 Vista-128B Vista-128BP Vista-128BPT Vista-128FB Vista-128FBP Vista-128FBPT Vista-128FBP (UL864 Edition 9) Vista-128FBPT (UL864 Edition 9) Vista-250BP Vista-250FBP Vista-250FBPT Vista-250FBP (UL864 Edition 9) Vista-250FBPT (UL864 Edition 9) Vista-40 Vista-50P 7720ULF 7720ULFPLUS Vista-21iP Vista-20PS Vista-20P <Select Panel> 1.2 Factor 0.1 0.2 0.4 Gauge <Select Wire Gauge> #12 AWG Solid #12 AWG Stranded #14 AWG Solid #14 AWG Stranded #16 AWG Solid #16 AWG Stranded #18 AWG Solid #18 AWG Stranded #20 AWG solid #20 AWG Stranded #22 AWG Solid #22 AWG Stranded Polling Loop (mA) 0 128 0 64 128 128 128 128 128 128 128 128 128 128 128 128 128 128 64 64 0 0 0 0 0 0 Value 1.1 1.2 1.4 Ohms/1K ft 0 2.01 2.05 3.19 3.26 5.08 5.29 8.08 8.45 10.15 10.5 16.14 16.8 Aux. Power (normal; mA) 0 750 350 750 1000 750 750 750 1000 1000 1000 1000 1000 750 1000 1000 1000 1000 750 750 150 150 500 500 500 0 Selection 2 1.2 Ohms/1KM 0 6.59448818897638 6.7257217847769 10.4658792650919 10.6955380577428 16.6666666666667 17.3556430446194 26.509186351706 27.7230971128609 33.2 34.1 51.7 52.7 Aux. Power (alarm; mA) 0 1000 1000 750 1700 1000 1000 1000 1700 1700 1700 1700 1700 1000 1700 1700 1700 1700 750 750 600 900 500 500 500 0 Lookups from Calc Page 6 8 8 1 1 Panel Standby (mA) 0 300 155 300 300 250 250 250 300 300 300 300 300 250 300 300 300 300 250 250 100 100 85 85 85 0 Panel Alarm (mA) 0 470 235 470 470 330 330 330 470 470 470 470 470 330 470 470 470 470 330 330 900 900 160 160 160 0 This code automatically selects battery contingency factor based on standby time (in cell Calculator!J3). Using this method, the factor is 1.4 if standby time is 4 hours or less, and 1.1 (10%) if the standby time is over 4 hours. To implement, copy cell G26 to B20. 1.1 Unit Selection 1 2 Output Selection 1 2 Bell #1 Output (mA) 0 1700 1000 1700 1700 1700 1700 1700 1700 1700 1700 1700 1700 1700 1700 1700 1700 1700 1700 1700 500 500 600 600 600 0 Units Feet Meters Output Output A Output B Bell #2 Output (mA) 0 1700 0 1700 1700 NA NA NA 1700 1700 1700 1700 1700 NA 1700 1700 1700 1700 NA NA NA NA NA NA NA 0 Lookup 1 1 Max Panel Standby Output 0 1000 350 1000 1000 750 750 750 1000 1000 1000 1000 1000 750 1000 1000 1000 1000 750 750 250 250 500 500 500 0 2 Max Panel Alarm Output 0 2300 1000 2300 2300 1700 1700 1700 2300 2300 2300 2300 2300 1700 2300 2300 2300 2300 750 1700 2100 2100 600 600 600 0 Supports Polling Loop? 1 1 0 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 1 Supports Graphic UI? 1 0 0 0 0 0 1 1 0 1 1 1 1 1 1 1 1 1 0 0 0 0 1 1 1 1 Supports SN Vplex Devices? 1 1 0 0 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 1 Supports All Keypads? 1 0 0 0 0 0 1 1 0 0 0 0 0 1 0 0 0 0 1 1 0 0 1 1 1 1 Comm'l Fire Rated? 1 1 1 1 1 0 0 0 1 1 1 1 1 0 1 1 1 1 0 0 1 1 0 0 0 1 Max. Batt Capacity (AH) 0 34.4 14 34.4 34.4 17.2 17.2 17.2 34.4 34.4 34.4 34.4 34.4 17.2 34.4 34.4 34.4 34.4 17.2 34.4 7 7 17.2 17.2 17.2 0 2W Smokes? 0 32 16 32 32 16 16 16 32 32 32 32 32 16 32 32 32 32 16 16 0 0 16 16 16 0 8 Lookup from Select Panel control