HomeMy WebLinkAboutA13-0088 - Unit-B DSC - Battery Calc Fire Alarm System Secondary Battery-set Calculation Worksheet ITEM DESCRIPTION STANDBY QTY TOTAL ALARM QTY TOTAL CURRENT STANDBY CURRENT ALARM PER UNIT CURRENT PER UNIT CURRENT (AMPS) PER ITEM (AMPS) PER ITEM DSC Fire Alarm Control Unit 0.1100 X 1 = 0.1100 0.1100 X 1 = 0.1100 DSC PC5204 Aux Pwr Supply 0.0200 X 1 = 0.0200 0.4150 X 1 = 0.4150 DSC PC5108 Zone Exp 0.0350 X 1 = 0.0350 0.0350 X 1 = 0.0350 DSC PK5500 Keypad 0.1250 X 1 = 0.1250 0.1250 X 1 = 0.1250 Sys Sen PR-2 Pwr Super. Relay 0.0250 X 1 = 0.0250 0.0250 X 1 = 0.0250 Sys Sen MHW-Mini-Horn 0.0010 X 8 = 0.0080 0.0120 X 8 = 0.0960 Sys Sen 4WTB-Smoke Detector 0.0050 X 9 = 0.0450 0.0200 X 9 = 0.1800 Sys Sen 601 P Heat Detector 0.0000 X 4 = 0.0000 0.0000 X 4 = 0.0000 Macurco CME-1 CO Detector 0.0150 X 6 = 0.0900 0.0350 X 6 = 0.2100 0.0000 X 0 = 0.0000 0.0000 X 0 = 0.0000 0.0000 X 0 = 0.0000 0.0000 X 0 = 0.0000 0.0000 X 0 = 0.0000 0.0000 X 0 = 0.0000 0.0000 X 0 = 0.0000 0.0000 X 0 = 0.0000 TOTAL SYSTEM TOTAL SYSTEM STANDBY CURRENT AMPS y � e ALARM CURRENT AMPS 1.1960 Pre ared for: REQUIRED TOTAL REQUIRED REQUIRED TOTAL REQUIRED Dobyns Residence STANDBY SYSTEM STANDBY ALARM TIME SYSTEM ALARM 3080 Booth Falls Court TIME (HRS) STANDBY CAPACITY (HOURS) ALARM CAPACITY Vail,CO NFPA 72-2002 CURRENT (AMP-HOURS) NFPA 72-2002 CURRENT (AMP-HOURS) 4.4.1.5.3.1 (AMPS) 4.4.1.5.3.1 (AMPS) 24 X = 10.9920 0.083 X 1.1960 = 0.0993 Prepared bv: REQUIRED REQUIRED TOTAL TOTAL SAFETY ADJUSTED Ken Buffington STANDBY ALARM CAPACITY CAPACITY FACTOR BATTERY Apex Security CAPACITY CAPACITY (AMP-HOURS) (AMP-HOURS) CAPACITY NICET-IV# 113575 (AMP-HOURS) (AMP-HOURS) (AMP-HOURS) + 0.0993 = 11.0913 11.0913 X 120°/a =