HomeMy WebLinkAboutF14-0002 specs Matterhorn Residence
1664 Matterhorn Circle
Vail, CO
HYDRAULIC CALCULATIONS
AND
PRODUCT SUBMITTALS
THIS SET OF FIRE SPRINKLER SHOP SPECIFICATIONS AND HYDRAULIC CALCULATIONS HAVE
BEEN REVIEWED AND FOUND TO BE ACCEPTABLE-N.I.C.E.T.IV#102055 SR.ENGINEERING
TECHNICiAN-FIRE PROTECTION,NATIONAL INSTITUTE FOR CERTIFICATION IN
ENGINEERING TECHNICIANS
/ /
TIMOTHY N TROSTEL,JR-SET DATE
PHOENIX AUTOMATIC SPRINKLER
7684 S. BRENTWOOD ST.
LITTLETON, CO 80128
720.922.9231 PHONE
720-922-9231 FAX
CALCULATION SUMMARY
Project Name:Matterhorn Res Project Location: 1664 Matterhorn Circle
Drawing No. : City: Vail, CO
Design Areas
Design Area Calc. Mode Occupancy Area of Total Water Pressure @ Min. Min. Min. Calculated Hose Margin To
Name (Model) Application Source Density Pressure Flow Heads Streams Source
�ftz) �9Pm) �PS�) �9Pm/�Z) �PS�) �9Pm) # �9Pm) �ps�)
1 Demand (HW) Res 1152 86.1 102 0.066 20.5 19 4 0 16.9
File:C:\dwg\PHOENIX-MATTERHORN\Matterhorn FP1.dwg
Date 1/22/2014 Copyright O 2002-2012 Tyco Fire Protection Products Page 1
HYDRAULIC CALCULATIONS
for
Job Information
Project Name:Matterhorn Res
Contract No. : City: Vail, CO
Project Location: 1664 Matterhorn Circle Date: 1/5/2013
Contractor Information
Name of Contractor: Phoenix Fire
Address: City:
Phone Number: E-mail:
Name of Designer: TEM
Authority Having Jurisdiction: Vail Fire
Design
Remote Area Name 1
Remote Area Location Great Room
Occupancy Classification Res
Density(gpm/ftz) 0.066
Area of Application(ftz) 1152
Coverage per Sprinkler(ftz) 288
Number of Calculated Sprinklers 4
In-Rack Demand(gpm) 0
Special Heads
Hose Streams(gpm) 0
Total Water Required(incl. Hose Streams)(gpm) 86.1
Required Pressure at Source(psi) 85.1
Type of System Wet
Volume-Entire System (gal) 23.2 gal
Water Supply Information
Date Dec.2013
Location near site
Source W1
Notes
Maximum head spacing is 18'x18'
File:C:\dwg\PHOENIX-MATTERHORN\Matterhorn FP1.dwg
Date 1/22/2014 Copyright�O 2002-2012 Tyco Fire Protection Products Page 2
Job: Matterhorn Res Node Labels: Off
Pipe Labels: Off
Diagram for Design Area : 1
(Oatimized Hvdraulic Simalifiedl
<r s
i
E
,r
a
— _r—
1 -
File:C:\dwg\PHOENIX-MATTERHORN\Matterhorn FP1.dwg
Date 1/22/2014 Copyright�O 2002-2012 Tyco Fire Protection Products Page 3
Job:Matterhorn Res
Hydraulic Analysis for : 1
Calculation Info
Calculation Mode Demand
Hydraulic Model Hazen-Williams
Fluid Name Water @ 60F (15.6C)
Fluid Weight, (Ib/ft3) N/A for Hazen-Williams calculation.
Fluid Dynamic Viscosity, (Ib•s/ft2) N/A for Hazen-Williams calculation.
Water Supply Parameters
Supply 1 : W1 Flow(gpm) Pressure(psi)
0 102
1300 97
Hoses
Inside Hose Flow/Standpipe Demand(gpm)
Outside Hose Flow(gpm)
Additional Outside Hose Flow(gpm)
Other(custom defined) Hose Flow(gpm)
— — — — — — — — — — — — — — — — — — — — —
Total Hose Flow(gpm)
Sprinklers
Ovehead Sprinkier Flow(gpm) 86.1
InRack Sprinkler Flow(gpm) 0
Other(custom defined)Sprinkler Flow(gpm) 0
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Total Sprinkler Flow(gpm) 86.1
Other
Required Margin of Safety(%) 10
W1 -Pressure(psi) 85.1
W1 -Flow(gpm) 86.1
Demand w/o System Pump(s) N/A
File:C:\dwg\PHOENIX-MATTERHORN\Matterhorn FP1.dwg
Date 1/22/2014 Copyright O 2002-2012 Tyco Fire Protection Products Page 4
Job:Matterhorn Res
Hydraulic Analysis for : 1
f Supply � Supply; Safety Pressure f System Demand
150
140=__ _ _ . .. ,. ��.._ `
130 ------ -- -- � �--
-
.
120 _ _ ��� ���
11 S:I� _ _ ° -------- �
� � ��� 96.265 �'
100�1-------------��__ ��
���F���
g D2 --------�------ —1�---�
.N ��
�
Gj 80 ----9— �—�—�-- I ��� P
N 70 ---� — � —,— � ����
�
L
a 60 ---------------
50 ---� � � � u �
I� � �
40 --- — -- �� i
- � � � � P i P w � �
30 _�
2 p� ---- —
10 �----�--�--�--�--�--�_ i d � d i
0 ���������������������������'
0 400 500 600 700 800 900 1000 1100 1200 1300 1400
Flow, gpm
File:C:\dwg\PHOENIX-MATTERHORN\Matterhorn FP1.dwg
Date 1/22/2014 Copyright O 2002-2012 Tyco Fire Protection Products PBge 5
Job:Matterhorn Res
Hydraulic Analysis for : 1
Graph Labels
Values
Label Description Flow (gpm) Pressure (psi)
S1 Supply point#1 -Static 0 102
S2 Supply point#2-Residual 1300 97
D1 Elevation Pressure 0 10.6
D2 System Demand 86.1 85.1
Curve Intersections & Safety Margins
Intersection Safety Margin
Curve Name
Pressure (psi) Flow (gpm) Pressure (psi) @ Flow (gpm)
Supply 102 96.2 16.9 86.1
Supply;Safety Pressure 91.8 90.2 6.7 86.1
Open Heads
Required Calculated
Head Ref. Head Type Coverage K-Factor
Density Flow Pressure Density Flow Pressure
(ftz) (gpm/psiYz) (gpm/ftz) (gpm) (psi) (gpm/ftz) (gpm) (psi)
100 Overhead Z$$ 4.2 0.05 14.4 20.5 0.086 24.6 34.4
Sprinkler
101 Overhead Z$$ 4.2 0.05 14.4 20.5 0.066 19 20.5
Sprinkler
102 Overhead 288 4.2 0.05 14.4 20.5 0.081 23.4 31.1
Sprinkler
103 Overhead 288 4.2 0.05 14.4 20.5 0.066 19 20.5
Sprinkler
File:C:\dwg\PHOENIX-MATTERHORN\Matterhorn FP1.dwg
Date 1/22/2014 Copyright O 2002-2012 Tyco Fire Protection Products Page 6
Job:Matterhorn Res Hydraulic Calculations/Fluid Delivery Time Analysis
Node Data
Node# Type K-Fact. Discharge Coverage Tot. Pres. Req. Pres.
Elev Hgroup Open/Closed Overdischarge Density Elev. Pres. Req. Discharge
gpm/psi Ya 9pm ftz psi psi
ft gpm gpm/ftz psi gpm
101 Overhead Sprinkler 4.2 19 288 20.5 20.5
22.75 HEAD Open 4.6 0.066 -10.6 14.4
103 Overhead Sprinkler 4.2 19 288 20.5 20.5
22.75 HEAD Open 4.6 0.066 -10.6 14.4
102 Overhead Sprinkler 4.2 23.4 288 31.1 20.5
22.75 HEAD Open 9 0.081 -10.6 14.4
100 Overhead Sprinkler 4.2 24.6 288 34.4 20.5
22.75 HEAD Open 10.2 0.086 -10.6 14.4
006 Node 24.3
19.5 NODE -9
026 Node 39.8
9 NODE -3.7
029 Node 41.5
9 NODE -3.7
032 Node 45.7
9 NODE -3.7
039-0 Node 55.6
3 NODE -0.7
039-I Node 59.7
3 NODE -0.7
040-0 Node 60.4
3 NODE -0.7
040-I Node 68
3 NODE -0.7
041-0 Node 68.6
3 NODE -0.7
041-I Node 76.7
3 NODE -0.7
W1 Supply -86.1 85.1
1.5 SUPPLY 0
File:C:\dwg\PHOENIX-MATTERHORN\Matterhorn FP1.dwg
Date 1/22/2014 Copyright�O 2002-2012 Tyco Fire Protection Products Page 7
Job:Matterhorn Res Hydraulic Calculations/Fluid Delivery Time Analysis
Pipe Data
Pipe Ref. Start End Size Velocity Length Fittings Eq.Len. Total Len. Type HWC
ft/s ft ft ft
007 006 101 1 6.41 16.88 4(BM.Tee-Run);1(BM.Tee-Br);2(BM 19 35.88 Brline 150
.90);
023 026 006 1 12.82 35.76 5(BM.Tee-Run);1(BM.Tee-Br); 10 45.76 Brline 150
028 029 026 1.25 8 16.42 2(BM.Tee-Run);1(BM.Tee-Br); 8 24.42 Cmain 150
031 032 029 1.25 12.92 16.48 2(BM.Tee-Run);1(BM.Tee-Br); 8 24.48 Cmain 150
041 039-0 032 1.25 18.11 7.86 1(coupling);2(BM.90); 13.59 21.45 Cmain 150
181 039-I 039-0 1.25 0 0.73 VALVE 0
042 040-0 039-I 1.25 18.11 0.69 1(coupling); 1.59 2.28 Cmain 150
180 040-I 040-0 1.25 0 1.33 BFP 0
043 041-0 040-I 1.25 18.11 0.46 1(coupling); 1.59 2.05 Cmain 150
179 041-I 041-0 1.25 0 0.5 VALVE 0
050 W1 041-I 2 9.17 94.52 5(us.90); 29.07 123.59 Cmain 150
004 006 103 1 6.41 13.2 2�BM.Tee-Run);1(BM.Tee-Br);3(BM Z2 35.2 Brline 150
.90);
053 029 102 1 7.9 17.75 1(BM.Tee-Run);1(BM.Tee-Br);3(BM Z1 38.75 Brline 150
.90);
034 032 100 1 8.31 19.26 1(BM.Tee-Br);4(BM.90); 25 44.26 Brline 150
File:C:\dwg\PHOENIX-MATTERHORN\Matterhorn FP1.dwg
Date 1/22/2014 Copyright�O 2002-2012 Tyco Fire Protection Products Page 8
Job:Matterhorn Res Hydraulic Calculations
PIPE INFORMATION
Node 1 Elev 1 K-Factor 1 Flow added (q) Nominal ID Fittings L C Factor total (Pt)
Node 2 Elev 2 K-Factor 2 Total flow (Q) Actual ID quantity x (name) = length F Pf per ft elev (Pe) NOTES
T frict (Pf)
(ft) (gpm/psiYz) (gpm) (in) (ft) (ft) (psi) (psi)
Path No: 1
101 22.75 4.2 19 1 4x(BM.Tee-Run)=4 16.88 150 20.5
006 19.5 19 1.101 lx(BM.Tee-Br)=5 19 0.0617 1.4
2x(BM.90)=10 35.88 2.2
006 19.5 19 1 5x(BM.Tee-Run)=5 35.76 150 24.3
026 9 38.1 1.101 lx(BM.Tee-Br)=5 10 0.223 4.5
45.76 10.2
026 9 0 1.25 2x(BM.Tee-Run)=2 16.42 150 39.8
029 9 38.1 1.394 ix(BM.Tee-Br)=6 8 0.0707 0
24.42 1.7
029 9 23.4 1.25 2x(BM.Tee-Run)=2 16.48 150 41.5
032 9 61.5 1.394 lx(BM.Tee-Br)=6 8 0.1719 0
24.48 4.2
03Z 9 24.6 1.25 ix(coupling)=1.59 7.86 150 45.7
039-0 3 86.1 1.394 2x(BM.90)=12 13.59 0.3209 2.6
21.45 6.9
039-0 3 0 1.25 0.73 0 55.6 Flow Switch
039-I 3 86.1 0 0 5.6403 0
0.73 4.1
039-I 3 0 1.25 ix(coupling)=1.59 0.69 150 59.7
040-0 3 86.1 1.394 1.59 0.3209 0
2.28 0.7
040-0 3 0 1.25 1.33 0 60.4 Febco 850
040-I 3 86.1 0 0 5.6781 0 SMALL
1.33 7.6
040-I 3 0 1.25 lx(coupling)=1.59 0.46 150 68
041-0 3 86.1 1.394 1.59 0.3209 0
2.05 0.7
041-0 3 0 1.25 0.5 0 68.6 WILKINS PRV
041-I 3 86.1 0 0 16.1936 0
0.5 8.1
041-I 3 0 2 5x(us.90)=29.07 94.52 150 76.7
W 1 1.5 86.1 1.959 29.07 0.0612 0.6
123.59 7.6
W1 85.1
Path No: 2
103 22.75 4.2 19 1 2x(BM.Tee-Run)=2 13.2 150 20.5
006 19.5 19 1.101 lx(BM.Tee-Br)=5 22 0.0618 1.4
3x(BM.90)=15 35.2 2.2
006 24.3
Path No: 3
102 22.75 4.2 23.4 1 ix(BM.Tee-Run)=1 17.75 150 31.1
029 9 23.4 1.101 lx(BM.Tee-Br)=5 21 0.0909 6
3x(BM.90)=15 38.75 3.5
029 41.5
File:C:\dwg\PHOENIX-MATTERHORN\Matterhorn FP1.dwg
Date 1/22/2014 Copyright�O 2002-2012 Tyco Fire Protection Products Page 9
Job:Matterhorn Res Hydraulic Calculations
PIPE INFORMATION
Path No: 4
100 2Z.75 4.2 24.6 1 ix(BM.Tee-Br)=5 19.26 150 34.4
032 9 24.6 1.101 4x(BM.90)=20 25 0.0998 6
44.26 4.4
032 45.7
* Pressures are balanced to a high degree of accuracy. Values may vary by 0.1 psi due to display rounding.
* Maximum Velocity of 18.11 ft/s occurs in the following pipe(s): (039-0-032), (040-0-039-I), (041-0-040-I)
File:C:\dwg\PHOENIX-MATTERHORN\Matterhorn FP1.dwg
Date 1/22/2014 Copyright�O 2002-2012 Tyco Fire Protection Products Page 10
Job:Matterhorn Res Device Graphs
Pressure vs. Flow Function
Design Area: 1; Supply Ref.: W1; Supply Name:W1
115 � �
110
105
100
95
90
KS
80
75
'y 70
Q
65
N
� 60
y 55
L 50
a 45
40
35
30
25
20
15
]0
5
0 �
0 0 0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0 0
N �n V �n �O 1� 00 O� O
Flow,gpm
Pressure Loss Function
Design Area: 1; BFP Ref.: 180 (Febco 850 SMALL, Size = 1.25)
�o
y_
7.6 psi @ 86.1 gpm
8
7
.y
O.
N 6
L
�
y
Vi 5
N
L
a
4 -
3
2
I ,.
i ,
0 0 0 0 0 0 0 0
-� N R �O oo O N
Flow,gpm
File:C:\dwg\PHOENIX-MATTERHORN\Matterhorn FP1.dwg
Date 1/22/2014 Copyright O 2002-2012 Tyco Fire Protection Products Page 1 1
Job:Matterhorn Res Device Graphs
Pressure Loss Function
Design Area: 1; Valve Ref.: 179 (WILKINS PRV, Size = 1.25)
�oo
yo Iso �
�o
•y
�
N �'�
L
�
y
N 50 -
N
L
a
40
30
20
8.1 psi @ 86.1 gpm
io
� ,
� � � � � , • ; ,
O N O v� O O
M V v� �D l� G1 O� N O
-� N c+i
Flow,gpm
Pressure Loss Function
Design Area: 1; Valve Ref.: 181 (Flow Switch, Size = 1.25)
is.sos
14.808
13.805
12.808
11.808
10.R08
Q 9.808
i 8.80A
7
y 7.808
N
a 6.sos
s.soa
4.1 psi @ 86.1 gpm
4.808
3.808
2.808 I.
I.808 �
o.sox — — -
� � � . � , � � , , � , � . � �
� N V v� �C oc O l�
Flow,gpm
File:C:\dwg\PHOENIX-MATTERHORN\Matterhorn FP1.dwg
Date 1/22/2014 Copyright O 2002-2012 Tyco Fire Protection Products Page 12
CO Worldwide www,tyco-fire.com
Contacts
RAP/D RESPONSE Series LFII Residential Sprinklers
4.9 K-factor Flat-Plate Concealed Pendent
Wet Pipe and Dry Pipe Systems
General tial fires and to improve the chance for
occupants to escape or be evacuated.
Description The Series LFII Residential Flat-Plate _�
The TYCO RAPID RESPONSE Series Concealed Pendent Sprinklers are �
LFII Residential Flat-Plate Concealed shipped with a Disposable Protective l �
Cap.The Protective Cap protects the r �-��_
Pendent Sprinklers(TY2524)are decora- sprinkler during ceiling installation or ,� �� `?
tive,fast response,fusible solder sprin- finish.After ceiling installation is com- L ��-- �
klers designed for use in residential oc- plete, the Protective Cap is removed ! - ��- .�
cupancies such as homes,apartments, and the Cover Plate/Retainer Assem-
dormitories,and hotels. bly is installed. Removing the Protec-
The Cover Plate/Retainer Assembly con- tive Cap is required for proper sprinkler
ceals the sprinkler operating compo- performance.
nents above the ceiling.The flat profile Dry Pipe System Application
of the Cover Plate provides the optimum The Series LFII Residential Flat-Plate The owner is res onsible for maintain-
aesthetically appealing sprinkler design. Concealed Pendent Sprinkler offers a ing their fire protection system and de-
Additionally,the concealed design of the laboratory approved option for design- vices in proper operating condition. The
Series LFII Residential Flat-Plate Con- ing dry pipe residential sprinkler sys- installing contractor or sprinkler manu-
cealed Pendent Sprinklers provides 1/2 tems, whereas, most residential sprin- facturer should be contacted with any
inch(12,7 mm)vertical adjustment.This
adjustment provides a measure of flex- klers are laboratory approved for wet questions.
ibility when cutting fixed sprinkler drops. systems only.
The Series LFII Residential Flat-Plate Through extensive testing, it has been Sprinkler
Concealed Pendent Sprinklers are in- determined that the number of design
tended for use in the following systems: sprinklers(hydraulic design area)for the /dentification
Series LFII Residential Flat-Plate Con-
• wet and dry pipe residential sprin- cealed Sprinklers(TY2524)need not be Number (SIN)
kler systems for one- and two-fam- increased over the number of design
ily dwellings and mobile homes per sprinklers(hydraulic design area)speci- TY2524
NFPA 13D fied for wet pipe sprinkler systems, as
• wet and dry pipe residential sprin- is customary for density/area sprinkler
kler systems for residential occu- systems designed per NFPA 13, 13D,
pancies up to and including four sto- or 13R.
ries in height per NFPA 13R Consequently,the Series LFII Residen-
• wet and dry pipe sprinkler systems tial Flat-Plate Concealed Sprinklers
for the residential portions of any (TY2524)offer the features of non-wa-
occupancy per NFPA 13 ter filled pipe in addition to not having to
increase the number of design sprinklers
The Series LFII Residential Sprinklers (hydraulic design area)for systems de-
have been designed with heat sensitiv- signed to NFPA 13, 13D, or 13R. Non-
ity and water distribution characteristics water filled pipe will permit options for
proven to help in the control of residen- areas sensitive to freezing.
IMPORTANT �
Always refer to Technical Data The Series LFII Residential Flat-Plate
Sheet TFP700 for the "INSTALLER Concealed Pendent Sprinklers(TY2524)
WARNING" that provides cautions described herein must be installed and
with respect to handling and instal- maintained in compliance with this doc-
lation of sprinkler systems and com- ument and the applicable standards of
ponents. Improper handling and in- the National Fire Protection Association,
stallation can permanently damage in addition to the standards of any au-
a sprinkler system or its components thorities having jurisdiction. Failure to
and cause the sprinkler to fail to do so may impair the performance of
operate in a fire situation or cause it these devices.
to operate prematurely.
Page 1 of 6 APRIL 2013 TFP443
TFP443
Page 2 of 6
BODY SEALING WRENCH
(1/2" NP� ASSEMBLY RECESS
/
CAP � SPRINKLER
WRENCHING
AREA
SADDLE
�y PUSH WRENCH
SUPPORT �`� COMPRESSION IN TO ENSURE
CUP WITH �7 � SCREW ENGAGEMENT
ROLL FORMED WITH SPRINKLER
THREADS WRENCHING AREA
LEVER FIGURE 2
� W-TYPE 18
GUIDE I I SPRINKLER WRENCH
PIN
I �i �i �i �i I SOLDER LINK
i i ELEMENT
GUIDE PW I I I I i I
HOUSING � � � �
ii ii
i � __ � � DEFLECTOR
� � �-J� ` _ � � � i (OPERATED
DEFLECTOR I� - �--- - POSITION)
I SPRWKLER/SUPPORT CUP I
�
ASSEMBLY
THREAD INTO I I RETAINER
SUPPORT WITH THREAD
CUP UNTIL DIMPLES
MOUNTING O 0
SURFACE IS
FLUSH WITH
CEILING EJECTION
SPRING
�
SOLDER J COVER PLATE/RETAINER COVER
TAB ASSEMBLY PLATE
FIGURE 1
RAPID RESPONSE SERIES LFII RESIDENTIAL
FLAT-PLATE CONCEALED PENDENT SPRINKLER(TY2524)
2-1/2" DIA. SPRINKLER-
(63,5 mm) 1/2" (12,7 mm) FACE OF SUPPORT CUP
1/2��
THREADED SPRINKLER ASSEMBLY
NPT ADJUSTMENT FITTING
\ ' OPERATED
SPRINKLER
\
1-7/8"±1/4" - COVER JJ
(47,6 mm PLATE SS
RETAINER
I 1/8"GAP ±6,4 mm)
(3,2 mm)
J 1 � � 1
COVER- SPRINKLER- � 7/8"(22,2 mm)
RETAINER SUPPORT CUP 3�1� SOURFACE 1-1/8" (28,6 mm)
ASSEMBLY ASSEMBLY �4$mm� \ t
3-3/16" DIA. DISPOSABLE DEFLECTOR IN
(81,0 mm) TIP PROTECTIVE CAP OPERATED POSITION
FIGURE 3
RAPID RESPONSE SERIES LFII RESIDENTIAL FLAT-PLATE(TY2524)
INSTALLATION DIMENSIONS/PROTECTIVE CAP/ACTIVATED DEFLECTOR
TFP443
Page3of6
Technical Design The number of "design sprinklers"
specified in NFPA 13 for wet pipe sys-
Data Criteria tems is to be applied when designing
dry pipe systems.
Approvals The TYCO RAPID RESPONSE Series Dry Pipe System Water Delivery
UL and C-UL Listed LFII Residential Flat-Plate Concealed When using the Series LFII Residential
The TYCO RAPID RESPONSE Series Pendent Sprinklers (TY2524) are UL Flat-Plate Concealed Pendent Sprinklers
and C-UL Listed for installation in ac- TY2524 in dr i e s rinkler s stems,
LFII Residential Flat-Plate Concealed cordance with this section: � � y p p p y
Pendent Sprinklers are only listed with the time for water delivery must not ex-
the Series LFII Concealed Cover Plates Residential Sprinkler Design Guide ceed 15 seconds for the most remote
having a factory-applied finish. When conditions exist that are outside operating sprinkler.
For details on approvals,refer to the De- the scope of the provided criteria, re- Obstruction to Water Distribution.
sign Criteria section. fer to the Residential Sprinkler Design Sprinklers are to be located in accor-
Guide TFP490 for the manufacturer's dance with the obstruction rules of
Maximum Working Pressure recommendations that may be accept- NFPA 13D, 13R, and 13 as applicable
175 psi (12,1 bar) able to the authority having jurisdiction. for residential sprinklers as well as with
Discharge Coefficient System Type the obstruction criteria described within
K=4.9 GPM/psi'�z(70,6 LPM/bar1z) Per the UL Listing,wet pipe and dry pipe the Technical Data Sheet TFP490.
systems may be utilized. Per the C-UL Operational Sensitivity
Temperature Rating Listing, only wet pipe systems may be
Sprinkler: 160°F(71°C) utilized. Install sprinklers relative to the ceiling
Cover Plate: 139°F(59°C) mounting surface as shown in Figure 3.
Refer to Technical Data Sheet TFP485
Vertical Adjustment about the use of Residential Sprinklers The Series LFII Residential Flat-Plate
1/2 inch (12,7 mm) in residential dry pipe systems. Concealed Pendent Sprinklers must
not be used in applications where the
Finishes Ceiling Types air pressure above the ceiling is greater
Refer to the Ordering Procedure section. Smooth flat horizontal, or beamed, or than that below. Down drafts through
sloped, in accordance with the 2013 the Support Cup can delay sprinkler op-
Physical Characteristics Edition of NFPA 13D, 13R or 13 as eration in a fire situation.
Cover Plate/Retainer Assembly: applicable.
Cover Plate . . . . . . . . . . . . . Copper Sprinkler Spacing
Ejection Spring . . . . Stainless Steel Hydraulic Design The minimum spacing between sprin-
Retainer . . . . . . . . . . . . . . . . Brass (NFPA 13D and 13R) klers is 8 feet (2,4 m). The maximum
For systems designed to NFPA 13D or spacing between sprinklers cannot ex-
Sprinkler/Support Cup Assembly: NFPA 13R,the minimum required sprin- ceed the length of the coverage area
Body . . . . . . . . . . . . . . . . . . . Brass kler flow rate are given in Tables A and (Table A)being hydraulically calculated
Cap . . . . . . . . . . . . . . . . . . . Bronze g as a function of temperature rating (e.g.,a maximum of 12 feet for a 12 ft.x
Saddle. . . . . . . . . . . . . . . . . . Brass and the maximum allowable coverage 12 ft. coverage area or 20 feet for a 20
Sealing Assembly . . . . . . .Beryllium areas.The sprinkler flow rate is the mini- ft.x 20 ft. coverage area.)
Nickel w/TEFLON mum required discharge from each of
Soldered Link Halves . . . . . . Nickel the total number of"design sprinklers"
Lever . . . . . . . . . . . . . . . . . . Bronze as specified in NFPA 13D or NFPA 13R.
Compression Screw . . . . . . . Brass The number of"design sprinklers"spec-
Deflector . . . . . . . . . . . . . . . Bronze ified in NFPA 13D and 13R for wet pipe
Guide Pin Housing. . . . . . . . Bronze systems is to be applied when designing
Guide Pins . . . . . . . . . . . . . Bronze dry pipe systems.
Support Cup . . . . . . . . . . . . . . Steel
Hydraulic Design
Operation (NFPA 13)
For systems designed to NFPA 13,the
When exposed to heat from a fire,the number of design sprinklers is to be
Cover Plate,which is normally soldered the four most hydraulically demanding
to the Retainer at three points,falls away sprinklers.The minimum required dis-
to expose the Sprinkler/Support Cup As- charge from each of the four sprinklers
sembly.At this point,the Deflector,sup- is to be the greater of the following:
ported by the Guide Pins, drops down
to its operated position. •The flow rates given in Tables A and
B as a function of temperature rating
The Solder Link Element of the Sprinkler/ and the maximum allowable cover-
Support Cup Assembly is comprised of age area
two link halves that are soldered togeth- .A minimum discharge of 0.1 gpm/ft2.
er with a thin layer of solder. When the over the "design area" comprised of
rated temperature is reached,the sol- the four most hydraulically demand-
der melts and the two link halves sepa- ing sprinklers for the actual coverage
rate, allowing the sprinkler to activate areas being protected by the four
and flow water. sprinklers
TFP443
Page 4 of 6
WET PIPE SYSTEM
Minimum Flow and Residual Pressure�b,°�
Maximum Maximum
Coverage Spacing Ordinary Temp Rating
Area 160°F(71°C)
Ft.x Ft. Ft' Deflector to Installation Minimum
(m x m) (m) Flow Pressure Ceiling Type Spacing
GPM PSI Ft.
(L/min) (bar) (m�
12 x 12 12 13 7.0 Smooth
(3,7 x 3,7) (3,7) (49,2) (0,48) Ceilings 7/8 to
14 x 14 14 13 �� 1-1/8 inches.
(4,3 x 4,3) (4,3) 49,2) (0,48) Beamed
Ceilings per
16 x 16 16 13 �•� NFPA 13D Concealed $
(4,9 x 4,9) (4,9) (49,2) (0,48) 13R,or 13 �2'4�
18 x 18 18 17 �2,0 Installed in
(5,5 x 5,5) (5,5) (64,3) (0,83) beam 7/8 to
1-1/8 inches
20 x 20 20 20 16.7 below bottom
(6,1 x 6,1) (6,1) (75,7) (1,15) of beam
(a) For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest
coverage area for which Hydraulic Design section under the Design Criteria are stated.
(b) The Minimum Flow requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pres-
sures are calculated using the nominal K-factor.Refer to"Hydraulic Design"in the Design Criteria section for details.
(c) For NFPA 13 residential applications,the greater of 0.1 gpm/ft.2 over the design area or the flow in accordance with the
criteria in this table must be used.
TABLE A
WET PIPE SYSTEM
SERIES LFII RESIDENTIAL FLAT-PLATE CONCEALED PENDENT SPRINKLER(TY2524)
NFPA 13D, 13R,AND 13 HYDRAULIC DESIGN CRITERIA
DRY PIPE SYSTEM
Maximum Minimum Flowand Residual Pressure�b>
Coverage Maximum
Area�a> Spacing Ordinary Temp Rating
Ft.x Ft.
Ft. 160°F(71°C) Deflectorto Installation Minimum
(m x m) �m) Flow Pressure Ceiling Type Spacing
GPM PSI Ft.
(L/min) (bar) (m)
12 x 12 12 15 9.4 Smooth
(3,7 x 3,7) (3,7) (56,8) (0,65) Ceilings 7/8 to
14 x 14 14 15 9 4 1-1/8 inches.
(4,3 x 4,3) (4,3) (56,8) (0,65) Beamed
Ceilings per
16 x 16 16 16 10,7 NFPA 13D Concealed $
(4,9 x 4,9) (4,9) (60,6) (0,74) 13R,or 13 �2'4�
18 x 18 18 17 12.0 Installed in
(5,5 x 5,5) (5,5) (64,3) (0,83) beam 7/8 to
1-1/8 inches
20 x 20 20 21 18,4 below bottom
(6,1 x 6,1) (6,1) (79,5) (1,27) of beam
(a) For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest
coverage area for which Hydraulic Design section under the Design Criteria are stated.
(b) The Minimum Flow requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual
pressures are calculated using the nominal K-factor.Refer to"Hydraulic Design"in the Design Criteria section for details.
(c) For NFPA 13 residential applications,the greater of 0.1 gpm/ft.z over the design area or the flow in accordance with the
criteria in this table must be used.
TABLE B
DRY PIPE SYSTEM
SERIES LFII RESIDENTIAL FLAT-PLATE CONCEALED PENDENT SPRINKLER(TY2524)
NFPA 13D, 13R,AND 13 HYDRAULIC DESIGN CRITERIA
TFP443
Page5of6
Installation Step 6.Screw on the Cover Plate/Re- Automatic sprinklers must never be
tainer Assembly until its flange contacts painted, plated, coated, or otherwise
The TYCO RAPID RESPONSE Series the ceiling. Do not continue to screw altered after leaving the factory. Modi-
LFII Residential Flat-Plate Concealed on the Cover Plate/Retainer Assembly fied or overheated sprinklers must be
Pendent Sprinklers must be installed in such that it lifts a ceiling panel out of replaced.
accordance with this section: its normal position.
Care must be exercised to avoid dam-
General Instructions If the Cover Plate/Retainer Assembly age to the sprinklers- before, during,
Damage to the Solder Link Element dur- cannot be engaged with the Mounting and after installation. Sprinklers dam-
ing installation can be avoided by han- Cup or the Cover Plate/Retainer Assem- aged by dropping,striking,wrench twist/
dling the sprinkler by the Support Cup bly cannot be engaged sufficiently to slippage, or the like, must be replaced.
contact the ceiling,the Sprinkler Fitting
only;that is,do not apply pressure to the must be repositioned. The owner is responsible for the in-
Solder Link Element(Figure 1). spection,testing, and maintenance of
A leak-tight 1/2 inch NPT sprinkler joint Care and their fire protection system and devices
should be obtained by applying a min- in compliance with this document, as
imum-to-maximum torque of 7 to 14 well as with the applicable standards of
ft.-Ibs. (9,5 to 19,0 Nm). Higher levels Maintenance the National Fire Protection Association
of torque can distort the sprinkler inlet The TYCO RAPID RESPONSE Series �e.g., NFPA 25), in addition to the stan-
with consequent leakage or impairment LFII Residential Flat-Plate Concealed dards of any other authorities having ju-
of the sprinkler. Pendent Sprinkler (TY2524) must be risdiction.Contact the installing contrac-
maintained and serviced in accordance tor or sprinkler manufacturer regarding
Do not attempt to compensate for insuf- any questions.
ficient adjustment in the Cover Plate/ with ths section:
Retainer Assembly by under- or over- gefore closing a fire protection system Automatic sprinkler systems are rec-
tightening the sprinkler. Re-adjust the main control valve for maintenance work ommended to be inspected, tested,
position of the sprinkler fitting to suit. on the fire protection system that it con- and maintained by a qualified Inspec-
trols,obtain ermission to shut down the tion Service in accordance with local
Step 1. Install pendent sprinklers in P requirements and/or national codes.
the pendent position, with the center- affected fire protection system from the
line of the sprinkler perpendicular to the proper authorities and notify all person-
mounting surface. nel who may be affected by this action.
Step 2. Remove the Protective Cap. Absence of a Cover Plate may delay the
Step 3. With pipe-thread sealant ap- sprinkler operation in a fire situation.
plied to the pipe threads, and using the The owner must assure that the sprin-
W-Type 18 Wrench shown in Figure 2, klers are not used for hanging any ob-
install and tighten the Sprinkler/Sup- jects and that the sprinklers are only
port Cup Assembly into the fitting.The cleaned by means of gently dusting with
W-Type 18 Wrench accepts a 1/2 inch a feather duster;otherwise, non-opera-
ratchet drive. tion in the event of a fire or inadvertent
Step 4. Replace the Protective Cap by operation may result.
pushing it upwards until it bottoms out �Nhen properly installed,there is a nomi-
against the Support Cup.The Protec- nal 1/8 inch (3,2 mm) air gap between
tive Cap helps prevent damage to the the lip of the Cover Plate and the ceil-
Deflector and Guide Pins during ceiling ing, as shown in Figure 3.This air gap
installation and/or during application of is necessary for proper operation of the
the finish coating of the ceiling. sprinkler by allowing heat flow from a
fire to pass below and above the Cover
� Plate to help assure appropriate release
of the Cover Plate in a fire situation. If the
As long as the protective Cap remains ceiling needs repainting after sprinkler
in place, the system is considered"Out installation,exercise care to ensure that
Of Service", the new paint does not seal off any of
Step 5.After the ceiling has been com- the air gap. Failure to do so may impair
pleted with the 2-1/2 inch(63 mm)diam- sprinkler operation.
eter hole and in preparation for install- Factory painted Cover Plates must not
ing the Cover Plate/Retainer Assembly, be repainted.They should be replaced,
remove and discard the Protective Cap, if necessary, by factory painted units.
and verify that the Deflector moves up Non-factory applied paint may adversely
and down freely. delay or prevent sprinkler operation in
If the sprinkler has been damaged and the event of a fire.
the deflector does not move up and Do not pull the Cover Plate relative to the
down freely, replace the entire sprinkler Retainer. Separation may result.
assembly. Do not attempt to modify or
repair a damaged sprinkler. Sprinklers which are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
TFP443
Page 6 of 6
Ordering
Procedure
Contact your local distributor for avail-
ability.When placing an order, indicate
the full product description and Part
Number(P/N).
Sprinkler/Support Cup Assembly
Specify: Series LFII (TY2524), K=4.9
(70,6), Residential Flat-Plate Concealed
Pendent Sprinkler without Cover Plate/
RetainerAssembly, P/N 51-114-1-160
Cover Plate/Retainer Assembly
Specify: Series LFII (TY2524), K=4.9
(70,6), Residential Flat-Plate Concealed
Pendent Sprinkler Cover Plate/Retain-
er Assembly with (specify)finish, P/N
(specify):
Ivory(RAL 1015)........... P/N 56-202-0-135
Beige(RAL 1001).......... P/N 56-202-2-135
Pure White(b)(RAL 9010)... P/N 56-202-3-135
Signal White(a)(RAL 9003).. P/N 56-202-4-135
Grey White(RAL 9002) ..... P/N 56-202-5-135
Brown(RAL 8028) ......... P/N 56-202-6-135
Black(RAL 9005).......... P/N 56-202-7-135
Brushed Brass............ P/N 56-202-8-135
Brushed Chrome.......... P/N 56-202-9-135
Custom Paint............. P/N 56-202-X-135
(a)Previously known as Bright White.
(b)Eastern Hemisphere sales only.
Note:All Custom Cover P/ates are painted using
Sherwin Williams Interior Latex Paint.Contact
TYCO Customer Service with any questions
related to custom orders.
Sprinkler Wrench
Specify: W-Type 18 Sprinkler Wrench,
P/N 56-000-1-265
GLOBAL HEADQUARTERS�1400 Pennbrook Parkway,Lansdale,PA 19446�Telephone+1-215-362-0700
Copyright OO 2012 Tyco Fire Products,LP. All rights reserved. t�G.O
TEFLON is trademark of The DuPont Corporation.
CO Worldwide www,tyco-fire.com
Contacts
RAPID RESPONSE Series LFII Residential Sprinklers
4.2 K-factor Horizontal Sidewall
Wet Pipe and Dry Pipe Systems
General Escutcheon reduces the accuracy to
which the pipe nipples to the sprinklers
Description must be cut. ��-�
The Series LFII Residential Sprinklers ��' �� _��
The TYCO RAPID RESPONSE Series have been designed with heat sensitivity ,� �
LFII Residential Horizontal Sidewall and water distribution characteristics '��.,�� , � �
Sprinklers (TY1334) are decorative, proven to help in the control of residen- •
fast response,frangible bulb sprinklers tial fires and to improve the chance for
designed for use in residential occupan- occupants to escape or be evacuated. �
-s.
cies such as homes,apartments,dormi- ' .� �
tories, and hotels.When aesthetics and � '
optimized flow characteristics are the Dry Pipe System Application
major consideration, the Series LFII The Series LFII Residential Horizontal - �,.
Residential Sidewall Sprinklers(TY1334) and Recessed Horizontal Sidewall
should be the first choice. Sprinklers offers a laboratory approved
option for designing dry pipe residen-
The Series LFII Residential Sprinklers tial sprinkler systems, whereas, most
are intended for use in the following residential sprinklers are laboratory Snrinkler
scenarios: approved for wet systems only. M
• wet and dry pipe residential sprinkler Through extensive testing, it has been Identification
systems for one- and two-family determined that the number of design
dwellings and mobile homes per NFPA sprinklers (hydraulic design area) for Number (SIN)
13D the Series LFII Residential Horizontal TY1334
• wet and dry pipe residential sprinkler Sidewall Sprinklers (TY1334) need not
systems for residential occupancies be increased over the number of design
up to and including four stories in sprinklers (hydraulic design area) as
height per NFPA 13R specified for wet pipe sprinkler systems,
as is accustomed for density/ area
• wet and dry pipe sprinkler systems sprinkler systems designed per NFPA
for the residential portions of any 13.
occupancy per NFPA 13 Consequently,the Series LFII Residential
The recessed version of the Series Sprinklers offer the features of non-water
LFII Residential Sprinklers is intended filled pipe in addition to not having to
for use in areas with finished walls. increase the number of design sprin-
It employs a two-piece Style 20 klers(hydraulic design area)for systems
Recessed Escutcheon. The Recessed designed to NFPA 13, 13D, or 13R.
Escutcheon provides 1/4 inch (6,4 mm) Non-water filled pipe will permit options
of recessed adjustment or up to 1/2 inch for areas sensitive to freezing.
(12,7 mm) of total adjustment from the
flush mounting surface position. The �
adjustment provided by the Recessed The Series LFII Residential Horizontal
Sidewall Sprinklers described herein
must be installed and maintained in
IMPORTANT compliance with this document and the
Always refer to Technical Data applicable standards of the National Fire
Sheet TFP700 for the "INSTALLER Protection Association, in addition to the
WARNING" that provides cautions standards of any authorities having juris-
with respect to handling and instal- diction. Failure to do so may impair the
lation of sprinkler systems and Performance of these devices.
components. Improper handling and The owner is responsible for maintaining
installation can permanently damage a their fire protection system and devices
sprinkler system or its components and in proper operating condition. The
cause the sprinkler to fail to operate in installing contractor or sprinkler manu-
a fire situafion or cause it to operate facturer should be contacted with any
prematurely. questions.
Page 1 of 6 APRIL 2013 REV A TFP410
TFP410
Page2of6
Components: 5 3 2 1
1 - Frame WRENCH
2 - Button Assembly FLATS
3 - Sealing Assembly p
4 - Bulb �
5 - Compression Screw
6 - Deflector* TOP-OF- 6* 4 7/16" (11,1 mm)
DEFLECTOR � NOMINAL 2-7/8" DIA.
*Temperature rating � MAKE-IN (73,0 mm)
is indicated on top � D
of Deflector. CENTERLINE
OF WATERWAY
7/16"
(11,1 mm) � STYLE 20
1/2" NPT RECESSED
1-5/8" y� ESCUTCHEON
END-OF- ~(41,3 mm) ESCUTCHEON
DEFLECTOR 2-1/4" PLATE SEATING
BOSS (57,2 mm) SURFACE
FIGURE 1
RAPID RESPONSE SERIES LFII RESIDENTIAL
HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS(TY1334)
7/16±1/8"
�(11,1±3,2 mm)
MOUNTING FACE OF / WRENCH RECESS
SURFACE SPRINKLER � (END "A" USED
FITTING FOR TY1334)
TOP-OF- CLOSURE
DEFLECTOR } FIGURE 3
\ TY1334 I W-TYPE 6
j� 2-7/8" DIA. SPRINKLER WRENCH
(73,0 mm)
2-1/4" DIA. WRENCH
� a (57,2 mm) RECESS
7/16" �
(11,1 mm)
MOUNTING �
PLATE
END-OF-
DEFLECTOR 1/8" �
BOSS (3,2 mm)
PUSH WRENCH
1-3/8" (34,9 mm) 1/2" (12,7 mm) IN TO ENSURE
1-1/8"(28,6 mm) 1/4" (6,4 mm) ENGAGEMENT
WITH SPRINKLER
FIGURE 2 WRENCHING AREA
STYLE 20 RECESSED ESCUTCHEON FIGURE 4
FOR USE WITH THE RAPID RESPONSE SERIES LFII RESIDENTIAL W-TYPE 7 RECESSED
HORIZONTAL SIDEWALL SPRINKLER(TY1334) SPRINKLER WRENCH
TFP410
Page3of6
Technical System Types Operational Sensitivity
Per the UL Listing, wet pipe and dry The sprinklers are to be installed with an
Data pipe systems may be utilized. Per the end-of-deflector-boss to wall distance
C-UL Listing, only wet pipe systems of 1-1/4 to 6 inches.
may be utilized. In addition the top-of-deflector-to-
Approvals
UL Listed for use with wet pipe and dry Refer to Technical Data Sheet TFP485 ceiling distance is to be within the range
pipe systems about the use of Residential Sprinklers (Tables A and B) being hydraulically
in residential dry pipe systems. calculated.
NSF Certified to NSF/ANSI 61
C-UL Listed for use only with wet pipe Ceiling Types Sprinkler Spacing
systems Smooth flat horizontal, or beamed, or The minimum spacing between sprin-
sloped, in accordance with the 2013 klers is 8 feet (2,4 m). The maximum
NYC Approved under MEA 44-03-E Edition of NFPA 13D, 13R, or 13 as spacing between sprinklers cannot
For details on these approvals, refer to applicable. exceed the width of the coverage area
the Design Criteria section. (Tables A and B) being hydraulically
Hydraulic Design calculated(e.g., maximum 12 feet for a
Maximum Working Pressure (NFPA 13D and 13R) 12 ft. x 12 ft. coverage area, or 16 feet
175 psi (12,1 bar) For systems designed to NFPA 13D for a 16 ft. x 20 ft, coverage area.).
or NFPA 13R, the minimum required
Discharge Coefficient sprinkler flow rates are given in Tables
A and B as a function of temperature
K=4.2 GPM/psi1�2 (60,5 LPM/bar��2) rating and the maximum allowable
coverage areas.The sprinkler flow rate
Temperature Rating is the minimum required discharge
155°F(68°C)or 175°F(79°C) from each of the total number of
"design sprinklers" as specified in
Finishes NFPA 13D or NFPA 13R.The number of
Signal or Pure White "design sprinklers" specified in NFPA
Chrome Plated 13D and 13R for wet pipe systems is
Natural Brass to be applied when designing dry pipe
Physical Characteristics systems.
Frame . . . . . . . . . . . . . . . . . . . . Brass Hydraulic Design
Button . . . . . . . . . . . . . . . . . . .Copper �NFPA 13)
Sealing Assembly . . . . . . . . Beryllium For systems designed to NFPA 13,
Nickel w/TEFLON the number of design sprinklers is
Bulb (3 mm). . . . . . . . . . . . . . . . Glass to be the four most hydraulically
Compression Screw . . . . . . . . Bronze demanding sprinklers. The minimum
Deflector . . . . . . . . . . . . . . . . .Copper required discharge from each of the
four sprinklers is to be the greater of
Operation the following:
The glass bulb contains a fluid that • The flow rates given in Tables A and
expands when exposed to heat.When B as a function of temperature rat-
the rated temperature is reached, the ing and the maximum allowable
fluid expands sufficiently to shatter the coverage area
glass bulb, allowing the sprinkler to . A minimum discharge of 0.1 gpm/ft2
activate and flow water. over the "design area" comprised of
the four most hydraulically demand-
Des� n ing sprinklers for actual coverage ar-
g eas protected by the four sprinklers
Criteria The number of "design sprinklers"
The TYCO RAPID RESPONSE specified in NFPA 13 for wet pipe
Series LFII Residential Horizontal systems is to be applied when
and Recessed Horizontal Sidewall designing dry pipe systems.
Sprinklers(TY1334)are UL and C-UL Dry Pipe System Water Delivery
Listed for installation in accordance When using the Series LFII Residential
with the following criteria. Horizontal Sidewall Sprinklers(TY1334)
in dry pipe sprinkler systems,the time
Residential Sprinkler Design Guide for water delivery must not exceed 15
When conditions exist that are outside seconds for the most remote operating
the scope of the provided criteria, refer sprinkler.
to the Residential Sprinkler Design
Guide TFP490 for the manufactur- Obstruction to Water Distribution
er's recommendations that may be Sprinklers are to be located in accor-
acceptable to the local authority having dance with the obstruction rules of
jurisdiction. NFPA 13D, 13R, and 13 as applicable
for residential sprinklers as well as
with the obstruction criteria described
within the TYCO Technical Data Sheet
TFP490.
TFP410
Page4of6
WET PIPE SYSTEM
Max.Coverage Max. Minimum Flow and Residual Pressure�b,c�
Area�a� Spacing Ordinary Temp.Rating Intermediate Temp.Rating
Width x Length ld> Ft. 155°F(68°C) 175°F(79°C) Minimum
Ft.x Ft. �m) Flow Pressure Flow Pressure Deflector to Installation Spacing
(m x m) GPM PSI GPM PSI Ceiling Type Ft.
(L/min) (bar) (L/min) (bar) (m�
12 x 12 12 12 8.2 12 8.2
(3,7 x 3,7) (3,7) (45,4) (0,57) (45,4) (0,57)
14 x 14 14 14 11.1 16 14.5
(4,3 x 4,3) (4,3) (53,0) (0,77) (60,6) (1,00)
16 x 16 16 16 14.5 16 14.5 4 to
(4,9 x 4,9) (4,9) (60,6) (1,00) (60,6) (1,00) 6 inches
16 x 18 16 19 20.5 19 20.5
(4,9 x 5,5) (4,9) (71,9) (1,41) (71,9) (1,41)
16 x 20 16 23 30.0 23 30.0 Recessed
(4,9 x 6,1) (4,9) (87,1) (2,07) (87,1) (2,07) Escu�tchteon2or 8
12 x 12 12 13 9.6 13 9.6 non-recessed (2,4)
(3,7 x 3,7) (3,7) (49,2) (0,66) (49,2) (0,66) per NFPA 13D,
13R,or 13
14 x 14 14 17 16.4 18 18.4
(4,3 x 4,3) (4,3) (64,3) (1,13) (68,1) (1,27)
16 x 16 16 18 18.4 18 18.4 6 to
(4,9 x 4,9) (4,9) (68,1) (1,27) (68,1) (1,27) 12 inches
16 x 18 16 21 25.0 21 25.0
(4,9 x 5,5) �4,9) ��9,5) �1,�2) ��9,5) �1,�2)
16 x 20 16 26 38.3. 26 38.3.
(4,9 x 6,1) (4,9) (98,4) (2,64) (98,4) (2,64)
(a) For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which
hydraulic design criteria are stated.
(b) Requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K-
factor.Refer to Hydraulic Design under the Design Criteria section.
(c) For NFPA 13 residential applications,the greater of 0.1 gpm/ftz over the design area or the flow in accordance with the criteria in this table must be
used.
(d) The Width x Length dimension refers to the Width(backwall where the sprinkler is located)times the Length(horizontal throw of sprinkler).
TABLE A
WET PIPE SYSTEM
SERIES LFII RESIDENTIAL HORIZONTAL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS(TY1334)
NFPA 13D, 13R,AND 13 HYDRAULIC DESIGN CRITERIA
TFP410
Page5of6
DRY PIPE SYSTEM
Max.Coverage Max. Minimum Flow and Residual Pressure�b,°1
Area�a> Spacing Ordinary Temp.Rating Intermediate Temp.Rating
Width x Length(dl Ft. 155°F(68°C) 175°F(79°C) Minimum
Ft.x Ft. �m� Flow Pressure Flow Pressure Deflector to Installation Spacing
(m x m) GPM PSI GPM ps� Ceiling Type Ft.
(L/min) (bar) (L/min) (bar) �m)
12 x 12 12 12 8.2 12 8.2
(3,7 x 3,7) (3,7) (45,4) (0,57) (45,4) (0,57)
14 x 14 14 16 14.5 16 14.5
(4,3 x 4,3) (4,3) (60,6) (1,00) (60,6) (1,00)
16 x 16 16 16 14.5 16 14.5 4 to
(4,9 x 4,9) (4,9) (60,6) (1,00) (60,6) (1,00) 6 inches
16 x 18 16 19 20.5 N/A N/A
(4,9 x 5,5) (4,9) (71,9) (1,41)
16 x 20 16 23 30.0 Recessed
(4,9 x 6,1) (4,9) (87,1) (2,07) N/A N/A Escu�tchteon2or 8
12 x 12 12 13 9.6 13 9.6 non-recessed (2,4)
(3,7 x 3,7) (3,7) (49,2) (0,66) (49,2) (0,66) per NFPA 13D,
13R,or 13
14 x 14 14 18 18.4 18 18.4
(4,3 x 4,3) (4,3) (68,1) (1,27) (68,1) (1,27)
16x16 16 18 18.4 21 25.0 6to
(4,9 x 4,9) (4,9) (68,1) (1,27) (79,5) (1,72) 12 inches
16 x 18 16 21 25.0 21 25.0
(4,9 x 5,5) �4,9) ��9,5) �1,�2) ��9,5) �1,�2)
(4 9 x 61) (4,g) N/A N/A N/A N/A
(a) For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which
hydraulic design criteria are stated.
(b) Requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K-
factor.Refer to Hydraulic Design under the Design Criteria section.
(c) For NFPA 13 residential applications,the greater of 0.1 gpm/ftz over the design area or the flow in accordance with the criteria in this table must be
used.
(d) The Width x Length dimension refers to the Width(backwall where the sprinkler is located)times the Length(horizontal throw of sprinkler).
TABLE B
DRY PIPE SYSTEM
SERIES LFII RESIDENTIAL HORIZONTAL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS(TY1334)
NFPA 13D, 13R,AND 13 HYDRAULIC DESIGN CRITERIA
TFP410
Page6of6
Installation Step B. After installing the Style 20 damaged by dropping,striking,wrench
Mounting Plate over the sprinkler twist/slippage, or the like, must be
The TYCO RAPID RESPONSE threads and with pipe-thread sealant replaced. Also, replace any sprinkler
Series LFII Residential Horizontal applied to the pipe threads, hand- that has a cracked bulb or that has lost
and Recessed Horizontal Sidewall tighten the sprinkler into the sprinkler liquid from its bulb. (Ref. Installation
Sprinklers (TY1334) must be installed fitting. Section.)
in accordance with this section. Step C. Tighten the sprinkler into the The owner is responsible for the
sprinkler fitting using only the W-Type inspection,testing,and maintenance of
General Instructions 7 Recessed Sprinkler Wrench (Figure their fire protection system and devices
Do not install any bulb type sprinkler if 4).With reference to Figure 1,apply the in compliance with this document, as
the bulb is cracked or there is a loss of �/_Type 7 Recessed Sprinkler Wrench well as with the applicable standards of
liquid from the bulb. With the sprinkler to the sprinkler wrench flats. the National Fire Protection Association
held horizontally, a small air bubble (e.g. NFPA 25), in addition to the
should be present.The diameter of the Step D. After the ceiling has been
air bubble is approximately 1/16 inch installed or the finish coat has been standards of any authorities having
(1,6 mm). applied, slide on the Style 20 Closure Jurisdiction. Contact the installing
over the Series LFII Residential contractor or sprinkler manufacturer
A leak-tight 1/2 inch NPT sprinkler Sprinkler and push the Closure over the regarding any questions.
joint should be obtained by applying a Mounting Plate until its flange comes in Automatic sprinkler systems are recom-
minimum to maximum torque of 7 to 14 contact with the wall. mended to be inspected, tested, and
ft. Ibs. (9,5 to 19,0 Nm). Higher levels maintained by a qualified Inspection
of torque can distort the sprinkler Inlet Service in accordance with local
with consequent leakage or impairment Care and
of the sprinkler. requirements and/or national codes.
0o not attempt to compensate Maintenance Ordering
for insufficient adjustment in an The TYCO RAPID RESPONSE
Escutcheon Plate by under- or over- Series LFII Residential Horizontal procedure
tightening the Sprinkler. Re-adjust the and Recessed Horizontal Sidewall
position of the sprinkler fitting to suit. Sprinklers(TY1334)must be maintained Contact your local distributor for
and serviced in accordance with this availability. When placing an order,
Series LFII Residential Horizontal section. indicate the full product name and Part
Sidewall Sprinklers Number(P/N).
The Series LFII Residential Horizontal Before closing a fire protection system
Sidewall Sprinklers must be installed main control valve for maintenance Sprinkler Assembly
in accordance with the following Work on the fire protection system Specify: Series LFII (TY1334), K=4.2,
instructions. that it controls, obtain permission to Residential Horizontal Sidewall
shut down the affected fire protection Sprinkler, (specify)temperature rating,
Step 1. Install horizontal sidewall sprin- systems from the proper authorities (specify)finish, P/N (specify).
klers in the horizontal position with their and notify all personnel who may be iss°F(68°c)
centerline of waterway perpendicular to affected by this action. NatUrai arass................PiN 5i-zii-i-i55
the backwall and parallel to the ceiling. . PUre wn�te�RA�soio�'........P/N 51-211-3-155
The word "TOP" on the Deflector is to Absence of the outer piece of an Signal White(RAL9003) .......P/N 51-211-4-155
face towards the ceiling with the front escutcheon, which is used to cover Chrome Plated.............. P/N 51-211-9-155
edge of the Deflector parallel to the a clearance hole, can delay sprinkler ��s°F(79°c)
ceiling. operation in a fire situation. Naturai Brass................PiN si-zii-l-i�s
Ste 2. With i e-thread sealant The owner must assure that the sprin- Pure wn�te(Ra�soio)'........P/N 51-211-3-175
p p p Signal White(RAL9003) .......P/N 51-211-4-175
applied to the pipe threads, hand klers are not used for hanging any Chrome Plated.............. P/N 51-211-9-175
tighten the sprinkler into the sprinkler objects and that the sprinklers are only
fitting. cleaned by means of gently dusting `Eastern Hemisphere sales only.
with a feather duster; otherwise, non-
Step 3. Tighten the sprinkler into the operation in the event of a fire or inad- Recessed Escutcheon
sprinkler fitting using only the W-Type vertent operation may result. Specify: Style 20 Recessed
6 Sprinkler Wrench (Figure 3). With Escutcheon with (specify�)finish, P/N
reference to Figure 1, apply the W-Type Sprinklers which are found to be �specify').
6 Sprinkler Wrench to the wrench flats. leaking or exhibiting visible signs of
corrosion must be replaced. `Refer to Technical Data Sheet TFP770.
Series LFII Residential Recessed Automatic sprinklers must never be Sprinkler Wrench
Horizontal Sidewall Sprinklers painted, plated, coated, or otherwise Specify W-Type 6 Sprinkler Wrench,
The Series LFII Residential Recessed altered after leaving the factory. P/N 56-000-6-387.
Horizontal Sidewall Sprinklers must Modified sprinklers must be replaced.
be installed in accordance with the Sprinklers that have been exposed to Specify W-Type 7 Sprinkler Wrench,
following instructions. corrosive products of combustion, but P�N 56-850-4-001.
Step A. Install recessed hori- have not operated,should be replaced
zontal sidewall sprinklers in the hori- if they cannot be completely cleaned
zontal position with their centerline by wiping the sprinkler with a cloth or
of waterway perpendicular to the by brushing it with a soft bristle brush.
backwall and parallel to the ceiling.The Care must be exercised to avoid
word "TOP" on the Deflector is to face damage to the sprinklers - before,
towards the ceiling. during, and after installation.Sprinklers
GLOBAL HEADQUARTERS�1400 Pennbrook Parkway,Lansdale,PA 19446�Telephone+1-215-362-0700
Copyright OO 2013 Tyco Fire Products,LP. All rights reserved. t�G.O
TEFLON is trademark of The DuPont Corporation.
• • - 1 • •
. .. - ' • - � ' - - ' -• • -
L�STEO
UL U��� APPLICATION
� The Pressure Reducing Valve automatically reduces a higher
'�� .��..�' - � �' inlet pressure to a steady lower downstream pressure re-
\�'�� � "' F gardless of changing flow rate and/or varying inlet pressure
- _ ,•�� in a fire protection system.This valve's pilot control system
� ,_� �� L�� , is very sensitive to slight downstream pressure fluctuations
and will automatically open or close to maintain the desired
SIZES pressure setting.
GLOBE: Flanged ends ❑ 1 1/2"thru 8"(class 150) MATERIALS
❑ 1 1/2"thru 6"(class 300) Main Valve Body&Bonnet Ductile IronASTMA536
Threaded ❑ 1 1/2"thru 3" Disc Guide & Seat BronzeASTM B 61
Grooved ❑ 1 1/2", 2", 3", 4" &6" Disc Buna-N Rubber
ANGLE: Flanged ends ❑ 2"thru 6" (class 150) Diaphragm Nylon reinforced Buna-N
❑ 2"thru 6" (class 300) Stem &Spring Stainless Steel
Threaded ❑ 1 1/2"thru 3" UUULC LISTING
Grooved ❑ 2", 3" &4" (CIaSS 300� 3001b Flange 1501b Flange Globe Body Angle Body
TEMPERATURE RATING: ❑water 33°F to 180°F Size Grooved Grooved
PILOT SPRING RANGE: ❑ 30-165 psi u� u�C u� u�C u� u�
❑ Pressure differentia1,10 psi min. 1 1�2 �� `
2" • • • • •
MAX.INLETPRESSURE: ❑ 300 psi (class 300) 21i2�� � � � �
FEATURES 3" • • • • •
❑ Epoxy Coated, FDA approved 4�� ' ' ` ' '
❑ Pilot Assembly 6 � � ` � �
• Flowclean strainer sizes 1 1/2"-3" 8 � � �
( ) 10° • •
• "Y"type strainer(sizes 4"-10")
• Opening speed control(sizes 1 1/2"-3") - �� �i O �
• Isolation Valve(sizes 4"-10") � p p °� i
MAIN VALVE OPTIONS � �- �� --� _ °�'
Size _ �� � ,. ����G FFFF
. ��.�E. o i � o �
X - Class 150 flange(175 psi max.) �
TH - Threaded ends(400 psi max.) r E=E r, ,���s,E����o�k� ���AEAS� EEEE
KB - Viton rubber �
SS - Stainless Steel Seat r' 1 ° ��
AN - Angle body �� � � - ��Er
D - Check Valve in pilot i I� - � ;' F'�FF
n�
BB FF
I
G - Groove body �,�- ���.�E. I -:-_=::_:--� �
CS - Cast steel(ASTM A216)main valve �AA I I--AAAA SHCN" V`� _EEE EE
body&bonnet
DIMENSIONS
DIM ANSI CLASS VALVE SIZE inches
11/2 2 21/2 3 4 6 8 10
AA 150 8 1/2 9 3/8 11 12 15 20 25 3/8 29 3/4
AAA 300 9 10 11 5/8 13 1/4 15 5/8 21 26 3/8 31 1/8
AAAA GROOVED 81/2 9 - 121/2 15 20 - -
B 1 1/8 1 1/2 1 11/16 2 9/16 3 3/16 4 5/16 5 5/16 9 1/4
BB GROOVED 115/16 21/8 - 6 41/8 6 - -
C Max. 5 1/2 6 1/2 7 9/16 8 3/16 10 5/8 13 3/8 16 17 1/8
CC Max. 4 3/32 5 - 6 1/2 8 13/16 11 3/32 - -
D 2 13/16 3 5/16 4 4 9/16 5 3/4 7 7/8 10 11 13/16
DD GROOVED 2 13/16 3 5/16 - 4 9/16 5 3/4 7 7/8 - -
EE 150 4 4 3/4 5 1/2 6 7 1/2 10 12 3/4 14 7/8
EEE 300 4 1/4 5 5 7/8 6 3/8 7 7/8 10 1/2 13 1/4 15 9/16
EEEE GROOVED - 4 3/4 - 6 7 1/2 - - -
FF 150 4 3 1/4 4 4 5 6 8 8 5/8
FFF 300 4 1/4 3 1/2 4 5/16 4 3/8 5 5/16 6 1/2 8 1/2 9 5/16
FFFF GROOVED - 31/4 - 41/2 5 - - -
G Mvc. 7 1/2 7 3/4 7 3/4 8 9 9 1/2 10 1/2 11 1/2
GG Max. 8 3/32 8 - 8 1/8 9 5/16 10 1/2 - -
�• •
�• �
Page 1 of 2
OPERATION
The Model ZW109FP utilizes a pressure reducing pilot valve that installs on the discharge side of the control circuitry.The
pilot is a direct acting, normally open, spring loaded, diaphragm actuated valve; the spring being adjustable within a 5.5:1
ratio.The operation of the ZW109FP begins with accurately sizing the valve,then fine tuning the control circuit by adjusting
the pilot spring to the desired downstream pressure.
Inlet pressure is piped to the inlet port of the pressure reducing pilot.A sensing line runs internally from the discharge side
of the pilot to its lower control chamber under the diaphragm. Thus, downstream pressure exceeding the preset acts to
close the pilot while the adjustable spring seeks to keep it open. The result is a modulating action in the pilot that is
transmitted to the bonnet of the main valve.This creates a mirror modulation of the diaphragm assembly in the main valve.
Downstream pressure is maintained within narrow limits regardless of changing flow rates or varying inlet pressures.
FLOW CHARACTERISTICS
Valve Size inches 1 1/2 2 2 1/2 3 4 6 8 10
m m 40 50 65 80 100 150 200 250
Max. Flow Rate (GPM) 160 262 373 576 992 2251 3900 6150
Min. Flow Rate (GPM) 10 15 20 30 50 115 200 300
For basic valves suggested flow calculations are based on flow through Schedule 40 Pipe. Maximum continuous flow is
approx. 20 ft./sec(6.1 meters/sec)&maximum intermittent is approx. 25 ft./sec(7.6 meters/sec)and minimum continu-
ous flow is approx. 1 ft./sec (0.3 meters/sec). Many factors should be considered in sizing pressure reducing valves
including inlet pressure, outlet pressure and flow rates.
TYPICAL INSTALLATION
Underwriters Laboratories requires the MAIN FIRE
HEADER ZW109FP
installation of pressure gauges upstream PRESSURE
and downstream of the Pressure Reduo- �`' REDUCING VALVE
ing Valve.Also, a relief valve of not less �'�'�
than 1/2"in size must be installed on the
downstream side of the pressure control � � �
valve. Adequate drainage for the relief � � �
valve discharge must be provided. � � ��
UL INSTALLATION SPECIFICATIONS �� U ��
REQUIREMENTS MODEL P4000
PRESSURE
The valve is to be installed in accordance RELIEF VALVE �' ��
with the standard for installation of sprin-
kler systems, NFPA 13. �' �
I '�
—�
/ - O DISTRIBUTION TO EACH FLOOR
The valve is to be inspected,tested and � O
� � �
maintained in accordance with the stan- — = �
dard for the inspection,testing and Main- zw,osFP
tenance of Water-Based Fire Protection PRESSURE ,I "��1�=
Systems, NFPA Z�J. REDUCING VALVE MODEL P4000
PRESSURE
SPECIFICATIONS RELIEF VALVE
The Pressure Reducing Valve shall be a single seated, line pressure operated,diaphragm actuated, pilot controlled,globe or
angle valve.The valve shall seal by means of a corrosion-resistant seat and resilient, rectangular seat disc.These and other
parts shall be replaceable in the field;all such service and adjustments to be possible without removing the valve from the line.
The main valve body shall be Ductile Iron ASTM A 536.The stem of the basic valve shall be guided top and bottom by integral
bushings.The basic valve and its pilot control system shall contain no packing glands or stuffing boxes.The diaphragm shall not
be used as a seating surface nor shall pistons be used as an operating medium.All internal and external ferrous surfaces shall
be coated with a high quality,fusion epoxy coating. The pilot control system shall consist of a two-way, normally open, direct
acting,adjustable spring loaded,diaphragm actuated pressure reducing pilot.The pilot control shall be field adjustable from 30
psi to 165 psi; adjustment range not to exceed a 5.5:1 ratio. The Pressure Reducing Valve shall be a WILKINS Model
ZW109FP.
JOB NAME CONTRACTOR
JOB LOCATION ENGINEER
Page 2 of 2
WILKINS a Zurn company, 1747 Commerce Way, Paso Robles, CA 93446 Phone:805/238-7100 Fax:805/238-5766
IN CANADA:ZURN INDUSTRIES LIMITED,3544 Nashua Dr.,Mississauga,Ontario L4V 1L2 Phone:905/405-8272 Fax:905/405-1292
Product Support Help Line: 1-877-BACKFLOW (1-877-222-5356) • Website: http://www.zurn.com
' ' • • � : 1
FEBCOo DOUBLE CHECK ASSEMBLY
BACKFLOW PREVENTION
Characteristics
Physical Properties
Size 1/2", 3/4", 1", 1-1/4", 1-1/2",2" �
Max.Working Pressure 175 PSI (1200 KPa) � � �
Hydrostatic Test Press. 350 PSI (2400 KPa)
Temperature Range 32°F to 140°F (0°C to 60°C) � � �
End Connections Threaded ANSI B2.1
Materials
Valve Body Bronze
Elastomers Silicone
Springs Stainless Steel MODEL 850(1/2"-2")DOUBLE CHECK ASSEMBLY
Agency Compliance
• ANSI/AWWA Conformance (C510-92) Application
• ASSE Listed (Std. 1015) Non-Health Hazard
• CSA
• Approved by the Foundation for Cross Connection OptIO11S
Control and Hydraulic Research at the University of ❑ Wye - Strainer
Southern California.
Model 850 (1/2" - 2") Flow Curves ��2�� 1-1/2"
� zo � zo
a �5 a 15
J �p J 10
m 5 � 5
d �
_ � = 0
0 3 6 9 12 15 18(GPM) 0 20 40 60 80 100 120 (GPM)
3/4" 2"
,.. zo _ 20
� �
a 15 a 15
N N
0 10 0 10
J J
� 5 � 5
m d
x o x p
0 5 10 15 20 25 30(GPM) 0 30 60 90 120 150 180 (GPM)
1"
-- 20 Installation Recommendations
�
a 15
N *
0 1� �
'� 12"Minimum Clearance
a 5
� to Fixed Structure
a� a
= a : B a a 1
0 10 20 30 40 50 60 (GPM) / b o �
� 20
1-1/4" ? �
� 12��
a 15 Minimum
" 1J 10
d 5 FIOW MODEL 850(1/2"-2")
= 0 � Outdoor Installation
0 20 40 60 80 100 120(GPM)
Model 850 (1/2" - 2")
A ITEM DESCRIPTION MATERIALS
9 11 21 1 60 61 21 9.1 1 Body Bronze
1.2
� 1.2 Tailpiece Bronze
C 1.4 O-Ring Silicone
' ° _
2 Cover Bronze
2.2 O-Ring Silicone
3 Seat Noryl
B , _, ° _, 3.1 O-Ring Silicone
� n n 4 POppOt NOryl
5 Seat Disc Silcone
5.1 Disc Retainer Noryl
5.2 Rnd HD Screw Stainless Steel
6 Spring Stainless Steel
3 3.1 8 22 7 1.4 7 Guide Noryl
8 Retainer Spacer Noryl
2 � 9 Ball Valve(w/tap) Brozne
� � _ � � 9.1 Ball Valve Bronze
� _ = 11 Test Cock Bronze
21 Hex HD Capscrew Stainless Steel
� i i � 60 Identification Plate Brass
61 Drive Screw Stick Stainless Steel
E
� 5.1 5 4 5.2 6 � Model 850 (1/2�� - 2���
0 0 Check Assembly
5.1 5 4 7
5.2
Dimensions and Weights
U.S.-Inches(mm) NET WT.
SIZE A B C D E Lbs. (kgs.)
'Iz'� 10(254.00) 1'Iz(38.10) 1'Iz(38.10) 3'Is(79.38) 1�I4(31.75) 4.2(1.91)
31a" 1031a(273.05) 1'Iz(38.10) 1'Iz(38.10) 3'Is(79.38) 1'la(31.75) 4.4(2.00)
1" 12'Iz(317.50) 1'la(47.63) 151s(41.28) 3'Is(85.73) 1'Iz(38.10) 6.8(3.08) 3 3.1 6
1'la" 15'la(403.23) 3(76.20) 2'Iz(63.50) 4'la(107.95) 2'la(57.15) 15.8(7.17)
1'Iz" 1631a(415.93) 3(76.20) 2'Iz(63.50) 4'la(107.95) 2'I4(57.15) 16.2(7.35)
2" 1751a(447.68) 3'Iz(88.90) 2'Iz(63.50) 4'la(107.95) 2'la(57.15) 21.1 (9.57)
Note:Dimensions are nominal.Allowances must be made for normal manufacturing tolerances.
FEBCO Backflow Prevention FEBCO is a product of
P.O.Box 8070•Fresno,CA 93747-8070 �SPX VALVES&CONTROLS'"
559 252-0791 •Fax:559 453-9030•www.FEBCOonline.com
ssa5osm a/o2 Copyright 2002 SPX Valves&Controls ISO 9001 Certified
RESIDENTIAL RISER
P POTTER
� The Symbol of Protection
Service Pressure: Up to 175 PSI (12,07 BAR)
� Minimum Flow Rate for Alarm: 8-10 GPM (30-38 LPM)
� Maximum Surge: 18 FPS (5,5 m/s)
� �� Usage: Listed CPVC plastic piping systems manufactured by
Central Sprinkler Corp.,Grinnell Sprinkler Corp.,Spears
Manufacturing Co., Harvel and IPEX(Scepter).
..�,�-- �_�,.� _ Fits pipe sizes- 1", 1-1/4", 1-1/2"and 2"
Environmental Specifications:
• Indoor use only
��� � • Temperature range:40°F to 120°F(4.5°C to 49°C)
�- � "�
� � Service Use:
One or two family dwelling NFPA-13D
� Flow Switch
�! Enclosure: Die-cast, red powdercoat finish
;,;,�,� Cover held in place with tamper resistant screws.
�
i� Contact Ratings: Two sets of SPDT(Form C)
�;��J �, 15,0 Amps at 125/250 VAC
�' 2.0 Amps at 30 VDC
- Conduit Entrances: Two knockouts provided for 1/2" conduit.
Switch Contacts: SPDT(Form C)
� Contact Rating: 3 Amps at 250VAC
Terminations: 8" No. 22 AWG Wire Leads
Caution: This device is not intended for applications in explosive
environments.
The residential riser is a CPVC sprinkler riser with flow switch,test and the flow switch in the appropriate direction to detect waterflow.The
drain for use with wet sprinkler systems using CPVC plastic piping and paddle must not rub the inside of the TEE or bind in any way.The stem
fittings manufactured by Central Sprinkler Corp.,Grinnell Sprinkler Corp., should move freely when operated by hand. See Fig. 1.
Spears Manufacturing Co., Harvel,and IPEX(Scepter)that use 1", 1-1/ Note: A1/2"NPTfemalefittingisavailableforattachingareliefvalvewhen
4", 1-1/2" or 2" pipe sizes. The flow switch is equipped with a union to required.See Fig 2.Suggested Valves:Watts 530C,Brecco 1/2PR.
accommodate installation in confined spaces.
CAUTION: Do not over-tighten the union nut, hand tighten only!
The flow switch contains two single pole double throw snap action
switches and an adjustable, instantly recycling pneumatic retard. The INSPECTION AND TESTING:Check the operation of the unit by opening
switches are actuated when a flow of 8-10 gallons per minute (30-38 the test and drain connection,if an inspector's test valve is not provided.
liters per minute) or more occurs downstream of the device. The flow The frequency of the inspection and testing and its associated protective
condition must exist for a period of time necessary to overcome the monitoring system should be in accordance with the applicable NFPA
selected retard period. Codes and Standards and/or authority having jurisdiction (manufacturer
INSTALLATION: recommends quarterly or more frequently).
1. Following CPVC manufacturer's instructions for preparation and
gluing of CPVC piping systems,glue the main riser to the main supply ORDERINGINFORMATION
line for the sprinkler heads.
Stock No. Description
2. Usingappropriatefittings,connectthemainwatersupplytothebottom 1119010 1"Riser
of the check valve and the drain connection to an adequate drain line. 1119015 1-1/4"Riser
The riser must be mounted in a vertical position,(arrow on check valve
must point up).See Fig 2. 1119020 1-1/2"Riser
3. Attach gauge to riser.Apply teflon tape to male fitting of gauge only. 1119025 2"Riser
SeeFig2. 5310064 WattsAdjustableReliefValve
4. Select the proper Spears paddle and attach it to the flow switch. 5510132 Brecco 175 PSI Relief Valve
(Paddle size must match the riser pipe size.)See Fig.4. 0090151 Watts Relief Valve Kit(adjustable)
5. Install the flow switch to the main riser.Verify that the o-ring is properly 0090152 Brecco Relief Valve Kit(fixed at 175 PSI)
positioned in its groove.Hand tighten the nut to the union after orienting
Potter Electric Signal Company•2081 Craig Road,St.Louis,MO,63146-4161•Phone:800-325-3936/Canada 888-882-1833•www.pottersignal.com
PRINTED IN USA MFG.#5401083-REV G PAGE 1 OF 2
M KT.#880001 2-3/02
RESIDENTIAL RISER
P POTTER
� The Symbol of Protection
FIG. 1 FIG.2 OPTIONAL
DO NOT LEAVE COVER RELIEF
OFF FOR EXTENOED VALVE KIT
�� PERIOD OF TIME
� PIPING TO
SPRINKLER HEROS
4
RETARD �� FIG.�
ADJUSTING ���
KNOB
MOUNT 50 �
CAUTION: INSVRE ARROW ON
THAT 0-RING IS BASE POINTS
IN O-RING GROOVE IN DIRECTION
BEFORE INSTALLING OF WATERFLOW
SWITCH. �
`\J
3
1" MALE �
FITTING ON
ALL SIZES
i
OwG. �1083-2
RISER MAY BE
1", 1 1/4",
1 1/2"OR 2" ��/
�
� DIRECTION OF
WATERFLOW
� � � Z
UvG.a1063-9
MP1N
APPROX.RETARD SETTINGS(IN SEC.) �'ATER su��v
0 A B C D E
0 10-25 20-40 35-55 50-70 60-90
1O Main Riser
O2 Flow Switch
Retard Adjustment:
To change time,turn retard adjusting knob(either direction)for desired time O Test and Drain DWG. �1083-5
delay.Use the minimum amount of retard necessary to prevent false alarms. O 1/2" NPT female fitting for relief valve
A"B"setting is usually adequate for this. Factory set at"B".
FIG.4 FIG. 5 TYPICALELECTRICALCON- SWITCHTERMINAL COVERTAMPER
NECTIONS CONNECTIONS SWITCH
r� CLAMPING PLATE (SHOWN WITH COVER
DIRECTION OF 2 SETS aF TERMINAL IN PLACE)
WATERFLOW NORMALLY OPEN CONTACIS wqrgqf�pw iONE EOLR fRpM �`
/\ CLOSE ON AIARM pN FIRE PFNEL FIRE PnNEL FIG. V
V \\ � EO�P
� � � � � �i�� ��
iNG� + + +
OwC. K7063-3 �uu w xc xa xc
� � � � �� �HT� �R�� �B��
0�'L.I98t00i9-3
mpOrtant� THE NC ANO NO MARKiNGS P�SITNE OC
7 paddles are furnished Wlth ON TnE SwiTCH NiE FpR �R��T� BEII �d
each flow $W�tCh t� C�CCOIT�' T�E CONTA�CTS nREORE�VER5E0 Qq ryE�TppL p� O�r��'�
wHEN THE OEVICE i5 iN �,���fi1_2 DWG. (f923-3
modate the various sizes and T�E NORMRL CONOITiON.
manufacturers of TEES. The CAUTION:
paddles have raised let- NOTES: An uninsulated section of a
tering that show the pipe 1. The model VSR-SFG has two switches,one can single conductor should not be
size and the TEE manufac- be used to operate a central station, proprietary looped around the terminal and
turer they are to be used or remote signaling unit,while the other is used to serve as two separate con-
with. The proper paddle operate a local audible or visual annunciator. nections. The wire must be
must be used. The paddle 2. For supervised circuits see "Switch Terminal severed,thereby providing su-
must be properly attached and Connections"drawing and caution note (Fig. 6). pervision of the connection in
the screw that holds the pad- the event that the wire be-
dle must be securely tight- comes dislodged from under
ened. the terminal.
PRINTED IN USA MFG.#5401083-REV G PAGE 2 OF 2
MKT.#880001 2-3/02
�'���Q Fire & Building
Products
rapid respanse�'�`
Hann� F�r�E Sarer�u�c���r 5rrsr�nr�
Technical Services: Tel: (800)381-9312/Fax: (800)791-5500
BlazeMaster °
CPVC Fire Sprinkler Pipe & Fittings
Submittal Sheet
General
Descripfion Technical
Tyco� CPVC Pipe and Fittings pro- Da ta
duced by Tyco Fire & Building Prod-
ucts (TFBP) are designed exclusively Sizes :t:, -
for use in wet pipe automatic fire sprin- 3/4"to 3" w ' � � -
kler systems. The Tyco CPVC Pipe Maximum Working Pressure ., -
and Fittings are produced from Blaze- 175 psi .���
Master� CPVC compound that is a �` .__
specially developed thermoplastic Approvals '',�j,, `�i
compound composed of post chlorin- UL, FM, C-UL, NSF, LPCB, MEA, and � ,L
ated polyvinyl chloride (CPVC) resin the City of Los Angeles. (Refer to In- _ ,�
and state of the art additives. Tyco stallation Handbook IH-1900 dated .�'
CPVC Pipe and Fittings are easier to June 2008 for exact listing/approval '�'
install than traditional steel pipe sys- information.) �
tems, and at the same time, provide Manufacture Source
superior heat resistance and strength U.S.A.
as compared to traditional CPVC and
PVC piping materials used in the Material
plumbing trade. Various adapters are �I Pipe: ASTM F442, SDR 13.5
available to connect CPVC pipe to me-
tallic piping. All female pipe thread I:I Fittings: ASTM F438 (Sch. 40) and
adapters have brass inserts for dura- ASTM F439(Sch.80),ASTM F1970
bility. Grooved adapters connect di- Color
rectly to grooved end valves and me- Orange
tallic pipe, with flexible grooved end
couplings.
�
Tyco� CPVC Pipe and Fittings pro-
duced with BlazeMastera CPVC com-
pound described herein must be in-
stalled and maintained in compliance
with this document and with the appli-
cable standards of the National Fire
Protection Association, in addition to
the standards ofany authorities having
jurisdiction. Failure to do so may im-
pair the performance of these devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condifion.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
BlazeMaste�is a registered trademark
of The Lubrizol Corporation
Page 1 of 2 JUNE, 2008 TFP1915
Page 2 of 2 TFP1915
1 nsta Ila tion Lim ite d
Tyco� CPVC Pipe and Fittings pro- Wa rra n t y
duced by Tyco Fire & Building Prod-
ucts (TFBP) are to be installed in Products manufactured by Tyco Fire&
accordance with Installation Hand- Building Products (TFBP) are war-
book IH-1900 dated June 2008. ranted solely to the original Buyer for
ten (10)years against defects in mate-
Ca re a n d rial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
M a i n t e n a n c e warranty will expire ten (10) years
from date of shipment by TFBP. No
The owner is responsible for the in- �niarranty is given for products or com-
spection, testing, and maintenance of ponents manufactured by companies
their fire protection system and de- not affiliated by ownership with TFBP
vices in compliance with this docu- or for products and components which
ment, as well as with the applicable have been subject to misuse,improper
standards of the National Fire Protec- installation, corrosion, or which have
tion Association (e.g., NFPA 25), in not been installed, maintained, modi-
addition to the standards of any fied or repaired in accordance with ap-
authority having jurisdiction. The in- plicable Standards of the National Fire
stalling contractor or product manufac- protection Association, and/or the
turer should be contacted relative to standards of any other Authorities
any questions. Having Jurisdiction. Materials found
Automatic sprinkler systems should be by TFBP to be defective shall be either
inspected,tested,and maintained by a repaired or replaced, at TFBP's sole
qualified Inspection Service in accord- option. TFBP neither assumes, nor
ance with local requirements and/or authorizes any person to assume for it,
national codes. any other obligation in connection with
the sale of products or parts of prod-
� ucts.TFBP shall not be responsible for
sprinkler system design errors or inac-
Before closing a fire profection system curate or incomplete information sup-
control valve for inspection or mainte- Plied by Buyer or Buyer's repre-
nance work on the fire protection sys- sentatives.
tem that it controls, permission to shut In no event shall TFBP be liable, in
down the affected fire protection sys- contract, tort, strict liability or under
tem must first be obtained from the any other legal theory, for incidental,
proper authorities and all personnel indirect,special or consequential dam-
who may be affected by this action ages, including but not limited to labor
must be notified. charges, regardless of whether TFBP
was informed about the possibility of
After placing a fire protection system such damages, and in no event shall
in service, notify the properauthorities TFBP's liability exceed an amount
and advise those responsible formoni- equal to the sales price.
toring proprietary and/or central sta-
tion alarms. The foregoing warranty is made in lieu
of any and all other warranties. ex-
press or implied. including warranties
of inerchantability and fitness for a par-
ticular�uraose•
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law.The invalidity, in
whole or part, of any portion of this
warranty will not affect the remainder.
O 2008 TYCO FIRE 8�BUILDING PRODUCTS,451 North Cannon Avenue, Lansdale, Pennsylvania 19446
� � � �
�. r• r.
�
. � . � �, — ■ • 11
Fig. 22C - Combination
Hanger & Restrainer Application ���
Size Range — 3/4" thru 2" CPVC pipe
Material — Carbon Steel, Pre-Galvanized
. ������ �r8„
Function — Designed to support a CPVC pipe away _ ��'�� �# ��-_
from the corner of a beam. This position allows for easy � '�,��"�I��,�� � �r��
installation of drops or risers without adding additional ..5 ���^'�� �~ � ��,rg�
wood blocks. ; ;, ; �x '' '
Approvals — Underwriters' Laboratories Listed in the USA ���` `• Cf
(UL) and Canada (cUL) for use as a combination hanger and °� yr�u�S HE�araE�
� f.�...
restrainer. ��..� �� ,��
Finish — Pre-Galvanized �`'�.T�-,�' � T�z�����t�T
Note—Approved UL Listed fastener into wood is furnished . �' `��� °� _ �����
with the product. A fastener into light gauge metal may be ;' ;}r � --•..*
ordered separately. Minimum acceptable #10 x 1" hardened `��'��} '' -'
' �j �•---._�,��� �r�„
self threading screw with 5/16" hex washer head. �� � -
Order By— Fig. 22C application is composed of two ��'� ��',���� �-v�: 1 �f�"
standard Fi . 22 models—order two sin les for each han er �, r,`�i '���� ,, �
9 9 9 t.,; ,��:�� �� �fI
and restrainer application required. �� �. �'
� �� f / �`
��� �� ��� �
� ��
�
-_ �� :
����, ,�� .,;� �..�����.
� -�.�� �: -. Y.
. . �� � �`t °.,,y.•
jw �.� � �I � ���
_ � :,.i� ��� ,.
� ��
�
�P�
`� �' �
������ {�
/ �' "��5 �t•����.
,i i;
�.� ��5f1�'I� �-�,"
i '��`�–. ��4 � �'a
_ °•.�� �� � AYI�, /
s r . �.ti� �
r 5~'
� MainCffice/ManufacturingFacility•1375S�rrpsonAve.•(brore,CA 92879•Fh: 909.737.5599•Fax 909.737.0330
• CUstomer Servi ce•800.786.5266
www.tolco.com
�
� � • . . .
�
_ � . . • ��:
Fig. 28M - Offset Hanger and Restrainer for
CPVC Plastic Pipe and IPS Pipe ` �` �5"�TE°
Size Range — 3/4" thru 1-1/4" pipe
Material — Carbon Steel, Electro-Galvanized
Function — Designed to be used as a hanger and restrainer for CPVC piping
where the "stand-off" design will ease installation by eliminating the need for
wood blocking I �
Features —
• Flared edge design protects CPVC pipe from any rough or abrasive A
surfaces
• Unique snap-on design holds pipe firmly in place and allows retrofit
type of installation
• The "Stand-Off" design eliminates the need for wood block extension
• Can be installed on horizontal or vertical piping regardless of mounting �
surface orientation C
• Attaches easily to wood structure with two hex head self-threading
screws furnished with product �B
• Installs easily using rechargeable electrical driver with 5/16" extension
socket eliminating impact tool damage to pipe
• Attaches easily to steel, minimum 18 gauge with (2) 1/4" x 1" tek type
self drilling tapping screws
• cULus Listed as a hanger and a restrainer for fire sprinkler piping
Approvals — Underwriters' Laboratory Listed in the USA(UL) and Canada (cUL)
to support automatic fire sprinkler systems. May be installed into wood using fas-
teners screws. Meets and exceeds the requirements of NFPA 13, 13R and 13D.
Fig. 28M satisfies the UL vertical restraint requirements where needed.
Order By — Figure number and pipe size
PATENT PENDING ,--� _ __________�
r---------?-------.----1 �� � 1
I � � � - - I / I n
� -- ---_____-y
i � . . Q i �--�
I � Q I I i
I . - � I T"'�`T
i ° i i i � �
i i i i i i
i i i i i i
i Q i i i i
i a i i i i
i a a i i i i i
L-___ �� _______ _�_J � � !,=+� RESTRAINT
� �
�
�
�
� �
,�t�. � �
` + L--- --- --L---�-=f
RESTRAINT � '�
�
Fig. 28M
Dimensions •Weights
Max.
Spacing
pipe required per Approx
Size A B C NFPA 13 for Wt./100
CPVC plastic pipe
3/4 2 3/16 3-1/2 5'-6" 9
1 2-1/8 3/16 3-1/2 6'-0" 12
1-1/4 2-5/16 3/16 3-1/2 6'-6" 13
m OFFICE/MANUFACTURING FACILITY•1375 SAMPSON AVE.•CORONA,CA 92879•PH: 951 J37.5599•FAX: 951 J37.0330
CUSTOMER SERVICE•800.786.5266
www.tolco.com
�[�CO Fire & Building
Products
Technical Services: Tel: (800) 381-9312/ Fax: (800)791-5500
Identification Signs
For Sprinkler Systems and Devices
NFPA 13 Signing Requirements
General WARNINGS Care and
The Identification Signs described
Descr�n�/�/'� herein must be installed and main- MaII1 tell aI1 Ce
I�+ tained in compliance with this docu-
Identification Signs (Ref. Figure 1) are ment, as well as with the applicable The following inspection procedure
designed to provide information to the standards of the National Fire Pro- must be performed as indicated, in ad-
end user about the sprinkler system tection Association, in addition to the dition to any specific requirements of
and its components. They are avail- standards of any other authorities hav- the NFPA, and any impairments must
able with a variety of wording combi- �ng jurisdiction. Failure to do so may be immediately corrected.
nations to meet the signing require- impair the performance of these
ments of NFPA 13. devices. The owner is responsible for the in-
The owner is responsible for maintain- spection, testing, and maintenance of
The five basic types of Identification their fire protection system and devic-
Signs are as follows: ing their fire protection system and de- es in compliance with this document,
vices in proper operating condition. as well as with the a licable stan-
Type A- Control Valve Sign The installing contractor or sprinkler pp
T e B- Multi-Pur ose Text Si ns manufacturer should be contacted dards of the National Fire Protection
Yp p g Association(e.g., NFPA 25), in addition
(See Below) with any questions. to the standards of any authority hav-
Type D-Fire Alarm Sign ing jurisdiction. The installing contrac-
Type E- Hydraulic Calculation Sign Technical tor or product manufacturer should be
contacted relative to any questions.
Type B- Identification Signs are avail- �ata It is recommended that automatic sprin-
able with the following text options: kler systems be inspected, tested, and
AIR CONTROL Material&Finish maintained by a qualified Inspection
18 gauge aluminum with mylar facing. Service in accordance with local re-
AIR LINE quirements and/or national codes.
ALARM TEST Width x Height
ANTIFREEZE SYSTEM After placing a fire protection system
AUXILIARY DRAIN Inches (mm) in service, notify the proper authorities
CONTROL VALVE Type A 9 x 7 (229 x 178) and advise those responsible for mon-
itoring proprietary and/or central sta-
DRAIN Type B 6 x 2 (152 x 51) tion alarms.
DRAIN VALVE Type C 73/a x 1'/a (197 x 32) INSPECTION PROCEDURE
INSPECTORS TEST
MAIN CONTROL Type D 9 x 7 (229 x 178) Annual visual inspections are recom-
MAIN DRAIN Type E 5 x 7 (127 x 17s) mended to ensure that Identification
Signs are properly located.
Installation
The Identification Signs are provid-
ed with 1/8 Inch (3,2 mm) diameter or
larger holes(or slots)in the corners for
easy attachment using standard hard-
ware chain, wire, plastic lock ties, or
light gauge metal strap(not included).
Page 1 of 4 AUGUST, 2007 TFP1615
Page 2 of 4 TFP1615
� . ■
+ � y s r r '� � �
• • �
� � � �
� �
_ � `
� �
s
. � . � ■ .• � • c. � .- -
� � 1
IN CP.SE C7F F[RE
Dfl NOT SHL�T 4'ALVE LJNTIL FIP.E 15 ENTIREL'f�UT � � ■ + � ■ ,
•
�� � ' � � �'� '� •� M
SIGN- TYPE A, P/N 2300A SIGN- TYPE D
RECTANGULAR 6-1/2"X 8-1/2'; P/N2316
OR
ROUND 7-1/4"DIAMETER, P/N2329
• • ■ �- �
AUiCI'�IARY DRAIN � � ■ ' • � � � r .
� � � � - � - ■ + �
a
SIGN- TYPE B,
AVAILABLE WITH THE ' � �
FOLLOWING TEXT OPTIONS
"AIR CONTROL".........................P/N 2328 � � i '
"AIR LINE"..............................P/N 2302
"ALARM TEST"........................ P/N 2304A : . ■ � - i
"ANTIFREEZE SYSTEM" ..................P/N 2306
"AUXILIARY DRAIN°......................P/N 2307 R ���+54,�`�.
"CONTROL VALVE"......................P/N 2310 . , , . . , - . SQ.FT.
„DRAIN" ...............................P/N 2311
"DRAIN VALVE" .........................P/N 2327
� s
"INSPECTORS TEST" ....................P/N 2313 A
"MAIN CONTROL" .......................P/N 2319 ` • �P�
"MAIN DRAIN°..........................P/N 2320 .- • ��#
_ ,
.,. .
SIGN- TYPE E, P/N 2317
FIGURE 1
IDENTIFICATION SIGNS
TFP1615 Page 3 of 4
Limited Ordering
Warranty Procedure
Products manufactured by Tyco Fire Orders must include the description
& Building Products (TFBP) are war- and Part Number (P/N). Contact your
ranted solely to the original Buyer for local distributor for availability.
ten (10)years against defects in mate-
rial and workmanship when paid for Hardware for hanging is not sup-
and properly installed and maintained Plied with the Sign. It must be ordered
under normal use and service. This separately.
warranty will expire ten(10)years from Identification Signs,
date of shipment by TFBP. No warran- (Types A,C, D,or E)
ty is given for products or components Specify:Type(A, C, D, or E)
manufactured by companies not af- Identification Sign, P/N(specify).
filiated by ownership with TFBP or for ldentification Signs
products and components which have �Type B)
been subject to misuse, improper in- Specify: Type B Identification Sign in-
stallation, corrosion,or which have not scribed (specify,e.g. `AIR CONTROL"),
been installed,maintained,modified or P/N(specify).
repaired in accordance with applicable
Standards of the National Fire Protec- rype a..........................Pirv 2sooa
tion Association, and/or the standards Type D(Round)....................P/N 2329
of any other Authorities Having Juris- ryPe��Reotangie�................. P�N zsis
diction. Materials found by TFBP to be Type E........................... P/N 2317
defective shall be either repaired or re-
placed, at TFBP's sole option. TFBP Type B
neither assumes, nor authorizes any 'AIR CONTROL"...................P/N 2328
person to assume for it, any other ob- AiR uNE"........................P/N 2302
ligation in connection with the sale of "ALARM TEST"...................P/N 2304A
products or parts of products. TFBP "ANTIFREEZE SYSTEM"............P/N 2306
shall not be responsible for sprinkler "AUXILIARY DRAIN"................P/N 2307
system design errors or inaccurate or "CONTROL VALVE"................ P/N 2310
incomplete information supplied by °�DRAIN" ......................... P/N 2311
Buyer or Buyer's representatives. °�DRAIN VALVE" ...................P/N 2327
�11 n0 event shall TFBP be liable, In "INSPECTORS TEST" .............. P/N 2313
contract, tOYt, strict liability OY under "MAIN CONTROL" ................. P/N 2319
any other legal theory, for incidental, "MAIN DRAIN"....................P/N 2320
indirect,special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP's liability exceed an amount
equal to the sales price.
The foregoing warranty is made in lieu
of any and all other warranties, ex-
�ress or implied, including warranties
of inerchantability and fitness for a
particular purpose.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity,
in whole or part, of any portion of this
warranty will not affect the remainder.
Page 4 of 4 TFP1615
TYCO FIRE&BUILDING PRODUCTS,451 North Cannon Avenue,Lansdale Pennsylvania 19446
�`L�CO Fire & Building
Products
Technical Services: Tel: (800) 381-9312 / Fax: (800)791-5500
Sprinkler Cabinets
3, 6, & 12 Sprinklers, y/2 or 3/4 Inch NPT
6 ESFR Sprinklers, 3/4 or 1 Inch NPT
General
�,W.... .
Description -�`
Tyco° Sprinkler Cabinets are con- '
structed of inetal enclosures with
hinged covers designed to provide on- - _ �
site storage of an emergency supply �°, - ``�
of sprinklers and a sprinkler wrench. _ -
_ � �� � +
NFPA 13 requires a representative �'F` � ;
number of each type of sprinkler used
in a sprinkler system to be stored in a „�. � P'`�'` "" _
cabinet on-site to allow for immediate
removal and replacement of sprinklers --�
that may have operated or become ;;;,�KK°�
damaged.
Sprinkler Cabinets are manufactured � � "b ��
of heavy gauge steel with knock-outs
to accommodate NPT threaded sprin- �""
klers and are painted an attractive red
enamel.
WARNINGS Technical
The Sprinkler Cabinets described here- Data
in must be installed and maintained in
compliance with this document, as Material
well as with the applicable standards Carbon Steel
of the National Fire Protection Asso- Weights
ciation, in addition to the standards of
any other authorities having jurisdic- 3 Sprinkler Cabinet . . . . . . . . . .
tion. Failure to do so may impair the • • • • • • • • • • • • � • • • •1.5 Lbs. (0,68 kg) o
performance of these devices. 6 Sprinkler Cabinet. . . . . . . . . . . . . . o
The owner is responsible for maintain- ' ' ' ' ' ' � � • • • • • • • • •2•3 Lbs. (1,04 kg) o
ing their fire protection system and de- 12 Sprinkler Cabinet . . . . . . . . . . . . . �
vices in proper operating condition. • � • • • � • . • • � • • • . . .4.0 Lbs. (1,81 kg) o �
The installing contractor or sprinkler 6 ESFR Sprinkler Cabinet. . . . . . . . .
manufacturer should be contacted , , , , , , , , , , , , , , , , ,3.3 Lbs. (1,36 kg) ,,. �
with any questions.
Page 1 of 4 AUGUST, 2007 TFP785
Page 2 of 4 TFP785
REMOVE KNOCKOUTS HOLES ACCOMMODATE
TO ACCOMMODATE 1/2�� NPT SPRINKLERS
3/4"NPT SPRINKLERS
1
HINGES "/ ' OO �
1-5/16" 5-1/4"R
� (33,3 mm) (133,4 mm)
7-1/4" 1-1/4" DOOR SWING
(184,2 mm) (31,8 mm) __
5" 1-1/8" ,�-- -'`�
i (127,0 mm) �(28,6 mm) / ,
r
3-1/4" 2" 2-5/8" 1-3/16" � 2-9/16"
(98,4 mm) (50,8 mm) (66,7 mm) �(30,2 mm) ��(65,1 mm)
� 6"(150 mm) '
� MINIMUM
HOLESFOR � o � � C�EARANCE
3/16"(5 mm) —
SCREWS 5��
1'� (127,0 mm)
1-3/4" (25,4 mm) � ' ~°'-
(44,5 mm)
�
SPRINKLER SLOTS FOR WRENCH DOOR
1"(25,4 mm) AND HINGES
SHELF STRAP HANGER SHELF NOT SHOWN
FIGURE 1
3 SPRINKLER CABINET
REMOVE KNOCKOUTS HOLES ACCOMMODATE
TO ACCOMMODATE 1/2" NPT SPRINKLERS
3/4" NPT SPRINKLERS
�
- ,� %;. �; � � �
HINGES �� �� ��.,�� `�„�� ��� + +
1-5/16" 5-1/4" R
1 (33,3 mm) (133,4 mm)
I
14-1/16" 1-1/4" DOOR SWING
(357,2 mm) (31,8 mm) __
10-13/16" 1-5/8" � � I
(274,6 mm) �(41,3 mm) / ,
6"(150 mm) �
2" 6" 1-3/16" � 2-9/16"
3-1/4" MINIMUM �
(50,8 mm) y �(152,4 mm) y (30,2 mm) CLEARANCE �(65,1 mm)
(98,4 ml m)
r
o ° } � t��
1" (127,0 mm)
1-3/4° (25,4 mm) � - —�-
(44,5 mm)
�
HOLES FOR SPRINKLER SLOTS FOR WRENCH DOOR
3/16"(5 mm) 1"(25,4 mm) AND HINGES
SCREWS SHELF STRAP HANGER SHELF NOT SHOWN
FIGURE 2
6 SPRINKLER CABINET
TFP785 Page 3 of 4
REMOVE KNOCKOUTS HOLES ACCOMMODATE
TO ACCOMMODATE 1/2" NPT SPRINKLERS
3/4"NPT SPRINKLERS
�. �. �. ; � �
�,,�i `�„%i \i\,�i i\� �
,;-�� z. �. 1-1/2��
HWGES �� ��.��i ��.�i� ��� O O � (38,1 mm)
� 1-1/2" 5-1/4"R
(38,1 mm) (133,4 mm)
14-1/16" 1-1/8" DOOR SWING
(357,2 mm) (28,6 mm) _
10-13/16" 1-5/8" � �
(274,6 mm) �(41,3 mm)
6"(150 mm)
2" 6" 1-3/16" 4-1/8"
3-1/4" MINIMUM �
(50,8 mm) y �(152,4 mm) y (30,2 mm) CLEARANCE (104,8 mm)
(98,4 ml m) � �
0 ° � f,�
1" (127,0 mm)
1-3/4" (25,4 mm) � -*_�_�
(44,5 mm)
f
HOLES FOR SPRINKLER SLOTS FOR WRENCH DOOR
3/16"(5 mm) 1"(25,4 mm) AND HINGES
SCREWS SHELF STRAP HANGER SHELF NOT SHOWN
FIGURE 3
12 SPRINKLER CABINET
REMOVE KNOCKOUTS HOLES ACCOMMODATE
TO ACCOMMODATE 3/4" NPT SPRINKLERS
1"NPTSPRINKLERS
1
,--�� �_:� �-:� �% 1
HINGES � �) ��"�) �"'J I�'' O � � 6-7/16" R
1-9/16" (163,5 mm)
� (39,7 mm) DOOR SWING
14-1/16" 1-9/16" -------
(357,2 mm) (39,7 mm) � '/
10-13/16" 1-5/8" /�
(274,6 mm)� �(41,3 mm) �%
7"(180 mm) �
2" 6" 1-3/16" 3-1/8"
(50,8 mm) y (152,4 mm) (30,2 mm) MINIMUM y � ���g,4 mm)
� CLEARANCE � �
�
3-1�/16" O � f �
(96,8 mm)
1" 6-3/16"
+ (25,4 mm) (157,2 mm)
1 -1=s
2-3/8"
(60,3 mm)
�
HOLES FOR SPRINKLER SLOTS FOR WRENCH DOOR
3/16"(5 mm) 1"(25,4 mm) AND HINGES
SCREWS SHELF STRAP HANGER SHELF NOT SHOWN
FIGURE 4
6 ESFR SPRINKLER CABINET
Page 4 of 4 TFP785
Installation Limited Ordering
Sprinkler Cabinets are designed with Warranty Procedure
two 3/16 Inch (4,7 mm) diameter holes
for wall mounting or direct attachment Products manufactured by Tyco Fire �Nhen placing an order, indicate the full
to the system riser with a strap-type & Building Products (TFBP) are war- product name. Contact your local dis-
hanger. The Sprinkler Cabinet should ranted solely to the original Buyer for tributor for availability.
be installed at or near the system con- ten (10)years against defects in mate- Sprinkler Cabinet:
trol valve and must be stocked with an rial and workmanship when paid for Specify: (Description), P/N (specify).
adequate supply of spare sprinklers and properly installed and maintained
and a sprinkler wrench. under normal use and service. This 3 Sprinkler Cabinet................. P/N 1177
warranty will expire ten(10)years from 6 Sprinkler Cabinet................. P/N 1119
The stock of spare sprinklers should 12 Sprinkler Cabinet................ P/N 1124
include sprinklers of each type and date of shipment by TFBP. No warran- 6 EsFR sprinkier cabinet ........... Pirv 111i
temperature rating as are installed in ty is given for products or components
the sprinkler system, in the following manufactured by companies not af-
quantities: filiated by ownership with TFBP or for
products and components which have
Sprinklers In Spare Sprinklers been subject to misuse, improper in-
System Required stallation, corrosion,or which have not
been installed,maintained,modified or
Under 300 6 repaired in accordance with applicable
Standards of the National Fire Protec-
300-1000 12 tion Association, and/or the standards
Over 1000 24 of any other Authorities Having Juris-
diction. Materials found by TFBP to be
defective shall be either repaired or re-
The 3, 6, and 12 Sprinkler Cabinets placed, at TFBP's sole option. TFBP
are designed to accept both 1/2 &3/4 neither assumes, nor authorizes any
Inch NPT threaded sprinklers, where- person to assume for it, any other ob-
as the 6 ESFR Sprinkler Cabinets are ligation in connection with the sale of
designed to accept both 3/4 & 1 Inch products or parts of products. TFBP
NPT threaded sprinklers. As neces- shall not be responsible for sprinkler
sary, insert a screwdriver blade from system design errors or inaccurate or
the front top of the shelf and under the incomplete information supplied by
near bottom part of the knockout an- Buyer or Buyer's representatives.
nular ring. Press the screwdriver han- In no event shall TFBP be liable, in
dle down to remove the knockout ring. contract, tort, strict liability or under
any other legal theory, for incidental,
Care and indirect,special or consequential dam-
ages, including but not limited to labor
Maintenance charges, regardless of whether TFBP
was informed about the possibility of
The Sprinkler Cabinet, wrench, and such damages, and in no event shall
stock of spare sprinklers should be in- TFBP's liability exceed an amount
spected at least quarterly. The follow- equal to the sales price.
ing items should be checked: The foregoing warranty is made in lieu
•The Sprinkler Cabinet should be of any and all other warranties, ex-
readily accessible, and not exposed press or implied, including warranties
to a corrosive atmosphere or tem- of inerchantability and fitness for a
peratures in excess of 100°F(38°C). particular purpose.
•The stock of spare sprinklers should This limited warranty sets forth the ex-
include an adequate number of each clusive remedy for claims based on
type and temperature rating. failure of or defect in products, materi-
als or components, whether the claim
•The stock of sprinklers must be in is made in contract, tort, strict liability
good condition. or any other legal theory.
•A sprinkler wrench of the appropriate This warranty will apply to the full ex-
type must be included in the Sprin- tent permitted by law. The invalidity,
kler Cabinet. in whole or part, of any portion of this
warranty will not affect the remainder.
TYCO FIRE&BUILDING PRODUCTS,451 North Cannon Avenue, Lansdale Pennsylvania 19446
1� � �`'�
- � - - - � +,1
, � � � � ''�,
;� � ,
�
��
�
,
i
� I '
� � no c �� t. �
� o
,
,
nver �
� ,
_ - _ -
�
_ _
fires rin ler mh� llc . com
p
;-
A FIR ����KLER
DESIGN COMPANY