HomeMy WebLinkAboutF14-0002 specs Matterhorn Residence 1664 Matterhorn Circle Vail, CO HYDRAULIC CALCULATIONS AND PRODUCT SUBMITTALS THIS SET OF FIRE SPRINKLER SHOP SPECIFICATIONS AND HYDRAULIC CALCULATIONS HAVE BEEN REVIEWED AND FOUND TO BE ACCEPTABLE-N.I.C.E.T.IV#102055 SR.ENGINEERING TECHNICiAN-FIRE PROTECTION,NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNICIANS / / TIMOTHY N TROSTEL,JR-SET DATE PHOENIX AUTOMATIC SPRINKLER 7684 S. BRENTWOOD ST. LITTLETON, CO 80128 720.922.9231 PHONE 720-922-9231 FAX CALCULATION SUMMARY Project Name:Matterhorn Res Project Location: 1664 Matterhorn Circle Drawing No. : City: Vail, CO Design Areas Design Area Calc. Mode Occupancy Area of Total Water Pressure @ Min. Min. Min. Calculated Hose Margin To Name (Model) Application Source Density Pressure Flow Heads Streams Source �ftz) �9Pm) �PS�) �9Pm/�Z) �PS�) �9Pm) # �9Pm) �ps�) 1 Demand (HW) Res 1152 86.1 102 0.066 20.5 19 4 0 16.9 File:C:\dwg\PHOENIX-MATTERHORN\Matterhorn FP1.dwg Date 1/22/2014 Copyright O 2002-2012 Tyco Fire Protection Products Page 1 HYDRAULIC CALCULATIONS for Job Information Project Name:Matterhorn Res Contract No. : City: Vail, CO Project Location: 1664 Matterhorn Circle Date: 1/5/2013 Contractor Information Name of Contractor: Phoenix Fire Address: City: Phone Number: E-mail: Name of Designer: TEM Authority Having Jurisdiction: Vail Fire Design Remote Area Name 1 Remote Area Location Great Room Occupancy Classification Res Density(gpm/ftz) 0.066 Area of Application(ftz) 1152 Coverage per Sprinkler(ftz) 288 Number of Calculated Sprinklers 4 In-Rack Demand(gpm) 0 Special Heads Hose Streams(gpm) 0 Total Water Required(incl. Hose Streams)(gpm) 86.1 Required Pressure at Source(psi) 85.1 Type of System Wet Volume-Entire System (gal) 23.2 gal Water Supply Information Date Dec.2013 Location near site Source W1 Notes Maximum head spacing is 18'x18' File:C:\dwg\PHOENIX-MATTERHORN\Matterhorn FP1.dwg Date 1/22/2014 Copyright�O 2002-2012 Tyco Fire Protection Products Page 2 Job: Matterhorn Res Node Labels: Off Pipe Labels: Off Diagram for Design Area : 1 (Oatimized Hvdraulic Simalifiedl <r s i E ,r a — _r— 1 - File:C:\dwg\PHOENIX-MATTERHORN\Matterhorn FP1.dwg Date 1/22/2014 Copyright�O 2002-2012 Tyco Fire Protection Products Page 3 Job:Matterhorn Res Hydraulic Analysis for : 1 Calculation Info Calculation Mode Demand Hydraulic Model Hazen-Williams Fluid Name Water @ 60F (15.6C) Fluid Weight, (Ib/ft3) N/A for Hazen-Williams calculation. Fluid Dynamic Viscosity, (Ib•s/ft2) N/A for Hazen-Williams calculation. Water Supply Parameters Supply 1 : W1 Flow(gpm) Pressure(psi) 0 102 1300 97 Hoses Inside Hose Flow/Standpipe Demand(gpm) Outside Hose Flow(gpm) Additional Outside Hose Flow(gpm) Other(custom defined) Hose Flow(gpm) — — — — — — — — — — — — — — — — — — — — — Total Hose Flow(gpm) Sprinklers Ovehead Sprinkier Flow(gpm) 86.1 InRack Sprinkler Flow(gpm) 0 Other(custom defined)Sprinkler Flow(gpm) 0 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ Total Sprinkler Flow(gpm) 86.1 Other Required Margin of Safety(%) 10 W1 -Pressure(psi) 85.1 W1 -Flow(gpm) 86.1 Demand w/o System Pump(s) N/A File:C:\dwg\PHOENIX-MATTERHORN\Matterhorn FP1.dwg Date 1/22/2014 Copyright O 2002-2012 Tyco Fire Protection Products Page 4 Job:Matterhorn Res Hydraulic Analysis for : 1 f Supply � Supply; Safety Pressure f System Demand 150 140=__ _ _ . .. ,. ��.._ ` 130 ------ -- -- � �-- - . 120 _ _ ��� ��� 11 S:I� _ _ ° -------- � � � ��� 96.265 �' 100�1-------------��__ �� ���F��� g D2 --------�------ —1�---� .N �� � Gj 80 ----9— �—�—�-- I ��� P N 70 ---� — � —,— � ���� � L a 60 --------------- 50 ---� � � � u � I� � � 40 --- — -- �� i - � � � � P i P w � � 30 _� 2 p� ---- — 10 �----�--�--�--�--�--�_ i d � d i 0 ���������������������������' 0 400 500 600 700 800 900 1000 1100 1200 1300 1400 Flow, gpm File:C:\dwg\PHOENIX-MATTERHORN\Matterhorn FP1.dwg Date 1/22/2014 Copyright O 2002-2012 Tyco Fire Protection Products PBge 5 Job:Matterhorn Res Hydraulic Analysis for : 1 Graph Labels Values Label Description Flow (gpm) Pressure (psi) S1 Supply point#1 -Static 0 102 S2 Supply point#2-Residual 1300 97 D1 Elevation Pressure 0 10.6 D2 System Demand 86.1 85.1 Curve Intersections & Safety Margins Intersection Safety Margin Curve Name Pressure (psi) Flow (gpm) Pressure (psi) @ Flow (gpm) Supply 102 96.2 16.9 86.1 Supply;Safety Pressure 91.8 90.2 6.7 86.1 Open Heads Required Calculated Head Ref. Head Type Coverage K-Factor Density Flow Pressure Density Flow Pressure (ftz) (gpm/psiYz) (gpm/ftz) (gpm) (psi) (gpm/ftz) (gpm) (psi) 100 Overhead Z$$ 4.2 0.05 14.4 20.5 0.086 24.6 34.4 Sprinkler 101 Overhead Z$$ 4.2 0.05 14.4 20.5 0.066 19 20.5 Sprinkler 102 Overhead 288 4.2 0.05 14.4 20.5 0.081 23.4 31.1 Sprinkler 103 Overhead 288 4.2 0.05 14.4 20.5 0.066 19 20.5 Sprinkler File:C:\dwg\PHOENIX-MATTERHORN\Matterhorn FP1.dwg Date 1/22/2014 Copyright O 2002-2012 Tyco Fire Protection Products Page 6 Job:Matterhorn Res Hydraulic Calculations/Fluid Delivery Time Analysis Node Data Node# Type K-Fact. Discharge Coverage Tot. Pres. Req. Pres. Elev Hgroup Open/Closed Overdischarge Density Elev. Pres. Req. Discharge gpm/psi Ya 9pm ftz psi psi ft gpm gpm/ftz psi gpm 101 Overhead Sprinkler 4.2 19 288 20.5 20.5 22.75 HEAD Open 4.6 0.066 -10.6 14.4 103 Overhead Sprinkler 4.2 19 288 20.5 20.5 22.75 HEAD Open 4.6 0.066 -10.6 14.4 102 Overhead Sprinkler 4.2 23.4 288 31.1 20.5 22.75 HEAD Open 9 0.081 -10.6 14.4 100 Overhead Sprinkler 4.2 24.6 288 34.4 20.5 22.75 HEAD Open 10.2 0.086 -10.6 14.4 006 Node 24.3 19.5 NODE -9 026 Node 39.8 9 NODE -3.7 029 Node 41.5 9 NODE -3.7 032 Node 45.7 9 NODE -3.7 039-0 Node 55.6 3 NODE -0.7 039-I Node 59.7 3 NODE -0.7 040-0 Node 60.4 3 NODE -0.7 040-I Node 68 3 NODE -0.7 041-0 Node 68.6 3 NODE -0.7 041-I Node 76.7 3 NODE -0.7 W1 Supply -86.1 85.1 1.5 SUPPLY 0 File:C:\dwg\PHOENIX-MATTERHORN\Matterhorn FP1.dwg Date 1/22/2014 Copyright�O 2002-2012 Tyco Fire Protection Products Page 7 Job:Matterhorn Res Hydraulic Calculations/Fluid Delivery Time Analysis Pipe Data Pipe Ref. Start End Size Velocity Length Fittings Eq.Len. Total Len. Type HWC ft/s ft ft ft 007 006 101 1 6.41 16.88 4(BM.Tee-Run);1(BM.Tee-Br);2(BM 19 35.88 Brline 150 .90); 023 026 006 1 12.82 35.76 5(BM.Tee-Run);1(BM.Tee-Br); 10 45.76 Brline 150 028 029 026 1.25 8 16.42 2(BM.Tee-Run);1(BM.Tee-Br); 8 24.42 Cmain 150 031 032 029 1.25 12.92 16.48 2(BM.Tee-Run);1(BM.Tee-Br); 8 24.48 Cmain 150 041 039-0 032 1.25 18.11 7.86 1(coupling);2(BM.90); 13.59 21.45 Cmain 150 181 039-I 039-0 1.25 0 0.73 VALVE 0 042 040-0 039-I 1.25 18.11 0.69 1(coupling); 1.59 2.28 Cmain 150 180 040-I 040-0 1.25 0 1.33 BFP 0 043 041-0 040-I 1.25 18.11 0.46 1(coupling); 1.59 2.05 Cmain 150 179 041-I 041-0 1.25 0 0.5 VALVE 0 050 W1 041-I 2 9.17 94.52 5(us.90); 29.07 123.59 Cmain 150 004 006 103 1 6.41 13.2 2�BM.Tee-Run);1(BM.Tee-Br);3(BM Z2 35.2 Brline 150 .90); 053 029 102 1 7.9 17.75 1(BM.Tee-Run);1(BM.Tee-Br);3(BM Z1 38.75 Brline 150 .90); 034 032 100 1 8.31 19.26 1(BM.Tee-Br);4(BM.90); 25 44.26 Brline 150 File:C:\dwg\PHOENIX-MATTERHORN\Matterhorn FP1.dwg Date 1/22/2014 Copyright�O 2002-2012 Tyco Fire Protection Products Page 8 Job:Matterhorn Res Hydraulic Calculations PIPE INFORMATION Node 1 Elev 1 K-Factor 1 Flow added (q) Nominal ID Fittings L C Factor total (Pt) Node 2 Elev 2 K-Factor 2 Total flow (Q) Actual ID quantity x (name) = length F Pf per ft elev (Pe) NOTES T frict (Pf) (ft) (gpm/psiYz) (gpm) (in) (ft) (ft) (psi) (psi) Path No: 1 101 22.75 4.2 19 1 4x(BM.Tee-Run)=4 16.88 150 20.5 006 19.5 19 1.101 lx(BM.Tee-Br)=5 19 0.0617 1.4 2x(BM.90)=10 35.88 2.2 006 19.5 19 1 5x(BM.Tee-Run)=5 35.76 150 24.3 026 9 38.1 1.101 lx(BM.Tee-Br)=5 10 0.223 4.5 45.76 10.2 026 9 0 1.25 2x(BM.Tee-Run)=2 16.42 150 39.8 029 9 38.1 1.394 ix(BM.Tee-Br)=6 8 0.0707 0 24.42 1.7 029 9 23.4 1.25 2x(BM.Tee-Run)=2 16.48 150 41.5 032 9 61.5 1.394 lx(BM.Tee-Br)=6 8 0.1719 0 24.48 4.2 03Z 9 24.6 1.25 ix(coupling)=1.59 7.86 150 45.7 039-0 3 86.1 1.394 2x(BM.90)=12 13.59 0.3209 2.6 21.45 6.9 039-0 3 0 1.25 0.73 0 55.6 Flow Switch 039-I 3 86.1 0 0 5.6403 0 0.73 4.1 039-I 3 0 1.25 ix(coupling)=1.59 0.69 150 59.7 040-0 3 86.1 1.394 1.59 0.3209 0 2.28 0.7 040-0 3 0 1.25 1.33 0 60.4 Febco 850 040-I 3 86.1 0 0 5.6781 0 SMALL 1.33 7.6 040-I 3 0 1.25 lx(coupling)=1.59 0.46 150 68 041-0 3 86.1 1.394 1.59 0.3209 0 2.05 0.7 041-0 3 0 1.25 0.5 0 68.6 WILKINS PRV 041-I 3 86.1 0 0 16.1936 0 0.5 8.1 041-I 3 0 2 5x(us.90)=29.07 94.52 150 76.7 W 1 1.5 86.1 1.959 29.07 0.0612 0.6 123.59 7.6 W1 85.1 Path No: 2 103 22.75 4.2 19 1 2x(BM.Tee-Run)=2 13.2 150 20.5 006 19.5 19 1.101 lx(BM.Tee-Br)=5 22 0.0618 1.4 3x(BM.90)=15 35.2 2.2 006 24.3 Path No: 3 102 22.75 4.2 23.4 1 ix(BM.Tee-Run)=1 17.75 150 31.1 029 9 23.4 1.101 lx(BM.Tee-Br)=5 21 0.0909 6 3x(BM.90)=15 38.75 3.5 029 41.5 File:C:\dwg\PHOENIX-MATTERHORN\Matterhorn FP1.dwg Date 1/22/2014 Copyright�O 2002-2012 Tyco Fire Protection Products Page 9 Job:Matterhorn Res Hydraulic Calculations PIPE INFORMATION Path No: 4 100 2Z.75 4.2 24.6 1 ix(BM.Tee-Br)=5 19.26 150 34.4 032 9 24.6 1.101 4x(BM.90)=20 25 0.0998 6 44.26 4.4 032 45.7 * Pressures are balanced to a high degree of accuracy. Values may vary by 0.1 psi due to display rounding. * Maximum Velocity of 18.11 ft/s occurs in the following pipe(s): (039-0-032), (040-0-039-I), (041-0-040-I) File:C:\dwg\PHOENIX-MATTERHORN\Matterhorn FP1.dwg Date 1/22/2014 Copyright�O 2002-2012 Tyco Fire Protection Products Page 10 Job:Matterhorn Res Device Graphs Pressure vs. Flow Function Design Area: 1; Supply Ref.: W1; Supply Name:W1 115 � � 110 105 100 95 90 KS 80 75 'y 70 Q 65 N � 60 y 55 L 50 a 45 40 35 30 25 20 15 ]0 5 0 � 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 N �n V �n �O 1� 00 O� O Flow,gpm Pressure Loss Function Design Area: 1; BFP Ref.: 180 (Febco 850 SMALL, Size = 1.25) �o y_ 7.6 psi @ 86.1 gpm 8 7 .y O. N 6 L � y Vi 5 N L a 4 - 3 2 I ,. i , 0 0 0 0 0 0 0 0 -� N R �O oo O N Flow,gpm File:C:\dwg\PHOENIX-MATTERHORN\Matterhorn FP1.dwg Date 1/22/2014 Copyright O 2002-2012 Tyco Fire Protection Products Page 1 1 Job:Matterhorn Res Device Graphs Pressure Loss Function Design Area: 1; Valve Ref.: 179 (WILKINS PRV, Size = 1.25) �oo yo Iso � �o •y � N �'� L � y N 50 - N L a 40 30 20 8.1 psi @ 86.1 gpm io � , � � � � � , • ; , O N O v� O O M V v� �D l� G1 O� N O -� N c+i Flow,gpm Pressure Loss Function Design Area: 1; Valve Ref.: 181 (Flow Switch, Size = 1.25) is.sos 14.808 13.805 12.808 11.808 10.R08 Q 9.808 i 8.80A 7 y 7.808 N a 6.sos s.soa 4.1 psi @ 86.1 gpm 4.808 3.808 2.808 I. I.808 � o.sox — — - � � � . � , � � , , � , � . � � � N V v� �C oc O l� Flow,gpm File:C:\dwg\PHOENIX-MATTERHORN\Matterhorn FP1.dwg Date 1/22/2014 Copyright O 2002-2012 Tyco Fire Protection Products Page 12 CO Worldwide www,tyco-fire.com Contacts RAP/D RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Flat-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems General tial fires and to improve the chance for occupants to escape or be evacuated. Description The Series LFII Residential Flat-Plate _� The TYCO RAPID RESPONSE Series Concealed Pendent Sprinklers are � LFII Residential Flat-Plate Concealed shipped with a Disposable Protective l � Cap.The Protective Cap protects the r �-��_ Pendent Sprinklers(TY2524)are decora- sprinkler during ceiling installation or ,� �� `? tive,fast response,fusible solder sprin- finish.After ceiling installation is com- L ��-- � klers designed for use in residential oc- plete, the Protective Cap is removed ! - ��- .� cupancies such as homes,apartments, and the Cover Plate/Retainer Assem- dormitories,and hotels. bly is installed. Removing the Protec- The Cover Plate/Retainer Assembly con- tive Cap is required for proper sprinkler ceals the sprinkler operating compo- performance. nents above the ceiling.The flat profile Dry Pipe System Application of the Cover Plate provides the optimum The Series LFII Residential Flat-Plate The owner is res onsible for maintain- aesthetically appealing sprinkler design. Concealed Pendent Sprinkler offers a ing their fire protection system and de- Additionally,the concealed design of the laboratory approved option for design- vices in proper operating condition. The Series LFII Residential Flat-Plate Con- ing dry pipe residential sprinkler sys- installing contractor or sprinkler manu- cealed Pendent Sprinklers provides 1/2 tems, whereas, most residential sprin- facturer should be contacted with any inch(12,7 mm)vertical adjustment.This adjustment provides a measure of flex- klers are laboratory approved for wet questions. ibility when cutting fixed sprinkler drops. systems only. The Series LFII Residential Flat-Plate Through extensive testing, it has been Sprinkler Concealed Pendent Sprinklers are in- determined that the number of design tended for use in the following systems: sprinklers(hydraulic design area)for the /dentification Series LFII Residential Flat-Plate Con- • wet and dry pipe residential sprin- cealed Sprinklers(TY2524)need not be Number (SIN) kler systems for one- and two-fam- increased over the number of design ily dwellings and mobile homes per sprinklers(hydraulic design area)speci- TY2524 NFPA 13D fied for wet pipe sprinkler systems, as • wet and dry pipe residential sprin- is customary for density/area sprinkler kler systems for residential occu- systems designed per NFPA 13, 13D, pancies up to and including four sto- or 13R. ries in height per NFPA 13R Consequently,the Series LFII Residen- • wet and dry pipe sprinkler systems tial Flat-Plate Concealed Sprinklers for the residential portions of any (TY2524)offer the features of non-wa- occupancy per NFPA 13 ter filled pipe in addition to not having to increase the number of design sprinklers The Series LFII Residential Sprinklers (hydraulic design area)for systems de- have been designed with heat sensitiv- signed to NFPA 13, 13D, or 13R. Non- ity and water distribution characteristics water filled pipe will permit options for proven to help in the control of residen- areas sensitive to freezing. IMPORTANT � Always refer to Technical Data The Series LFII Residential Flat-Plate Sheet TFP700 for the "INSTALLER Concealed Pendent Sprinklers(TY2524) WARNING" that provides cautions described herein must be installed and with respect to handling and instal- maintained in compliance with this doc- lation of sprinkler systems and com- ument and the applicable standards of ponents. Improper handling and in- the National Fire Protection Association, stallation can permanently damage in addition to the standards of any au- a sprinkler system or its components thorities having jurisdiction. Failure to and cause the sprinkler to fail to do so may impair the performance of operate in a fire situation or cause it these devices. to operate prematurely. Page 1 of 6 APRIL 2013 TFP443 TFP443 Page 2 of 6 BODY SEALING WRENCH (1/2" NP� ASSEMBLY RECESS / CAP � SPRINKLER WRENCHING AREA SADDLE �y PUSH WRENCH SUPPORT �`� COMPRESSION IN TO ENSURE CUP WITH �7 � SCREW ENGAGEMENT ROLL FORMED WITH SPRINKLER THREADS WRENCHING AREA LEVER FIGURE 2 � W-TYPE 18 GUIDE I I SPRINKLER WRENCH PIN I �i �i �i �i I SOLDER LINK i i ELEMENT GUIDE PW I I I I i I HOUSING � � � � ii ii i � __ � � DEFLECTOR � � �-J� ` _ � � � i (OPERATED DEFLECTOR I� - �--- - POSITION) I SPRWKLER/SUPPORT CUP I � ASSEMBLY THREAD INTO I I RETAINER SUPPORT WITH THREAD CUP UNTIL DIMPLES MOUNTING O 0 SURFACE IS FLUSH WITH CEILING EJECTION SPRING � SOLDER J COVER PLATE/RETAINER COVER TAB ASSEMBLY PLATE FIGURE 1 RAPID RESPONSE SERIES LFII RESIDENTIAL FLAT-PLATE CONCEALED PENDENT SPRINKLER(TY2524) 2-1/2" DIA. SPRINKLER- (63,5 mm) 1/2" (12,7 mm) FACE OF SUPPORT CUP 1/2�� THREADED SPRINKLER ASSEMBLY NPT ADJUSTMENT FITTING \ ' OPERATED SPRINKLER \ 1-7/8"±1/4" - COVER JJ (47,6 mm PLATE SS RETAINER I 1/8"GAP ±6,4 mm) (3,2 mm) J 1 � � 1 COVER- SPRINKLER- � 7/8"(22,2 mm) RETAINER SUPPORT CUP 3�1� SOURFACE 1-1/8" (28,6 mm) ASSEMBLY ASSEMBLY �4$mm� \ t 3-3/16" DIA. DISPOSABLE DEFLECTOR IN (81,0 mm) TIP PROTECTIVE CAP OPERATED POSITION FIGURE 3 RAPID RESPONSE SERIES LFII RESIDENTIAL FLAT-PLATE(TY2524) INSTALLATION DIMENSIONS/PROTECTIVE CAP/ACTIVATED DEFLECTOR TFP443 Page3of6 Technical Design The number of "design sprinklers" specified in NFPA 13 for wet pipe sys- Data Criteria tems is to be applied when designing dry pipe systems. Approvals The TYCO RAPID RESPONSE Series Dry Pipe System Water Delivery UL and C-UL Listed LFII Residential Flat-Plate Concealed When using the Series LFII Residential The TYCO RAPID RESPONSE Series Pendent Sprinklers (TY2524) are UL Flat-Plate Concealed Pendent Sprinklers and C-UL Listed for installation in ac- TY2524 in dr i e s rinkler s stems, LFII Residential Flat-Plate Concealed cordance with this section: � � y p p p y Pendent Sprinklers are only listed with the time for water delivery must not ex- the Series LFII Concealed Cover Plates Residential Sprinkler Design Guide ceed 15 seconds for the most remote having a factory-applied finish. When conditions exist that are outside operating sprinkler. For details on approvals,refer to the De- the scope of the provided criteria, re- Obstruction to Water Distribution. sign Criteria section. fer to the Residential Sprinkler Design Sprinklers are to be located in accor- Guide TFP490 for the manufacturer's dance with the obstruction rules of Maximum Working Pressure recommendations that may be accept- NFPA 13D, 13R, and 13 as applicable 175 psi (12,1 bar) able to the authority having jurisdiction. for residential sprinklers as well as with Discharge Coefficient System Type the obstruction criteria described within K=4.9 GPM/psi'�z(70,6 LPM/bar1z) Per the UL Listing,wet pipe and dry pipe the Technical Data Sheet TFP490. systems may be utilized. Per the C-UL Operational Sensitivity Temperature Rating Listing, only wet pipe systems may be Sprinkler: 160°F(71°C) utilized. Install sprinklers relative to the ceiling Cover Plate: 139°F(59°C) mounting surface as shown in Figure 3. Refer to Technical Data Sheet TFP485 Vertical Adjustment about the use of Residential Sprinklers The Series LFII Residential Flat-Plate 1/2 inch (12,7 mm) in residential dry pipe systems. Concealed Pendent Sprinklers must not be used in applications where the Finishes Ceiling Types air pressure above the ceiling is greater Refer to the Ordering Procedure section. Smooth flat horizontal, or beamed, or than that below. Down drafts through sloped, in accordance with the 2013 the Support Cup can delay sprinkler op- Physical Characteristics Edition of NFPA 13D, 13R or 13 as eration in a fire situation. Cover Plate/Retainer Assembly: applicable. Cover Plate . . . . . . . . . . . . . Copper Sprinkler Spacing Ejection Spring . . . . Stainless Steel Hydraulic Design The minimum spacing between sprin- Retainer . . . . . . . . . . . . . . . . Brass (NFPA 13D and 13R) klers is 8 feet (2,4 m). The maximum For systems designed to NFPA 13D or spacing between sprinklers cannot ex- Sprinkler/Support Cup Assembly: NFPA 13R,the minimum required sprin- ceed the length of the coverage area Body . . . . . . . . . . . . . . . . . . . Brass kler flow rate are given in Tables A and (Table A)being hydraulically calculated Cap . . . . . . . . . . . . . . . . . . . Bronze g as a function of temperature rating (e.g.,a maximum of 12 feet for a 12 ft.x Saddle. . . . . . . . . . . . . . . . . . Brass and the maximum allowable coverage 12 ft. coverage area or 20 feet for a 20 Sealing Assembly . . . . . . .Beryllium areas.The sprinkler flow rate is the mini- ft.x 20 ft. coverage area.) Nickel w/TEFLON mum required discharge from each of Soldered Link Halves . . . . . . Nickel the total number of"design sprinklers" Lever . . . . . . . . . . . . . . . . . . Bronze as specified in NFPA 13D or NFPA 13R. Compression Screw . . . . . . . Brass The number of"design sprinklers"spec- Deflector . . . . . . . . . . . . . . . Bronze ified in NFPA 13D and 13R for wet pipe Guide Pin Housing. . . . . . . . Bronze systems is to be applied when designing Guide Pins . . . . . . . . . . . . . Bronze dry pipe systems. Support Cup . . . . . . . . . . . . . . Steel Hydraulic Design Operation (NFPA 13) For systems designed to NFPA 13,the When exposed to heat from a fire,the number of design sprinklers is to be Cover Plate,which is normally soldered the four most hydraulically demanding to the Retainer at three points,falls away sprinklers.The minimum required dis- to expose the Sprinkler/Support Cup As- charge from each of the four sprinklers sembly.At this point,the Deflector,sup- is to be the greater of the following: ported by the Guide Pins, drops down to its operated position. •The flow rates given in Tables A and B as a function of temperature rating The Solder Link Element of the Sprinkler/ and the maximum allowable cover- Support Cup Assembly is comprised of age area two link halves that are soldered togeth- .A minimum discharge of 0.1 gpm/ft2. er with a thin layer of solder. When the over the "design area" comprised of rated temperature is reached,the sol- the four most hydraulically demand- der melts and the two link halves sepa- ing sprinklers for the actual coverage rate, allowing the sprinkler to activate areas being protected by the four and flow water. sprinklers TFP443 Page 4 of 6 WET PIPE SYSTEM Minimum Flow and Residual Pressure�b,°� Maximum Maximum Coverage Spacing Ordinary Temp Rating Area 160°F(71°C) Ft.x Ft. Ft' Deflector to Installation Minimum (m x m) (m) Flow Pressure Ceiling Type Spacing GPM PSI Ft. (L/min) (bar) (m� 12 x 12 12 13 7.0 Smooth (3,7 x 3,7) (3,7) (49,2) (0,48) Ceilings 7/8 to 14 x 14 14 13 �� 1-1/8 inches. (4,3 x 4,3) (4,3) 49,2) (0,48) Beamed Ceilings per 16 x 16 16 13 �•� NFPA 13D Concealed $ (4,9 x 4,9) (4,9) (49,2) (0,48) 13R,or 13 �2'4� 18 x 18 18 17 �2,0 Installed in (5,5 x 5,5) (5,5) (64,3) (0,83) beam 7/8 to 1-1/8 inches 20 x 20 20 20 16.7 below bottom (6,1 x 6,1) (6,1) (75,7) (1,15) of beam (a) For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which Hydraulic Design section under the Design Criteria are stated. (b) The Minimum Flow requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pres- sures are calculated using the nominal K-factor.Refer to"Hydraulic Design"in the Design Criteria section for details. (c) For NFPA 13 residential applications,the greater of 0.1 gpm/ft.2 over the design area or the flow in accordance with the criteria in this table must be used. TABLE A WET PIPE SYSTEM SERIES LFII RESIDENTIAL FLAT-PLATE CONCEALED PENDENT SPRINKLER(TY2524) NFPA 13D, 13R,AND 13 HYDRAULIC DESIGN CRITERIA DRY PIPE SYSTEM Maximum Minimum Flowand Residual Pressure�b> Coverage Maximum Area�a> Spacing Ordinary Temp Rating Ft.x Ft. Ft. 160°F(71°C) Deflectorto Installation Minimum (m x m) �m) Flow Pressure Ceiling Type Spacing GPM PSI Ft. (L/min) (bar) (m) 12 x 12 12 15 9.4 Smooth (3,7 x 3,7) (3,7) (56,8) (0,65) Ceilings 7/8 to 14 x 14 14 15 9 4 1-1/8 inches. (4,3 x 4,3) (4,3) (56,8) (0,65) Beamed Ceilings per 16 x 16 16 16 10,7 NFPA 13D Concealed $ (4,9 x 4,9) (4,9) (60,6) (0,74) 13R,or 13 �2'4� 18 x 18 18 17 12.0 Installed in (5,5 x 5,5) (5,5) (64,3) (0,83) beam 7/8 to 1-1/8 inches 20 x 20 20 21 18,4 below bottom (6,1 x 6,1) (6,1) (79,5) (1,27) of beam (a) For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which Hydraulic Design section under the Design Criteria are stated. (b) The Minimum Flow requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K-factor.Refer to"Hydraulic Design"in the Design Criteria section for details. (c) For NFPA 13 residential applications,the greater of 0.1 gpm/ft.z over the design area or the flow in accordance with the criteria in this table must be used. TABLE B DRY PIPE SYSTEM SERIES LFII RESIDENTIAL FLAT-PLATE CONCEALED PENDENT SPRINKLER(TY2524) NFPA 13D, 13R,AND 13 HYDRAULIC DESIGN CRITERIA TFP443 Page5of6 Installation Step 6.Screw on the Cover Plate/Re- Automatic sprinklers must never be tainer Assembly until its flange contacts painted, plated, coated, or otherwise The TYCO RAPID RESPONSE Series the ceiling. Do not continue to screw altered after leaving the factory. Modi- LFII Residential Flat-Plate Concealed on the Cover Plate/Retainer Assembly fied or overheated sprinklers must be Pendent Sprinklers must be installed in such that it lifts a ceiling panel out of replaced. accordance with this section: its normal position. Care must be exercised to avoid dam- General Instructions If the Cover Plate/Retainer Assembly age to the sprinklers- before, during, Damage to the Solder Link Element dur- cannot be engaged with the Mounting and after installation. Sprinklers dam- ing installation can be avoided by han- Cup or the Cover Plate/Retainer Assem- aged by dropping,striking,wrench twist/ dling the sprinkler by the Support Cup bly cannot be engaged sufficiently to slippage, or the like, must be replaced. contact the ceiling,the Sprinkler Fitting only;that is,do not apply pressure to the must be repositioned. The owner is responsible for the in- Solder Link Element(Figure 1). spection,testing, and maintenance of A leak-tight 1/2 inch NPT sprinkler joint Care and their fire protection system and devices should be obtained by applying a min- in compliance with this document, as imum-to-maximum torque of 7 to 14 well as with the applicable standards of ft.-Ibs. (9,5 to 19,0 Nm). Higher levels Maintenance the National Fire Protection Association of torque can distort the sprinkler inlet The TYCO RAPID RESPONSE Series �e.g., NFPA 25), in addition to the stan- with consequent leakage or impairment LFII Residential Flat-Plate Concealed dards of any other authorities having ju- of the sprinkler. Pendent Sprinkler (TY2524) must be risdiction.Contact the installing contrac- maintained and serviced in accordance tor or sprinkler manufacturer regarding Do not attempt to compensate for insuf- any questions. ficient adjustment in the Cover Plate/ with ths section: Retainer Assembly by under- or over- gefore closing a fire protection system Automatic sprinkler systems are rec- tightening the sprinkler. Re-adjust the main control valve for maintenance work ommended to be inspected, tested, position of the sprinkler fitting to suit. on the fire protection system that it con- and maintained by a qualified Inspec- trols,obtain ermission to shut down the tion Service in accordance with local Step 1. Install pendent sprinklers in P requirements and/or national codes. the pendent position, with the center- affected fire protection system from the line of the sprinkler perpendicular to the proper authorities and notify all person- mounting surface. nel who may be affected by this action. Step 2. Remove the Protective Cap. Absence of a Cover Plate may delay the Step 3. With pipe-thread sealant ap- sprinkler operation in a fire situation. plied to the pipe threads, and using the The owner must assure that the sprin- W-Type 18 Wrench shown in Figure 2, klers are not used for hanging any ob- install and tighten the Sprinkler/Sup- jects and that the sprinklers are only port Cup Assembly into the fitting.The cleaned by means of gently dusting with W-Type 18 Wrench accepts a 1/2 inch a feather duster;otherwise, non-opera- ratchet drive. tion in the event of a fire or inadvertent Step 4. Replace the Protective Cap by operation may result. pushing it upwards until it bottoms out �Nhen properly installed,there is a nomi- against the Support Cup.The Protec- nal 1/8 inch (3,2 mm) air gap between tive Cap helps prevent damage to the the lip of the Cover Plate and the ceil- Deflector and Guide Pins during ceiling ing, as shown in Figure 3.This air gap installation and/or during application of is necessary for proper operation of the the finish coating of the ceiling. sprinkler by allowing heat flow from a fire to pass below and above the Cover � Plate to help assure appropriate release of the Cover Plate in a fire situation. If the As long as the protective Cap remains ceiling needs repainting after sprinkler in place, the system is considered"Out installation,exercise care to ensure that Of Service", the new paint does not seal off any of Step 5.After the ceiling has been com- the air gap. Failure to do so may impair pleted with the 2-1/2 inch(63 mm)diam- sprinkler operation. eter hole and in preparation for install- Factory painted Cover Plates must not ing the Cover Plate/Retainer Assembly, be repainted.They should be replaced, remove and discard the Protective Cap, if necessary, by factory painted units. and verify that the Deflector moves up Non-factory applied paint may adversely and down freely. delay or prevent sprinkler operation in If the sprinkler has been damaged and the event of a fire. the deflector does not move up and Do not pull the Cover Plate relative to the down freely, replace the entire sprinkler Retainer. Separation may result. assembly. Do not attempt to modify or repair a damaged sprinkler. Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced. TFP443 Page 6 of 6 Ordering Procedure Contact your local distributor for avail- ability.When placing an order, indicate the full product description and Part Number(P/N). Sprinkler/Support Cup Assembly Specify: Series LFII (TY2524), K=4.9 (70,6), Residential Flat-Plate Concealed Pendent Sprinkler without Cover Plate/ RetainerAssembly, P/N 51-114-1-160 Cover Plate/Retainer Assembly Specify: Series LFII (TY2524), K=4.9 (70,6), Residential Flat-Plate Concealed Pendent Sprinkler Cover Plate/Retain- er Assembly with (specify)finish, P/N (specify): Ivory(RAL 1015)........... P/N 56-202-0-135 Beige(RAL 1001).......... P/N 56-202-2-135 Pure White(b)(RAL 9010)... P/N 56-202-3-135 Signal White(a)(RAL 9003).. P/N 56-202-4-135 Grey White(RAL 9002) ..... P/N 56-202-5-135 Brown(RAL 8028) ......... P/N 56-202-6-135 Black(RAL 9005).......... P/N 56-202-7-135 Brushed Brass............ P/N 56-202-8-135 Brushed Chrome.......... P/N 56-202-9-135 Custom Paint............. P/N 56-202-X-135 (a)Previously known as Bright White. (b)Eastern Hemisphere sales only. Note:All Custom Cover P/ates are painted using Sherwin Williams Interior Latex Paint.Contact TYCO Customer Service with any questions related to custom orders. Sprinkler Wrench Specify: W-Type 18 Sprinkler Wrench, P/N 56-000-1-265 GLOBAL HEADQUARTERS�1400 Pennbrook Parkway,Lansdale,PA 19446�Telephone+1-215-362-0700 Copyright OO 2012 Tyco Fire Products,LP. All rights reserved. t�G.O TEFLON is trademark of The DuPont Corporation. CO Worldwide www,tyco-fire.com Contacts RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Horizontal Sidewall Wet Pipe and Dry Pipe Systems General Escutcheon reduces the accuracy to which the pipe nipples to the sprinklers Description must be cut. ��-� The Series LFII Residential Sprinklers ��' �� _�� The TYCO RAPID RESPONSE Series have been designed with heat sensitivity ,� � LFII Residential Horizontal Sidewall and water distribution characteristics '��.,�� , � � Sprinklers (TY1334) are decorative, proven to help in the control of residen- • fast response,frangible bulb sprinklers tial fires and to improve the chance for designed for use in residential occupan- occupants to escape or be evacuated. � -s. cies such as homes,apartments,dormi- ' .� � tories, and hotels.When aesthetics and � ' optimized flow characteristics are the Dry Pipe System Application major consideration, the Series LFII The Series LFII Residential Horizontal - �,. Residential Sidewall Sprinklers(TY1334) and Recessed Horizontal Sidewall should be the first choice. Sprinklers offers a laboratory approved option for designing dry pipe residen- The Series LFII Residential Sprinklers tial sprinkler systems, whereas, most are intended for use in the following residential sprinklers are laboratory Snrinkler scenarios: approved for wet systems only. M • wet and dry pipe residential sprinkler Through extensive testing, it has been Identification systems for one- and two-family determined that the number of design dwellings and mobile homes per NFPA sprinklers (hydraulic design area) for Number (SIN) 13D the Series LFII Residential Horizontal TY1334 • wet and dry pipe residential sprinkler Sidewall Sprinklers (TY1334) need not systems for residential occupancies be increased over the number of design up to and including four stories in sprinklers (hydraulic design area) as height per NFPA 13R specified for wet pipe sprinkler systems, as is accustomed for density/ area • wet and dry pipe sprinkler systems sprinkler systems designed per NFPA for the residential portions of any 13. occupancy per NFPA 13 Consequently,the Series LFII Residential The recessed version of the Series Sprinklers offer the features of non-water LFII Residential Sprinklers is intended filled pipe in addition to not having to for use in areas with finished walls. increase the number of design sprin- It employs a two-piece Style 20 klers(hydraulic design area)for systems Recessed Escutcheon. The Recessed designed to NFPA 13, 13D, or 13R. Escutcheon provides 1/4 inch (6,4 mm) Non-water filled pipe will permit options of recessed adjustment or up to 1/2 inch for areas sensitive to freezing. (12,7 mm) of total adjustment from the flush mounting surface position. The � adjustment provided by the Recessed The Series LFII Residential Horizontal Sidewall Sprinklers described herein must be installed and maintained in IMPORTANT compliance with this document and the Always refer to Technical Data applicable standards of the National Fire Sheet TFP700 for the "INSTALLER Protection Association, in addition to the WARNING" that provides cautions standards of any authorities having juris- with respect to handling and instal- diction. Failure to do so may impair the lation of sprinkler systems and Performance of these devices. components. Improper handling and The owner is responsible for maintaining installation can permanently damage a their fire protection system and devices sprinkler system or its components and in proper operating condition. The cause the sprinkler to fail to operate in installing contractor or sprinkler manu- a fire situafion or cause it to operate facturer should be contacted with any prematurely. questions. Page 1 of 6 APRIL 2013 REV A TFP410 TFP410 Page2of6 Components: 5 3 2 1 1 - Frame WRENCH 2 - Button Assembly FLATS 3 - Sealing Assembly p 4 - Bulb � 5 - Compression Screw 6 - Deflector* TOP-OF- 6* 4 7/16" (11,1 mm) DEFLECTOR � NOMINAL 2-7/8" DIA. *Temperature rating � MAKE-IN (73,0 mm) is indicated on top � D of Deflector. CENTERLINE OF WATERWAY 7/16" (11,1 mm) � STYLE 20 1/2" NPT RECESSED 1-5/8" y� ESCUTCHEON END-OF- ~(41,3 mm) ESCUTCHEON DEFLECTOR 2-1/4" PLATE SEATING BOSS (57,2 mm) SURFACE FIGURE 1 RAPID RESPONSE SERIES LFII RESIDENTIAL HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS(TY1334) 7/16±1/8" �(11,1±3,2 mm) MOUNTING FACE OF / WRENCH RECESS SURFACE SPRINKLER � (END "A" USED FITTING FOR TY1334) TOP-OF- CLOSURE DEFLECTOR } FIGURE 3 \ TY1334 I W-TYPE 6 j� 2-7/8" DIA. SPRINKLER WRENCH (73,0 mm) 2-1/4" DIA. WRENCH � a (57,2 mm) RECESS 7/16" � (11,1 mm) MOUNTING � PLATE END-OF- DEFLECTOR 1/8" � BOSS (3,2 mm) PUSH WRENCH 1-3/8" (34,9 mm) 1/2" (12,7 mm) IN TO ENSURE 1-1/8"(28,6 mm) 1/4" (6,4 mm) ENGAGEMENT WITH SPRINKLER FIGURE 2 WRENCHING AREA STYLE 20 RECESSED ESCUTCHEON FIGURE 4 FOR USE WITH THE RAPID RESPONSE SERIES LFII RESIDENTIAL W-TYPE 7 RECESSED HORIZONTAL SIDEWALL SPRINKLER(TY1334) SPRINKLER WRENCH TFP410 Page3of6 Technical System Types Operational Sensitivity Per the UL Listing, wet pipe and dry The sprinklers are to be installed with an Data pipe systems may be utilized. Per the end-of-deflector-boss to wall distance C-UL Listing, only wet pipe systems of 1-1/4 to 6 inches. may be utilized. In addition the top-of-deflector-to- Approvals UL Listed for use with wet pipe and dry Refer to Technical Data Sheet TFP485 ceiling distance is to be within the range pipe systems about the use of Residential Sprinklers (Tables A and B) being hydraulically in residential dry pipe systems. calculated. NSF Certified to NSF/ANSI 61 C-UL Listed for use only with wet pipe Ceiling Types Sprinkler Spacing systems Smooth flat horizontal, or beamed, or The minimum spacing between sprin- sloped, in accordance with the 2013 klers is 8 feet (2,4 m). The maximum NYC Approved under MEA 44-03-E Edition of NFPA 13D, 13R, or 13 as spacing between sprinklers cannot For details on these approvals, refer to applicable. exceed the width of the coverage area the Design Criteria section. (Tables A and B) being hydraulically Hydraulic Design calculated(e.g., maximum 12 feet for a Maximum Working Pressure (NFPA 13D and 13R) 12 ft. x 12 ft. coverage area, or 16 feet 175 psi (12,1 bar) For systems designed to NFPA 13D for a 16 ft. x 20 ft, coverage area.). or NFPA 13R, the minimum required Discharge Coefficient sprinkler flow rates are given in Tables A and B as a function of temperature K=4.2 GPM/psi1�2 (60,5 LPM/bar��2) rating and the maximum allowable coverage areas.The sprinkler flow rate Temperature Rating is the minimum required discharge 155°F(68°C)or 175°F(79°C) from each of the total number of "design sprinklers" as specified in Finishes NFPA 13D or NFPA 13R.The number of Signal or Pure White "design sprinklers" specified in NFPA Chrome Plated 13D and 13R for wet pipe systems is Natural Brass to be applied when designing dry pipe Physical Characteristics systems. Frame . . . . . . . . . . . . . . . . . . . . Brass Hydraulic Design Button . . . . . . . . . . . . . . . . . . .Copper �NFPA 13) Sealing Assembly . . . . . . . . Beryllium For systems designed to NFPA 13, Nickel w/TEFLON the number of design sprinklers is Bulb (3 mm). . . . . . . . . . . . . . . . Glass to be the four most hydraulically Compression Screw . . . . . . . . Bronze demanding sprinklers. The minimum Deflector . . . . . . . . . . . . . . . . .Copper required discharge from each of the four sprinklers is to be the greater of Operation the following: The glass bulb contains a fluid that • The flow rates given in Tables A and expands when exposed to heat.When B as a function of temperature rat- the rated temperature is reached, the ing and the maximum allowable fluid expands sufficiently to shatter the coverage area glass bulb, allowing the sprinkler to . A minimum discharge of 0.1 gpm/ft2 activate and flow water. over the "design area" comprised of the four most hydraulically demand- Des� n ing sprinklers for actual coverage ar- g eas protected by the four sprinklers Criteria The number of "design sprinklers" The TYCO RAPID RESPONSE specified in NFPA 13 for wet pipe Series LFII Residential Horizontal systems is to be applied when and Recessed Horizontal Sidewall designing dry pipe systems. Sprinklers(TY1334)are UL and C-UL Dry Pipe System Water Delivery Listed for installation in accordance When using the Series LFII Residential with the following criteria. Horizontal Sidewall Sprinklers(TY1334) in dry pipe sprinkler systems,the time Residential Sprinkler Design Guide for water delivery must not exceed 15 When conditions exist that are outside seconds for the most remote operating the scope of the provided criteria, refer sprinkler. to the Residential Sprinkler Design Guide TFP490 for the manufactur- Obstruction to Water Distribution er's recommendations that may be Sprinklers are to be located in accor- acceptable to the local authority having dance with the obstruction rules of jurisdiction. NFPA 13D, 13R, and 13 as applicable for residential sprinklers as well as with the obstruction criteria described within the TYCO Technical Data Sheet TFP490. TFP410 Page4of6 WET PIPE SYSTEM Max.Coverage Max. Minimum Flow and Residual Pressure�b,c� Area�a� Spacing Ordinary Temp.Rating Intermediate Temp.Rating Width x Length ld> Ft. 155°F(68°C) 175°F(79°C) Minimum Ft.x Ft. �m) Flow Pressure Flow Pressure Deflector to Installation Spacing (m x m) GPM PSI GPM PSI Ceiling Type Ft. (L/min) (bar) (L/min) (bar) (m� 12 x 12 12 12 8.2 12 8.2 (3,7 x 3,7) (3,7) (45,4) (0,57) (45,4) (0,57) 14 x 14 14 14 11.1 16 14.5 (4,3 x 4,3) (4,3) (53,0) (0,77) (60,6) (1,00) 16 x 16 16 16 14.5 16 14.5 4 to (4,9 x 4,9) (4,9) (60,6) (1,00) (60,6) (1,00) 6 inches 16 x 18 16 19 20.5 19 20.5 (4,9 x 5,5) (4,9) (71,9) (1,41) (71,9) (1,41) 16 x 20 16 23 30.0 23 30.0 Recessed (4,9 x 6,1) (4,9) (87,1) (2,07) (87,1) (2,07) Escu�tchteon2or 8 12 x 12 12 13 9.6 13 9.6 non-recessed (2,4) (3,7 x 3,7) (3,7) (49,2) (0,66) (49,2) (0,66) per NFPA 13D, 13R,or 13 14 x 14 14 17 16.4 18 18.4 (4,3 x 4,3) (4,3) (64,3) (1,13) (68,1) (1,27) 16 x 16 16 18 18.4 18 18.4 6 to (4,9 x 4,9) (4,9) (68,1) (1,27) (68,1) (1,27) 12 inches 16 x 18 16 21 25.0 21 25.0 (4,9 x 5,5) �4,9) ��9,5) �1,�2) ��9,5) �1,�2) 16 x 20 16 26 38.3. 26 38.3. (4,9 x 6,1) (4,9) (98,4) (2,64) (98,4) (2,64) (a) For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) Requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K- factor.Refer to Hydraulic Design under the Design Criteria section. (c) For NFPA 13 residential applications,the greater of 0.1 gpm/ftz over the design area or the flow in accordance with the criteria in this table must be used. (d) The Width x Length dimension refers to the Width(backwall where the sprinkler is located)times the Length(horizontal throw of sprinkler). TABLE A WET PIPE SYSTEM SERIES LFII RESIDENTIAL HORIZONTAL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS(TY1334) NFPA 13D, 13R,AND 13 HYDRAULIC DESIGN CRITERIA TFP410 Page5of6 DRY PIPE SYSTEM Max.Coverage Max. Minimum Flow and Residual Pressure�b,°1 Area�a> Spacing Ordinary Temp.Rating Intermediate Temp.Rating Width x Length(dl Ft. 155°F(68°C) 175°F(79°C) Minimum Ft.x Ft. �m� Flow Pressure Flow Pressure Deflector to Installation Spacing (m x m) GPM PSI GPM ps� Ceiling Type Ft. (L/min) (bar) (L/min) (bar) �m) 12 x 12 12 12 8.2 12 8.2 (3,7 x 3,7) (3,7) (45,4) (0,57) (45,4) (0,57) 14 x 14 14 16 14.5 16 14.5 (4,3 x 4,3) (4,3) (60,6) (1,00) (60,6) (1,00) 16 x 16 16 16 14.5 16 14.5 4 to (4,9 x 4,9) (4,9) (60,6) (1,00) (60,6) (1,00) 6 inches 16 x 18 16 19 20.5 N/A N/A (4,9 x 5,5) (4,9) (71,9) (1,41) 16 x 20 16 23 30.0 Recessed (4,9 x 6,1) (4,9) (87,1) (2,07) N/A N/A Escu�tchteon2or 8 12 x 12 12 13 9.6 13 9.6 non-recessed (2,4) (3,7 x 3,7) (3,7) (49,2) (0,66) (49,2) (0,66) per NFPA 13D, 13R,or 13 14 x 14 14 18 18.4 18 18.4 (4,3 x 4,3) (4,3) (68,1) (1,27) (68,1) (1,27) 16x16 16 18 18.4 21 25.0 6to (4,9 x 4,9) (4,9) (68,1) (1,27) (79,5) (1,72) 12 inches 16 x 18 16 21 25.0 21 25.0 (4,9 x 5,5) �4,9) ��9,5) �1,�2) ��9,5) �1,�2) (4 9 x 61) (4,g) N/A N/A N/A N/A (a) For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) Requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K- factor.Refer to Hydraulic Design under the Design Criteria section. (c) For NFPA 13 residential applications,the greater of 0.1 gpm/ftz over the design area or the flow in accordance with the criteria in this table must be used. (d) The Width x Length dimension refers to the Width(backwall where the sprinkler is located)times the Length(horizontal throw of sprinkler). TABLE B DRY PIPE SYSTEM SERIES LFII RESIDENTIAL HORIZONTAL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS(TY1334) NFPA 13D, 13R,AND 13 HYDRAULIC DESIGN CRITERIA TFP410 Page6of6 Installation Step B. After installing the Style 20 damaged by dropping,striking,wrench Mounting Plate over the sprinkler twist/slippage, or the like, must be The TYCO RAPID RESPONSE threads and with pipe-thread sealant replaced. Also, replace any sprinkler Series LFII Residential Horizontal applied to the pipe threads, hand- that has a cracked bulb or that has lost and Recessed Horizontal Sidewall tighten the sprinkler into the sprinkler liquid from its bulb. (Ref. Installation Sprinklers (TY1334) must be installed fitting. Section.) in accordance with this section. Step C. Tighten the sprinkler into the The owner is responsible for the sprinkler fitting using only the W-Type inspection,testing,and maintenance of General Instructions 7 Recessed Sprinkler Wrench (Figure their fire protection system and devices Do not install any bulb type sprinkler if 4).With reference to Figure 1,apply the in compliance with this document, as the bulb is cracked or there is a loss of �/_Type 7 Recessed Sprinkler Wrench well as with the applicable standards of liquid from the bulb. With the sprinkler to the sprinkler wrench flats. the National Fire Protection Association held horizontally, a small air bubble (e.g. NFPA 25), in addition to the should be present.The diameter of the Step D. After the ceiling has been air bubble is approximately 1/16 inch installed or the finish coat has been standards of any authorities having (1,6 mm). applied, slide on the Style 20 Closure Jurisdiction. Contact the installing over the Series LFII Residential contractor or sprinkler manufacturer A leak-tight 1/2 inch NPT sprinkler Sprinkler and push the Closure over the regarding any questions. joint should be obtained by applying a Mounting Plate until its flange comes in Automatic sprinkler systems are recom- minimum to maximum torque of 7 to 14 contact with the wall. mended to be inspected, tested, and ft. Ibs. (9,5 to 19,0 Nm). Higher levels maintained by a qualified Inspection of torque can distort the sprinkler Inlet Service in accordance with local with consequent leakage or impairment Care and of the sprinkler. requirements and/or national codes. 0o not attempt to compensate Maintenance Ordering for insufficient adjustment in an The TYCO RAPID RESPONSE Escutcheon Plate by under- or over- Series LFII Residential Horizontal procedure tightening the Sprinkler. Re-adjust the and Recessed Horizontal Sidewall position of the sprinkler fitting to suit. Sprinklers(TY1334)must be maintained Contact your local distributor for and serviced in accordance with this availability. When placing an order, Series LFII Residential Horizontal section. indicate the full product name and Part Sidewall Sprinklers Number(P/N). The Series LFII Residential Horizontal Before closing a fire protection system Sidewall Sprinklers must be installed main control valve for maintenance Sprinkler Assembly in accordance with the following Work on the fire protection system Specify: Series LFII (TY1334), K=4.2, instructions. that it controls, obtain permission to Residential Horizontal Sidewall shut down the affected fire protection Sprinkler, (specify)temperature rating, Step 1. Install horizontal sidewall sprin- systems from the proper authorities (specify)finish, P/N (specify). klers in the horizontal position with their and notify all personnel who may be iss°F(68°c) centerline of waterway perpendicular to affected by this action. NatUrai arass................PiN 5i-zii-i-i55 the backwall and parallel to the ceiling. . PUre wn�te�RA�soio�'........P/N 51-211-3-155 The word "TOP" on the Deflector is to Absence of the outer piece of an Signal White(RAL9003) .......P/N 51-211-4-155 face towards the ceiling with the front escutcheon, which is used to cover Chrome Plated.............. P/N 51-211-9-155 edge of the Deflector parallel to the a clearance hole, can delay sprinkler ��s°F(79°c) ceiling. operation in a fire situation. Naturai Brass................PiN si-zii-l-i�s Ste 2. With i e-thread sealant The owner must assure that the sprin- Pure wn�te(Ra�soio)'........P/N 51-211-3-175 p p p Signal White(RAL9003) .......P/N 51-211-4-175 applied to the pipe threads, hand klers are not used for hanging any Chrome Plated.............. P/N 51-211-9-175 tighten the sprinkler into the sprinkler objects and that the sprinklers are only fitting. cleaned by means of gently dusting `Eastern Hemisphere sales only. with a feather duster; otherwise, non- Step 3. Tighten the sprinkler into the operation in the event of a fire or inad- Recessed Escutcheon sprinkler fitting using only the W-Type vertent operation may result. Specify: Style 20 Recessed 6 Sprinkler Wrench (Figure 3). With Escutcheon with (specify�)finish, P/N reference to Figure 1, apply the W-Type Sprinklers which are found to be �specify'). 6 Sprinkler Wrench to the wrench flats. leaking or exhibiting visible signs of corrosion must be replaced. `Refer to Technical Data Sheet TFP770. Series LFII Residential Recessed Automatic sprinklers must never be Sprinkler Wrench Horizontal Sidewall Sprinklers painted, plated, coated, or otherwise Specify W-Type 6 Sprinkler Wrench, The Series LFII Residential Recessed altered after leaving the factory. P/N 56-000-6-387. Horizontal Sidewall Sprinklers must Modified sprinklers must be replaced. be installed in accordance with the Sprinklers that have been exposed to Specify W-Type 7 Sprinkler Wrench, following instructions. corrosive products of combustion, but P�N 56-850-4-001. Step A. Install recessed hori- have not operated,should be replaced zontal sidewall sprinklers in the hori- if they cannot be completely cleaned zontal position with their centerline by wiping the sprinkler with a cloth or of waterway perpendicular to the by brushing it with a soft bristle brush. backwall and parallel to the ceiling.The Care must be exercised to avoid word "TOP" on the Deflector is to face damage to the sprinklers - before, towards the ceiling. during, and after installation.Sprinklers GLOBAL HEADQUARTERS�1400 Pennbrook Parkway,Lansdale,PA 19446�Telephone+1-215-362-0700 Copyright OO 2013 Tyco Fire Products,LP. All rights reserved. t�G.O TEFLON is trademark of The DuPont Corporation. • • - 1 • • . .. - ' • - � ' - - ' -• • - L�STEO UL U��� APPLICATION � The Pressure Reducing Valve automatically reduces a higher '�� .��..�' - � �' inlet pressure to a steady lower downstream pressure re- \�'�� � "' F gardless of changing flow rate and/or varying inlet pressure - _ ,•�� in a fire protection system.This valve's pilot control system � ,_� �� L�� , is very sensitive to slight downstream pressure fluctuations and will automatically open or close to maintain the desired SIZES pressure setting. GLOBE: Flanged ends ❑ 1 1/2"thru 8"(class 150) MATERIALS ❑ 1 1/2"thru 6"(class 300) Main Valve Body&Bonnet Ductile IronASTMA536 Threaded ❑ 1 1/2"thru 3" Disc Guide & Seat BronzeASTM B 61 Grooved ❑ 1 1/2", 2", 3", 4" &6" Disc Buna-N Rubber ANGLE: Flanged ends ❑ 2"thru 6" (class 150) Diaphragm Nylon reinforced Buna-N ❑ 2"thru 6" (class 300) Stem &Spring Stainless Steel Threaded ❑ 1 1/2"thru 3" UUULC LISTING Grooved ❑ 2", 3" &4" (CIaSS 300� 3001b Flange 1501b Flange Globe Body Angle Body TEMPERATURE RATING: ❑water 33°F to 180°F Size Grooved Grooved PILOT SPRING RANGE: ❑ 30-165 psi u� u�C u� u�C u� u� ❑ Pressure differentia1,10 psi min. 1 1�2 �� ` 2" • • • • • MAX.INLETPRESSURE: ❑ 300 psi (class 300) 21i2�� � � � � FEATURES 3" • • • • • ❑ Epoxy Coated, FDA approved 4�� ' ' ` ' ' ❑ Pilot Assembly 6 � � ` � � • Flowclean strainer sizes 1 1/2"-3" 8 � � � ( ) 10° • • • "Y"type strainer(sizes 4"-10") • Opening speed control(sizes 1 1/2"-3") - �� �i O � • Isolation Valve(sizes 4"-10") � p p °� i MAIN VALVE OPTIONS � �- �� --� _ °�' Size _ �� � ,. ����G FFFF . ��.�E. o i � o � X - Class 150 flange(175 psi max.) � TH - Threaded ends(400 psi max.) r E=E r, ,���s,E����o�k� ���AEAS� EEEE KB - Viton rubber � SS - Stainless Steel Seat r' 1 ° �� AN - Angle body �� � � - ��Er D - Check Valve in pilot i I� - � ;' F'�FF n� BB FF I G - Groove body �,�- ���.�E. I -:-_=::_:--� � CS - Cast steel(ASTM A216)main valve �AA I I--AAAA SHCN" V`� _EEE EE body&bonnet DIMENSIONS DIM ANSI CLASS VALVE SIZE inches 11/2 2 21/2 3 4 6 8 10 AA 150 8 1/2 9 3/8 11 12 15 20 25 3/8 29 3/4 AAA 300 9 10 11 5/8 13 1/4 15 5/8 21 26 3/8 31 1/8 AAAA GROOVED 81/2 9 - 121/2 15 20 - - B 1 1/8 1 1/2 1 11/16 2 9/16 3 3/16 4 5/16 5 5/16 9 1/4 BB GROOVED 115/16 21/8 - 6 41/8 6 - - C Max. 5 1/2 6 1/2 7 9/16 8 3/16 10 5/8 13 3/8 16 17 1/8 CC Max. 4 3/32 5 - 6 1/2 8 13/16 11 3/32 - - D 2 13/16 3 5/16 4 4 9/16 5 3/4 7 7/8 10 11 13/16 DD GROOVED 2 13/16 3 5/16 - 4 9/16 5 3/4 7 7/8 - - EE 150 4 4 3/4 5 1/2 6 7 1/2 10 12 3/4 14 7/8 EEE 300 4 1/4 5 5 7/8 6 3/8 7 7/8 10 1/2 13 1/4 15 9/16 EEEE GROOVED - 4 3/4 - 6 7 1/2 - - - FF 150 4 3 1/4 4 4 5 6 8 8 5/8 FFF 300 4 1/4 3 1/2 4 5/16 4 3/8 5 5/16 6 1/2 8 1/2 9 5/16 FFFF GROOVED - 31/4 - 41/2 5 - - - G Mvc. 7 1/2 7 3/4 7 3/4 8 9 9 1/2 10 1/2 11 1/2 GG Max. 8 3/32 8 - 8 1/8 9 5/16 10 1/2 - - �• • �• � Page 1 of 2 OPERATION The Model ZW109FP utilizes a pressure reducing pilot valve that installs on the discharge side of the control circuitry.The pilot is a direct acting, normally open, spring loaded, diaphragm actuated valve; the spring being adjustable within a 5.5:1 ratio.The operation of the ZW109FP begins with accurately sizing the valve,then fine tuning the control circuit by adjusting the pilot spring to the desired downstream pressure. Inlet pressure is piped to the inlet port of the pressure reducing pilot.A sensing line runs internally from the discharge side of the pilot to its lower control chamber under the diaphragm. Thus, downstream pressure exceeding the preset acts to close the pilot while the adjustable spring seeks to keep it open. The result is a modulating action in the pilot that is transmitted to the bonnet of the main valve.This creates a mirror modulation of the diaphragm assembly in the main valve. Downstream pressure is maintained within narrow limits regardless of changing flow rates or varying inlet pressures. FLOW CHARACTERISTICS Valve Size inches 1 1/2 2 2 1/2 3 4 6 8 10 m m 40 50 65 80 100 150 200 250 Max. Flow Rate (GPM) 160 262 373 576 992 2251 3900 6150 Min. Flow Rate (GPM) 10 15 20 30 50 115 200 300 For basic valves suggested flow calculations are based on flow through Schedule 40 Pipe. Maximum continuous flow is approx. 20 ft./sec(6.1 meters/sec)&maximum intermittent is approx. 25 ft./sec(7.6 meters/sec)and minimum continu- ous flow is approx. 1 ft./sec (0.3 meters/sec). Many factors should be considered in sizing pressure reducing valves including inlet pressure, outlet pressure and flow rates. TYPICAL INSTALLATION Underwriters Laboratories requires the MAIN FIRE HEADER ZW109FP installation of pressure gauges upstream PRESSURE and downstream of the Pressure Reduo- �`' REDUCING VALVE ing Valve.Also, a relief valve of not less �'�'� than 1/2"in size must be installed on the downstream side of the pressure control � � � valve. Adequate drainage for the relief � � � valve discharge must be provided. � � �� UL INSTALLATION SPECIFICATIONS �� U �� REQUIREMENTS MODEL P4000 PRESSURE The valve is to be installed in accordance RELIEF VALVE �' �� with the standard for installation of sprin- kler systems, NFPA 13. �' � I '� —� / - O DISTRIBUTION TO EACH FLOOR The valve is to be inspected,tested and � O � � � maintained in accordance with the stan- — = � dard for the inspection,testing and Main- zw,osFP tenance of Water-Based Fire Protection PRESSURE ,I "��1�= Systems, NFPA Z�J. REDUCING VALVE MODEL P4000 PRESSURE SPECIFICATIONS RELIEF VALVE The Pressure Reducing Valve shall be a single seated, line pressure operated,diaphragm actuated, pilot controlled,globe or angle valve.The valve shall seal by means of a corrosion-resistant seat and resilient, rectangular seat disc.These and other parts shall be replaceable in the field;all such service and adjustments to be possible without removing the valve from the line. The main valve body shall be Ductile Iron ASTM A 536.The stem of the basic valve shall be guided top and bottom by integral bushings.The basic valve and its pilot control system shall contain no packing glands or stuffing boxes.The diaphragm shall not be used as a seating surface nor shall pistons be used as an operating medium.All internal and external ferrous surfaces shall be coated with a high quality,fusion epoxy coating. The pilot control system shall consist of a two-way, normally open, direct acting,adjustable spring loaded,diaphragm actuated pressure reducing pilot.The pilot control shall be field adjustable from 30 psi to 165 psi; adjustment range not to exceed a 5.5:1 ratio. The Pressure Reducing Valve shall be a WILKINS Model ZW109FP. JOB NAME CONTRACTOR JOB LOCATION ENGINEER Page 2 of 2 WILKINS a Zurn company, 1747 Commerce Way, Paso Robles, CA 93446 Phone:805/238-7100 Fax:805/238-5766 IN CANADA:ZURN INDUSTRIES LIMITED,3544 Nashua Dr.,Mississauga,Ontario L4V 1L2 Phone:905/405-8272 Fax:905/405-1292 Product Support Help Line: 1-877-BACKFLOW (1-877-222-5356) • Website: http://www.zurn.com ' ' • • � : 1 FEBCOo DOUBLE CHECK ASSEMBLY BACKFLOW PREVENTION Characteristics Physical Properties Size 1/2", 3/4", 1", 1-1/4", 1-1/2",2" � Max.Working Pressure 175 PSI (1200 KPa) � � � Hydrostatic Test Press. 350 PSI (2400 KPa) Temperature Range 32°F to 140°F (0°C to 60°C) � � � End Connections Threaded ANSI B2.1 Materials Valve Body Bronze Elastomers Silicone Springs Stainless Steel MODEL 850(1/2"-2")DOUBLE CHECK ASSEMBLY Agency Compliance • ANSI/AWWA Conformance (C510-92) Application • ASSE Listed (Std. 1015) Non-Health Hazard • CSA • Approved by the Foundation for Cross Connection OptIO11S Control and Hydraulic Research at the University of ❑ Wye - Strainer Southern California. Model 850 (1/2" - 2") Flow Curves ��2�� 1-1/2" � zo � zo a �5 a 15 J �p J 10 m 5 � 5 d � _ � = 0 0 3 6 9 12 15 18(GPM) 0 20 40 60 80 100 120 (GPM) 3/4" 2" ,.. zo _ 20 � � a 15 a 15 N N 0 10 0 10 J J � 5 � 5 m d x o x p 0 5 10 15 20 25 30(GPM) 0 30 60 90 120 150 180 (GPM) 1" -- 20 Installation Recommendations � a 15 N * 0 1� � '� 12"Minimum Clearance a 5 � to Fixed Structure a� a = a : B a a 1 0 10 20 30 40 50 60 (GPM) / b o � � 20 1-1/4" ? � � 12�� a 15 Minimum " 1J 10 d 5 FIOW MODEL 850(1/2"-2") = 0 � Outdoor Installation 0 20 40 60 80 100 120(GPM) Model 850 (1/2" - 2") A ITEM DESCRIPTION MATERIALS 9 11 21 1 60 61 21 9.1 1 Body Bronze 1.2 � 1.2 Tailpiece Bronze C 1.4 O-Ring Silicone ' ° _ 2 Cover Bronze 2.2 O-Ring Silicone 3 Seat Noryl B , _, ° _, 3.1 O-Ring Silicone � n n 4 POppOt NOryl 5 Seat Disc Silcone 5.1 Disc Retainer Noryl 5.2 Rnd HD Screw Stainless Steel 6 Spring Stainless Steel 3 3.1 8 22 7 1.4 7 Guide Noryl 8 Retainer Spacer Noryl 2 � 9 Ball Valve(w/tap) Brozne � � _ � � 9.1 Ball Valve Bronze � _ = 11 Test Cock Bronze 21 Hex HD Capscrew Stainless Steel � i i � 60 Identification Plate Brass 61 Drive Screw Stick Stainless Steel E � 5.1 5 4 5.2 6 � Model 850 (1/2�� - 2��� 0 0 Check Assembly 5.1 5 4 7 5.2 Dimensions and Weights U.S.-Inches(mm) NET WT. SIZE A B C D E Lbs. (kgs.) 'Iz'� 10(254.00) 1'Iz(38.10) 1'Iz(38.10) 3'Is(79.38) 1�I4(31.75) 4.2(1.91) 31a" 1031a(273.05) 1'Iz(38.10) 1'Iz(38.10) 3'Is(79.38) 1'la(31.75) 4.4(2.00) 1" 12'Iz(317.50) 1'la(47.63) 151s(41.28) 3'Is(85.73) 1'Iz(38.10) 6.8(3.08) 3 3.1 6 1'la" 15'la(403.23) 3(76.20) 2'Iz(63.50) 4'la(107.95) 2'la(57.15) 15.8(7.17) 1'Iz" 1631a(415.93) 3(76.20) 2'Iz(63.50) 4'la(107.95) 2'I4(57.15) 16.2(7.35) 2" 1751a(447.68) 3'Iz(88.90) 2'Iz(63.50) 4'la(107.95) 2'la(57.15) 21.1 (9.57) Note:Dimensions are nominal.Allowances must be made for normal manufacturing tolerances. FEBCO Backflow Prevention FEBCO is a product of P.O.Box 8070•Fresno,CA 93747-8070 �SPX VALVES&CONTROLS'" 559 252-0791 •Fax:559 453-9030•www.FEBCOonline.com ssa5osm a/o2 Copyright 2002 SPX Valves&Controls ISO 9001 Certified RESIDENTIAL RISER P POTTER � The Symbol of Protection Service Pressure: Up to 175 PSI (12,07 BAR) � Minimum Flow Rate for Alarm: 8-10 GPM (30-38 LPM) � Maximum Surge: 18 FPS (5,5 m/s) � �� Usage: Listed CPVC plastic piping systems manufactured by Central Sprinkler Corp.,Grinnell Sprinkler Corp.,Spears Manufacturing Co., Harvel and IPEX(Scepter). ..�,�-- �_�,.� _ Fits pipe sizes- 1", 1-1/4", 1-1/2"and 2" Environmental Specifications: • Indoor use only ��� � • Temperature range:40°F to 120°F(4.5°C to 49°C) �- � "� � � Service Use: One or two family dwelling NFPA-13D � Flow Switch �! Enclosure: Die-cast, red powdercoat finish ;,;,�,� Cover held in place with tamper resistant screws. � i� Contact Ratings: Two sets of SPDT(Form C) �;��J �, 15,0 Amps at 125/250 VAC �' 2.0 Amps at 30 VDC - Conduit Entrances: Two knockouts provided for 1/2" conduit. Switch Contacts: SPDT(Form C) � Contact Rating: 3 Amps at 250VAC Terminations: 8" No. 22 AWG Wire Leads Caution: This device is not intended for applications in explosive environments. The residential riser is a CPVC sprinkler riser with flow switch,test and the flow switch in the appropriate direction to detect waterflow.The drain for use with wet sprinkler systems using CPVC plastic piping and paddle must not rub the inside of the TEE or bind in any way.The stem fittings manufactured by Central Sprinkler Corp.,Grinnell Sprinkler Corp., should move freely when operated by hand. See Fig. 1. Spears Manufacturing Co., Harvel,and IPEX(Scepter)that use 1", 1-1/ Note: A1/2"NPTfemalefittingisavailableforattachingareliefvalvewhen 4", 1-1/2" or 2" pipe sizes. The flow switch is equipped with a union to required.See Fig 2.Suggested Valves:Watts 530C,Brecco 1/2PR. accommodate installation in confined spaces. CAUTION: Do not over-tighten the union nut, hand tighten only! The flow switch contains two single pole double throw snap action switches and an adjustable, instantly recycling pneumatic retard. The INSPECTION AND TESTING:Check the operation of the unit by opening switches are actuated when a flow of 8-10 gallons per minute (30-38 the test and drain connection,if an inspector's test valve is not provided. liters per minute) or more occurs downstream of the device. The flow The frequency of the inspection and testing and its associated protective condition must exist for a period of time necessary to overcome the monitoring system should be in accordance with the applicable NFPA selected retard period. Codes and Standards and/or authority having jurisdiction (manufacturer INSTALLATION: recommends quarterly or more frequently). 1. Following CPVC manufacturer's instructions for preparation and gluing of CPVC piping systems,glue the main riser to the main supply ORDERINGINFORMATION line for the sprinkler heads. Stock No. Description 2. Usingappropriatefittings,connectthemainwatersupplytothebottom 1119010 1"Riser of the check valve and the drain connection to an adequate drain line. 1119015 1-1/4"Riser The riser must be mounted in a vertical position,(arrow on check valve must point up).See Fig 2. 1119020 1-1/2"Riser 3. Attach gauge to riser.Apply teflon tape to male fitting of gauge only. 1119025 2"Riser SeeFig2. 5310064 WattsAdjustableReliefValve 4. Select the proper Spears paddle and attach it to the flow switch. 5510132 Brecco 175 PSI Relief Valve (Paddle size must match the riser pipe size.)See Fig.4. 0090151 Watts Relief Valve Kit(adjustable) 5. Install the flow switch to the main riser.Verify that the o-ring is properly 0090152 Brecco Relief Valve Kit(fixed at 175 PSI) positioned in its groove.Hand tighten the nut to the union after orienting Potter Electric Signal Company•2081 Craig Road,St.Louis,MO,63146-4161•Phone:800-325-3936/Canada 888-882-1833•www.pottersignal.com PRINTED IN USA MFG.#5401083-REV G PAGE 1 OF 2 M KT.#880001 2-3/02 RESIDENTIAL RISER P POTTER � The Symbol of Protection FIG. 1 FIG.2 OPTIONAL DO NOT LEAVE COVER RELIEF OFF FOR EXTENOED VALVE KIT �� PERIOD OF TIME � PIPING TO SPRINKLER HEROS 4 RETARD �� FIG.� ADJUSTING ��� KNOB MOUNT 50 � CAUTION: INSVRE ARROW ON THAT 0-RING IS BASE POINTS IN O-RING GROOVE IN DIRECTION BEFORE INSTALLING OF WATERFLOW SWITCH. � `\J 3 1" MALE � FITTING ON ALL SIZES i OwG. �1083-2 RISER MAY BE 1", 1 1/4", 1 1/2"OR 2" ��/ � � DIRECTION OF WATERFLOW � � � Z UvG.a1063-9 MP1N APPROX.RETARD SETTINGS(IN SEC.) �'ATER su��v 0 A B C D E 0 10-25 20-40 35-55 50-70 60-90 1O Main Riser O2 Flow Switch Retard Adjustment: To change time,turn retard adjusting knob(either direction)for desired time O Test and Drain DWG. �1083-5 delay.Use the minimum amount of retard necessary to prevent false alarms. O 1/2" NPT female fitting for relief valve A"B"setting is usually adequate for this. Factory set at"B". FIG.4 FIG. 5 TYPICALELECTRICALCON- SWITCHTERMINAL COVERTAMPER NECTIONS CONNECTIONS SWITCH r� CLAMPING PLATE (SHOWN WITH COVER DIRECTION OF 2 SETS aF TERMINAL IN PLACE) WATERFLOW NORMALLY OPEN CONTACIS wqrgqf�pw iONE EOLR fRpM �` /\ CLOSE ON AIARM pN FIRE PFNEL FIRE PnNEL FIG. V V \\ � EO�P � � � � � �i�� �� iNG� + + + OwC. K7063-3 �uu w xc xa xc � � � � �� �HT� �R�� �B�� 0�'L.I98t00i9-3 mpOrtant� THE NC ANO NO MARKiNGS P�SITNE OC 7 paddles are furnished Wlth ON TnE SwiTCH NiE FpR �R��T� BEII �d each flow $W�tCh t� C�CCOIT�' T�E CONTA�CTS nREORE�VER5E0 Qq ryE�TppL p� O�r��'� wHEN THE OEVICE i5 iN �,���fi1_2 DWG. (f923-3 modate the various sizes and T�E NORMRL CONOITiON. manufacturers of TEES. The CAUTION: paddles have raised let- NOTES: An uninsulated section of a tering that show the pipe 1. The model VSR-SFG has two switches,one can single conductor should not be size and the TEE manufac- be used to operate a central station, proprietary looped around the terminal and turer they are to be used or remote signaling unit,while the other is used to serve as two separate con- with. The proper paddle operate a local audible or visual annunciator. nections. The wire must be must be used. The paddle 2. For supervised circuits see "Switch Terminal severed,thereby providing su- must be properly attached and Connections"drawing and caution note (Fig. 6). pervision of the connection in the screw that holds the pad- the event that the wire be- dle must be securely tight- comes dislodged from under ened. the terminal. PRINTED IN USA MFG.#5401083-REV G PAGE 2 OF 2 MKT.#880001 2-3/02 �'���Q Fire & Building Products rapid respanse�'�` Hann� F�r�E Sarer�u�c���r 5rrsr�nr� Technical Services: Tel: (800)381-9312/Fax: (800)791-5500 BlazeMaster ° CPVC Fire Sprinkler Pipe & Fittings Submittal Sheet General Descripfion Technical Tyco� CPVC Pipe and Fittings pro- Da ta duced by Tyco Fire & Building Prod- ucts (TFBP) are designed exclusively Sizes :t:, - for use in wet pipe automatic fire sprin- 3/4"to 3" w ' � � - kler systems. The Tyco CPVC Pipe Maximum Working Pressure ., - and Fittings are produced from Blaze- 175 psi .��� Master� CPVC compound that is a �` .__ specially developed thermoplastic Approvals '',�j,, `�i compound composed of post chlorin- UL, FM, C-UL, NSF, LPCB, MEA, and � ,L ated polyvinyl chloride (CPVC) resin the City of Los Angeles. (Refer to In- _ ,� and state of the art additives. Tyco stallation Handbook IH-1900 dated .�' CPVC Pipe and Fittings are easier to June 2008 for exact listing/approval '�' install than traditional steel pipe sys- information.) � tems, and at the same time, provide Manufacture Source superior heat resistance and strength U.S.A. as compared to traditional CPVC and PVC piping materials used in the Material plumbing trade. Various adapters are �I Pipe: ASTM F442, SDR 13.5 available to connect CPVC pipe to me- tallic piping. All female pipe thread I:I Fittings: ASTM F438 (Sch. 40) and adapters have brass inserts for dura- ASTM F439(Sch.80),ASTM F1970 bility. Grooved adapters connect di- Color rectly to grooved end valves and me- Orange tallic pipe, with flexible grooved end couplings. � Tyco� CPVC Pipe and Fittings pro- duced with BlazeMastera CPVC com- pound described herein must be in- stalled and maintained in compliance with this document and with the appli- cable standards of the National Fire Protection Association, in addition to the standards ofany authorities having jurisdiction. Failure to do so may im- pair the performance of these devices. The owner is responsible for maintain- ing their fire protection system and de- vices in proper operating condifion. The installing contractor or sprinkler manufacturer should be contacted with any questions. BlazeMaste�is a registered trademark of The Lubrizol Corporation Page 1 of 2 JUNE, 2008 TFP1915 Page 2 of 2 TFP1915 1 nsta Ila tion Lim ite d Tyco� CPVC Pipe and Fittings pro- Wa rra n t y duced by Tyco Fire & Building Prod- ucts (TFBP) are to be installed in Products manufactured by Tyco Fire& accordance with Installation Hand- Building Products (TFBP) are war- book IH-1900 dated June 2008. ranted solely to the original Buyer for ten (10)years against defects in mate- Ca re a n d rial and workmanship when paid for and properly installed and maintained under normal use and service. This M a i n t e n a n c e warranty will expire ten (10) years from date of shipment by TFBP. No The owner is responsible for the in- �niarranty is given for products or com- spection, testing, and maintenance of ponents manufactured by companies their fire protection system and de- not affiliated by ownership with TFBP vices in compliance with this docu- or for products and components which ment, as well as with the applicable have been subject to misuse,improper standards of the National Fire Protec- installation, corrosion, or which have tion Association (e.g., NFPA 25), in not been installed, maintained, modi- addition to the standards of any fied or repaired in accordance with ap- authority having jurisdiction. The in- plicable Standards of the National Fire stalling contractor or product manufac- protection Association, and/or the turer should be contacted relative to standards of any other Authorities any questions. Having Jurisdiction. Materials found Automatic sprinkler systems should be by TFBP to be defective shall be either inspected,tested,and maintained by a repaired or replaced, at TFBP's sole qualified Inspection Service in accord- option. TFBP neither assumes, nor ance with local requirements and/or authorizes any person to assume for it, national codes. any other obligation in connection with the sale of products or parts of prod- � ucts.TFBP shall not be responsible for sprinkler system design errors or inac- Before closing a fire profection system curate or incomplete information sup- control valve for inspection or mainte- Plied by Buyer or Buyer's repre- nance work on the fire protection sys- sentatives. tem that it controls, permission to shut In no event shall TFBP be liable, in down the affected fire protection sys- contract, tort, strict liability or under tem must first be obtained from the any other legal theory, for incidental, proper authorities and all personnel indirect,special or consequential dam- who may be affected by this action ages, including but not limited to labor must be notified. charges, regardless of whether TFBP was informed about the possibility of After placing a fire protection system such damages, and in no event shall in service, notify the properauthorities TFBP's liability exceed an amount and advise those responsible formoni- equal to the sales price. toring proprietary and/or central sta- tion alarms. The foregoing warranty is made in lieu of any and all other warranties. ex- press or implied. including warranties of inerchantability and fitness for a par- ticular�uraose• This limited warranty sets forth the ex- clusive remedy for claims based on failure of or defect in products, materi- als or components, whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full ex- tent permitted by law.The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. O 2008 TYCO FIRE 8�BUILDING PRODUCTS,451 North Cannon Avenue, Lansdale, Pennsylvania 19446 � � � � �. r• r. � . � . � �, — ■ • 11 Fig. 22C - Combination Hanger & Restrainer Application ��� Size Range — 3/4" thru 2" CPVC pipe Material — Carbon Steel, Pre-Galvanized . ������ �r8„ Function — Designed to support a CPVC pipe away _ ��'�� �# ��-_ from the corner of a beam. This position allows for easy � '�,��"�I��,�� � �r�� installation of drops or risers without adding additional ..5 ���^'�� �~ � ��,rg� wood blocks. ; ;, ; �x '' ' Approvals — Underwriters' Laboratories Listed in the USA ���` `• Cf (UL) and Canada (cUL) for use as a combination hanger and °� yr�u�S HE�araE� � f.�... restrainer. ��..� �� ,�� Finish — Pre-Galvanized �`'�.T�-,�' � T�z�����t�T Note—Approved UL Listed fastener into wood is furnished . �' `��� °� _ ����� with the product. A fastener into light gauge metal may be ;' ;}r � --•..* ordered separately. Minimum acceptable #10 x 1" hardened `��'��} '' -' ' �j �•---._�,��� �r�„ self threading screw with 5/16" hex washer head. �� � - Order By— Fig. 22C application is composed of two ��'� ��',���� �-v�: 1 �f�" standard Fi . 22 models—order two sin les for each han er �, r,`�i '���� ,, � 9 9 9 t.,; ,��:�� �� �fI and restrainer application required. �� �. �' � �� f / �` ��� �� ��� � � �� � -_ �� : ����, ,�� .,;� �..�����. � -�.�� �: -. Y. . . �� � �`t °.,,y.• jw �.� � �I � ��� _ � :,.i� ��� ,. � �� � �P� `� �' � ������ {� / �' "��5 �t•����. ,i i; �.� ��5f1�'I� �-�," i '��`�–. ��4 � �'a _ °•.�� �� � AYI�, / s r . �.ti� � r 5~' � MainCffice/ManufacturingFacility•1375S�rrpsonAve.•(brore,CA 92879•Fh: 909.737.5599•Fax 909.737.0330 • CUstomer Servi ce•800.786.5266 www.tolco.com � � � • . . . � _ � . . • ��: Fig. 28M - Offset Hanger and Restrainer for CPVC Plastic Pipe and IPS Pipe ` �` �5"�TE° Size Range — 3/4" thru 1-1/4" pipe Material — Carbon Steel, Electro-Galvanized Function — Designed to be used as a hanger and restrainer for CPVC piping where the "stand-off" design will ease installation by eliminating the need for wood blocking I � Features — • Flared edge design protects CPVC pipe from any rough or abrasive A surfaces • Unique snap-on design holds pipe firmly in place and allows retrofit type of installation • The "Stand-Off" design eliminates the need for wood block extension • Can be installed on horizontal or vertical piping regardless of mounting � surface orientation C • Attaches easily to wood structure with two hex head self-threading screws furnished with product �B • Installs easily using rechargeable electrical driver with 5/16" extension socket eliminating impact tool damage to pipe • Attaches easily to steel, minimum 18 gauge with (2) 1/4" x 1" tek type self drilling tapping screws • cULus Listed as a hanger and a restrainer for fire sprinkler piping Approvals — Underwriters' Laboratory Listed in the USA(UL) and Canada (cUL) to support automatic fire sprinkler systems. May be installed into wood using fas- teners screws. Meets and exceeds the requirements of NFPA 13, 13R and 13D. Fig. 28M satisfies the UL vertical restraint requirements where needed. Order By — Figure number and pipe size PATENT PENDING ,--� _ __________� r---------?-------.----1 �� � 1 I � � � - - I / I n � -- ---_____-y i � . . Q i �--� I � Q I I i I . - � I T"'�`T i ° i i i � � i i i i i i i i i i i i i Q i i i i i a i i i i i a a i i i i i L-___ �� _______ _�_J � � !,=+� RESTRAINT � � � � � � � ,�t�. � � ` + L--- --- --L---�-=f RESTRAINT � '� � Fig. 28M Dimensions •Weights Max. Spacing pipe required per Approx Size A B C NFPA 13 for Wt./100 CPVC plastic pipe 3/4 2 3/16 3-1/2 5'-6" 9 1 2-1/8 3/16 3-1/2 6'-0" 12 1-1/4 2-5/16 3/16 3-1/2 6'-6" 13 m OFFICE/MANUFACTURING FACILITY•1375 SAMPSON AVE.•CORONA,CA 92879•PH: 951 J37.5599•FAX: 951 J37.0330 CUSTOMER SERVICE•800.786.5266 www.tolco.com �[�CO Fire & Building Products Technical Services: Tel: (800) 381-9312/ Fax: (800)791-5500 Identification Signs For Sprinkler Systems and Devices NFPA 13 Signing Requirements General WARNINGS Care and The Identification Signs described Descr�n�/�/'� herein must be installed and main- MaII1 tell aI1 Ce I�+ tained in compliance with this docu- Identification Signs (Ref. Figure 1) are ment, as well as with the applicable The following inspection procedure designed to provide information to the standards of the National Fire Pro- must be performed as indicated, in ad- end user about the sprinkler system tection Association, in addition to the dition to any specific requirements of and its components. They are avail- standards of any other authorities hav- the NFPA, and any impairments must able with a variety of wording combi- �ng jurisdiction. Failure to do so may be immediately corrected. nations to meet the signing require- impair the performance of these ments of NFPA 13. devices. The owner is responsible for the in- The owner is responsible for maintain- spection, testing, and maintenance of The five basic types of Identification their fire protection system and devic- Signs are as follows: ing their fire protection system and de- es in compliance with this document, vices in proper operating condition. as well as with the a licable stan- Type A- Control Valve Sign The installing contractor or sprinkler pp T e B- Multi-Pur ose Text Si ns manufacturer should be contacted dards of the National Fire Protection Yp p g Association(e.g., NFPA 25), in addition (See Below) with any questions. to the standards of any authority hav- Type D-Fire Alarm Sign ing jurisdiction. The installing contrac- Type E- Hydraulic Calculation Sign Technical tor or product manufacturer should be contacted relative to any questions. Type B- Identification Signs are avail- �ata It is recommended that automatic sprin- able with the following text options: kler systems be inspected, tested, and AIR CONTROL Material&Finish maintained by a qualified Inspection 18 gauge aluminum with mylar facing. Service in accordance with local re- AIR LINE quirements and/or national codes. ALARM TEST Width x Height ANTIFREEZE SYSTEM After placing a fire protection system AUXILIARY DRAIN Inches (mm) in service, notify the proper authorities CONTROL VALVE Type A 9 x 7 (229 x 178) and advise those responsible for mon- itoring proprietary and/or central sta- DRAIN Type B 6 x 2 (152 x 51) tion alarms. DRAIN VALVE Type C 73/a x 1'/a (197 x 32) INSPECTION PROCEDURE INSPECTORS TEST MAIN CONTROL Type D 9 x 7 (229 x 178) Annual visual inspections are recom- MAIN DRAIN Type E 5 x 7 (127 x 17s) mended to ensure that Identification Signs are properly located. Installation The Identification Signs are provid- ed with 1/8 Inch (3,2 mm) diameter or larger holes(or slots)in the corners for easy attachment using standard hard- ware chain, wire, plastic lock ties, or light gauge metal strap(not included). Page 1 of 4 AUGUST, 2007 TFP1615 Page 2 of 4 TFP1615 � . ■ + � y s r r '� � � • • � � � � � � � _ � ` � � s . � . � ■ .• � • c. � .- - � � 1 IN CP.SE C7F F[RE Dfl NOT SHL�T 4'ALVE LJNTIL FIP.E 15 ENTIREL'f�UT � � ■ + � ■ , • �� � ' � � �'� '� •� M SIGN- TYPE A, P/N 2300A SIGN- TYPE D RECTANGULAR 6-1/2"X 8-1/2'; P/N2316 OR ROUND 7-1/4"DIAMETER, P/N2329 • • ■ �- � AUiCI'�IARY DRAIN � � ■ ' • � � � r . � � � � - � - ■ + � a SIGN- TYPE B, AVAILABLE WITH THE ' � � FOLLOWING TEXT OPTIONS "AIR CONTROL".........................P/N 2328 � � i ' "AIR LINE"..............................P/N 2302 "ALARM TEST"........................ P/N 2304A : . ■ � - i "ANTIFREEZE SYSTEM" ..................P/N 2306 "AUXILIARY DRAIN°......................P/N 2307 R ���+54,�`�. "CONTROL VALVE"......................P/N 2310 . , , . . , - . SQ.FT. „DRAIN" ...............................P/N 2311 "DRAIN VALVE" .........................P/N 2327 � s "INSPECTORS TEST" ....................P/N 2313 A "MAIN CONTROL" .......................P/N 2319 ` • �P� "MAIN DRAIN°..........................P/N 2320 .- • ��# _ , .,. . SIGN- TYPE E, P/N 2317 FIGURE 1 IDENTIFICATION SIGNS TFP1615 Page 3 of 4 Limited Ordering Warranty Procedure Products manufactured by Tyco Fire Orders must include the description & Building Products (TFBP) are war- and Part Number (P/N). Contact your ranted solely to the original Buyer for local distributor for availability. ten (10)years against defects in mate- rial and workmanship when paid for Hardware for hanging is not sup- and properly installed and maintained Plied with the Sign. It must be ordered under normal use and service. This separately. warranty will expire ten(10)years from Identification Signs, date of shipment by TFBP. No warran- (Types A,C, D,or E) ty is given for products or components Specify:Type(A, C, D, or E) manufactured by companies not af- Identification Sign, P/N(specify). filiated by ownership with TFBP or for ldentification Signs products and components which have �Type B) been subject to misuse, improper in- Specify: Type B Identification Sign in- stallation, corrosion,or which have not scribed (specify,e.g. `AIR CONTROL"), been installed,maintained,modified or P/N(specify). repaired in accordance with applicable Standards of the National Fire Protec- rype a..........................Pirv 2sooa tion Association, and/or the standards Type D(Round)....................P/N 2329 of any other Authorities Having Juris- ryPe��Reotangie�................. P�N zsis diction. Materials found by TFBP to be Type E........................... P/N 2317 defective shall be either repaired or re- placed, at TFBP's sole option. TFBP Type B neither assumes, nor authorizes any 'AIR CONTROL"...................P/N 2328 person to assume for it, any other ob- AiR uNE"........................P/N 2302 ligation in connection with the sale of "ALARM TEST"...................P/N 2304A products or parts of products. TFBP "ANTIFREEZE SYSTEM"............P/N 2306 shall not be responsible for sprinkler "AUXILIARY DRAIN"................P/N 2307 system design errors or inaccurate or "CONTROL VALVE"................ P/N 2310 incomplete information supplied by °�DRAIN" ......................... P/N 2311 Buyer or Buyer's representatives. °�DRAIN VALVE" ...................P/N 2327 �11 n0 event shall TFBP be liable, In "INSPECTORS TEST" .............. P/N 2313 contract, tOYt, strict liability OY under "MAIN CONTROL" ................. P/N 2319 any other legal theory, for incidental, "MAIN DRAIN"....................P/N 2320 indirect,special or consequential dam- ages, including but not limited to labor charges, regardless of whether TFBP was informed about the possibility of such damages, and in no event shall TFBP's liability exceed an amount equal to the sales price. The foregoing warranty is made in lieu of any and all other warranties, ex- �ress or implied, including warranties of inerchantability and fitness for a particular purpose. This limited warranty sets forth the ex- clusive remedy for claims based on failure of or defect in products, materi- als or components, whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full ex- tent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. Page 4 of 4 TFP1615 TYCO FIRE&BUILDING PRODUCTS,451 North Cannon Avenue,Lansdale Pennsylvania 19446 �`L�CO Fire & Building Products Technical Services: Tel: (800) 381-9312 / Fax: (800)791-5500 Sprinkler Cabinets 3, 6, & 12 Sprinklers, y/2 or 3/4 Inch NPT 6 ESFR Sprinklers, 3/4 or 1 Inch NPT General �,W.... . Description -�` Tyco° Sprinkler Cabinets are con- ' structed of inetal enclosures with hinged covers designed to provide on- - _ � site storage of an emergency supply �°, - ``� of sprinklers and a sprinkler wrench. _ - _ � �� � + NFPA 13 requires a representative �'F` � ; number of each type of sprinkler used in a sprinkler system to be stored in a „�. � P'`�'` "" _ cabinet on-site to allow for immediate removal and replacement of sprinklers --� that may have operated or become ;;;,�KK°� damaged. Sprinkler Cabinets are manufactured � � "b �� of heavy gauge steel with knock-outs to accommodate NPT threaded sprin- �"" klers and are painted an attractive red enamel. WARNINGS Technical The Sprinkler Cabinets described here- Data in must be installed and maintained in compliance with this document, as Material well as with the applicable standards Carbon Steel of the National Fire Protection Asso- Weights ciation, in addition to the standards of any other authorities having jurisdic- 3 Sprinkler Cabinet . . . . . . . . . . tion. Failure to do so may impair the • • • • • • • • • • • • � • • • •1.5 Lbs. (0,68 kg) o performance of these devices. 6 Sprinkler Cabinet. . . . . . . . . . . . . . o The owner is responsible for maintain- ' ' ' ' ' ' � � • • • • • • • • •2•3 Lbs. (1,04 kg) o ing their fire protection system and de- 12 Sprinkler Cabinet . . . . . . . . . . . . . � vices in proper operating condition. • � • • • � • . • • � • • • . . .4.0 Lbs. (1,81 kg) o � The installing contractor or sprinkler 6 ESFR Sprinkler Cabinet. . . . . . . . . manufacturer should be contacted , , , , , , , , , , , , , , , , ,3.3 Lbs. (1,36 kg) ,,. � with any questions. Page 1 of 4 AUGUST, 2007 TFP785 Page 2 of 4 TFP785 REMOVE KNOCKOUTS HOLES ACCOMMODATE TO ACCOMMODATE 1/2�� NPT SPRINKLERS 3/4"NPT SPRINKLERS 1 HINGES "/ ' OO � 1-5/16" 5-1/4"R � (33,3 mm) (133,4 mm) 7-1/4" 1-1/4" DOOR SWING (184,2 mm) (31,8 mm) __ 5" 1-1/8" ,�-- -'`� i (127,0 mm) �(28,6 mm) / , r 3-1/4" 2" 2-5/8" 1-3/16" � 2-9/16" (98,4 mm) (50,8 mm) (66,7 mm) �(30,2 mm) ��(65,1 mm) � 6"(150 mm) ' � MINIMUM HOLESFOR � o � � C�EARANCE 3/16"(5 mm) — SCREWS 5�� 1'� (127,0 mm) 1-3/4" (25,4 mm) � ' ~°'- (44,5 mm) � SPRINKLER SLOTS FOR WRENCH DOOR 1"(25,4 mm) AND HINGES SHELF STRAP HANGER SHELF NOT SHOWN FIGURE 1 3 SPRINKLER CABINET REMOVE KNOCKOUTS HOLES ACCOMMODATE TO ACCOMMODATE 1/2" NPT SPRINKLERS 3/4" NPT SPRINKLERS � - ,� %;. �; � � � HINGES �� �� ��.,�� `�„�� ��� + + 1-5/16" 5-1/4" R 1 (33,3 mm) (133,4 mm) I 14-1/16" 1-1/4" DOOR SWING (357,2 mm) (31,8 mm) __ 10-13/16" 1-5/8" � � I (274,6 mm) �(41,3 mm) / , 6"(150 mm) � 2" 6" 1-3/16" � 2-9/16" 3-1/4" MINIMUM � (50,8 mm) y �(152,4 mm) y (30,2 mm) CLEARANCE �(65,1 mm) (98,4 ml m) r o ° } � t�� 1" (127,0 mm) 1-3/4° (25,4 mm) � - —�- (44,5 mm) � HOLES FOR SPRINKLER SLOTS FOR WRENCH DOOR 3/16"(5 mm) 1"(25,4 mm) AND HINGES SCREWS SHELF STRAP HANGER SHELF NOT SHOWN FIGURE 2 6 SPRINKLER CABINET TFP785 Page 3 of 4 REMOVE KNOCKOUTS HOLES ACCOMMODATE TO ACCOMMODATE 1/2" NPT SPRINKLERS 3/4"NPT SPRINKLERS �. �. �. ; � � �,,�i `�„%i \i\,�i i\� � ,;-�� z. �. 1-1/2�� HWGES �� ��.��i ��.�i� ��� O O � (38,1 mm) � 1-1/2" 5-1/4"R (38,1 mm) (133,4 mm) 14-1/16" 1-1/8" DOOR SWING (357,2 mm) (28,6 mm) _ 10-13/16" 1-5/8" � � (274,6 mm) �(41,3 mm) 6"(150 mm) 2" 6" 1-3/16" 4-1/8" 3-1/4" MINIMUM � (50,8 mm) y �(152,4 mm) y (30,2 mm) CLEARANCE (104,8 mm) (98,4 ml m) � � 0 ° � f,� 1" (127,0 mm) 1-3/4" (25,4 mm) � -*_�_� (44,5 mm) f HOLES FOR SPRINKLER SLOTS FOR WRENCH DOOR 3/16"(5 mm) 1"(25,4 mm) AND HINGES SCREWS SHELF STRAP HANGER SHELF NOT SHOWN FIGURE 3 12 SPRINKLER CABINET REMOVE KNOCKOUTS HOLES ACCOMMODATE TO ACCOMMODATE 3/4" NPT SPRINKLERS 1"NPTSPRINKLERS 1 ,--�� �_:� �-:� �% 1 HINGES � �) ��"�) �"'J I�'' O � � 6-7/16" R 1-9/16" (163,5 mm) � (39,7 mm) DOOR SWING 14-1/16" 1-9/16" ------- (357,2 mm) (39,7 mm) � '/ 10-13/16" 1-5/8" /� (274,6 mm)� �(41,3 mm) �% 7"(180 mm) � 2" 6" 1-3/16" 3-1/8" (50,8 mm) y (152,4 mm) (30,2 mm) MINIMUM y � ���g,4 mm) � CLEARANCE � � � 3-1�/16" O � f � (96,8 mm) 1" 6-3/16" + (25,4 mm) (157,2 mm) 1 -1=s 2-3/8" (60,3 mm) � HOLES FOR SPRINKLER SLOTS FOR WRENCH DOOR 3/16"(5 mm) 1"(25,4 mm) AND HINGES SCREWS SHELF STRAP HANGER SHELF NOT SHOWN FIGURE 4 6 ESFR SPRINKLER CABINET Page 4 of 4 TFP785 Installation Limited Ordering Sprinkler Cabinets are designed with Warranty Procedure two 3/16 Inch (4,7 mm) diameter holes for wall mounting or direct attachment Products manufactured by Tyco Fire �Nhen placing an order, indicate the full to the system riser with a strap-type & Building Products (TFBP) are war- product name. Contact your local dis- hanger. The Sprinkler Cabinet should ranted solely to the original Buyer for tributor for availability. be installed at or near the system con- ten (10)years against defects in mate- Sprinkler Cabinet: trol valve and must be stocked with an rial and workmanship when paid for Specify: (Description), P/N (specify). adequate supply of spare sprinklers and properly installed and maintained and a sprinkler wrench. under normal use and service. This 3 Sprinkler Cabinet................. P/N 1177 warranty will expire ten(10)years from 6 Sprinkler Cabinet................. P/N 1119 The stock of spare sprinklers should 12 Sprinkler Cabinet................ P/N 1124 include sprinklers of each type and date of shipment by TFBP. No warran- 6 EsFR sprinkier cabinet ........... Pirv 111i temperature rating as are installed in ty is given for products or components the sprinkler system, in the following manufactured by companies not af- quantities: filiated by ownership with TFBP or for products and components which have Sprinklers In Spare Sprinklers been subject to misuse, improper in- System Required stallation, corrosion,or which have not been installed,maintained,modified or Under 300 6 repaired in accordance with applicable Standards of the National Fire Protec- 300-1000 12 tion Association, and/or the standards Over 1000 24 of any other Authorities Having Juris- diction. Materials found by TFBP to be defective shall be either repaired or re- The 3, 6, and 12 Sprinkler Cabinets placed, at TFBP's sole option. TFBP are designed to accept both 1/2 &3/4 neither assumes, nor authorizes any Inch NPT threaded sprinklers, where- person to assume for it, any other ob- as the 6 ESFR Sprinkler Cabinets are ligation in connection with the sale of designed to accept both 3/4 & 1 Inch products or parts of products. TFBP NPT threaded sprinklers. As neces- shall not be responsible for sprinkler sary, insert a screwdriver blade from system design errors or inaccurate or the front top of the shelf and under the incomplete information supplied by near bottom part of the knockout an- Buyer or Buyer's representatives. nular ring. Press the screwdriver han- In no event shall TFBP be liable, in dle down to remove the knockout ring. contract, tort, strict liability or under any other legal theory, for incidental, Care and indirect,special or consequential dam- ages, including but not limited to labor Maintenance charges, regardless of whether TFBP was informed about the possibility of The Sprinkler Cabinet, wrench, and such damages, and in no event shall stock of spare sprinklers should be in- TFBP's liability exceed an amount spected at least quarterly. The follow- equal to the sales price. ing items should be checked: The foregoing warranty is made in lieu •The Sprinkler Cabinet should be of any and all other warranties, ex- readily accessible, and not exposed press or implied, including warranties to a corrosive atmosphere or tem- of inerchantability and fitness for a peratures in excess of 100°F(38°C). particular purpose. •The stock of spare sprinklers should This limited warranty sets forth the ex- include an adequate number of each clusive remedy for claims based on type and temperature rating. failure of or defect in products, materi- als or components, whether the claim •The stock of sprinklers must be in is made in contract, tort, strict liability good condition. or any other legal theory. •A sprinkler wrench of the appropriate This warranty will apply to the full ex- type must be included in the Sprin- tent permitted by law. The invalidity, kler Cabinet. in whole or part, of any portion of this warranty will not affect the remainder. TYCO FIRE&BUILDING PRODUCTS,451 North Cannon Avenue, Lansdale Pennsylvania 19446 1� � �`'� - � - - - � +,1 , � � � � ''�, ;� � , � �� � , i � I ' � � no c �� t. � � o , , nver � � , _ - _ - � _ _ fires rin ler mh� llc . com p ;- A FIR ����KLER DESIGN COMPANY