HomeMy WebLinkAboutB13-0554 REV2 fire rated outlet Bulletin 20-066/March 2009
The Un�co System° �uc�,�u��rnr�s�EC►�rc�r�onrs
UPC-56FR
Firestop, Duct Outlet, 1 -hour, UL-555C*
Part No. Application
UPG56FR — X Designed for floor, ceiling, or wall applications
where the supply outlets are located in a 1-hour
X = Quantity in box or less F rated structure. The firestop is
designed for static conditions, meaning that the
fire suppression system should turn off the air
Package Contents flow in the event of a fire.
-Firestop, White
-2 Toggles and Screws per outlet It is dimensionally identical to the standard
-Instruction sheet Unico round outlet (UPG56B) and should be
installed in the same manner as all other Unico
round outlets.
*Patent Pending
� �
;�� . _
��„„„ � ;�'.
. I P F� ��111 . _
•15 �
- ��
���
UPC-56FR �N�ERrEk
Listed Duct Outlet v�
1-hour F-Rating :�M
per UL 555C �drhockHe�Sea US
O Copyright 2006 Unico,Inc
Bulletin 20-066— Page 2
UPC-56FR Firestop Duct Outlet*
Installation Instructions
���_ ----� ����.
1f � 55
I I �I
�. �---� � ' ^ ' ����������M1�—= ��
� �4.� � � � _ _ ,. ---
, '"� ��I � � - - � `.� ��',� �"� � ��
� , i ;
�°= ��`� ? 5 �_,__---� � I
,_- `� �
� • '�ap �}. _ - k -_--
�� � -
. �+I� ~ �� -~ —�— i ..
'.�I
���
�r 5 � 'r� �
! � � f� �� �i
� � � L
��
'� ___ �� � ���.
�- �. ___
L Floor or Ceiling Assembly—Minimum 1-inch thick or 2layers 1/2-inch thick fire-rated gypsum
board constructed per IMC 2000. Diameter of opening to be 4-inches (102 mm).
2. Firestop Outlet—One firestop outlet centered within opening. The firestop outlet consists of a 3.3
inch diameter x 1 inch galvanized steel tube with an intumescent material lining. The firestop outlet
must be installed in accordance with this instruction. The firestop outlet is secured in place with the
supplied toggles and screw.
UNICO,INC.—UPG56FR
2A.Caulk—(Optional, not shown)—As an option,the firestop outlet can be further sealed with a
bead of fire-rated caulk between the back of the firestop outlet and the ceiling assembly.
SPECIFIED TECHNOLOGIES INC—SpecSeal 100, 101, 102, 105
3. Screw-#4 x 1.5 inch long screw. Two per device.
4. Toggle—Single-sided toggle. Two per device.
5. Duct—Unico Sound Attenuator or Supply Tubing rated as an Air Duct per UL Standard 181. Peel
back the insulation and secure the inner duct to the Firestop device using a metal hose clamp.
Straighten the insulation and outer vapor barrier of the duct and stuff into and under the metal tube
lined with the intumescent material.
UNICO,INC.—UPG25, UPG26C
6. Tape—Secure and seal the duct vapar barrier to the outside of firestop metal tube with aluminum
tape listed per UL Standard 181 A-P. Tape must bear the UL mark.
7. Clamp—Metal clamp to secure the duct to the Firestop Outlet.
UPC-56FR �N�ERrFk
Listed Duct Outlet v�
1-hour F-Rating :�M
per UL 555C �drnockHe�yea US
OO Copyright 2006 Unico,Inc
"Patent Pending