Loading...
HomeMy WebLinkAboutB14-0092 Load Calcs PANEL BACK PROJECT: KIDS SPORTS ENGINEER: SOH PROJECT#: 14027 VOLTAGE: 120/208V, 1 P, 3W MOUNTING: SURFACE MAINS: 100A MLO TYPE: SQUARE D QO OR EQUAL AIC: 10K PHASE PHASE DESCRIPTION A B BKR P CIR CIR P BKR A B DESCRIPTION EAST WALL LIGHTING 1200 20 1 1 2 1 20 1080 BENCH OVERHEAD WEST TRACK LIGHTS 1200 20 1 3 4 1 20 1080 SOUTH BANK EAST TRACK LIGHTS 1200 20 1 5 6 1 20 1200 SOUTH FLUORESCENTS SHOWROOM RECEPTACLE 1080 20 1 7 8 1 20 1200 SHOWCASE LIGHTING SOUTH PLUG STRIP 1080 20 1 9 10 1 20 0 SPARE NORTH TRACK LIGHTS 1200 20 1 11 12 2 20 1000 SHOP HEAT BASEMENT HEATER 1500 30 2 13 14 1000 1500 15 16 1 20 180 BASEMENT CASH REGISTER SPACE 0 17 18 0 SPACE 0 19 20 0 0 21 22 0 0 23 24 0 0 25 26 0 0 27 28 0 0 29 30 0 0 31 32 0 0 33 34 0 0 35 36 0 0 37 38 0 0 39 40 0 0 41 42 0 LOAD CALCULATION SUMMARY PROVIDE NEW PANEL AS SCHEDULES. RELOCATE PANEL, EXTEND EXISTING CONDUCTORS. at`�������2. CALCULATED POWER FACTOR: ����� �J�l�u�� 0.95 �, '�, CONNECTEDLOAD CONNECTED AMPS DEMANDLOAD DEMAND AMPS . � LIGHTING/CONTINUOUS 7200 35 9000 43 ' RECEPTACLES 4500 22 4500 22 �s ����4 MECHANICAL 5000 24 5750 28 US'cHVn�Er't,cy KITCHEN 0 0 0 0 r` TOTAL 16700 80 19250 93 4/4/2014 � � � �odg � PANEL FRONT PROJECT: KIDS SPORTS ENGINEER: SOH PROJECT#: 14027 VOLTAGE: 120/208V, 1 P, 3W MOUNTING: SURFACE MAINS: 100A MLO TYPE: SQUARE D QO OR EQUAL AIC: 10K PHASE PHASE DESCRIPTION A B BKR P CIR CIR P BKR A B DESCRIPTION RECEPTACLE BY HATS 900 20 1 1 2 1 20 1080 UNIDENTIFIED FRONT ENTRANCE LIGHTS 1200 20 1 3 4 1 20 1200 WEST FLUORESCENTS FRONT TRACKS 1200 20 1 5 6 1 20 1080 UNIDENTIFIED NORTH TRACK LIGHTS 1200 20 1 7 8 1 20 1080 UNIDENTIFIED SOUTH COUNTER TRACKS 1200 20 1 9 10 1 20 1200 FLUORESCENTS OVER COUP MIDDLE TRACKS 1200 20 1 11 12 1 20 1200 MIDDLE FLUORESCENTS REGISTER 360 20 1 13 14 1 20 1080 UNIDENTIFIED COUNTER RECEPTACLE 540 20 1 15 16 1 20 1080 UNIDENTIFIED SPACE 0 20 1 17 18 0 SPACE 0 19 20 0 0 21 22 0 0 23 24 0 0 25 26 0 0 27 28 0 0 29 30 0 0 31 32 0 0 33 34 0 0 35 36 0 0 37 38 0 0 39 40 0 0 41 42 0 LOAD CALCULATION SUMMARY PROVIDE NEW PANEL AS SCHEDU�ES. RELOCATE PANEL, EXTEND EXISTING CONDUCTORS. e.�'Q���3.4�� CALCULATED POWER FACTOR: �� p r��; rfi,�a 1.00 �� � �' �., CONNECTEDLOAD CONNECTED AMPS DEMANDLOAD DEMAND AMPS . y : LIGHTING/CONTINUOUS 9600 46 12000 58 �, ��� RECEPTACLES 7200 35 7200 35 '��s`��t�����4� MECHANICAL 0 0 0 0 �����`Y KITCHEN 0 0 0 0 TOTAL 16800 81 19200 92 4/4/2014 � � � �����