HomeMy WebLinkAboutDRB140086 Plans ApprovedGENERAL NOTES: 775 POTATO PATCH DECK ADDITION JOB# 0210 -13 DESIGN CRITERIA: DECK LIVE LOAD: 100 PSF DECK LIVE LOAD W /HOTTUB: 200 PSF DECK DEAD LOAD: 10 PSF SEISMIC DESIGN CATEGORY: C IBCARC EDITION: 2012 FOUNDATION DESIGN 1. DESIGN OF FOOTINGS IS BASED ON AN ASSUMED MAXIMUM ALLOWABLE BEARING PRESSURE OF 2000 PSF. 2. FOOTINGS SHALL BE PLACED BELOW FROST DEPTH ON UNDISTURBED SOIL OR ON STRUCTURAL FILL COMPACTED AS REQUIRED BYTHE GEOTECHNICAL ENGINEER. 3. SOIL VALUES AND CONDITIONS SHALL BE VERIFIED BYA REPRESENTATIVE OF THE GEOTECHNICAL ENGINEER. BECAUSE SOILS INFORMATION WAS NOT AVAILABLE AT THE TIME OF PREPARATION OFTHE CONSTRUCTION DOCUMENTS, WE HAVE USED ASSUMED VALUES BASED ON SIMILAR SITES IN THEAREA. CONSTRUCTION OF THE FOUNDATION MAY NOT PROCEED WITHOUT VERIFYING THESE VALUES. REPORT ANY DISCREPANCIES FROM THE DESIGN ASSUMPTIONS TO THE STRUCTURAL ENGINEER. REINFORCED CONCRETE 1. CONCRETE DESIGN IS BASED ON THE MOST CURRENT PUBLICATION OF "BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE" (ACI 318). 2. STRUCTURAL CONCRETE SHALL HAVE A MINIMUM 28 DAY COMPRESSIVE STRENGTH OF 3000 PSI. 3. CONCRETE SHALL BE PROPORTIONED USING TYPE 1 -11 SULFATE RESISTANT CEMENT. DO NOT USE ADMIXTURES CONTAINING CHLORIDE SALTS. 4. FOR COLD WEATHER CONCRETING PROCEDURES REFER TO THE "ACI MANUAL OF CONCRETE PRACTICE." 5. EXPANSION ANCHORS SHALL BE LOCATED NO LESS THAN 6 BOLT DIAMETERS FROM CONCRETE EDGES AND SPACED AT NO LESS THAN 12 BOLT DIAMETERS UNLESS NOTED OTHERWISE. 6. CONCRETE FLOOR SLABS ON GRADE SHALL HAVE SAWN OR TOOLED CONTROL JOINTS AT A MAXIMUM SPACING OF 12 FEET IN EACH DIRECTION. IF POSSIBLE, LOCATE CONTROL JOINTSALONG COLUMN GRIDLINES. CONCRETE COVERAGE FOR REINFORCING STEEL (ACI 318 -95): ABBREVIATIONS LIST CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH: 3" CONCRETE EXPOSED TO EARTH OR WEATHER: © #6 BAR THROUGH #18 BAR: 2" #5 BAR, W31 OR D31 WIRE, AND SMALLER: 1 1/2" CONCRETE NOT EXPOSED TO WEATHER NOR IN CONTACT WITH GROUND: a. SLABS, WALLS AND JOISTS ( #11 BAR AND SMALLER): ARCHITECT #14 AND NO 18 BARS: 1 1/2" #11 BAR AND SMALLER: 3/4" b. BEAMS AND COLUMNS: BLOCKING PRIMARY REINFORCEMENT, TIES, STIRRUPS, SPIRALS: 1 1/2" REINFORCING STEEL 1. EXCEPT WHERE OTHERWISE NOTED, REINFORCING BARS SHALL BE GRADE 60 EXCEPT TIES, FIELD BENT BARS AND BARS TO BE WELDED WHICH MAYBE GRADE 40. ALL REINFORCING BARS SHALL CONFORM TO ASTM SPEC. 2. FOR BARS #8 AND SMALLER, LAP BARS 36 DIAMETERS AT SPLICES IN CONCRETE. DO NOT WELDOR USE MECHANICAL SPLICING DEVICES UNLESS APPROVED BY ENGINEER. 3. HORIZONTAL BARS SHALL BE CONTINUOUS OR LAPPED WITH CORNER BARS AT CORNERS. PROVIDE (2) - #5 BARS EXTENDING A MINIMUM OF 2 FEET BEYOND EDGE OF ALL OPENINGS OR STEPS. 4. EXTEND REINFORCING STEEL A MINIMUM OF 2 FEETTHROUGH COLD JOINTS COORDINATE ALL COLD JOINT LOCATIONS WITH ENGINEER. 5. WELDED WIRE FABRIC SHALL CONFORM TO ASTM SPEC. A -185. LAP WELDED WIRE FABRIC A MINIMUM OFTWO FULL MESH GRIDS. STRUCTURAL WOOD FRAMING 1. BOTTOM PLATES IN CONTACT WITH CONCRETE SHALL BE PRESSURE TREATED LUMBER OR A LUMBER OF NATURALLY DURABLE MATERIAL. 2. BOLTS USED IN FRAMING CONNECTIONS SHALL BE INSTALLED WITH STANDARD WASHERS AND NUTS. 3. REFER TO THE 2012 IRC TABLE R602.3(1) OR 20012 IBC TABLE 2304.9.1 FOR MINIMUM FASTENING SCHEDULE. A COPY OF THIS TABLE CAN BE PROVIDED UPON REQUEST. AS STATED IN SECTION 2304.9.5 OF THE 20012IBC SECTION 2304.9.5: FASTENERS FOR PRESERVATIVE- TREATED AND FIRE - RETARDANT - TREATED WOOD SHALL BE OF HOT- DIPPED ZINC - COATED GALVANIZED STEEL, STAINLESS STEEL, SILICON BRONZE OR COPPER. FASTENINGS FOR WOOD FOUNDATIONS SHALL BE AS REQUIRED IN AF &PA TECHNICAL REPORT No. 7. 4. UNLESS NOTED OTHERWISE, STEEL CONNECTORS SHALL BE USED TO JOIN JOISTS AND BEAMS SUCH AS SIMPSON STRONG -TIE CONNECTORS OR EQUIVALENT. BACKFILLING PROCEDURES: ABBREVIATIONS LIST 1. VERIFY TYPE OF FILL WITH GEOTECHNICAL ENGINEER. A.B. ANCHOR BOLT © ADJ. ADJACENT GENERAL REQUIREMENTS: ALT. ALTERNATE ARCH. ARCHITECT 1. CHECK ALL DIMENSIONS AGAINST ARCHITECTURAL DRAWINGS PRIOR TO BD BOARD CONSTRUCTION. DO NOT SCALE DRAWINGS. CONTACT ENGINEER IF BLKG. BLOCKING DISCREPANCIES IN DIMENSIONS ARE DISCOVERED. BM, BEAM 2. THE STRUCTURAL DRAWINGS DESCRIBE THE COMPLETED STRUCTURE. BM.PKT. BEAM POCKET THESE DRAWINGS HAVE BEEN PREPARED FOR THE USE OFAQUALIFIED BRG. BEARING CONTRACTOR WITH EXPERIENCE IN THECONSTRUCTION SYSTEMSAND CANT. CANTILEVER TECHNIQUES DESCRIBED. THE CONTRACTOR SHALL PROVIDE ADEQUATE CLR. CLEAR SHORING AND BRACING IN THE PROPER SEQUENCE, AS MAYBE REQUIRED TO CMU CONCRETE MASONRY UNIT ACHIEVE THE FINAL COMPLETED STRUCTURE. THE SEQUENCE OF COL. COLUMN CONSTRUCTION IS THE RESPONSIBILITY OF THE CONTRACTOR. CONSULTWITH CONC. CONCRETE THE ENGINEER FOR SHORING DESIGN AND RECOMMENDATIONS (NOT IN CONT. CONTINUOUS CONTRACT). C.P. CRIPPLE POST 3. THE CONTRACTOR IS RESPONSIBLE FOR THE MEANS, METHODS SEQUENCES DWL. DOWEL AND PROCEDURES FOR CONSTRUCTION OF THIS PROJECT. NOTIFY EA. EACH STRUCTURAL ENGINEER OF ERRORS OR OMISSIONS IN THE CONSTRUCTION EQ. EQUAL DOCUMENTS IMMEDIATELY. DO NOT PROCEED UNTIL ERRORS OR OMISSIONS EXP. EXPANSION ARE RESOLVED. COORDINATE REQUIREMENTS FOR ALL PENETRATIONS EXSTG. EXISTING THROUGH STRUCTURAL MEMBERS WITH STRUCTURAL ENGINEER. JOBSITE F.D. FLOOR DRAIN SAFETY IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR. FNDTN. FOUNDATION 4. OBSERVATION VISITS BY THE STRUCTURAL ENGINEER ARE FOR FTG. FOOTING DETERMINATION OF GENERAL COMPLIANCE WITH THE CONSTRUCTION G.L. GLUED LAMINATED DOCUMENTS. THIS OBSERVATION VISIT IS NOTAN INSPECTION. THE HDR. HEADER CONTRACTOR SHALL CONTACTTHE ENGINEER AT THE APPROPRIATE TIME TO HORIZ. HORIZONTAL SCHEDULE THIS VISIT. INFO. INFORMATION JOISTS 5. IF NEW CONSTRUCTION ADJOINS AN EXISTING STRUCTURE, THE K.S. K.S. KING STUD CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING DIMENSIONS, LLV LONG LEG VERTICAL ELEVATIONS AND ALL EXISTING CONDITIONS UNDERPINNING AND SHORING OF EXISTING STRUCTURES SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. LONGIT. LONGITUDINAL CONSULT WITH THE ENGINEER FOR SHORING DESIGN AND RECOMMENDATIONS LTWT. LIGHTWEIGHT (NOT IN CONTRACT). LVL LAMINATED VENEER LUMBER MANF. MANUFACTURER 6. WHILE EVERY EFFORT IS MADE TO PROVIDE A COMPLETE AND ACCURATE SET O.C. ON CENTER OF CONSTRUCTION DOCUMENTS, ERRORS OR OMISSIONS MAYOCCUR. IT- PLATE RELEASE OF THESE DRAWINGS ANTICIPATES CONTINUED COOPERATION AND REF. REFERENCE COMMUNICATION BETWEEN THE CONTRACTOR, ARCHITECTAND ENGINEERTO REINF. REINFORCING PROVIDE THE BEST POSSIBLE STRUCTURE. SCHED. SCHEDULE S.I.P. STRUCTURAL INSULATED PANEL STL. STEEL T.B. THROUGH BOLT T &G TONGUE & GROOVE TO TOP OF TOF TOP OF FOOTING TOW TOP OF WALL TRANSV. TRANSVERSE TRTD. TREATED TS TUBE STEEL TYP. TYPICAL VERT. VERTICAL VIF VERIFY IN FIELD W.P. WATERPROOF W/ WITH rowN of va� CONNECTION SCHEDULE 0 SIMPSON LUS210 © SIMPSON LUS210 -2 © SIMPSON ABU66 Design Review Staff Approval By Joe Batcheller at 4:51 pm, Apr 28, 2014 CC r O CV r r O r 'IT O O r1- m N O r-- � co CO N — co X 0 0i O m U o 0 O Z rn Od < A c O J C — CD Z W W Z c� Z LLJ C�r) LL_ O ❑ O Lj ❑ W Q O , __J U 0c) Q U W W Q Q ❑ > CV CD PROJECT: 0210 -13 DRAWN BY: TFA REVIEWED BY: JPL DATE: 10.11.2013 REVISIONS. GENERAL NOTES S1 Design Review Staff Approval TOWN OF By Joe Batcheller at 4:51 pm, Apr 28, 2014 VAIL 47 v ---------------- ---------------------------------- (p ----- ------ -------- - -- ------------------------------------- ---- -\ - -61 1414 I CL ,4:r , z Nl� S I T F- 01 V) -All A 7 W Q V10 4 OWAA-rr -------------------------------- / ---------- 0 4?/, L191T Q KEY 70 aQA.-.C)V—� 57.0 014 �ATC PL*t4 = %00!0" ON Fq-Ai -Albk, F-XVZ>TIMC.:- 11BPOT ELIEVAT10�4 W6V-�-OW MA.RK 141EW tWCM EX 1c7T1 w.14 COKTt>►V:ZtN, CA..qri Ar&o) Cx;)KA-r0%-1P.41* T e M - rxQ0L1t-4Q) KILXT"','Q I&T M Ti- 11- P'1 N - b .a1k Wi W-Q W.I. = S40,0 Rear Setback Design Review Staff Approval TOWN By Joe Batcheller at 4:52 pm, Apr 28, 2014 OF VAIL VERIFY ALL DIMENSIONS W/ CONTRACTOR & EXISTING CONDITIONS. CONTACT ENGINEER IF DIFFERENT THAN THAT SHOWN ON PLAN. INDICATES OUTLINE OF NEW DECK INDICATES EXSTG. CONC. FNDTN. m 21 -011 . 61 -0111 x.21 -011 '— INDICATES NEW 10 "0 CONC. PIER ON NEW 28" O BELLED BASE (BIGFOOT BF28 OR EQUIV., TYP.) rT T-1 LJ LJ FOUNDATION PLAN PLAN NOTES: 0 w 0 Deck limited to 13' 4" 1. NEW CONSTRUCTION INDICATED ( ), EXISTING CONSTRUCTION INDICATED ( ) 2. REFER TO GENERAL NOTES SHEET S1 FOR SOILS INFO & REQUIREMENTS. 3. IF OVEREXCAVATION IS REQUIRED FOR ADEQUATE SOIL BEARING CONTACT ENG. 4. DO NOT SCALE DRAWINGS. SCALE: 1/4" = V -0 't C) Of- ON Of� N M X 00 O O Op rnrn 0z rnrn a0 a< c c J U 0 U � � 0 0 J j Y 0 Q C-) J N 00 r T r C r 0 z W W z c� z PROJECT: 0210 -13 DRAWN BY: TFA REVIEWED BY: JPL DATE: 10.11.2013 REVISIONS: FOUNDATION PLAN S2 rowN of VAIL Design Review Staff Approval By Joe Batcheller at 4:52 pm, Apr 28, 2014 INDICATES EXSTG. EDGE OF DECK EXSTG. DECK FRAMING NOT SHOVE 2x12 BLKG. BTWN. JOISTS @ BRG. PROVIDE GAP TO ALLOW DIFFERENTIAL - MOVEMENT BETWEEN EXSTG. DECK AND NEW DECK INDICATES EXSTG. RIM BD. — VIF PRIOR TO CONSTRUCTION INDICATES EXSTG. FLOOR FRAMING 1 S4 INDICATES NEW 10 "0 CONC. PIER ON NEW 28" O BELLED BASE (BIGFOOT BF24 OR EQUIV., TYP.) f'4KIT © /Nl TPTfI Fv17O (4�IT �L L FYP. DECK FRAMING PLAN PI AN n10TFS- w 0 V--n rt INDICATES PROPOSED HOT TUB LOCATION. IF RELOCATED CONTACT ENG. Deck limited to 13' 4" SCALE: 1/4" = 1' -0 1. NEW POSTS CONTINUOUS BELOW ARE INDICATED: 0 NEW POSTS FROM ABOVE NOT CONTINUOUS BELOW ARE INDICATED: ❑ 2. NEW CONSTRUCTION INDICATED ( ). EXISTING CONSTRUCTION INDICATED ( ). 3. NEW DECK JOISTS ARE TRTD. 2x12 @ 16" UNLESS NOTED OTHERWISE. 4. Q INDICATES CONNECTION TYPE. REFERENCE SCHEDULE SHEET S1 5. DO NOT SCALE DRAWINGS r r It C) oI­ Ir O I­ 'IT CO M D Il- CM X 00 6 Op CO V rnrn o 0 0z rnrn (2) -2,,12 a< Tf' 16" A N c - x12 N T. TD. (N N E 0 TRT ILS & UIV.) . 2x1 (1) -1/ 16' (DR LED "O x4" (VIF PPE ER TIM OLID / (4)- ER- RIM 0d OK ( D.) J R LA L FYP. DECK FRAMING PLAN PI AN n10TFS- w 0 V--n rt INDICATES PROPOSED HOT TUB LOCATION. IF RELOCATED CONTACT ENG. Deck limited to 13' 4" SCALE: 1/4" = 1' -0 1. NEW POSTS CONTINUOUS BELOW ARE INDICATED: 0 NEW POSTS FROM ABOVE NOT CONTINUOUS BELOW ARE INDICATED: ❑ 2. NEW CONSTRUCTION INDICATED ( ). EXISTING CONSTRUCTION INDICATED ( ). 3. NEW DECK JOISTS ARE TRTD. 2x12 @ 16" UNLESS NOTED OTHERWISE. 4. Q INDICATES CONNECTION TYPE. REFERENCE SCHEDULE SHEET S1 5. DO NOT SCALE DRAWINGS r r It C) oI­ 0') N O I­ 'IT CO M N Il- CM X 00 6 Op CO V rnrn o 0 0z rnrn a0 a< c c - 0 z W W z 0 z Lu J U o� U � � o O J � Y O Q C-) J N 00 T_ PROJECT: 0210 -13 DRAWN BY: TFA REVIEWED BY: JPL DATE: 10.11.2013 REVISIONS: DECK FRAMING PLAN S3 0 1 rowH OF VAIL Design Review Staff Approval By Joe Batcheller at 4 :52 pm, Apr 28, 2014 Irlh n1.10 rlC4140 (N) 10" O CONC. PIER (2) - #5's VERT (N) 2' -4 O BELLED BASE (BIGFOOT BF280R EQUIV., TYP.) SCALE: 3/4" = V -0 r 't C) CD I- 0*) N O I- ,* W � M N — I— M x00 �0i 00 CO V O� rn o0 0 a0 Q 2X a L r O C — Y' u W J U oF) U 00Lo J I--- Q O T- _j CU oo Q W J N CO 7— PROJECT. 0210 -13 DRAWN BY: TFA REVIEWED BY: JPL DATE: 10.11.2013 REVISIONS: DETAIL t - i — :: y I it' � I 1 i I �f f �; ► i � I I ; } I �I I I i I P' ry i f F LI �. �G.L '[�Q (.� ', �, I I !,, r „ � is �- I. ,I .I I (,. 1 � I '. .: i I r ( I� Ii .� I� � ti ,' I. '� ,' I` I• 11 - I � I� {f 3 I , t + P k 1 ...:n.a ..Par..r jq r A p 4 F A++M 1 'F 7— j g ro 9 8 NP _ NEW DECK x ..:.. p ADDITION � mow, c �._<- y ; X° kimam ,. ZIT `��P .T .�... ^�. II i f r E i t M M t � 6 _ f wm c f •, r 4 ' TI s i z i � 4 • S C.. t, - . i i ! ° 6 , 8 ¢j64 ' E .� F -I @ - '� , . � � ,,,.. p •. - � .,keg.. >s ", ..; _ �° ro .. ,dia�sA9e «pc i - � t ' e � ,.�- °,°...«.�m'.:.,�...:. .�:;+,o-�.�,«_ � ae.nt:.®�.�° .w».,..�,+..®r ®.sr �' 9 �� {{ a� " �a,R.- s+ �. G.., a.• �kY °i.o-- ��- 4�.,x.w.o ",�".�>G>ad�.a ,r.>�'.�w.r .�m,,,T,.�.- ..,,.,«.,.,�.»� k � � b " PL TO ' 1 F '. gR6M H Z ba^-r,. glv4v t µda. tip€ °?� i'',xa #,q ° 6 n .....,r..envwv:m..za«,r,nw>.�+- ,,,.macaw,– :.wn.w.,.. "..... +w.. .. [• i, ` .. wa,�A' w',. .�.wn,'i•a 's°^''w�marbwgrsb «n ✓i0,w'a.+ { fi v _ �..- _ 4 J�, �Y v R b. o ^� r ..- �,.>'� m � � � � � �, -n d§e�✓ fav®a, pf. y& �ryww Y �� L i F A q • � / r -« � 4 Maroc k w�N �°' � . E - _ .f _ � � { _ w! +"^'. T' o°,^ v. na. rmw�!. k�.'<, � .�n.y,�+..,tlw�i.-..p.40m.m•�� -n Ye. e......- 4 . .Ln.�run+� "w..WniN, lF�i+,eklhe. '^^ M...�.���+�.wv` e•T 6 � F pby, tg rq.,. .hh^'^tr.`� -„pkrk •' n„rawe °,. ..d ny 9¢.a ,y .. �'W°adtf. y ,i r P 'F T'^a. , • i T. I q�v;l .q _..._.,..,,. _ ....._...._...:._.w.w___, ol pq* r • e - � s..- r....-. x. w.• v.. n..:,.,. e-., r.: �.,. aw,.., m+ o: ,.w.mP.wwe�.w..,,wu,�.,.:,..w.. '....:..w. Nv�,m, ....+e.m- +M=ewin..:..m.wum+, .,:: c_ °...a,... °.. .., s„-+ -i PkR,.k A �Y .,, n •"...,.....,.,e..-- .- ....« -«..q F:a..:- „.,,. = `M- R�.,.n �r '••�, -'off xn -Y <rw.r.,,:xr�,.:.... -.w,. wp�..�.:w.,,...,..,, _ +!' � [ � �, «.,. � as @ q r^ w f ., s. t , - - � ^ c # m . q ° 4. - 1 ° k ,.� r , 4 n. 4�• &” h � y- .-Fe* "`� �� � i � , . r „i .. ._._.+.,.. ...:.. .... .... .. ..."..,.a,... �. ._,.e,... .. ... .,r.,., -.. . -, ,. ., _. -.. ......k ...:s . +n,. ..a .. -... :. . ...... .... ,: :..,. _ .�.r ...« w-r.- ..w..e- r». :.. .. .,-T, n., ,: �: w. .,..,:".. n <we..r �.,..., .,w+.,.e.:..... -.w,., wnmm, ,m.:.ra>.a�wwr. n,r:e .r. .., .�e k .. «-..w a- ».._. .,.m. ..,:.� ,, wa. ®xr.e•xa�.m• .. ma+ .ww+.,°,.:e- a.+,ew+ssL.Iw• +..,.: .. , C) V R_V t l'� klk/ A�r �4 rl-!� 4 Design Review 7, Staff Approval ELECT-, p-q &k11aA4__.rZ 1__�> ME, 'C L .. .. .... ..... .... . UMIT rF: um I J I N1 C11-S. F-2 ^1 & By Joe BatcheHer at 4:53 pm, Apr 28, 2014 . . . ..... .. .. . TOWN OF VA IL L_D as! . . . ....... F P-,L IA TI'A L DUCT' F-AW 4 W .... . ......... .. . ... .... �41 ... .. . . .... J1, (t Ij _7T �V% �E_ 1D IP11 _4 L I- L I V �_i z> 'k M 18 . ... ..... . 14 17 C �_t TP_ D 4 '14W/� 'Z�� `15 C� 0 . . . . ... ..... F ra" �J_ .. ........ LA 7 a 4 H .. .. . . . ....... .. j rt �7.�7 t -P 7V ­4! r j ..... ... .. .. .... ...... I'll A . ... .... . . iy�rl P 7 .7 LL, D. .... .... j . .... ... . ... ... .... ....... SMOKE AND CO DETECTORS WILL BE ADDED TO COMPLY WITH CURRENT CODES FOR ALL AREAS COMPLIANCE WITH 2012 IECC ELECRICAL LOAD CALCS BELOW PROVIDED BY EAGLE VALLEY ELECTRIC, INC VAI The following is a current Electrical Load Calculation, based on National Electric Code - Article 220.82 (A) (B) (C) 1953 square ft. g 3 watts - 5,859 --------- - Appliance circuits 4 (0, 1,500 - 6,000 C� Laundry - 1,500 70 _ — ---- Dryer - 5,000 Disposal - 900 Dishwasher - 1,500 Microwave - 1,500 Refrigerator - 1,400 Range - 10,000 Heat/Vent/Light - 1,800 Heat Trace Cable 3,200 watts (:a 125% 4,000 Total - 39,459 1st I OK watts - 10,000 29,459 g 40% 11,784 Boller (Heat) 1,500 Total Demand 23,284 Existing Electrical Service is 125 Amps g 120/240 Volts 23 284 Wattsg 240 Volts= 97 Amps .. . ..... ...... .......... 7 ... .... ... . ..... .. .... .. T. V, 7 JE U Ek F7- 4! I10th Mountain Builders, LLC PO BOX 955 Minturn, Colorado 81645 Jeff Armistead - General Contractor C - C) 4 970-471-0618 NOTE: These scans are the original blueprints from 1974 and are being submitted for reference purposes only and are not intended to represent any structural changes to the unit, only to represent the existing condition of the Unit. Q I W-1-4 L I Gl F I., "TO C_ Lj Q I W-1-4 L I Gl N1 0 T L a Wrla�, X LA A� �-A T�� j__:, V�7 %40 F r_CD A 71 \A 17 4 1/,/ T7-1./- 14 LA, 1,p 'z-„mom 1-d F'tom FR, Z`z Cl, m 1 9 P 11-vAl Y2, j"l U T"; E L ' C-T- 13 1 E 7 _ Ar,Z- ra-077 0'1'-A A� � t,� 7 (-_S -J �:D W I r__ t F -I j 7. F'R0N/1VD'F_ :5 �ZMCp ql 4,,LAT�1,A Ll 1 NA "TO C_ 177 V­ ED 1_1 C,, T x'714_C' F_ C-_ _5 To jt�"Z IP �„®Er,'n ., 5" C', 1< 6 as T-7 a- T J­� - �47 T C� �b 1�70 N1 0 T L a Wrla�, X LA A� �-A T�� j__:, V�7 %40 F r_CD A 71 \A 17 4 1/,/ T7-1./- 14 LA, 1,p 'z-„mom 1-d F'tom FR, Z`z Cl, m 1 9 P 11-vAl Y2, j"l U T"; E L ' C-T- 13 1 E 7 _ Ar,Z- ra-077 0'1'-A A� � t,� 7 (-_S -J �:D W I r__ t F -I j 7. F'R0N/1VD'F_ :5 �ZMCp ql 4,,LAT�1,A Ll 1 NA