TO: Steve - SRE
�
I
II DATE.• 04/22/14 JOB NUMBER: 1404-18
i
� PROJECT.• Landmark 504 Remodel
I
I
I
i ❑ RF/ ❑ MEET/NG NOTES � RESPONSE ❑ CLAR/F/CAT/ON/CHANGE
I
iI was informed of the desire to penetrate the concrete wall with holes for plumbing behind the kitchen on
I the main level and behind the master bathroom on the upper level.
I
Kitchen:
i
�, (1) - 3" diameter hole to be added approximately 51" from party wall and 15" above the floor.
Master Bath:
, (1) - 5" diameter hole approximately 44" from party wall at the floor level.
(2) - 1 1/2" diameter holes approximately 102" from party wall at the floor level.
I've reviewed these locations, and these hoJes may be cut into the concrete wall with the following
Irequirements:
I
The wall will most likely need to be x-rayed to avoid any reinforcement.
The (2)-holes at the master bath shall be spaced at least 6" apart (center to center).
I
; Please do not hesitate to call with any questions.
KRM Consultants, Inc.
I Structural Engineering & Design