HomeMy WebLinkAboutB14-0216 corrections required
Date: 6/26/2014
Re: B14-0216 1067 Ptarmigan
Dear Shelly Mello ,
RESPONSE INSTRUCTIONS
● Submit two complete sets of revised construction documents containing the requested
information with all plan revision items clouded or otherwise identified.
● Please respond in writing to each comment with a response letter addressing each comment.
BUILDING
COMMENTS
Architectural Comments:
General
1. Landscape architect to stamp, date and sign plans per DORA regulations, State of Colorado.
Sheet L1.1
1. Show gates to be in compliance
with section AG 105.2 (8.2) IRC 2012 edition.
2. Indicate how barrier requirements are to be met per section AG 105.(9) and AG 105.5 IRC 2012 edition.
Sheet PL.1
1. Show how suction
outlets for the pool and spa are to comply with section AG 106 IRC 2012 edition.
Structural Comments:
Reviewed and accepted
Plumbing Comments:
General
1. Provide gas piping plans
to include, developed length, btu demand, branch circuits, pipe sizes, pressure being used, pipe materials, and location.
Mechanical Comments:
Reviewed and accepted
Electrical Comments:
Reviewed and accepted
PLANNING COMMENTS
Reviewed and accepted
FIRE COMMENTS
NA
PUBLIC WORKS COMMENTS
Proposed
snow melt shall require a separate zone in the right of way and a permit from the Public Works Department
Sincerely,
Martin A. Haeberle
Chief Building Official