HomeMy WebLinkAboutB14-0261 load calcs Single Family Service Calculation
Adddress:1738 Golf lane Unit p64 �e p��a
Date:5-1LL14
Genxal lightlng Lwd 2,500 Sq.Ft. 3 VA 7,500.00 � Tobl
SmatlAppliance Z Q7Y 3,500 VA 3,000.00 Total Table220.12,Tabk220.42,
laundryGrcuit 1 1500 VA 1,500.00 - Total 22052�AJ,22052�8)
12,000.00 SubTotal
3,000.00 3000 VA at 100%
3,150.00 9,000 VA-3,000 VA et 35%
6,150.00 NM load
Range Demanded Load 1 QN 8,000 VA 12 KW use BKW,if�eate� Demand fac[or 5,000.00 Total Table 220.55
than 12 KW add 5%for
�ch Kw
Dryer Demanded Load 1 Qtt 5,000 VA 5,00 or name plare rating Demand Factar 5,000.00 Toql 220.54,Table 220.54
which ever is greter
F6ced Applknx Demanded
Dishwasher 1 QTV 1,20D VA 1,200.00 2I053
Trash Compactor 1 Q7Y 800 VA 800.0p
Ice Machine QTY 1,200 VA 0.00
Fridge 3 QTY 1,000 VA 1,000.00
ffeezer 0 QTY 1,000 VA O.Op
WinefridBe QiY 800 VA 0.00
HotTUb 4TY 4S� VA 0.00
luauzziTub 0 QTY 2,500 VA 0.00
Suana 0 qTY 3,800 VA 0.00
Steamer Q7V 5,000 VA 0.00
Incta Hot QTY 1,200 VA 0.00
Attic Fen Q1Y VA O.pp
Micorwave 3 QTY 1,500 VA 1,500.00
Water Heater QTY 6,800 Vp p,Op
Dispoul 1 QTY 1,SOD VA 1,500.00
QN 1,500 VA 0.00
Q7Y 1,500 VA 0.00
an�:
6.000.00
0.75
Demand Fac[or 4 or mwe appliances
45�.� Total
Heating and A/C Load 1 QlY 11,300 VA 11,300.00 Total 22051,220.50,220.60
100%of Largest Load ONLY
25%of largest Motor 1 47Y 375 VA Motw WadOnly-S00%is 375.00 Tolal
alrhdy included In 22050,430.24,Mnex D
Gkulatlon Example Dl�b)
35,325.00
240 Single Phase
147.19 Amps
�1 � ��� � .