HomeMy WebLinkAboutB14-0237 REV4 Balance Report � � Air Balancing
� Hydronic Balancing
seRV�c�s,iNC. System Analysis
Energy Evaluation
Commissioning
� � � � � � ESTING, ADJUSTING & BALANCING
�
��(; � i� ��14 REPORT FOR
TOWN OF VA T C/L-Vail
Project Address: 169 N.Frontage Rd.Vail,Co,81657
TAS Job#2014-178-CM W
ARCHITECT Archcentric, P.C.
ENGINEER BCER Engineering, inc.
CONTRACTOR Trautman& Shreve
REPORT ISSUE DATE December 2, 2014
..��
�� o
�
TESTING,ADJUSTINCi AND BALANCINQ 6UREAU
O THE PROFESSIONAVS CHOICE"`
Certiflcation No. 2687 Certificafion No. B8009004C
���1 � - ���� `���"'
2065 S.RAftITAN STREET DENVER,CO.80223-U382 PHONE(303)-649-1213 FAX(303)-649-1216
Email tab@tabservicescolorado.com WEBSITE tabservicescotorado.com
I
� � Serving Colorado forover 30 years. Air Balancing
�
Hydronic Balancing
SERVICES, iNC. System Analysis
Fire Life Safety
Fume Hood Certificafion
Hospital Pressurization
NEBB I TABB CERTIFICATlON STATEMENT
FOR
CIL - Vail �
The data presenfed in this report is a record of system measurements and final adjustments that
have been obtained in accordance wifh the current edition of the " NEBB !TABB PROCEDURAL
STANDARDS FOR TESTING, ADJUSTING, AND BALANCING OF ENVIRC}NMENTAL
STSTEMS". Any variances from design quantities v�hich exceed NEBB /TABB tolerances are
noted in the Project Summary
-�
� P� °
0
TESTiN�,AQJUSTiNQ AND BALANCiNQ BUR6AU
O THE PltOFESSIONAL'S CHOIC@'"
H
Certlflcation No. 2687 Certification No. BB009004C
�P�gervlce � ,�P�s u��8 s�,�ic
� esoo�oo c
r•a �
3� !VCMNER s��� N0728
C TIF'rCATIpN ��t Valk1{JMess
��3T
Exp.3/31/i5 �
�� ?131/201 �O
�''a �� 9
2065 S. Raritan Stre�t, rnt A, Denver, CO 80223 �
Office- {303) 649-1213 FA1�- (303) 64�'1�16 Email- fab tabservicescolorado.com
@
Website-tabservicescolorado.com
� ~
� IIVSTRUMENT LIST
S�RVICBS, INC.
PROJECT: C/l. -Vail
Calibration
Enstrument Make Model Serial Number Date
Air Data Meter Shorlridge AbM-860C M07617 8/31/2009
Air Data Meter Shortridge ADM-860 M91854 213/2014
Alr Data Meter Shorfridge ADM-860 M88051 10/14/2090
Air bata Meter Shortridge ADM-860C M11250 3/26/2013
Air Data Meter Shortridge ADM-864 M92637 3I25I2014
Air Data Meter Shortridge ADM-8SOC M07781 4/5/2012
Air Data Meter Shortridge ADM-860 M08022 7/10/2010
Air Data Meter Shortridge ADM-860 M97878 7I30/2013
Air Data Meter Shortridge ADM-860 M90858 4123/2014
Air Data Meter Sho�tridge ADM-860 M98122 3/19/2011
Anemometer Extech AN200 11433098
Hydro Data Meter Sho�lridge HDM-300 W95082 5i2l2013
Hydro bata Meter Sha�iridge HDM-300 W95054 14/12/2019
Hydro Data Meter Shartridge HDM-250 W98142 1/16/2012
Hydro Dala Meter Short�idge HDM-30b W98155 9/612U13
Hydro Data Mefer Shortridge hIQM-300 W01054 6/1/2012
TachometerlStrobe tioto EliT-500 503060
Tachometer/Strobe Hoto EHT-500 503061
Tachometer/Sl�obe Hoto EHT-500 503082
Tachometer/Strobe Albuquerue Ind CDT-2000HD 1303916 8/2/2073
Tachometer/Strobe Pioneer DT-25 P-2834
Tachometer/Strobe Pioneer DT-25 P-2858
Tachometer/Strobe Shimpo DT-311 22018501
Tachometer/Strobe Shimpo EE-1 10959808
Psychromefer Exfech RH390 5144403 5/31I2U13
Thermometer Atkins 39658-K tab-002 5/31/2013
Thermometer Fluke 51 I I 844080004
Thermomater Fluke 50R 7549045
Thermometer Fluke 51 45150713
Thermometer Fluke 51 I I 75600172
7herr�tomeEer Fluke 80PK-4A 247613
VoIt/AMP Meter Amprobe ACD•1UTRMSPRO 2339028d
Voit/AMP Meter Arnprobe ACD-'[OTRMSPRO 9Q601262 5/30/2013
VoEt/AMP Meter Amprobe ACD-10TRMSPRO A33114T9
VoIUAMP Meter Amprobe ACD-10TRMSPRO 054500234
Volt/AMP Meter Amprobe ACD-1oTRMSPRO 05450Q209
VoIt1AMP Meter Fluke 920 940602f5
VoIt/AMP Meter Fluke 902 92680087
VoitlAMP Meter Fluke 902 86$60050
Ciamp on Flowmeter Controlotron 1010W�P1 EU0883
Clamp on Flowmeter Confrolotron 101aWDP1 U1454
Duct Pressure Tester McGilf Leak Detective E.CT-5CA
L.aser Particle Counter Climet CI-50o 000955
� � ABBREVIATIONS
S�RVICES, INC.
PROJECT: C/L -Vail
ACU -Air Conditioning Unit MEAS'D - Measured
AHU -Air Handling Unit MIN - Minimum
AMP -Amperage NA - Not Applicable
ATMOS -Atmosphere NG - Not Given
BAS- Building Automation System PD - Pressure Drop
CD - Ceiling Diffuser PF - Power F'actor
CFM - Cubic Feet/ Minute PH - Phase
DDB - Dual Duct Box REQ'D - Required
DP - Differential pressure RF - Return Fan
EF - Exhaust Fan RH - Reheat
EFF - Effeciency RPM - Revolufions/Minute
FCU - Fan Coil Unit RTU - Roof Top Unit
FLR. - Flaor SF - Supply F'an
FPM- l=eeU Minute SG - Supply Grilfe
FP VAV- Fan Pawered Variable Air Volume SR - Supply Register
FR - Frame SWR - Side Wall Register
GPM - Gallons/ Minute TSTAT-Thermostat
HP - Horsepower VAV-Variable Air Volume
HZ - Hertz Volt -Voitage
LT - Light Troffer VP -Vefocity Pressure
MAX - Maximum XMTR - Transmifter
MEAS'D - Measured
� r
� RECAP SUMMARY
Page 2
SERVICES, INC.
PROJECT: C/L -Vail
Maximum Minimum K.F.
S stem Branch Re uired Measured % Set oint Set oint Remark
AHU-1 Total 20404 22320 109
VAV-1 900 940 104 '�.�2
VAV-2 400 405 101 1.36
VAV-3 300 290 97 �•�4
�ther 18800 19035 101
RF-1 Total 20400 20390 100
� � Page 3
� EQUIPMENT DATA TEST REPORT Date 11/25/14
SERVIC�S, INC. Tech �.R.
PROJECT: C/L - Vai) SYSTEM: AHU-1
UN1T DATA MOTOR DATA X 2
Make HAAKON lNDUSTRIES Make Bafdor
Model # AIRPAK HP RPM 15 1765
Seriaf # 1�4-8530-707-C PH T e 3 Nof Given
T e Draw Thru SF Volt 1.15 230/460
Ratin 22540 CF'M 5.50 " T.S.P. FR Am s 54T 35.4 / 17.7
Re uired 20400 CFM EFF P.F. 93.0 86.0
STARTER DATA DRIVE DATA X 2
Make ABB Motor Drive 3 - 3V6.50 SDS
Model # ACH550-VDR-046A-2+�267 Motar Bore SDS x 1 S/8"
Size Not Given Fan Drive 3 - 3V5.30 SDS
Heater Electronic Fan Bore SDS x 1 15/'f6"
Ratin 'f 5 H.P. - 240 V. - 46.2 Am s Beft Size 3VX450
Re d. Htr. No. Belts 3
Ratin Drive Chan e None
TEST DATA TEST DATA
CFM 22,320 IN OUT eP
Volt 210 -209 - 210 Mixins section -0.38 " -0.71 " 0.33 "
SF'-1 SF-2 Filters -0.71 " No Access NA
RPM 1919/ 1918 1919 / 1918 DX Coil No Access -2.09 " NA
Am s 27.1 /27.3 27.1 /27.3 Fan -2,09 " 1.06 " 3.15 "
Hertz 53 53
Minimum Outside Reguired 250p CFM
Minimum Outside Air Set @ 2545 CFM
Stafic Pressure Setpoint = 0.80"
1) Final Readings were taken while in Auto, unab�e to Isolate Fans due to Low Outside Temp
& Freeze Protection systems.
2) AHU-1 Fan AirFlow Station reading 22,000 CFM.
_ __
, � Page 4
� VELGRID TEST REPORT
�ate 11/25/'i4
SERViCES, INC. Tech F.R.
PROJECT; C/L -Vail SYSTEM: AHU-1 SF
LOCATION: Discharge of the DX Coil DUCT S.P. : NA
Duct Required Actual
Size 90" x 72" Sq. F't. 45.00 FPM 453 CFM 20400 FPM 496 CFM 22318
PT. A B C D E F G H I J K L M
1 499 465 467 493 478 507
2 518 479 �94 548 547 487
3 533 546 575 56 515 505
4 553 468 540 543 549 538
5
6
7
8
9
10
11
12
13
14
'i 5
16
11943 = 496 FPM X 45 Sq. Ft. = 22318 CFM
24
1 � Page 5
� VELGRID TEST REPORT
Date 11/25/14
SERVICES, INC. Tech F.R.
AHU-1
PROJECT: C/L - Vail SYSTEM: Min OSA
LOCATION: Inlet of Sound Attenuator DUCT S.P. : NA
Duct Required Actual
Size 86" x 13.5" Sq. Ft. 8.06 FPM 310 C�M 250Q FPM 3'!6 CFM 2543
PT. A B C D E F G H I J K L M
1 341 37$ 32$ 257 331 258
2
3
4
S
6
7
8
9
10
11
12
93
14
15
1S
1893 = 396 FPM X 8.46 Sq. Ft. = 2543 CFM
6
� � Page 6
� AIR OUTLET TEST REPORT
Date 11/21/14
SERVICES, iNC. 7ech F.R.
AHU-1
PROJECT: C/L -Vail SYSTEM: VAVs
Area Q enin Desi n Initial Final
Served No. T e Size AK VEL CFM VEL CFM VEL NOTE VEL CFM
VAV-1 DT 14"x 12" 1.17 769 900 1056 1235 804 940
Total 900 1235 940
Min 135 145
Heatin 450 460
VAV-2 1 SWR 12"x 6" 0.41 488 200 253 105 493 200
Total DT 20"x 8" 1.11 360 400 385 425 366 405
Min 80 9�
Heatin 204 2�0
VAV-3 DT 16"x 8" 0.89 337 300 225 200 323 290
Total 300 200 290
Min �0 ��
Heafin 200 205
� ■ Page 7
� TRAVERSE TEST REPORT
Date 11/20/14
SERVICES, lNC. Tech F.R.
AHU-1 Suppiy
PROJECT: C/L -Vail SYSTEM: VAV-1
LOCATION: After VAV-1, Before the autlets DUCT S.P. : -0.04"
Duct Required Actual
Size 14" x 12" Sq. Ft. 9.17 FPM 769 CFM 900 FPM 804 CFM 940
PT. A B C D E F G H I J K L M
1 -551 1199 1437 9398
2 -345 1054 1532 157Q
3 -430 749 1542 '1835
4 -533 -168 1346 9226
5
6
7
8
9
�a
11
�z
'f 3
14
15
'[6
12861 = 804 FPM X 1.17 Sq. Ft. = 940 CFM
16
` � Page 8
� TRAVERSE TEST REPORT Date 11/21/14
SERVICES, fNC. 1'ech F.R.
AHU-1 Supply
PROJECT: C/L -Vail SYSTEM: VAV-2
LOCATION: After VAV-2, Before the outlets DUCT S.P. : Q.11"
Duct Required Acfual
Size 20" x 8" Sq. Ft. 1.1'� FPM 360 CFM 400 FPM 366 CFM 406
PT. A B C D E F G H I J K L M
1 258 332 338 313
2 381 449 388 400
3 311 415 424 406
4 311 41'i 496 384
5 318 355 375 336
6
7
8
9
10
11
12
13
'I 4
15
96
7321 = 366 FPM X 1.11 Sq. Ft. = 406 CFM
20
� ■ Page 9
� TRAVERSE TEST REPORT
Date 11/29114
SERVICES, INC. Tech F.R.
AHU-1 Suppiy
PROJECT: C/L - Vail SYSTEM: VAV-3
LOCATiON: After VAV-3, Befare the out[ets DUCT S.P. : 0.08"
Duct Required Actual
Size 16" x 8" Sq. �'t. 0.89 FPM 337 CFM 300 FPM 323 CFM 288
PT. A B C D E F G H I J K L M
1 320 318 3Q6 277
2 348 363 344 321
3 332 336 357 338
4 298 296 317 304
5
6
7
8
9
10
11
'i 2
13
14
15
16
5169 - 323 FPM X 0.89 Sq. Ft. = 288 CFM
16
1 � Page 10
� AlR OUTLET TEST REPORT
Date 91/24/'i 4
SERVICES, INC. TeCh F.R•
AHU-1 C.V.
PROJECT: C/L -Vail SYSTEM; Zones
Area � enin Desi n Initial �inal
Served No. T e Size AK VEL CFM VEL CFM VEL NOTE VEL CFM
1 DT 20"x 26" 3.61 208 750 28 100 225 815
2 DT 30"x 20" 4.17 576 2400 1131 4715 557 2325
3 DT 1 s"x 30" 3.75 640 2400 693 2600 650 2440
4 DT 1 s"x 18" 2.25 0 0 42 95 1 8 20
5 DT 30"x 20" 4.17 576 2400 218 9'i� 601 2510
Zone - 4 6 DT 2s��x zo�� 3.61 166 640 1095 3955 178 640
Zone - 2 7 DT 28"x 16" 3.11 965 3000 787 2450 979 3445
Zone - 5 8 DT 26"x 20" 3.6'i 1163 4200 'f 197 4320 1159 4185
Zone - 6 9 DT 2s"x 20" 3.61 845 3050 1199 4330 8�46 3Q55
Total 18800 23475 19035
1) Balance damper is 100% Closed.
� ■ Page 11
� TRAVERSE TEST REPORT
Date 11/21/14
SERVICES, INC. Tech 1=.12.
AHU-1 Supply
PROJECT: C/L - Vail SYSTEM: Traverse-1
LOCATION: After the MVD, Before the outiets. Initial DUCT S.P, : 0.01"
Duct Required Actuai
Size 20" x 26" Sq. Ft. 3.61 FPM 208 CFM 750 FPM 28 CFM 101
PT. A B C D E F G H 1 J K L M
1 37 29 82 4q
2 0 0 35 0
3 56 0 0 0
4 3$ 30 40 -43
5 43 76 56 39
6
7
8
9
10
11
12
13
14
15
16
562 - 28 FPM X 3.61 Sq. Ft, = 101 CFM
20
1) Initial Readings
` � Page 12
� TRAVERSE TEST REPORT
Date 11/24/14
S�RViCES, INC. 7ech F.R.
AHU-1 Supply
PROJECT: C!L -Vail SYSTEM: Traverse-1
LOCATION: After the MVD, Before the outlets. Final DUCT S.P. : 0.0'f 3"
Duct Required Actual
Size 20" x 26" Sq. Ft. 3.61 FPM 208 CFM 750 FPM 225 CFM 814
PT. A B C D E F G H I J K L M
1 246 221 216 293
2 171 124 159 317
3 179 13'I 175 328
4 247 'i86 227 310
5 204 237 261 276
6
7
8
9
10
11
12
13
14
15
16
4508 -- 225 FPM X 3,61 Sq. Ft. = 814 CFM
20
1) �inal Readings.
L � Page 13
� TRAVERSE TEST REPORT
Date 11/21/14
S�RVICES, INC. Tech �.R.
AHU-1 Supply
PROJECT: C/L -Vail SYSTEM: Traverse-2
LOCATION; After the MVD, Before the outiets. Initial DUCT S.P. : 0.07"
Duct Required Acfual
Size 30" x 20" Sq. Ft. 4.17 FPM 576 CFM 2400 FPM 1130.9 CFM 4716
PT. A B C D E F G H I J K L M
1 539 1326 1160 'E115 963
2 857 1250 1235 1281 1130
3 'l296 1421 'i197 1345 1261
4 1041 1238 951 987 1024
5
6
7
8
9
10
11
12
13
14
15
16
22617 = 1131 FPM X 4.17 Sq. Ft. = 4716 CFM
20
1} Initiai Readings
� � Page 14
� TRAVERSE TEST REPORT
Date 19/24/14
SERVICE3, INC. Tech F.R.
AHU-1 Supply
PROJECT: C/L -Vail SYSTEM: Traverse-2
LOCATION: After the MVD, Before the outlets. Final DUCT S.P. : -0.03
Duct Required Actual
Size 30" x 2Q" Sq. Ft. 4.17 FPM 576 CFM 2400 FPM 557 CFM 2323
PT. A B C D E F' G H I J K L M
1 1560 1571 1595 1675 1542
2 945 577 808 831 1Q31
3 514 -261 -441 -367 529
4 -294 -442 -2'12 -306 206
5
6
7
8
9
10
11
12
13
14
15
16
11141 = 557 FPM X 4.17 Sq. Ft. = 2323 CFM
20
1) Final Readings.
A � Page 15
� TRAVERSE TEST REPORT Date 11121/14
SERVICES� INC. Tech F.R.
AHU-1 Supply
PROJECT: C/L - Vail SYSTEM: Traverse-3
LOCATION: After the MVD, Before fhe autlets. Initial DUCT S.P. ; -0.03"
Duct Required Actua!
Size 18" x 30" Sq. Ft. 3.75 FPM 640 CFM 2400 FPM 693 CFM 2600
PT. A B C D E F G H I J K L M
1 1487 1385 1466 1359
2 1540 17�42 1698 1798
3 1531 1160 1202 1662
4 518 224 -426 528
5 -205 -335 -470 133
6 -34'f -493 -315 -290
7
8
9
10
11
12
13
14
15
16
16638 -- 693 FPM X 3.75 Sq. Ft. = 2600 CFM
24
1) Initiai Readings
.
� � Page 16
� TRAVERSE TEST REPORT
Date 11/24/'f 4
SERViCES, INC. Tech F.R.
AHU-1 Supply
PROJEGT; C/l. -Vail SYSTEM: Traverse-3
LOCATION: After the MVD, Before the outlets. �inal DUCT S.P. : -O.QS"
Duct Required Actuaf
Size 18" x 30" Sq. Ft. 3.75 FPM 640 CFM 2400 FPM 650 CFM 2438
PT. A B C D E F G H I J K L M
1 1548 1521 1569 1602
2 1481 1689 1747 1699
3 1572 1122 953 1684
4 325 -331 -242 691
5 -1$5 -420 -478 -343
6 -435 -436 -377 -354
7
8
9
10
11
12
13
14
15
16
15602 - 650 FPM X 3.75 Sq. Ft. = 2438 CFM
24
9} Final Readings.
j ■ Page 17
� TRAVERSE TEST REPORT Date 11/21/14
SERViCES, INC. Tech F.R.
AHU-1 Supply
PROJECT: C/L -Vail SYSTEM: Traverse-4
LOCATION: After the MVD, Before the outiets. Initial DUCT S.P. : 0.00"
Duct Required Actual
Size 18" x 18" Sq. Ft. 2.25 F'PM 0 CFM Q FPM 42 CFM 94
PT. A B C D E F G H 1 J K L M
1 68 38 79 129
2 74 63 0 72
3 98 56 25 32
4 -53 52 -39 -25
5
6
7
8
9
10
11
12
13
14
15
16
669 -- 42 FPM X 2.25 Sq. Ft. = 94 CFM
16
9) Initial Readings
1 � Page 18
� TRAVERSE TEST REPORT
Date 11/24/14
SERVICES, INC. Tech F.R.
AHU-1 Supply
PROJECT: C/L -Vail SYSTEM: Traverse-4
L4CATION: After the MVD, Befare the outlets. Final DUCT S.P. : 0.001"
Duct Required Actual
Size 18" x 18" Sq, Ft. 2.25 FPM 0 CFM 0 FPM 8 CFM 18
PT. A B C D E F G H I J K L M
1 97 39 0 134
2 55 81 0 54
3 26 0 -72 -57
4 0 -68 -64 -94
5
6
7
8
9
10
11
12
13
14
15
16
131 = 8 FPM X 2.25 Sq. Ft. = 18 CFM
16
1} Final Readings,
� � Page 19
� TRAVERSE TEST REPORT
Date 11/21/14
SERVICES, INC. Tech F.R.
AHU-1 Supply
PROJECT: C/L - Vail SYSTEM: Traverse-5
LOCATION: After the MVD, Befare the outlets. Initial DUCT S.P. : -0.02"
Duct Required Actual
Size 30" x 20" Sc�. Ft. 4.17 FPM 576 CFM 2400 FPM 218 CFM 9Q8
PT. A B C D E F G H I J K L M
1 935 921 796 834 1349
2 305 -147 -203 176 458
3 389 -287 -439 -337 '182
4 106 -341 -200 -44 -96
5
6
7
8
9
1Q
11
12
13
94
15
16
4357 - 218 FPM X 4.17 Sq. Ft, = 908 CFM
20
1} Initial Readings
� � Page 20
� TRAVERSE TEST REPORT
Date 11/24/14
SERVICES, INC. Tech F.R.
AHU-1 Supply
PROJECT: C/L -Vail SYSTEM: Traverse-5
LOCATION: After the MVD, Before fhe outlets. Final DUCT S.P. : -0.03"
Duct Required Actual
Size 30" x 20" Sq. Ft. 4.17 FPM 576 CF'M 2400 FPM 641 CFM 2508
PT. A B C D E F G H I J K L M
1 1629 9734 1734 1795 1873
2 901 448 769 1105 1233
3 405 -365 -433 551 596
4 -139 -542 -376 -544 -341
5
6
7
8
9
10
11
12
'13
14
'i 5
16
12029 = 601 FPM X 4.17 Sq. Ft, = 2508 CFM
Za
1} Final Readings.
� � Page 21
� TRAVERSE TEST REPORT �
Date 11/21/14
SERVICES, INC. Tech F.R.
AHU-1 Zone -4
PROJECT: C/L - Vail SYSTEM: Traverse-6
LOCATiON: After the MVD, Before the outlets. Initial DUCT S.P. : 0.48"
Duct Required Actual
Size 26" x 20" Sq. Ft. 3.69 FPM 166 CFM 600 FPM 1Q95.3 CFM 3954
PT. A B C D E F G H I J K L M
1 1515 1539 1568 1587 1625
2 115'i 1088 1193 '[564 1268
3 313 476 912 1094 1254
4 -334 1042 840 1062 1149
5
6
7
8
9
'14
11
12
'13
14
15
16
21906 = '1095 FPM X 3.61 Sq. Ft. = 3954 CFM
20
1) Initial Readings �
� � Page 22
� TRAVERSE TEST REPQRT
Date 11/24/1a
SERVICES, INC. 7ech F.R.
AHU-1 Zone -4
PROJECT: C/L -Vail SYSTEM: Traverse-6
LOCATION: After the MVD, Before the outlets. �inal DUCT S.P. : 0.08"
Duct Required Actual
Size 26" x 20" Sq. Ft. 3.61 FPM 166 CFM 600 FPM 178 CFM 641
PT. A B C D E F G N I J K L M
1 502 515 345 329 474
2 408 218 212 63 100
3 312 189 109 -68 -186
4 154 122 -67 -45 -136
5
6
7
8
9
10
1'i
12
13
14
15
16
3550 = 178 FPM X 3.69 Sq. Ft. = 641 CFM
20
1) Fina1 Readings.
� � Page 23
� TRAVERSE TEST REPORT Date 11/21/14 �
SERVECES, INC. 7'ech F.R.
AHU-1 Zone -2
PROJECT: C/L -Vail SYSTEM: Traverse-7
LOCATION: After the MVD, Befare the outlets. Initial DUCT S.P. : 0.47"
Duct Required Actual
Size 28" x 16" Sg. Ft. 3.1'i FPM 965 CFM 3000 FPM 787 CFM 2448
PT. A B C D E F G H I J K L M
1 373 556 1167 1236 1364
2 336 632 753 945 1198
3 5'i 9 431 679 646 1191
4 49 8 7'i 8 632 840 1106
5
6
7
8
9
10
91
92
13
14
15
16
'f 574Q = 787 FPM X 3.11 Sq. Ft. = 2448 CFM
20
1) Initial Readings
� � Page 24
� TRAVERSE TEST REPC?RT
Date 11/24/14
SERVICES, INC. Tech F.R.
AHU-1 Zane -2
PROJECT: C/L -Vail SYSTEM: Traverse-7
LOCATION: After the MVD, Before the outlets. Final DUCT S.P. : 0.52"
Duct Required Actual
Size 28" x 16" Sq. Ft. 3.11 FPM 965 CFM 3000 F'PM 979 CFM 3044
PT. A B C D E F G H I J K L M
1 883 '032 1258 1446 1427
2 637 857 1281 1123 1997
3 612 640 844 1003 1064
4 601 738 878 846 12�4
5
6
7
8
9
10
11
12
'[3
14
15
16
18599 = 979 FPM X 3.11 Sq. Ft. = 3Q44 CFM
19
1} Final Readings.
� � Page 25
� TRAVERSE TEST REPORT bate 19/21/14
SERVICES, INC. Tech F.R.
AHU-'i Zone - 5
PROJECT: C/L -Vail SYSTEM: 7raverse-8
LOCATION: After the MVD, Before the outfets. Initial DUCT S.P. : 0.31"
Duct Required Actual
Size 26" x 2Q" Sq. Ft. 3.61 FPM 9163 CFM 4200 FPM 1197.3 CFM 4322
PT. A B C D E F G H I J K L M
'i 2252 1966 2066 '1807 1723
2 1919 1'i87 882 559 345
3 1572 784 643 254 444
4 1651 1389 991 865 654
5
6
7
8
9
10
11
92
13
14
15
'I 6
23945 = 9197 FPM X 3.61 Sq. Ft. = 4322 CFM
20
1} Initial Readings
_
� � Page 26
� TRAVERSE TEST REPORT
Date 11/24/14
SERVICES, INC. Tech F.R.
AHU-1 Zone - 5
PROJECT: C/L -Vai! SYSTEM: Traverse-8
LOCATiON: After the MVD, Before the outlets. Final DUCT S.P. : 0.25"
Duct Required Actual
Size 26" x 20" Sq. Ft. 3.61 FPM 1163 CFM 4200 FPM 1158.8 CFM 4183
PT. A B C D E � G H I J K L M
9 2084 2{�04 1823 1941 1893
2 1908 1777 1519 782 554
3 1247 1397 1123 587 302
4 436 503 762 322 212
5
6
7
8
9
10 �
11
12
13
14
'!5
16
23176 - 1159 FPM X 3.61 Sq. Ft. = 4183 CFM
20
;
1) Final Readings.
� � Page 27
� TRAVERSE TEST REPORT Date 11/21l14
SERVlCES, INC. Tech F.R.
AHU-1 Zone -6
PROJECT; C/L -Vail SYSTEM: Traverse-9
LOCATION: After the MVD, Before the outlets. Initial DUCT S.P. : 0.43"
Duct Required Actual
Size 26" x 20" Sq. Ft. 3.61 FPM 845 CFM 3050 FPM 1198.8 CFM 4328
PT. A B C D E F G H I J K L M
1 1482 1382 1464 9610 1482
2 1272 971 1417 9115 1230
3 9457 746 1864 'f196 829
4 1394 710 990 7Q4 741
5
6
7
8
9
10
11
12
13
14
"i 5
'f 6
23976 = 1199 FPM X 3.61 Sq. Ft. = 4328 CFM
20
'f) Initial Readings
` � Page 28
� TRAVERSE TEST REPORT Date 91/24/14
SERVICES, INC. Tech F.R.
AHU-1 Zone - 6
PROJECT: C/L -Vail SYSTEM: Traverse-9
LOCATION: After the MVD, Before the outlets. Final DUCT S.P. : 0.18"
Duct Required Actual
Size 26" x 20" Sq. Ft. 3.61 FPM 845 CFM 3050 FPM 846 CFM 3053
PT. A B C D E F G H I J K L M
1 1120 1254 1347 '1403 1342
2 841 988 986 949 1014
3 722 753 59'i S42 501
4 738 569 414 332 407
5
6
7
8
9
10
11
12
13
14
15
16
16913 = 846 FPM X 3.61 Sq. Ff. = 3053 CFM
20
1} Final Readings.
� � Page 29
� AIR OUTLET TEST REPORT
Date 91/24/94
SERVlCES, INC. Tech F.R.
AHU-1
PR�JECT: C/L- Vail SYSTEM: Constant volume
Area O enin Desi n lnitia! Final
Senred No. T e Size AK VEL CFM VEL CFM VEL NOTE VEL CFM
Zone - 2 1 SWR 48"x 8" 2.38 756 1800 789 1880 787 9875
2 SWR 18"x s" 0.87 805 700 1083 940 812 705
3 DT �o'�x 10" 0.69 725 500 651 450 764 525
Total 3000 3270 3105
Zone - 6 'i SWR 12"x 6" 0.41 366 15Q 678 280 353 145
2 SWR 12"x 6" 0.41 366 150 69'I 285 362 150
3 SWR 12"x 6" 4.41 366 150 517 210 371 150
Total 450 775 445
� r Page 30
� TRAVERSE TEST REPORT Date 11/24/14
SERVICES, INC. Tech F.R.
AHU-1
PROJECT: C/L - Vail SYSTEM: Zone- 2 -3
LOCATION: After the MVD, Before the ou#lets DUCT S.P. ; O.Q5"
Duct Required Actual
Size 'f0" x 10" Sq. Ft. 0.69 FPM 725 CFM 500 FPM 651 CFM 449
PT. A B C D E F G H I J K L M
1 473 521 500 505
2 683 5S4 562 712
3 775 604 6'f 6 689
4 871 822 772 758
5
6
7
8
9
�a
'i 1
12
13
14
15
'I 6
10417 = 651 FPM X Q.69 Sq. Ft. � 449 CFM
16
1) Initial Readings
� � Page 31
i TRAVERSE TEST REPORT oate 11/24/14
SERVICES, INC. Tech F.R.
AHU-1
PROJECT: C/L. -Vail SYSTEM: Zone - 2 -3
LOCATION: After the MVD, Before the outlets DUGT S.P. : 0.08"
Duct Required Actual
Size 10" x 10" Sq. Ft. 0.69 FPM 725 CFM 500 FPM 764 CFM 527
PT. A B C D E F G H I J K L M
1 513 649 648 642
2 802 614 709 695
3 864 70'i 765 971
4 $53 878 968 954
5
6
7
8
9
'i 0
11
12
13
14
15
16
12226 = 764 FPM X 0.69 Sq. Ft. = 527 CFM
16
'f j Final Readings.
� � Page 32
� EQUIPMENT DATA TEST REPORT Date 19/25/14
SERVICES, INC. Tech F.R.
PROJECT: C/L -Vail SYSTEM; RF-1
UNIT DATA MOTOR DATA
Make Loren Coolc Make Baldor
Model # 445 CPA 445 CPA CL1 HP RPM 10 1770
Serial # 183SF30976 00/0000701 PH T e 3 Not Given
T e Utilit SF Volf 1.15 230 /460
Ratin 20500 CFM 'i.75 " S.P. FR Am s 215T 25.0 / 'i 2.5
Re uired 2040Q CFM EFF P.F. 91.7 82.0
STARTER DATA DRIVE DATA
Make ABB Motor Drive 2TB44 P1
Model # ACH550-UH-031A-2 Motor Bore P1 x 1 3/8"
Size Not Given Fan Drive 2B 13.6
Heater Elecfronic Fan Bore SK x 2 7l16"
Ratin 10 H.P. - 240 V. - 30.8 Am s Belt Size BX108
Re d. Htr. No. Beits 2
Ratin Drive Chan e None
TEST DATA TEST DATA
CFM 2039Q IN OUT �P
Volt 210 - 209 - 209 Fan -0.18 " 0.20 " 0.38 "
INlTIAL FINAL 1,2
RPM 457 457
Am s 13.2 13.2
Hertz 46 46
1. �inal Readings taken while in Auto, unable to Isolate Fan due to Low Outside Temp&F'reeze Protection.
2. R�'-1 set to 18000 CFM and Tracking 81%of AHU-1 @ 43 NZ for Min OSA, Fina1 Testing at Required CFM.
� � Page 33
� AIR OUTLET TEST REPORT
Dafe 11/25/14
SERVICES, INC. Tech F.R.
RF-1
PROJECT: C/L -Vail SYSTEM: Return Zones
Area O enin Desi n Initial �inal
Served No. T e Size AK VEL CFM VEL CFM VEL NOTE VEL CFM
2nd Floor R-1 SWR 72��x s2�� 41.99 184 7950 312 13490 1 312 13060
2nd Floor R-2 DT 30��x 22�� 4.58 349 'i600 333 1525 328 1505
1 st Floor R-3 DT as��x s2" 10.67 109 7 10850 572 6105 546 5825
Total 20400 21120 24390
955Q 14565
1. No MVD
_
� ■ Page 34
� VELGRID TEST REPORT
Date 11/25/14
SERVICES, tNC. Tech F.R.
RF-1
PROJECT: C/L -Vail SYSTEM: Branch R-'i
L.00ATION: Telco 113A DUCT S.P. :
Duct Required Actual
Size 72" x 92" Sq. Ft. 41.91 FPM 184 CFM 7950 FPM 312 CFM 13059
PT. A B C D E F G H I J K L M
9 397 3Q1 277 328
2 320 349 315 313
3 268 287 293 284
4 312 328 350 332
5 301 313 317 327
6
7
8
9
10
11
12
13
14
15
16
6232 � 312 FPM X 41.91 Sq. Ft. = 13059 CFM
20
� ■ Page 35
� TRAVERSE TEST REPORT oate 1'f/25/19
8ERVICES, INC. Tech F.R.
RF-1
PROJECT: C/L -Vail SYSTEM: Branch R-2
LOCATiON: Af#er the MVD, Before the outlets DUCT S.P. : -0.02"
Duct Required Actual
Size 30" x 22" Sq. Ft. 4.58 FPM 349 CFM 1600 FPM 286 CFM 1312
PT. A B C D E F G H I J K L M
1 291 273 254 298
2 291 314 289 285
3 251 264 271 266
4 286 3Q1 317 3Q3
5 285 292 295 302
6
7
$
9
10
11
12
13
14
15
16
5728 = 286 FPM X 4.58 Sq. Ft. = 1312 CFM
20
� � . Page 38
� AtR OUTLET TEST REPORT Date 11i25/14
SERVICES, INC. Tech F.R.
RF-1
PROJECT: C/l. -Vail SYSTEM: Zone R-2
Area O enin Desi n Initial Final
Served No. T e Size AK VEL CFM VEL CFM VEL NOTE VEL CF'M
� R-2-'f DT 20"x 12" 'I.67 419 700 177 295 'i 177 295
Total R-2 DT 30"x 22^ 4.58 349 1600 333 1525 328 15Q5
1. MVD 100% Open
� � Page 37
� TRAVERSE TEST REPORT
Date 11/25/14
SERVICES, INC. Tech F.R.
RF-1
PROJECT: C/L-Vaif SYSTEM: Branch R-2-1
LOCATION: After the MVD, Before the outiets DUCT S.P. : -0.004"
Duct Required Ac#ual
Size 20" x 12" Sq. Ft. 9.67 FPM 419 CFM 700 FPM 177 CFM 296
PT. A B C D E F G H I J K L. M
1 158 197 140 136
2 194 221 223 210
3 '196 19$ 160 989
4 120 162 155 'f$6
5
6
7
8
9
10
11
12
13
14
15
16
2837 - 177 FPM X 1.67 Sq. F't. = 296 CFM
16
� � Page 38
� TRAVERSE TEST REPORT
Date 11/25/14
SERVICES� INC. Tech F.R.
RF-'I
PROJECT; C/L -Vail SYSTEM: Branch R-3
LOCATION: After the MVD, Before the autlets DUCT S.P. : -0.03"
Duct Required Actual
Size 48" x 32" Sq. Ft. 10.67 FPM 1017 CFM 10850 FPM 424 CFM 4525
PT. A B C D E F G H I J K L M
1 291 273 254 298 85 892 928 644
2 291 314 289 285 889 750 744 713
3 251 264 271 266 582 fi93 758 650
4 286 301 317 303 436 682 673 524
5 285 292 295 302 216 361 781 606
6 483 140 �137 62 265 314 498 474
7
8
9
10
19
12
13
94
15
16
20354 = 424 FPM X 10.67 Sq. Ft. = 4525 CFM
48
,p�