HomeMy WebLinkAboutB11-0496 REV08 ASI 19 � ARCHITECTURE ARCHITECT'S SUPPLEMENTAL INSTRUCTIONS URBAN DESIGN INTERIOR DESIGN PROJECT NAME: Lion Vail(Strata Vail) ASI#: oig �OWNER �ARCHITECT � CONSULTANT � CONTRACTOR PROJECT#: 17004.15 DATE OF ISSUANCE: 05/21/2015 0 FIELD 0 OWNER: Lionshead Inn, LLC ARCHITECT: OZ Architecture,Inc. Patricio Burillo Rodrigo Cortina TO CONTRACTOR: PCL 705 West Lionshead Circle CONTRACT FOR: Construction Vail,CO 8i657 CONTRACT DATED: May zoi4 The work shall be carried out in accordance with the following supplemental instructions issued in accordance with the Contract Documents without change in Contract Sum or Contract Time. Prior to proceeding in accordance with these instructions, indicate your acceptance of these instructions for minor change to the Work as consistent the Contract documents and return a copy to the Architect. DESCRIPTION: The Following information is forthe issuance of`FOR CONSTRUCTION DOCUMENTS'to be included in the permit set of drawings issued 3�3i/zoz4. Revisions include updated Code Plan to coordinate with PR-os and PR-o4 ARCHITECTURAL: • Revisions include updated Code Plans to coordinate with PR-ol and PR-o4 ATTACHMENTS: Architectural Sheets: Tz.i,Tz.z,Tz.3,Tz.4,Tz.S,Tz.6,and Tz.7 ISSUED BY: �� ACCEPTED BY: ARCHITECT: OZ ACChit�Ctt��e CONTRACTOR: siz��zo�s Page i of i G:�zoo71i7ooG Lionshead Inn�CA1A51�A51_oi9 Building Depar[ment Review�A51_os9 Buildind Department Review docx DENVER PHONE: 303.861.5704 3003 LARIMER STREET FAX: 303.861.9230 DENVER BOULDER COLORADO SPRINGS DENVER,COLORADO 60205 WWW.OZARCH.COM BUILDING AREA MATRIX BUILDING CODE SUMMARY ,�\ IBC 1004.1.2: MAX FLOOR AREA ALLOWANCES PER OCCUPANT: BLDG A & B 41,481 GSF/200 = 208 OCCUPANTS FLOOR LEVEL BLDG A (GROSS SF) BLDG B (GROSS SF) TOTAL (GROSS SF) CODE APPLICATION \ TELE/COMM IBC 1021.2: MINIMUM NUMBER OF EXITS FOR OCCUPANT LOAD: 1 17,010 11,645 28,655 APPLICABLE CODES: MINIMUM OF 2 EXITS REQUIRED 2 15,412 14,737 30,149 2012 INTERNATIONAL BUILDING CODE (IBC), INCL APPENDICES B, C, E, G, J & K R fl C H I 1 E C t U R E 3 EXITS PROVIDED � 1 3 15,412 14,845 30,257 2012 INTERNATIONAL PLUMBING CODE (IPC) , IBC TABLE 1016.2: EXIT ACCESS TRAVEL DISTANCE: STAFF MAX TRAVEL DISTANCE ALONG NATURAL PATH FOR 4 15,412 14,845 30,257 2012 INTERNATIONAL MECHANICAL CODE (IMC) OCCUPANCY S-2 = 400 FEET FOR FULLY SPRINKLERED BUILDING 2012 INTERNATIONAL ENERGY CONVERSATION CODE (IEEC) 3003 Larimer Street MAINTENA 5 15,412 14,790 30,202 2012 INTERNATIONAL FUEL GAS CODE (IFGC) 1 0 6 16,666 13,305 29,971 2012 INTERNATIONAL FIRE CODE (IFC), INCL APPENDICES A, B, C, D, E, G, H & J Denver, Colorado 80205 ��6 2012 INTERNATIONAL PERFORMANCE CODE FOR BUILDINGS & FACILITIES (ICCPC) 7 6,830 6,830 2011 NATIONAL ELECTRICAL CODE (NEC) Phone 303,861.5704 2 SUB-TOTAL 95,324 90,997 186,321 2009 ICC/ANSI A117.1 �\ TOWN OF VAIL AMENDMENTS, ORDINANCE N0. 2 - SERIES OF 2013 GARAGE: � \ P1 41,506 ZONING: LMU-1, LIONSHEAD MIXED-USE ELEV � P2 41,481 PRIMARY OCCUPANCIES: R-2, RESIDENTIAL CONDOMINIUMS 0 MACH RM R-1, HOTEL LOCK-OFF UNITS ELEVATOR TO ACCOMMODATE P3 41,481 SECONDARY OCCUPANCIES: A-2, RESTAURANT & LOUNGE AMBULANCE STRETCHER 59 x 0.3 = 17.7° STAIR PROVIDED AT ONE ELEV B-1 SUB-TOTAL 124,468 A-3, INDOOR POOL MIN. EGRESS B-SOU EV 24x84 (PER IBC 3002.4)- S-1, TENANT STORAGE STAIR NADTH B-� � GEN-2-3500 OTIS ELEVATOR BLDG TOTAL 219,792 90,997 310,789 S-2, PARKING GARA6E M, RETAIL ` PRESSURIZED NON-SEPARATED USES PER IBC 508.3: FIRE SEPARATIONS ARE NOT REQUIRED BETWEEN USES, , � � LEV HOISTWAY ENCLOSURE EXCEPT AS REQUIRED BY OTHER PROVISIONS. , � � - I B-2 CONSTRUCTION TYPE: I-B , o " ' FIRE SPRINKLERS: FULLY SPRINKLERED PER NFPA 13 � .l' G 59 x 0.3 = 17.7" BASIC ALLOWABLE BUILDING AREA: � � S-1 = 48,000 SF/STORY 59x0.2 = 11.8" ° � o STAIR WIDTH S-2 = 79,000 SF/STORY MIN. EGRESS NADTH 59 L U A I = 59 x o.2 = 11.8" TOTAL ALLOWABLE BUILDING AREA: ��� � ��� \O MIN. EGRESS WID1H S-1 = 144,000 SF/STORY (INCLUDES INCREASE PER IBC 506.1) �, STAIR S-2 = 237,000 SF/STORY (INCLUDES INCREASE PER IBC 506.1) �,�' � 59 ������� �� � § � �L������� � � �\ - ALL OTHER OCCUPANCIES = UNLIMITED � �� ALLOWABLE BUILDING HEIGHT: 12 STORIES, 180 FEET (INCLUDES INCREASE PER IBC 504.2) ��� � o � PRESSURIZED � 2�� �� � � STAIR ENCLOSURE / STRUCTURAL FRAME: 2-HOUR, NONCOMBUSTIBLE �.� � � PARK , U � � FIRE-RESISTANCE REQUIREMENTS: � , � ��� � BEARING WALLS, EXTERIOR: 2-HOUR, NONCOMBUSTIBLE h���� �� �� BEARING WALLS, INTERIOR: 2-HOUR, NONCOMBUSTIBLE NONBEARING WALLS, EXTERIOR: PER IBC TABLE 602 ■ NONBEARING WALLS, INTERIOR: NON-RATED, NONCOMBUSTIBLE 03.31.2014 ❑ O �I � ROO�RCONSTRUCTIONN� 1-HOUR, NONCOMBUSTIB E , � EXTERIOR OPENINGS: NOT PERMITTED < 3', UNPROTECTED > 3' � 2�s' MAINTAIN MIN 8-2 H GH etEARANCE _ SHAFT & EXIT ENCLOSURES: 2-HOUR FIRE BARRIER O N ��3 AT ALL DRIVE AISLES A 0 RAMPS FOR EXIT PASSAGEWAYS: 2-HOUR FIRE BARRIER TO A Oq ACCESS TO HANDICAPPED PARKING SPACES MAIN �CT SLEEPING UNIT SEPARATION: 1-HOUR FIRE PART1T10N 3 CORRIDORS, R OCCUPANCIES: 0.5-HOUR FIRE PARTITION � �i� �2 CORRIDORS, OTHER OCCUPANCIES: NON-RATED - �� REFUSE ACCESS/TERMINATION ROOM: 1 HOUR � � � HC SIGN �'��,` /3 ACCESSIBILITY: 1 ALL COMMON FACILITIES, SPACES, ELEMENTS TO BE ACCESSIBLE PER IBC 1103. � O / ,�26 R-1 HOTEL UNITS: ACCESSIBLE UNITS PER IBC TABLE 1107.6.1. TYPE B UNITS ALL OTHERS �j� ELEC � R-2 CONDOMINIUMS: ACCESSIBLE UNITS- 2% � TYPE B UNITS ALL OTHERS � � ` TYPE A & B DWELLING AND SLEEPING UNITS TO COMPLY WITH ICC/ANSI A117.1- 2009 LEV PARKING STALLS: 169 PROVIDED IN PRIVATE PARKING GARAGE. PER IBC TABLE 1106.1, � /� ._ � , , � % � , _2 / 6 ACCESSIBLE STALLS SHALL BE PROVIDED. 1 STALL SHALL BE VAN ACCESSIBLE. � ' o - PRESSURIZE � � � � - HOISTWAY ENCL SURE ELEVATOR TO ACCOMMODATE E MECH - ' AMBULANCE STRETCHER C001 WG T�WFRS ELEV ° - o ° q-� MNXEGRESS177� STAIR o LEV 240$DEDER IBCN3002.4 B-1 � O B-SOUTJ� _ _ � � 4 � STAIR WIDTH B 1 � GEN 2 3500 OTIS ELEVATOR P H AS E D 0 C C U PA N CY I N T E N T U , RAMP � 3 ; � - � ' ' '- " "•-� L BBY / �. PRESSURIZED ^ ' ° �� E V HOISTWAY ENCLOSURE � � TENA - �� � � _2 PHASED OCCUPANCY MAY BE CONSIDERED FOR THIS PROJECT BASED ON CONSTRUCTION � � U _ � I SCHEDULE AND UNIT SALES. SHOULD PHASED OCCUPANCY BE REQUESTED, ALL FIRE 1 MACH R 1 o ( , PROTECTION AND LIFE SAFETY SYSTEMS WILL BE OPERATIONAL, INSPECTED AND � \ / COMMISSIONED PRIOR TO ANY OCCUPANCY OF THE BUILDING. THE REQUEST FOR � '� _ �\ � PHASED OCCUPANCY AND SPECIFIC DETAILS WILL BE PROVIDED BY THE CONTRACTOR AT � � ��J ❑ � � � �- -0�� � � , ❑ , � � A LATER DATE AS THE PROJECT IS DEVELOPED FURTHER. �� � � ° EXIT � � � � � M N X EGRESS���� � 249 FEET < 400 FEET TRAVEL DISTANCE ' S9 x o.2 = 11.8" ° � � STAIR WIDTH ` �� PARKING � _ MIN. EGRESS WIDTH 59 L ! � � � 59x0.2 = 11.8" ' , � � � � -� �� �� ,� / - � - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - J 59 x 0.2 = 11.8" O MIN. EGRESS WIDTH � - - - - - -- - - - - - - - -- - - - - - - - 1 MIN. EGRESS WID1N ST � - STOR STAIR 59 � � � 190 FEET> 100 FEET COMMON PATH OF EGRESS TRAVEL EXIT , B-NORTH \ I SEE T2.8 AND T2.9 FOR NARRATIVE � � °� � �J ❑ � �] �J � MIN X EGRESS 17J" ■ I STAIR WIDTH PRESSURIZED ' J 2 TELE STAIR ENCLOSURE � ��r- J � COMM. PARKING -� � � � � � o 0 0 0 0 N � T A ' � 3 �' o HC SIGN CODE PLAN - LEVEL P-3 � / RAMP 1 ' o , ; SCA�E: �/�s" _ �'-o" PLAN '� � z 0 0 8 16 32 � = ELEV _2 � \ i � LOBBY 1�CH� MEC � � E� H BOIL�S COOL TOWERS �� � � ` �� - ELEV STOR _ _ �� � - V A-� O �� �.� � � , PRESSURIZED - � _ � HOISTWAY ENCLOSURE 1 \ - - J� RAMP A-3 � I MAINTAIN MIN 8'-2' HEIGHT CLE E PROJ. NO. 17004.00 AT ALL DRIVE AISLES AND RAI�I'S FOR � � ACCESS TO HANDICAPPED PARKING SPACES DRAWN: RW � � CJ � � � � � 5s x o.2 = ».s• CHECKED: HK � EXIT A � _ \ MIN. EGRESS WIDTH PARKING CADD FILE. .dwg -�R � 0 _ DATE: 12/20/2013 � 59x0.3 = 17.7" � �E - - - TEL C - � MIN. EGRESS REVISIONS: r --- - - - - - -- - -- - - --- - -- - - - - - - -- - - --- - - - 190 FEET> 100 FEET COMMON PATH OF EGRESS TRA STAIR WIDTH 1 ADDENDUM 1 01/24/2014 iSEE T2.8 AND T2.9 FOR NARRATIVE EXIT o Q2 BLDG DPT COMMENTS 03/31/2014 � L� � � � ❑ ❑ �3 FOR CONSTRUCTION 07�15�2014 � �� 2 � � � � AS�19 BLDG DEPT REVIEW 05/18/2015 J � � � r STOR CQOZ ARCHITECTURE -- - J I � � HC SIGN STRATA VAIL � 100% CD'S � �, SHEET TITLE: �� CODE PLAN �� LEVEL P-3 & LEVEL P-2 � �, ~° CODE PLAN - LEVEL P-2 SHEET LEGEND gv 2 SCALE: 1/16" = 1'-0" PLAN � , � , � „ � „ � „ � , � � � � � � � � � � � 2 HOUR WALL SCALE:AS Noted \i� Z �� �� O � � � � � � � � � � � � � � 1HOURWALL SHEETNUMBER: 0 8 16 32 .� _ ■ i � i � i � i � i � i � i � i � i � i � i � i ■ ,5 HOUR WALL 12 #O T ANTICIPATED OCCUPANT LOAD & DIRECTION OF EXIT ■ / / � � �� \ TABLE 602: EXTERIOR WALL BASED ON / � \ EG SS �_ � �� � �� � -I FIRE SEPARATION DISTANCE: / -�� J'o � I _ \ ' � DISTANCE 10'-30' = 1 HOUR % � �� � \ G� ��LIC _ �-�� ii � ii � ii � ii ii � ii � ii p % w/o ❑ 4 .�+.� " p � ��� i �� � � \ � � � � � i� � o, � �� o� � � �NE �- � � � � / / � II / J� � / ALLOWABLE AREA FOR UNPROTECTED R� �' � �i� � \ 9 ,, I , , , , , , ��,; I �'� ql��� o� ° JI� OPENINGS BASED ON FIRE SEPARATION: QR�P� � ��� c � �` � _ _ TURE BA - - � � � ��� ° � ' ' � 'j �%�� ° �'� � �° RflCHI1ECtURE � TENANT � _ _ II ` �I � 1�11 ( DISTANCE 10-15 = 45% �� o � 0 - - - -FllT��.RE KITCH �I �!I�I��-���I� I / � p,��� �%�' � �� � `S���y 1,225 SF/15 NET= � / ' oY� ���� � \\ �°� 3003 Larimer Street � o. SE�O� DOCK SERVICE � / s2 occ FUTURE RESTA � RANT- �, �� � �^ � � � TENANT 1,530 SF/200 GROSS= � ;�� / �/�� ELECOMM � ��°� Denver, Colorado 80205 � 8 OCC / ' � � ] POOL/SPA 9 OCC � �26 � �!i� FITNESS ` o \� PRESSURIZED \ �� Phone 303,861.5704 � ❑ 1,833 SF/15 NET= POOL DECK 72 OCC - �i 0 � HOISTWAY ENCLOSUR I 41 123 OCC 97;-2n/3= � » g�,2,� 66 I TOTAL = 81 OCC � �,���� \ �� ELECT 13 � � � / � � n �� 32-5 < 32� � , � /� INDOOR POOL ELEVATOR TO ACCOMM DATE � 53-3 /3= 21�'S" 32'-g" i � �/\ � O o AMBULANCE STRETCHER PROVIDED AT ONE ELEV 1 � ��,-9n��,-5n - i 65 - �� / H ��\ RATOR �� 24x84 (PER IBC 3002.4)� �' / ' � ------- _ � ' � �- .L � � - � ao x o.2 = s.o" � � \ 14 �: GEN-2-3500 OT1S ELEVATdR a�� � -� \ ------ , -- -- i MIN. EGRESS WIDTH � � \ � � � � SSIBLE , O ■ � , -, ENTRANCESSI�!�n_ r�� ' ENTR CCE _ � � 55 x 0.2 = 11.0" ASr1 � E � � - !._ ',--- I '--- � NCE,` i � � MIN. EGRESS WIDTH 'R��6� � \ / - , �/ EGRESS EGRESS , � \ W 5 � SERVICE '`��c> .� 41x0.2 = 8.2" c , � .�0 � MIN. EGRESS NADTH \ � 41 BAY �0 � - TO PUBLIC WAY TO PUBLIC WAY � -� � \ � _ -� �•' 0 �. � \ ,, . � PRESSURIZED � � � IE °� � f � STAIR ENCLOSU E �\ � � � ` - STAI R TABLE 602: EXTERIOR WALL BASED \��_ . � \ \ � " � �°�M 5 OCC � g-NORTH s2 x o.3 = 24.6" ON FIRE SEPARATION DISTANCE: � 66x0.2 = 13.2 � � MIN. EGRESS WIDTH \ � '� ^� \ � ` � � � � � P E OUSING \ MIN. EGRESS DISTANCE > 30' = 0 HR � _� C � I � � � � � � � , � STAIR WID1N � \ � � � � U \� � � � \ �� \I � I � � � r� � \ ALTERNATE CODE PLAN - � � � � � � � 5 � � °.2 - ,6.4� � MIN. EGRESS WIDTH � � � � �1 \ � OBB �o _ � � � I � I � 5 OCC 5 I �r��`� FUTU RE RESTAU RANTS LEVEL 1 � � � _ N nl \ , � � �� ��� � , i.. _I �L1.,"�1 � � o�� � � � � �� � � � � �� � EGRES �. �. SCALE: 1�16" = 1'-0" PLAN I I � � „ �\� 5 ° 60 � � ��� TO P BLIC WAY � � � ������� � � Z � � 1 �(� \ 71� `. � „ 27x0.2 = 5.4 82 � \ � � �+� � " o � '-o ��;; �� ■ 21 � � 0 171 - T2.7 � � �L����� � � � I � � � V�,�� 7 s3 X o.z = �o.s MiN. EcRESS w��n-i o , � . �t����� � 0 8 6 32 � � � � �� \ ; MIN. EGRESS WIDTH 171 x 0 3 - 51.3 � � z � V� � � �.,,��� � �� � � � T � I MIN. E ESS � ��� �� � � �NOT PHRT OF rROJECi` -o� �'^� '��.� �� 121 x o.2 = 24.2" ADA ACCESSIBLE � � \ sTAIR DTH � � �� 1 �_ �o � ENTRANCE ' �� � � � � I , � p �� , MIN. EGRESS NADTH 27 54 x 0.2 = .$� i� �, � V � � � �� '�, � MIN. EGRESS�WID � � �� � ����� � � - � � � � �_ � � `�, � n�A nccESSie� 27 54 � � ��' , � ��� y � ���, ENTRANCE \ � � 03.31.2014 I I � � � `� � ',. ` ` ° °o I - � � �� \ \ � \ ^ \ � 54x0.2 = 5.4" � I �C � � � � � MIN. E6RESS WIDTH I \ ,�,• � � \ C V I � � � � � s��o.2 = �s.2• GREAT ROOM I ENTERTA MENT ��� \ 32 FT X 50 FT �,♦ � \ C'�\I� I ,� �\N� �I � � IN. EGRESS WID1H � - I � PRIMARY � � FIRE TRUCK ��\� II � \ PR�P�R �+ ���/ 81 x 0.3 = 24.3" 0 713 SF/15= � � 466 S /15= \ \ � STAGING AREA i'� � � � � � 1 '� � � � � °s ' � MIN. EGRESS ' � � 48 OCC I 32 0 C � \ \ � ��R BLDG B &A � � �� \ Y�,,��''' � � � � �I , I � � S�.�p,�K� \ STAIR WIDTH EGRESS '----- I � - - \ \ \ \ i `� ` I `�I I �I � � � � TO PUBLIC WAY � ■ � � \ \ \ �,. ' � � ��\, \ ��o,0 \ \ /j I � \ � � � ��� � � � 170x0.3 = 51.0" . �11 � � � � � � QUANTITY OF POOL CHEMICALS � ���� � , ELECT �\ � �� � � � �� \ \ � MIN. EGRESS a n� I "� \ V � ARE TO BE MAINTAINED �� �� ELECT � � I I 1 � � � \ � EGRESS TO PUBLIC RAMP �nDTH � � , O LESS THAN EXCEMPT AMOUNTS �� 3 \ � `� V � \ WAY VIA RAMP= , 170 .LOUNGE \ � IN THE FIRE CODE. 1 ,i'� � � � \ � g% SLOPE \ ___! �, O FIRE \ \ � � Q 6 . �2• �,� . � � \ � _� RAMP/ TRASH � COMMAND \ � � ,, - __ POOL ,�� 0 � \ (i��T PArcT OF Pn�JECT) \ .P� � .----""" PARKING ENTRANCE CHUTE � �� � ° Q STOR i '� \ ) �/� �1, - "" ADA ACCESSIBLE 212 SF/15 � � �� �� POOL ��� � � � / ' �� \ �� � � 38 x o.3 = 11.4" � ENTRANCE � 15 OCC � AS�19 � �� � � STOR � � �� -� : � � � �� 3o\ory i / � � MIN. EGR - --ol o--1 --- � - -� E v = � -- � �� -. � o c <, � : - _. -- . _ � � �\ � � o � � ; ° _ � � 5 I °� \ J �' - _ - - = � � ,1 ? � � � �� o� � � � STAIR � � / � � �� - �� ELEVATOR TO ACCO�IMODATE � 38 x 0. = 7.6" � � � - �- � AMBULANCE STRETCH�R � O �� ELEVATOR TO AC�OMMODATE �, A-SOUTH . cR �nDT�-� � - 2 AM ULANCE STRET�HER � a / / BUSINESS �, EL V PROVIDED AT ONE ELEV B-1 � PRO�IDED AT ONE E�EV B-1 HOSE LENGTH / c,, � ��� ��� � qS 19 ■ CENTER h - _ 6' � 8 OCC �� 24x84 (PER IBC 3002.4�- � � 59 x 0.3 = 17J° STAIR ,o i' LEV 24X8� (PER IBC 3002,4)- 61 FT / 3 � h° �� ��jRIZED AIR C SU LEV � I' � 4 OCC � � GEN-2-3500 OTIS ELEV�TOR ^ - MIN. EGRESS 6_SO B-1 � GEN-2\3500 OTIS ELEVt�TOR / � ��0° �/ BASED ON M F E DEP RTM T q_3 � 411 SF/100= �' j �� ( � EGRESS � ME�H � STAIR WIDTH PRESSU IZED � \ � /�� / STAIR A-SO GOES TO ROOF ❑ �� ( � � PRESSURIZ�D \ / �� � � / � TO PUBLIC � � � 5 OCC �� HOISTW �� � � � � � WAY - = /� � ENCLO � � LEV HOISTWAY E CLOSURE \ / � / � � � � � � � � � � � � � � � � ❑ wi� ❑ � � o � , ❑ , \ � , � i� � � � � � B-2 �� � ��� � j /�� I A� � o � A o o� � o � ' I � i � � � � � � -- i I �� ' I I / J� s / I 4 OCC � � o ! � � � � �� ���� ,��. � - �� � 1� �1�1`o � � � 202 SF�15= � � - \ , / � / � � / / i � � � � � � � qlll, � � � 140CC � � � �� � � � � � � � �� I � �� � , � � � � �� � / � FU' RE RESTAU�ANT = _ II � �I�� ��II� � , � � � � i I- - - - - J ACCESSIBLE � / � � � � � � � �.� � � ��� � �� � o �� ONE TENANT � � � � ����� LOBBY � � � A�NORTH - • ROUTE TO � � = 9 x 0.3 = 17.7 I � � � � �' / � SEPARATE PERMIT WILL �E APPLIED FOR WHEN THESE OFFICES � � MNXEGRESS17� ; 59 ° MIN. EGRESS � C�\ �� � � � X 142.0 �� � 3,o5s sF/�5 NEr= FUTURE KITCHEN � XIT ACCESS TRAVEL DISTANCE 118 FT � - ' - 59 x 0.2 = 11.8' L STAIR WIDiH � �� \ � / � �/ 204 OCC AREAS ARE TO BE FINIS�1ED TO ACCOMMODATE , , STAIR WIDTH � MIN. EGRESS WIDTH � \ � � � � /� ACCESSIBE ACCESS AT F�UTURE RESTAURANT � _ � �i - _ I � , �� � �� � � � � � � � � _ � 1,530 SF�200 GROSS= � ' �C � � f i ' I � _ . � � / " � �J � ' 59x0.2 = 11.8" � STAI R � �� ��_ � \ � �32 FT X 50 FT / � � L - STA UTURE ��� � �5 OCC � MIN. EGRESS WIDTH � B-NORTH i 59 \ �\ �� � SECO DAY / � � TENANT �38� h I � � ��° , � � FIR TRUCK 3 , � � � � � � \ / � ST GING ARE � / � 106 ❑ ❑ C ❑ 106 � �� � ' - � \� � � � FIRE AC SS � � / 3 62'-4 1/2" > 138'-3"\3(46'-1") 55 '� � , I � EGRESS � ANTITY OF POOL CHEMICALS PRESSURIZED � T BLDG A NLY � / AT2.7 _ ' �KI � R� , 59 �� TO PUBUC WAY � ARE TO BE MAINTAINED STAIR ENCLOSURE / ; � LESS THAN EXCEMPT AMOUNTS PARKING � � � � �_:_�1� i: i �; - u � �� - \ � IN THE FIRE CODE. 0 � � � ADA ACCESSI. � ADA 4CCESSI ADA a'CCESSIBLE 35 � � � 59 x o.2 = 11.8" � � � ,�-- -, �� � ,, ----, �� , ---; NCE. -- ENTRANCE- --- ;- � � / ENTRANCE ENTR � MIN. EGRESS WIDTH � ' � � �------�� � ' ---�' i I�'�,_ � �, - ----��'' A �� � ------' ------------------- � 0 , '��� � � L� EGRESS � n A o SETBACK � C � � 0 � �L 7-Q 55x0.3 = 16.5 0 � ASr,9 � � - a_QS_x o.2 = 2�.2' EGRESS EGRESS TO PUB IC WAY � , , 2 SPA � TO PUBLIC WAY TO PUBLIC WAY MIN. EGRESS ^ MIN. EGRESS-WID STAIR WIDTH PROPERTY LINE _ _ _ � STQR � --- ss X o.2 = ».o' _ PUBLIC SIDEWALK MIN. EGRESS WIDTH o 0 106 x 0.2 = 21.2" i i TABLE 602: EXTERIOR WALL BASED ON � -. � MIN. EGRESS WIDTH M N FIRE SEPARATION DISTANCE: , ' � � � DISTANCE > 30' = 0 HR HC SIGN �� r� �� ` + + � i ii ii ' ' ' ' � WEST LIOSNHEAD CIRCLE i R� ���� ���� - - - � � � ', ', ', ', TRASH 0 AT2.� a LJ LJ ELEV CODE PLAN - LEVEL 1 - � � � �A_2 � � SCALE: 1/16" _ �'-o" PLAN � ' PRESSURIZED HOISTWAY ENCLOSURE p TELECO � ■ �. � �� ' ��� ELEV o a �s 32 z RAMP _ � � A-1 \ � , '� � �; � O LO BY ELEV �° PROJ. N0. ��004.00 A-3 �� DRAWN: RW �/ _ 1 � � '���EC EXIT - � - ��'� , ,- CHECKED: HK o ID � I o �� o � � : IR 59 _ 5s X o.z = ,,.s� PLUMBING FIXTURE REQUIREMENTS CADD FILE: .dwg � , _ _ _ _ _ � � - � o A NORTH -� MiN. EcRESS w��n� DATE: 12 20 2013 12 I � �� 223 FEET> 100 FEET COMMON PATH OF EGRESS TRAVEL � OCC OCC MALE FEMALE gATHTUBS� DRINKING SERVICE UNISEX KITCHEN WASHER � � O EXIT SPACE GROUP LOAD WC LAV WC LAV SHOWERS FOUNTAINS SINKS TOILETS SINK CONNECTION � SEE T2.8 AND T2.9 FOR NARRATIVE REVISIONS. STORAGE I �, LOBBY AREA: Q1 ADDENDUM 1 01/24/2014 . � 59 x o.3 = t�.�° LOBBY SEATING A-2 14 0.1 0.1 0.1 0.1 0 0.1 (1) 0 0 0 � PARKING MAINTAIN MIN 8-2 HEIGHT CLEARANCE MIN. EGRESS � � ASr1 I ', I � � AT ALL DRIVE AISLES AND RAMPS FOR STAIR WID1H GREAT ROOM A-2 48 0.4 0.2 0.4 0.2 0 0.1 (1) 0 0 0 QBLDG DPT COMMENTS 03 31 2014 L� ACCESS TO HANDICAPPED PARKING SPACES ENTERTAINMENT A-3 32 0.2 O.1 0.3 O.1 O O.1 �1� O O O 3 FOR CONSTRUCT10N 07/15/2014 ' � ° � �°° LOUNGE A-2 15 0.1 0.1 0.1 0.1 0 0.1 (1) 0 0 0 ASr19 BLDG DEPT REVIEW 05/18/2015 � �� � 0 �I LOBBY TOTAL 1 1 1 1 0 1 1 0 0 0 I WATER COOZ ARCHITECTURE I � � FIRE PU�P INDOOR POOL/FITNESS A-3 95 1 1 1 1 0 1 (1) 0 0 0 ,_ _ _ _ _ _ __ _ � � � � FUTURE RESTAURANT A-2 212 2 1 2 1 0 0 (1) 0 0 0 STORAGE � STAFF* B 16 0 0 0 0 0 (1) (1) 1 0 0 � ' � NVA , �� 2 HOTEL LOCK-OFF UNITS (EA) R-1 N.A. 0 0 0 0 1 0 (1) 1 0 o STRATA VAIL � � � � -- � RESIDENTIAL UNITS (EA) R-2 N.A. 0 0 0 0 1 0 (1) 1 1 1:20 UNITS o � 100% CDS � HC SIGN * PER VAIL AMENDMENT, SPACES WITH UP TO 30 OCCUPANTS DO NOT REQUIRE SEPARATE FACILITIES. SHEET TITLE: �� CODE PLAN �� �� LEVEL P-1 & LEVEL 1 �o ,� SHEET LEGEND gv, ��� 2 HOUR WALL � ' ' � " � � ' � " � ' � ' � " � " � ' � SCALE:As Noted � CODEPLAN - LEVELP- 1 _ � _ � _ � _ � _ � _ � � 1HOURWALL SHEETNUMBER: �� 1 SCALE: 1/16" = 1'-0" PLAN .5 HOUR WALL ■ i � ; � � � � � � i � � � . � i � i � � � i ■ Z �2 O 0 8 16 32 = #O T ANTICIPATED OCCUPANT LOAD & DIRECTION OF EXIT ■ IBC TABLE 602: EXTERIOR WALL BASED ON FIRE SEPARATION DISTANCE: � � DISTANCE 10'-30' = 1 HOUR ,. � ASr19 j>�'�� REV'�^�EC1' UNIT MATRI� QA7E : 45�r'21���15 ALLOWABLE AREA FOR UNPROTECTED OPENINGS BASED ON FIRE SEPARATION R-2 TYPE A ,,,- ��� �,, DISTANCE: 10'-15' = 45� 1 BR uNIT >:- `' �`;� UM1�1T IU114�Tf�l�( = � LJNlTTYPE� �TLPDIC! 1BF� 2Bk� 2�R{�O} 3BR 3BR[L�} 4BR 4BR{LC�� 4�F�(L�) T�]71�L IJNITS k� RflCHI1ECtURE ��� � ��-z} 4�-�� ��-�� (�°�}!��-�� ��-�� ��-�}���-�� ����-�� ��-��,���-y ��-��r��-�� P�� ��va�� , �, � � , � � � OPEN T BELOW ������ � � 3003 Larimer Street 1 // o �26 �� � ELEVATOR TO ACCOMMODATE ����� � 1 � � � � Denver, Colorado 80205 � � o � ELECT � AMBULANCE STRETCHER � PROVIDED AT ONE ELEV A-2 Phone 303,861.5704 , -��J � ' � a � \��� _ ;� 24x84 (PER IBC 3002.4)- �E��� � � `� � � � '� � �� T ASH ;� GEN 2 3500 O11S ELEVATOR � ✓� � ' � �� �� �� LEVEL 4 1 �# 1 � 2 2 1 12 % � � � � j� � �� �� PRESSURIZED � \ �� O ,. � � , \� HOISTWAY ENCLOSURE LEV'�� � 1 4 1 3 2 � �13 \ � ■ ' O �`<<<<�```� � GENER OR \\ �,\ � ��v�� � � � � � � 1a UNIT B201 - 72'-0" COMMON \ � OCC�� � \ � R-1 ACCESSIBLE PATH OF EGRESS TRAVEL. �'� '�^- � � � STUD�o uN�T SB SIMILAR AT UNITS 6303, B403 �� � � �� ,�, `'� ,� � �� �X,=�� LEWE� 1 y 1 1 3 AND 6503 V A, � " � � % .,•''� o � �0 V ��•° � 8 OCC �.�•' 0 � ■ � \ � / � ,� �� 22 O � � OCC ,\ 'f�'DTA� R-� U�ITS 3 9 � � *U \ � � o � - o � STAIR \ � M�c � \� � � � � B-NORTH T�[3TAL {Fi-�) iJNI�� s � z� � �v � � � 2 s� IBC TABLE 602: EXTERIOR WALL BASED - o ��•''\ � , � ��� * ON FIRE SEPARATION DISTANCE: • ' DISTANCE 10'-30' = 1 HOUR �° OCC / • � \ ����� ����� � � �� � �� � � � � �� � � � � g EZ � STA RS ENCLOSURE � ALLOWABLE AREA FOR UNPROTECTED � � ° Q 23 x 0.3 = 6.9" OPENINGS BASED ON FIRE SEPARATION DISTANCE: 10�-15' = 45% � � , ' \ w� . 23 L�� STAIR WIDTH • � = • � EMPLOYEE HOUSING UNIT 2 BR - R-2 IS NOT INCLUDED IN THIS COUNT. UNIT 6102 - 79'-0" COMMON � � � � �, 23 x 0.2 = 4.6" ��� ����� PATH OF EGRESS TRAVEL � , � � � � MIN. EGRESS WIDTH * R-1 & R-2 UNIT TYPES DO NOT MATCH THE OVERALL UNIT COUNTS AS SOME UNIT � TYPES CONTAIN BOTH R-1 & R-2 UNITS (20 LOCK-OFF UNITS) �� ������� \ � � � �' 22 X o.3 = s.s• � � � ��������� � ,, �'\ � srniR wi�n� __ a IBC TABLE 602: EXTERIOR WALL BASED ON FIRE SEPARATION DISTANCE: DISTANCE 10'-30' = 1 HOUR ELECT w `� � � TRASH � ALLOWABLE AREA FOR UNPROTECTED CHUTE •/ ° ' OPENINGS BASED ON FIRE SEPARATION ��� DISTANCE: 10'-15' = 45� �' "� � � �, � ;i ' r� ■ C 1C ���; , � `, 1 � , . � ��� � ����,�,� � �26 ;�> ''� � � � ,� `;ti� ` � � 3003 Larimer Street 4 / � 1 ` ; � �� 8 OCC Denver, Colorado 80205 , � • � • � Phone 303,861.5704 ,,, � � ELEVATOR TO ACCOMMODATE . . � ' � AMBULANCE STRETCHER PROVIDED AT ONE ELEV A-2 • '� . � o �� 24x84 (PER IBC 3002.4)- ASr19 �\ � � � ,- GEN-2-3500 OTIS ELEVATOR � � ,5 \ � �, ..� � � _ . : �.y . , ;; �,t, ,, ,., �� � `, ` 3 OCC �` �� ' PRESSURIZED \` • HOISTWAY ENCLOSURE . •. � �e---� � � IBC TABLE 602: EXTERIOR WALL BASED ° `, �,� �•''� � ON FIRE SEPARATION DISTANCE: �� � ,8 �� � '�• � � � � 0 DISTANCE 10'-30' = 1 HOUR � � � .,'' �� , � o STAIR �� � � � , �, s occ g-NORTH _ � ALLOWABLE AREA FOR UNPROTECTED ��o � ''�� �.\ ,� � ' � OPENINGS BASED ON FIRE SEPARATION �.,`,,�-- � � � . � IPRESSURIZED DISTANCE: 10'-15' = 45% '' • 9 OCC � � � ELEV � B_2 � � � � STAIR ENCLOSURE ° � � � � o � ME� \ � � � ,�° o ' ''�� 28x0.3 = 8.4" MIN. EGRESS � STAIR WIDTH � � STAI ''�� ` - �TH 2s x o.2 = 5.s° �Y�� � EGRESS WIDTH ���� ���� � . � �� 27 x 0.3 = 8.1" � � ` - -------------�.i','', � ������� � MIN. EGRESS WI § � ������� � I 2�� �� � a 2 T2.7 � 22x0.2 = 5.4" 1 MIN. EGRESS WID i � STAIR WIDTH r ,j ��� � ���� g� � �� II � � � � II � � � II IBC TABLE 602: EXTERIOR WALL BASED � � 03.31.2014 � ON FIRE SEPARATION DISTANCE: � �� - � ASr19 DISTANCE 10'-30' = 1 HOUR , � ,. � � i � \ � i � r IBC TABLE 602: EXTERIOR WALL BASED ALLOWABLE AREA FOR UNPROTECTED TRASH � i �� . ,o \ CHUT � 0 ON FIRE SEPARATION DISTANCE: 3 ELEVATOR TO ACCOMMODATE OPENINGS BASED ON FIRE SEPARAl10N � DISTANCE 10'-30' = 1 HOUR � � � � � � � i � _ _ - , AMBULANCE STRETCHER DISTANCE: 10-15 = 45% o� � �� � '� __- _ r_ ' PROVIDED AT ONE ELEV A-2 �r � �� 24x84 (PER IBC 3002.4)- � � � � ALLOWABLE AREA FOR UNPROTECTED � II ��� GEN-2-3500 OTIS ELEVATOR � OPENINGS BASED ON FIRE SEPARATION - TRASH I I 1 � � � � �� ' �, �,��•� � UNIT 6505 - 66'-0" COMMON � . / ASr19 DISTANCE 25'-30' = 75% CHUTE PRESSURIZED O - - HOISTWAY ENCLOSURE � � � PATH OF EGRESS TRAVEL. � � � � SIMILAR AT UNITS B305 AND � ♦ .. 30, / - __ ; _ _ . . _, _ _ ` _ _ � �\ � 0 , , , � � ` 4 I , 6405 � � � ----- � � � `� � � � >��� �,< > � � � . � . ,. �� � �.\ ,- � . °� � � \' ;`� a ELEVATOR TO ACCOMMODATE � �_ . - � o , � ` � �� AMBULANCE STRETCHER � I ' _ " � PROVIDED AT ONE ELEV A-2 O � ��� � � � 3 >�>�SS >���; �� _ � A � � • � , � • o � 24x84 (PER IBC 3002.4)- � r _ T2.3 � I <" �� GEN-2-3500 OTIS ELEVATOR , � � ■ ��� � � , � � � � � � . 3��pb �� _1__ _ � - � � �- i � ■ �� � �° k� � � � - ELEV � � �`���• � ' i �iJ�-!��.,�� ME� �_� I ;� ❑ :� b ._ � ��, ,�, �'��� 3 OCC �' � � ' PRESSURIZED � 1 - :�] � ' � A-� � ���. ��'`, ` '�� , ,�:'� %r HOISTWAY ENCLOSURE � , � � � � � � U �� _____ �� ' _- � � � IBC TABLE 602: EXTERIOR WALL BASED � ,. ' ������ ,��' � � � � � / � o= i i� � �� � � II , �� , � � .o�.�-�� ■ .. / [ � E ECT � � � ON FIRE SEPARATION DISTANCE: � � 8 OG��`� ,� �, � � � � � � ���^�� � °° � DISTANCE 10'-30' = 1 HOUR `O � 7 �� � � / _ �-1� � ao 8 occ � �� � .�-� o � STAIR - �� \ , 8 occ � - ME� W o . � i� - . � 0 .�� � o - : �B-NORTH � W/� MEC � I I I I � I l o \' � i�i � � i�i� �\ 3 �� � 11� --� � ■ i 1 ■ f�-J� -- �� ■ ■�_ ■ i i�� � � Ec� � � ♦ AT2.7 STAI� � � - - - - 39 STAIR ALLOWABLE AREA FOR UNPROTECTED '\ � �\ � > I -�-� -. --�--.- -_--_ - • ,. _ " : -,_ - : __- . ,` , ;, , _x _ ._ - __- --- -- _ OPENINGS BASED ON FIRE SEPARATION � 9 0 - � 0 � PRESSURIZED " A-SOUTH = , �,_� , X � � � � ELEV � I �- �II, I __ _ ;' i,. -.�, „ � . ME�, _ - - ' � B-Z ,� � STAIR ENCLOSURE '"' A NORTH __ I ' � � IQ� l � � _-., , '� ;� Y�� � - _ � , , ME�H ai � [�: . � DISTANCE: 10-15 45% • � , � I���.� � � ,����� � ���1� C��9 � � a PRESSURIZED �� ■ _r. - - -� - - %I � ' -- - • AS�19 � � � ..- , -.. ' „ � 39x0.2 = 7.8 ,� � o STAIR ENCLOSUR _ � L� I II �j ' x � X � II � MIN. EGRESS WIDTH `�� o � �- � ��� � � '� �` '` � y ° � 28 x 0.3 = 8.4" � �� � �"��� - � x 39 x 0.3 = 11.7 � �� '-� - 38 x 0.2 = 7.6 � C� � �x x. • � MIN. EGRESS MIN. EGRESS WID1H f'il .� ' j '` „ � �; ° MIN. EGRESS STAIR WIDTH I � STAIR NADTH � 38 x 0.3 = 11.4" � I� � ��� -�� ��� --- � • � - MIN. EGRESS � ;� � ��� �1■ - ` , ST � ' 28 x 0.2 - 5.6" STAIR WIDTH o ° � MIN. EGRESS WIDTH B� OUTH ; - � _ �!_ - �:; '�, o i 0 27 x 0.3 = 8.1" ■ � ■ : _ � , MIN. EGRESS WIDTH ;��i i ; 0 � � ;fi,, �!1 �. � • �� _ �_ \ 5, a Z � " T2J � _ � � � � , � � � � �� , .yr rtie •w 22 x 0.2 = 5.4" - . ��: -� �_�� � /� MIN. EGRESS WI � --- � AS' I `19 STAIR WIDiH i II �I� C7 �7 �� � �'S � II AT2.7 � I.I ASr19 \ � IBC TABLE 602: EXTERIOR WALL BASED � gd'� �� ON FIRE SEPARATION DISTANCE: ELEVATOR TO ACCOMMODATE C O D E P LA N - L E V E L 4 � DISTANCE 10'-30' = 1 HOUR �_ i � _ AMBULANCE STRETCHER � 1 SCALE: 1/16" = 1'-0" PLAN \ � I �J ` x � 4 ____ " PROVID�D AT ONE ELEV)A-2 , 24x84 PER IBC 3002.4 � ALLOWABLE AREA FOR UNPROTECTED I I - GEN-2-3500 OTIS ELEVATOR z � OPENINGS BASED ON FIRE SEPARATION - TRASH I I 0 8 16 32 � . � DISTANCE 25'-30' = 75� CHUTE �II _ � PRESSURIZED � � ,,,'„ h HOISTWAY ENCLOSURE � ��y : . � � � �_.� >. � � � � ����� � � � � -A--- � � � � � � � _;���- - �,. . o _. x - - - - � � o_ � � � � I � � / �e _ ■ � o I � � J ��i � i �k _� I ol ��� T2.3 >: �. s X � 3�\�y � ' � �� Mt� � ;� ° � ELEV '� I � � '� � / X _ � A-1 � � .� hx � � _ --,. x , o �� / ` � E� � '� , II � � PROJ. N0. ��004.00 � i ! �1 � Y COM oo � �} � [ � - i i I' ! , � oo s oc DRAWN: RW I �i��. - ... ._ _� MEC W�D � � �1 � _ � � W�� MEC � 3 . � ���_� . � ,�-� . � . �_�J . . _ .� - . . . . CHECKED: HK / STAIR - _,_ _,_ , - - - _ _ 39 - AT2.� ' I _,_, +_. , , , � �_�_�T_ _, STAIR CADD FILE: .dwg A-SOUTH E W o � � ,-�_ W o �� � � -- - _ A-NORTH � EC � 4� � �`, � � ... / � ..; ' , . �. � � � - ' � �� �� ' 1 �2 �2013 �� : __ �� - . � DATE 2 0 PRESSURIZED �' � � �- OCC ; �o ,: � � �� � r � ���<<! � J� > � r ; . � 39 x 0.2 = 7.8" sTAiR E►vc�os E ! � ,;' I II �, � �� �� � ���;��� � II � M�N. EcRESS �n�n� REVISIONS: , - , 38 0.2 = 7.6" � � i �� �� � �' �� �� �� � 3 N X EGR SS 11 J" _ 1 ADDENDUM 1 01/24/2014 MIN. GRESS WIDTH _i I� � j� i � �;�77 11 ' _ _- '_ � � I� � � M • E �2 BLDG DPT COMMENTS 03�31�2014 _ '�' � � � _ �� a� ' k � -x � �� STAIR WIDTH 38x .3 = 11.4" II �; MIN. E ESS � !�� �� ` � � ;� , ��� �� �;x � �3 FOR CONSTRUCTION 07�15�2014 STAIR TH I � �; �_�i � AS�19 BLDG DEPT REVIEW 05�18�2015 � �_� ��� � -� � � � �� � � � � �� � � w � CQOZ ARCHITECTURE „�=, I ��� � �� �: o . � � . � � � � � � � � � � � � � � � � ��� c R �� � � � � � � � � STRATA VAIL � 100% CD'S � � � SHEET TITLE: �� AT2.7 CODE PLAN �� LEVEL 4 & LEVEL 5 � �, �� ga CODE PLAN - LEVEL 5 SHEET LEGEND ��� � � � � � � � � � � � � � � � � � � � � � � � � � � 2HOURWALL SCALE:As Noted �� SCALE: 1/16° = 1'-0" PLAN LOCKOFF UNIT z � � � � � � � � � � � � � 1HOURWALL SHEETNUMBER: 0 0 8 16 32 � ■ � � � � � � � � � � � � � � � � � � � � � � � ■ ,5 HOUR WALL _ 12 LODGE DWELLING UNIT # T ANTICIPATED OCCUPANT LOAD & DIRECTION OF EXIT ■ ELECT STAI R TABLE 602: EXTERIOR WALL BASED ON TRASH WEST � FIRE SEPARATION DISTANCE: 1 HR CHUTE r T r EXTERIOR WALL FOR DISTANCE >10' TO 30' � b I b \\ ALLOWABLE AREA FOR UNPROTECTED , OPENINGS BASED ON FIRE SEPARAl10N — ,� � � � � 3003 Larimer Street DISTANCE >10' TO 15' = 45% 6 �2' � � � Denver, Colorado 80205 � � � — �� � �'' Phone 303,861.5704 � ��� , 7 OCC � � �— �� ; W�� `� ELEVATOR TO ACCOMMODATE � � � � AMBULANCE STRETCHER � � �� � � \ � � PROVIDED AT ONE ELEV A-2 � � � " � 24x84 (PER IBC 3002.4)— � r� � � GEN-2-3500 OT1S ELEVATOR ,i' � � , � �/ � '�\ �� PRESSURIZED �, ��y � , % HOISTWAY ENCLOSURE o ., a ,� 13 � � � ° \ � ° �� � � � � -� o TABLE 602: EXTERIOR WALL BASED ON �F� '�� 27 � ;� �\ , � � STAIR FIRE SEPARATION DISTANCE: 1 HR o C:� � �, ' 'f'� � " 7 OCC B—NORTH EXTERIOR WALL FOR DISTANCE >10' TO 30' � �� ` �� �� ; � " � � , � � � � �° � ELEV � �� � PRESSURIZED � B_2 � �� � � � STAIR ENCLOSURE / 0 io � �� � � � wE � � ` � � � 2� 27 x 0.3 =8.1" � MIN. EGRESS � �- ����-��`�� � STAIR WIDTH � ��`������"��� - ,•^'� � ��� ���� ���� =% ,•,•� � � � �' �� � 13 �� 27x0.2 = 5.4" � �� ��� � � �� ���� � ; t'�, � � MIN. EGRESS WID1H � ��������� � � B SSOUTH � \ ������ � � � 2�� �� � \\ MECH MECH 2 T2.7 �,� � �� 0 ��� �� � - 14x03 =4.2" � MIN. EGRESS WIDTH � /\ � � TABLE 602: EXTERIOR WALL BASED ON 14 x 0.2 = 2.8" � 03.31.2014 FIRE SEPARATION DISTANCE: MIN. EGRESS WIDTH STAIR WIDTH _ � �o o DISTANCE 10'-30' = 1 HOUR � � STAIR � � i�— �; ALLOWABLE AREA FOR UNPROTECTED WEST ✓ \ , TABLE 602: EXTERIOR WALL BASED ON �; :� OPENINGS BASED ON FIRE SEPARATION — . ,0" \ � DISTANCE: DISTANCE 10 15 45% � � �0 FIRE SEPARATION DISTANCE: 3002.4 ELEVATOR TO ACCOMMODATE �, � DISTANCE 10'-30' = 1 HOUR � � AMBULANCE STRETCHER \ � �� PROVIDED AT ONE ELEV A-2 � � �� O � 24X84 (PER IBC 2009)— .��6 � 2 \ Q \ GEN-2-3500 OTIS ELEVATOR O � T2.7 > � TRASH � o � � Q / � / CH U TE ° PRESSURIZED � / /� HOISTWAY ENCLOSURE � � ' 3p, - - ' i � !� � _ � � �� �0 � � RASH AMBUL NCE�TRET�HERDATE �O4 .� I_�� I � � � ���-'��-' � O � __ � �� CHUTE PROVIDED AT ONE ELEV A-2 � � � � � � ■ ti ,, 24x84 (PER IBC 3002.4)- � °s � 1, '� � ��' � � % � , � � �/ GEN-2-3500 OTIS ELEVATOR � � / �� � 3 � �_� � � AS�19 � 14 �'' � � -_— - � _ __ — � — —J o �� PRESSURIZED U - �� ° U � � � � � ' HOISTWAY ENCLOSURE . 3 �p� / _ ❑ __ �- - - - - � c �, � �► o / - I ■ � : � ELEV� � � ' occ \ � � \ =� � ; A_� � � � � � � STORAGE ', O — o , , � ' � � ELE � �� �� Q � � � � � � — — , � _ � ; � ME� ❑ o ' �� II o - ° B-� � �� � � � - _ I = W�� EL CT ! ! -� ■ �o� - � � � I° � � 9 OCC � i 6 OCC �_ � / � - �� � - - � wECH � � � i - �� • � I � _,_ � °� � � � �_� �� � � �_ � �- LE �� �� 3 � ������� U I AT2.7 � � AS 19 � _ _ _ _ � 22 � � B_ � 13 STAIR ENCLOSURE � 22 STAIR � � I I � / STAI R ' � A-SOUTH �„ ` I�! �s oc _�E� ME�H ME�H i _ _ � � A-NORTH �, �' ��� , - STAIR 1 � � » occ / � � ,, 1 b ' I I - � -:� ME��� a � , ` , � B-NORTH .. . r — � ❑ ME�y W,� o � CY PRESSURIZED — L J � �� �� i _� 0 � �� ° � ° _ � � ' STAIR ENCLOSURE , � � ,� o _ 22 x o.2 — 4.4 13 x 0.3 = 3.9" $] _ � MIN. EGRESS WIDTH MIN. EGRESS � , I STAIR WIDTH 22x0.2 = 4.4" $] � 22x0.3 = 6.6" ^ MIN. EGRESS WIDTH �I I I � , 13 x 0.2 = 2.6 �u � � o � o - o � MIN. EGRESS MIN. EGRESS NADTH 22x0.3 = 6.6" ;I — STAIR WIDTH MIN. EGRESS STAIR WIDTH ,� �__ - -i I_ 0 I_I ';�� ' ! UNIT A602 — 101'-0" COMMON PATH OF EGRESS TRAVEL 1 AT2.7 1 CODE PLAN - LEVEL 6 CODE PLAN - LEVEL 7 SCALE: �/�s" _ �'-o" PLAN � SCALE: �/�6" _ �'-o" PLAN z Z 0 0 0 8 16 32 = 0 8 16 32 � _ � � � g II � � ' . 0� — � — � : � � : ii i ii - PROJ. N0. ��004.00 _ L DRAWN: j CHECKED: RW ( - � - - � CADD FILE: HK � = DATE: �g20/2013 � � - REVISIONS: __ � _ i Q1 ADDENDUM 1 01/24/2014 _ � ■ / Q2 BLDG DPT COMMENTS 03/31/2014 j i Q3 FOR CONSTRUCTION 07/15/2014 II I I � Q4 PR 001 UNIT MODS 12/19/2014 � _ ■ � ASr19 BLDG DEPT REVIEW 05/18/2015 : - o CQOZ ARCHITECTURE � �_ � � �, i � .i.i. .i.i. � -i.i.i.i.i.i.i.i.i.i.i� STRATA VAIL � 100% CD'S 0 � � SHEET TITLE: � � � �.�.�.�.�.� � � � � �� ! � CODE PLAN *� ■ �„ � - � �� LEVEL 6 & LEVEL 7 �o ga BLDG A ELEVATOR CORRIDOR SHEET LEGEND ��� C O D E P LA N - L E V E L 6 2 HOUR WALL SCALE:AS Noted �� 3 _ � _ � _ � � _ � � _ � � _ � � _ � � _ � � _ � � _ SCALE: �/�s° _ �'-o" PLAN � � � � � � � � � � � � � 1 HOUR WALL SHEET NUMBER: z ■ i � i � i � i � i � i � i � i � i � i � i � i ■ ,5 HOUR WALL O 0 8 16 32 � 12 _ # T ANTICIPATED OCCUPANT LOAD & DIRECTION OF EXIT ■ BUILDING B BUILDING A 1 HR ROOF RflCHI1ECtURE CONSTRUCTION UL P732 1 HR EXTERIOR WALL -- 1 HR ROOF / CEILING 3003 Larimer Street SEE: GA FILE N0. WP8005, CONSTRUCTION SEE SHEET T2.2 FOR LOCATION-- � r UL P732 Denver, Colorado 80205 SEE 10/A9.2.1 FOR WALL � _ � � -� ASSEMBLY DETAIL - a� �� - Phone 303,861.5704 � � , � � � T.O. SLAB LEVEL 7 � � � � � _ � � � � � 169-8 - R-2 R'� R'� R'Z UNIT CORRIDOR WALL 0.5 HR T.O. SLAB LEVEL 6 -' � ; „ — 157-8 � � _ R-2 R-2 � � , - � , . ._ - - � T.O. SLAB LEVEL 5 � � IDI �, 146—3 ` — UNIT CORRIDOR WALL 0.5 HR — , � ; R-2 R-2 — R-2 _ R-2 T.O. SLAB LEVEL 4 _ _ � � � � , 134-10 CORR - R_� � �_� 2 HR FLOOR �_� ASr19 T.O. SLAB LEVEL 3 / CEILING: UL D779 — �_ - -WETFF FIREPROOFING RT — — , 123—5 STRUCTURE AND UNDERSIDE � °°� OF METAL DECK ' � ��� ����� R-2 R-2 , � - sTA�R R-1 � � T.O. SLAB LEVEL 2 � �-- - , � �� ������� � 112-0 -- � - 2—HR—F�OORf-CEINNG:— — — � � ��������� � � POOL � CONCRETE DECK � � 0 -3 R-2 - _—�-----' I ESTAURANT n _� � 2�� �� � T.O. SLAB LEVEL 1 � ,`1 � 100-0 EL. USGS 8151.0 —, , . �-r �-� �� �-r ��;-�-�fi-�- _� � -� _ � _ � _ � _ � _�_� � _ � _ � _ � _ � _ � - _ — -, �-� � �-,-�--�-� - , -- - � - — �-� - - ' ;�� �� � p�,� � � � � � � � � .� PARKING _2 - , - j, As(��s PARKING -� - �; � � = S-2 ; T.O. SLAB LEVEL P1 � _ _ �_ � _ _ _ _ _ _ _- _ � � ! - 03.31.2014 ,_� �.�_:�� �_� �. � -�-�,-,-�-�, � �-�-� �,-�,-r� ,,: �� � � �,, � � i 8$-0 - � � _� �� � � -� � � .����, � � ��_ � � � � � � _ � �—� � ,� ,�� � � � � � � � � � _ � �__ �� _ PARKING ( 1 HR EXTERIOR WALL _ PARKING _� � � S_2 i i � � - T.O. SLAB LEVEL P2 � - � � � � � � � � _ 76-6 � � � � � � � � � � - � � � � � � �r_.. � � � r� � � � � � � � � � � � � � � � � � � � � � � � � � � PARKING PARKING �+ �i - � 2 0 `7 2 � ,�T.O. SLAB LEVEL P3 � 65-0 -- -- - � SEE T2.7 FOR FIRE DEPARTMENT VEHICLE O ACCESS RELATIONSHIP TO BUILDING Q ELEVATIONS FOR CLARIFICATION OF STRATA VAIL NOT BEING A HIGH-RISE � � O CODE SECTION J 1 � O S�A�: ,i,6„ _ ,�-o„ U 0 8 16 32 .. � J � � / I�ASr19 � ��s���r�r��a� �L�ur���r�� �i�c�u�� s+����u�� - ���� � l�E�l�E�I'�I�L R�1��1�IN� FI�C'�U�� S�H��1ULE - BL�� � SHEET LEGEND FLc�Q� LEV'EL I�NIT� UI+ATEf� LAV �•ATHTi:�B.� FCITCHEN �LC�THE� C�N1hv�ENTS FLQO� LE1�EL k�NIT� U°J�4TEI� LA'� �r��HT�B��' KITCHEN �LC�THE� GC11�Ih�lENT� E3LllC� � �L���Y �W�WEC� �I�lMS VUA,�W�I� E�Li7�l;� � �L�?���` �F�C�4��R �I�1K 'JU,�,�f ICR � i : � � i � � i � i i � i � � � i � i i � i i � i � � 2 HOUR WALL L��fEL 1 A101 � � � 1 1 L�11�L 1 �1f�1 � 4 4 1 1 � ��fC�l�'YlJ�1f�' � , � , � , � , � � � � � 1 HOUR WALL LE'�EL i T�TA'L� � � � 1 1 B1C�� 4 � � 1 �I 2 �*�JRYUNIT ■ � � � � � � � � � � � � � � � � � � � � � � � ■ .5 HOUR WALL �E�'�L �� T�TAL� 7 9 9 � � I�E�EI� � �,�07 � � � 1 1 12 �,��� � � 1 1 1 L���fEL � B�(�1 4 i � 1 �I #O T ANTICIPATED OCCUPANT LOAD & DIRECTION OF EXIT €��4� � � 4 1 1 ���� 1 1 1 1 1 A��]� � 5 � 1 1 B��]3 1 1 1 1 7 A��]5 4 � 5 1 1 8�04 1 1 1 1 1 �2�7� 1 1 1 � 1 8��5 � 5 � 1 1 A�i�7 � � � � 1 LE1f�L 2 TC)�'AL� 11 1� 1� 5 5 A�QB � 4 � 1 1 11�C]� 4 5 � 1 1 I��V'��. � �3�Q1 � � � 1 7 L,�V�L � T{�T�I�� �6 3� 30 � '9 8�0�2 � � 4 1 7 ��f�� � 7 � 1 1 LEV'EL � A�Q� � � 4 1 1 ���� � � 4 1 � A�C�� �4 5 � 1 1 ��(}� 3 4 � 1 � �1�0� � 7 5 1 1 ���7 � � � 1 7 .�3(�� 4 5 4� 1 1 L.EV'�L � `T�`1"AI.S �Q �7 �� � � A��D� � � � 1 1 A��J� � 4 4 1 1 L�1fEL 4 8��1 2 � � 1 �1 L€'��L 3 T�T�IL� �� 3i �7 f fi B��?� 3� 4 4 1 1 B4[}3 � � � 1 7 LEV�L � ���}1 � � 4 1 1 8�05 � 4 � 1 1 ���2 � � 5 1 1 B�tb6 � �4 4 1 1 A�3�73 � �' � 1 1 B40' � 12 ' 1 1 A�d}� � � & 1 1 LE1f�L � ��T�L� �� �� �� � � A4�p� 4 �6 �r 1 1 t���°� � � 4 1 1 �,�1f�� � B5fJ1 � 3 � 1 1 �EVEL � T�TA�L� �� 3� �� � � ��t�� 3 �4 � 1 1 PROJ. N0. ��004.00 ���3 � ? 5 1 1 LE�I�L 5 A50� 3 � 4 1 1 �50� 3 � 4 1 � DRAWN: RW ,��(�� � � � 1 1 B�C�� 3 � 4 1 1 CHECKED: HK ,��0� � 7 � 1 1 B��7 � 1 � 7 1 1 A�O�- �4 � � 1 1 �EV'EL � T�TAL� �� �� �� 6 � CADD FILE: .dwg ���� � � � 1 � DATE: 12/20/2013 A50� � 4 4 1 1 L.��1`EL � �6�1 1 1 1 1 7 I�E'JEL 5 T�TA��.S �'� �1 �l +� � BG�I� 4 5 � 1 1 REVISIONS: B��]� � 4 4 1 1 Q1 ADDENDUM 1 01/24/2014 L��IEL � a���1 � � �L 1 1 8��� � 4 4 1 1 Q2 BLDG DPT COMMENTS 03/31/2014 A�O� � � � 1 1 8�05 5 � � 1 1 Q3 FOR CONSTRUCTION 07/15/2014 A60� � � 5 1 1 iJ E�+'�� � T�TA,�� 1� ��} 1'� � � A�p� � ; � 1 1 ASr19 BLDG DEPT REVIEW 05/18/2015 �E�'E� � T�T1��S �4 �8 �� � � �,���� 7 �f�1 � �' � 1 � � �T�R'�I�IVIT CQOZ ARCHITECTURE B�Q2 5 �6 � 2 7 � �TC7R�flJNIT TC���a� Fr�U�E ���ra� � � � i�� ��� �2 �� !LE�'�L � T�T�L� �� �� 1� � 2 � 6�L�?� �k � T�TAL �I�CTlJRE !C�IJNT ��� ��,� ��� �� �� STRATA VAI L � �L�� � 100% CD'S �, SHEET TITLE: � �� TflTAL EI�TI�FCE ��]19N� � 11 1�4�' ��� �� �� CODE SECTIONS x� � � �L�� l� �� �o sv T+pT�1L FI�TI�R� ��1��1T �1� ��7 �.�� �� �� �', �L[�� A �& � �� SCALE:As Noted SHEET NUMBER: ■ SHEET NOTES 1. '',�;� HATCHING INDICATES HIGHEST OCCUPIED FLOOR LEVEL. ' �/. 2. THIS SHEET CLARIFIES THAT SECTION 403 HIGH-RISE BUILDINGS DOES NOT APPLY TO THIS BUILDING. RflCHITEC1UflE 3003 Larimer Street SHEET LEGEND Denver, Colorado 80205 � ii � i � � i � � i � ii � ii � i � � � i � ii � 2 HOUR WALL Phone 303,861.5704 � � � � � � � � � � � � � 1 HOUR WALL ■ i � i � i � i � i � i � i � i � i � i � i � i ■ .5 HOUR WALL 12 #O � ANTICIPATED OCCUPANT LOAD & DIRECTION OF EXIT x,�.L,s,b.---=� ��� ����.. �°� ���A��� � , � ��������� � � �LL�6��� �' � �O��T,� � � ��� � ��� �� p1�'►.� ,, , , , -- -, . ,. , � - �� �� ' ' �>> � HIGHEST OCCUPIED � FLOOR - BLDG B 3 � � � � � �, % � LEVEL 7 - - - , i � � � � � ,�'� � ,� , , � ° �� HIGHEST OCCUPIED /� ��� ,, i , � __ ,�� � �.� � _ � / � , FLOOR - BLDG A LEVEL 6 � � � � - � ��� �� LEVEL 6 LEVEL 6 � 6 FLOORS - — x ° O o � � — � � � � _ x r � ���� �� � � N i � i � i � � � i � � �� ' o � �-' ` �� � �� �" 5 FLOORS ���o0 0�o0 �o 00 00 _ o0 o LEVEL 5 � �� � LEVEL 5 LEVEL 5 ,� ;' � � 0 0 0 � . - � � � — — — � � � � . . � � - — —o- p . . p � �� � �� � o� � � � � a a � � � �� � �� � ���� K\ �� j _ ��� o � �� ��� � ��� o � o0 00 0 0 0 0 0�o0 0�oo � io 00 ° � o0 00 0 0 00 ° LEVEL 4 z � � � LEVEL 4 LEVEL 4 - - -�-- - -- — - � - - - - - � , ��. ,- — — _ �o o � . o p . . O .� . . . 'O ' o � � � � � � � � i � i � i �� � � i �� � �� �� �� � � �� i � i � i� � � o � �� � _ ��� � � o0 00 0000 � LEVEL 3 � ° � O 0o LEVEL 3 0 oc � LEVEL 3 '� i - - - - -� - - � - — — — — — = z � i cD ° � � ° / \ �—i � � _ � s � � � I � � � � � � � � � ��� ' �� ��� � ��� ^ � � � � � � � � � o � � � � c° � � ;� oo � o�n � � � o0 00 0 •� 0 00 00 00 0 � o o� � � _ I LEVEL 2 LEVEL 2 _i _ - - - - ----------- - - - - LEVEL 2 � - � - 0 000000 � � — ---------- ---- ----------------- �------ ---------� ------ � � � ' ` _� o � I�I� � � � o0 s � _ __ . o 00 00 I I � I O =——————————- � Q II �-------� I e � N ; ', �----, ' �0 `� LEVEL 1 � oDO � 00 0 II� °o°o �� _ ---�---r- ' ----- � i �-- � � -- - _ � fi > n n n - -------- - � LEVEL 1 BLDG B ------� I�l �I�_� I I LEVEL 1 z =__ _ _____-__ ___-_-_-___------------------------------------------ � 6. � - ------ _ �_�__ _ , - EL. USGS 8151.0 0 0o i � ---- -- EtSfS�S�lSY..d=_____