Lion's Ridge Apartments —Buildings 1 & 2
Final Duct Leakage Report
Testing Date: September 4; September 9
Builder: Gorman Builders
Contact: Chuck Collins
Site Address: Lion's Ridge Apartments,Vail
Testing By: Kristen Hartel
Report By: Kristen Hartel
Background
Final Duct Leakage Performance testing was completed for all upper level units in buildings 1 and 2
of Lion's Ridge Apartments.
The Town of Vail has adopted the 2012 IECC, which currently requires that losses within the duct
system do not exceed 4 cubic feet per minute(cfm)to the exterior of the unit for every 100 square feet
of living space.
Measured Leakage
Building 1
Unit Number Unit Type Allowable Confirmed
Leaka e Leaka e
1301 A 22 cfm 16 cfm
1302 D 33 cfm 17 cfm
1303 C 32 cfm 30 cfm
1304 D 33 cfm 26 cfm
1305 C 32 cfm 27 cfm
1306 D 33 cfm 23 cfm
1307 C 32 cfm 19 cfm
1308 E 34 cfm 31 cfm
Building 2
Unit Number Unit Type Allowable Confirmed
Leakage Leakage
2301 A 22 cfm 10 cfm
2302 D 33 cfm 13 cfm
2303 C 32 cfm 29 cfm
2304 D 33 cfm 12 cfm
2305 C 32 cfm 19 cfm
2306 D 33 cfm 15 cfm
2307 C 32 cfm 24 cfm
2308 D 33 cfm 15 cfm
Please call with any questions or concerns.