Lion's Ridge Apartments —Building 4
Final Duct Leakage Report
Testing Date: April 18, 2016
Builder: Gorman Builders
Contact: Clint Tyrrell; Chuck Collins
Site Address: Lion's Ridge Apartments,Vail
Testing By: Kristen Hartel
Report By: Kristen Hartel
Background
Final duct leakage performance testing was completed for all upper level units in Building 4 of
Lion's Ridge Apartments.
The Town of Vail has adopted the 2012 IECC, which currently requires that losses within the duct
system do not exceed 4 cubic feet per minute (cfm)to the exterior of the unit for every 100 square
feet of living space.
Measured Leakage
Building 4
Unit Number Unit Type Unit Allowable Confirmed
Condition Leakage (cfm) Leakage (cfm)
4301 C Exterior 37 36
4302 B Exterior 26 25
4303 C Interior 37 35
4304 D Interior 39 37
4305 C Interior 37 37
4306 D Interior 39 19
4307 C Interior 37 30
4308 D Interior 39 22
4309 A Interior 25 21
4310 B Interior 26 24
4311 C Exterior 37 37
4312 B Exteriar 26 26