October 3, 2016
JR Mondragon
Town of Vail
42 W. Meadow Drive
Vail, CO 81657
RE: Reference : B11-0496 Strata Vail Permit Drawings
Dear JR:
• We are submitting to the TOV building department for review and approval the following :
• Incorporate Rooftop Kitchen Equipment for Future Restaurant Kitchen into the project scope.
1. We issued CCD 079 on 08/23/2016 to PCL for providing pricing to ownership and also
procure long lead Mechanical equipment.
2. Refer to enclosed CCD 079 Cover Letter for full description of drawings Revisions; inclusive
of Architectural, Structural, Plumbing, Mechanical and Electrical drawings.
Enclosures :
• CCD 079 Cover Letter
• Architectural, Structural, Plumbing, Mechanical and Electrical Drawings indicate in CCD 079.
• Assembly Evaluation Report AER 09038 2HR Horizontal Duct Shaft Enclosure ; Figure 8.
Sincerely,
10/03/2016
OZ Architecture, Inc.
ARCHITECTURE
URBAN DESIGN
INTERIOR DESIGN
10/3/2016
Page 1 of 2 G:\2007\17004 Lionshead Inn\CA\Permits\CCD 079 Future Kitchen Rooftop Equipment\CCD-079 - Rooftop Kitchen
Equipment Cover Letter.docx
DENVER BOULDER COLORADO SPRINGS
DENVER PHONE: 303.861.5704
3003 LARIMER STREET FAX: 303.861.9230
DENVER, COLORADO 80205 WWW.OZARCH.COM
CONSTRUCTION CHANGE DIRECTIVE
YOU ARE HEREBY DIRECTED TO MAKE THE FOLLOWING CHANGE(S) IN THIS CONTRACT:
Architecture
1. A2.07A – Roof Plan A
a. Added 4 mechanical equipment roof penetrations.
b. Updated equipment layout – updated roof hatch location to match installed location.
c. Added flag note #19.
2. A3.06A – Reflected Ceiling Plan Level 6A
a. Added (2x) 24”x24” access panels.
b. Located 2hr rated horizontal enclosure.
3. A4.11 – Building Section
a. Updated mechanical equipment roof penetration.
4. A10.04 – Interior Details
a. New Detail 20 – 2 Hr Rated Horizontal Enclosure. Contractor to follow figure 8 of the enclosed AER-
09038.pdf for the rated horizontal enclosure at locations indicated on the drawings.
Structure
1. S2.07A – Roof Plan A
a. Added roof penetrations and associated detail call out.
Plumbing
2. P1.03 – Plumbing Details
a. Added detail for piping of an evaporative cooling unit.
3. P2.06-A – Floor Plan Level 6-A Plumbing
a. Added cold water and drain for the makeup air unit.
Mechanical
Per the attached mark up, furnish and install the roof mounted kitchen equipment.
4. M1.03 – Mechanical Schedules
a. Revised GMAU-3 schedule.
5. M1.04 – Mechanical Schedules
a. Revised KEF-1 schedule.
b. Added DWEF-1 and TEF-3 schedules.
6. M2.06-A – Floor Plan Level 6-A Mechanical
a. Illustrated the ductwork in the 6th level ceiling space (previously shown on M2.07A).
7. M2.07-A – Roof Plan Level 7-A Mechanical
a. Removed the ductwork previously shown at this level.
b. Indicate that the equipment shall be installed now.
PROJECT NAME: Lion Vail ( Strata Vail ) CCD #: 079 OWNER ARCHITECT
CONSULTANT
CONTRACTOR FIELD
PROJECT #: 17004.15 DATE OF ISSUANCE: 08/23/2016
CONTRACTOR: PCL Construction
2000 South Colorado Blvd
Tower Two Suite 2-500
Denver, Colorado 80222
Vail Colorado
ARCHITECT: OZ Architecture, Inc.
OWNER: LionsHead Inn, LLC
CONTRACT FOR: Construction
CONTRACT DATED: May 2014
10/3/2016
Page 2 of 2 G:\2007\17004 Lionshead Inn\CA\Permits\CCD 079 Future Kitchen Rooftop Equipment\CCD-079 - Rooftop Kitchen Equipment
Cover Letter.docx
Electrical:
Per the attached mark up, provide power wiring for the HVAC equipment for the future kitchen.
8. E1.07 – Mechanical Equipment Schedule
a. Added provisions for DWEF-1.
9. E1.08 – Mechanical Equipment Schedule
a. Revised provisions for KEF-1 and KMAU-1.
b. Added provisions for TEF-3.
c. Revised Mechanical Equipment Schedule Note #5.
10. E2.06-A– Floor Plan Level 6-A Electrical
a. Added fire/smoke dampers.
11. E2.07-A– Roof Plan Level 7-A Electrical
a. Added provisions for DWEF-1 and TEF-3.
b. Added controls conduit requirements.
ATTACHMENTS:
Structural : S2.07A
Architectural : SV_CCD 079 – OZ Drawings.pdf & AER-09038.pdf
Mechanical: 20160822 CCD-079 – Mech-Plbg.pdf
Electrical : 20160822 CCD-079 – Elec.pdf
Plumbing : P1.03, P2.06-A
For review of AIA Document G714-2001
PROPOSED ADJUSTMENTS
1. The proposed basis of adjustment to the Contract Sum or Guaranteed maximum Price is:
i. Lump Sum Decrease of $00000.00
ii. Unit Price of $ 00000.00 per
iii. As provided in Subparagraph 7.3.6 of AIA Document A201, 2007 edition.
iv. As follows:
2. The Contract Time is proposed to be determined . The proposed adjustment, if any, is days.
WHEN SIGNED BY THE OWNER AND ARCHITECT AND RECEIVED BY THE CONTRACTOR, THIS DOCUMENT BECOMES EFFECTIVE IMMEDIATELY
AS A CONSTRUCTION CHANGE DIRECTIVE (CCD) AND THE CONTRACTOR SHALL PROCEED WITH THE CHANGE(S) DESCRIBED ABOVE.
SIGNATURE BY THE CONTRACTOR INDICATES THE CONTRACTOR’S AGREEMENT WITH THE PROPOSED ADJUSTMENTS IN CONTRACT SUM
AND CONTRACT TIME SET FORTH IN THIS CONSTRUCTION CHANGE DIRECTIVE.
ARCHITECT:
OZ Architecture, Inc.
OWNER:
Lionshead Inn, LLC
CONTRACTOR:
PCL Construction
3003 Larimer Street
Denver, Colorado 80205
705 West Lionshead Circle
Vail, CO 81657
2000 South Colorado Blvd.
Denver, CO 80222
Vail, CO
SIGNED: Jeff Mapp SIGNED: SIGNED:
BY: OZ Architecture BY: BY:
DATE:
8/23/2016 DATE:
DATE:
Page 1 of 10
574-533-0337
www.p-e-i.com
Assemblies Listed For
1. Non Axial Load Bearing Wall 3. Fire Resistance
2. Transverse Load Capacity
Compliance
1. Meets the requirements for shaft enclosures in accordance with the 2009 International Building Code®.
Component Descriptions
1. J-Runners
3. Gypsum Liner Panels
3. Meets the requirements for structural integrity of exit enclosures and elevator hoistway enclosures for High-Rise
Buildings (Section 403.2.3. of the 2009 International Building Code) when minimum 4-inch, 20 gage framing members are
used in conjunction with a base layer of Fiberock® VHI in a minimum 2-hour fire resistance rated assembly.
2. Meets the requirements for non-combustible construction in accordance with Section 703.4 of the 2009 International Building
Code®.
4. Tested for fire resistance in accordance to ASTM E119.
5.USG Shaftwall Systems are classified and tested by Underwriters Laboratories Inc. as to fire resistive design listings of
assemblies, and as described in this report.
The paper-faced products listed below comply with ASTM C1396 and Glass-Mat panel is in compliance with ASTM
C1658. Both types are tested in accordance with ASTM E119, E136 (modified), E84 and are classified as
composite non-combustible, Class A building materials.
USG Shaft & Stair Wall Systems are generally constructed with the following components.
Assembly Evaluation Report
Progressive Engineering Inc.
58640 State Road 15
Goshen, Indiana 46528
This Document Published By:
Initial Listing Re-Approved
April, 2009
Progressive Engineering Inc.is an accredited Testing Laboratory and
Third Party Quality Control Agency. This Assembly Evaluation
Report represents a system that Pei has performed testing and
evaluation. This Assembly Evaluation Report in no way implies
warranty for this product or relieves United States Gypsum Company of
their liabilities for this product.Pei is accredited to ISO Standard 17020
and 17025. This AER is an official document if it is within one year of
the initial or renewal date.Chicago, IL 60661
Listed Assemblies
USG Shaft & Stair Wall Systems
Listed For
United States Gypsum Company
550 West Adams Street
SHEETROCK®Brand Gypsum Liner Panels a high performance panel that is composed of a non-
combustible gypsum core encased in a water resistant 100% recycled green face and back paper. Gypsum
Liner Panels are a nominal thickness of 1" x 24" wide x 8-14 ft. long. Used in Fire-Rated, non-load bearing
Shaftwall assemblies.
Terminations: Install full length steel E-Studs or J-Runners vertically at T-Intersections, corners, door jambs and
Openings: Frame with vertical E-stud or J-Runner at vertical edges, horizontal J-runner at head or sill.
The metal framing members used in construction of USG Shaft & Stair Wall Systems are manufactured from cold
roll-formed light gauge galvanized steel conforming to ASTM A 653, with a yield strength of 33,000 psi minimum.
The galvanization coating shall be a G40 minimum. The available sizes in 2-1/2", 4" and 6" deep and lengths of up
to 16 feet, 20 or 24 gauges. Position steel J-runners at floor and ceiling with the 1" leg towards the finished side of
the wall. Securely attach the runners to the structure supports with power actuated fasteners.
For attachment to steel framed construction install floor and ceiling J-runners and End wall J-Runners or E-Studs,
on columns and beams before the steel is fireproofed.
Cut the C-H studs 3/8" to 5/8" shorter than the floor-to-ceiling height. Install C-H studs interlocked between the
SHEETROCK brand gypsum Liner Panels with the liner panels securely engaged.
2. Steel C-H Studs
USG Steel C-H and E Studs are manufactured from cold roll-formed light gauge steel conforming to ASTM A653
with a yield strength of 33,000 psi minimum. The galvanization coating shall be a G40 minimum. The available
sizes are 2-1/2", 4" and 6" deep and lengths of up to 16 feet, 20 or 25 gauges.
June, 2013
ver 7.4
AER-09038
Page 2 of 10
3. Gypsum Liner Panels cont.
4. Gypsum Wallboard
5. Fiber Reinforced Gypsum Panels
One-Hour Cavity Shaft Wall (Non-Load Bearing), See Figure 1
1. Minimum 2-1/2" wide 24 gauge floor and ceiling J-runners, attached to structure as described above.
Two-Hour Cavity Shaftwall (Non-Load Bearing), See Figure 2
1. 2-1/2" deep 25 gauge minimum floor and ceiling J-runners, attached to structure as described above.
4. 1" thick SHEETROCK® Brand Gypsum Liner Panel - Friction-fitted in "H" portion of CH studs.
3. A minimum 2-1/2" deep USG C-H studs 25 gauge, spaced 24" o.c., with the H-Section of the C-H stud towards the shaft
side of the assembly. Screw attachment is not required to affix the stud to the runner, if Shaft Wall is less then 16 ft. tall. E-
shaped studs may be used for closure panels at the end of walls or columns. (If J-runners are used at end walls, the
gypsum liner needs to be fastened at the ends with 1-5/8" long Type S screws that are spaced 12" o.c.).
Note: All of these panels should be cut 1" shorter than the floor-to-ceiling height, to allow for the panel to be fitted
between the top and bottom J-runners. Where shaft wall height exceeds the length of the liner panel; it must be
butted together with meeting factory end cuts. The joints should be staggered and positioned in the upper or lower
1/3 of the wall. Panels are UL/ULC classified for fire resistance and identified as Type SLX on the UL marking and
UL Fire Resistance Directory.
2. One-layer, 5/8" thick SHEETROCK
®Brand FIRECODE
®Core Gypsum Panels (Type X), installed vertically with 1" long
Type S screws spaced 12" o.c. in field and at edges for vertical application, and 8" o.c. for horizontal application.
SHEETROCK®Brand Mold Tough
TM Gypsum Liner Panels feature a non-combustible, moisture- and mold-
resistant gypsum core encased in moisture and mold-resistant, 100-percent blue face and back papers. They offer
enhanced moisture and mold resistance over standard gypsum liner panels. The panels are UL Classified for fire-
rated construction (Type SLX). Available 1 inch thick, 24 inches wide and in lengths up to 14 feet.
2. Two (2) layers, 1/2" thick SHEETROCK
®Brand FIRECODE
®C Core Gypsum Panels. Apply base layer with 1" long Type
S screws 24" o.c. in field and at the edges for vertical application and 16" o.c. for horizontal applications. Apply face layer C-
H studs and J-runners with 1-5/8" long Type S screws. Space the screws 12" o.c. at the edges and in the field when applied
horizontally. All joints between the base and face layers must be staggered.
SHEETROCK®Brand Glass-Mat Liner Panel have a noncombustible, moisture- and mold-resistant gypsum core
that is encased in moisture- and mold-resistant glass mat. The panels are UL Classified as to fire resistance (Type
SLX) and feature double-beveled edges for easy installation.
3. Minimum 2-1/2" deep USG C-H Studs 25 gauge 24" o.c., with the H-Section of C-H Stud towards the shaft side of the
assembly. Screw attachment is not required to affix the stud to the runner, if Shaft Wall is less then 16 ft. tall. E-shaped
studs may be used for closure panels at end of the walls or columns. (If J-runners are used at end walls, the gypsum liner
is fastened at the ends with 1-5/8" long Type S Screws 12" o.c.)
4. 1" thick SHEETROCK® Brand Gypsum Liner Panel - Friction-fitted in "H" portion of C-H studs.
~Cavity Shaft Wall Systems ~
The products listed below comply with ASTM C1396 and are tested in accordance with ASTM E119, E136
(modified), E84 and are classified as composite non-combustible, Class A building materials.
SHEETROCK®Brand Mold Tough
TM Gypsum Panels have a non-combustible, moisture- and mold-resistant
gypsum core encased in moisture- and mold-resistant, 100-percent recycled green face and brown back
paper. They offer enhanced moisture and mold resistance over standard gypsum panels. Available in
FIRECODE® and FIRECODE® C core formulations in the same widths, thicknesses and lengths listed above.
SHEETROCK®Brand FIRECODE
®Core Gypsum Panels (Type X)are composed of fire-resistant gypsum
core encased in 100-percent recycled natural finish face paper and 100-percent recycled liner paper on the
back side. The panels are UL Classified for fire-rated construction (Type SCX). Available 5/8 inch thick, 48 or
54 inches wide and lengths up to 14'.
SHEETROCK®Brand FIRECODE
®C Core Gypsum Panels provide improved fire protection over standard
FIRECODE panels due to additives that enhance the integrity of the core under fire exposure. Comply with
Type X requirements. The panels are UL Classified for fire-rated construction (Type C). Available in 1/2 and
5/8 inch thicknesses, 48 inches wide and lengths up to 14'.
FIBEROCK Brand VHI (Very High Impact) Abuse-Resistant Interior Panels (Type X)are high
performance abuse resistant panels. The panels are UL classified for fire-rated construction
(Type FRX-G). Available panels are 5/8" thick, 48" wide and available in lengths up to 12'.
The product listed below complies with ASTM C1278 in accordance with ASTM E119, E84 and are classified as a
Class A building material.
AER-09038
Page 3 of 10
Two-Hour Stair Cavity Shaftwall (Non-Load Bearing), See Figure 3
4. 1" thick SHEETROCK® Brand Gypsum Liner Panel - Friction-fitted in "H" portion of C-H studs.
Three-Hour Cavity Shaft Wall (Non-Load Bearing), See Figure 4
1. A minimum 2-/12" deep 25 gauge floor and ceiling J-runners, attached to the structure as described in the Figure 4.
4. 1" thick SHEETROCK® Brand Gypsum Liner Panel - Friction-fitted in "H" portion of C-H studs.
Three-Hour Stair Cavity Shaftwall (Non-Load Bearing), See Figure 5
4. 1" thick SHEETROCK® Brand Gypsum Liner Panel - Friction-fitted in "H" portion of C-H studs.
Two-Hour Horizontal Stud Cavity Shaft Wall Assembly (Non-Load Bearing), See Figure 6
1. A minimum 4" deep 20 gauge J-runner to be installed vertically, on the ends of the wall.
One & Two Hour Horizontal Cavity Ceiling Membrane (Corridor Ceiling or Underside Stair Applications),See Figure 7
3. A minimum of 2-1/2" deep USG C-H studs 25 gauge, spaced 24" o.c., with the H-section of the C-H stud towards the
shaft side of the assembly, if the Shaft Wall is less than 16 ft. tall. Screw attachment is not required to affix the stud to the
runner, if Shaft Wall is less then 16 ft. tall. E-shaped studs may be used for closure panels at the end of walls or columns.
(If J-runners are used at end walls, the gypsum liner needs to be fastened at the ends with 1-5/8" long Type S screws that
are 12" o.c.).
3. A minimum 2-1/2"USG C-H studs 25 gauge that are spaced 24" o.c., with the H-section of the C-H stud towards the
shaft side of the assembly. Screw attachment is not required to affix the stud to the runner, if Shaft Wall is less then 16 ft.
tall. E-shaped studs may be used for closure panels at the end of walls or columns. (If J-runners are used at the end walls,
the gypsum liner needs to be fastened at the ends with 1-5/8" Type S screws spaced 12" o.c.)
2. Apply (3) layers of 5/8" thick SHEETROCK
®Brand FIRECODE
®C Core Gypsum Panels (Type C), vertically or
horizontally to the room side of the C-H stud. First layer shall be attached with a 1" long Type S screw placed 24" o.c. in the
field and at the edges when applied vertically, for horizontal applications the screws shall be spaced 16" o.c. The second
layer shall be applied with 1-5/8" long Type S screws spaced 24" o.c. when applied vertically or spaced 16" o.c. when the
applied horizontally. The Face layer shall be applied with 2-1/4" long Type S screws that are spaced 16" o.c. when the
board is applied vertically, and spaced 12" o.c. when the board is applied horizontally. All joints must be staggered a
minimum of 24" o.c. from the adjacent layers, where screws are offset a minimum of 6" from the layer below.
2. Apply two (2) layers of 5/8" thick SHEETROCK
®Brand FIRECODE
®C Core Gypsum Panels (Type C), vertically or
horizontally to the "room" side of the C-H stud. For vertical applications using a 1" long Type S screw spaced 24" o.c. in the
field and at the edges. For vertical applications the gypsum panels need to be spaced 16" o.c. and for horizontal
applications they need to be spaced at 16" o.c.
1. A minimum 2-1/2" deep 25 gauge floor and ceiling J-runners attached to the structure as described above.
3. A minimum 2-1/2" deep USG C-H Stud 25 gauge spaced 24" o.c., where the H-section of the C-H stud faces the shaft.
Screw attachment is not required to affix the stud to the runner, if Shaft Wall is less then 16 ft. tall. E-shaped studs may be
used for closure panels at the end of the walls or columns. (If J-runners are used at end walls, the gypsum liner should be
fastened at the ends with a 1-5/8" long Type S screw, spaced 12" o.c.)
~Cavity Shaft Wall Systems cont. ~
4. 1" thick SHEETROCK
®Brand Gypsum Liner Panel - Friction-fitted in "H" portion of C-H studs. The wall width is limited to
the length of the Gypsum Liner Panel.
1. A minimum 2-1/2" deep 24 gauge J-runner attached horizontally to perimeter or boundary walls with a power actuated
fasteners.
3. A minimum 4" deep USG C-H stud or E Studs 20 gauge, are to be installed horizontally between the J-runners. The H-
section of the C-H stud faces the shaft. C-H Studs shuld be attached to vertical J-runners with Type S fasteners.
1. Minimum 2-1/2" deep, 25 gauge floor and ceiling J-runners, attached to the structure as described.
2. Apply one (1) layer of 1/2" SHEETROCK
®Brand FIRECODE
®Gypsum Panels (Type C) to each side of the C-H stud.
Attach the C-H stud with 1" long Type S screws 12" o.c. in the field and at the edges for a vertical application and 8" o.c.
center for a horizontal application.
2. Apply two (2) layers of 5/8" thick SHEETROCK
®Brand FIRECODE
®Core Gypsum Panels (Type X) vertically or
horizontally to the room side of the C-H stud, with 1" long Type S screws spaced 12 " o.c. in the field and at the edges for
the BASE layer. The FACE layer shall be installed with 1-5/8" long Type S screws spaced 8" o.c. All joints must be
staggered a minimum of 24" from the adjacent layers.
AER-09038
Page 4 of 10
One & Two Hour Horizontal Cavity Ceiling Membrane (Corridor Ceiling or Underside Stair Applications),See Figure 7
Two-Hour Horizontal Gypsum Duct Enclosure, See Figure 8
3. Install the C-H studs perpendicular to the J-runners, spacing them 24" o.c. with the C-section of the C-H stud facing
downward towards the corridor side of the assembly with two (2) screws a minimum of 1/2" long Type S-12 screws, one on
4. 1" thick SHEETROCK® Brand Gypsum Liner Panel - Friction-fitted in "H" portion of C-H studs.
1. A minimum 2-1/2" deep 24 gauge J-runners attached horizontally to the perimeter or boundary wall, with power actuated
fasteners.
2. Attach three (3) layers of 1/2" (minimum) SHEETROCK
®Brand FIRECODE
®C Core Gypsum Panels to the underside
"ceiling" side of the assembly. The Base layer is attached with 1" long Type S Screws that are spaced 24" o.c. The second
layer is attached with 1-5/8" long Type S screws that are spaced 12" o.c., with all the joints staggered 24" o.c. from the
base layer. The Face layer is attached perpendicular to the C-H Studs with 2" long Type S screws that are spaced 12" o.c.
and the joints are staggered 24" o.c. from the base layer.
b.For a two (2) hour assembly: Attached two (2) layers of minimum 1/2" thick SHEETROCK
®Brand
FIRECODE®C Core Gypsum Panels (Type C), to the underside of the "Corridor Ceiling" of the C-H stud and
the perimeter J-For the BASE layer, use a 1" long Type S screw that is spaced 24" o.c. along the perimeter
and the edges. The FACE layer should be applied with a 1-5/8" long Type S screw that is spaced 12" o.c. in
the field and perimeter. All joints must be staggered a minimum of 24" o.c. from the adjacent layer.
Figure 1 Figure 2
2-HR Cavity Shaft Wall (Non-Load Bearing)
4. 1" thick SHEETROCK® Brand Gypsum Liner Panel - Friction-fitted in "H" portion of C-H studs.
1-HR Cavity Shaft Wall (Non-Load Bearing)
3. Install the C-H studs perpendicular to the J-runner spaced 24" o.c. with the C-section of the C-H stud facing
downward towards the corridor side of the assembly with two (2) screws a minimum 1/2" long Type S-12 screws, one
on each side.
~Cavity Shaft Wall Systems cont. ~
2. Gypsum Wall
a.For a one (1) hour assembly: Attach one (1) layer of 5/8" thick SHEETROCK
®Brand FIRECODE
®CCore
Gypsum (Type C), to the underside of the "Corridor Ceiling" of the C-H stud and the perimeter J-runners. Use
1" long Type S screws that are spaced 12" o.c. in the field and at the edges.
AER-09038
Page 5 of 10
Figure 6
Figure 3 Figure 4
3-HR Cavity Shaft Wall (Non-Load Bearing)
Figure 5
3-HR Stair Cavity Shaft Wall (Non-Load Bearing)
2-HR Stair Cavity Shaft Wall (Non-Load Bearing)
2-Hr Horizontal Stud Cavity Shaft Wall Assembly (Non-Load Bearing)
AER-09038
Page 6 of 10
Figure 7
1 & 2-Hr Horizontal Cavity Shaft Wall (Corridor Ceiling/Stair Application)
Horizontal Gypsum Duct Shaft Enclosure (2HR Fire Rating)
Figure 8
AER-09038
Page 7 of 10
AER-09038
Table 2. Limiting Heights Vertical Shaft Walls, Applicable to Fig. 1
Stud
Description
Allowable
Deflection
L/120 11510091711
L/240 107938474
L/360 94827566
L/120 13511810893
L/240 1231099986
L/360 1010968776
L/120 15212510989
L/240 14512510989
L/360 12911210189
L/120 20 5 17 10 16 2 13 4
L/240 17 6 15 3 13 10 12 1
L/360 15 3 13 4 12 1 10 7
L/120 26 3 21 5 18 7 15 2
L/240 24 0 20 12 18 7 15 2
L/360 21 1 18 5 16 9 14 8
212CH20-34
400CH25-18
400CH20-34
600CH20-34
212CH25-18
1-hr Shaftwall/Stairwell
5psf
design
(ft - in)
7.5psf
design
(ft - in)
10psf
design
(ft - in)
15psf
design
(ft - in)
Table 1. Limiting Spans - Horizontal Shaft Walls (Ceiling Application), Applicable to Fig. 7 & 8
2-Hours Horizontal Membrane or Metal Duct Enclosure
Triple-layer 1/2" gypsum panels Maximum Span
212CH25-18 6' - 5"
212CH20-34 9' - 0"
400CH25-18 8' - 6"
400CH20-34 12' - 11"
600CH20-34 16' - 4"
2-Hours Corridor Ceiling and Stair Soffits
Double-layer 1/2" gypsum panels Maximum Span
212CH25-18 7' - 2"
212CH20-34 9' - 8"
400CH25-18 9' - 5"
400CH20-34 14' - 0"
600CH20-34 19' - 1"
1-Hour Corridor Ceiling and Stair Soffits
Single-layer 5/8" gypsum panels Maximum Span
212CH25-18 8' - 0"
212CH20-34 10' - 5"
400CH25-18 10' - 6"
400CH20-34 14' - 0"
600CH20-34 20' - 11"
Notes:
a) Based on L/240 allowable deflection with studs at 24" o.c. and JR24 runner.
b) Full stress allowed based on ASTM E119.
Page 8 of 10
General Product Usage and Limitations
3.For horizontal ceiling and ductwork applications, please see manufacturer's product brochure SA926 Shaft Wall
Systems .
2.The USG Sheetrock®Brand Cavity Shaftwall system is designed to enclose stairwalls, elevator shafts, mechanical
components and other vertical shafts.
1.These products shall be installed in accordance with ASTM C 840 Standard Specification for Application and Finishing
of Gypsum Board, and in accordance with USG Product Literature.
5.For High-Rise buildings as defined in Section 402.2.3 of the 2009 International Building Code, minimum 4", 20 gage
framing must be in conjunction with a base layer of FIBEROCK VHI in a minimum 2-hour fire resistance rated assembly.
4.Non-load bearing and limited to fire-resistance only. Structural and other requirements shall be in accordance with
pertinent building code and and manufacturer's requirements.
AER-09038
Table 4. Limiting Heights Vertical Shaft Walls, Applicable to Fig. 4 & 5
Stud
Description
Allowable
Deflection
L/120 12 2 10 8 9 8 8512410 10 9 10 87
L/240 11 2 9 9 81079114911812710
L/360 9 10 8 7 7106 10104 9 1 8372
L/120 14 2 12 5 11 3 9 10143 12 5 11 4 911
L/240 13 0 11 5 10 4 9 1 12 10 11 3 10 2 811
L/360 11 6 10 0 9 1 7 12117 10 1 9 2 80
L/120 16 4 14 3 12 11 10 7 17 9 14 6 12 7 10 3
L/240 15 2 13 3 12 0 10 6 15 7 13 8 12 5 10 3
L/360 13 4 11 8 10 7 9 3 13 11 12 2 11 1 98
L/120 19 6 17 1 15 6 13 7 19 11 17 4 15 9 13 10
L/240 17 11 15 8 14 3 12 5 18 1 15 9 14 4 12 6
L/360 15 10 13 10 12 7 10 12 16 2 14 1 12 10 11 3
L/120 28 0 25 1 21 9 17 9 25 4 22 2 19 8 16 1
L/240 24 10 21 9 19 9 17 3 21 9 19 0 17 4 15 1
L/360 21 11 19 2 17 5 15 2 20 0 17 6 15 11 13 11
600CH20-34
10psf
design
(ft - in)
15psf
design
(ft - in)
212CH25-18
212CH20-34
400CH25-18
400CH20-34
5psf
design
(ft - in)
7.5psf
design
(ft - in)
10psf
design
(ft - in)
15psf
design
(ft - in)
5psf
design
(ft - in)
7.5psf
design
(ft - in)
3-hr Stairwell 3-hr Shaftwall
Table 3. Limiting Heights - Vertical & Horizontal Shaft Walls, Applicable to Fig. 2, 3 & 6
Stud
Description
Allowable
Deflection
L/120 1221089885124101091087
L/240 1129981079114911812710
L/360 91087710610104918372
L/120 14 2 12 5 11 3 9 10 14 3 12 5 11 4 9 11
L/240 130115104911210113102811
L/360 116100917121171019280
L/120 16 414 3121110 717 914 612 710 3
L/240 15 2 13 3 12 0 10 6 15 7 13 8 12 5 10 3
L/360 13411810793131112211198
L/120 19 617 115 613 7191117 415 91310
L/240 17 11 15 8 14 3 12 5 18 1 15 9 14 4 12 6
L/360 15 10 13 10 12 7 10 12 16 2 14 1 12 10 11 3
L/120 28 0 25 1 21 9 17 9 25 4 22 2 19 8 16 1
L/240 24 10 21 9 19 9 17 3 21 9 19 0 17 4 15 1
L/360 21 11 19 2 17 5 15 2 20 0 17 6 15 11 13 11
Note: In Horizontal stud applications (Fig. 7), use above values for maximum stud spans.
212CH25-18
212CH20-34
400CH25-18
400CH20-34
600CH20-34
15psf
design
5psf
design
7.5psf
design
10psf
design
15psf
design
2-hr Stairwell 2-hr Shaftwall
5psf
design
7.5psf
design
10psf
design
Page 9 of 10
Product Labeling
1.USG's name
3. Plant Identifier & Date Code
4. UL Classification label for Firecode Resistance, surface burning characteristics and non-combustibility.
Tested to
Product Documentation
An Assembly Evaluation Service Agreement between Progressive Engineering Inc. and USG Company
A Pei test report No. 2003-1150 (A) - ICBO AC86 Limiting Height Test on a 2 Hour Shaftwall Using a 2-1/2" X 25 ga. CH
Stud 8 ft. Wall Height - Dated 12/01/2003 - Stamped by a professional engineer.
A Pei test report No. 2003-1150 (G) - ICBO AC86 Limiting Height Test on a 2 Hour Stairwall Using a 2-1/2" X 20 ga. CH
Stud 8 ft. & 10 ft. Wall Heights - Dated 12/17/2003 - Stamped by a professional engineer.
A Pei test report No. 2003-1150 (H) - ICBO AC86 Limiting Height Test ona2HourStairwallUsinga4"X25ga.CHStud8
ft. & 10 ft. Wall Heights - Dated 12/19/2003 - Stamped by a professional engineer.
Test report No. R1319, Project 04NK2667 - Shaftwall Assembly With Horizontal Placement of Studs and Gypsum Liner
Panels - Dated 2/10/2004.
Test report No. R1319, Project 04NK2667 - Shaftwall Assembly With Horizontal Placement of Studs and Gypsum Liner
Panels - Dated 3/02/2004.
Test report No. WHI-495-PSH-0154/0167 - Two Pilot Scale Horizontal Fire Endurance Tests on a Corridor Ceiling/Duct
Assembly with Either Side as the Exposed Face - Dated 2/05/1990 & 5/23/1990.
USG Drywall Shaft Partition System Product Installation Guidelines SA926 (Rev 10/07)
Test report No. R1319, Project No. 82NK27438 - Engineering Study - Classification of A 2 H Fire Resistance Shaft
Wall Constructed of 1/2" Type C Gypsum Wallboard and 1" Gypsum Board Liner - Dated 12/17/1982.
Test report - Fire Tests of Two-Hour Cavity Shaft Wall System Having C-H Vented Studs - Dated 6/23/1975
Test report - Fire Tests of Two-Hour Cavity Shaft Wall System Having C-H Vented Studs - Dated 4/02/1975
A Pei test report No. 2003-1150 (O) - ICBO AC86 Limiting Height Test on a 1 Hour Shaft/Stairwall Using a 6" X 20 ga. CH
Stud on 8 ft. and 16 ft. Wall Heights - Dated 12/10/2003 - Stamped by a professional engineer.
A Pei test report No. 2003-1150 (P) - ICBO AC86 Limiting Height Test ona1HourShaft/Stairwall Using a 2-1/2" X 20 ga.
CH Stud on 8 ft. and 10 ft. Wall Heights - Dated 12/10/2003 - Stamped by a professional engineer.
A Pei test report No. 2003-1150 (I) - ICBO AC86 Limiting Height Test ona2HourStairwallUsinga4"X20ga.C-HStud8
ft. & 12 ft. Wall Heights - Dated 12/23/2003 - Stamped by a professional engineer.
A Pei test report No. 2003-1150 (J) - ICBO AC86 Limiting Height Test on a 2 Hour Stairwall Using a 6" X 20 ga. CH Stud 8
ft. & 16 ft. Wall Heights - Dated 12/11/2003 - Stamped by a professional engineer.
A Pei test report No. 2003-1150 (K) - ICBO AC86 Limiting Height Test ona1HourShaft/Stairwall Using a 2-1/2" X 25 ga.
CH Stud 8 ft. Wall Heights - Dated 12/29/2003 - Stamped by a professional engineer.
A Pei test report No. 2003-1150 (L) - ICBO AC86 Limiting Height Test on a 1 Hour Shaft/Stairwall Using a 2-1/2" X 20 ga.
CH Stud - Dated 12/18/2003 - Stamped by a professional engineer.
A Pei test report No. 2003-1150 (N) - ICBO AC86 Limiting Height Test on a 1 Hour Shaft/Stairwall Using a 4" X 20 ga. CH
Stud on 8 ft. and 12 ft. Wall Heights - Dated 12/26/2003 - Stamped by a professional engineer.
ICC-ES Report NER-258 - USG Drywall Shaft Partition Systems - Dated April 1, 1991
A Pei test report No. 2003-1150 (B) - ICBO AC86 Limiting Height Test on a 2 Hour Shaftwall Using a 2-1/2" X 20 ga. CH
Stud 8 ft. & 10 ft. Wall Heights - Dated 12/17/2003 - Stamped by a professional engineer.
A Pei test report No. 2003-1150 (C) - ICBO AC86 Limiting Height Test on a 2 Hour Shaftwall Using a 4" X 25 ga. CH Stud 8
ft. & 10 ft. Wall Heights - Dated 12/18/2003 - Stamped by a professional engineer.
A Pei test report No. 2003-1150 (F) - ICBO AC86 Limiting Height Test on a 2 Hour Stairwall Using a 2-1/2" X 25 ga. CH
Stud 8 ft. Wall Heights - Dated 11/26/2003 - Stamped by a professional engineer.
A Pei test report No. 2003-1150 (D) - ICBO AC86 Limiting Height Test on a 2 Hour Shaftwall Using a 4" X 20 ga. CH Stud 8
ft. & 12 ft. Wall Heights - Dated 12/23/2003 - Stamped by a professional engineer.
A Pei test report No. 2003-1150 (E) - ICBO AC86 Limiting Height Test ona2HourShaftwallUsinga6"X20ga.CHStud8
ft. & 16 ft. Wall Heights - Dated 12/11/2003 - Stamped by a professional engineer.
ICC-ES (Formerly ICBO) AC86 (1995) -Acceptance Criteria for determining limiting height of composite walls constructed
of gypsum and steel studs to revision date: July 1995.
ASTM E330-97 -Standard Test Method for Structural Performance of Exterior Windows, Curtain Walls and Doors by
Uniform Static Air Pressure Differences, following procedure A. (Test Reports 2004-0329 B-L were based on this test
method)
ASTM E84 - Standard Test for Surface Burning Characteristics of Building Materials.
Each assembled USG Drywall Shaft Partition System that is covered by this AER, must be marked with the following
information:
2. Product Name
AER-09038
Page 10 of 10
Product Documentation
Opinion Letter for USG's Shaft Wall Systems - Fire Resistance Classification - Dated 10/13/2010.
NYC Department of Buildings, Report MEA 309-03-M Volume 2 - Fire Rated Gypsum Panels, Non- Load Bearing Shaft
Wall Assembly - Dated 4/23/2007
Test report No. Tz871, Book 22E - Fire Tests of One-Hour Cavity Shaft Wall System Having C-H Vented Studs - Dated
4/3/1975.
Test report for - Fire Resistance of United States Gypsum Company's 3-Hour Cavity Shaft Wall System - Dated 2/16/1972.
www.usg.com
Wiss, Janney, Elstner Associates, Inc, report no. 2006.0351 - New York Local Law 26; Rule 32-05 Impact Resistance
Testing for Stair and Elevator Enclosures using USG Shaft Wall System with FIBEROCK VHI and SHEETROCK Firecode
Core Panels - Dated 2/16/2007.
Test report for - Fire Tests of Two-Hour Cavity Shaft Wall System Having C-H Vented Studs - Dated 6/23/1975.
AER-09038