HomeMy WebLinkAboutB16-0069 Cut Sheets.pdf VCVERMONT G �O CASTINGS Designer Series Direct Vent Gas Fireplace Installation and Operating Instructions Models: STLDV(N/P)SCSB, PFLDV(N/P)SCSB, CRLDV(N/P)SCSB, CLLDV(N/P)SCSB =ice_ CERTIFIED ©WARNING: SAFETY BARRIER FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly " could result in serious injury, death or t `n property damage. • Do not store or use gasoline or other i4iCl ,. • flammable vapors and liquids in the vicinity of this or any other appliance.• WHAT TO DO IF YOU SMELL GAS " — Do not try to light any appliance. Ilifr-.01 — Do not touch any electrical switch; do not use any phone in your building.— Leave the building immediately. Ill ' —Immediately call your gas supplier from a neighbor's phone. Follow the gas ' � supplier's instructions. oEs l G4,— If you cannot reach your gas supplier, ( 7 '\\ call the fire department. • Installation and service must be performed O O CERTIFIED by a qualified installer, service agency or FRrIF�`` ® e the gas supplier. WARNING: Improper installation, adjustment, I DAGER alteration, service or maintenance can cause • injury or property damage. Refer to this manual. HOT GLASS WILL For assistance or additional information consult CAUSE BURNS. a qualified installer, service agency or the gas supplier. DO NOT TOUCH GLASS This appliance may be installed in an aftermarket,* UNTIL COOLED. permanently located, manufactured home(USA NEVER ALLOW CHILDREN only) or mobile home, where not prohibited by TO TOUCH GLASS. local codes. A barrier designed to reduce the risk of burns from This appliance is for use only with the type of gas the hot viewing glass is provided with this indicated on the rating plate. This appliance is appliance and shall be installed. not convertible for use with other gases, unless a certified kit is used. INSTALLER: Leave this manual with the appliance. ' Aftermarket Completion of sale.not for purpose of resale,from CONSUMER: Retain this manual for the manufacturer. future reference. 20306750 12/14 Rev. 1 INSTALLATION INFORMATION Designer Series Direct Vent Gas Fireplace PRODUCT SPECIFICATIONS GAS PRESSURES • This appliance has been certified for use with either Natural Propane (LP) natural or propane gas. See appropriate data plates. Inlet Minimum 4.5" w.c. 11.0" w.c. • This appliance is not for use with solid fuels. Inlet Maximum 10.5" w.c. 13.0"w.c. • The appliance is approved for bedroom or bedsitting Manifold Pressure 3.5"w.c. 10.0" w.c. room installations. • The appliance must be installed in accordance with local codes if any. If none exist use the current installation GAS SPECIFICATIONS & ORIFICE SIZE code.ANSI Z223.1/NFPA 54 in the USA. CSA B149 in Canada. Max. Min. • This appliance is mobile home approved. Input Input Orifice • The appliance must be properly connected to a venting Model Fuel Controls BTUIh BTU/h Size system. PFLDVNS Nat. SCS 37.000 25.000 #31 • The appliance is not approved for closet or recessed PFLDVPS LP SCS 35,000 27.000 1.8 mm installations. STLDVNS Nat. SCS 37.000 25,000 #31 STLDVPS LP SCS 35.000 27,000 1.8 mm CLLDVNS Nat. SCS 37,000 25,000 #31 HIGH ELEVATIONS CLLDVPS LP SCS 35.000 27,000 1.8 mm Input ratings are shown in BTU per hour and are certified CRLDVNS Nat. SCS 37.000 25,000 #31 without deration for elevations up to 4,500 feet (1,370 CRLDVPS LP SCS 35.000 27,000 1.8 mm m) above sea level. For elevations above 4.500 feet (1.370 m) in USA. installations must be in accordance with the current ANSI Z223.1/NFPA 54 and/or local codes having juris- diction. In Canada. please consult provincial and/or local authori- ties having jurisdiction for installations at elevations above 4.500 feet (1,370 m). a - • FP2815 Command Control Box Gas Valve Center Figure 1 - Designer Controls 20306750 5 Designer Series Direct Vent Gas Fireplace INSTALLATION INFORMATION FIREPLACE DIMENSIONS Centerline of Flue Outlet 11'4" . (305 mm) ~(298 mm) --A 1 L 16,........1 477/8' II MI (1216 mm) q B 34" 417/s" 253/4" i , 359/18'(903 mm) d 1_(864 mm) (1064 mm) (654 mm) E 28Y" • (718 mm) 377/s" E (962 mm) __, 1V4 32 mm) 1 1 :— 111 0 r r r 1 i mii i I 1 1 I 1 s =i ii im 1 IN H331/16"(840 mm) I 23"(584 mm) 33/16" ---► - 389/16"(979 mm) --77/8" (81 mm) (200 mm) 499/16"(1259 mm) - FP2851 Figure 2- STLDV(See-thru) Fireplace Dimensions Centerline of Flue Outlet .., - (305 12"x(298 mm) pp L1 0 1� IZ■ I !1 77/8" II 471" (200'm (1216 mm).� - -- , - --�� 41 7/8" . 21"(533 mm) 253/4 359/18"(903 mm) (1064 mm) (654 mm) 281/4" e 34" (718 mm) 1 i 377/9" (864 mm) (962 mm) 1Y4" 11/4'___• -- r �,32 mm (32 mm) •1 ` / r em .i . m. . L...„1 11/9" 23"(584 mm)—► (29 mm) I-18Yz"(470 mm)� 51/8„ I 33 hs'(840 mm) - (130 mm), , -4,-273/4"(705 mm) 33/4"--- 24"(610 mm) 389/16"(979 mm) 7�' (95 mm) - (200 mm) 273/4"(705mm)� 463/8"(1178 mm) Figure 3- FP2852 CLLDV/CRLDV(Corner)Fireplace Dimensions 6 20306750 Designer Series Direct Vent Gas Fireplace INSTALLATION INFORMATION STLDV FRAMING 23" (1/2" Drywall)-' or Adjustable to iff 223/4" (5/8" Drywall) pii Remove and Insulationbox for To pi, Vent Configurations Noncombustible W; ��Material \11111 \I 4 1 (1024" (178 ' '• Min m) Min m) 1 1 ra trfr \ Fold Outer Tabs Mih.m)~' and Nail to Framing '4 ,� .. ,.. 483/,6" Members • (1224 mm) NOTE: Glass cen- terline is off center 011 ill from rought framing dimensions. ..--22/7/764It (S?6 kil mm) \ �k 507 , 2)34„ 6 (1 (695 If using 5/8"drywall,remove 2j2 Mn)) mnl) framing tabs and re-install Figure 5- �. on 2nd set of holes STLDV(See-thru)Framing positioned slightly inwards If using 5/8"drywall.remove noncombustible supports, rotate 180°and reinstall to achieve 5/8"depth The fireplace must be secured to the floor and/or to framing W The area above and on the sides of the studs as shown in Figure 5 . Use four(4) wood screws or H fireplace must be a noncombustible material. masonry!concrete screws to secure fireplace to the floor. 0 p Use four(4)screws to attach fireplace to framing.The side Z Figures 5, 6, 7 brackets or nailing flanges are designed to accommodate two wall boards thicknesses, 1/2" or 5/8". W Never install combustible materials over O front face of fireplace. Z 8 20306750 INSTALLATION INFORMATION Designer Series Direct Vent Gas Fireplace CRLDV/CLLDV FRAMING 461/8" (1172 mm) (1/2" Drywall) 271/2"(699 mm) or (1/2" Drywall) 46" (1168 mm) or (5/8" Drywall) Remove box and 273/8' (696 mm) ii Insulation for Top (5/8" Drywall) ✓ NIVent Configurations '• \II- 1. Noncombustible Material i ? \ Jr" 483/,8" 1 (1/4 iii 1 S NI (1224 m Min m) ` ifoi) ., 21 .._ /..* 2 P If using 5/8"drywall. 08 gym)'remove framing �tabs and re-install \ ( te.on 2nd set of holespositioned slightly , inwards II% IFold Outer Tabs I� and Nail to Framing �� Members If using 5/8"drywall,remove on 2nd tabst and sre-install on 2nd set of holes positioned slightly inwards l • (118 If using 5/8"drywall,remove �%"(� �6'g noncombustible supports.rotate �8 nl 180°and reinstall to achieve m) �� 5/8"depth Figure 6- CRLDV and CLLDV(Corner) Framing The fireplace must be secured to the floor and/or to framing w The area above and on the sides of the studs as shown in Figure 6 . Use four(4) wood screws or H fireplace must be a noncombustible material. masonry/concrete screws to secure fireplace to the floor. Q p Use four(4)screws to attach fireplace to framing.The side Z Figures 5, 6, 7 brackets or nailing flanges are designed to accommodate two wall boards thicknesses, 1/2" or 5/8". 1— Never install combustible materials over O front face of fireplace. Z 9 20306750 INSTALLATION INFORMATION Designer Series Direct Vent Gas Fireplace CLEARANCES TO COMBUSTIBLES Follow these instructions carefully to 12 ensure safe installation. Failure to follow instructions exactly can create a fire6" Noncombustible hazard. 1 Material to Top of 16" Standoffs Z The appliance cannot be installed on a ) E carpet, tile or other combustible material 12° 12'i2„ 11 < other than wood flooring. If installed on t - carpet or vinyl flooring, the appliance ::" _ O _ shall be installed on a metal, wood or noncombustible material panel extending + - - full width and depth of the appliance. Top of Fireplace / e Opening e e I . Ge��� FP2817 Side View Combustible Mantel Spacer 12" 72" (305 mm) (1829 mm) Max.Depth Stud Min. .did\ 16" Combustible (406 mm) 1Material Area Min. FP2818 ��11����� Top View — 4T.-11\ 3 " i 5.. 45° I Side of Fireplace J 6., Opening 6" (152 mm) Figure 10- Min. \ Mantel Clearance Figure 9- FP2544 Ceiling and Side Wall Clearances MANTEL CLEARANCES NOTE: The combustible area above the facing must not protrude more than 1/2" from the facing. If it does, 0 Never obstruct or modify the air inlet or it is considered a mantel and must meet the mantel Z outlet grilles (louvers). This may create requirements listed in this manual. IX a fire hazard. Q NOTE: Vermont Castings Group Model BPWC500 Mantel is designed to comply with all mantel temperature requirements. 20306750 13