Vail Fire&Emergency Services
BatteryCalculations 05/02/16
ELK Ml SYMBOL DEVICE MANUFACTURER/PART# MOUNTING
Standby FACP ELK M1 GOLD
Number of Current Total Current Fire Alarm Control Panel w/10AH Batteries Mount on wall in manufacturer backbox
Device Type Devices (Amps) (Amps) —
Main FACP CPU 1 X 0.032 = 0.032 KP
Keypad 1 X 0.04 = 0.04 LCD Keypad/Annunciator ELK M1 LCD Mount on wall in manufacturer backbox
i3 Smoke Detector with Sounder 7 X' 0.00005 = 0.00035 -
14 COSMO Smoke/CO Detector w/Sounder 6 X' 0.00005 = 0.0003
COSMO Interface Module 3 X 0.022 = 0.066 O Combination Smoke &
Heat Detector w/Sounder System Sensor i3 series 4WTA—B 4" square box
SUM COLUMN FOR STANDBY LOAD 0.13865 = AMPS
Alarm LoadCombination Smoke and
Number of Current Total Current ®co CO Detector w/Sounder System Sensor i4 series COSMO-4W 4" square box
Device Type Devices (Amps) (Amps)
Main FACP CPU 1 X 0.032 = 0.032 O System Sensor 5601 P
Keypad 1 X' 0.04 = 0.04 Heat Detector w/4193SN Addressable module 4" square box
i3 Smoke Detector with Sounder 7 X 0.025 '= 0.175 a
i4 COSMO Smoke/CO Detector w/Sounder 6 X' 0.04 = 0.24 H
Cosmo Interface Module COSMOD4W
COSMO Interface Module 3 X 0.034 0.102 E
0
Outside Horn/Strobe 1 X' 0.212 = 0.212 cn
SUM COLUMN FOR ALARM LOAD 0.801 = AMPS o
Standby Load Required Standby Time in Hours KB Knox Box oz
Current (Amps)
0.13865 X 24 = 3.33 0 w
,0, Horn/Strobe, weatherproof System Sensor P2RK Weatherproof backbox i
Alarm Load Required Alarm Time in Hours
Current (Amps) (15 MINUTES)
0.801 X 0.25 = 0.20
Add Standby and Alarm Load for Required
Ampere Hour Battery 3.53 GENERAL NOTES: w
Multiply by the Derating Factor of 1.2 Q
Total Ampere Hours Required = 4.23 1 . ALL EQUIPMENT IS TO BE INSTALLED AND TESTED IN ACCORDANCE WITH MANUFACTURER STANDARDS, 0
Minimum Battery Size Provided: 1OAH FIRE DEPARTMENT REQUIREMENTS AND NFPA 72.
2. REFER TO MANUFACTURERS DATA SHEETS AND INSTALLATION INSTRUCTIONS FOR FURTHER
INFORMATION REGARDING PRODUCT INSTALLATION, WIRING DIAGRAMS, PROGRAMMING AND DEVICE z
ZONE LIST OPERATION.
N (—
LI
ZONE # DESCRIPTION O zz
1 SPRINKLER WATERFLOW cin
•
2 SPRINKLER TAMPER cY)o <
3 LOWER LEVEL CO DETECTION U
4 LOWER LEVEL SMOKE DETECTION r .0,000 I/.' :›1 V/ I
I o
5 MAIN LEVEL CO DETECTION 3 avo_.E'I r`
6 MAIN LEVEL SMOKE DETECTION a +��161Yr ' F
7 UPPER LEVEL CO DETECTION r r i .$;my: 43
8 UPPER LEVEL SMOKE DETECTION ! V I 35233i I,- %°I
o z
`
9 GARAGE HEAT DETECTOR . �•*�;P ',i ;' �' �• � _
10 SYSTEM TROUBLE a • R' �;' ' cn
Approved for install. No heat detection required in garage. -..:V.r ,..? 0 c
• V)
C
(1)
w
C
O
}
LI.
U
D = 4—WIRE DATA/POWER, 4—#16AWG (2 PAIR) N
(1)
X = 2—WIRE DATA, 2—#16AWG EOL EOL 4ro
N = 2—WIRE SOUNDER CIRCUIT, 2—#18AWG CO
o0
Z = 2—WIRE DATA CIRCUIT, 2—#16AWG D D 0 - O
C
KP = KEYPAD CIRCUITING, 4—#18AWG
RISER NOTES: 5:-)CO ? 1:: r0 0
N O
, - U
1 . REFER TO VISTA INSTALLATION MANUAL FOR D D
MORE INFORMATION. O 0
2. WIRE SIZE MAY BE VARIED, PROVIDED IT MEETS L,N L,N MMANUFACTURERS SPECIFICATIONS. LI r� O E
3. VERIFY WIRING OF SYSTEM SENSOR COSMOD4W (TYP) (TYP) 0_ u`
PRIOR TO INSTALLATION. WIRING DIAGRAM IS Z
INCLUDED SUBMITTAL BOOKS. O
120VAC DEDICATED POWER ELK FIRE ALARM Z
CONTROL PANEL FLOW SWITCH
Z TAMPER SWITCH
TELEPHONE LINE — FIRE
TELEPHONE LINE — SECURITYN uWP
BELL ,�, EOLR
OUTPUT
DATA/COM KP I I I
S E AG �AfV OUTPUT (KEYPAD [KEYPAD L.U.
0
0
Q C
W
PROJECT I \ FOVATIO\ : 0 Q
HUGHES RESIDE\ CE 0 =
SEQUENCE OF z < o VAIL, COLORADO 0 =
OPEATIO\S: (.7) 4 z Z 6z X FRE ALARV SYSTEV J
w Z O O 0 O
O Q Q
o z j N > N m N AHJ: VAIL FIRE & EMERGENCY SERVICES o
aD oz o D Z o APPLICABLE CODES: 2013 NFPA 72, 2015 IFC, 2015 IBC W
= c� 0 O () O 0 p w m
0 21— Q E N E I— E I- m USE: SINGLE FAMILY HOME Z 1— W
W Cl)
UJ 1- ° o o o 1 w FIRE ALARM SYSTEM FOR SINGLE FAMILY HOME. SYSTEM INCLUDES A NEW Z
DEVICE Q QD V) V)z . z . Q0 Q\
DESCRIPTION Q Q Q COMBO SECURITY/FIRE ALARM CONTROL PANEL. SMOKE DETECTORS WILL 0) 0
o H o I- OCO
Q Q Q o Q 2BE INSTALLED IN SLEEPING ROOMS AND COMBINATION SMOKE/CARBON W = 2 0
SMOKE DETECTOR X X X MONOXIDE DETECTORS WILL BE INSTALLED WITHIN 15' OF FIREPLACES Q W
AND AREAS OUTSIDE OF SLEEPING ROOMS. DETECTORS HAVE INTEGRAL CO W Q J Z
X X X SOUNDERS. A KNOX BOX WILL BE MOUNTED ON THE OUTSIDE OF THE _ F- <
HEAT DETECTOR HOME. THE SPRINKLER SYSTEM WILL BE MONITORED, SMOKE DETECTORS oCL
W
X X X ARE RESTORABLE AT THE KEYPAD. D 0, W
CARBON MONOXIDE DETECTOR
I = � LL �
SPRINKLER WATERFLOW SWITCH X X X X FIRE PROTECTION ENGINEER: SHEET DESCRIPTION:
DEBORAH SHANER, P.E., SHANER LIFE SAFETY COVER SHEET
SPRINKLER TAMPER SWITCH X X
PO BOX 1073, FRISCO, CO 80443
PHONE: 970-409-9082 DRAWN BY: DATE:
POWER LOSS, OPEN CIRCUIT, GROUND FAULT X X FAX: 970-797- 1898 D LS 4/12/16
SHEET#:
FA-0 .00