Loading...
HomeMy WebLinkAboutF16-0068 Hydraulic and Equipment.pdf O t/i Western States Fire Protection Co. pozotezeie, Iicee4 aea pow/zero 7026 South Tucson Way Centennial, CO 80112 (303) 792-0022 Fax (303) 792-9049 Fire Protection System Hydraulic Calculations and Equipment Village Inn Plaza Unit 501 Fire Sprinkler System 68 E. Meadow Dr. Vail, Colorado 81657 Prepared by: Zack Hinson Project Manager Phone: (303)792-0022 Cell: (720) 346-3113 Fax: (303)792-9049 Email: Zachary.hinson@wsfp.us } Hydraulic Summary Job Number:CS2911 Re.ort Descri.tion:16X16 Job Job Number Design Engineer CS2911 Zack Hinson Job Name: State Certification/License Number Village Inn Plaza Unit#501 032 Address l Mat 68 East Meadow Dr. Vail Fire Department Address 2 Job Site/Building 68 East Meadows Dr. Address 3 Drawing Name Existing System Remote Area(s) Most Demanding Sprinkler Data Occupancy Job Suffix 4.9 K-Factor 24.0 at 24.0 16X16 Hose Allowance At Source Density Area of Application 0.0 0.10gpm/ft2 464.00ft2(Actual 605.83ft2) Additional Hose Supplies Number Of Sprinklers Calculated Coverage Per Sprinkler Node Flow(agm) 4 256.00ft2 AutoPeak Results:Pressure For Remote Area(s)Adjacent To Most Remote Area Total Hose Streams 0.0 System Flow Demand Total Water Required(Including Hose Allowance) 91.3 91.3 Maximum Pressure Unbalance In Loops 0.0 Maximum Velocity Above Ground 22.37 between nodes 6 and 4 Maximum Velocity Under Ground Volume capacity of Wet Pipes Volume capacity of Dry Pipes 471.9gal Supplies Hose Flow Static Residual Flow Available Total Demand Required Safety Margin Node Name (gpm) (psi) (psi) @ (gpm) (psi) @ (gpm) (psi) (psi) 1 Water Supply 150.0 15.1 I 721.0 147.1 I 91.3 115.6 31.4 Contractors 1111 Contractor Number Contact Name Contact Title Zack Hinson PM Name of Contractor. Phone Extension Western States Fire Protection 720-346-3133 Address l FAX 274 Center Drive Address 2 E-mail Glenwood Springs,CO.81601 zachary.hinson@wsfp.us Address 3 Web-Site ©M.E.P.CAD,Inc. AutoSPRINK®12 v12.0.59.0 11/7/2016 1:57:35PM Page 1 Hydraulic Graph Job Number:CS2911 Report Descri.tion:16X16 Water Supply at Node 1 200 180 160 Static Pressure 150.0 140 120 X91.3 @ 115.6 .N EC 100 m 80 System demand curve 60 40 20 — 721.0 @ 15.1 0 IOILI111111I 111 111 1 I I I 11 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 111111111 1 1 1 1 1 1 1 1 1 111111111 111111111 0150 300 450 600 750 900 1050 1200 1350 1500 Water flow,gpm Hydraulic Graph Water Supply at Node 1 Static:Pressure 150.0 Residual:Pressure 15.1 @ 721.0 Available Pressure at Time of Test 147.1 @ 91.3 system Dsmaaa 115.6 @ 91.3 System Demand(Including Hose Allowance at source) 115.6 @ 91.3 ML ©M.E.P.CAD,Inc. M AutoSPRINK®12 v12.0.59.0 11/7/2016 1:57:36PM Page 2 iii -Summary Of Outflowing Devices I Job Number:CS2911 Report Description:16X16 Actual Flow Minimum Flow K-Factor Pressure Device (qpm) (qpm) (K) (psi) Sprinkler 101 22.1 20.0 4.9 20.4 4 Sprinkler 102 24.0 24.0 4.9 24.0 Sprinkler 103 22.8 20.0 4.9 21.7 Sprinkler 104 22.3 20.0 4.9 20.7 * Most Demanding Sprinkler Data E,©M.E.P.CAD,Inc. In AutoSPRINK®12 v12.0.59.0 11/7/2016 1:57:37PM Page 3 Job S2911 go ydraulic Analysis Report Description:C 16X16 Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq.Length Summary Upstream Total Length OF Route 1 DR 1.055 24.0 8.81 150 0.117360 11'-71,4 Pf 2.1 102 18'-0 24.0 4.9 24.0 Sprinkler, 6'-0 Pe -0.4 10 19'-0 25.6 2E(2'-0),T(2'-0) 17'-7Yz Pv AO 1.291 91.3 22.37 150 0.519701 12'-5'% Pf 8.0 10 19'-0 67.3 25.6 Flow(q)from Route 2 3'-0 Pe 11 19'-0 33.6 T(3'-0) 15'-5'% Pv FR 1.291 91.3 22.37 150 0.519701 9'-0 Pf 6.2 11 19'-0 33.6 3'-0 Pe 3.9 4 10'-0 43.8 T(3'-0) 12'-0 Pv BL 1.291 91.3 22.37 150 0.519701 38'-7% Pf 25.3 4 10'-0 43.8 10'-0 Pe 6 10'-0 69.0 3T(3'-0),cplg(1'-(1) 48'-7% Pv BL 2.067 91.3 8.73 120 0.079349 22'-9 Pf 3.8 6 10'-0 69.0 25'-0 Pe 5 10'-0 72.8 3E(5'-0),T(10'-0) 47'-9 Pv FM 4.026 91.3 2.30 120 0.003087 266-5% Pf 11.6 5 10'-0 72.8 884'-4%z Pe 29.7 3 -58'-6 114.1 55E(10'-0),14T(20'-0), 1150'-10 Pv 8fE(6'-9'%),BFP(-8.0) BL 6.065 91.3 1.01 120 0.000420 9'-8'% Pf 6.0 3 -58'-6 114.1 30'-0 Pe 1.3 2 -61'-6 121.4 PRV(-6.0),3fE(10'-0) 39'-8'% Pv BL 6.280 91.3 0.95 140 0.000266 161'-6 Pf 0.1 2 -61'-6 121.4 179'-8 Pe -5.9 1 -48'-0 115.6 6E(22'-1),T(47'-3%),S 341'-2 Pv 0.0 Hose Allowance At Source 1 91.3 - Route 2 DR 1.055 22.1 8.13 150 0.101138 8'-0 Pf 1.2 101 18'-0 22.1 4.9 20.4 Sprinkler, 4'-0 Pe -0.4 8 19'-0 21.2 E(2'-0),T(2'-0) 12'-0 Pv AO 1.291 44.4 10.89 150 0.137294 6'-3 Pf 0.9 8 19'-0 22.3 21.2 Flow(q)from Route 3 Pe 7 19'-0 22.1 6'-3 Pv AO 1.291 67.3 16.49 150 0.295537 9'-0% Pf 3.6 7 19'-0 22.8 22.1 Flow(q)from Route 4 3'-0 Pe 10 19'-0 25.6 T(3'-0) 12'-0% Pv Route 3 DR 1.055 22.3 8.18 150 0.102450 3'-6% Pf 0.8 104 18'-0 22.3 4.9 20.7 Sprinkler, 4'-0 Pe -0.4 9 19'-0 21.1 2E(2'-0) 7'-6% Pv AO 1.291 22.3 5.47 150 0.038330 4'-1 Pf 0.2 9 19'-0 21.1 Pe 8 19'-0 21.2 4'-1 Pv Route 4 DR 1.055 22.8 8.38 150 0.106931 3'-61/2 Pf 0.8 103 18'-0 22.8 4.9 21.7 Sprinkler, 4'-0 Pe -0.4 7 19'-0 22.1 E(2'-0),T(2'-0) 7-6% Pv Equivalent Pipe Lengths of Valves and Fittings(C=120 only) a Value Multiplier Actual Inside Diameter 487 Value Of C 100 130 140 150 Schedule 40 Steel Pipe Inside Diameter ) =Factor Multiplying Factor 0.713 1.16 1.33 1.51 ©M.E.P.CAD,Inc. ,111 AutoSPRINK®12 v12.0.59.0 11/7/2016 1:57:39PM Page 4 Job S2911 111 ydraulic Analysis Report Description:C 16X16 Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq.Length Summary Upstream Total Length Pipe Type Legend 1 Units Legend IF r Fittings Legend AO Arm-Over Diameter Inch ALV Alarm Valve BL Branch Line Elevation Foot AngV Angle Valve CM Cross Main Flow gpm b Bushing DN Drain Discharge gpm BaIV Ball Valve DR Drop Velocity fps BFP Backflow Preventer DY Dynamic Pressure psi BV Butterfly Valve FM Feed Main Length Foot C Cross Flow Turn 90° FR Feed Riser Friction Loss psi/Foot cplg Coupling MS Miscellaneous HWC Hazen-Williams Constant Cr Cross Run OR Outrigger Pt Total pressure at a point in a pipe CV Check Valve RN Riser Nipple Pn Normal pressure at a point in a pipe DeIV Deluge Valve SP Sprig Pf Pressure loss due to friction between points DPV Dry Pipe Valve ST Stand Pipe E 90°Elbow Pe Pressure due to elevation difference between indicated points UG Underground Pv Velocity pressure at a point in a pipe EE 45°Elbow Eel 11W Elbow Ee2 221/ Elbow Flow Device fd Flex Drop FDC Fire Department Connection fE 90°FireLock(TM)Elbow fEE 45°FireLock(TM)Elbow flg Flange FN Floating Node fT FireLock(TM)Tee g Gauge GIoV Globe Valve GV Gate Valve Ho Hose Hose Hose HV Hose Valve Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PRV Pressure Reducing Valve PrV Pressure Relief Valve red Reducer/Adapter S Supply sCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 90° Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap ©M.E.P.CAD,Inc. ,111 AutoSPRINK®12 v12.0.59.0 11/7/2016 1:57:39PM Page 5 Bulletin 135 Rev. M CIJ® Model Fl Residential Sprinklers for CO Design Density of .05 gpmfft2 Model Fl Res Sprinklers engineered for the lowest flows to meet the minimum design density of.05 gpmfft2 Types: 1. Fl Res 30 Pendent . 2. Fl Res 30 Recessed Pendent/F2 3. Fl Res 30 Recessed Pendent/FP is fetid r r� 4. Fl Res 49 Pendent r; ' 5. Fl Res 49 Recessed Pendent/F1 _ - u= `{ , a 6. Fl Res 49 Recessed Pendent/FP 7. Fl Res 58 Pendent Fl Res 30, 49, 58&76 Fl Res 30, 49, 58&76 8. Fl Res 58 Recessed Pendent/F1 Recessed Pendent/Fl Recessed Pendent/FP Fl Res 58 HSWX 9. Fl Res 58 Recessed Pendent/FP 10. Fl Res 76 Pendent 11. Fl Res 76 Recessed Pendent/F1 12. Fl Res 76 Recessed Pendent/FP 13. Fl Res 30 CCP Pendent , - a. -1. 'i!1) 14. Fl Res 49 CCP Pendent \ v/ :+' 15. Fl Res 58 CCP Pendent 16. Fl Res 76 CCP Pendent 17. Fl Res 44 HSW Fl Res 30, 49, 58& 76 Fl Res 44&58 Fl Res 44 SWC 18. Fl Res 44 Recessed HSW/F2 CCP Pendent Recessed HSW/F2 19. Fl Res 58 HSW 20. Fl Res 58 HSWX Horizontal Sidewall sprinklers(Figs. 5, 6&7)are equally attrac- 21. KRes58 HSWX tive when above ceiling piping cannot be used. 22. Fl Res 58 HSW Recessed HSW/F2 The 3mm glass-bulb pendent sprinklers permit the efficient use 23. Fl Res 44 SWC of residential water supplies for sprinkler coverage in residential Listings & Approvals fire protection design. The low flow Fl Res sprinklers are specially engineered for fast 1. Listed by Underwriters Laboratories Inc. and thermal response to meet the sensitive fire protection applica- UL Certified for Canada (cULus) tion needs of the latest residential market standards (UL 1626 Standard). Upon fire conditions, rising heat causes a sprinkler's Sprinklers for .10 Density: Refer to Bulletin 176 heat-sensitive element,glass bulb or link to actuate,releasing the UL Listing Category waterway for water flow onto the deflector,evenly distributing the Residential Automatic Sprinkler discharged water to control a fire. UL Guide Number Technical Data: VKKW • Thermal Sensor: Soldered Element (Link) or Nominal 3mm glass-bulb Patents • Sprinkler Frame : Brass Casting US Patent No. 6,516,893 applies to the Model Fl Res 49 • Sprinklers' Pressure Rating : 175 psi & 58 Pendent Sprinklers Factory Hydrostatically Tested to 500 psi US Patent No. 7,353,882 applies to Model Fl Res 44&58 • Thread Size: 1/2" NPT(R'/2) HSW Sprinklers • K-Factor: 3.0(43.2)(Actual)-Fl Res 30 Pendent Sprinkler US Patent No. 7,784,555 applies to Model Fl Res 44 SWC 4.9(70.6)(Actual) Fl Res 49 Pendent Sprinkler Sprinklers 5.8 (83.5)(Actual)-Fl Res 58 Pendent&HSW Sprinkler Product Description 7.6(109)(Actual)-Fl Res 76 Pendent Sprinkler Model Fl Res Pendent sprinklers (Figs. 1, 2, 3, &4) are fast 4.4(63)(Actual)-Fl Res 44 HSW Sprinkler response sprinklers combining excellent durability,high sensitiv- • Density: Minimum 0.05 gpm/ft2 ity glass-bulb and low profile decorative design. The Fl Res Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Application Model Fl Res Sprinklers are used for Residential Fire Pro- the only recessed escutcheons to be used with Model Fl Res tection according to UL 1626 Standard*. For ceiling types: sprinklers. Use of any other recessed escutcheon will void all Smooth Flat Horizontal,or beamed,or sloped, in accordance approvals and warranties. For installing Model Fl Res Pen- with NFPA 13D, 13R,or 13 2013 editions. Be sure that orifice dent sprinklers use only the Model D sprinkler Wrench; for size,temperature rating,deflector style and sprinkler type are installing Models Fl Res Recessed Pendent, CCP & SWC in accordance with the latest published standards of The Na- sprinklers use only the Model GFR2 sprinkler wrench; for in- tional Fire Protection Association or the approving authority stalling Model Fl Res Recessed HSW sprinklers use only the having jurisdiction. Model GFR2 Sprinkler Wrench. Use of wrenches other than Installation those specified may damage these sprinklers. Install Fl Res Models Fl Res sprinklers are to be installed as shown. 44 with a ceiling to deflector distance of 4" 12". Flow arrow Model F1, F2 and FP Escutcheons, illustrated herewith, are on deflector must point away from near wall and "Top" mark - Model must face ceiling. Escutcheon*, Fl or F2, Data: Adjustment "A" Face of fitting to ceiling B Type Inch(mm) Inch(mm) Inch(mm) Deflector Distance below bottom of beam Inch(mm) F1 3/4(19.0) Min.Recessed=15/8(41.3) 3/8(9.5) 13/4(44.4) Max.Recessed=7/8(22.2) 11/8(28.6) 1 (25.4) F2 /2(12.7) Min.Recessed=15/8(41.3) 3/6(9.5) 13/4(44.4) Max.Recessed=11/8(28.6) '/6(22.2) 11/4(31.7) *Note:Escutcheons F1 or F2 may be used with Model F1 Res 49,58&76 Recessed Pendent Sprinkler • Model Fl Res 30 Recessed Pendent/F2 • Model Fl Res 30, 49, 58 &76 Pendent • Model Fl Res 49, 58 &76 Recessed Pendent/Fl f , .r �J , • F1 escutcheon, 3/4" (19mm) adjustment �— 2 1/4"HOLE DIA. r : [57.2mm] 1 15/16"DIA. [49.2mm] TURN COLLAR UNTIL I rt 1"X 1/2"REDUCER TIGHT AGAINST SPRINKLER 1 FACE OF FITTING TO .=--- --1 WRENCH BOSS. r 1 CEILING DIMENSION.. _ 3/8"-1 1/8"(F1 ESCUTCHEON) /, ' =i 3/8"-7/8"(F2 ESCUTCHEON) II ®�wi IIp �� =KJ. III!'111!1_ ..I ADJUSTMENT El!l-Willi 1%//. Ii'u NIli } I�i 1 'i l ] 1 1 Vit _nit �il AN iHi, [.31. 78//V 1 1 ••.•�� _ .... 2 27/32"DIA. I3sFt;o.3 1 +asFroie [72.2mm] Fig. 1 Fig. 2 Technical Data: F1 Res 30 Pendent and Recessed Pendent (SIN R3511) Thread Nominal Orifice Max.Pressure Sprinkler Temp.Rating Max.Ambient Temp. Actual K Sprinkler Length Size Inch(mml psi(bar) PF PC PF PC Factor Inch(mm) /(RN�T 8 21/64"(8.2) 175(12) 175 155 7g 100 38 3.0(43.2) 2.25(57) Ordinary Temp.Rating Intermediate Temp.Rating Max.Coverage area Max. Minimum g (155PF/68PC) (175PF/79°C) Top of Deflector to Ceiling Ft x Ft(m x m) Spacing Flow Pressure Flow Pressure Inch(mm) Spacing Ft(m) GPM(L/min) PSI(bar) GPM(L/min) PSI(bar) Ft(m) 12 x 12(3,6 x 3,6) 12(3,6) 8(30,3) 7.0(0,48) 8(30,3) 7.0(0,48) Smooth Ceilings 11/4 to 4(31.7 to 102) using F2 escutcheon. 14 x 14(4,3 x 4,3) 14(4,3) 10(37,8) 11 (0,76) 10(37,8) 11 (0,76) Beamed Ceilings per NFPA 13D, 13R 8(2,4) or 13 installed in beams 11/4 to 13/4 16 x 16(4,9 x 4,9) 16(4,9) 13(49) 18.8(1,3) 13(49) 18.8(1,3) (31.7 to 44.4)using F2 escutcheon For Ceiling types refer to NFPA 13, 13R or 13D 2. Technical Data: F1 Res 49 Pendent and Recessed Pendent(SIN R3516) Thread Nominal Orifice Max. Sprinkler Max. Actual Sprinkler Size Inch(mm) Pressure Temp.Rating Ambient Temp. K Length psi(bar) PF rC 1°F wC Factor Inch(mm) /z"NPT7/16"(11) 175(12) 155 68 100 38 4.9(70.6) 2.25(57) (R1/2) 175 79 150 66 Ordinary Temp.Rating Intermediate Temp.Rating Top of Deflector Minimum Max.Coverage area Max.Spacing (155PF/681C) (1751F/791C) Ft x Ft(m x m) Ft(m) Flow Pressure Flow Pressure to Ceiling Spacing GPM(L/min) PSI(bar) GPM(L/min) PSI(bar) Inch(mm) Ft(m) 12 x 12(3,6 x 3,6) 12(3,6) 13(49) 7.0(0,48) 13(49) 7.0(0,48) Smooth Ceilings 11/4 to 4(31.7 to 102)using F2 escutcheon. 14 x 14(4,3 x 4,3) 14(4,3) 13(49) 7.0(0,48) 13(49) 7.0(0,48) 1 to 4(25.4 to 102)using F1 escutcheon. 16 x 16(4,9 x 4,9) 16(4,9) 13(49) 7.0(0,48) 13(49) 7.0(0,48) Beamed Ceilings per NFPA 8(2,4) 13D, 13R or 13 installed in 18 x 18(5,5 x 5,5) 18(5,5) 17(64,3) 12(0,83) 17(64,3) 12(0,83) beams 11/4 to 13/4 (31.7 to 44.4)using F2 escutcheon, 1 20 x 20(6,1 x 6,1) 20(6,1) 20(75,7) 16.7(1,14) 20(75,7) 16,7(1,14) to 13/4(25.4 to 44.4)using F1 escutcheon For Ceiling types refer to NFPA 13, 13R or 13D Ordinary Temp.Rating Intermediate Temp.Rating Top of Deflector Minimum Max.Coverage area Max.Spacing (1551F/68WC) (1751F/791C) Ft x Ft(m x m) Ft(m) Flow Pressure Flow Pressure to Ceiling Spacing GPM(L/min) PSI(bar) GPM(L/min) PSI(bar) Inch(mm) Ft(m) 12 x 12(3,6 x 3,6) 12(3,6) 15(57) 9.4(0,65) 15(57) 9.4(0,65) Smooth Ceilings 4 to 8(100 to 203)using F2 escutcheon. 14 x 14(4,3 x 4,3) 14(4,3) 16(60,5) 10.6(0,73) 16(60,5) 10.6(0,73) 4 to 8(100 to 203)using F1 escutcheon. 16 x 16(4,9 x 4,9) 16(4,9) 17(64,3) 12.0(0,83) 17(64,3) 12.0(0,83) Beamed Ceilings per NFPA 13D, 8(2,4) 13R or 13 installed in beams 18 x 18(5,5 x 5,5) 18(5,5) 19(72) 15.0(1,0) 19(72) 15.0(1,0) 41/4 to 8(108 to 203)using F2 escutcheon,4 to 8(100 to 203) 20 x 20(6,1 x 6,1) 20(6,1) 22(83,2) 20.2(1,4) 22(83,2) 20.2(1,4) using F1 escutcheon Technical Data: F1 Res 58 Pendent and Recessed Pendent(SIN R3513) Thread Nominal Orifice Max. Sprinkler Max. Actual Sprinkler Pressure Temp.Rating Ambient Temp. Length Size Inch(mm) psi(bar) WF PC PF pC K Factor Inch(mm) /z"NPT1/"(13) 175(12) 155 68 100 38 5.8(83.5) 2.25(57) (R1/) 175 79 150 66 Ordinary Temp.Rating Intermediate Temp.Rating Top of Deflector Minimum Max.Coverage area Max.Spacing (155rF/68WC) (175"F7791C) Ft x Ft(m x m) Ft(m) Flow Pressure Flow Pressure to Ceiling Spacing GPM(L/min) PSI(bar) GPM(L/min) PSI(bar) Inch(mm) Ft(m) 12 x 12(3,6 x 3,6) 12(3,6) 16(61) 7.6(0,53) 16(61) 7.6(0,53) Smooth Ceilings 11/4 to 4(31.7 to 102)using F2 escutcheon. 14 x 14(4,3 x 4,3) 14(4,3) 16(61) 7.6(0,53) 16(61) 7.6(0,53) 1 to 4(25.4 to 102)using F1 escutcheon. 16 x 16(4,9 x 4,9) 16(4,9) 16(61) 7.6(0,53) 16(61) 7.6(0,53) Beamed Ceilings per NFPA 13D, 8(2,4) 13R or 13 installed in beams 18 x 18(5,5 x 5,5) 18(5,5) 19(72) 10.8(0,75) 19(72) 10.8(0,75) 11/4 to 13/4 (31.7 to 44.4)using F2 escutcheon, 1 to 13/4(25.4 to 20 x 20(6,1 x 6,1) 20(6,1) 22(83,3) 14.4(1,0) 22(83,3) 14.4(1,0) 44.4)using F1 escutcheon For Ceiling types refer to NFPA 13, 13R or 13D 3. Technical Data: Fl Res 76 Pendent and Recessed Pendent(SIN R7618) Thread Nominal Orifice Max. Sprinkler Max. K Sprinkler Pressure Temp.Rating Ambient Temp. Length Size Inch(mm) psi(bar) PF PC PF PC Factor Inch(mm) 3/4NPT 17/32"(13.5) 175(12) 155 68 100 38 7.6(109) 2.25(57) (R3/4) 175 79 150 66 Ordinary Temp.Rating Intermediate Temp.Rating Max.Coverage area Max.Spacing (155,7/68°C) (175PF/79PC) Top of Deflector to Ceiling Minimum Ft x Ft(m x m) Ft(m) Flow Pressure Flow GPM Pressure Inch(mm) Spacing GPM(L/min) PSI(bar) (L/min) PSI(bar) Ft(m) 12 x 12(3,6 x 3,6) 12(3,6) 21 (79,5) 7.6(0,53) 21 (79,5) 7.6(0,53) Smooth Ceilings 41/4 to 8(108 to 203)using F2 escutcheon. 14 x 14(4,3 x 4,3) 14(4,3) 21 (79,5) 7.6(0,53) 21 (79,5) 7.6(0,53) 4 to 8(100 to 203)using F1 escutcheon. 16 x 16(4,9 x 4,9) 16(4,9) 21 (79,5) 7.6(0,53) 21 (79,5) 7.6(0,53) Beamed Ceilings per NFPA 8(2,4) 13D, 13R or 13 installed in 18 x 18(5,5 x 5,5) 18(5,5) 21 (79,5) 7.6(0,53) 21 (79,5) 7.6(0,53) beams 41/4 to 8(108 to 203)us- ing F2 escutcheon,4 to 8(100 20 x 20(6,1 x 6,1) 20(6,1) 23(87,1) 9.2(0,63) 23(87,1) 9.2(0,63) to 203)using F1 escutcheon For Ceiling types refer to NFPA 13, 13R or 13D • Model Fl Res 30, 49, 58 & 76 CCP Pendent* • Model Fl Res 30, 49, 58 & 76 Recessed Pendent/FP Zimi) • isr,, --s--\ , ._ _ r, Not listed for corrosion resistance. FP push-on/thread-off escutcheon 2 5/8"[66.7mm] DIA. 2 5/8" DIA. [66.7mm] 2 5/16" DIA. HOLE IN CEILING —HOLE IN CEILING [58.7mm] CUP -----+—-'),, 2 5/16" DIA. k,_4_`__-s [58.7mm] T ------__ CUP_ k1/2" REDUCER r CUP \ / I IT 1 I 1" X 1/2" REDUCER CEILING II[1_17II III , 1 1/4"[31.5mm] \ .f MAX. FACE OF FITTING j nn TO FACE OF CEILING L 1 III I1I CEILING j vi jai DIMENSION I 1 1/2" [38.1mm] MAX. »C. �� �I/ �II I�' FACE OF FITTING "A" �A'� a" -'� S' { TO FACE OF CEILING I , COVER ADJUSTMENT HEIGHT o ' DIMENSION 1 1/2 [13mm] MAX. 0..._/ III I FP ADJUSTMENT ��% �� A "I 3 5/16"DIA. "" I I 7 35FC04E [84.1 mm] Mo 113 Fl RES 30, 49, 58 & 76 CCP PEND. Fl RES 49 PENDENT/FP Fig. 3 Fig. 4 Note: The F1 Res 76 will use a 1"x%"reducer. CCP Cover Plate Data: FP Escutcheon Data: "C„ "B" Deflector Distance below bottom "A" Deflector Distance below bottom Cover Adjustment CCP Height of beam FP Position Inch(mm) of beam Inch(mm) Inch(mm) Inch(mm) Inch(mm) 1/2(12.7) 15/16(24) 1/2(13)-1 (25.4) Max.Recessed 7/16(11) 1/2(12.7) 5/16(7.9) 3/4(19) 1/2(13)-1 (25.4) Min.Recessed 15/16(24) 1 (25.4) Note: Sprinklers shown in Fig. 3 and Fig. 4 are not suitable for installation in ceilings which have positive pressure in the space above. 4. Technical Data: F1 Res 30 CCP Pendent and Recessed Pendent/FP (SIN R3511) Thread Nominal Max. CCP Assembly Max. K Sprinkler Orifice Pressure Temp.Rating Ambient Temp. Length Size Inch(mm) psi(bar) PF PC PF PC Factor Inch(mm) '/z"NPT 21 (R1/2) /64"(8.2) 175(12) 135 57 100 38 3.0(43.2) 2.25(57) Ordinary Temp. Rating Minimum Max.Coverage area Max.Spacing (155PF/68PC) Top of Deflector to Ceiling Spacing Ft x Ft(m x m) Ft(m) Flow Pressure Inch(mm) GPM(Umin) PSI(bar) Ft(m) 12 x 12(3,6 x 3,6) 12(3,6) 8(30,3) 7.0(0,48) Smooth Ceilings Y to 1 (13 to 25.4)using CCP. /z to 1 (13 to 25.4)using FP escutcheon. Beamed Ceilings per NFPA 13D,13R or 13 installed in 8(2,4) 14 x 14(4,3 x 4,3) 14(4,3) 11 (37,8) 13.4(0,92) beams 1/2 to 1 (13 to 25.4)using CCP. /z to 1 (13 to 25.4)using FP escutcheon. For Ceiling types refer to NFPA 13, 13R or 13D Technical Data: F1 Res 49 CCP Pendent and Recessed Pendent/FP (SIN 3516) CCP Nominal I Max. Assembly Max. Sprinkler Thread Orifice Ambient K Size Inch Pressure Temp. Temp. Factor Length psi(bar) Rating Inch(mm) (mm) PF PC PF PC 1"NPT 'h (RYz) s"(11) 175(12) 135 57 100 38 4.9(70.6) 2.25(57) Max.Coverage Ordinary Temp.Rating Minimum Max.Spacing (155r'F/68r'C) Top of Deflector to Ceiling area Ft(m) Flow Pressure Inch(mm) Spacing Ft x Ft(m x m) GPM(Umin) PSI(bar) Ft(m) 12 x 12(3,6 x 3,6) 12(3,6) 13(49) 7.0(0,48) Smooth Ceilings Y to 1 (13 to 25.4)using 14 x 14(4,3 x 4,3) 14(4,3) 13(49) 7.0(0,48) CCP. '/z to 1 (13 to 25.4)using FP escutcheon. 16 x 16(4,9 x 4,9) 16(4,9) 14(53) 8.2(0,56) Beamed Ceilings per NFPA 13D,13R or 13 8(2,4) installed in beams Y to 1 (13 to 25.4)using 18 x 18(5,5 x 5,5) 18(5,5) 18(68,1) 13.5(0,93) CCP. '/z to 1 (13 to 25.4)using FP escutcheon. 20 x 20(6,1 x 6,1) 20(6,1) 20(75,7) 16.7(1,14) For Ceiling types refer to NFPA 13, 13R or 13D Technical Data: F1 Res 58 CCP Pendent and Recessed Pendent/FP(SIN R3513) Thread Nominal Max. CCP Assembly Max. K Sprinkler Orifice Pressure Temp. Rating Ambient Temp. Length Size Inch(mm) psi(bar) PF PC PF )''C Inch Inch(mm) Y"NPT (R1/2) '/2"(13) 175(12) 135 57 100 38 5.8(83.5) 2.25(57) Max.Coverage Ordinary Temp.Rating Minimum Max.Spacing (1557'F/68PC) Top of Deflector to Ceiling area Ft(m) Flow Pressure Inch(mm) Spacing Ft x Ft(m x m) GPM(1../min) PSI(bar) Ft(m) 12 x 12(3,6 x 3,6) 12(3,6) 16(61) 7.6(0,53) 14 x 14(4,3 x 4,3) 14(4,3) 16(61) 7.6(0,53) Smooth Ceilings Y to 1 (13 to 25.4)using CCP. '/z to 1 (13 to 25.4)using FP escutcheon. 16 x 16(4,9 x 4,9) 16(4,9) 16(61) 7.6(0,53) Beamed Ceilings per NFPA 13D,13R or 13 installed in beams 1/2 to 8(2,4) 1 (13 to 25.4)using CCP. 18 x 18(5,5 x 5,5) 18(5,5) 19(72) 10.8(0,75) '/z to 1 (13 to 25.4)using FP escutcheon. 20 x 20(6,1 x 6,1) 20(6,1) 22(83,3) 14.4(1,0) For Ceiling types refer to NFPA 13, 13R or 13D 5. Technical Data: F1 Res 76 CCP Pendent and Recessed Pendent/FP (SIN R7618) Thread Nominal Max. CCP Assembly Max. K Sprinkler Size Orifice Pressure Temp.Rating Ambient Temp. Factor Length Inch(mm) psi(bar) PF PC PF PC Inch(mm) 3/4"NPT17/32"(13.5) 175(12) 135 57 100 38 7.6(109) 2.25(57) (R3/4) 150 66 Max.Coverage Ordinary Temp.Rating Minimum Max.Spacing (155PF/68PC) Top of Deflector to Ceiling area Ft(m) Flow Pressure Inch(mm) Spacing Ft x Ft(m x m) GPM(L/min) PSI(bar) Ft(m) 12 x 12(3,6 x 3,6) 12(3,6) 21 (79,5) 7.6(0,53) 14 x 14(4,3 x 4,3) 14(4,3) 21 (79,5) 7.6(0,53) Smooth Ceilings 1/2 to 1 (13 to 25.4)using CCP. 1/2 to 1 (13 to 25.4)using FP escutcheon. 16 x 16(4,9 x 4,9) 16(4,9) 21 (79,5) 7.6(0,53) Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams Y 8(2,4) to 1 (13 to 25.4)using CCP. 18 x 18(5,5 x 5,5) 18(5,5) 22(83,3) 8.4(0,58) 1/2 to 1 (13 to 25.4)using FP escutcheon. 20 x 20(6,1 x 6,1) 20(6,1) 25(94,6) 10.8(0,74) For Ceiling types refer to NFPA 13, 13R or 13D • Model Fl Res 44&58 HSW r ' k FACE OF FITTING TO WALL DIMENSION 1 1/4"MIN. 2 1/4"HOLE DIA. [31.8mm] A [57.2mm] —0-1/8CEILING TO [3.2mm] DEFLECTOR 7"X 1/2"REDUCER 1 //'/ DIMENSION f .� Model Fl Res 44 &58 Recessed HSW/F2 gi ; IRI ��i 7 15/76""DIA.I J no _ _ I =i.� (,-,..iii— I [49.2mm] )) ni" 1 —"�" ---•.; 2 27/32"DIA. wn 1__,I. [72.2mm] 1 1 , , TURN COLLAR UNTIL4., TIGHT AGAINST i WRENCH BOSS.SPRINKLER \\\`!I j 135Fco6—o 1/2"[13mm] ADJUSTMENT Fl RES 58 & 44 HSW/F2 F2 escutcheon, Fig. 5 1/2" (13mm) adjustment Technical Data: F1Res 44 HSW & HSW/F2 (SIN R3531) Escutcheon, F2, Data: Nominal Max. Sprinkler Max. p Sprinkler rinkler Thread Ambient K Adjustment Face of Fitting Size Orifice Pressure Temp.Rating Temp. Factor Length Type Inch(mm) to wall Inch(mm) psi(bar) PF PC PF PC Inch(mm) Inch(mm) /2"NPT3/$ (10) 175(12) 155 68 100 38 4.4(63) 2.45(62) F2 1/2(13) 3/l6-"/l6 (R'/2) 175 79 150 66 (4.7-17.4) 6. Ordinary Temp.Rating Intermediate Temp.Rating Top of Deflector to Minimum Max.Coverage area Max.Spacing (155PF/68PC) (175PF/799C) Ceiling Spacing Ft x Ft(m x m) Ft(m) Flow Pressure Flow Pressure GPM(L/min) PSI(bar) GPM(L/min) PSI(bar) Inch(mm) Ft(m) 12 x 12(3,6 x 3,6) 12(3,6) 12(45,4) 7.5(0,52) 12(45,4) 7.5(0,52) 14 x 14(4,3 x 4,3) 14(4,3) 14(53,0) 10.2(0,71) 14(53,0) 10.2(0,71) 16 x 16(4,9 x 4,9) 16(4,9) 16(60,6) 13.3(0,92) 16(60,6) 13.3(0,92) 4 to 6(100 to 152); 1/2(13)recessed 16 x 18(4,9 x 5,5) 16(4,9) 18(68,1) 16.8(0,53) 18(68,1) 16.8(0,53) using F2 escutcheon 18 x 18(5,5 x 5,5) 18(5,5) 19(72,0) 18.7(1,29) 19(72,0) 18.7(1,29) 16 x 20(4,9 x 6,1) 16(4,9) 23(87,1) 27.4(1,89) 23(87,1) 27.4(1,89) 8(2,4) 12 x 12(3,6 x 3,6) 12(3,6) 14(53,0) 10.2(0,71) 14(53,0) 10.2(0,71) 14 x 14(4,3 x 4,3) 14(4,3) 16(60,6) 13.3(0,92) 16(60,6) 13.3(0,92) 6 to 12(152 to 305); 16 x 16(4,9 x 4,9) 16(4,9) 17(64,4) 15.0(1,04) 17(64,4) 15.0(1,04) 1/2(13)recessed using F2 escutcheon 16 x 18(4,9 x 5,5) 16(4,9) 20(75,7) 20.7(1,43) 20(75,7) 20.7(1,43) 16 x 20(4,9 x 6,1) 16(4,9) 23(87,1) 27.4(1,89) 23(87,1) 27.4(1,89) For Ceiling types refer to NFPA 13, 13R or 13D Technical Data: Fl Res 58 HSW & HSW/F2 (SIN R3533) Escutcheon, F2, Data: Nominal Max. Sprinkler Face of Fitting Max. Sprinkler Adjustment Thread Orifice Pressure Temp.Rating Ambient K Length Type Inch mm to wall Size Inch psi(bar) Temp. Factor Inch ( ) Inch(mm) (mm) PF PC PF PC (mm) '/z 3/7 -11/1, (R1/2) 1/z"(13) 175(12) 175 79 150 66 5.8(83.5) 2.45(62) (4.7-17.4) Ordinary Temp.Rating Intermediate Temp.Rating Top of Deflector to Minimum Max.Coverage area Max.Spacing (155PF/68PC) (175PF/79PC) Ceiling Spacing Ft x Ft(m x m) Ft(m) Flow Pressure Flow Pressure Inch(mm) Ft(m) GPM(L/min) PSI(bar) GPM(L/min) PSI(bar) 12 x 12(3,6 x 3,6) 12(3,6) 16(60,6) 7.6(0,53) 16(60,6) 7.6(0,53) 14 x 14(4,3 x 4,3) 14(4,3) 18(68,2) 9.7(0,69) 18(68,2) 9.7(0,69) 4 to 6(100 to 152); 16 x 16(4,9 x 4,9) 16(4,9) 21 (79,5) 13.2(0,91) 21 (79,5) 13.2(0,91) 1/2(13)recessed using F2 escutcheon 16 x 18(4,9 x 5,5) 16(4,9) 25(94,7) 18.6(1,28) 25(94,7) 18.6(1,28) 16 x 20(4,9 x 6,1) 16(4,9) 29(109,8) 25.0(1,73) 29(109,8) 25.0(1,73) 8(2,4) 12 x 12(3,6 x 3,6) 12(3,6) 22(83,3) 14.4(1,0) 22(83,3) 14.4(1,0) 14 x 14(4,3 x 4,3) 14(4,3) 22(83,3) 14.4(1,0) 22(83,3) 14.4(1,0) 6 to 12(152 to 305); 1/2(13)recessed 16 x 16(4,9 x 4,9) 16(4,9) 26(98,4) 20.1 (1,39) 26(98,4) 20.1 (1,39) using F2 escutcheon 16 x 18(4,9 x 5,5) 16(4,9) 31 (117,4) 28.6(1,97) 31 (117,4) 28.6(1,97) For Ceiling types refer to NFPA 13, 13R or 13D 7. • Model F1 Res 44 SWC* A ] ti` 1 .r ''''L.. .i...__....--, \---7........." "Not listed for corrosion resistance. 4"to 12" A [101.60mm To 1 1/4"[31.75mm]Maximum 304.80mm] Face Of Fitting PUSH ON COVER, THEN To Wall Dimension TURN TO ADJUST UNTIL TIGHT AGAINST WALL. 1"X 1/2"Reducer Ita' 1.4 Recommended TM' ' Woll Hale 2 5/18" ° '�. ., •I 2 5/8" [5874mm)�--nx_ migg 3 5/16" [s6.68mm] Dia. in .:All , [84.14mm] 1, 010. TURN COLLAR UNTIL [:i I TIGHT AGAINST SPRINKLER _ WRENCH BOSS. 121/32" [42.07mm) 135FG07 1/2"[12.70mm] Adjustment Fl RES 44 SWC Fig. 6 Technical Data: F1 Res 44 SWC 'SIN R3531) Nominal Max. Cover Max. Sprinkler Thread Temp. Ambient K Size Orifice Pressure Rating Temp. Factor Length Inch(mm) psi(bar) PF pC 7,F pC Inch(mm) /2"NPT 3/8"(10) 175(12) 135 57 100 38 4.4(63) 2.45(62) (R/) Ordinary Temp.Rating Top of Deflector to Minimum Max.Coverage area Max.Spacing (155?F/68r'C) Ft x Ft(m x m) Ft(m) Flow Pressure Ceiling Spacing GPM(L/min) PSI(bar) Inch(mm) Ft(m) 12 x 12(3,6 x 3,6) 12(3,6) 13(49,2) 8.7(0,60) 14 x 14(4,3 x 4,3) 14(4,3) 14(53,0) 10.2(0,71) 4 to 6(100 to 152); 16 x 16(4,9 x 4,9) 16(4,9) 17(64,3) 15.0(1,1) Y (13)recessed using F2 escutcheon 16 x 18(4,9 x 5,5) 16(4,9) 19(71,8) 18.7(1,13) 16 x 20(4,9 x 6,1) 16(4,9) 23(87,1) 27.4(1,89) 8(2,4) 12 x 12(3,6 x 3,6) 12(3,6) 14(52,9) 10.2(0,71) 14 x 14(4,3 x 4,3) 14(4,3) 15(56,7) 11.7(0,81) 6 to 12(152 to 305); 1(13)recessed 16 x 16(4,9 x 4,9) 16(4,9) 18(68,1) 16.8(1,16) using F2 escutcheon 16 x 18(4,9 x 5,5) 16(4,9) 20(75,6) 20.7(1,43) For Ceiling types refer to NFPA 13, 13R or 13D 8. Technical Data: Fl Res 58 HSWX (SIN RA3533) Nominal Max. Sprinkler Max. Sprinkler Sprinkler Thread Ambient K Size Orifice Pressure Temp.Rating Temp. Factor Length Identification Inch(mm) psi(bar) pF rc PF I'DInch(mm) Number(SIN) Bulb /z NPT 1/2"(13) 175(12) 155 68 100 38 5.8(83.5) 2.45(62) RA3533 (R1/2) 175 79 150 66 1 Ordinary Temp.Rating Intermediate Temp.Rating Top of Deflector to Minimum Max.Coverage area Max.Spacing (155?F/68r'C) (175PFl79)*C) Ceiling Spacing Ft x Ft(m x m) Ft(m) Flow Pressure Flow Pressure Inch(mm) Ft(m) GPM(Umin) PSI(bar) GPM(Umin) PSI(bar) 18 x 20(5,5 x 6,1) 18(5,5) 30(114) 26.8(1,85) 30(114) 26.8(1,85) 20 x 20(6,1 x 6,1) 20(6,1) 30(114) 26.8(1,85) 30(114) 26.8(1,85) 4 to 6(100 to 152); 16 x 22(4,9 x 7,3) 16(4,9) 33(125) 32.4(2,23) 33(125) 32.4(2,23) 1/2(13)recessed using F2 escutcheon 16 x 24(4,9 x 7,3) 16(4,9) 38(144) 42.9(2,96) 38(144) 42.9(2,96) 14 x 26(4,3 x 7,9) 14(4,3) 42(160) 52.4(3,75) 42(160) 52.4(3,75) 8(2,4) 18 x 20(5,5 x 6,1) 18(5,5) 35(133) 36.4(2,5) 35(133) 36.4(2,5) 16 x 22(4,9 x 6,7) 16(4,9) 38(144) 42.9(2,96) 38(144) 42.9(2,96) 6 to 12(152 to 305); 1/2(13)recessed 16 x 24(4,9 x 7,3) 16(4,9) 42(160) 52.4(3,6) 42(160) 52.4(3,6) using F2 escutcheon 14 x 26(4,3 x 7,9) 14(4,3) 46(174) 62.9(4,34) 46(174) 62.9(4,34) For Ceiling types refer to NFPA 13, 13R or 13D • Model Fl Res 58 HSWX(Bulb) FACE OF FITTING TO --..—.-- WALL —WALL DIMENSION 1 11/16" MIN. [31.8mm] 0 4,41. ,..- 2 1/4" HOLE DIA. y f1/8", [57.2mm] [3.2mm] CEILING TO DEFLECTOR 7"X 1/2"REDUCER ,(/ \ DIMENSION _irRI\I -� 1 re 1 75/16" DIA.\lion I jS`�;-I.. `.. I [49[49.2,77m,] I , c"� 2 2" DIA. nn / /% o r -I, 0 [72.2mm27/3 ] L—Ili i_-��� .• I TURN COLLAR UNTIL �� • TIGHT AGAINST SPRINKLER `\`! Model KRes58 HSWX(Link) WRENCH BOSS. f 1/2"[73mm] - . . I35FG08 ADJUSTMENT / F1 RES 58 HSWX f Fig. 7 � -- . �t I! 9. Technical Data: KRes58 HSWX (RA3593) Nominal Max. Max. Sprinkler Sprinkler Thread Ambient K Size Orifice Pressure Temp. Factor Length Identification Inch(mm) psi(bar) WF rc Inch(mm) Number(SIN) Link /z NPT" 1/2"(13) 175(12) 100 38 5.8(83.5) 2.45(62) RA3593 (R1) Ordinary Temp.Rating Top of Deflector to Minimum Max.Coverage area Max.Spacing (165PF/74PC) Ft x Ft(m x m) Ft(m) Flow Pressure Ceiling Spacing GPM(L/min) PSI(bar) Inch(mm) Ft(m) 18 x 20(5,5 x 6,1) 18(5,5) 29(109) 25(1,72) 20 x 20(6,1 x 6,1) 20(6,1) 30(114) 26.8(1,85) 4 to 6(100 to 152); 16 x 22(4,9 x 7,3) 16(4,9) 33(125) 32.4(2,23) 1/2(13)recessed using F2 escutcheon 16 x 24(4,9 x 7,3) 16(4,9) 38(144) 42.9(2,96) 14 x 26(4,3 x 7,9) 14(4,3) 42(160) 52.4(3,75) 8(2,4) 18 x 20(5,5 x 6,1) 18(5,5) 35(133) 36.4(2,5) 16 x 22(4,9 x 6,7) 16(4,9) 38(144) 42.9(2,96) 6 to 12(152 to 305); 1/2(13)Recessed 16 x 24(4,9 x 7,3) 16(4,9) 42(160) 52.4(3,6) using F2 escutcheon 14 x 26(4,3 x 7,9) 14(4,3) 46(174) 62.9(4,34) For Ceiling types refer to NFPA 13, 13R or 13D Maintenance Model Fl Res 30, 49, Fl Res 58, Fl Res 76 and Fl Res ter seal assembly shall consist of a Teflon* coated Bel- 44 Sprinklers should be inspected and the sprinkler sys- leville spring washer with top-loaded extruded or cold tern maintained in accordance with NFPA 25, 13, 13D, head cup with 3 mm glass bulb containing no plastic and 13R. Do not clean sprinkler with soap and water,Am- parts, and having a temperature rating of [155°F (68°C)] monia or any other cleaning fluids. Remove dust by using [175°F (79°C)]. Sprinklers shall have a nominal K-factor a soft brush or gentle vacuuming. Remove any sprinkler of 3.0, 4.9 and 5.8. Standard finish: [Bronze] [Chrome- which has been painted (other than factory applied) or plated] [White Polyester] [Special finish- specify]. Resi- damaged in any way. A stock of spare sprinklers should dential pendent sprinklers shall be Reliable Model Fl Res be maintained to allow quick replacement of damaged or 30, 49 &58, SIN R3511, R3516& R3513 (Bulletin 135). operated sprinklers. Prior to installation, sprinklers should Model F1 Res 49 & 58 Recessed Pendent/F1, remain in the original cartons and packaging until used. Model F1 Res 30, 49 & 58 Recessed Pendent/ This will minimize the potential for damage to sprinklers F2, Model F1 Res 30, 49&58 Recessed Pendent/ that could cause improper operation or non-operation. FP Model F1 Res 30, 49 & 58 Pendent Sprinklers shall be [cULus Listed] [New York City MEA Sprinkler Specifications Approved (258-93-E)] low flow residential recessed pen- Sprinklers shall be [cULus Listed] [New York City MEA dent sprinklers engineered to provide a minimum design Approved (258-93-E)] low flow residential pendent sprin- density of 0.05 gpm/ft2 over the listed coverage area. klers engineered to provide a minimum design density of Listed flows as specified by the manufacturer's technical 0.05 gpm/ft2 over the listed coverage area. Listed flows data sheets are to be used. Residential sprinklers shall as specified by the manufacturer's technical data sheets be installed in conformance with the manufacturer's in- are to be used. Residential sprinklers shall be installed stallation guidelines and the applicable installation stan- in conformance with the manufacturer's installation guide- dard. Deflector-to-ceiling distance listing shall be 1"to 8" lines and the applicable installation standard. Deflector- maximum, only for Fl Res 49. Sprinkler frame and deflec- to-ceiling distance listing shall be 1" to 8" maximum, only tor shall be of bronze frame construction having a'/2" NPT for F1 Res 49. Sprinkler frame and deflector shall be of thread. Water seal assembly shall consist of a Teflon* bronze frame construction having a 1/2" NPT thread. Wa- coated Belleville spring washer with top-loaded extruded *DuPont Registered Trademark 10. or cold head cup with 3 mm glass bulb containing no leville spring washer with top-loaded extruded or cold plastic parts, and having a temperature rating of [155°F head cup with 3 mm glass bulb containing no plastic (68°C)] [175°F (79°C)]. Sprinklers shall have a nomi- parts, and having a temperature rating of [155°F (68°C)] nal K-factor of 3.0, 4.9 & 5.8. Standard finish: [Bronze] [175°F (79°C)]. The solder element (Link) version, the [Chrome-plated] [White Polyester] [Special finish— spec- water seal consist of a cap with a bellville spring washer ify]. Recessed escutcheon assembly shall be a steel, and a temperature rating of 165°F (74°C). The recessed two-piece escutcheon [with 1/2" adjustment (Model F2)] assembly forthe HSWX (Bulb & Link) should be a steel [with 3/4" adjustment (Model F1)] [of push-on and thread two pieces escutcheon with 1/2" adjustment (Model F2) off design with 1/2" adjustment (Model FP)]. Standard fin- standard finish should be Bright Chrome and white paint- ish shall be [brass][bright chrome] [white painted]. Resi- ed. The Fl Res 58 HSW is also available with low lead dential recessed pendent sprinklers shall be Reliable frame. Fl Res 58 HSW and HSWX sprinklers shall have a [Model Fl Res 30, 49&58 Recessed Pendent/F1] [Model nominal K Factor of 5.8 and Fl Res 44 a nominal K factor Fl Res 30, 49&58 Recessed Pendent/F2] [Model Fl Res of 4.4. Standard finish: [Bronze] [Chrome-plated] [White 30, 49 & 58 Recessed Pendent/FP] SIN R3511, R3516 & Polyester] [Special finish—specify]. Residential horizontal R3513 (Bulletin 135). sidewall sprinklers shall be Reliable Model Fl Res 44, Fl Model Fl Res 30, 49 & 58 CCP Pendent Res 58, Fl Res 58 HSWX & Model KRes58 HSWX, SIN (Concealed) R3531, RA3533 & RA3593 (Bulletin 135). Sprinklers shall be [cULus Listed] [New York City MEA Model Fl Res 44 Recessed Approved (258-93-E)] low flow residential concealed Horizontal Sidewall Sprinkler sprinklers engineered to provide a minimum design den- Use description for the Model Fl Res 44 horizontal side- sity of 0.05 gpm/ft2 over the listed coverage area. Listed wall sprinkler with the following modifications: Replace flows as specified by the manufacturer's technical data "horizontal sidewall sprinkler" with "recessed horizontal sheets are to be used. Residential sprinklers shall be in- sprinkler." Add: Recessed escutcheon assembly shall be stalled in conformance with the manufacturer's installa- steel, two-piece escutcheon with 1/2" adjustment(Model tion guidelines and the applicable installation standard. F2). Standard finish shall be [brass][bright chrome] [white Sprinkler frame and deflector shall be of bronze frame painted] [Special finish— specify]. Residential recessed construction having a 1/2" NPT thread. Water seal as horizontal sidewall sprinklers shall be Reliable Model Fl sembly shall consist of a Teflon* coated Belleville spring Res 44/F2, SIN R3531 (Bulletin 135). washer with top-loaded extruded or cold head cup with 3 Model Fl Res 76 Pendent mm glass bulb containing no plastic parts, and having a Sprinklers shall be [cULus Listed] low flow residential temperature rating of 155°F (68°C). Cover plate assem- pendent sprinklers engineered to provide a minimum bly shall consist of a brass cover plate and copper alloy design density of 0.05 gpm/ft2 over the listed coverage retainer flange. Method of attaching the cover plate to the area. Listed flows as specified by the manufacturer's sprinkler cup shall be a push-on and thread-off design technical data sheets are to be used. Residential sprin- allowing a '/2" cover plate adjustment. Cover plate tem- klers shall be installed in conformance with the manufac- perature rating shall be 135°F (57°C). A plastic protec- turer's installation guidelines and the applicable installa- tive cap shall be provided and factory installed inside the tion standard. Sprinkler frame and deflector shall be of sprinkler cup to protect the sprinkler from damage, which bronze frame construction having a 3/4" NPT thread. Wa- could occur during construction before the cover plate ter seal assembly shall consist of a Teflon* coated Bel- is installed. Standard cover plate finish: [White] [Custom leville spring washer with machined or cold head cup with Color— specify]. ]. Concealed pendent sprinklers shall 3 mm glass bulb containing no plastic parts, and having be Reliable Model Fl Res 30, 49 & 58 CCP, SIN R3511, a temperature rating of [155°F (68°C)] [175°F (79°C)]. R3516& R3513 (Bulletin 135). Sprinklers shall have a nominal K-factor of 7.6. Standard Model Fl Res 44, Fl Res 58 Horizontal finish: [Bronze] [Chrome-plated] [White Polyester] [Spe- Sidewall, Fl Res 58 HSWX & KRes58 HSWX cial finish— specify]. Residential pendent sprinklers shall Residential Sprinkler Specifications be Reliable Model Fl Res 76, SIN R7618 (Bulletin 135). Sprinklers shall be [cULus Listed] low flow residential horizontal sidewall sprinklers engineered to provide a minimum design density of 0.05 gpm/ft2 over the listed coverage area. Listed flows as specified by the manu- facturer's technical data sheets are to be used. Residen- tial sprinklers shall be installed in conformance with the manufacturer's installation guidelines and the applicable installation standard. Sprinkler frame and deflector shall be of bronze frame construction having a'/2" NPT thread. Water seal assembly shall consist of a Teflon*coated Bel- "Dupont Registered Trademark 11. Model F1 Res 76 Recessed Pendent/F1, Model F1 Res 76 Recessed Pendent/F2, a temperature rating of 155°F(68°C). Cover plate assem- Model F1 Res 76 Recessed Pendent/FP bly shall consist of a brass cover plate and copper alloy Sprinklers shall be [cULus Listed] low flow residential retainer flange. Method of attaching the cover plate to the recessed pendent sprinklers engineered to provide a sprinkler cup shall be a push-on and thread-off design minimum design density of 0.05 gpm/ft2 over the listed allowing a 1" cover plate adjustment. Cover plate tem- coverage area. Listed flows as specified by the manu- perature rating shall be 135°F (57°C). A plastic protec- facturer's technical data sheets are to be used. Residen- tive cap shall be provided and factory installed inside the tial sprinklers shall be installed in conformance with the sprinkler cup to protect the sprinkler from damage, which manufacturer's installation guidelines and the applicable could occur during construction before the cover plate installation standard. Sprinkler frame and deflector shall is installed. Standard cover plate finish: [White] [Custom be of bronze frame construction having a 3/4" NPT thread. Color—specify]. ]. Concealed pendent sprinklers shall be Water seal assembly shall consist of a Teflon*coated Bel- Reliable Model Fl Res 76 CCP, SIN R7618 (Bulletin 135). leville spring washer with machined or cold head cup with Finishes (1) 3 mm glass bulb containing no plastic parts, and hav- Standard Finishes ing a temperature rating of [155°F(68°C)] [175°F(79°C)]. Sprinklers shall have a nominal K-factor of 7.6. Standard Sprinkler Fl,F2,FP Cover Plates finish: [Bronze] [Chrome-plated] [White Polyester] [Spe Escutcheons cial finish— specify]. Recessed escutcheon assembly Bronze Brass White Painted shall be a steel, two-piece escutcheon [with '/2" adjust Chrome Plated Bright Chrome Plated Chrome White and Black White Painted ment (Model F2)] [with 3/4" adjustment (Model F1)] [of Polyester(2)Coated push-on and thread off design with t/" adjustment (Mod- _ el FP)]. Standard finish shall be [brass][bright chrome] Special Application Finishes [white painted]. Residential recessed pendent sprinklers Sprinkler Fi,F2,FP shall be Reliable [Model Fl Res 76 Recessed Pendent/ Escutcheons F1] [Model Fl Res 76 Recessed Pendent/F2] [Model Fl Electroless Nickel PTFE(Teflon®)(2) Electroless Nickel PTFE(Teflon®) Res 76 Recessed Pendent/FP] SIN R7618 (Bulletin 135). Bright Brass Bright Brass Model Fl Res 76 CCP Pendent (Concealed) Black Plated Black Plated Black Paint Black Paint Sprinklers shall be [cULus Listed] low flow residential Off White Off White concealed sprinklers engineered to provide a minimum Chrome Dull Chrome Dull design density of 0.05 gpm/ft2 over the listed coverage (1)Other finishes and colors are available on special order. area. Listed flows as specified by the manufacturer's Consult factory for details. technical data sheets are to be used. Residential sprin 12)cULus listed corrosion Resistant Note: Paint or any other coating applied over the factory finish will void klers shall be installed in conformance with the manufac- all approvals and warranties. turer's installation guidelines and the applicable installa- Ordering Information tion standard. Sprinkler frame and deflector shall be of bronze frame construction having a 3/4" NPT thread. Wa- Specify: ter seal assembly shall consist of a Teflon* coated Bel 1. Sprinkler Model leville spring washer with machined or cold head cup with 2. Sprinkler Type 3 mm glass bulb containing no plastic parts, and having 3. Temperature Rating 4. Sprinkler Finish 5. Escutcheon Finish 6. Cover Plate Finish "DuPont Registered Trademark The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association,Factory Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 90 years,and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States,Canada and foreign countries. Manufactured by Reliable Automatic Sprinkler Co.,Inc. ® Recycled ® (800)431-1588 Sales Offices Paper eIiabI (800)848 6051 Sales Fax (914)829-2042 Corporate Offices Revision lines indicate updated or new data. www.reliablesprinkler.com Internet Address EG.Printed in U.S.A.07/14 P/N 9999970235