HomeMy WebLinkAboutB16-0481_E100_1482188427.pdfSHEET # DRAWING TITLE
DRAWING INDEX
ELECTRICAL GENERAL INFORMATION
E100
ELECTRICAL LIGHTING PLAN
E200
GENERAL NOTES
1. ALL WORK SHALL BE DONE IN ACCORDANCE WITH 2014 NEC WITH LOCAL AMENDMENTS.
REFER TO THE LATEST EDITION OF THE NEC, IECC, IBC AND LOCAL ORDINANCES IN
EFFECT AT THE TIME OF CONSTRUCTION AS THE CONTROLLING DOCUMENTS.
2. ALL DEVICES AND EQUIPMENT INSTALLED OUTDOORS OR EXPOSED TO THE WEATHER
SHALL BE OF WEATHERPROOF CONSTRUCTION.
3. ALL SINGLE AND GANGED PLATES SHALL BE THERMOPLASTIC AND SHALL MATCH THE
DEVICE IN COLOR. COORDINATE DEVICE COLOR WITH THE ARCHITECT PRIOR TO
INSTALLATION. GANG DEVICES AT GROUP LOCATIONS UNDER A SINGLE COVER PLATE.
4. THE ELECTRICAL PLANS ARE SCHEMATIC IN NATURE AND ARE NOT INTENDED TO SHOW
ALL OF THE ARCHITECTURAL DETAIL OR SPECIFICS OF ELECTRICAL CONSTRUCTION.
TAKE ALL DIMENSIONS FROM THE ARCHITECTURAL DRAWINGS. PRIOR TO ROUGH-IN,
CONTRACTOR TO REVIEW ALL SUBMITTALS OF EQUIPMENT PROVIDED BY OTHER TRADE
AND MAKE NECESSARY ADJUSTMENTS.
5. ALL CONNECTIONS TO MECHANICAL EQUIPMENT SHALL BE MADE WITH A MINIMUM OF 24"
OF WEATHERPROOF FLEXIBLE CONDUIT TO PREVENT SOUND AND VIBRATION
TRANSMISSION TO THE STRUCTURE.
6. COORDINATE ALL MOTOR OVERLOADS AND/OR FUSES FURNISHED BY THIS CONTRACT
WITH THE ACTUAL EQUIPMENT INSTALLED. SIZE OVERLOADS BASED ON MOTOR
NAMEPLATE FULL LOAD CURRENT AND SERVICE FACTOR. FUSES FOR MOTOR AND
TRANSFORMER CIRCUITS SHALL BE DUAL ELEMENT. FUSES FOR OTHER "NON-INRUSH"
LOADS SHALL BE FAST ACTING. ALL FUSES SHALL BE CURRENT LIMITING CLASS RK5 OR
CLASS L UNLESS OTHERWISE NOTED.
FUSES SHALL BE PROVIDED WITH REJECTION TYPE FUSE HOLDERS.
7. GROUNDING CONDUCTORS ARE GENERALLY NOT SHOWN. GROUND AND BOND
TOGETHER ALL EQUIPMENT, RACEWAYS, MOTORS, PANELBOARDS AND SWITCHBOARDS,
ETC. IN ACCORDANCE WITH NEC ARTICLE 250.
BONDING OF ALL INTERIOR METAL PIPING SHALL BE IN ACCORDANCE WITH NEC ARTICLE
250 AS FOLLOWS:
A. ALL INTERIOR METAL WATER PIPING SHALL BE BONDED TO ONE OR MORE
GROUNDING ELECTRODES USED. THE BONDING JUMPER SHALL BE SIZED IN
ACCORDANCE WITH NEC ARTICLE 250.
B. INTERIOR METAL PIPING THAT MAY BECOME ENERGIZED (i.e. GAS PIPING, ETC.),
SHALL BE BONDED TO ONE OR MORE GROUNDING ELECTRODES USED. THE
BONDING JUMPER SHALL BE SIZED IN ACCORDANCE WITH NEC ARTICLE 250, USING
THE RATING OF THE CIRCUIT THAT MAY ENERGIZE THE PIPING SYSTEM.
C. INTERIOR METAL PIPING SYSTEM SEPARATED BY A PLUMBING EQUIPMENT (I.E.
METER, WATER HEATER) SHALL BE PROVIDED WITH A BONDING JUMPER SIZED PER
NEC ARTICLE 250. ALL GROUNDING ELECTRODE INSTALLED IN THE BUILDING
(SINGLE OR MULTIPLE SERVICES) SHALL BE BONDED TOGETHER TO FORM A SINGLE
GROUNDING ELECTRODE SYSTEM
8. INSTALL ALL WALL MOUNTED POWER, TELEPHONE AND DATA OUTLETS AT +15" A.F.F. TO
BOTTOM OF THE BOX, UNLESS OTHERWISE NOTED. INSTALL ALL LIGHTING CONTROL
SWITCHES, FIRE ALARM PULLSTATIONS, AND WALL TELEPHONE JACKS AT +48" A.F.F. TO
TOP OF THE BOX, UNLESS OTHERWISE NOTED.
9. CONDUCTOR PENETRATION OF FIRE RATED PORTIONS OF A STRUCTURE SHALL BE
EFFECTIVELY SEALED AND SLEEVED WITH STEEL FLEX 3 FEET EACH SIDE OF THE
PENETRATION, OR OTHER APPLIED METHODS.
10. RECESSED LIGHT FIXTURES INSTALLED WHERE THERE ARE INSULATION IS REQUIRED TO
BE I.C. RATED. ALL LIGHT SWITCHES NOT WITHIN SIGHT OF THE LUMINAIRES SHALL BE
EQUIPPED WITH A PILOT LIGHT, EVEN IF NOT SHOWN IN THE DRAWINGS. CONTRACTOR
TO PROVIDE ALL REQUIRED SEISMIC SUPPORT WIRES FOR THE LIGHTING FIXTURES.
PENDANT FIXTURES SHALL BE PROVIDED WITH SEISMIC SUPPORT WIRES SO AS NOT TO
HIT ANYTHING ON A 45 DEGREE SWING AND AS REQUIRED NY THE AHJ.
11. ALL EQUIPMENT SHALL BE UL LISTED AND SHALL BE INSTALLED AS PER THEIR LISTINGS.
INSTALLATION INSTRUCTION FOR ALL UL LISTED EQUIPMENT SHALL BE MADE AVAILABLE
TO THE BUILDING INSPECTOR AT THE TIME OF INSPECTION. ALL DEVICES AND
EQUIPMENT INSTALLED OUTDOORS OR EXPOSED TO THE WEATHER SHALL BE OF
WEATHERPROOF CONSTRUCTION. ALL RECEPTACLES SHALL COMPLY WITH THE LATEST
EDITION OF THE N.E.C., EVEN IF NOT SPECIFICALLY IDENTIFIED IN THE DRAWINGS (GFCI,
AFCI, TAMPER RESISTANT, HOSPITAL GRADE, ETC.)
12. STRUCTURAL STEEL FIREPROOFING THAT WERE DAMAGED DURING CONSTRUCTION
SHALL BE PATCHED AND REPAIRED BY THIS CONTRACTOR.
13. NO FLEXIBLE CONDUIT IS PERMITTED IN DEMISING WALLS. FLEXIBLE CONDUIT IS
PERMITTED FOR SHORT, FINAL CONNECTIONS ONLY (6'-0" OR LESS).
14. EXPOSED CONDUIT SHALL BE INSTALLED IN STRAIGHT LINES, PARALLEL OR IN RIGHT
ANGLES TO THE BUILDING STRUCTURE. DO NOT LOOP EXCESS FLEXIBLE CONDUIT IN
CEILING SPACE OR WALL CAVITY.
15. CABLE TYPES AC AND NM CABLES ARE NOT ACCEPTABLE. TYPE MC CABLE, ELECTRIC
METALLIC TUBING (EMT) AND RIGID GALVANIZED CONDUIT ARE PERMITTED.
16. ALL ELECTRICAL PANELS TO BE UL LABELED WITH BOLT ON TYPE CIRCUIT BREAKERS.
ELECTRICAL PANELS MAY NOT BE RECESSED IN DEMISING PARTITIONS. SURFACE MOUNT
OF FUR OUT WALL TO ACHIEVE FLUSH FINISH APPEARANCE. PANELS SHALL BE MOUNTED
ON PLYWOOD BACKER BOARD.
17. 7 DAY, 24 HOUR TIME CLOCK IS REQUIRED TO CONTROL STOREFRONT ENTRY LIGHTS,
SHOW WINDOW LIGHTS, SHOW WINDOW RECEPTACLES AND STOREFRONT SIGNAGE.
ILLUMINATED STOREFRONT SIGNS MUST REMAIN LIT DURING ALL MALL BUSINESS
HOURS.
18. CONTRACTOR IS REQUIRED TO MAKE A FIELD SURVEY OF THE EXISTING ELECTRICAL
SERVICE TO ENSURE THAT THE TOTAL CONNECTED LOAD DOES NOT EXCEED THE
ELECTRICAL SERVICE. ANY/ ALL MODIFICATIONS OR UPGRADES NEEDED ARE SUBJECT
TO LANDLORD'S PRIOR APPROVAL, AND WILL BE COMPLETED BY TENANT/ TENANT'S GC,
AT TENANT'S SOLE EXPENSE.
19. COORDINATE ALL CONCRETE TRENCHING/ CORING TO ENSURE THAT ANY UNDER SLAB
UTILITIES, ETC., ARE NOT DAMAGED DURING FLOOR CUT. ANY DAMAGE TO BE REPAIRED
AT TENANT EXPENSE. PRIOR APPROVAL AND COORDINATION WITH PROPERTY
MANAGEMENT IS REQUIRED FOR ALL CONCRETE CUTTING.
20. PROVIDE UPSIZED CONDUCTORS TO COMPENSATE FOR VOLTAGE DROP, FOR 12A LOAD,
120V CIRCUIT: USE #10 FOR 76'-125' RUN, USE #8 FOR 126'-175' RUN, USE #6 FOR 176'-225'
RUN.
ELECTRICAL POWER PLAN
E300
E600 ELECTRICAL SPECIFICATIONS
E601 ELECTRICAL SPECIFICATIONS
E400 ELECTRICAL ONE-LINE DIAGRAM AND PANEL SCHEDULES
GROUNDING ELECTRODE SYSTEM:
UFER, GROUND ROD, U.G. WATER PIPE, STRUCTURAL STEEL.
CIRCUIT BREAKER
E100
ELECTRICAL
GENERAL
INFORMATION
ABBREVIATION
DESCRIPTION
SYMBOL
WEATHERPROOF
WP
UNLESS NOTED OTHERWISE
U.N.O. U.O.N.
SEE PLUMBING DRAWINGS
S.P.D.
PHASE
PH
NIGHT LIGHT, "ON" 24/7
NL
GROUND FAULT INTERRUPTER
GFI
ABOVE FINISHED FLOOR
AFF
EXHAUST FAN
EF
VOLTAGE DROP
VD
AMPERE
A
MAIN CIRCUIT BREAKER
MCB
MAIN LUG ONLY
MLO
AMPERE INTERRUPTING CAPACITY
AIC
SEE MECHANICAL DRAWINGS
S.M.D.
SEE ARCHITECTURAL DRAWINGS
S.A.D.
EMERGENCY
EM
SUBSCRIPT LOCATED NEXT TO THE DEVICE
MEANS 42"AFF TO CENTER OF DEVICE
+42
NATIONAL ELECTRICAL CODE
NEC
RIGID METAL CONDUIT
RMC
AMERICAN WIRE GAUGE
AWG
CONDUIT
C
VARIABLE FREQUENCY DRIVE
VFD
COPPER
CU
GROUND
G, GND
FURNISH, INSTALL, CONNECT
PROVIDE
POLE
P
VOLTS
V
VOLT AMPERE
VA
SHORT CIRCUIT CURRENT
ISC
ONE WAY DISTANCE OF FEEDER/ BRANCH
CIRCUIT
D
REMOVE, DEMO
(R)
EXISTING
(E)
EXISTING TO BE RELOCATED
(RE)
RELOCATED TO THIS NEW LOCATION
(RL)
PROVISION FOR FUTURE METER
PFM
PROVISION FOR FUTURE BREAKER
PFB
LEGEND
DESCRIPTION
SYMBOL
15A WALL MOUNTED DUAL TECH (U.N.O.) OCCUPANCY OR VACANCY SWITCH
SENSOR. LOWER CASE LETTER INDICATES CIRCUIT CONTROLLED BY SWITCH.
HORSEPOWER RATED TOGGLE SWITCH WITH THERMAL OVERLOADS.
20A THREE WAY SWITCH AND BOX
WALL MOUNTED 1P, 20A SWITCH AND BOX.
LOWER CASE LETTER INDICATES CIRCUIT CONTROLLED BY SWITCH.
ab
3
T
ab
DIMMER SWITCH, VA RATING AS SHOWN AND AS REQUIRED
DUPLEX OR QUAD CONVENIENCE OUTLET: 20AMP, 120V
STANDARD - WHITE = PASS & SEYMOUR #CRB5362-W
"B" - BLACK = PASS & SEYMOUR #CRB5362-B
"R" - RED = PASS & SEYMOUR #CRB5362-R
CONTROLLED OUTLET:
20AMP, 120V, SPLIT-WIRED: PASS & SEYMOUR #5362CH-X
20AMP, 120V, DUAL-CONTROLLED: PASS & SEYMOUR #5362CD-X
R
R
B
B
SIMPLEX RECEPTACLE, NEMA CONFIGURATION AS NOTED.
"B" - BLACK.
SPECIAL RECEPTACLE, NEMA CONFIGURATION AS NOTED.
"B" - BLACK.
FLUSH FLOOR MOUNTED OUTLET BOX WITH DUPLEX RECEPTACLE.
SEE FLOOR PLAN FOR SPEC.
FLUSH CEILING MOUNTED OUTLET BOX WITH DUPLEX OR QUAD RECEPTACLE.
"C" INDICATES FLUSH MOUNTED IN CEILING.
C
C
DATA OUTLET DEVICE BOX. PROVIDE 3/4" CONDUIT INTO CEILING SPACE.
PROVIDE ELBOW, BUSHING AND PULL STRING.
TELEPHONE OUTLET DEVICE BOX. PROVIDE 3/4" CONDUIT INTO CEILING SPACE.
PROVIDE ELBOW, BUSHING AND PULL STRING.
AP
CEILING MOUNTED DATA OUTLET (REFER TO VENDOR DRAWINGS):
"AP" - ACCESS POINT
"ST" - SHOPPER TRAK
ST
JUNCTION BOX - WALL OR CEILING MOUNTED
NON-FUSED DISCONNECT SWITCH.
FUSED DISCONNECT SWITCH WITH DUAL ELEMENT FUSES PER
EQUIPMENT NAME PLATE RATING.
MAGNETIC MOTOR STARTER.
COMBINATION MAGNETIC MOTOR STARTER AND DISCONNECT SWITCH.
MOTOR OUTLET AND FLEX CONNECTION TO MOTOR.
HOMERUN TO PANEL INDICATING CIRCUIT NUMBERS.
ALL WIRING SHALL BE #12 AWG WITH GROUND WIRE IN 3/4" U.O.N.
CONSULT VOLTAGE DROP TABLE FOR MAXIMUM DISTANCE.
T
TRANSFORMER WITH REQUIRED GROUNDING.
SIZE, VOLTAGE, TYPE AS PER PLANS.
SWITCH & FUSE
PANELBOARD SURFACE OR FLUSH MOUNTED.
SIZE, VOLTAGE, TYPE AS PER PLANS.
FACP FIRE ALARM CONTROL PANEL, TOP OF PANEL AT +6'-0" A.F.F.
F
A
V
AV
xx
xx
FIRE ALARM MANUAL PULL STATION, +48" AFF. TO TOP OF OPERABLE HANDLE, UON.
FIRE ALARM HORN, MOUNTED AT +90" AFF. TO TOP OF DEVICE, UON.
FIRE ALARM STROBE LIGHT, +90" AFF. TO TOP OF THE LENS
"xx" INDICATES CANDELA RATING.
FIRE ALARM HORN/STROBE COMBINATION, +90" AFF. TO TOP OF THE
LENS, UON. "xx" INDICATES CANDELA RATING.
HVAC SMOKE DUCT DETECTOR, S.M.D.
LINE-VOLTAGE THERMOSTAT, S.M.D.
T
SECURITY CAMERA, REFER TO PLANS.
M
MOTION SENSOR LOCATION: COORDINATE WITH SECURITY CONTRACTOR.
PROVIDE DEVICE BACKBOX AND 3/4" CONDUIT WITH NYLON BUSHING STUBBED
INTO ACCESSIBLE CEILING SPACE. SEE GENERAL NOTE S9.
SECURITY DEVICE LOCATION: SEE SECURITY VENDOR DRAWINGS.
PROVIDE DEVICE BACKBOX AND 3/4" CONDUIT WITH NYLON BUSHING
STUBBED INTO ACCESSIBLE CEILING SPACE.
"CR" - CARD READER.
"KP" - KEYPAD.
GENERAL CONTRACTOR
GC
FIRE ALARM DESIGN BUILD NOTES
1. FIRE ALARM (FA) SYSTEM SHALL BE DESIGNED BY A LANDLORD APPROVED FA
SYSTEM CONTRACTOR. THE FA CONTRACTOR SHALL PRODUCE DRAWINGS,
EQUIPMENT CUT SHEETS, ETC. PER LOCAL CODE, LOCAL CITY FIRE DEPARTMENT,
NEC AND NFPA72 REQUIREMENTS. SUBMIT TO THE LOCAL AUTHORITIES HAVING
JURISDICTION AND OWNER'S INSURANCE COMPANY FOR APPROVAL PRIOR TO
ORDERING EQUIPMENT.
2. LANDLORD WILL STUB-OUT INTO TENANT'S SPACE A CONDUIT WITH ALARM WIRE
AND A J-BOX, FOR CONNECTION TO MALL'S FA SYSTEM.
3. NEW FA SYSTEM SHALL MEET MINIMUM REQUIREMENTS OF MALL AND SHALL BE
CONNECTED TO THE MALL'S FA MONITORING SYSTEM.
4. ALL PANELS, PERIPHERAL DEVICES AND MATERIALS SHALL BE STANDARD
PRODUCT OF SINGLE MANUFACTURER AND SHALL DISPLAY THE MANUFACTURER'S
NAME ON EACH COMPONENT. DEVICES AND MATERIALS SHALL BE COMPATIBLE
WITH LANDLORD'S MAIN SYSTEM.
5. GC TO OBTAIN QUOTE FROM THE LL DESIGNATED FA CONTRACTOR AND ENGAGE
HIS SERVICES. INCLUDE IN BID ALL COSTS FOR PERMITS AND FEES, IF APPLICABLE.
DEMOLITION NOTES
1. WHERE REMOVAL OF AN EXISTING WORK (I.E., OUTLET, CONDUIT, WIRING ETC.) WILL
RESULT IN LOSS OF CIRCUIT CONTINUITY, THE REMAINING ISOLATED PORTIONS OF THE
CIRCUIT SHALL BE RECONNECTED TO THE NEAREST AVAILABLE AND APPROPRIATE
EXISTING OUTLETS.
2. WHERE EXISTING WIRING OR EQUIPMENT IS TO BE ABANDONED, IT SHALL BE REMOVED
AND THIS WORK SHALL INCLUDE BUT NOT LIMITED TO THE FOLLOWING:
A. REMOVE WIRES AND CABLES
B. REMOVE AND RELOCATE LIGHTING FIXTURES
C. REMOVE DEVICES AND EQUIPMENT
D. REMOVE EXPOSED CONDUITS
E. CUT OFF & CAP ABANDONED CONDUIT; STUBS SHALL NOT EXTEND ABOVE FLOOR
F. REMOVE OTHER ITEMS NOT INCLUDED IN ITEMS (A) THRU (D)
3. WHERE EXISTING WIRING, DEVICES AND EQUIPMENT ARE REMOVED, SUCH ITEMS SHALL
NOT BE RE-USED UNLESS SPECIFICALLY DIRECTED AND APPROVED BY OWNER.
4. REFER TO DEMOLITION NOTES ON ARCHITECTURAL DRAWINGS, REGARDING EXISTING
LIGHT FIXTURES.
5. REROUTE ALL CONDUITS THAT ARE TO REMAIN IN SERVICE AND WHICH CONFLICT WITH
EQUIPMENT INSTALLATION.
6. WHEREVER EXISTING ELECTRICAL DEVICES, CONDUITS, CABLES, OR OTHER ITEMS
CONFLICT WITH REMODEL WORK, WHETHER SHOWN OR NOT, RELOCATE THESE ITEMS.
7. PATCH AND PAINT TO MATCH EXISTING, IN ALL AREAS AFFECTED BY REMOVAL OF
ELECTRICAL EQUIPMENT AND DEVICES.
8. DISCONNECT AND REMOVE ALL EXISTING ELECTRICAL DEVICES IN EXISTING CEILINGS
AND WALLS WHICH ARE REQUIRED TO BE DEMOLISHED, WHETHER SHOWN OR NOT.
MAINTAIN CIRCUITS TO ALL REMAINING DEVICES.
ITEM
#
FURNISHED
BY
INSTALLED
BY
C
O
N
T
R
A
C
T
O
R
O
W
N
E
R
C
O
N
T
R
A
C
T
O
R
DESCRIPTION
SWITCHBOARDS,
PANELBOARDS,
TRANSFORMERS,
CIRCUIT BREAKERS, FUSES,
SAFETY SWITCHES.
LIGHTING FIXTURES
(INTERIOR, EXTERIOR).
LIGHTING CONTROL SYSTEM
TELECOM PATHWAYS,
BOXES, CONDUITS.
TELECOM DEVICES,
SERVER EQUIPMENTS.
O
W
N
E
R
V
E
N
D
O
R
O
W
N
E
R
V
E
N
D
O
R
SECURITY SYSTEM.
O
W
N
E
R
EXTERIOR LIGHTING SIGNAGE.
ELECTRICAL WIRING
PROVISION FOR MECHANICAL
& PLUMBING EQUIPMENTS.
ALL OTHERS.
RECEPTACLES, N14-50R's.
MATRIX
RESPONSIBILITY
E500 ELECTRICAL LIGHTING FIXTURE SCHEDULE & COMPLIANCE FORMS
DUPLEX OR QUAD CONVENIENCE OUTLET: 20AMP, 120V
ABOVE COUNTER. SEE ARCHITECTURAL ELEVATIONS FOR EXACT HEIGHT.
DUPLEX OR QUAD CONVENIENCE OUTLET: 20AMP, 120V, GFCI
STANDARD - WHITE = PASS & SEYMOUR #2095W
SCALE:
PROJECT NUMBER:
DRAWING TITLE
ISSUE / REVISION
51643
SOLARIS PLAZA
141 E MEADOW DRIVE
#202
VAIL, CO 81657
SHEET NUMBER
10.26.16 PERMIT ISSUE
960 Atlantic Ave.
Alameda, CA 94501
510 865 8663
mbharch.com
3371 Olcott Street
Copyright c 2016
info@acies.net
fx: (408) 522-5260
ph: (408) 522-5255
Santa Clara, CA 95054
ENGINEERING
EXP: 10/31/17
12.15.16 PLAN CHECK COMMENTS
12/19/16