HomeMy WebLinkAboutB16-0481_E200_1482188427.pdfL202-13
6
L202-17
L202-17
L202-17
L202-17
L202-17
L202-17
L202-17
(E)
(E)
(E) (E)
a a b
L202-17
6 6
6
6 6
6
(E)
8 7 6 5 4 3 9
2
ADJACENT TENANT (N.I.C.)
MALL EXIT CORRIDOR
MALL EXTERIOR
X1
L4 L4
F F F
X3
X3 X3
X3
X3
X3
X3
9
-EM
LV
(RL) PANEL L202
k,m n,p r,s
x,y
1/k3/m5/n7/p
9/r
11/s21/x 23/y
w w
7
a,b
17/w
(E) LIGHTING SWITCHBANK
8A
8B
LCP
1
2
2
3
LV
8
9
T
L202-41 4
5
SCALE:
1/4" = 1'-0"
FLOOR PLAN - LIGHTING 1
SCALE:
NONE LIGHTING CONTROL PANEL SCHEDULE 2
1. SEE SHEET E100, GENERAL NOTES.
2. MOUNTING TYPES INDICATED FOR EXIT LIGHTS (WALL, CEILING, ETC.) ARE INTENDED TO
BE DIAGRAMMATIC ONLY TO INDICATE REQUIRED LOCATIONS. ELECTRICAL
CONTRACTOR SHALL PROVIDE SPECIFIC TYPES OF MOUNTING HARDWARE AS REQUIRED
BY FIELD CONDITIONS.
3. IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO DETERMINE THE
TYPE OF CONSTRUCTION INTO WHICH EACH LIGHTING FIXTURE WILL BE INSTALLED AND
TO FURNISH THE APPROPRIATE MOUNTING HARDWARE AND ACCESSORIES.
4. EXPOSED RACEWAYS SUPPLYING LIGHTING FIXTURES (AND ALL OTHER ITEMS) SHALL BE
INSTALLED PARALLEL OR PERPENDICULAR TO BUILDING WALLS. WHERE OFFSETS,
"KICKS", ETC. ARE REQUIRED TO AVOID OBSTACLES, THESE SHALL BE DONE IN A
WORKMANLIKE MANNER WITHOUT KINKS, "DOGLEGS", ETC.
5. INSTALLATION OF LIGHTING FIXTURES SHALL BE CAREFULLY COORDINATED WITH
ARCHITECTURAL AND MECHANICAL DRAWINGS TO AVOID CONFLICTS WITH DUCTWORK,
ARCHITECTURAL FEATURES, ETC. WHERE CONFLICTS ARISE, CLARIFY WITH ARCHITECT
PRIOR TO PROCEEDING WITH INSTALLATION.
6. BASED ON LIGHTING MANUFACTURERS PUBLISHED DATA, EMERGENCY BATTERY LIGHTS
ARE LOCATED TO PROVIDE ONE (1) FOOT CANDLE ALONG THE MEANS OF EGRESS.
7. THIS CONTRACTOR SHALL MEET IN THE FIELD WITH FIRE INSPECTOR TO AIM AND ADJUST
EMERGENCY LIGHTS AS HE DEEMS NECESSARY. CONTRACTOR SHALL ADD ADDITIONAL
BATTERY LIGHTS AND EXIT SIGNS WERE THE FIRE INSPECTOR MANDATES.
8. WIRE EMERGENCY LIGHTING BATTERY PACKS, BATTERY BACKUP EXIT SIGNS AND NIGHT
LIGHTS INDICATED TO LOCAL LIGHTING CIRCUIT AHEAD OF ALL LOCAL SWITCHING.
9. PROVIDE APPROVED HANDLE TIE FOR ALL MULTIWIRE BRANCH CIRCUITS AS REQUIRED
PER NEC ART. 210.4(B).
10. PROVIDE LINEAR DISCONNECT FOR THOSE FIXTURES EMPLOYING DOUBLE-ENDED
FLUORESCENT LAMPS PER NEC 410.130(G).
11. AIM AND ADJUST ALL LIGHT FIXTURES AS PER ARCHITECTURAL PLANS.
WIRE THROUGH RELAY IN LIGHTING CONTROL PANEL "LCP" FOR CONTROL BY TIME CLOCK FOR
"GC - GENERAL CLEANING" LIGHTING CONTROL.
WIRE THROUGH RELAY IN LIGHTING CONTROL PANEL "LCP" FOR CONTROL BY TIME CLOCK FOR
"SO - STORE OPENING" LIGHTING CONTROL.
PROVIDE LIGHTING CONTROL PANEL AND LIGHTING CONTACTORS IN A NEMA-1 ENCLOSURE.
SEE DETAIL ON THIS SHEET FOR MORE INFORMATION.
WIRE THROUGH RELAY IN LIGHTING CONTROL PANEL "LCP" FOR CONTROL BY TIME CLOCK FOR
"SN - SIGN" LIGHTING CONTROL.
LED EXTERIOR SIGN TO BE PROVIDED BY OTHERS. CONTRACTOR SHALL REFER TO VENDOR
DRAWINGS FOR EXACT WIRING REQUIREMENTS AND ROUGH IN.
EMERGENCY FIXTURE SHALL BE WIRED WITH LOCAL LIGHTING CIRCUIT AHEAD OF ALL
SWITCHING DEVICES.
EMERGENCY LIGHT SHALL BE WIRED AS A SWITCHED FIXTURE. INTEGRAL BATTERY PACK SHALL
BE WIRED HOT AHEAD OF SWITCHING PER MANUFACTURERS SPECIFICATIONS SO THAT
EMERGENCY LIGHTS COMES ON IN A POWER FAILURE REGARDLESS OF SWITCHING.
LOCATION OF LOW VOLTAGE OVERRIDE SWITCH. VERIFY EXACT LOCATION WITH OWNER PRIOR
TO ROUGH-IN. SEE DETAIL ON THIS SHEET FOR MORE INFORMATION.
EXISTING LOCATION OF TRACK LIGHTING CONTROLS. CONFIRM REQUIREMENTS WITH OWNER
AND RELOCATE TO NEW LOCATION AS REQUIRED. INTERCEPT AND EXTEND ALL CIRCUITS TO
RELOCATED PANEL L202 LOCATION. ROUTE ALL LIGHTING CIRCUITS VIA TIME-CLOCK AND
LIGHTING CONTACTORS. SEE DETAIL ON THIS SHEET FOR MORE INFORMATION.
REPLACE EXISTING DIMMER SWITCH WITH NEW ON/OFF SWITCH. INTERCEPT AND EXTEND
CIRCUIT TO RELOCATED PANEL L202 LOCATION. ROUTE CIRCUIT VIA TIME-CLOCK AND LIGHTING
CONTACTOR. SEE DETAIL ON THIS SHEET FOR MORE INFORMATION.
CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR WITH COMPATIBLE REMOTE
POWERPACK. HUBBELL CAT. #OMNI-DT SERIES WITH #UNVPP POWERPACK. PROVIDE WITH
COMPATIBLE LOW-VOLTAGE MOMENTARY SWITCHES FOR 50% AUTO - 50% MANUAL ON/AUTO OFF
OPERATION. FIELD VERIFY EXACT MOUNTING LOCATION AND HEIGHT FOR MAXIMUM COVERAGE.
1
2
3
4
5
6
7
8
8B
SHEET GENERAL NOTES SHEET KEYED NOTES
SCALE:
NONE SHEET NOTES 2
1. LIGHT FIXTURES AUTOMATICALLY TURN ON PER SCHEDULE.
2. LIGHTS AUTOMATICALLY SHUT OFF AT THE END OF SCHEDULED HOURS.
3. DURING NON-BUSINESS HOURS, PRESSING THE LV SWITCH ACTIVATES CORRESPONDING LIGHT FIXTURES FOR
MAXIMUM OF 2 HOURS. LIGHTS WILL FLICKER 5-10 MINUTES PRIOR TO SCHEDULED SHUT-OFF.
SEQUENCE OF OPERATIONS
"STAFF" IS DEFINED:
MONDAY THROUGH SATURDAY - 5:45AM UNTIL 11:15 PM
SUNDAY - 8:45AM UNTIL 8:15PM
"SIGNAGE" IS DEFINED:
DUSK TO DAWN.
"CUSTOMER" IS DEFINED:
MONDAY THROUGH SATURDAY - 9:45AM UNTIL 9:15PM
SUNDAY - 11:45AM UNTIL 6:15PM
STORE BUSINESS HOURS(*)
1. LIGHTING CONTROL PANEL SHALL BE HUBBELL CX4 OR APPROVED EQUAL.
2. PROVIDE COMPATIBLE LOW-VOLTAGE SWITCH WITH PILOT LIGHT, HUBBELL LVSMXPL OR EQUAL.
3. CONSULT WITH OWNER FOR STORE BUSINESS HOURS PRIOR TO PROGRAMMING.
4. LIGHTING CONTROL SYSTEM IS FURNISHED BY OWNER VENDOR AND TO BE INSTALLED BY CONTRACTOR, UON.
REFER TO MANUFACTURER WIRING DIAGRAM AND INSTALLATION INSTRUCTIONS FOR MORE INFORMATION.
DETAIL NOTES
CP1
CP2
E200
ELECTRICAL
LIGHTING
PLAN
AS NOTED
SCALE:
PROJECT NUMBER:
DRAWING TITLE
ISSUE / REVISION
51643
SOLARIS PLAZA
141 E MEADOW DRIVE
#202
VAIL, CO 81657
SHEET NUMBER
10.26.16 PERMIT ISSUE
960 Atlantic Ave.
Alameda, CA 94501
510 865 8663
mbharch.com
3371 Olcott Street
Copyright c 2016
info@acies.net
fx: (408) 522-5260
ph: (408) 522-5255
Santa Clara, CA 95054
ENGINEERING
EXP: 10/31/17
12.15.16 PLAN CHECK COMMENTS
8A
9
1
1
12/19/16