NONE PARTIAL ONE-LINE DIAGRAM 1
1. ALL ELECTRICAL EQUIPMENTS AND FEEDERS ARE "(E)", EXISTING UNLESS OTHERWISE
NOTED AS "(N)" FOR NEW. RE-TORQUE ALL EXISTING TERMINATIONS PER
MANUFACTURER RECOMMENDATION.
2. SWITCHBOARD SHOWN ON THE SINGLE LINE DIAGRAM SHALL BE "FULLY-RATED"
ADEQUATE FOR THE MAXIMUM FAULT CURRENT AVAILABLE AT THE POINT OF
APPLICATION, INCORPORATING THE CURRENT LIMITING DEVICES AS SPECIFIED.
"SERIES-RATING" FOR PANELBOARDS IS ACCEPTABLE. PROVIDE REQUIRED MARKING
AS REQUIRED PER NEC ARTICLE 110.22(B) & (C) FOR SIGNAGE AT ALL PANELS AND
EQUIPMENT. IF NOT "FULLY-RATED SYSTEM" CONTRACTOR SHALL SUBMIT SHOP
DRAWINGS INDICATING SERIES RATING AND INCLUDE A COPY OF ALL LABELING,
INCLUDING RESPECTIVE UL LISTING, TO THE AHJ FOR REFERENCE.
3. ALL PANELS SHALL BE PAINTED TO MATCH ADJACENT WALL FINISH (VERIFY WITH
ARCHITECT PRIOR TO PAINTING). PROVIDE PHENOLIC NAMEPLATE LABELLING &
PANEL DIRECTORY FOR ALL PANELS (EXISTING OR NEW).
4. INTERIOR METAL PIPING SYSTEM SHALL BE BONDED TO THE GROUNDING ELECTRODE
SYSTEM.
5. GROUND AND NEUTRAL SHALL ONLY BE BONDED AT THE SERVICE EQUIPMENT AND
AT THE SEPARATELY DERIVED SYSTEM.
6. CONTRACTOR TO VERIFY THE INTEGRITY OF THE EXISTING GROUNDING ELECTRODE
SYSTEM AND SUBMIT FINDINGS TO ELECTRICAL ENGINEER FOR REVIEW.
7. THE INSULATION OF THE SPECIFIED CONDUCTORS SHALL BE THWN-2, XHHW-2 OR
THHN.
DETAIL NOTES: DETAIL KEYED NOTES:
RELOCATE EXISTING PANEL L202 TO NEW LOCATION AS SHOWN ON SHEET E300.
INTERCEPT AND EXTEND ALL EXISTING CIRCUITS TO NEW PANEL LOCATION.
EXISTING (2) SETS OF 2-1/2" C. STUBBED INTO TENANT SPACE. FIELD VERIFY EXACT
LOCATION.
INTERCEPT AND EXTEND EXISTING 4#4/0 + 1#4GND IN 2-1/2"C FOR FEEDER SERVING
PANEL TO NEW LOCATION.
A
SCALE:
NONE PANEL SCHEDULES 2 E400
ELECTRICAL
PARTIAL ONE-LINE
& PANEL
SCHEDULES
N.T.S.
B
C
ELECTRICAL CONTRACTOR SHALL INVESTIGATE THE EXISTING CONDITIONS
AND FUNCTIONALITY OF THE EXISTING PANELS AND TRANSFORMER TO BE
RELOCATED IN THIS SCOPE OF WORK, AND SHALL PROVIDE A BID ALTERNATE
FOR REPAIRING OR REPLACING NON-FUNCTIONAL AND/OR DEFECTIVE
EQUIPMENT.
BID ALTERNATE NOTE:
SCALE:
PROJECT NUMBER:
DRAWING TITLE
ISSUE / REVISION
51643
SOLARIS PLAZA
141 E MEADOW DRIVE
#202
VAIL, CO 81657
SHEET NUMBER
10.26.16 PERMIT ISSUE
960 Atlantic Ave.
Alameda, CA 94501
510 865 8663
mbharch.com
3371 Olcott Street
Copyright c 2016
info@acies.net
fx: (408) 522-5260
ph: (408) 522-5255
Santa Clara, CA 95054
ENGINEERING
EXP: 10/31/17
12.15.16 PLAN CHECK COMMENTS
(E) TENANT DISTRIBUTION DSL-A:
2000A, 3PH, 4W, 208/120V, 65K AIC