HomeMy WebLinkAboutB16-0481_M100_1482188442.pdfM100
N.T.S.
MECHANICAL GENERAL
NOTES, SYMBOLS &
SCHEDULES
MANUFACTURER
OUTSIDE AIR
NEW
OPPOSED BLADE DAMPER
MECHANICAL
MAXIMUM OVERCURRENT PROTECTION
MINIMUM CIRCUIT AMPACITY
HEATING, VENTILATING, AND AIR CONDITIONING
UP THRU ROOF
TYPICAL
UNLESS OTHERWISE NOTED
STAINLESS STEEL
PHASE
SUPPLY AIR (RISE/DROP)
RETURN AIR DUCT (RISE/DROP)
EXHAUST AIR DUCT (RISE/DROP)
CEILING DIFFUSER/SUPPLY REGISTER
EXHAUST REGISTER/GRILLE
RETURN REGISTER/GRILLE
FIRE DAMPER
MANUAL VOLUME DAMPER
FLEXIBLE CONNECTION
DUCT LINING (1" THICK UNLESS OTHERWISE NOTED)
RECTANGULAR DUCT ELBOW WITH TURNING VANES
SINGLE LINE DUCT BRANCH TAKE-OFF
( 4-WAY TYPICAL IF NO ARROWS)
(ARROWHEAD REPRESENTS NUMBER OF THROW)
CONDENSATE DRAIN
ZONE DAMPER
FIRE DAMPER
DUCT SMOKE DETECTOR
PROGRAMMABLE THERMOSTAT
FLEXIBLE DUCT
DUCT TRANSITION (RECTANGULAR TO ROUND)
CONTRACTOR.
DIAMETER
DOOR LOUVER
CONTRACTOR.
DOOR UNDERCUT (3/4" MINIMUM)
FURNISHED AND INSTALLED BY MECHANICAL
INSTALLED BY ELECTRICAL CONTRACTOR.
FURNISHED BY MECHANICAL CONTRACTOR AND
FURNISHED AND INSTALLED BY ELECTRICAL
AIR CONDITIONING
DESIGNATED NUMBER
CEILING
CONNECT/CONNECTION
BACK DRAFT DAMPER
BOTTOM OF DUCT
MECHANICAL EQUIPMENT DESIGNATION
DISCONNECT
DETAIL
CONTRACTOR
CUBIC FEET PER MINUTE
EXISTING
GAGE/GAUGE
FIRE DAMPER
EXHAUST FAN
EXTERNAL STATIC PRESSURE
CONTINUATION
AIR QUANTITY IN CFM
GENERAL CONTRACTOR
DESCRIPTION
LEGEND
TEMPERATURE
SENSIBLE
COMBINATION FIRE/SMOKE DAMPER
DEMOLITION
RELOCATE
POINT OF CONNECTION
VOLTS
DRAWING SCHEDULE
MECHANICAL FLOOR PLAN
M100 MECHANICAL GENERAL NOTES, SYMBOLS & SCHEDULES
M200
M101 MECHANICAL NOTES & SCHEDULES
MECHANICAL SPECIFICATIONS
M300
% :,17(5 )
DESIGN CONDITIONS
OUTSIDE: A. SUMMER: N/A - WINTER OPERATION ONLY
INSIDE: C. SUMMER: N/A - WINTER OPERATION ONLY
BASED ON LOCATION AND ASHRAE HANDBOOK. VAIL, CO
GENERAL NOTES
ALL FRESH AIR INTAKES SHALL BE LOCATED A MINIMUM OF 10'-0" FROM ANY
SANITARY VENT, EXHAUST FAN DISCHARGE AND FLUE OF OTHER FURNACES.
WHEN NECESSARY EXTEND VENT OR PROVIDE ADDITIONAL FRESH AIR INTAKE
DUCTWORK AS DIRECTED BY THE ENGINEER.
WHERE ANCHORAGE DETAILS ARE NOT SHOWN ON THE DRAWINGS, THE FIELD
INSTALLATION SHALL BE SUBJECT TO THE APPROVAL OF THE STRUCTURAL
ENGINEER.
THE CONTRACTOR SHALL COORDINATE HIS WORK WITH ALL TRADES AT THE
SITE. ANY COST TO INSTALL WORK TO ACCOMPLISH SAID COORDINATION
WHICH DIFFERS FROM THE WORK AS SHOWN ON THE PLANS SHALL BE
INCURRED BY THE CONTRACTOR. ANY DISCREPANCIES, AMBIGUITIES OR
CONFLICTS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT
DURING BID TIME FOR CLARIFICATION. ANY SUCH CONFLICTS NOT CLARIFIED
PRIOR TO BID SHALL BE SUBJECT TO THE INTERPRETATION OF THE ARCHITECT
AT NO ADDITIONAL COST TO THE OWNER.
AFTER ALL REQUIREMENT'S OF THE SPECIFICATIONS AND/OR THE DRAWINGS
HAVE BEEN FULLY COMPLETED, REPRESENTATIVES OF THE OWNER WILL
INSPECT THE WORK. THE CONTRACTOR SHALL PROVIDE COMPETENT
PERSONNEL TO DEMONSTRATE THE OPERATION OF ANY ITEM OR SYSTEM, TO
THE FULL SATISFACTION OF EACH REPRESENTATIVE. FINAL ACCEPTANCE OF
THE WORK WILL BE MADE BY THE OWNER AFTER RECEIPT OF APPROVAL AND
RECOMMENDATION OF ACCEPTANCE FROM EACH REPRESENTATIVE.
PENETRATION OF PIPES. CONDUITS, ETC., IN WALLS REQUIRING PROTECTED
OPENING SHALL BE FIRE STOPPED. FIRE STOP MATERIAL SHALL BE A U.L.
TESTED AND APPROVED ASSEMBLY APPROVED BY THE STATE FIRE MARSHALL.
WHEREVER A DISCREPANCY IN QUANTITY OR SIZE OF MECHANICAL EQUIPMENT
MATERIAL ARISES ON THE DRAWINGS AND/OR SPECIFICATIONS, THE
CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING AND INSTALLING ALL
MATERIAL AND SERVICES REQUIRED BY THE STRICTEST CONDITIONS NOTED
ON DRAWINGS AND/OR IN THE SPECIFICATION TO ENSURE COMPLETE AND
OPERABLE SYSTEMS AS REQUIRED BY THE OWNER AND ENGINEER.
IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO DO ALL CORING, SAW
CUTTING, PATCHING AND REFINISHING OF EXISTING WALLS AND SURFACES
WHEREVER IT IS NECESSARY FOR HIM TO PENETRATE FOR HIS WORK. ALL
OPENING SHALL BE SEALED TO MEET THE FIRE RATING OF THE PARTICULAR
WALL, FLOOR OR CEILING PENETRATED.
THE INSTALLATION SHALL COMPLY WITH THE FOLLOWING CODES ANY AND/OR
ALL REQUIREMENTS OF THE LEGALLY CONSTITUTED AUTHORITIES HAVING
JURISDICTION.
ALL INDICATED DIMENSIONS ARE APPROXIMATE AND ARE GIVEN FOR ESTIMATE
PURPOSES ONLY. BEFORE PROCEEDING WITH THE WORK, THIS CONTRACTOR
SHALL CAREFULLY CHECK AND VERIFY ALL DIMENSIONS, SIZES, REQUIRED
CLEARANCES, AND SHALL ASSUME FULL RESPONSIBILITY FOR THE FITTING OF
ALL EQUIPMENT AND MATERIALS HEREIN REQUIRED TO OTHER PARTS OF THE
WORK AND TO THE WORK OF OTHER TRADES.
CONTRACTOR SHALL COMPLY WITH ALL CONTRACT DOCUMENTS IN LAYING
OUT HIS WORK AND EQUIPMENT OR SPECIALTIES REQUIRING READING,
ADJUSTMENT, INSPECTION, REPAIRS, REMOVAL OR REPLACEMENT SHALL BE
CONVENIENTLY AND ACCESSIBLY LOCATED WITH REFERENCE TO THE FINISHED
BUILDING.
DUCTWORK SHALL BE FABRICATED AND INSTALLED IN ACCORDANCE WITH
CHAPTER 6 OF THE IMC, 2012 EDITION AND SMACNA, 2005 EDITION.
ALL BRACING OF DUCTS AND PIPING SHALL INSTALLED IN ACCORDANCE WITH
``SMACNA'' GUIDELINES AS FOR SEISMIC RESTRAINTS OF MECHANICAL AND
PLUMBING SYSTEMS. WHERE BRACING DETAILS ARE NOT SHOWN ON
DRAWINGS OR IN THE GUIDELINES, THE FIELD INSTALLATION SHALL BE TO THE
APPROVAL OF THE ARCHITECT AND THE STRUCTURAL ENGINEER.
INSTALLATION INSTRUCTIONS FOR ALL LISTED EQUIPMENT SHALL BE MADE
AVAILABLE TO THE BUILDING INSPECTOR AT THE TIME OF INSPECTION.
PROVIDE MANUAL BALANCE DAMPERS AT EVERY DUCT BRANCH WHETHER
SHOWN OR NOT.
ALL WIRING SHALL BE PROVIDED BY ELECTRICAL CONTRACTOR: COORDINATE
FOR PROVISION OF INFORMATION AND ANY DEVICES TO ELECTRICAL
CONTRACTOR.
PROVIDE SMOKE DETECTORS AND AUTOMATIC SHUTOFF FOR HVAC UNITS OR
COMBINATION THEREOF SUPPLYING AIR IN EXCESS OF 2000 CFM. WHERE FIRE
DETECTION OR ALARM SYSTEMS ARE PROVIDED FOR THE BUILDING, THE
SMOKE DETECTORS SHALL BE SUPERVISED BY SUCH SYSTEMS AND SHALL
ACTIVATE THE FIRE ALARM SYSTEMS. COORDINATE DUCT DETECTORS AND
AUTO SHUT OFF WITH THE FIRE ALARM SYSTEM, IF APPLICABLE
AIR CONDITIONING EQUIPMENT SHALL BE LABELED AS TO THE SPACE IT
SERVES. TEMPERATURE SENSORS SHALL BE LABELED AS TO UNITS AND/OR
ZONES CONTROLLED.
CONSTRUCTION TO CONFORM:
- 2015 INTERNATIONAL BUILDING CODE WITH LOCAL AMENDMENTS
- 2015 INTERNATIONAL MECHANICAL CODE WITH LOCAL AMENDMENTS
- 2015 IECC WITH LOCAL AMMENDMENTS
PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR
REQUIRED TO INSTALL COMPLETE AN OPERABLE MECHANICAL SYSTEMS AS
INDICATED ON THE DRAWINGS.
UNLESS OTHERWISE SHOWN LOCATE ALL ROOM THERMOSTATS 4'-0 ABOVE
FINISH FLOOR. NOTIFY THE ENGINEER OF ANY ROOMS WHERE THE ABOVE
LOCATION CANNOT BE MAINTAINED OR WHERE THERE IS A QUESTION ON
LOCATION.
STEEL
FITTINGS
DUCT CONSTRUCTION DETAIL & MINIMUM SHEET METAL THICKNESSES CHART
0.020 INCH (NO. 24 B&S GAGE)
0.025 INCH (NO. 22 B&S GAGE)
0.032 INCH (NO. 20 B&S GAGE)
0.040 INCH (NO. 18 B&S GAGE)
0.051 INCH (NO. 16 B&S GAGE)
(MINIMUM THICKNESS, NOMINAL)
0.022 INCH (26 GAGE, GALV.)
0.028 INCH (24 GAGE, GALV.)
0.052 INCH (18 GAGE, GALV.)
0.040 INCH (20 GAGE, GALV.)
0.034 INCH (22 GAGE, GALV.)
(MINIMUM THICKNESS, NOMINAL)
13 THROUGH 30 0.028 INCH (24 GAGE, GALV.)
SPIRAL SEAM DUCT
0.040 INCH (20 GAGE, GALV.)
0.034 INCH (22 GAGE, GALV.)
0.028 INCH (24 GAGE, GALV.)
0.022 INCH (26 GAGE, GALV.)
0.019 INCH (28 GAGE, GALV.)
(MINIMUM THICKNESS, NOMINAL)
13 THROUGH 18
19 THROUGH 28
37 THROUGH 52
29 THROUGH 36
MAXIMUM SIZE
31 THROUGH 54
55 THROUGH 84
THROUGH 12
(INCHES)
OVER 84
ROUND DUCTS
LONGITUDINAL SEAM DUCT
0.022 INCH (26 GAGE, GALV.)
0.052 INCH (18 GAGE, GALV.)
0.040 INCH (20 GAGE, GALV.)
0.034 INCH (22 GAGE, GALV.)
0.028 INCH (24 GAGE, GALV.)
(MINIMUM THICKNESS, NOMINAL)
0.034 INCH (22 GAGE, GALV.)
0.052 INCH (18 GAGE, GALV.)
0.040 INCH (20 GAGE, GALV.)
STEEL STEEL
MAXIMUM SIZE
(INCHES)
THROUGH 12
RECTANGULAR DUCTS
(MINIMUM THICKNESS, NOMINAL)
0.022 INCH (26 GAGE, GALV.)
STEEL ALUMINUM
MECHANICAL COMCHECK COMPLIANCE FORMS
M400
CONSTRUCTION OF BRANCH TAKEOFFS FROM MAIN
SQUARE BRANCH TAKEOFF
ROUND BRANCH TAKEOFF
DETAIL OF TURN VANES
1" 1"
DETAIL THIS SHEET
&216758&7,21 2) (/%2:6
&216758&7,21 2) (/%2:6
648$5( (/%2:
"W"
ROUND 90 ELBOW
5281' (/%2:
1 1/2W
USE THIS DESIGN
:+(5( 5281'
ON PLANS
ELBOWS ARE SHOWN
"W"
"W"
THIS SHEET
TURN VANES,
SEE DETAIL
1 1/2W
ON PLANS
ELS ARE SHOWN
:+(5( 5281'
USE THIS DESIGN
"W"
"W"
648$5( (/%2:
ON PLANS
ELBOWS ARE SHOWN
:+(5( 5281'
USE THIS DESIGN FLOW
TURN VANES-SEE
MAIN
"W"
AIR
MAIN
AIR
FLOW
"W"
THIS SHEET
:+(5( 648$5(
PLANS OR IF SPACE
ELS ARE SHOWN ON
USE THIS DESIGN
TURN VANES-SEE DETAIL
PERMIT INSTALLATION
CONDITIONS DO NOT
1" 1"
2" R
TYPICAL RECTANGULAR TO ROUND TRANSITION
SLOPE NOT TO EXCEED
1" IN 4"
TYPICAL RECTANGULAR TRANSITION
SLOPE NOT TO EXCEED
RECTANGULAR
BRANCH "W"
BRANCH
1"R
1" IN 4"
ROUND DUCT
SIGHT GLASS WITH
MOISTURE INDICATOR
INSTALLATION NOTES
1. ALL DUCTS SHALL BE CONSTRUCTED AND ERECTED IN
A NEAT AND WORKMANLIKE MANNER.
2. DUCTS SHALL BE CONSTRUCTED OF THE WEIGHTS,
GAGES AND MATERIAL SHOWN IN THE SCHEDULE ON
THESE DRAWINGS.
3. THE DIMENSION SHOWN FOR ALL DUCTS SHOWN IN
PLAN GIVE THE WIDTH FIRST AND THEN THE HEIGHT.
4. DUCT RISERS SHOULD BE SUPPORTED BY ANGLES AT
EVERY FLOOR.
5. AIR TURN SHALL BE INSTALLED IN ALL ABRUPT ELBOWS
TO PREVENT TURBULENCE.
6. DUCTS SHALL BE SECURELY ATTACHED TO THE
BUILDING CONSTRUCTION IN AN APPROVED MANNER.
7. DIVERGING TRANSITION PIECES SHALL BE MADE AS
GRADUAL AS POSSIBLE.
8. INSTALL FIRE DAMPERS IN ACCORDANCE WITH UL 555.
9. ACCESS PANELS SHOULD BE PLACED BEFORE AND/OR
AFTER EQUIPMENT INSTALLED IN THE DUCT.
10. DUCT AREA SHOULD NOT BE DECREASED MORE THAN
10 PERCENT WHEN OBSTRUCTIONS CANNOT BE
AVOIDED, AND THEN A STREAMLINED FITTING SHOULD
BE USED.
11. FLEXIBLE FABRIC CONNECTIONS (OR EQUAL) SHOULD
BE USED ON BOTH INLETS AND OUTLETS OF ALL FANS
AND AIR HANDLING UNITS.
12. JOINTS AND SEAMS OF SUPPLY DUCTS SHALL BE
FASTENED SECURELY AND MADE AIR TIGHT.
DUCT
MECHANICAL DETAILS M500
% :,17(5 )
SCALE:
PROJECT NUMBER:
DRAWING TITLE
ISSUE / REVISION
51643
SOLARIS PLAZA
141 E MEADOW DRIVE
#202
VAIL, CO 81657
SHEET NUMBER
10.26.16 PERMIT ISSUE
960 Atlantic Ave.
Alameda, CA 94501
510 865 8663
mbharch.com
3371 Olcott Street
Copyright c 2016
info@acies.net
fx: (408) 522-5260
ph: (408) 522-5255
Santa Clara, CA 95054
ENGINEERING
EXP: 10/31/17
12.15.16 PLAN CHECK COMMENTS
MECHANICAL COMCHECK COMPLIANCE FORMS
M401
12/19/16