HomeMy WebLinkAboutF16-0058_Equipment Data.pdf 0 OF go._/
12 ill 111
IS
if
Vail Fire 8 Emergency Services
09/29/16
western States
Fire Protection Co.
Pøee&4t 41ue4 4,,,,,e preizertv
7026 South Tucson Way
Centennial, CO 80112
(303) 792-0022 Fax (303) 792-9049
Fire Protection Equipment Submittal
Vail Cascade Remodel
1300 Westhaven Drive
Vail, CO 81657
WSFP #CS2893
Prepared by:
Bryan Horn,PE
Senior Project Manager
Western States Fire Protection Co.
7026 South Tucson Way
Centennial. CO 80112
(608)215-0568
Email:bryan.horn@wsfp.us
September 1,2016
olti OF 10
r
e,
Reliable
® Model F1 FR Seri
Quick Response '30 si' ;
Glass Bulb Sprink - 1(1°''°
Vail Fire&Emergency Services
09/29/16 G
Model F1 FR56 Sprinkler Types - ,
Standard Spray Upright
Standard Spray Pendent0 ill
Conventional Upright/Pendent
Vertical Sidewall :- --, -rn
Horizontal Sidewall —
Model Fl FR56 Recessed Sprinkler Types Upright Pendent Conventional
Standard Spray Pendent
Horizontal Sidewall ,;
Model Fl FR56 Concealed Sprinkler Types1r 4 -'
Standard Spray Pendent . �. ; :;;
Model F1FR42, F1FRXLH & F1FR28 Sprinkler r�
Types Vertical Sidewall Horizontal Sidewall Recessed
Standard Spray Upright Pendent/F1/F2
Standard Spray Pendent —
Model F1 FR40 Sprinkler Types
Standard Spray Pendent ' ., ,� . .., • '. , i
Model F1 FR42, F1 FR40, F1 FRXLH & F1 FR28 _
Recessed Sprinkler Types .. '. : 1 .• .
Standard Spray Pendent �` :,t ..
Model F1 FR56LL & F1 FR42LL NSF Certified Low Recessed Concealed Recessed
Lead Sprinkler Types Horizontal Sidewall Pendent Pendent/FP
Standard Spray Pendent with less than 0.25% Lead 41.1116 -
Content
Listing & Approvals ! .__=_.
The following organizations provide Listings or Approvals •.Yaw
for various Model Fl FR series sprinklers. See the Design CM
and Installation table in this Bulletin for information on XLH Upright XLH Pendent XLH Recessed
specific listings and approvals applicable to each sprin- Pendent F1/F2
kler.
1. Underwriters Laboratories Inc. and Certified for Product Description
Canada(cULus). Reliable Model F1FR series sprinklers
2. FM Approvals (FM) are quick-response automatic sprin-
klers with a glass bulb thermal element. •
3. Loss Prevention Certification Board (LPCB) A
4. VdS Schadenverhutung GmbH (VdS) Model F1FR series sprinklers are Stan
5. NSF Certified to NSF/ANSi Standard 61 Annex G dard Spray sprinklers, with the excep-
(NSF) tion of the Model F1 FR56 Conventional XLH Recessed
6. EC Certificate: 0786-CPD-40239 (RA1414), 0786- sprinkler which is an Old-style/Conven- Pendent FP
CPD-40251 (RA1425), 0786-CPD-40252 (RA1475) tional sprinkler.
(EC) The Model F1FR Series automatic sprinklers utilize a 3.0
mm frangible glass bulb.These sprinklers have demonstrat-
UL Listing Category ed response times in laboratory tests which are five to ten
Sprinklers,Automatic&Open(VNIV) times faster than standard response sprinklers. This quick
Quick Response Sprinkler response enables the Model Fl FR Series sprinklers to apply
water to a fire faster than standard-response sprinklers of the
same temperature rating.
The glass bulb consists of an accurately controlled amount
of special fluid hermetically sealed inside a precisely man-
ufactured glass capsule. This glass bulb is specially con-
structed to provide fast thermal response.
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
olti OF lo4,!
At normal temperatures, the glass bulb contains the fluid Model F1FR Series sprinklers must be in'
in both the liquid and vapor phases. The vapor phase can Reliable sprinkler installation wrench identifi
be seen as a small bubble. As heat is applied, the liquid and Installation Information table in this B
expands, forcing the bubble smaller and smaller as the liq- wrench may damage the sprinkler. A leak ti•
uid pressure increases. Continued heating forces the liquid can be obtained with a torque of 8 to 18 lb-ft
to push out against the bulb, causing the glass to shatter, Do not tighten sprinklers over the maximum re. ' 1g0]
opening the waterway and allowing the deflector to distrib- installation torque. Exceeding the maximum reco
ute the discharging water. installation torque may cause leakage orim� . ii An '8rricy Services
Model Fl FR Series sprinklers provide a wide range of op- sprinkler.
tions where quick-response, glass bulb sprinklers are used: Recessed Sprinklers
• Pendent, recessed pendent, upright, horizontal side- Model F1 FR Series Recessed sprinklers are to be installed
wall, and vertical sidewall deflectors as shown in Fig. 1, Fig. 2,or Fig.3, as applicable to the spe-
• K-factors of 2.8 (40 metric), 4.0 (57 metric), 4.2 (60 cific model being installed.The Recessed Escutcheon Data
metric), and 5.6 (80 metric) table in the Bulletin identifies the only recessed escutcheons
• Flush, recessed, and concealed installations that are permitted to be used with each Model Fl FR Series
See the Design and Installation Information table in this Recessed sprinkler.The use of any other recessed escutch-
Bulletin for information on the approvals and availability of eon will void all approvals and negate all warranties.
specific Model Fl FR series sprinkler configurations. Concealed Sprinklers
Model F1FR Recessed Pendent and Recessed Horizon- Model Fl FR Series Concealed Pendent sprinklers are to
tal Sidewall sprinklers are required to be used with Reliable be installed as shown in Fig.4 or Fig. 5, as applicable to the
Model F1, F2, or FP recessed escutcheons. See the Re- selected cover plate. Model F1 FR56 Concealed Pendent
cessed Escutcheon Data table in this Bulletin for listing and and Model F1 FR56LL Concealed Pendent sprinklers have
approval information with each specific Model F1FR series a factory-installed Model CCP cup. A protective cap is in-
sprinkler. Model Fl and F2 recessed escutcheons, shown in stalled at the factory that should remain on the sprinkler until
Fig. 1 and 3, are a friction fit assembly allowing for 3/4-inch the sprinkler is installed and should then be reinstalled on
(19mm) and 1/2-inch (12.7mm) of adjustment, respectively. the sprinkler until the cover plate is installed.The concealed
Model FP recessed escutcheons, shown in Fig. 2, provide a sprinkler assemblies are completed by the installation of a
1/2-inch (12.7mm)threaded adjustment. Model CCP push-on/thread-off cover plate assembly. The
Model F1 FR56 Concealed Pendent and Model F1 FR56LL cover plate and sprinkler cup assemblies are joined using
Concealed Pendent sprinklers are required to be used with a cover plate skirt with flexible tabs for threaded engage-
Model CCP cover plates.A standard profile Model CCP cov- ment. A choice of two Model CCP cover plate assemblies
er plate is available that provides up to 1/2-inch(12.7mm)of provides either 1/2-inch (13mm) or 5/8-inch (8mm)of cover
cover plate adjustment. In addition,a low profile Model CCP adjustment. Do not install Model F1FR Series Concealed
cover plate is also available that provides up to 5/16-inch Pendent sprinklers in ceilings which have positive pressure
(8.0mm)of cover plate adjustment. See the Design and In- in the space above.
stallation Information and Listed and Approved Temperature Model F1FR Series Concealed Pendent sprinklers require a
Ratings tables in this Bulletin for further information on ap- 2-5/8-inch (67mm) diameter hole to be cut in the ceiling. The
proved cover plate options. Model RC1 wrench is used to engage the sprinkler wrenching
Application surfaces and to install the sprinkler in the fitting. Remove the
Model Fl FR Series sprinklers are intended for use in protective cap to install the sprinkler,then reinstall the protective
accordance with NFPA 13, FM Property Loss Prevention cap until the cover plate is installed. When inserting or remov-
Data Sheets, and the requirements of the Authority Hav- ing the wrench from the sprinkler/cup assembly,care should be
ing Jurisdiction. Care must be exercised that the k-factor, taken to prevent damage to the sprinkler. Do not wrench any
temperature rating, deflector style, and sprinkler type are other part of the sprinkler/cup assembly. Installation is corn-
in accordance with the requirements of the applicable pleted by removing the protective cap from the sprinkler and
design and installation standards. In addition, Model pushing the cover plate onto the cup. Final adjustment is made
F1 FR Series sprinklers must be used in accordance with by hand turning the cover plate until the skirt flange makes full
their listings and approvals, as well as the information contact with the ceiling.Cover plate removal requires turning the
provided in this Bulletin. cover plate in the counter clockwise direction.After installation,
Installation inspect all sprinklers to ensure that there is a gap between the
Glass bulb sprinklers have orange bulb protectors or pro- cover plate and ceiling and that the four cup slots are open and
tective caps to minimize bulb damage during shipping,han- free from any air flow impediment to the space above.
dling and installation. Reliable sprinkler installation wrench- Concealed cover plate/cup assemblies are listed only for
es are designed to install sprinklers with bulb protectors in use with specific sprinklers.The use of any concealed cover
place.Remove the bulb protector at the time when the sprin plate/cup assembly other than the Reliable Model CCP with
kler system is placed in service for fire protection. Removal Model F1 FR56 Concealed Pendent and Model F1 FR56LL
of the bulb protector before this time may leave the bulb vul- Concealed Pendent sprinklers or the use of the Model CCP
nerable to damage. Remove bulb protectors by undoing the Concealed cover plate assembly on any sprinkler with which
clasp by hand. Do not use tools to remove bulb protectors. it is not specifically listed my prevent good fire protection and
will void all guarantees,warranties, listings and approvals.
2.
Technical Data: z � 4.
Sensitivity: Quick-response #
Thread Size: 1/2-inch NPT standard; ISO 7-R1/2 optional ,
Maximum Working Pressure: 175 psi (12 bar) - 100% Factory tested hydrostatically to 500 psi (3. 7.0 b
SIN RA1425, RA1414& RA1435 cULus listed for 250 psi (17 bar) ig07
Vail Fire&Emergency Services
Design and Installation Information 09/29/16
Nominal Nominal
Nominal Listings
Orifice Deflector/ Sprinkler Installation Approval
Model K factor Diameter Orientation Height Wrench SIN and Notes
US Metric inches mm inches mm
Approvals
Pendent 2.25 57 D RA1411 cULus 2
F1FR28 2.8 40 3/8 10 Recessed Pendent 2.25 57 GFR2 RA1411 cULus 2
Upright 2.25 57 D RA1421 cULus 1,2
Pendent 2.25 57 D RA1418 VdS
F1 FR40 4.0 57 3/8 10
Recessed Pendent 2.25 57 GFR2 RA1418 VdS
Pendent 2.25 57 D RA1413 cULus 2
F1FR42 4.2 60 7/16 10 Recessed Pendent 2.25 57 GFR2 RA1413 cULus 2
Upright 2.25 57 D RA1423 cULus 1,2
Pendent 2.25 57 D RA1410 cULus, NSF
F1FR42LL 4.2 60 7/16 10
Recessed Pendent 2.25 57 GFR2 RA1410 cULus, NSF
F1FRXLH Pendent 2.25 57 D RA1413 cULus 2
(F1FR42 4.2 60 7/16 10 Recessed Pendent 2.25 57 GFR2 RA1413 cULus 2
with Pintle) Upright 2.25 57 D RA1423 cULus 1,2
Pendent 2.25 57 D RA1414 cULus, FM, 1,2,3,4
LPCB,VdS, EC
Recessed Pendent 2.25 57 GFR2 RA1414 cULus, FM, 1,2,3,4
LPCB,VdS, EC
F1FR56 5.6 80 1/2 15 Concealed Pendent 2.25 57 RC1 RA1414 cULus,VdS,EC 5,6
Upright 2.25 57 D RA1425 cULus, FM, 1,2,3,4
LPCB,VdS, EC
"Conventional
2.25 57 D RA1475 LPCB,VdS, EC 4
(Pendent or Upright)"
Pendent 2.25 57 D RA1415 cULus, NSF 1
F1FR56LL 5.6 80 1/2 15 Recessed Pendent 2.25 57 GFR2 RA1415 cULus, NSF
Concealed Pendent 2.25 57 RC1 RA1414 cULus, NSF 6
Horizontal Sidewall 2.63 67 D RA1435 cULus, FM 1,2,3,7
F1FR56 5.6 80 1/2 15 Recessed Horizontal 2.63 67 GFR2 RA1435 cULus, FM 8
Sidewall
F1FR56 5.6 80 1/2 15 Vertical Sidewall 2 25 57 D RA1485 cULus, FM, 1,2,3,9
(Pendent or Upright) LPCB
(I)cULus Listed Corrosion Resistant sprinkler when ordered with available Polyester coating.
(2)cULus Listed Corrosion Resistant sprinkler when ordered with available Electroless Nickel PTFE plating.
(3)Available with FM approved Polyester coating in black or white.
(4)Available with LPCB and VdS approved Polyester coating.
(5)VdS and EC approvals of the F1FR56 Concealed Pendent sprinkler are for 155°F(68°C)temperature rated sprinklers only.VdS approved sprin-
klers must use Norbulb brand glass bulbs with the 1/2-inch(12.7mm)adjustment Model CCP cover plate only.
(6) Model F1FR56 Concealed Pendent and Model F1FR56LL Concealed Pendent sprinklers must be used with Reliable Model CCP cover plates,
available as either standard depth with 1/2-inch(12.7mm)of adjustment or low profile with 5/16-inch(8.0 mm)of adjustment.
(7)cULus Listing of the F1FR56 Horizontal Sidewall sprinkler is for Light and Ordinary Hazard occupancies only. FM Approval of the F1FR56 Hori-
zontal Sidewall sprinkler is for Light Hazard occupancies only.
(8)cULus Listing and FM Approval of the Fl FR56 Recessed Horizontal Sidewall sprinkler is for Light Hazard occupancies only.
(9)The F1FR56 Vertical Sidewall sprinkler is listed and approved for use only in Light Hazard occupancies. Minimum to maximum deflector to ceil-
ing distance shall be 4 inches to 12 inches(102mm to 305mm). LPCB approval of the Fl FR56 Vertical Sidewall sprinkler is for installation in the
Pendent position only.
3.
rF I/4%
Listed and Approved Temperature Ratings z � 4.
Ordinary Temp. Intermediate Temp. Hig I # J•
Classification Classification Class ,
Deflector/ 100°F(38°C)Max.Ambient _ 150°F(65°C) Max. Ambient 225°F(1 r `a IS
Model i.
Orientation Tedip. Temp. Ambient407
135°F(57°C) 155°F(68°C) 175°F(79°C) 200°F(93°C) 286°F(141°C)
Temp. Rating Temp. Rating Temp. Rating Temp. Rating Ra�ire&Emergency Services
Orange Bulb Red Bulb Yellow Bulb Green Bulb Blue BulI6
Pendent cULus
F1FR28 Recessed Pendent cULus --
Upright cULus
F1 FR40 Pendent VdS
Recessed Pendent VdS --
Pendent cULus
F1FR42 Recessed Pendent cULus --
Upright cULus
F1FR42LL Pendent -- cULus, NSF --
Recessed Pendent -- cULus, NSF --
Pendent cULus
F1FRXLH Recessed Pendent cULus --
Upright cULus
Pendent cULus, FM, LPCB,VdS, EC
Recessed Pendent cULus, FM, LPCB,VdS, EC --
F1FR56 Concealed Pendent* cULus cULus,VdS,EC cULus --
Upright cULus, FM, LPCB,VdS, EC
"Conventional LPCB,VdS, EC
(Pendent or Upright)"
Pendent -- cULus, NSF --
F1FR56LL Recessed Pendent -- cULus, NSF --
Concealed Pendent" -- cULus, NSF --
Horizontal Sidewall cULus, FM
F1FR56 Recessed Horizontal
Sidewall cULus, FM --
F1FR56 Vertical Sidewall(Pen cULus, FM, LPCB
dent or Upright)
* Model F1FR56 Concealed Pendent and F1 FR56LL Concealed Pendent sprinklers must be used with Reliable Model
CCP cover plates. For Ordinary Temperature Classification sprinklers use a 135°F (57°C) temperature rated cover
plate. For Intermediate Temperature Classification sprinklers use a 165°F(74°C)temperature rated cover plate.
Recessed Escutcheon Data
Listed and Approved Recessed Escutcheons
Deflector/ Model F1 Model F2 Model FP
Model Orientation (Fig. 1 &3) (Fig. 1 &3) (Fig.2) SIN
3/4-inch(19mm) 1/2-inch(12.7mm) 1/2-inch(12.7mm)
adjustment adjustment adjustment
F1FR28 Recessed Pendent cULus cULus cULus RA1411
F1FR40 Recessed Pendent VdS VdS VdS RA1418
F1FR42 Recessed Pendent cULus cULus cULus RA1413
F1FR42LL Recessed Pendent cULus, NSF cULus, NSF cULus, NSF RA1410
F1 FR42XLH Raraccarl Panrlant rl II i is rl II i is rl II i is RA 1 d1'
F1FR56 Recessed Pendent cULus, LPCB,VdS, cULus, FM, LPCB, cULus,VdS, EC RA1414
EC VdS, EC
F1 FR56LL Recessed Pendent cULus, NSF cULus, NSF cULus, NSF RA1415
F1FR56 Recessed Horizontal Sidewall cULus cULus, FM cULus RA1435
4.
olti OF 10
ilk.1 11
2 1/4'"HOLE D/A. J # P7
[57.2mm]
1 15/16"DIA
[49.2mm] Oj "LS
[__— — -=-I Vail Fire&Emergency Se ices
rs
olti OF 10
."4„,e
FACE OF FITTING S
TO FACE OF CEILING DIMENSION #%-ill ,T
Fl ESCUTCHEON /<��������A +
A' MAXIMUM RECESS = 1"[25.4mm] '
AT INIMUM RECESS = 3/879.5mmJ / F1 ESCUTCHEON O.?
F2 ESCUTCHEON 1` AT MAXIMUM RECESS = 1-3/8'[34.9mm] g0]
AT MAXI UM RECESS = 3/4"[19mmJ AT MINIMUM RECESS = 2-1/16'[52.4mm] Va ire&Emergen y Services
AT MINIM , RECESS = 3/8"[9.5mm]
Z
F2 ESCUTCHEON 0• 9/16
AT MAXIMUM RECESS = 1-5/87-41.3mm]
— 1/4" HOLE DIA. 1/8„ AT MINIMUM RECESS = 2-1/16'[52.4m
57.2mm]
[3.2mm]
1" X 1 " REDUCER
1 r-,— _r_ PI
_
I
nl{I, r, (1)
I i I 4"-12"
1 15/16" DIA.' 1 -iim _ IIII 1 III
/ xi - _---- [101.6mm-304.8mm]
[49.2mm] 11111 I'llllllll II 2 27/32" DIA. CEILING TO
I 041 [72.2mm] DEFLECTOR
JL_J All. 1.,,'y
' I
TURN COLLAR UNTIL
TIGHT AGAINST SPRINKLER
WRENCH BOSS. Fl ESCUTCHEON
3/4"[19mm] ADJUS ENT
F2 ESCUTCHEON
1/2[12.7mm] DJUSTMENT
013FGOJE
RECESSED HSW W/F1 OR ' ES'UTCHEON
(1) FM APPROVED FOR 4" — 6" [101.6MM — 15• MM] CEILING TO DEFLECTOR WITH F2 ONLY.
F..3
Model Fl FR56 Recessed Horizontal Si.-wall spri' ler with Model Fl or F2 escutcheon
1" x 7/2" REDUCING
TEE OR ELBOW
TR
- - - - - -+- - - - i{-F - - - _
I IT
111 1
n j r- - 2 5/8" PIA.
2 516" DIA — ' �� l' HOLE IN CE.NG
L J
CUP
r i l 'I
��.
I�� 01:vu lilts ' 1 1 " MAX.
�� iii ) FACE 0 FITTING
//////, FACE 0 CEILING
,`__1! if
1 �� I r������/J7-0 DIMENSIb
CEIL ' G _ Iii i, i ������ i
-----
/2" MAX. T - -
15/16"
COV'R ADJUSTMENT NN/1
COVER PLATE
ASSEMBLY3 5/16" DIA.
SPRINKLER /
CONCEALED, 1/2" ADJUSTMENT 017FGO1A
Fig.4
Model F1 FR56/F1 FR56LL Concealed Pendent sprinkler with standard depth
1/2-inch(12.7mm)adjustment-Model CCP cover plate
6.
olti OF 10
.r.4-14o
1" x 7/2" REDUCING Z 4.
TEE OR ELBOW .,
70
Oj 556P"
r 2 5/8" P A. Vail Fire&Emergency Se ices
2 5/16" I ' - HOLE * CEILING 09/29/16
CUP i . T,
I ,.....do
®3'aEI lilt 1 1/2 MAX.
tulii;.. • s.. FACE OF FITTING
""""A (' hn 0 TO FACE OF CEILING
,l ,`II��4. r://////= DIMENSION
'�\
CEILING ' -�
5/16" MAX. �tim' 3/4"
COVER ADJUSTv" T
CO PLATE t
ASSEMBLY
3 5/16" DIA.
SPRINKLER
CONCEALED, 5/1 6" ADJUSTMENT 017FG02A
/-
Fig.5-Model Fl FR56/F1 FR56LL Concealed Pendent sprinkler with low profile
5/16-inch(8.0mm)adjustment-Model CCP cover plate
Maintenance Material Data
The Model Fl FR Series sprinklers should be inspected and
the sprinkler system maintained in accordance with NFPA Frame: DZR Brass, QM Brass,or Low Lead Brass
25. Do not clean sprinklers with soap and water,ammonia or Deflector: CDA Alloy 220, 260, or 510
any other cleaning fluids. Remove dust by using a soft brush Load Screw\Pintle: CDA Alloy 360 or 544
or gentle vacuuming. Replace any sprinkler which has been
painted(other than factory applied)or damaged in any way. Cup: CDA Alloy 651 or 693
A stock of spare sprinklers should be maintained to allow Washer: Nickel Alloy 440 or 360, coated with PTFE
quick replacement of damaged or operated sprinklers. Adhesive Tape
Finishes (1) Bulb: Glass
Standard Finishes
Sprinkler Escutcheon Cover plate(')
Bronze Brass Chrome Ordering Information
Chrome Plated Chrome White Specify:
Polyester Plated 1. Sprinkler Model: [F1 FR28][F1 FR40][F1 FR42]
Coated(4)(5)(6) White Painted [F1 FR42LL][F1 FRXLH][F1 FR56][F1 FR56LL]
Speciai Application 1-inishes 2. Sprinkler Deflector/Orientation: [Pendent][Recessed
Sprinkler Escutcheon Cover plate(') Pendent][Upright][Conventional][Horizontal Sidewall]
Electroless Nickel Electroless Nickel
Bright Brass [Recessed Horizontal Sidewall][Vertical Sidewall]3 PTFE g 3. Sprinkler threads: [1/2-inch NPT][ISO 7-R1/2]
Bright Brass Bright Brass Black Plating 4. Sprinkler Temperature Rating: [135°F (57°C)][155°F
Black Plated Black Plated Black Paint
Black Paint(2)(6) Black Paint Off White (68°C)][175°F(79°C)][200°F(93°C)][286°F(141°C)]
Off White(2)(6) Off White Satin Chrome 5. Sprinkler Finish
Chrome Dull Chrome Dull 6. Escutcheon Model: [F1][F2][FP]
(1)Other finishes and colors are available on special order. Consult the 7. Escutcheon Finish (where applicable)
factory for details.Custom color painted sprinklers may not retain their 8. Cover plate Model: [standard profile CCP 1/2-inch
UL Corrosion resistance listing.Coverplate custom paint is semi-gloss, (12.7mm) adjustment][low profile CCP 5/16-inch
unless specified otherwise.
(2) cULus Listed only. (8.0mm) adjustment]
(3) 200°F(93°C)maximum. 9. Cover plate Temperature Rating: [135°F(57°C)for use
(4) cULus listed "corrosion resistance" applies to SIN Numbers RA1435 with Ordinary Temperature sprinklers][165°F (74°C)
(HSW), RA1485(VSW), RA1425 (Upright), RA1414 (Pendent) and for use with Intermediate Temperature sprinklers]
RA1415 (Pendent) in standard black or white. Corrosion resistance in
other polyester colors is available upon request. 10. Cover plate Finish
(5) FM Approvals finish as"Polyester coated"applies to SIN Number
RA1414,RA1435 and RA1425 in standard black or white. Note: When Model Fl FR Series Recessed sprinklers are ordered, the
(6)LPCB and VdS Approved finish applies only to RA1425, RA1414, RA1418 sprinklers and escutcheons are packaged separately.
(VdS)and RA1475.
(7)cULus listed Corrosion Resistant 7.
oto OF iv,!
Model Fl FR QR
Reliable
..c . ..,7
® K8.0 (115 metric)
Quick ResponseQ '6#
15/t
Coverage Sprinkl &EmergencyServrgs
2 16
A complete line of UL Listed and FM Approved
quick response extended coverage sprinklers
for light hazard applications. —x ,, ::.,> 4 h,Syx-
Horizontal Sidewall Sprinklers are approved
1 . -k` I (1 ' .for installation 4" 12" (102mm 305mm) ,., e
below the ceiling.
Model Fl FR QREC Sprinkler Types '
Extended Coverage Pendent
Extended Coverage Horizontal Sidewall Extended Coverage Recessed Extended
• EC-9 Deflector Pendent Coverage Pendent
Model Fl FR QREC Recessed Sprinkler Types
Recessed Extended Coverage Pendent
Recessed Extended Coverage Horizontal '
e,� —
' "' Aw .
Sidewall: 111611. 11111pr VI W• EC-9 Deflector /f ,
For Model Fl FR QREC 1/2" K 5.6 (80) Sprinkler Types
refer to Bulletin 028. Extended Coverage Recessed Extended
Horizontal Sidewall EC-9 Coverage Horizontal Sidewall
Approval Organizations EC-9
1. Underwriters' Laboratories, Inc. (UL)
2. Underwriters Laboratories of Canada (ULC)
3. Factory Mutual Approvals (FM)
4. NYC MEA 258-93-E
UL Listing Category The glass bulb consists of an accurately controlled amount
Sprinklers, Automatic & Open of special fluid hermetically sealed inside a precisely manu-
Quick Response Extended Coverage Sprinkler factured glass capsule. This glass bulb is specially con
structed to provide fast thermal response. The balance of
UL Guide Number parts are made of brass, copper and beryllium nickel.
VN IV The temperature rating of the sprinkler is identified by the
Note: Consult appropriate FM Installation Standards color of the glass bulb.
regarding limitations of room size, ceiling height and Application
minimum wall fire resistance rating.
Product Description Quick response sprinklers are used in fixed fire protec-
tion systems: Wet, Dry, Deluge or Preaction. Care must be
Reliable Models F1FR QREC and F1FR QREC Recessed exercised that the orifice size, temperature rating, deflector
Sprinklers are quick response sprinklers which combine the style and sprinkler type are in accordance with the latest
durability for a standard sprinkler with the attractive low pro- published standards of the National Fire Protection Asso-
file of a decorative sprinkler. ciation or the approving authority having jurisdiction. Quick
The Models Fl FR QREC and Fl FR QREC Recessed Auto- response sprinklers are intended for installation as specified
matic Sprinklers utilize a 3.0mm frangible glass bulb. These in NFPA 13.
sprinklers have demonstrated response times in laboratory
tests which are five times faster than standard response
sprinklers. This quick response enables these sprinklers to
apply water to a fire faster than standard response sprinklers
of the same temperature rating.
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
40 OF gr.
,del F1FR QREC Pendent Sprinkler c
De -ctor: EC
Insta .tion Wrench: Model D Sprinkler Wrencheb
Appro -I Type: Quick Response Extended Coverage-Light Hazard Occupancy o #x
Mk,IIMAIQf
Installation B ata: a ��i{ -rgency Services
I pprA ii i
Nominal
Nominal Thread Sprinkler Temperature Approval
Sprinkler
K-Factor p pIdentification
Orifice Size S Metric Length Rating Organizations Number(SIN)
17/32" 3/4" NPT 8.0 115 2.2" 135°F(57°C) 1,2,3,4 R4842 �,
(20mm) (R3/4) (56.1mm) 155°F(68°C) ,.
Model F1FR QREC Recesses Pendent Sprinkler
Deflector: EC
Installation Wrench: Model GFR2 irinkler Wrench
Approval Type: Quick Response Extended Coverage-Light Hazard Occupancy
Installation Data:
NominalSprinkler
Nominal Thread K-Factor Sprinkler Temp;rature Approv. 1)
Orifice Size Length Rati • Organiz. ions Identification
US Metric Number(SIN)
17/32" 3/4"NPT 8 0 115 2.2" 135°F(57°C 2, 3,4 R4842
(20mm) (R3/4) (56.1 mm) 155°F(68°C)
(1)Refer to escutcheon data table for dimensions.
Model Fl FR QREC Pendent and Recessed 'endent
Required Minimum Flow/Pressure
Maximu
Flow Rate Pressure Coverage ,rea2 1/4"HOLE DIA.
gpm(L/min) psi (bar) Width x ength [5Z 15mm]
1 15/16"DIA
ft.x ft. m x m) [49.21mm]
26 (98.4) 10.6(0,7) 16 x . (4.9 x 4.9) -
33 (125.0) 17.0(1,2) 18/ 18 (5.5 x 5.5) 1"x 3/4"REDUCER
TURN COLLAR - - OR
UNTIL TIGHT I"X 1/2"REDUCER
40 (151.4) 25.0(1,7) ! x 20 (6.0 x 6.0)(2) AGAINST SPRINKLER
WRENCH BOSS _\ _
(2)UL/ULC Listed for both Pendent and Recessed Pendent at FACE OF FITTING TO
135°F(57°C)only. II Emma II CEILING DIMENSION(2)
�s
ADJUSTMENT 0 00'V?J p�, A_ f[[3.18mm]
1}I
1-
i
2 27/32 DIA.
[72.23mm] 136FG028
2.
Model F1FR QREC Horizontal Sidewall Sprinkler z � 4.
Deflector: EC-9 #
Installation Wrench: Model D Sprinkler Wrench
Approval Type: Quick Response Extended Coverage-Light Hazard Occupancysg�7 o
I Installation DataVail Fire&Emergency Services
I - 09/29/16
Nominal Sprinkler
Nominal Thread K-Factor Sprinkler Approval(2) Temperature p e
Orifice Size Length Organizations Rating
Identification /;
US Metric Number(SIN)
135°F (57°C)
"/32" 3/4" NPT 8.0 115 2'85 1,2,3,4 155°F (68°C) R4862 li
(20mm) (R3A) (72.4mm) 175°F (78°C)
Model F1FR QREC Recessed Horizontal Sidewall Sprinkler
Deflector: EC-9
Installation Wrench: Model GFR2 Sprinkler Wrench
Approval Type: Quick Response Extended Coverage-Light Hazard Occupancy
Model Fl FR QREC Horizontal Sidewall and Recessed Horizontal Sidewall
Required Minimum Flow/Pressure
Flow Rate Pressure Maximum Approvalt2) Deflector to Ceiling
gpm(Umin) psi(bar) Coverage Area Temperature Organizations Dimension
UL FM UL FM Width x Length Rating(') Fl F2 Min.-Max.
ft.x ft.(m x m) Inches(mm)
26 (98.4) - 10.6 (0,7) - 16 x 16 (4.9 x 4.9) 135°F (57°C) 6-12 (153-305)
29 (109.8) 32 (121.1) 13.1 (0,9) 16.0 (1,1) 16x16 (4.9x4.9) 4-12 (102-305)
29 (109.8) 36 (136.3) 13.1 (0,9) 20.2 (1,4) 16 x 18 (4.9 x 5.5) 155°F (68°C) 1,2,4 1,2,3,4 4-12 (102-305)
32 (121.1) 40 (151.4) 16.0 (1,1) 25.0 (1,7) 16x20 (4.9x6.0) 4-12 (102-305)
36 (136.3) 44 (166.6) 20.2 (1,4) 30.2 (2,1) 16 x 22 (4.9 x 6.7) 175°F (78°C) 4-12 (102-305)
39 (147.6) 48 (181.7) 23.8 (1,6) 36.0 (2,5) 16 x 24 (4.9 x 7.3) 4-12 (102-305)
33(124.9) 17.0(1,2) 18 x 18(5.5 x 5.5) 135°F (57°C) 4-12(102-305)
39(147.6) 23.8(1,6) 14 x 26(4.3 x 7.9) 135°F (57°C) 4-6(102- 153)
40(151.4) 25.0(1,7) 18 x 22(5.5 x 6.7) 135°F (57°C) 4-12(102-305)
46(174.1) 33.1 (2,25) 14 x 26(4.3 x 7.9) 135°F (57°C) 1,2 1,2 6-12(153-305)
33(124.9) 17.0(1,2) 18 x 18(5.5 x 5.5) 155°F (68°C) 4-12(102-305)
40(151.4) 25.0(1,7) 18 x 22(5.5 x 6.7) 155°F (68°C) 4-12(102-305)
46(174.1) 33.1 (2,25) 14 x 26(4.3 x 7.9) 155°F (68°C) 6-12(153-305) _
(I)FM Approval of recessed sprinkler-135°F(57°C)and 155°F(68°C)only.
(2)Refer to escutcheon data table for dimensions.
FACE OF FITTING TO(2)
CEILING DIMENSION 1/8
\ 4"TO 12"
1\ TURN SPRING COLLAR,
l.UMI UNTIL TIGHT AGAINST
= , ii SPRINKLER WRENCH
BOSS.
1 15//B" IIIIIIIIIIII`'Ii 2 27/32"DIA.
DIA 000000U
1-11.1
c - I
RECOMMENDED
WALL HOLE A"(2)
2 1/4"DIAMETER
59FG02
ADJUSTMENT(2J 14826'02
olti OFpi
!
Installation Sprinkler Types
Quick response sprinkler are intended for installation as Extended Coverage Pendent114. d ,..„,
specified in NFPA 13. Quick response sprinklers and stan- Extended Coverage Sidewall # ,47dard response sprinklers should not be intermixed. • EC-9 HSW Deflector
The Model F1FR QREC Recessed Sprinklers are to be in- Recessed Extended Coverage Pendent 7.0
1.11.7
J "55b
stalled as shown. The Model Fl or F2 Escutcheons illus- Recessed Extended Coverage Sidewall igO]
trated are the only recessed escutcheons to be used with • EC-9 HSW Deflector
the Model F1FR QREC Sprinklers. The use of any other Finishes(') Vail Fire 09/29/16&Emergency Services
recessed escutcheon will void all approvals and negate all Standard Finishesto
warranties. Sprinkler Escutcheon
When installing Model F1FR QREC Sprinklers, use the Bronze Brass
Model D Sprinkler Wrench. When installing Model F1FR Chrome Chrome
QREC Recessed Pendent or Recessed Sidewall Sprinklers, 1White&Black Polyester)3) White
use the Model GFR1 Sprinkler Wrench. Any other type of pecial Application Finishes
wrench may damage these sprinklers. Sprinkler(2) Escutcheon
Glass bulb sprinklers have orange bulb protectors to Electroless Nickel PTFE(3) Electroless Nickel PTFE
minimize bulb damage during shipping, handling and in- Bright Brass Bright Brass
stallation. REMOVE THIS PROTECTION AT THE TIME THE Black Plating Black Plating
SPRINKLER SYSTEM IS PLACED IN SERVICE FOR FIRE Black Paint Black Paint
Off White Satin Off White
PROTECTION. Removal of the protectors before this time Chrome Chrome Dull
may leave the bulb vulnerable to damage. RASCO wrench- (1)Other colors and finishes are available on special order. Consult
es are designed to install sprinklers when covers are in factory for details.
place. REMOVE PROTECTORS BY UNDOING THE CLASP (2)FM Approval limited to bronze,bright and satin chrome plated,
BY HAND. DO NOT USE TOOLS TO REMOVE THE PRO- and polyester coated only.
mcULus Listed Corrosion Resistant Sprinkler
TECTORS.
Maintenance Escutcheon Data
The Models Fl FR QREC and Fl FR QREC Recessed Sprin- Face of Fining
klers should be inspected and the sprinkler system main- Model°n Adjustment Dimension to Ceiling or
tained in accordance with NFPA 25. Do not clean sprinklers Wall Dimension
with soap and water, ammonia or any other cleaning fluids. Fl 3/4"(19mm) 3/4"(19mm)�(2 s'(5mm)
I Remove dust by gentle vacuuming. Replace any sprin-
1 /6 (35mm) 15/16"(24mm)
kler which has beenpainted (other than factoryapplied) or F2 1/2" 13mm 1" (25mm)1) 3/,s'(5mm)
pp ) ( ) 19/16"(40mm))2) 11/16' (18mm)
damaged in any way. A stock of spare sprinklers should be EC Pendent
maintained to allow quick replacement of damaged or op- (2)Ec Hsw
erated sprinklers. Prior to installation, sprinklers should be
maintained in the original cartons and packaging until used Ordering Information
to minimize the potential for damage to sprinklers that would Specify:
cause improper operation or non-operation. 1. Sprinkler Model: Fl FR QREC
2. Sprinkler Type
Temperature Ratings 3. Temperature Rating
Sprinkler Maximum 4. Sprinkler Finish
Classification Rating Ambient Temp. Bulb 5. Thread Type: [3/4" NPT] [ISO 7-1R3/4]
°F °C °F °C Color 6. Escutcheon Type
Ordinary 135 57 100 38 Orange 7. Escutcheon Finish (where applicable)
Ordinary 155 68 100 38 Red I Note: When Model F1FR Recessed sprinklers are or-
Intermediate 175 79 150 66 Yellow p
dered, the sprinklers and escutcheons are pack-
Maximum Working Pressure aged separately.
175 psi(12 bar)
SIN R4842&R4862 cULus listed for 250 psi(17 bar)
100% Factory tested hydrostatically to 500 psi (34.5 bar)
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association,Factory
Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years,and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States,Canada and foreign countries.
Manufactured b
Reliable Automatic Sprinkler Co.,Inc. h Recycled
Reliabi ® (800)431-1588 Sales Offices % Paper
(800)848 6051 a Sales Fax
(914)829 2042 Corporate Offices Revision lines indicate updated or new data.
www.reliablesprinkler.com Internet Address EG.Printed in U.S.A.12/15 P/N 9999970142