SYSTEM NO.C-AJ-3095 SYSTEM NO.W-L-1056
MI
ANSI/UL 1479(ASTM E814) CAN/UCL S115 ANSI/UL 1479(ASTM E814) CAN/UCL S115 cif,. +7},
F RATING-3 HR F RATING-3 HR F RATING-2 HR F RATING-2 HR
T RATINGS-0,1/2&3/4 HR(SEE 3) FT RATINGS-0,1/2&3/4 HR(SEE 3) T RATING-0 HR FT RATING-0 HR ' 107'
FH RATING-3 HR L RATING AT AMBIENT FH RATING-2 HR
FHT RATINGS-0,1/2&3/4 HR(SEE 3) LESS THAN 1 CFM/SQ FT FHT RATING-0 HR _ 09/16/16
L RATING AT 400 F- 4 CFM/SQ FT L RATING AT AMBIENT
LESS THAN 1 CFM/SQ FT
L RATING AT 400 F- 4 CFM/SQ FT
3 A 3 -
5 I I1B 1 —5 THE RITZ CARLTON CLUB VAILA
�A 728 LIONSHEAD CIRCLE
'� , 112
2 • II 3B VAIL,CO 81657
A. 7 � % � Rev: Date: Description: By:
NIB
I 2 8/19
i
1 6/2/16/16 PRELIMINARYREVISION1 JND
4
- -
2 A
�• %/
SECTION A-A 2
3C Ill8/24/16
3C CONSTRUCTION SL
A 3A
4 8/29/16 PERMIT SET SL
SECTION A-A
1. FLOOR OR WALL ASSEMBLY-MIN 2-1/2 IN.(64 MM)THICK REINFORCED LIGHTWEIGHT OR NORMAL 1. WALL ASSEMBLY-THE FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY
WEIGHT(100-150 PCT OR 1600 2400 KG/M3)CONCRETE FLOOR OR MIN 3 IN.(76 MM)THICK SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER SPECIFIED IN
REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE WALL.WALL MAY ALSO BE THE INDIVIDUAL U300 OR U400 SERIES WALL AND PARTITION DESIGNS IN THE UL
CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*.MAX DIAM OF OPENING IS 6 IN.(152 FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING
MM). CONSTRUCTION FEATURES:
SEE CONCRETE BLOCKS(CAZT)CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF
MANUFACTURERS. A. STUDS-WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL
2. SLEEVE-(OPTIONAL)-NOM 6 IN.(152 MM)DIAM(OR SMALLER)SCHEDULE 1 0(OR HEAVIER)STEEL CHANNEL STUDS.WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN.(51 BY 102 I
PIPE CAST OR GROUTED INTO FLOOR OR WALL ASSEMBLY,FLUSH WITH FLOOR OR WALL MM)LUMBER SPACED 16 IN.(406 MM)OC.STEEL STUDS TO BE MIN 2-1/2 IN.
SURFACES OR EXTENDING A MAX 3 IN.(76 MM)ABOVE THE FLOOR OR BOTH SURFACES OF THE (64 MM)WIDE AND SPACED MAX 24 IN.(610 MM)OC.
WALL.IF THE STEEL SLEEVE EXTENDS ABOVE THE FLOOR OR BOTH SURFACES OF THE WALL,THE B. GYPSUM BOARD*-TWO LAYERS OF NOM 5/8 IN.(16 MM)THICK GYPSUM
T RATING OF THE FIRESTOP SYSTEM IS O HR. WALLBOARD,AS SPECIFIED IN THE INDIVIDUAL WALL AND PARTITION DESIGN. PLANS PREPARED BY:
3. CABLES-AGGREGATE CROSS-SECTIONAL AREA OF CABLES IN OPENING TO BE MIN 25 PERCENT
TO MAX 45 PERCENT OF THE AGGREGATE CROSS-SECTIONAL AREA OF THE OPENING.CABLES TO MAX DIAM OF OPENING IS 18-314 IN.(476 MM). C E N T E R L I N E
BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.ANY COMBINATION OF 2. THROUGH PENETRANTS-ONE METALLIC PIPE OR TUBING TO BE INSTALLED
THE FOLLOWING TYPES AND SIZES OF METALLIC CONDUCTOR OR FIBER OPTIC CABLE MAY BE EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. SOLUTIONS
USED: PIPE OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL Advancing Wireless Networks
A. MAX 500 KCMIL SINGLE COPPER CONNECTOR POWER CABLE WITH THERMOPLASTIC ASSEMBLY.THE ANNULAR SPACE SHALL BE MIN 3/4 IN.(19 MM)TO MAX 4-1/2 IN.
INSULATION AND POLYVINYL CHLORIDE(PVC)JACKET.WHEN SINGLE COPPER (114 MM).THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES OR TUBING MAY 16360 TABLE MOUNTAIN PARKWAY
CONDUCTOR POWER CABLE IS USED,T,FT AND FTH RATING IS 0 HR. BE USED: Golden,CO 80403
A. MAX 350 KCMIL SINGLE CONDUCTOR POWER CABLES WITH EITHER ALUMINUM OR 12 IN
STEEL PIPE A. -NORN .
COPPER CONDUCTORS AND CROSS-LINKED POLYETHYLENE(XPLE)INSULATION.WHEN (305MM)DIAM(OR SMALLER))SCHEDULE 10(OR 303-993-3293
SINGLE ALUMINUM CONDUCTOR POWER CABLE IS USED,T RATING ISO HR.WHEN HEAVIER)STEEL PIPE. WWW.CENTERLINESOLUTIONS.COM
SINGLE COPPER CONDUCTOR POWER CABLE IS USED,T,FT AND FTH RATING IS 1/2 HR. B. IRON PIPE-NORN 12 IN.(305 MM)DIAM(OR SMALLER)CAST OR DUCTILE IRON I
B. MAX 300 PAIR NO.24 AWG COPPER CONDUCTOR TELECOMMUNICATION CABLES WITH PIPE.
POLYVINYL CHLORIDE(PVC)INSULATION AND JACKET MATERIAL.WHEN C. COPPER TUBING-NORN 4 IN.(102 MM)DIAM(OR SMALLER)TYPE L(OR LICENSURE NO:
TELECOMMUNICATION CABLE IS USED,T,FT AND FTH RATING ISO HR. HEAVIER)COPPER TUBING.
C. MAX THREE COPPER CONNECTOR NO.6 AWG CABLE WITH POLYVINYL CHLORIDE(PVC) D. COPPER PIPE-NORN 4 IN.(102 MM)DIAM(OR SMALLER)REGULAR(OR
INSULATION AND JACKET MATERIAL.WHEN MULTI-CONNECTOR POWER CABLE IS USED, HEAVIER)COPPER PIPE.
T RATING ISO HR.
D. MAX 7/C COPPER CONDUCTOR NO.12 AWG MULTICONDUCTOR POWER AND CONTROL 3. FIRESTOP SYSTEM-THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING:
CABLES WITH PVC OR CROSS-LINKED POLYETHYLENE(XLPE)INSULATION AND PVC A. METALLIC SLEEVE-CYLINDRICAL SLEEVE FABRICATED FROM MIN 0.028 IN.
JACKET.WHEN MULTICONDUCTOR POWER AND CONTROL CABLE IS USED,T,FT AND THICK(24 GAUGE)GALV SHEET STEEL AND HAVING A MIN 1 IN.(25 MM)LAP
FTH RATING IS 3/4 HR. ALONG THE LONGITUDINAL SEAM.LENGTH OF STEEL SLEEVE TO BE 1 IN.(25
E. MULTIPLE FIBER OPTICAL COMMUNICATION CABLES JACKETED WITH PVC AND HAVING MM)MORE THAN THE OVERALL THICKNESS OF THE WALL SUCH THAT,WHEN
A MAX OUTSIDE DIAM OF 1/2 IN.WHEN FIBER OPTIC CABLE IS USED,T,FT AND FTH
RATING IS 3/4 HR. INSTALLED IN CIRCULAR OPENING,THE ENDS OF THE SLEEVES PROJECT 1/2
F. MAX 3/C COPPER CONDUCTOR NO.12 AWG WITH BARE ALUMINUM GROUND,POLYVINYL IN.(13 MM)FROM EACH SURFACE OF THE WALL.THE DIAM OF THE OPENINGS
CHLORIDE(PVC)INSULATED STEEL,METAL-CLAD CABLE..WHEN MC CABLE IS USED,T, CUT IN THE GYPSUM WALLBOARD LAYERS ON EACH SIDE OF THE WALL
FT AND FTH RATING IS 0 HR. ASSEMBLY TO BE 1-1/2 TO 6 IN.(38 TO 152 MM)LARGER THAN OUTSIDE DIAM
H. MAX 3/C WITH GROUND 2/0 AWG COPPER CONDUCTOR SER CABLE WITH OF PIPE SUCH THAT,WHEN THE SLEEVE IS INSTALLED,A 314 TO 4-1/2 IN.(19
CROSS-LINKED POLYETHYLENE(XLPE)INSULATION AND POLYVINYL CHLORIDE TO 114 MM)ANNULAR SPACE WILL BE PRESENT BETWEEN THE STEEL SLEEVE
(PVC)WHEN SER CABLE IS USED,T,FT AND FTH RATING ISO HR. AND THE PIPE AROUND THE ENTIRE CIRCUMFERENCE OF THE PIPE.SLEEVE
I. MAX RG/U COAXIAL CABLE WITH POLYETHYLENE(PE)INSULATION AND POLYVINYL INSTALLED BY COILING THE SHEET STEEL TO A DIAM SMALLER THAN THE
CHLORIDE(PVC)JACKET HAVING A MAX OUTSIDE DIAMETER OF 1/2 IN.WHEN THROUGH OPENING,INSERTING THE COIL THROUGH THE OPENINGS AND ALL SCALES ARE SET FOR 24'k36"SHEET
COAXIAL CABLE IS USED,T RATING ISO HR.
J. FIRE RESISTIVE CABLES'-MAX 1-1/4 IN.(32 MM)DIAM SINGLE CONDUCTOR OR RELEASING THE COIL TO LET IT UNCOIL AGAINST THE CIRCULAR CUTOUTS IN DRAWN BY: CHK BY: APV BY:
MULTI CONDUCTOR TYPE ML CABLE.A MIN 1/8 IN.(3 MM)SEPARATION SHALL BE THE GYPSUM WALLBOARD LAYERS.
MAINTAINED BETWEEN ML CABLES AND ANY OTHER TYPE OF CABLE.WHEN FIRE B. PACKING MATERIAL-MIN 4 IN.THICKNESS OF MIN 4.0 PCF(64 KG/M3)MINERAL WOOL JND SL KS
RESISTIVE CABLES'ARE USED,T,FT AND FTH RATING IS 0 HR. BAIT INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM PACKING
K. THROUGH PENETRATING PRODUCT'-ANY CABLES,METAL-CLAD CABLE+OR MATERIAL TO BE RECESSED FROM BOTH SURFACES OF WALL AS REQUIRED TO
ARMORED CABLE+CURRENTLY CLASSIFIED UNDER THE THROUGH PENETRATING ACCOMMODATE THE REQUIRED THICKNESS OF FILL MATERIAL.
PRODUCTS CATEGORY. C. FILL,VOID OR CAVITY MATERIAL'-SEALANT-MIN 3/4 IN.(19 MM)THICKNESS OF TIGHTLY
SEE THROUGH PENETRATING PRODUCT(XHLY)CATEGORY IN THE FIRE PACKED FILL MATERIAL APPLIED WITHIN THE ANNULUS,FLUSH WITH THE ENDS OF THE
RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS. STEEL SLEEVE.ADDITIONAL FILL MATERIAL TO BE INSTALLED TO THE OUTER ����
4. PACKING MATERIAL-MIN 2 IN.(51 MM)THICKNESS OF MIN 4 PCF(64 KG/M3)MINERAL WOOL PERIMETER OF THE STEEL SLEEVE AT ITS EGRESS FROM THE OPENING.
BAIT INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM.PACKING
MATERIAL TO BE RECESSED 1/2 IN.(13 MM)FROM TOP SURFACE OF FLOOR OR FROM BOTH HIL TL CONSTRUCTION CHEMICALS,DIV OF HIL TL INC-FS-ONE SEALANT OR FS-ONE MAX
SURFACES OF WALL TO ACCOMMODATE THE FILL MATERIAL.IF THE STEEL SLEEVE(ITEM 2) LNTUMESCENT SEALANT
EXTENDS ABOVE THE TOP OF THE FLOOR,THE PACKING MATERIAL SHALL BE FLUSH WITH * INDICATES SUCH PRODUCTS SHALL BEAR THE UL OR CUL CERTIFICATION MARK FOR
THE BOTTOM SURFACE OF THE FLOOR. JURISDICTIONS EMPLOYING THE UL OR CUL CERTIFICATION(SUCH AS CANADA),
5. FILL,VOID OR CAVITY MATERIAL'-SEALANT-MIN 1/2 IN.(13 MM)THICKNESS OF FILL MATERIAL RESPECTIVELY. Sheet Number:
APPLIED WITHIN THE ANNULUS,FLUSH WITH TOP SURFACE OF FLOOR OR WITH BOTH
SURFACES OF WALL.
HILITL CONSTRUCTION CHEMICALS,DIV OF HILITL INC-FS-ONE SEALANT OR FS-ONE MAX
LNTUMESCENT SEALANT D1
INDICATES SUCH PRODUCTS SHALL BEAR THE UL OR CUL CERTIFICATION MARK FOR
JURISDICTIONS EMPLOYING THE UL OR CUL CERTIFICATION(SUCH AS CANADA),RESPECTIVELY.
1 FIRE-RATED DECK PENETRATION 2 FIRE-RATED WALL PENETRATION 3 NOT USED