HomeMy WebLinkAboutB11-0496 Kitchen Exhaust CR documents ARCHITECTURE
URBAN DESIGN
INTERIOR DESIGN
January 3o, 2017
JR Mondragon
Town of Vail
42 W. Meadow Drive
Vail, CO 81657
RE: Reference : B11-o496 Strata Vail Permit Drawings Revision 32
Dear JR:
• We are submitting to the TOV building department for review and approval the following :
• Residential Kitchen Hoods Exhaust Air Requirements :
1. Refer to the Attached BCER Residential Kitchen Hoods Letter of Understanding.
2. Refer to the attached Testing and Balancing Report performed by Elite Balancing.
Enclosures :
• BCER Residential Kitchen Hoods Letter of Understanding
• Elite Balancing TAB Report.
• TOV Inspection Notice 2101063320011.
Sincerely,
Of COL
Du ,70�
ALEJANDR0
,LIANES
202672
s
kbArC4 0114>
,. .
1/30/2017
OZ Architecture, Inc.
1/3o/2017
Page 1 of 1
Gdzoo7\17oo4 Lionshead Inn\CA\Permits\Kitchen Hoods\TOV JR Mondragon Kitchen Exhaust Air Hoods Letter DENVER PHONE: 303.861.5704
2o17_013o.docx 3003 LARIMER STREET FAX 303.861.9230
DENVER BOULDER COLORADO SPRINGS DENVER,COLORADO 80205 WWW.OZARCH.COM
„,417-7• 3
•
Inspection Summary
TOWN OF VAIL '
Inspection Result: Fail
Inspector: Charlie Davis
Permit Type Inspection Type Address
Construction Mechanical Final 705 W LIONSHEAD CIR(210106332001) (2101063320011)
Inspection Date: 12/06/2016
Permit#: B11-0496.004
TMK: 2101063320011
Applicant name: The Wells Partnership- Lisa
Email: lisa@wellspartnership.com
Phone:
Comments:
1. Units B101, B102, B103 Provide CFM Rates for range hood, more or less than 400 CFM
Provide balance report for system. Supply and returns in spaces not verified provide approved plans.
2. Inspector Signature
3. Applicant Signature
w
BCER Response
The residential kitchen hoods in Units B101,B102 and B1.03 are specified Architecturally as 600 CFM
hoods. The make-up air for all residential kitchen hoods over 400 CFM on this project is through the
outside air ventilation duct connected to the return air side of the Fan Coil Units.
Brook Corning-BCER
December 6,2016
BCER .
—
Pnelneeding--
January 25, 2017
JR Mondragon
Town of Vail Chief Building Inspector
jmondragon@vailgov.com
RE: STRATA VAIL RESIDENTIAL KITCHEN HOODS LETTER OF UNDERSTANDING
Dear Mr. Mondragon:
As we discussed last week,the third party inspectors have written up the kitchen hood with the following
comments:
Units B101, BI02, B103 Provide CFM Rates for range hoods, more or less than 400 CFM. Provide
balance report for the system. Supply and returns in spaces not verified provide approved plans. "
BCER has witnessed the testing of six different hoods on the project, from the smaller condos to the larger
penthouse units. The test results are included in the attached test and balance report. All of the hoods tested
are greater than 400 CFM.
The question behind the inspection comment relates to the 2012 IMC section 505.2, which states that
residential exhaust hood systems capable of exhausting in excess of 400 CFM shall be provided with make-up
air at a rate approximately equal to the exhaust air rate...
The design for this project utilizes the ventilation duct serving the fan coil units. The ventilation duct connects
to the return side of the fan coil units and provides tempered OSA to the space for people ventilation and kitchen
hood make-up.
To make sure that the makeup air system is providing enough air, proof of flow was taken using indoor to
outdoor pressure differential readings as provided by the Test and Balance Contractor. The TAB report shows
minimal decrease in space pressure when the kitchen hoods are run through various speeds. This
demonstrates the make-up for the kitchen hood is being drawn through the ventilation duct at basically the
same rate as is required for the hood exhaust.
The design for people ventilation as required by the 2012 IMC section 401.2 is to operate the FCU fans(and
therefore the ventilation)continuously. In order to provide this ventilation,the ventilation duct must be open
and operational 24/7. Therefore,the ventilation duct cannot be provided with a means of closure as required
by section 505.2. During the balancing procedure units were tested with the FCU fans at low speed or off.
The pressure differentials were not affected when the kitchen hoods where operating.
Mr. JR Mondragon
January 25, 2017
Page 2
Through actual field verification the required make-up air serving the residential units is adequate and will not
cause infiltration from the exterior of the building, excessive negative pressures in the units and will not draw
air in from the corridor during operation of the kitchen hoods.
The Test and Balance Report demonstrates that the ventilation air is approximately equal to the exhaust air(by
the pressure differential test), and the code requires that the ventilation air be 100%available for the
occupants, so the isolation device will be open continuously and therefore not needed.
Thank you. Please let us know if you have any questions.
Sincerely,
BCER ENGINEERING,INC.
'Rk" Q L10 111
e4
- � ��p rd •' .'
Michael D. Schroeder, P.E. I C�: ! / �:0• 1
Associate Principal- Director of Engineering . '. 329 3 ff,:,
'1 . •� +r....
MDS: bec f1 0, 1 L
s �,t li
C: Jeff Mapp—OZ Architecture 1�k � ��-
1 l
�R0000.- 'ZS'I L
Final Test and Balancing Report by Elite Balancing
COLORADO SPRINGS OFFICE CORPORATE OFFICE TAMPA OFFICE
10807 NEW ALLEGIANCE DR,SUITE 400 5420 WARD ROAD,SUITE 200 4511 NORTH HIMES AVE,SUITE 200
COLORADO SPRINGS,COLORADO 80921 ARVADA,COLORADO 80002 TAMPA,FLORIDA 33614
719.533.1112 303.422.7400 813.449.4324
www.BCER.com
ELITE
NEte BALANCING N-413
2029 Kinnikinnick Dr. • Erie, CO 80516•Phone: (720) 523-0209 • Fax: (720)523-0225 • http://www.elitebalancing.com
Certified Test, Adjust, and Balance Report
Strata Vail Kitchen Hood Testing
Address: 705 W. Lionshead Circle
Vail, CO
Date: 1/19/2017
Job Number: 2017-649
Mechanical Engineer: BCER
General Contractor: PCL
Submitted & Certified By: ancin
e� 440
Elite Balancing LLC EiFihoZiejimai0
Certification Number: 3502 KEVIN L.SHAW
Cp f RGATION
3502
Certification Exp Date: March 31, 2018ne
NEBB Qualified Certified Professional: Kevin Shaw 9 !rut,
The data presented in this report is a record of system measurements and final
adjustments that have been obtained in accordance with the current edition of the
NEBB PROCEDURAL STANDARDS FOR TESTING, ADJUSTING, AND BALANCING
OF ENVIRONMEMTAL SYSTEMS. Any variances from design quantities, which
exceed NEBB tolerances, are noted in the Test-Adjust-Balance Report Project
Summary.
Revision
Number Date Description -
1 1/19/17 Final Report Issued
Elite Balancing, LLC 1/6
ELITE
N� B BALANCING NEt6g
2029 Kinnikinnick Dr. • Erie, CO 80516•Phone: (720)523-0209 • Fax: (720) 523-0225 • http://www.elitebalancing.com
Table of Contents
Instrument Calibration Report 3
Abbreviations Page 3
Report Summary/ Remarks 4
Fan Reports 5
Elite Balancing, LLC 2/6
ELITE
N'E B BALANCING Ng g
2029 Kinnikinnick Dr. • Erie, CO 80516•Phone: (720) 523-0209 • Fax: (720) 523-0225 • http://www.elitebalancing.com
Instrumentation
Rotation Measurement Extech 461995
Temperature Measurement Extech HD500
Electrical Measurement Fluke 335
Air Pressure Measurement Alnor EBT731
Air Velocity Measurement Alnor EBT731
Air Volume Measurement Alnor EBT731
Humidity Measurement Extech HD500
Hydronic Pressure Measurement Alnor HM670
Abbreviations
A Amperage FCU Fan Coil Unit NIC Not In Contract
A/C Air Conditioning FG Floor Grille NO Normally Open
AHU Air Handling Unit FILT Filter OBD Opposed Blade Damper
B Boiler FLA Full Load Amps OSA Outside Air
BD Backdraft Damper FPM Feet per Minute PH Phase
BP Boiler Pump/Booster Pump FPVAV Fan Powered Variable Air Volume PSI Pounds per Square Inch
BTUH British Thermal Unit FSD Fire Smoke Damper RA Return Air
CAV Constant Air Volume ftH2O Feet of Water Column RF Return Fan
CD Ceiling Diffuser FURN Furnace RG Return Grille
CFM Cubic Feet per Minute GC General Contractor RH Relative Humidity
CH Chiller GPM Gallons per Minute RPM Revolutions per Minute
CP Condenser Pump HP Heat Pump RTU Roof Top Unit
CRAC Computer Room Air Conditioner HP Horsepower SA Supply Air
CT Cooling Tower HVAC Heating,Ventilating&Air Conditioning SF Supply Fan
CUH Cabinet Unit Heater HW Heating Water SF Service Factor
CW Chilled Water HWP Heating Water Pump SP Set Point
CWP Chilled Water Pump HWR Heating Water Return SP Static Pressure
CWR Chilled Water Return HWS Heating Water Supply SW Side Wall
CWS Chilled Water Supply inH2O Inches of Water Column TA Transfer Air
DB Dry Bulb LAT Leaving Air Temperature TDH Total Dynamic Head
DDC Direct Digital Control LWT Leaving Water Temperature TEMP Temperature
DIFF Differential MAU Make-Up Air Unit TF Transfer Fan
DWDI Double Width,Double Inlet MBH 1000 BTU Per Hour THO Thermal Overload
EAT Entering Air Temperature MC Mechinacal Contractor TSP Total Static Pressure
EC Electrical Contractor MD Moterized Damper UH Unit Heater
EF Exhaust Fan MOSA Minimum Outside Air UV Unit Ventilator
EG Exhaust Grille MVD Manual Volume Damper V Voltage
ESP External Static Pressure N/A Not Applicable VAV Variable Air Volume
EWT Entering Water Temperature NAC No Access VEL Velocity
FBO Furnished By Others NC Normally Closed WB Wet Bulb
Elite Balancing, LLC 3/6
NE BB ELITE AN'E
2029 Kinnikinnick Dr. • Erie, CO 80516•Phone: (720) 523-0209 • Fax: (720)523-0225 • http://www.elitebalancing.com
Report Summary I Remarks
1. None
Elite Balancing, LLC 4/6
E LITE
N., _,.
E B.B BALANCING NELBB
Fan Unit
PROJECT: Strata Kitchen Hoods DATE: 1/19/2017
LOCATION: , CONTACT: Kevin Shaw
PROJECT#:
SYSTEM/UNIT: Room A202 Tested By: Kevin Shaw
Date: 1/18/2017
Log: Room A202 1/18/2017 Kevin Shaw Pressure to out side.Fan off-0.01 Low-0.016
Medium-0.022 High-0.030 Boost-0.038
Room A202 Exhaust Inlet Summary
System/Unit Inlet Type Size AK Factor Design Final Design Prelim Final %Final
Velocity Velocity Airflow Airflow Airflow Diff.
Inlet-01 Low Hood (3)6.75x8 1.125 304 342
Inlet-02 Med Hood .(3)6.75x8 1.125 467 525
Inlet-03 High Hood - (3)6.75x8 1.125 619 696
Inlet-04 Boost Hood (3)6.75x8- 1.125 _ 666 749
Totals: - I - - - - 0 0 2312 i 0
SYSTEM/UNIT: Room A403 Tested By: Kevin Shaw
Date: 1/18/2017
Log: Room A403 1/18/2017 Kevin Shaw Pressure to out side.Fan off 0.005 Low-0.004
Medium-0.007 High-0.014 Boost-0.017
Room A403 Exhaust Inlet Summary
System/Unit Inlet Type Size AK Factor Design Final Design Prelim ` Final %Final
Velocity Velocity Airflow Airflow Airflow Diff..............
Inlet-01 Low Hood (4)6.75x8 1.5 247 371
Inlet-02 Med Hood (4)6.75x8 1.5 376 564
Inlet-03 High Hood (4)6.75x8- 1.5 491 737
Inlet-04 Boost Hood (4)6.75x8 1.5 531 797
Totals: - - - - - .. 0 0 2469 0
SYSTEM/UNIT: Room B102
Log: Room B102 1/18/2017 Kevin Shaw Pressure to out side.Fan off-0.013 Low-0.016
Medium-0.016 High-0.018 Boost-0.018
Room B102 Exhaust Inlet Summary
System/Unit Inlet Type Size AK Factor Design Final Design Prelim Final %Final
Velocity Velocity Airflow Airflow Airflow Diff.
Inlet-01 Low Hood (4)6.75x8 1.5 228 342
Inlet-02 Med Hood (4)6.75x8 1.5 318 477
Inlet-03 High Hood (4)6.75x8 1.5 398 597
Inlet-04 Boost Hood (4)6.75x8 1.5 426 639
Totals: - - - - - 0 0 _ 2055 0
Elite Balancing, LLC 5/6
ELITE
N, . , . .
E BB B ......._..
Fan Unit
PROJECT: Strata Kitchen Hoods DATE: 1/19/2017
LOCATION: , CONTACT: Kevin Shaw
PROJECT#:
SYSTEM/UNIT: Room B201 Tested By: Kevin Shaw
Date: 1/18/2017
Log: Room B201 1/18/2017 Kevin Shaw Pressure to out side.Fan off-0.006 Low-0.013
Medium-0.021 High-0.021 Boost-0.021
Room B201 Exhaust Inlet Summary
SystemlUnit Inlet Type Size AK Factor Design Final Design Prelim Final _ %Final
Velocity Velocity Airflow Airflow Airflow Diff.
Inlet-01 Low Hood (4)6.75x8 1.5 240 360
Inlet-02 Med Hood ' (4)6.75x8 1.5 325 - 488
Inlet-03 High Hood (4)6.75x8 1.5 378 567
Inlet-04 Boost^ Hood (4)6.75x8 1.5 405 _ 608
Totals: - _ - - - - 0 0 2023 0
SYSTEM/UNIT: Room B403 Tested By: Kevin Shaw
Date: 1/18/2017
Log: Room B403 1/18/2017 Kevin Shaw Pressure to out side.Fan off-0.013 Low-0.015
Medium-0.04 High-0.04 Boost-0.03
Room B403 Exhaust Inlet Summary
SystemlUnit Inlet Type` Size AK Factor Design Final Design Prelim Final %Final
Velocity , Velocity Airflow Airflow Airflow Diff.
Inlet-01 Low Hood '(4)6.75x8 1.5 208 312 ___
Inlet-02 Med Hood (4)6.75x8 1.5 333 500
Inlet-03 High Hood r(4)6.75x8 1.5 441 6 662
Inlet-04 Boost Hood (4)6.75x8 1.5 487 731
Totals: - _ - - - - 0 0 2205 0
Elite Balancing, LLC 6/6