Loading...
HomeMy WebLinkAboutF16-0052_01_1478906023.pdf ,o OF,4, ,, ,, RI Vail Fire&Emergelcy Services 10/17/16 conditional approval. Full flow test required prior to final SANDY LANE RESIDENCE FIRE SPRINKLER SYSTEM LOT5 AIL POTATO PAT H SE ND FILINGV 738 SANDY LANE VAIL CO AUTOMATIC SPRINKLER SYSTEMS NOTES: SYMBOL LEGEND SPRINKLER LEGEND 1 . SEE THE FIRE PROTECTION EQUIPMENT DATA FOR ALL APPLICABLE MATERIALS AND ADJUST SPRINKLER TEMPERATURES AS REQUIRED PER NFPA 13, 2010 PARAGRAPH 8.3.2 EQUIPMENT INSTALLED UNDER THIS CONTRACT. Pendent Sprinkler on 25mm Drop SYMBOL DESCRIPTION SIN # NPT ORIF K FACTOR TEMP FINISH/ESCUTCHEON MAXIMUM TOTALS 2. THESE FIRE PROTECTION PLANS AND CALCULATION DESIGNED WITH THE INTENT OF COVERAGE COMPLYING WITH ALL STATE AND LOCAL CODES AND/ OR THE OWNERS INSURANCE Piping of Sprinkler System UNDERWRITER. 3. ALL MATERIALS, DEVICES AND HANGER'S INSTALLED UNDER THIS CONTRACT SHALL BE TYCO RAPID RESPONSE SERIES LFII CONCEALED PENDENT SPRINKLER TY3596 1/2" 1/2" 4.9 160E CONCEALED 16' x 16 ' 47 Horizontal Sidewall UL LISTED AND/ OR FACTORY MUTUAL APPROVED. ® System Riser 4. ALL MATERIALS, DEVICES, AND HANGERS SHALL BE INSTALLED IN ACCORDANCE WITH -Q TYCO RAPID RESPONSE SERIES LFII CONCEALED HORIZONTAL SIDEWALL TY2334 1/2" 1/2° 4.4 155F CONCEALED 16' x 18 ' 7 THEIR LISTINGS AND APPLICABLE NEPA ENGINEERING STANDARDS. ITC INPECTORS TEST CONNECTION 5. UNDER THIS CONTRACT, THE INSTALLING FIRE PROTECTION CONTRACTOR SHALL BEGIN TOTALS 54 ITS WORK AT A FITTING LOCATED 1 -0" ABOVE FINISHED FLOOR INSTALLED BY c PIPE CHANGE ELEVATION/ RISER OTHERS. 6. ALL EXTERIOR UNDERGROUND PIPING, VALVES, ETC. SHALL BE INSTALLED, TESTED, / Hanger Location AND FLUSHED IN ACCORDANCE WITH NEPA 13 AND NFPA 24 REQUIREMENTS AND ALL NFPA 13D 2013 EDITION 8.3 LOCATION OF SPRINKLERS GENERAL CONTRACTORS NOTES APPLICABLE STATE AND LOCAL CODES BY THE INSTALLING CONTRACTOR. x Branchline Restraint Location 7. THE INSTALLING CONTRACTOR OF ALL SUCH UNDERGROUND PIPING SHALL PROVIDE 8.3.1 SPRINKLER SHALL BE INSTALLED IN ALL AREAS EXCEPT WHERE OMISSION IS 1 . ALL RESIDENTIAL SPRINKLER PIPING LOCATED IN A ATTIC SPACES, EXTERIOR WALLS AND THE CONTRACTOR MATERIALS AND TEST CERTIFICATES TO THE FIRE PROTECTION PERMITTED BY 8.3.2 THROUGH 8.3.8 ANY OTHER Threaded Cap CONTRACTOR PRIOR TO CONNECTION TO ANY ABOVEGROUND PIPING SYSTEMS. POTENTIAL AREA SUBJECT TO FREEZING, SHALL BE PROTECTED FROM ANY EXPOSURE TO 8.3.2 SPRINKLER SHALL NOT BE REQUIRED IN BATHROOMS OF 55 SOFT AND LESS. FREEZING r 1 8. ANY AND ALL ELECTRICAL AND/ OR ALARM WIRING, CONNECTIONS AND TERMINATIONS, TEMPERATURES WITH BATT-TYPE INSULATION OR TENTING, AS APPROVED BY THE AUTHORITY I ! ADDITIONAL HORNS OR STROBES, SHALL BE BY OTHERS. 8.3.3 SPRINKLER SHALL NOT BE REQUIRED IN CLOSETS, LINEN CLOSETS, AND PANTRIES HAVING I r Remote Area THAT MEET ALL THE FOLLOWING CONDITIONS: JURISDICTION THESE MATERIALS ARE REQUIRED TO BE SECURED TO PROVIDE ADEQUATE L J 9. WHERE APPLICABLE, IT SHALL BE SOLE RESPONSIBILITY OF THE OWNER TO PROVIDE, 1 . THE AREA OF THE SPACE DOES NOT EXCEED 24 SOFT. PROTECTION INSTALL AND MAINTAIN AN APPROVED MONITORING SYSTEM OF ALL FIRE PROTECTION 2. THE SHORTEST DIMENSION NOT EXCEED 3FT. ABOVE/OUTSIDE THE PIPING AREA, AND TO PREVENT THE ACCUMULATION OF INSULATION SYSTEM ELECTRICAL COMPONENTS AND/ OR ANY OTHER COMPONENTS AS REQUIRED 3. THE WALLS AND CEILING ARE SURFACED WITH NON- COMBUSTIBLE OR LIMITED BETWEEN THE BY THE AUTHORITY HAVING JURISDICTION. COMBUSTIBLE MATERIALS AS DEFINED IN NFPA 220. HEATED BUILDING CAVITY AND THE SPRINKLER PIPING. 8.3.4 SPRINKLERS SHALL BE REQUIRED IN GARAGES AS PER VAIL REGULATION. 2. ALL SPRINKLER PIPING LOCATED IN ANY EXTERIOR WALL, SHALL PROVIDE ADEQUATE 10 IT SHALL BE THE SOLE RESPONSIBILITY OF THE OWNER TO PROVIDE, ADEQUATE HEAT SPACE BETWEEN THROUGHOUT THE FACILITY WHERE WET PIPE SPRINKLER SYSTEMS ARE PRESENT, TO 8.3.5 SPRINKLERS SHALL NOT BE REQUIRED IN ATTICS WITH OR WITHOUT STORAGE, THE EXTERIOR SHEATING AND THE SPRINKLER PIPING, FOR THE REQUIRED INSULATION. PREVENT FREEZING OF THE SPRINKLER SYSTEM COMPONENTS (MIN 40 DEG. F) PENTHOUSE EQUIPMENT ROOMS, ELEVATOR MACHINE ROOMS, CONCEALED SPACES - DEDICATED EXCLUSIVELY TO AND CONTAINING ONLY DWELLING UNIT VENTILATION 11 . THE OWNER SHALL MAINTAIN A CLEAR SPACE OF 18" BETWEEN THE TOP OF THE EQUIPMENT, FLOOR/ CEILING SPACES THAT NOT USED OR INTENDED FOR LIVING 3. AN INSPECTION IS REQUIRED, PRIOR TO CONCEAKMENT, FOR PROPER INSULATION STORAGE AND STANDARDS SPRINKLERS. SPACES. PROTECTION OF THE SPRINKLER PIPING. 12. ALL SPRINKLER PIPING PENETRATION THROUGH FIRE RATED ASSEMBLIES SHALL BE 8.3.5.1 SUCH SPACES THAT CONTAIN FUEL- FIRED EQUIPMENT SHALL ALSO COMPLY WITH SEALED WITH A APPROVED MATERIAL EQUAL TO THE RATING OF SUCH ASSEMBLY BY 8.3.5. 1 .1 OR 8.3.5. 4. ALL INSULATION JOINTS SHALL BE SEALED. OTHERS. 8.3.5.1 .1 WHERE THE FUEL- FIRE EQUIPMENT IS ABOVE ALL OF THE OCCUPIED AREAS OF 5. ANY DEVIATION, SHALL BE APPROVED BY COLORADO STATE FIRE PREVENTION, PRIOR TO 13. ALL NEW SPRINKLER PIPING INSTALLED UNDER THIS CONTRACT SHALL BE THE DWELLING UNIT, NO SPRINKLER PROTECTION SHALL BE REQUIRED IN THE INSTALLATION. HYDROSTATICALLY TESTED IN ACCORDANCE WITH ALL APPLICABLE NEPA ENGINEERING CONCEALED SPACES. STANDARDS AND STATE AND LOCAL CODES. 14. UPON SUCCESSFUL INSTALLATION AND COMPLETION: 8.3.5.1 .2 WHERE THE FUELED- FIRED EQUIPMENT IS BELOW OR ON THE SAME LEVEL AS A SPARE SPRINKLER HEAD BOX WITH ADEQUATE SPRINKLERS AND WRENCHES THE OCCUPIED AREAS OF THE DWELLING UNIT, AT LEAST ONE QUICK RESPONSE SHALL PROVIDED AND INSTALLED PER NEPA REQUIREMENTS. INTERMEDIATE TEMPERATURE SHALL BE INSTALLED ABOVE THE EQUIPMENT OR AT THE HYDRAULIC PLACARDS, CARE AND MAINTENANCE CARDS, AND 24 HOUR PHONE WALL SEPARATING THE SPACE WITH THE FUELED- FIRED EQUIPMENT FROM THE NUMBER SHALL BE POSTED. OCCUPIED SPACE. MINUNUM R-9 BATT OR AN APPROVED EQUAL OVER SPRINKLER PIPING COMPLETE OPERATION AND MAINTENANCE MANUALS SHALL BE PROVIDED \ . t�e�� COMPLETE CONTRACTORS MATERIALS AND TEST CERTIFICATES SHALL PROVIDED. 8.3.6 SPRINKLER SHALL NOT BE REQUIRED IN COVERED, UNHEATED PROJECTIONS OF THE ��� ALL SYSTEM CONTROL VALVES SHALL BE LEFT FULLY OPEN AND IN SERVICE. BUILDING AT ENTRANCES/ EXIT AS LONG AS THE DWELLING UNIT HAS ANOTHER '' -/ ' '- ALL SYSTEM DEVICES SHALL BE IDENTIFIED PER NEPA REQUIREMENTS. MEANS EGRESS. \, �� � ) ) �a SPRINKLE R PIPI\ G `� , J , Q JOISTTRUSSES `� 15. ADEQUATE DRAINAGE OF FERE PROTECTION PIPING SHALL BE PROVIDED FOR PER NEPA 8.3.7 SPRINKLERS SHALL NOT BE REQUIRED FOR CEILING POCKETS THAT MEET THE X_ ) `�r,15, X_� � / - / �' REQUIREMENTS. FOLLOWING CONDITIONS: A X X X �, \ ; \ ! \ 1 . THE TOTAL VOLUME OF ALL UNPROTECTED CEILING POCKET IN A COMPARTMENT DOES 41*PftatcPLi 16. PAINTING OR PRIMING OF FIRE PROTECTION PIPING IS NOT PART OF THIS CONTRACT. NOT EXCEED 100 CUBIC FEET. LINE OF FINISH CEI LI \G - T 3LOC <I N G 2. THE ENTIRE FLOOR UNDER THE UNPROTECTED CEILING POCKET IS PROTECTED BY 17. FIRE EXTINGUISHER AND CABINETS ARE NOT PART OF THIS CONTRACT. SPRINKLERS AT THE LOWER CEILING ELEVATION. SPI \ KLER HEAD 3. THE INTERIOR FINISHED OFF THE UNPROTECTED CEILING EXCLUDING DECORATIVE 18. FIRE PROTECTION PIPING IDENTIFICATION IS NOT PART OF THE CONTRACT. TREATMENTS IS NONCOMBUSTIBLE OR LIMITED COMBUSTIBLE MATERIAL. REFERENCE NEPA 13R 4.SKYLIGHTS NOT EXCEEDING 32 SOFT SHALL BE PERMITTED TO HAVE A PLASTIC COVER. 19. PROTECTION OF ELECTRICAL DEVICES, SUCH AS CIRCUIT BREAKER PANELS FROM WATER DISCHARGE, SHALL BE BY OTHERS. 8.3.8 SPRINKLERS SHALL NOT BE REQUIRED IN CLOSETS AND EXTERIOR CLOSETS REV DESCRIPTION DATE APPROVED (REGARDLESS OF SIZE) LOCATED ON EXTERIOR BALCONIES, EXTERIOR BREEZEWAY/ REVISIONS 20. CENTERING OF SPRINKLER HEADS IN THE CEILING TILE IS NOT PART OF THIS CORRIDORS, OR UNPROTECTED PENETRATIONS DIRECTLY INTO THE DWELLING UNIT. FOR PLANS PROVIDED BY: PHONE TYPICAL INSULATION DETAILS CONTRACT. SPRINKLER ARE REQUIRED IN GARAGE AS PER VAIL. LOFORPHONE SCALE: NOT TO SCALE 21 . THE FIRE PROTECTION CONTRACTOR SHALL NOT BE HELD RESPONSIBLE SHOULD THE 8.3.9 SPRINKLER SHALL BE INSTALLED IN ANY CLOSET USED FOR HEATING AND/ OR AIR- DRAWN BY: DATE NOTED FLOW TEST VALUES NOT BE SUPPLIED AT THE POINT OF CONNECTION NOW OR 10/12/2016 IN THE FUTURE DUE TO POSSIBILITY OF DETERIORATING WATER SUPPLIES, SEE CONDITIONING EQUIPMENT, WASHERS AND/ OR DRYERS, OR WATER HEATERS EXCEPT A �I CHECKED BY: DATE AS ALLOWED BY 8.3.8 A '0} 11119,..aRk HYDRAULIC SOURCE NODE LOCATION. 9nter 1ourattyin APPROVEDBY: Faro Et S cur r 22. ANY KNOX EQUIPMENT SHALL BE PROVIDED AND INSTALLED BY OTHERS. 23. ALL REQUIRED INTERIOR / EXTERIOR SIGNAGE SHALL BE PROVIDED AND INSTALLED BY OTHERS. MERIDIAN INTERMOUNTAIN FIRE & SECURITY 24. PROVISION FOR FLUSHING THE SPRINKLER PIPING SHALL BE PROVIDED BY THE P.O. BOX 3940 AVON CO, 81620 INSTALLING FIRE PROTECTION CONTRACTOR. TEL. NO. (970) 748-8888 SANDY LANE RESIDENCE 25. AS ALLOWED BY NFPA 13, SYSTE PIPING CONFORMS TO THE FOLLOWING LOT 5, VAIL/ POTATO PATCH SECOND FILING 738 SANDY LANE, VAIL, CO PROJECT TITLE, FSS LEGEND, NOTES, APPROX. SCALE DWG NO. REV NOT TO SCALE FAO.O. 01 SHEET NO. 1� 1 OF 8