HomeMy WebLinkAboutF16-0035 RFC43 Flat Concealed .pdf Bulletin 006 Rev. I
Model RFC30 (SIN RA0611) °J
R eia ® M (S
Modelodel RFC49RFC43 (SININ RA0616)RA0612) .
Residential Flat Concealed a
Sprinklers
A Residential Flat Concealed
Sprinkler engineered for a minimum
design density of 0.05 gpm/ft2 with
low GPM requirements.
Features
1 . Very low water flow requirements.
2. Cover plate attachment (Plain or Perforated)
with 1/2" (13mm)Total adjustment.
3. Thread-On/Thread-Off or Push-On/Thread
Off cover attachment option.
4. Smooth aesthetic ceiling profile.
5. Available in brass, chrome and black plated
or painted finishes. Plain Cover Plate
Listings & Approval
1. Listed by Underwriters Laboratories, and �. -' .
•
certified by UL for Canada (cULus) _ --.2-7-...„ .
•
UL Listing Categories
Residential Automatic Sprinklers
UL Guide Number - - - "
VKKW =__- -_ '- -- -__- --_ -_ -
Product Description -- - --- -- ------
Model RFC30, RFC43 and RFC49 Concealed Residen- - --- -- _-_ _ -
tial Sprinklers are fast response residential fusible solder
link automatic sprinklers. Residential sprinklers differ
from standard sprinklers primarily in their response time
and water distribution patterns. Perforated Cover Plate
Model RFC30, RFC43 and RFC49 sprinklers discharge
water in a hemispherical pattern below the sprinkler de- and positively attached and blends into the ceiling, con-
flector. Residential distribution patterns are higher and cealing the most dependable fire protection available, an
generally contain a finer droplet size than standard sprin- automatic sprinkler system.
kler patterns. The RFC30, RFC43 and RFC49 are UL Listed Residen-
The combination of speed of operation and high dis- tial Sprinklers to be installed in the residential portions
charge pattern required for residential sprinklers has of any occupancy in accordance with NFPA 13, 13R, &
demonstrated, in fire testing, an ability for controlling 13D.
residential fires, and thereby providing significant evacu- The RFC30, RFC43 and RFC49 can reduce the need
ation time for occupants. for precise cutting of drop nipples. The threaded cover
The RFC30, RFC43 and RFC49 Sprinklers provide the plate assembly can be adjusted without tools to fit ac-
best form of fire protection by combining an attractive ap- curately against the ceiling. The fire protection system
pearance and 1/2" (13mm) of cover adjustment for ease need not be shut down to adjust or remove the cover
of installation. The small diameter cover plate is easily plate assembly.
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Application and Installation
The RFC30, RFC43 and RFC49, for residential instal- When inserting or removing the wrench from the sprin-
lations, use a 165°F (74°C) fusible solder link in a tun- kler/cup assembly, care should be taken to prevent darn-
ing fork style sprinkler frame with a drop-down deflector. age to the sprinkler. DO NOT WRENCH ON ANY OTHER
This assembly is recessed into the ceiling and concealed PART OF THE SPRINKLER/CUP ASSEMBLY. MODEL
by a flat cover plate. The cover plate is attached to the RFC30, RFC43 AND RFC49 CONCEALED SPRINKLERS
skirt, using 135°F(57°C)ordinary temperature classifica- MUST BE INSTALLED ONLY WITH 135°F RATED COV-
tion solder.When the ceiling temperature rises,the solder ERS.
holding the cover plate releases the cover allowing the Note:A leak tight 1/2" NPT(R1/2)sprinkler joint can be ob-
deflector to drop into position and exposing the sprinkler tained with a torque of 8-18 ft-lbs (10,8- 24,4 N-m). Do not
inside to ceiling temperature. The subsequent operation tighten sprinklers over maximum recommended torque. It
of the solder link opens the waterway and causes the de- may cause leakage or impairment of the sprinklers.
flector to drop into position to distribute the discharging Cover assemblies provide up to 1/2" (13mm) of adjust-
water in a hemispherical pattern below the sprinkler de- ment. Turn the cover clockwise until the flange is in con-
flector. Any adjustment of thread engagement between tact with the ceiling. For the push-on/thread-off option,
the cover plate and cup will assure that the drop-down the cover assembly is pushed onto the cup and final ad-
deflector is properly located below the ceiling. The resi- justment is made by turning the cover clockwise until the
dential distribution pattern contains a finer droplet size skirt flange makes full contact with the ceiling. Cover re-
than a standard sprinkler, and the pattern produces sig- moval requires turning in the counter-clockwise direction.
nificantly higher wall wetting. In ceilings that have a plenum space above the
After a 25/s inch diameter hole is cut in the ceiling, the sprinkler,the plenum space may have neutral or neg-
sprinkler is to be installed with the Model FC Wrench. ative pressurization but must not be positively pres-
When installing a sprinkler, the wrench is first positioned surized. Inspect all sprinklers after installation to en-
into the sprinkler/cup assembly and around the hexago- sure that the gap between the cover plate and ceiling
nal body of the sprinkler frame. The Wrench must bottom and the 4 slots in the cup are all open and free from
out against the cup in order to ensure proper, safe instal- any air flow impediment.
lation. The sprinkler is then tightened into the pipe fitting.
Sprinkler CCP AssemblyMax.
Thread Nominal p
Ambientient K
Max.MModel Temp Rating Temp. Pressure reSize Orifice Temp. Factor(SIN)
Inch(mm) Inch (mm) PF /C rF rC /F pC psi (bar)
RFC 30
1/2„(15) 21/64(8,2) 165 74 135 57 100 38 3.0(43.2) 175(12)
(RA0611)
RFC 43 1/2"(15) 3/8(10) 165 74 135 57 100 38 4.3(62) 175(12)
(RA0612)
RFC 49 1/"(15) 7/6(11) 165 74 135 57 100 38 4.9(70.6) 175(12)
(RA0616)
Note: 1 bar= 100 Kpa
RFC 30
Ordinary Temp. Rating
Max. Coverage ?F/74r'C) Top of Deflector Minimum
area Max. Spacing (165to Ceiling Installation Spacing
Ft x Ft(m x m) Ft(m) Flow Pressure Inch (mm) Type Ft(m)
GPM (Umin) PSI(bar)
12 x 12(3,6 x 3,6) 12(3,6) 9(34,1) 9.0(0,62) Smooth Ceilings 1/2 to 1(13 to 25.4)
Beamed Ceilings per NFPA 13D, 13R or Concealed 8(2,4)
14 x 14(4,3 x 4,3) 14(4,3) 10(37,8) 11.0(0,76) 13 installed in beams 1/2 to 1(13 to 25.4)
For Ceiling types refer to NFPA 13, 13R or 13D
2.
RFC 43
Ordinary Temp. Rating
Max. Coverage Max. Spacing (165PF/74PC) Top of Deflector
Installation Minimum
area to Ceiling Spacing
Ft x Ft(m x m) Ft(m) Flow Pressure Inch (mm) Type Ft(m)
GPM (Vmin) PSI(bar)
12 x 12(3,6 x 3,6) 12(3,6) 12(4,5) 7.8(0,54)
14 x 14(4,3 x 4,3) 14(4,3) 13(49) 9.1 (0,63)
— Smooth Ceilings 1/2 to 1(13 to 25.4)
16 x 16(4,9 x 4,9) 16(4,9) 13(49) 9.1 (0,63) Beamed Ceilings per NFPA 13D, 13R or Concealed 8(2,4)
13 installed in beams'to 1(13 to 25.4)
18 x 18(5,5 x 5,5) 18(5,5) 18(68) 17.5(1,21)
20x20(6,1 x6,1) 20(6,1) 21 (79) 23.8(1,64)
For Ceiling types refer to NFPA 13, 13R or 13D
RFC 49
Ordinary Temp. Rating
Max.Coverage Max. Spacing (165WF/74/C) Top of Deflector Installation Minimum
area Ft(m) Flow Pressure to Ceiling Type Spacing
Ft x Ft(m x m) GPM(1../min) PSI(bar) Inch (mm) Ft(m)
12 x 12(3,6 x 3,6) 12(3,6) 13(49) 7.0(0,48)
14 x 14(4,3 x 4,3) 14(4,3) 13(49) 7.0(0,48)
Smooth Ceilings 1 to 1(13 to 25.4)
16 x 16(4,9 x 4,9) 16(4,9) 13(49) 7.0(0,48) Beamed Ceilings per NFPA 13D, 13R or Concealed 8(2,4)
13 installed in beams 1 to 1(13 to 25.4)
18 x 18(5,5 x 5,5) 18(5,5) 17(64,3) 12.0(0,83)
20x20(6,1 x6,1) 20(6,1) 20(75,73) 16.7(1,14)
For Ceiling types refer to NFPA 13, 13R or 13D
Maintenance
Model RFC30, RFC43 and RFC49 Concealed Sprin- symmetric lever mechanism, maintaining a Teflon-coated
klers should be inspected and the sprinkler system Belleville spring washer and machined brass cap water
maintained in accordance with NFPA 25. Do not clean seal assembly containing no plastic parts. Sprinkler K-
sprinklers with soap and water, ammonia or any other factor shall be nominal 3.0 (43.2), 4.3(62), and 4.9(70.6)
cleaning fluids. Remove dust by using a soft brush or having a 5/6", 3/" and 7/16" orifice. Temperature rating
gentle vacuuming. Remove any sprinkler cover plate as- shall be Ordinary 165°F(74°C); cover plate temperature
sembly which has been painted (other than factory ap- rating to be 135°F(57°C). Cover plate assembly shall
plied) or damaged in any way. A stock of spare sprin- consist of a brass cover plate and copper alloy retainer
klers should be maintained to allow quick replacement flange allowing a'/2" cover plate adjustment. Any secure
of damaged or operated sprinklers. Prior to installation, engagement between the cover plate and the cup will
sprinklers should be maintained in the original cartons assure that the drop-down deflector is properly located
and packaging until used to minimize the potential for below the ceiling. A plastic protective cap shall be
damage to sprinklers that would cause improper opera- provided and factory installed inside the sprinkler cup
tion or non-operation. to protect the drop-down sprinkler deflector from dam-
age, which could occur during construction before the
Model RFC30, RFC43 and RFC49 Residential cover plate is installed. Standard cover finish: [Chrome]
Concealed Sprinkler Specification [White] [Specialty—specify]. Residential concealed
sprinklers shall be Reliable Model RFC30, SIN RA0611
Sprinklers shall be cULus Listed low flow residential con- (Bulletin 006), Model RFC43, SIN RA0612(Bulletin 006)
cealed sprinklers with drop-down deflector and adjust- or Model RFC49, SIN RA0616(Bulletin 006).
able flat cover plate engineered for a minimum design
density of 0.05 gpm/ft2. Sprinkler frame and deflector
shall be of bronze frame construction having a'/2" NPT
thread. Thermal element shall consist of an approved
black-painted beryllium-nickel fusible solder link with
3.
Ordering Information Cover Plate Finishesf1
Specify: Standard Finishes
1. Sprinkler Model Chrome
2. Cover Plate Finish White Paint
3. Thread-On or Special Application
Push-On Feature Finishes/21
Bright Brass
Finished Bronze
Black Plating li
Black Paint
Off White
Satin Chrome I r,....J
(1) Other finishes and colors are
available on special order.
Consult factory for details.
Coverplate custom paint is
semi-gloss, unless specified •
otherwise.
00
(2) For the perforated style cover-
plate, consult factory for avail-
ability on these and other cus-
tom finishes.
1—
t"x 1/2"REDUCING
TEE OR ELBOW I
--T-- II --
—b7-- :--- i ---: ---
2i"[66.55mm]
27 "[58.42mm] D/A I Lam-__1 OLE IN CEILING F CUP
2"[50.8mm] MAX.
ji FACE OF FITTING
i"[12.70mm] MAX. 1\\\\\\\N"— TO FACE OF CEILING
COVER ADJUSTMENT \\\\\\\, )
\\\\\\\ DIMENSION
\\\\\\\\ Ili
1/2"[12.7Omm]MIN. TO CEILING2 ////////
1"[25.4mm]MAX. i l I. , „„„, i
DROPPED DEFLECTOR le it :_ --��
TO CEILINGi CEILING
_# tis
A"[4.96mm]—f
FLAT COVER PLATE 3i"[84.21 mm] DIA. -
ASSEMBLY
SPRINKLER
COVER PLATE: 1/2" [12.7mm] ADJUSTMENT
IC
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association,Factory
Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years,and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States,Canada and foreign countries.
Manufactured by
ReiReliable Automatic Sprinkler Co.,Inc. ® Recycled
® (800)431-1588 Sales Offices
' (800)848-6051 Sales Fax Revision lines indicate updated or new data.
(914)829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address EG.Printed in U.S.A.11/14 P/N 9999970261