HomeMy WebLinkAboutE16-0169 Load Calcs.pdf NATIVE ELECTRIC, INC. PO BOX 1807 EAGLE, CO 81631 PHONE: (970) 328-1293 // FAX: (970) 328-1908 Load Calculations Date: August 25, 2016 Submitted to: HMR Construction Attention: Michael Roe Job Location: 754 W. Potato Patch Rd. Vail CO Load Calculations: 120/240Volt 200AMP Services Total Square FT: 3600 3600 sq. ft. @ 3 watts per ft. = 10,800 Small Appliance Circuits = 3000 Dish Washer = 1500 Disposal = 1500 Washer = 1500 Dryer = 5000 Refrigerator = 1500 Range = 6500 Microwave = 1500 Steam Shower = 5000 Boiler = 1500 HWH Hot Water Heater = 5000 Hot Tub = 7000 Heat Tape = 10,000 Total = 61,300 First 10KVA @ 100% = 10,000 Remainder of load @ 40% =20,520 30,520 240 120/240Volt 200AMP Services = 127.2 AMPS