HomeMy WebLinkAboutA15-0025_ENZIAN FA DATA SHEETS_1428946980.pdf Vigilant Catalog►Small Building Fire Alarm Solutions /G/LA T TM Fire & Life Safety " IIII o - VS2 IN iff 1 ,,,,_ ____ . _ •_.... Life SafetyS stem -y __ _�, OliD Overview Features The Vigilant VS2 intelligent life safety system offers the speed of • Comes standard with one loop(expandable to two)that high-end intelligent processing in a configuration that delivers an supports up to 250(expandable to 500)intelligent devices: uncomplicated solution for small to mid-sized applications.With each VS2 loop supports up to 125 detectors and up to 125 intelligent detection, electronic addressing, automatic device modules. mapping, optional Ethernet°connectivity, and a full line of easily- • Four Class B NACs or two Class A NACs. configured option cards and modules,this quick-to-install system offers versatility that benefits building owners and contractors • Form C contacts for alarm and trouble, Form A for supervisory alike. • Electronic addressing with automatic device mapping The VS2 provides one Class A or Class B analog device loop that • Optional Ethernet port for diagnostics, programming and a supports up to 250 device addresses.A second 250-point loop variety of system reports may be added to the VS2 to expand total system capacity to up • Two programmable switches with LEDs and custom labeling to 500 device addresses.The panel includes four NACs that may be wired for either Class A or Class B operation. • Supports Genesis horn silence over two wires and UL 1971-compliant strobe synchronization This life safety system features an attractive contemporary design • Supports up to eight serial annunciators, (LCD, LED only, and that fits with any decor. Its gently curved doorfront offers a distinc graphic interface). tive flair with available red or silver finishes. Controls are discreetly inset behind a striking black bezel. • Can use existing wiring for most retrofit applications The VS2 supports a wide range of accessories and related equip • Supports V-Series single and multisensor detectors ment, including: • Upload/download remotely or locally • Intelligent modules, detectors, and bases • Two-level maintenance alert reporting • R-Series remote annunciators • Pre-alarm and alarm verification by point • option cards that expand system capacity and extend system • Adjustable detector sensitivity capabilities. • 4 x 20 character backlit LCD display Page 1 of 8 DATA SHEET M85005-0130 Not to be used for installation purposes. Issue 4 Application Operation The VS2 life safety system is an easy-to-use intelligent solution for The front panel provides an easy-to-use operator's interface, as small to mid-sized buildings.Analog technology delivers the benefits well as all the necessary controls for front panel programming. of quick and uncomplicated system installation,while a clean and A large back-lit 80-character LCD displays system status, event easy-to-operatate user interface makes panel operation and system details,and programming prompts. Large tactile control buttons maintenance quick and intuitive. are easy to see in low light conditions, and bright multi-color LEDs offer at-a-glance status indication. The smart choice LCD System Electronic addressing eliminates the tedium of setting dipswitches, display LEDs and automatic device mapping ensures that each device resides ees on the system at its correct location. Meanwhile, innovative pro- gramming ro- �' ,, O a rammin allows the designer to customize the system topre- 00:00:00 01/01/07 9 9 9 Y Banner ®® cisely suit the needs of the building owner. Configurable °'A°E® �a Versatility built right in — — =g 51"'" Two fully-programmable front panel switch/LED combinations pro- f `®1-1 j 3 DEF I vide an added measure of simplicity.Their slide-in labels take the �, (3 „� 6 MNo mystery out of custom applications,and present a clean finished TEEM 0%,.. D4WD FAULT - 7 Pom 5 appearance. LiataToR o ® , ,® [1=1 Perfect for retrofits System The VS2 is particularlywell-suited to retrofit applications.All LEDs Controlo pp buttons connections are made over standard wiring—no shielded cable required.This means that in most situations existing wiring can be used to upgrade a legacy control panel to V-Series technology Control buttons without the expense or disruption of rewiring the entire building. Button Description Signals with a difference Reset Initiates a system reset. VS2 NACs are configurable to fully support the advanced signaling ACK/Panel Silences the panel and remote annunciators during capabilities of Edwards Genesis and Enhanced Integrity notifica- Silence an active trouble,supervisory,or alarm event and tion appliances.These devices offer precision synchronization of acknowledges new event activations. strobes to UL 1971 standards. For Genesis devices, enabling this Signal Silence Alarm mode:Silences active notification appliances. feature allows connected horns to be silenced while strobes on Pressing Signal Silence a second time turns NACs back on. the same two-wire circuit continue to flash until the panel is reset. Drill Initiates a drill confirmation.Pressing drill a second time turns off the drill function. Clear-cut remote annunciation Remote Dialer:Disables or enables dialer. Remote annunciation is a strong suit of the VS2. Up to eight an- Disconnect Dialer set to modem only:Disables or enables the nunciators can be installed on a single system. Compatible annun- common alarm relay. ciators include a range of LED and LCD models that provide zone Left arrow Display mode:Moves the cursor to the left. or point annunciation,as well as common control capabilities. Menu mode:Toggles between programming selections. The VS2 also supports graphic annunciation with optional RA Right arrow Display mode:Moves the cursor to the right. Graphic Annunicator interface modules. Each interface provides Menu mode:Retrieves a programming option's sub common control, indicators, and 32 LEDS. Consult the Ordering menu and toggles between a programming option's Information section for details. selections. Up arrow Display mode:Advances to the previous event. A complete line of accessories Menu mode:Moves the cursor up. The VS2 life safety system is supported by a complete line of Down arrow Display mode:Advances to the next event. Disp intelligent detectors, modules and related equipment. Consult the Enter Display mode:mode::Displays Moves the cursor deisplays selected event details. Ordering Information section for details. Menu mode:Retrieves a programming option's sub menu or jumps to the Save function in the menu. Entry mode:Enters the selected data into the system. Cancel Display mode:Exits the detailed information display. Menu mode:Exits the current menu level. Entry mode:Clears the current entry. Menu Display mode: Enters the menu mode Menu mode:Exits menu mode Space Enters a space,such as a space between words. Alphanumeric Entry mode:Pressing a button once enters the number keypad on the button.Pressing the button twice enters the secondary value. Programmable These buttons can be programmed to control outputs, buttons disable devices or unlatch system outputs.The buttons can be labeled with a slip-in insert. Page 2 of 8 DATA S I. M85005-0130 Not to be used for installation purposes. Issue 4 System LEDs Panel Operation Options LED Description Language English or French Fire Alarm Red LED.On steady when there is an active Marketplace U.S.or Canada alarm. AC fail delay Off•Off-premise notification of an AC power failure Trouble Yellow LED. Flashes when there is a fault on a is immediate. monitored circuit or system component, or when 1 to 15 hours:Delays the off premise notification of a circuit is disabled. an AC power failure by the time period selected. Supv Yellow LED. On steady when there is an active Zone resound On:NACs resound each time a device in the zone goes into alarm even if they were silenced supervisory event. Off: Inhibits the NACs from turning on again(after AC Power Green LED.On when the panel has AC power. they were silenced)when a second device in the Disable Yellow LED. Double-flashes when there is a dis- zone goes into alarm. abled circuit or alarm relay. Reset inhibit after Off:Panel reset is operational immediately. Ground Yellow LED.On steady during an active ground NACs turn on 1 minute:Panel reset is inhibited for one minute. Fault fault. Auto signal Off•Allows immediate silencing of signals from an Test Yellow LED. Flashes when performing an audible silence off normal condition using the Signal Silence button walk test. Steady indicates a silent test. 5 to 30 minutes:Delays the silencing of signals from an off-normal condition by disabling the Signal Monitor Yellow LED. On steady when there is an active Silence button for the time period selected. monitor event. Day start Start time for daytime sensitivity Service Yellow LED. Indicates that detector needs servic- Night start Start time for nighttime sensitivity Detector ing. Date MM/DD/YYYY,DD/MM/YYYY Signal Yellow LED. On steady indicates that NAC cir- Sounder Base Six configuration settings Silence cults are turned off but the panel is still in alarm. Mapping Disabled:Device mapping is not available Remote Yellow LED. On steady indicates that the dialer Enabled:Device mapping is available Disconnect is disabled or that the alarm relay is enabled or LCD banner Banner text for line one and line two.Each line is disabled when the dialer is set to modem only. capable of up to 20 characters. Drill Yellow LED. Indicates that the panel is in drill. Event notification Zone:When a device is a member of a zone,only Reset Yellow LED. Indicates that the panel is resetting. the zone information is sent to the LCD display, LEDs,printer,and dialer. Panel Yellow LED. Indicates that the panel has been Zone/device:Zone information is sent to the LCD Silence silenced during an active trouble,supervisory, or display and LEDs.Device information is sent to the alarm event and indicates that new event activa- printer and dialer. tions have been acknowledged. Device:Only device information is reported. User keys Yellow LED. Programmable. Programming Dimensions V-Series panels are simple to set up, quick to program, and easy to maintain.The auto programming feature quickly gets the panel Surface mounting holes Backbox with Backbox with door and operational using factory default settings. Basic zone and point HD2HD3� door attached trim ring attached �D7 settings can be programmed easily through the front panel inter- 0- '0 0 80 *0 face,so the system is up and running in no time. I° •• u0 j °0 *0 For more advanced system configuration and correlation groups 1 1 r 0 0 programming,V-Series panels interface to a PC running compat- J ® .s 0 0 ible VS CU software.This option offers full system configuration 0.1 D1 . n<• • ® D4 D8 in the familiar Windows®operating environment. Connection is o — e N 0 0 typically made to a laptop through the panel's optional RS-232 o communications port,which can also be used to connect a sys- Surface mounting holes o a 0 tem printer. _ ° —D6� Among the many innovations of the VS2 control panel is the . D6 . LD9el —riD9►I optional network card.This module provides a standard 10/100 Base T Ethernet®network connection that permits access to Backbox and backbox with door the control panel from any remote location with the correct D1* D2 D3 D4 D5* D6 D7 D8 D9 communications protocols. The connection can be used to 28.0" 3.85 9.0" 22.0" 15.75 10.25' 3.9" 28.2" 2.7' download to the panel from the VS-CU, or upload and view 71.1cm 9.8cm 22.8cm 55.8cm 40.0cm 26.0cm 9.9cm 71.6cm 6.8cm system reports using the VS-CU. "Add 1-1/2 in.(3.81 cm)to D1 and D5 dimensions for trim kit. Available system reports include: • Correlation groups • Device details • Device maintenance • History • Internal status • System configuration • System status • Walk test • Dialer Page 3 of 8 DATA SHEET M85005-0130 Not to be used for installation purposes. Issue 4 Wiring & Configuration Notification appliance circuits(TB2) Device loop V-Series control panels come equipped with two notification The control panel provides one device loop circuit that can sup- appliance circuits. Each circuit can be individually configured for port 125 detectors and 125 module addresses.The loop circuit is continuous,temporal, synchronized, latching, and coded output. supervised for opens,shorts,and grounds. Circuit specifications Circuit specifications Circuit Type 4 Class B or 2 Class A,2.5 amps each Device loops 1 loop,expandable to 2,Class A or B,each loop Voltage 24 VFWR supporting up to 250 device addresses Current 6.0 A total,2.5 A max.per circuit at 120/230 VAC 60 Hz Communication Maximum 20 V peak-to-peak 5.0 A total at 230VAC 50 Hz line voltage 2.5 A max.per circuit Circuit current 0.5 A max Impedance 26 0 total,0.35 pF max Circuit 660 total,0.5 JF,max EOLR 15 K 4,Y W impedance Isolators 64 maximum Class B wiring Class B Wiring Class A Wiring NAC1 Z + C + C 0 Loop 1 SEC +® 0 NAC1+ Data Line - 0 NAC2- /\ < < Y11+ + EOLR Loop 1 PRI 0 NAC2+ +®""(eBN "(e�N Loop Loop Loop Loop TB2 Loop card device device Data Line device device 0 NAC3 0 NAC3+ < + < Marking indicates 0 NAC4 EOLR output signal polarity X + + / when the circuit is ac- Annunciator loop(TB4) 0 NAC4+ - \ - \ tive.Polarity reverses TB6 when the circuit is not The control panel provides a connection for up to eight serially active.Wire notification driven and supervised remote annunciators. appliances accordingly. Class A wiring Notification appliance Circuit specifications polarity shown in ac- Device loops Class B(Style Y)or Class A(Style Z) 0 NAC1- + tive state. 0 NAC1+ I C Circuit voltage 2.55 V - - � Circuit current 30 mA max 0NAC2 r\b + + _ Circuit Up to 8 annunciators or 4000 feet NAcz+ impedance TB2 Class B Class A 0 0 + Channell Channell Channell Channell 0 + iQQQTB4 ® is) is) ® TB4 Annunciator Annunciator TB6 CH1(+)IN &CH1(+)IN CH1(-)IN -(S)CH1(-)IN ®CH2( IN CH2( IN Auxiliary&Smoke power outputs(TB3) (S)CH2(-)IN (S)CH2(-) IN The control panel provides two auxiliary power outputs which can be used for powering ancillary equipment such as remote an- nunciators and two wire smoke detectors. Aux 2 can be software selected to operate continuous.The circuit is supervised for shorts Alarm,trouble,and supervisory relay(TB3) and grounds. The trouble relay is normally-open, held closed, and opens on any Note: For a complete list of devices that can be connected to this trouble event or when the panel is de-energized.The supervisory circuit, refer to the VS Series Compatibility List. relay is normally-open, and closes on any supervisory event.The Circuit specifications alarm relay changes over on any alarm event. Circuit voltage range 21.9 to 28.3 V Relay specifications Resettable circuit 24 VDC nominal at 500 mA Alarm 1 Trouble Supervisory (Aux power 2) Type Form C Form A Continuous circuit 24 VDC nominal at 500 mA.Use this circuit for Voltage 24 VDC at 1 A resistive 24 VDC at 1 A resistive (Aux power 1) powering two-wire smoke detectors. Note:Any current above 0.5 amp connected to both Aux 1 and 2 will reduce the total Relay circuits can only be connected to power limited sources. available NAC power by that amount. Page 4 of 8 DATA s I.,_,_ i M85005-0130 Not to be used for installation purposes. Issue 4 Option Cards V-Series panels are supported by a complete line of modules and SMK Smoke Power Converter related equipment that enhance performance and extend system The SMK Smoke Power capabilities. Option cards are easy to install and set up.They Converter Module pro- aux ry +1®( simply plug directly into the control panel main circuit board or are vides a regulated power (not resettablepower ) ®E connected to it with a ribbon cable.After installation,terminals source for two-wire smoke remain easily accessible for quick connection of field wiring.The circuits connected to a cabinet provides ample room for wire routing, keeping wiring neat Signature data circuit.The ©l II ®®®®I o and easy to service at all times. SMK monitors the operat- SMK a ing power from the power Power in Power out supply.When power be- o P3- * + SA-ETH Ethernet Interface Card gins to degrade,the SMK SA-ETH wiring The SA-ETH card provides a provides the necessary o ®®®® © rE wor connection standard 10/100 Base T Ethernet operating voltage to the Two-wire smoke 1 Network cable i r network connection for connect- two-wire smoke detection detectors al I ing to an intranet, a local net- circuits. ©I®®®®IP!I®e® I 1 work, or the Internet.The card 16151413 3U 121110 9 can be used to download JP1 - + Pe configuration programming from o +- ❑ ® network.the VS-CU to the panel over the ®®®®I 4 3 2 1 ®®®I o U ® t Data in -1 ® The Ethernet card is installed on +' ®ii the plastic assembly and con- Two-wiresmokei_ Ethernet card detectors i nects to the main circuit board via a ribbon cable. ©I®®®®IFuzllee®e I © 16 15 14 13 311 12 11 10 9 SA-ETH specifications JP1 + Terminate or to next Ethernet 10/100 Base T UM Operating environment 6 ' 6 5 4�3 2 1 Temperature 32 to 120°F(0 to 49°C) O ®®®® ®T®® O Humidity 0 to 93%RH,noncondensing at 90°F Data out (32°C) SMK specifications Input voltage 21.9 to 28.3 VDC(not resettable) V-SLC Loop Expander Card Output voltage 24 VDC nom.at 200 mA,max.,special The V-SLC Loop Expander Card provides an additional device applications loop on the control panel.The card expands the control panel's Ground fault 10 k ohm device capacity to 500 total device addresses, 250 per loop.The impedance card is compatible with Class B or Class A wiring. It is compatible Operating environment with VS2 control panels only. Temperature 32 to 120°F(0 to 49°C) Humidity 0 to 93%RH,noncondensing at 90°F(32°C) The loop expander card connects to connector J7 on the main Storage temperature -4 to 140°F(-20 to 60°C) circuit board. Compatible electrical North American 4 inch square x 2-1/2 in. Class B Wiring Class A Wiring boxes (64 mm)deep 2 gang box or Standard 4 in. - square box 1-1/2 in.(38 mm)deep + Loop 1 SEC ® Data Line Wire size 14, 16,or 18 AWG wire(1.5, 1.0,or 0.75 sq. mm)(Sizes 16 and 18 AWG are preferred) Loop 1 PRI +® "'(epil itgeB� • Loop Loop Loop Loop Loop card device device Data Line device device V-SLC specifications Device addresses on loop 125 detectors and 125 modules Wiring Class B(Style Y)or Class A(Style Z) Operating voltage 20 V peak-to-peak Operating current 0.5 A total Circuit impedance 66 0,0.5 pF,max Terminal rating 12 to 18 AWG(0.75 to 2.5 sq mm) Operating environment Temperature 32 to 120°F(0 to 49°C) Humidity 0 to 93%RH,noncondensing at 90°F (32°C) Page 5 of 8 DATA SHEET M85005-0130 Not to be used for installation purposes. Issue 4 SA-DACT Dialer The SA-DACT provides communications between the control The SA-DACT queues messages and transmits them based on panel and the central station over a telephone line system. It priority(alarm, supervisory,trouble,and monitor).Activations are transmits system status changes(events)to a compatible digital transmitted before restorations. alarm communicator receiver over the public switched telephone The SA-DACT is installed on the plastic assembly and connects to network.The dialer is capable of single, dual, or split reporting the main circuit board via a ribbon cable. of events to two different account and telephone numbers.The modem feature of the SA-DACT can also be used for uploading SA-DACT specifications and downloading panel configuration, history,and current status Phone line type One or two loop-start lines on a public, to a PC running the VS-CU. switched network SA-DACT Phone line 1 Phone line connector RJ-31/38X(C31/38X) wiring B To wall Communication formats Contact ID(SIA DC-05) Phone line phone jack Operating environment Phone cables Temperature 32 to 120°F(0 to 49°C) (supplied) T T RJ31 jacks Humidity 0 to 93%RH,noncondensing at 90°F El IVI_I (32°C) 1 Compatible DACRs + The dialer phone lines connect Receiver Models Formats 1 to connectors on the dialer's ®l Ir 44°'01`° main circuit board.Phone line 1 Ademco 685 Contact ID ED ^°.° E connects to connector J4 and FBII CP220 Contact ID ¢o . °° phone line 2 connects to Osborne-Hoffman OH 2000 Contact ID connector J1. Radionics D6600 Contact ID p ®� P.,:°_,1° 0Silent Knight 9800 Contact ID 10 li lil_ Oil o Sur-Gard SG-MLR1,MLR2 Contact ID ..111341...- ❑ , SA-232 RS-232 interface The RS-232 card is installed on the plastic assembly and con- The SA-232 card provides an RS-232 SA-232 wiring nects to the main circuit board via a ribbon cable. interface with VS2 panels. It can be GND(black wire) TXD(white wire) SA-232 specifications used for connecting a printer to the —RXD(red wire) p control panel to print system events.The Operating voltage Standard EIA-232 card also can be used for connecting a +66®® + Terminal rating 12 to18 AWG(0.75 to 2.5 sq mm) computer to download a configuration ❑ Operating environment program from the VS-CU to the controlEl 1 i Temperature 32 to 120°F(0 to 49°C) Humidity 0 to 93%RH,noncondensing at 90°F(32°C) panel. Specifications Device loops 1 loop,expandable to 2,Class A or B,each loop Battery placement VS2 cabinets accommodate up to 18 NH batteries. supporting up to 250 device addresses Use a external cabinet for larger battery sizes. NAC circuits 4 Class B or 2 Class A,2.5 amps each Batteries Batteries must be sealed lead acid type only. Power supply 6.0 A total,2.5 A max.per circuit at 120/230 VAC Maximum charging capacity=26 Ah. 60 Hz Loop circuit Maximum loop resistance:66 C.Maximum loop 5.0 A total at 230VAC 50 Hz,2.5 A max.per capacitance:0.5 pF.Style 4,6,and 7 wiring.64 circuit isolators maximum. 0.5 amps aux power GSA-UM/GSA-MAB 1.5 mA(see the UL and ULC compatibility list for NAC Operating 24 VDC.NAC minimum voltage: 19.5 VDC @ for the maximum quantity of detectors per circuit) voltage 20.4 V battery voltage Compatibility ID 100 SLC Loop circuit 20 V peak-to-peak Alarm contact Form C 24 VDC @ 1 A(resistive load) operating voltage Trouble contact Form C 24 VDC @ 1 A(resistive load) Primary power 120 VAC,60 Hz,230 VAC 50-60 Hz Supervisory contact Form A 24 VDC @ 1 A(resistive load) Aux Power 1 24 VDC nominal at 500 mA.A SMK module is Environmental Temperature:0 to 49°C(32 to 120°F). (Continuous circuit) required when using the GSA-UM module to Humidity:0 to 93%RH,noncondensing. support two-wire smoke detectors. Terminal rating All terminals rated for 12 to 18 AWG(0.75 to 2.5 Aux Power 2 24 VDC nominal at 500 mA. mm2) (Resettable circuit) Serial Voltage:2.55 V.Current:30 mA max Auxiliary output 19 to 25.7 VDC communications Base panel Standby: 172 mA Remote annunciator 8 drops max,RS-485 Class A or B current draw Alarm:267 mA Input zones 32 max. Agency Listing UL,CSFM and ULC Page 6 of 8 DATA S i,,_,_ , M85005-0130 Not to be used for installation purposes. Issue 4 Ordering Information Part Description VS2 Intelligent Multi-Loop Systems,500 analog point capacity VS2-R 1 Loop System,4 NACs,Red door.Surface mount enclosure, 115 Vac, English. VS2-RD 1 Loop System,two-line dialer,4 NACs, Red door.Surface mount enclosure, 115 Vac,English. VS2-G 1 Loop System,4 NACs,Silver door.Surface mount enclosure, 115 Vac, English. VS2-GD 1 Loop System,two-line dialer,4 NACs,Silver door.Surface mount enclosure, 115 Vac,English. VS2-GC(I) 1 Loop System,4 NACs, 16 zone LED display,Silver door.Surface mount enclosure, 115 Vac,English. VS2-G-F i'I 1 Loop System,4 NACs, 16 zone LED display,Silver door.Surface mount enclosure, 115 Vac,French. VS2-G-2(2) 1 Loop System,4 NACs,Silver door.Surface mount enclosure,230 Vac, English. VS2-R-2(2) 1 Loop System,4 NACs,Red door.Surface mount enclosure,230 Vac, English. VS2-G-SP121 1 Loop System,500 point capacity,4 NACs,silver door.Surface mount enclosure, 115 Vac,Spanish VS2-G-2-SP1�1 1 Loop System,500 point capacity,4 NACs,silver door.Surface mount enclosure,230 Vac,Spanish VS2-G-PG(2) 1 Loop System,500 point capacity,4 NACs,silver door.Surface mount enclosure, 115 Vac, Portuguese VS2-G-2-PG(2) 1 Loop System,500 point capacity,4 NACs,silver door.Surface mount enclosure,230 Vac, Portuguese SA-TRIM2 Flush mount trim,black Replacement Electronics 500elec-VS Replacement Base electronics,Vigilant,500pt system,includes main board,base plate,User interface and 1 loop. 500elec-VS-FR111 Replacement Base electronics,Vigilant,500pt system,includes main board,base plate,User interface and 1 loop,French 500elec-VS-SP121 Replacement Base electronics,Vigilant,500pt system,includes main board,base plate,User interface and 1 loop,Spanish 500elec-VS-PG121 Replacement Base electronics,Vigilant,500pt system,includes main board,base plate,User interface and 1 loop,Portuguese Option Cards SA-DACT Dual Line Dialer/Modem,supports 4/2 and Contact ID,mounts in cabinet on base plate. _ SA-232 Serial Port(RS-232),for connection to printers&computers,mounts in cabinet to base plate SA-ETH Ethernet Port,Slave,mounts in cabinet on base plate V-SLC SLC Loop Expansion Module.Adds second loop to VS2 systems,250 point capacity.Mounts in cabinet on main board. D16L-VS LED Annunciator Module, 16 groups,2 LEDs per group with insertable labeling. Mounts in cabinet on VS2 systems. Remote Annunciators(refer to Data Sheet 85005-0128) LCD Remote Annunciators(mount to standard 4"square electrical box) RLCD Remote Annunciator,4X20 LCD&Common Indicators for displaying system status.Off-white housing. RLCD-R Remote Annunciator,4X20 LCD&Common Indicators for displaying system status.Red housing. RLCD-C Remote Annunciator,4X20 LCD.Common controls and status indicators.Off-white housing. RLCD-CR Remote Annunciator,4X20 LCD.Common controls and status indicators. Red housing. RLCDF(1) Remote Annunciator,4X20 LCD&Common Indicators for displaying system status.Off-white housing. RLCD-CF(11 Remote Annunciator,4X20 LCD.Common controls and status indicators.Off-white housing. RLCD-SP(2) Remote Annunciator,4X20 LCD.Common system status indicators.Off-white housing.Spanish. RLCD-PG(2) Remote Annunciator,4X20 LCD.Common system status indicators.Off-white housing. Portuguese. RLCD-C-SP(2) Remote Annunciator,4X20 LCD.Common controls and status indicators.Off-white housing.Spanish. RLCD-C-PG(2) Remote Annunciator,4X20 LCD.Common controls and status indicators.Off-white housing.Portuguese. LED Remote Annunciators&Expander(mount to standard 4"square electrical box) RLED-C Remote Annunciator.Common controls and status indicators with 16 X 2-LED groups for zone display.Off-white housing. RLED-CR Remote Annunciator.Common controls and status indicators with 16 X 2-LED groups for zone display.Red housing. RLED-CF(1) Remote Annunciator.Common controls and status indicators with 16 X 2-LED groups for zone display.Off-white housing,French. RLED-C-SP(2) Remote Annunciator,common controls and status indicators. 16 groups w/2 LEDs each for zone display.Off-white housing.Spanish. RLED-C-PG(2) Remote Annunciator,common controls and status indicators.16 groups w/2 LEDs each for zone display.Off-white housing.Portuguese. RLED24 Remote Annunciator Zone expander.24 X 2-LED groups with custom label areas for display of alarm and trouble.Off-white housing. RLED24R Remote Annunciator Zone expander.24 X 2-LED groups with custom label areas for display of alarm and trouble.Red housing. Remote Annunciator Cabinets&Accessories RA-ENC1 Remote Annunciator Enclosure,key locked with plexiglass window for one RLCD(C)or RLED(C). RA-ENC2 Remote Annunciator Enclosure,key locked with plexiglass window with space for 2 of either RLCDx,RLEDx or RLED24. RA-ENC3 Remote Annunciator Enclosure,key locked with plexiglass window with space for 3 of either RLCDx,RLEDx or RLED25. RKEY Keyswitch,single gang,provides key operated enable or disable of common controls on RLCD or RLED units. LSRA-SB Surface Mount Box-for R Series single units. Graphic Annunciator Drivers(comes with a snap track for mounting in custom graphic enclosures) GCI Provides outputs for common indicators and 32 alarm/supv zones as well as inputs for common switches. Programming Tools VS-CU Vigilant VS Series configuration and diagnostics utility. 260097 RS232 cable,4 conductor,DB9 PC interface Notes: (1)Available in Canada only. (2)Available in international markets only. Page 7 of 8 DATA SHEET M85005-0130 Not to be used for installation purposes. Issue 4 Ordering Information TO WA R D S Part Description Ship wt. Number A UTC Fire&Security Company Analog Addressable Detectors and Bases Detection&alarm since 1872 V-PHS Intelligent Analog Optical/Fixed Temperature Detector 0.25(0.11) u.S. V-PS Intelligent Analog Optical Smoke Detector 0.25(0.11) T 888 378 2329 V-HRD Intelligent Analog Rate-of-Rise Heat Detector 0.25(0.11) F 866 503 3996 V-HFD Intelligent Analog Fixed Temperature Heat Detector 0.25(0.11) Canada GSA-SD Intelligent Analog Duct Detector 2.4(1.1) Chubb Edwards T 519 376 2430 B4U Standard Base 0.11 (0.05) F 519 376 7258 RB4U Relay Detector Base 0.11 (0.05) Southeast Asia IB4U Isolator Detector Base 0.11 (0.05) T:+65 6391 9300 SB4U Audible(Sounder)Detector Base 0.11 (0.05) F:+65 6391 9306 AB4G-SB Surface Box for Audible Base 1.0(0.45) India RLED Remote alarm LED,use with standard base only 0.2(.09) T:+91 80 4344 2000 F:+91 80 4344 2050 System Accessories Europe CTM City Tie Module. Mounts in 2-gang electric box.Provides connection to 0.6(0.3) T+32 2 725 11 20 a local energy fire alarm box. F+32 2 721 86 13 BC-1 Battery Cabinet. 14.0"x 18.25"x 7.25"Free-standing cabinet with key 50.0(22.7) Latin America lock.Supports up to 40 Ah batteries.Holds up to 2 12V24A batteries. T 305 593 4301 BC-1R Battery Cabinet-Red. 14.0"x 18.25"x 7.25"Free standing cabinet 50.0(22.7) F 305 593 4300 with key lock.Supports up to 40 Ah batteries. Holds up to 2 12V24A batteries. utcfireandsecurity.com IOP3A Isolator Module-RS232. For use with short haul modems. 1.61 (0.7) ©2010 UTC Fire&Security. RPM Reverse Polarity Module 3.0(1.36) All rights reserved. MFC-A Multifunction Fire Cabinet,8"x 14"x 3.5"-RED. 20.6(9.4) MIR-PRT/S System Printer-Desktop style. 36.6(16.6) Analog Addressable Modules GSA-CC1 Single Input Signal Module(Standard Mount) 0.5(0.23) GSA-MCC1 Single Input Signal Module(UIO Mount) 0.18(0.08) GSA-CC1S Synchronization Output Module(Standard Mount) 0.5(0.23) GSA-MCC1S Synchronization Output Module(UIO Mount) 0.18(0.08) GSA-CC2 Dual Input Signal Module(Standard Mount) 0.5(0.23) GSA-MCC2 Dual Input Signal Module(UIO Mount) 0.18(0.08) GSA-CR Control Relay Module(Standard Mount) 0.4(0.15) GSA-MCR Control Relay Module(UIO Mount) 0.18(0.08) GSA-CRR Polarity Reversal Relay Module(Standard Mount) 0.4(0.15) GSA-MCRR Polarity Reversal Relay Module(UIO Mount) 0.18(0.08) GSA-RM1 Riser Monitor Module(Standard Mount) 0.5(0.23) GSA-MRM1 Riser Monitor Module(Plug-in) 0.18(0.08) GSA-10 Input/Output Module(Standard Mount) 0.34(0.15) GSA-MIO Input/Output Module(Plug-in) 0.22(0.10) GSA-CT1 Single Input Module 0.4(0.15) GSA-CT2 Dual Input Module 0.4(0.15) GSA-MCT2 Dual Input Plug-in(UIO)Module 0.1 (0.05) GSA-IM Fault Isolator Module 0.5(0.23) GSA-MM1 Monitor Module 0.4(0.15) GSA-WTM Waterflow/Tamper Module 0.4(0.15) SMK Smoke Power Converter Module 0.4(0.15) 0 Page 8 of 8 DATA S i, , M85005-0130 Not to be used for installation purposes. Issue 4 Vigilant Catalog► Intelligent Initiating Devices /G/LAN T Fire & Life Safety Intelligentionom . 000000 amimmaCombination . Smoke/CO Detector V-PCOS, V-PCOS-CA O Description Standard Features Vigilant brand V-PCOS photoelectric detectors bring advanced • Optical smoke sensing technology with sensing technology to a practical design that increases efficiency, carbon monoxide sensor saves installation time,cuts costs, and extends life safety and • Field-replacable smoke chamber property protection capabilities. Continuous self-diagnostics en- sure reliability over the long-haul,while innovative field-replacable • Field-replacable carbon monoxide sensor/ smoke chambers make detector maintenance literally a snap.With daughterboard module its on-board CO sensor,this detector pulls double-duty — con- • Uses existing wiring tinually monitoring the environment for signs of smoke, as well as its invisible yet deadly companion,carbon monoxide. • Automatic device mapping The V-PCOS is an intelligent device that gathers analog informa- • Two levels of environmental compensation tion from its smoke and CO sensor(if present), converting this • Two levels of dirty detector warning data into digital signals.To make an alarm decision,the detector's • on-board microprocessor measures and analyzes sensor read Twenty pre alarm settings ings and compares this information to historical data. Digital filters • Five sensitivity settings remove signal patterns that are not typical of fires,thus virtually • eliminating unwanted alarms. Non volatile memory • The V-PCOS includes an advanced carbon monoxide sensor and Electronic addressing daughterboard.When the electrochemical cell reaches its end of • Environmental compensation life after approximately six years,the detector signals a trouble • Identification of dirty or defective detectors condition to the control panel.The sensor/daughterboard module is field-replaceable. • Identification of CO sensors approaching end of life • Automatic day/night sensitivity adjustment • Bicolor(green/red)status LED • Standard, relay,fault isolator, and audible mounting bases Page 1of4 DATA SHE._ . M85001-0619 Not to be used for installation purposes. Issue 2.1 Application Sensing and reporting technology Smoke detection The microprocessor in each detector provides four additional ben- The V-PCOS detects extremely small particles of combustion and efits-Self-diagnostics and History Log,Automatic Device Map- triggers an alarm at the first sign of smoke.Thanks to its high- ping,Stand-alone Operation and Fast, Stable Communication. performance forward scattering reflective response technology, Self-diagnostics and History Log-The V-PCOS constantly the photoelectric smoke sensor responds quickly and reliably to a wide range of fire types, especially slow burning fires fuelled by runs self checks to provide important maintenance information. combustibles typically found in modern multi use buildings. The results are automatically updated and permanently stored in the detector's non-volatile memory. Carbon monoxide detection CO detection has rapidly become a standard part of life safety Automatic Device Mapping-The loop controller learns where strategies everywhere. Monitored CO detection is becoming each device's serial number address is installed relative to other mandated with increasing frequency in all types of commercial devices on the circuit.The mapping feature provides supervision applications, but particularly in occupancies such as hotels, room- of each device's installed location to prevent a detector from being ing houses, dormitories, day care facilities,schools, hospitals, reinstalled(after cleaning etc.)in a different location from where it assisted living facilities, and nursing homes. In fact, more than half was originally. of the U.S. population already lives in states requiring the instal- Fast Stable Communication-On-board intelligence means less lation of CO detectors in some commercial occupancies.This information needs to be sent between the detector and the loop is because carbon monoxide is the leading cause of accidental controller. Other than regular supervisory polling response,the poisoning deaths in America. Known as the"Silent Killer,"CO is detector only needs to communicate with the loop controller when odorless,tasteless,and colorless. It claims nearly 500 lives, and it has something new to report. results in more than 15,000 hospital visits annually. Accessories Installation Detector mounting bases have wiring terminals that are acces- The V-PCOS mounts to North American 1-gang boxes, 3-1/2 inch sible from the"room-side"after mounting the base to the electrical or 4 inch octagon boxes, and to 4 inch square electrical boxes box.The bases mount to North American 1-gang boxes and to 1-1/2 inches(38 mm)deep.They also mount to European BESA 31h inch or 4 inch octagon boxes, 11h inches(38 mm)deep.They and 1-gang boxes with 60.3 mm fixing centers. See mounting also mount to European BESA and 1-gang boxes with 60.3 mm base installation and wiring for more information. fixing centers.The GSA-SB4, GSA-RB4, and GSA-IB4 mount to North American 4 inch sq. electrical boxes in addition to the above boxes.They include the GSA-TS4 Trim Skirt which is used Testing & Maintenance to cover the"mounting ears"on the base.The GSA-SBT bases mounts to 4 inch sq. boxes only. Each detector automatically identifies when it is dirty or defective and causes a"dirty detector"message.The detector's sensitiv- r-ti ity measurement can also be transmitted to the loop controller.A sensitivity report can be printed to satisfy NFPA sensitivity mea- surements which must be conducted at the end of the first year and every two years thereafter. GSA-SBT GSA-SB GSA-IB GSA-RB GSA-LED Audible Base Standard Base Isolator Base Relay Base Remote LED The user-friendly maintenance program shows the current state of each detector and other pertinent messages. Single detectors Remote LED GSA-LED-The remote LED connects to the may be turned off temporarily from the control panel.Availability GSA-SB or GSA-SB4 Standard Base only. It features a North of maintenance features is dependent on the fire alarm system American size 1-gang plastic faceplate with a white finish and red used. When the CO sensor's electrochemical cell reaches its end alarm LED. of life,the detector signals a trouble condition to the control panel. The sensor/daughterboard module is field-replaceable. Scheduled GSA-TS4 Trim Skirt Supplied with 4 inch bases, it can also maintenance(Regular or Selected)for proper detector operation be ordered separately to use with the other bases to help hide should be planned to meet the requirements of the Authority Hav surface imperfections not covered by the smaller bases. ing Jurisdiction(AHJ). Refer to current NFPA 72, NFPA 720, and GSA-SBT-This sounder base is designed for use where local- ULC CAN/ULC 536 standards. ized or group alarm signaling is required.When used with the GSA-T3T4 Temporal Pattern Generator module, it adds an audible output function to the V-PCOS detector. This detector will NOT sense fires that start in areas where smoke cannot reach the detector. Smoke from fires in walls, roofs, or on the opposite side of closed doors may not reach the detector to alarm it. Page 2 of 4 DATA SHEM85001-0619 Not to be used for installa oses. Issue 2.1 Typical Wiring Relay Detector Base,GSA-RB,GSA-RB4 Normally-Normally- The detector mounting bases accept#18 AWG(0.75mm2),#16 This base includes a relay. Nor common Closed Open (1.0mm2), #14 AWG(1.5mm2), and#12 AWG(2.5mm2)wire sizes. mally open or closed operation is selected during installation. Note: Sizes#16 AWG(1.0mm2)and#18 AWG(0.75mm2)are The dry contact is rated for 1 amp 5 ;-�j preferred for ease of installation. See the control panel reference (pilot duty)@ 30 Vdc.The relay's r° t manual for detailed wiring requirement specifications. position is supervised to avoid ac- IIID e` • cidentally jarring it out of position. j„ v The GSA-RB can be operated as DATA IN(-) c ,'7 I / DATA OUT(-) Standard Detector Base,GSA-SB, GSA-SB4 a control relay if programmed to do so at the control panel.The DATA IN(+) DATA OUT(.0 This is the basic mounting base Remote LEDFrom Signature Controller To Next Device for V-PCOS detectors.The GSA- 1 Max resistance relay base does not support the or Previous Device Term Description LED Remote LED is supported 4 11 I. per wire musttnotexceed GSA-LED Remote LED. 1 Normally Open - + CONTACT RATING 2 DATA IN/OUT(+) by the Standard Base. 10 Ohms 1.0 Amp(a30 VDC 3 Common „e (Pilot Duty) 4 DATA IN(-) Term Description \ 5 Not Used 1 Not Used ��J -4, 6 Normally-Closed 2 DATA IN/OUT(+) '� O A- 7 DATA OUT(-) O 3 Not Used c 4 DATA IN(-) r 4 Remote LED(-) DATA IN I-I s I O DATA OUT I-I 5 Remote LED(+) 6 Not Used O 7 DATA OUT(-) DATA IN(+I DATA OUT I+I Audible Detector Base for CO and Fire Detectors,GSA-SBT From Signature Controller To Next Device or Previous Device The GSA-SBT sounder base,when used with the GSA-T3T4 Temporal Pattern Generator, adds an audible output function to the V-PCOS detector. For more information on this device, refer Isolator Detector Base,GSA-IB,GSA-IB4 to Data Sheet M85001-0623--Sounder Base for CO and Fire This base includes a built-in line fault isolator for use on Class A Detectors. circuits.A detector must be installed for it to operate.The isolator T base does not support the GSA-LED Remote LED. 0 The isolator operates as follows: 1 10 i -a short on the line causes all iso- 5 (' % � I ® 000 lators to open within 23 msec .° a, -at 10 msec intervals, -o At- i- o beginning on one side of o Z Z i�` + I <6 <6 .;,, the Class A DATA IN(-) \ DATA OUT(-) 00 a a a circuit nearest the loop I 0 z I ° 0 controller,the isolators ONO*!, close to provide the DATA IN(+) DATA OUT(+)To Next Device NOM A T3T4 Riser+ OOMMM next isolator down the From Signature Controller T3T4 Riser+ ,_ �■.• line with power or Previous Device T3T4 Riser- T3T4 Riser- Term Description SLC+ • 1 Not Used I N SLC+ -when the isolator next to 2 DATA IN/OUT(+) SLC- V the short closes,reopens within 10 msec. 3 DATA IN(-) v sLc- 4 Not Used The process repeats beginning on the 5 Not Used 0 6 DATA OUT(-) O other side of the loopcontroller. 7 Not Used 1. Volume setting.Default is high volume.For low volume,cut trace per item 4. 2. Reserved for future use.Do not cut. 3. Reserved for future use.Do not cut. 4. To configure output volume,cut trace as shown. 5. To next GSA-SBT sounder base or EOL relay. 6. SLC_OUT to next intelligent addressable device. 7. SLC_IN from intelligent addressable controller or previous device. 8. From GSA-T3T4 Temporal Pattern Generator or previous GSA-SBT sounder base. Page 3 of 4 DATA SHE._ . M85001-0619 Not to be used for installation purposes. Issue 2.1 Compatibility -- DWAR D s V-PCOS detectors are compatible only with VS1 and VS2 panel loop controllers. United Technologies Contact us... Warnings & Cautions Email: edwards.fire@fs.utc.com This detector will not operate without electrical power.As fires frequently cause power Web: www.vigilant-fire.com interruption,we suggest you discuss further safeguards with your fire protection specialist. Vigilant is an EDWARDS brand. This detector will NOT sense fires that start in areas where smoke cannot reach the detec- 1016 Corporate Park Drive tor.Smoke from fires in walls, roofs,or on the opposite side of closed doors may not reach Mebane,NC 27302 the detector to alarm it. ©2014 UTC Fire&Security Americas Corporation,Inc.All rights reserved. Specifications subject to change without notice.Edwards is part of UTC Climate,Controls&Security,a unit of Specifications United Technologies Corporation. Normal operating current 70 pA Alarm current 70 pA Operating voltage 15.20 to 19.95 VDC Air velocity 0 to 4,000 ft./min(0 to 20 m/s). Construction High impact engineering polymer Wall mounting Maximum 12 in(305 mm)from ceiling Mounting Plug-in Shipping weight 0.44 lb.(164 g) Compatible bases See Ordering Information Operating environment 32 to 120°F(0 to 49°C),0 to 93%RH,noncondensing Storage temperature —4 to 140°F(-20 to 60°C) Environmental compensation Automatic UL Listed Spacing 30 ft(9.1 m) Ordering Information Catalog Description Ship Wt. Number lbs(kg) V-PCOS Intelligent Photoelectric Detector with carbon monoxide sensor 0.4(0.16) V PCOS CA Intelligent Photoelectric Detector with carbon monoxide sensor 0.4(0.16) (for use in Canadian markets only). Accessories GSA-SB Detector Mounting Base-Standard GSA-SB4 4-inch Detector Mounting Base c/w Trim Skirt GSA-RB Detector Mounting Base w/Relay GSA-RB4 4-inch Detector Mounting Base w/Relay,c/w Trim Skirt 0.2(.09) GSA-IB Detector Mounting Base w/Fault Isolator GSA-IB4 4-inch Detector Mounting Base w/Fault Isolator,c/w Trim Skirt GSA-LED Remote Alarm LED(not for EN54 applications) GSA-SBT Audible(Sounder)Base for CO and Fire Detectors 0.3(0.15) GSA-T3T4 Temporal Pattern Generator 0.3(0.15) GSA-TS4 Trim Skirt(supplied with 4-inch bases) 0.1 (.04) 2-SPRC2 Replacement Smoke Chamber(for V-PCOS detectors) 0.1 (.04) 2-CORPL Replacement CO Sensor 0.1 (.04) a Page4of4 DATA SHEL M85001-0619 Not to be used for installa oses. Issue 2.1 Vigilant Catalog ► Intelligent Initiating /G/LAN T Fire & Life Safety ■ ■ in h) ,-;r• - - - Intelligent -, . / Detectors and Bases Detectors: V-PS, V-PHS, V-HFD, V-HRD �c Bases: B4U, RB4U, IB4U, SB4U S1122 S1122 7300-1657: 0245-0248 Overview Edwards Vigilant brand intelligent analog detectors are meticu- Standard Features lously engineered to deliver high-performance features, superb reliability, and unbeatable quality.With their highly stable design, • Optical, heat, and multisensor models available these detectors resist air movement caused by heating and air • Compatible standard, relay, isolator,and audible bases conditioning, making them reliable performers ideally suited to modern building interiors. • Field replaceable optical chamber The installation and maintenance advantages of Vigilant brand • Electronic Addressing including mapping location intelligent detectors add value throughout their service life.The • Bases mount to standard North American two-gang or 4" twist-and-lock design makes short work of installation and main- square electrical boxes tenance operations.A plastic breakout on the detector housing • Dual color LED provides at a glance alarm indication optionally prevents removal from the base except with a special tool. • Tamper-resistant feature A bright, easy-to-see LED flashes red when the detector is in • Self diagnostic capability with on-board storage of results alarm,thus eliminating much of the guesswork when responding • Optical detectors feature automatic rate compensated sensitiv- to front-panel indications. ity adjustment, as well as dirty sensor warnings • The V-HFD is fixed-temperature heat detector with an alarm • Manufactured to strict international ISO 9001 standards threshold of 135° F(57°C). • The V-HRD is a rate-of-rise heat detector calibrated for 15°F • Assembled using surface mount technology for RF resistance (8°C)per minute. • Conformally coated components resist dust and humidity • The V-PHS houses an optical sensing chamber that detects • Automatic detector test smoke, as well as a fixed-temperature sensor that detects heat.The detector analyzes data from both sensors to deter- • Low Profile Design mine when an alarm is initiated. • The V-PS houses an optical sensing chamber that detects smoke. All detectors feature comprehensive self-diagnostic capability. V-PS and V-PHS optical detectors continuously adjust their sen- sitivity to compensate for changes in the environment such as the presence of dirt, smoke,temperature, and humidity.These detec- tors issue a dirty sensor warning when they reach their preset limit. Page 1 of 6 DATA SHEET M85001-0592 Not to be used for installation purposes. Issue 2 Heat Detectors Detector Bases The V-Series heat detectors are capable of performing compre- hensive self-diagnostics and storing the results. c > 4 in.square electrical box - ® j Thanks to advanced thermistor technology,V-Series heat detectors 0 are ideal for sensing fast,flaming fires and for applications where / smoke detection is inappropriate.They are particularly well-suited ' to areas such as kitchens and shower rooms,where the ambient — temperature is relatively constant,but where steam and smoke are --,-,, .J-;g,, present. gyp--- ,,!.�+; '.�., .�� J�,' r V-HRD Rate-of-Rise Heat Detector provides a 15°F(8°C)per ,k1-`'.i ,` minute rate-of-rise heat sensor for the detection of heat due to fire. ,,,,� 40 1_„------ The - Adaptor bracket The heat sensor monitors the temperature of the air and deter- . mines whether an alarm should be initiated. B4U base assembly V-HFD Fixed Temperature Heat Detector provides a 135°F(57°C) 4)1 _Screws fixed-temperature heat sensor for the detection of heat due to fire. The heat sensor monitors the temperature of the air and deter- Trim ring mines whether an alarm should be initiated. Connect the detector to the base by rotating the detector clock- Optical and combination detectors wise until it snaps into the locked position. V-Series optical detectors continuously adjust their sensitivity The head can be removed by turning it counterclockwise. based on fluctuating environmental conditions such as the pres / a ® o If the head must lock to the base, break away the ence of dirt, smoke, humidity, or changes in temperature, and // locking tab shown below using a pair of pliers. notifies the panel of any changes in sensor sensitivity.When the detector has adjusted its sensitivity to its maximum limit, it issues a a� To then remove the detector head, insert a small dirty sensor warning, allowing enough of a margin for maintenance screwdriver into the slot on the side of the base personnel to clean the detector before it goes into trouble condi- and press in while simultaneously turning the tion. Breakaway tab detector head counterclockwise. These detectors perform comprehensive self-diagnostics and store these details in their on-board memory. B4V-PHS Optical/Fixed Temperature Detector houses an optical The Standard Base sensing chamber that detects smoke, as well as a fixed-temper- detector B4U Analog Standard Detector Base features twist-and-lock ature sensor that detects heat.The detector analyzes data from detector installation and is compatible with with V-Series analog both sensors to determine when an alarm is initiated.This corn- bines om detectors.The base does not require a separate address because bines the suitability of optical sensing for slow burning fires with it shares the address of the device it is connected to. the sensitivity of fixed-temperature detection for fast flaming fires Femote LED Maximum to arrive at a solution that responds reliably to the widest range of oil. resistance - per wire fire types. must not ®� exceed A sophisticated algorithm processes data from both sensors over \`\ . ohms time so that an alarm is only reported when conditions preciselyFrommatch the signature of a fire.This eliminates the shortcomings of controllerr1O �. ^•- al single-sensor optical and heat detection,and significantly reduces or l>`a' the risk of nuisance alarms. previous !O\'0 ��0 To next device II - device V-PS Optical Smoke Detector uses an optical sensing chamber SIC in( I�–—... SIC out(-) to detect smoke.The detector analyzes data gathered by the sen- SLC in(+ SLC out(+) sor to determine when an alarm is initiated. Term Description Term Description Thanks to its high-performance optical sensing chamber,the V-PS 1 SLC in and SLC out(+) 4 Not used responds quickly and reliably to a wide range of fire types, espe- 2 SLC in(-) 5 Remote LED(+) cially slow burning fires fuelled by combustibles typically found 3 Not used 6 SLC out(-) in modern multi-use buildings.The V-PS detects extremely small 3 Not used 6 Remote LED(-) particles and triggers an alarm at the first sign of smoke. LED Indication V-Series detectors provide a bicolor status LED: • Normal: Green LED flashes • Alarm/active: Red LED flashes Page 2 of 6 DATA , M85001-0592 Not to be used for installation purposes. Issue 2 IB4U Isolator Detector Base SB4U Audible(Sounder) Detector Base The IB4U Analog Isolator Detector Base is designed to prevent The SB4U is designed to add an audible output function to corn- an entire communications loop from being disabled when a short patible detectors.The base can operate as an independent local circuit occurs.This is accomplished by isolating the part of the alarm, or as part of a zone or system alarm with synchronized loop containing the short from the remainder of the circuit.These audible output. bases automatically restore the entire loop when the cause of the Depending on the system supporting the device loop,the base short circuit is corrected. can operate as follows: SLCSLC in . SLC out in(jam • SIC out(+) • It can follow the state of the device it supports From To next • It can be controlled and configured for other operating modes controller O device or through programming. rough e pr '/ I ` 4 The SB4U is field-configurable for output tone(steady or temporal) TB2 1' ; °� I" and output volume(low dBA or high dBA).The base must be con- Wo -® nected to a continuous voltage whether the output tone is set to ® ® _ 0 `o „,...;•„, steady or temporal.The base does not require a separate address � •o because it shares the address of the device it is connected to. Term Description 2 3 SLC in(+) DATA+(IN) _ SLC in(-) DATA-(IN) 0 iii® —U— SLC out(+) DATA+(OUT) ' SLC out(-) DATA-(OUT) o 8 Oe, cal !IMIEE AUX_RISER+ A AIM= A gUX_RISER+ RB4U Relay Detector Base AUX_RISERgyM il�.E , AUX_RISER- SLC+ i- ; SLC+ The RB4U Analog Relay Detector Base is designed to add relay SLC- functionality to the listed compatible detectors. Form C latching SLc relay contacts are included for the control of appliances such as 0 door closers,fans, dampers, etc. 1. AUX-RISER IN(from power supply or previous base) SIC in(-)> ► SIC out(-) 2. Volume setting:default is high volume;cut per item 4 for low volume SII;in(+)) • SIC out(+) From 3. Tone setting:default is temporal pattern;cut per item 4 for steady tone To next controller 4 Ndevice 4. To configure output volume or tone,cut the circuit board as shown or 5. AUX_RISER OUT To next base or EOL relay previous /fAlp Q 6. SLC OUT to next intelligent addressable device device '7Ll" TB2 to j 7. SLC IN from intelligent addressable controller or previous device N �: w�� ' I . TB1 ,1' Sleeping rooms: In sleeping areas,the high dBA output and tem- p poral tone settings must be used. However, if the FACP is produc- ing the three-tone temporal evacuation signal,then the high dBA /O and steadytone settings maybe used. N/O COM N/C output g Term Description Term Description AB4G-SB:When using the AB4G-SB box, N/O(Normally open) SLC in(-) DATA-(IN) COM(Common) SLC out(+) DATA+(OUT) install a reinforcing plate at every knockout TB1 N/C(Normally DATA (OUT) used. (Reinforcing plates are included with "�-111r,--- Closed) SLC out(-) the box.) Remove the knockout first,then Contact rating: slide the reinforcing plate into the plastic SLC in(+) DATA+(IN) 2.0a 30vdc resistive housing.After the plate is in place, install the conduit connector and nut. Notes 1. Wire in accordance with NFPA 70,National Electrical Code. 2. Be sure to observe the polarity of the terminals on the terminal block as shown in the diagram. 3. Break wire run at each terminal.Do not loop signaling circuit field wires around terminals. Page 3 of 6 DATA SHEET M85001-0592 Not to be used for installation purposes. Issue 2 Specifications, SB4U Audible Detector Base Operating current in mA(RMS) Operating voltage 24 VDC or 24 VFWR,nominal Voltage Low dBA High dBA Operating current See Table 1 16 VDC 17 28 Supervisory current DC=1.46 mA,FWR=2.15 mA 24 VDC 24 41 Default settings 33 VDC 31 52 Output volume High dBA 16 VFWR 41 48 Output tone Temporal pattern 24 VFWR 51 60 Sound level output See Table 2 33 VFWR 60 66 Temporal pattern 0.5 s on,0.5 s off,0.5 s on,0.5 s off,0.5 s on, VDC=Volts direct current,regulated and filtered 1.5 s off,repeat cycle VFWR=Volts full wave rectified Operating environment Temperature 32 to 120°F(0 to 49°C) Sound level output(dBA) Humidity 0 to 93%RH,noncondensing at 90°F(32°C) Storage temperature -4 to 140°F(-20 to 60°C) Signal Voltage Low dBA High dBA Compatible V-PS,V-PHS,V-HRD,and V-HFD detectors Reverberant room per UL 464[1] detectors 16 VDC 71.3 77.2 Compatible electrical North American 2-1/2 in.(64 mm)deep 2 gang Temporal 24 VDC 75.0 79.8 boxes box 33 VDC 77.7 81.5 Standard 4"square box 1-1/2 in.(38 mm)deep 16 VDC 75.8 80.5 box Steady 24 VDC 79.2 84.1 European 100 mm square box 33 VDC 82.0 86.0 Wire size 12, 14, 16,or 18 AWG wire(2.5, 1.5, 1.0, Reverberant room per UL 268[2] or 0.75 sq.mm) (Sizes 16 and 18 AWG are preferred) 16 VDC 77.3 83.2 Base diameter 6.0 in.(152 mm) Temporal 24 VDC 81.0 85.8 Height from box 2.58 in.(66 mm) 33 VDC 83.7 87.5 (including detector) 16 VDC 81.8 86.5 Maximum distance 12 in.(305 mm) Steady 24 VDC 85.2 90.1 from ceiling(wall 33 VDC 88.0 92.0 mount) dBA=Decibels,A-weighted [1]For UL 464 applications,low dBA settings are for private mode only [2]For UL268 applications,high setting must be used for evacuation Specifications, Detectors V-PHS V-PS V-HRD V-HFD Air velocity 0 to 5,000 ft/min(0 to 25.39 m/s) N/A Smoke sensitivity range 0.67%-3.66% ULI fixed-temp alarm rating 135°F(57°C) N/A 135°F(57°C) ULC fixed-temp alarm rating 140°F(60°C) 140°F(60°C) Maximum Spacing 30 ft(9.1 m) 50 ft(15 m)centers Rate-of-Rise N/A 15°F(8°C)/min. N/A Operating voltage 15.2 to 19.95 VDC Normal operating current 45 pA,average Alarm current 45 pA,average Environmental compensation Automatic Compatible bases B4U Standard,RB4U Relay,IB4U Isolator,SB4U Audible Maximum distance from ceiling wall-mounted 12 in(305 mm) Storage temperature -4 to 140°F(-20 to 60°C) Operating environment Temperature:32 to 120°F(0 to 49°C);Humidity:0 to 93%RH,noncondensing at 90°F(32°C) Meets UL 268, Meets UL 268, Agency listings ULC-S529-02,UL 521, ULC-S529-02,NFPA 72, Meets UL 521,ULC-S530-M91,NFPA 72,and ULC-S530-M91, NFPA 72, and CAN/ULC S524-01 CAN/ULC S524-01 and CAN/ULC S524-01 Page4of6 DATA Si.,_, . M85001-0592 Not to be used for installation purposes. Issue 2 Specifications, Bases B4U Standard Base IB4U Isolator Detector Base RB4U Relay Detector Base Operating environment Temperature 32 to 120°F(0 to 49°C) Humidity 0 to 93%RH,noncondensing at 90°F(32°C) Storage temperature range -4 to 140°F(-20 to 60°C) Compatible detectors V-PS,V-PHS,V-HRD,and V-HFD detectors Compatible electrical boxes North American 2-1/2 in.(64 mm)deep 2 gang box Standard 4 in.square box 1-1/2 in.(38 mm)deep box European 100 mm square box Wire size 12, 14, 16,or 18 AWG wire(2.5, 1.5, 1.0,or 0.75 sq.mm) (Sizes 16 and 18 AWG are preferred) Base diameter 6.0 in.(152 mm) Height from box(including detector) 2.08 in.(53 mm) 2.57 in.(65 mm) Maximum distance from ceiling(wall 12 in.(305 mm) mount) Ordering Information Model Description Ship Wt.:lb.(kg) V-PHS Intelligent Analog Optical/Fixed Temperature Detector 0.25(0.11) V-PS Intelligent Analog Optical Smoke Detector 0.25(0.11) V-HRD Intelligent Analog Rate-of-Rise Heat Detector 0.25(0.11) V-HFD Intelligent Analog Fixed Temperature Heat Detector 0.25(0.11) B4U Standard Base 0.11 (0.05) RB4U Relay Detector Base 0.11 (0.05) IB4U Isolator Detector Base 0.11 (0.05) SB4U Audible(Sounder)Detector Base 0.11 (0.05) AB4G-SB Surface Box for Audible Base 1.0(0.45) GSA-LED Remote alarm LED,use with standard base only 0.2(.09) 211-10PKG Replacement optical chambers(package of 10) 0.25(0.11) Page 5 of 6 DATA SHEET M85001-0592 Not to be used for installation purposes. Issue 2 DWARDS United Technologies Contact us... Email: edwards.fire@fs.utc.com Web: www.vigilant-fire.com Vigilant is an EDWARDS brand. 1016 Corporate Park Drive Mebane,NC 27302 ©2013 UTC Fire&Security Americas Corporation,Inc.All rights reserved. Specifications subject to change without notice.Edwards is part of UTC Climate,Controls&Security,a unit of United Technologies Corporation. 0 rn Page 6 of 6 DATA S i M85001-0592 Not to be used for installation purposes. Issue 2