This letter outlines Phase 2 of the Enzian Condominiums fire alarm project. Last summer,the
fire alarm panel malfunctioned and was replaced. Phase 2 was to be completed this spring.
This phase will include the installation of smoke/carbon monoxide and smoke/heat detectors
with integral sounders into each unit. Carbon monoxide detection will sound a local alarm and
call the fire department. Smoke detection will be a local, supervisory condition only. Heat
detection will activate a general alarm condition. Devices have an integral sounder base for
occupant notification, temporal 3 pattern for smoke or heat detection, and temporal 4 pattern for
carbon monoxide.
Drawings outlining device locations are attached. A battery calculation and equipment data
sheets are also included. Please let me know if you have any questions.
Sincerely,
Deborah L. Shaner, PE
Fire Protection Engineer
v•
.'�° 352331 Z
' • ; :" ,
t i
t ����e .
�, -. .'. -
Vigilant VS2 FACP
Battery Calculations
Standby
Number of Current Total Current
Device Type Devices (Amps) (Amps)
Base Panel 1 X 0.172 = 0.172 _
SA-DACT 1 X 0.3 = 0.3
GSA-CT2 Dual Monitor Module 7 X 0.000396 = 0.002772 _
V-PHS Smoke/Heat Detectors 44 X 0.000045 = 0.00198
VPCOS Smoke/CO Detectors 36 X 0.000045 = 0.00162 _
GSA-CR Control Relay 3 X 0.0001 = 0.0003
SUM COLUMN FOR STANDBY LOAD 0.478672 = AMPS
Alarm Load
Number of Current Total Current
Device Type Devices (Amps) (Amps)
Base Panel 1 X 0.267 = 0.267 _
SA-DACT 1 X 0.3 = 0.3
GSA-CT2 Dual Monitor Module 7 X 0.00068 = 0.00476 _
V-PHS Smoke/Heat Detectors 44 X 0.000045 = 0.00198
VPCOS Smoke/CO Detectors 36 X 0.0001 = 0.0036 _
GSA-CR Control Relay 3 X 0.0001 = 0.0003
OUTSIDE A/V 1 X 0.475 = 0.475 _
SUM COLUMN FOR STANDBY LOAD 1.05264 = AMPS
Standby Load Required Standby Time in Hours
Current (Amps)
0.478672 X 24 = 11.49
Alarm Load Required Alarm Time in Hours
Current (Amps) (15 minutes)
1.05264 X 0.25 = 0.26
Add Standby and Alarm Load for Required
Ampere Hour Battery 11.75
Multiply by the Derating Factor of 1.2
Total Ampere Hours Required = 14.10
Batteries Provided: 17AH Batteries