Loading...
HomeMy WebLinkAboutA15-0033_Battery Calcs-Wall Street_1430760420.pdf Global Project Values: SILENT Project Name: Wall Street Building Standby Hours: 24 KNIGHT Project ID: Alarm Mins: 15 Prepared By: Brad Wolniak/George Sharer Derating Factor: 1.2 5820XL Calculations Date: 04/30/2015 Voltage Drop Warning Version 02.26.09 Threshold%: 10 Panel ID: 5820XL Model: 5820XL Add.Fire Alarm Control Panel Max NAC Current: 3.0 Amps Location: Main level lobby--front entry Volts: 24 VDC Max Panel Current: 6.0 Amps Ckt.# Circuit Name Qty Current Draw Wire AWG Ohms Per Length(ft) Actual Volts @ %Drop Standby Alarm &Type 1000 Ft. One-Way Ohms EOL 5820XL 5820XL CTRL Panel 1 0.309 0.880 SD500-AIM Addr.Input Mod 0.000 0.000 SD500-MIM Mini-Input Module 0.000 0.000 SD500-ARM Addr.Relay Module 0.000 0.000 SD500-PS Addr.Pull Station 6 0.003 0.003 SD505-AIS Addr.Ion Smoke Det 0.000 0.000 SD505-AHS Addr.Heat Detector 1 0.001 0.001 SD505-APS Addr.Photo Smoke Det 12 0.007 0.007 SD505-DUCTR Addr.Duct w/Relay 0.000 0.000 SD505-DUCT Addr.Duct 0.000 0.000 SD500-ANM Addr.Notification Module 0.000 0.000 SD500-LED Addr.LED Module 0.000 0.000 SD500-SDM Addr.Smoke Det.Mod. 0.000 0.000 SD505-6RB Addr.Det.Relay Base 0.000 0.000 SD505-6SB Addr.Det.Sounder Base 0.000 0.000 SD505-61B Addr.Det.Isolator Base 0.000 0.000 SD500-LIM Line Isolation Module 0.000 0.000 5815XL SLC Loop Expander 0.000 0.000 5860 LCD Remote Annunc 0.000 0.000 5824 Serial/Parallel Module 0.000 0.000 5496 Power Expander 0.000 0.000 5895XL Power Expander 0.000 0.000 5865-4 LED Annunciator(4G) 0.000 0.000 5865-3 LED Annunciator(3G) 0.000 0.000 5880 LED Driver Module 0.000 0.000 5883 Relay Module 0.000 0.000 PGM-I/O#1 Notification Appl Circuit 0.000 0.000 #14 Solid 2.52 0.00 20.40 0.00% PGM-I/O#2 Notification Appl Circuit 0.000 0.000 #14 Solid 2.52 0.00 20.40 0.00% #3 First Floor Notification Appl Circuit 0.020 1.412 #14 Solid 2.52 200 1.01 18.98 6.98% #4 Second Floor Notification Appl Circuit 0.020 1.909 #14 Solid 2.52 200 1.01 18.48 9.43% #5 Third Floor Notification Appl Circuit 0.001 0.005 #14 Solid 2.52 200 1.01 20.39 0.02% PGM-I/O#6 Notification Appl Circuit 0.000 0.000 #14 Solid 2.52 0.00 20.40 0.00% Total Standby Current(Amps) 0.360 4.216 Total Alarm Current(Amps) Standby Time In Hours 24 0.250 Alarm Time In Minutes/60 (15 Mins) Total Standby AH Required 8.651 1.054 Total Alarm AH Required Total Combined AH Required 9.70 Command Shortcuts Multiply By The Derating Factor 1.20 Minimum Battery AmpHours Required 11.65 Configure Circuits Print Page