Loading...
HomeMy WebLinkAboutA15-0036_FA000A_1432746660.pdf so CliI/4 4SFAimhutc X UNIT A - BatteryCalculations - O�' M1 QD7 EL LEGEND : Standby 05/27/15ilFi &Err ergency Services Number of Current Total Current SYMBOL DEVICE MANUFACTURER/PART# MOUNTING Device Type Devices (Amps) (Amps) ELK M1 GOLD Main FACP CPU 1 X 0.032 = 0.032 FACP Fire Alarm Control Panel w/10AH Batteries Mount on wall in manufacturer backbox Keypad 1 X 0.04 = 0.04 i3 Smoke Detector with Sounder 5 X 0.00005 = 0.00025 KP i4 COSMO Smoke/CO Detector w/Sounder 5 X 0.00005 = 0.00025 LCD Keypad/Annunciator ELK M1 LCD Mount on wall in manufacturer backbox COSMO Interface Module 10 X 0.022 = 0.22 SUM COLUMN FOR STANDBY LOAD 0.2925 = AMPS Alarm Load O Combination Smoke & System Sensor i3 series 4WTA-B Heat Detector w/Sounder Y 4" square box Number of Current Total Current Device Type Devices (Amps) (Amps) Combination Smoke and Main FACP CPU 1 X 0.032 = 0.032 COOCO Detector w/Sounder System Sensor i4 series COSMO-4W 4" square box Keypad 1 X 0.04 = 0.04 i3 Smoke Detector with Sounder 5 X 0.025 = 0.125System Sensor 5601P i4 COSMO Smoke/CO Detector wlSounder O 5 X 0.04 = 0.2 Heat Detector w/4193SN Addressable module 4" square box COSMO Interface Module 10 X 0.034 0 34 Outside Horn/Strobe 1 X 0.212 = 0.212 SUM COLUMN FOR ALARM LOAD 0.949 = AMPS E Cosmo Interface Module COSMOD4W it Standby Load Required Standby Time in Hours Current (Amps) o 0.2925 X 24 = 7.02 KB Knox Box z Alarm Load Required Alarm Time in Hours Current (Amps) (15 MINUTES) w Horn/Strobe, weatherproof System Sensor P2RK Weatherproof backbox 5 0.949 X 0.25 = 0.24 Add Standby and Alarm Load for Required Ampere Hour Battery 7.26 Multiply by the Derating Factor of 1.2 Total Ampere Hours Required = 8.71 GENERAL NOTES: w Minimum Battery Size Provided: 1OAH0 1 . ALL EQUIPMENT IS TO BE INSTALLED AND TESTED IN ACCORDANCE WITH MANUFACTURER STANDARDS, FIRE DEPARTMENT REQUIREMENTS AND NFPA 72. 2. REFER TO MANUFACTURERS DATA SHEETS AND INSTALLATION INSTRUCTIONS FOR FURTHER DEVICE ZONE LIST- UNIT A INFORMATION REGARDING PRODUCT INSTALLATION, WIRING DIAGRAMS, PROGRAMMING AND DEVICE zz Zone _Type of Device Level Description OPERATION. 001 SMOKE DETECTOR LOWER MECH RM AT FACP N 1- 002 CO/SMOKE DETECTOR LOWER MUDROOM oo Z 003 HEAT DETECTOR LOWER GARAGE rn • 004 SMOKE DETECTOR MAIN WEST BEDROOM I (1) 005 CO/SMOKE DETECTOR MAIN FAMILY ROOM 0 U 006 CO/SMOKE DETECTOR MAIN HALLWAY 007 SMOKE DETECTOR MAIN NE BEDROOM i O O0 008 SMOKE DETECTOR MAIN SE BEDROOM .• ��IG •� /f\ E U) 009 SMOKE DETECTOR UPPER MASTER BEDROM . � r::0. ( 1 ) L a� 010 CO/SMOKE DETECTOR UPPER HEARTH ROOMd _ c w 011 CO/SMOKE DETECTOR UPPER GREAT ROOM mr:-4. ` tali 3523.a 4) o z 1.-%T • • -C Q 012 MONITOR LOWER SPRINKLER WATERFLOW µ 6.,: .; c= 013 MONITOR LOWER SPRINKLER TAMPER �� s ' ,,C, 0 C 014 015 016 i C 1 W �NDTE: LEVEL WILL BE INCLUDED IN DEVICE ADDRESS DESCRIPTION. W D = 4-WIRE DATA/POWER, 4-#16AWG (2 PAIR) -� C X = 2-WIRE DATA, 2-#16AWG 2 approved for install. Stamped plans to be kept N = 2-WIRE SOUNDER CIRCUIT, 2-#18AWG on job site and available at time of inspection. Z = 2-WIRE DATA CIRCUIT, 2-#16AWG EOL EOL C KP = KEYPAD CIRCUITING, 4-#18AWG co a) - ro RISER NOTES: C 1- o D D d °O 1. REFER TO ELK M1 INSTALLATION MANUAL FOR MORE INFORMATION. 0 . 2. WIRE SIZE MAY BE VARIED, PROVIDED IT MEETS L,N L,N N < MANUFACTURERS SPECIFICATIONS. c c rre) 0 3. VERIFY WIRING OF SYSTEM SENSOR COSMOD4W (TYP) (TYP) - o 0 PRIOR TO INSTALLATION. WIRING DIAGRAM ISZ (f) W > U INCLUDED SUBMITTAL BOOKS. 1 0p O m U 120VAC DEDICATED POWER ELK M1 N CONTROL PANEL Z FLOW SWITCH o. � Z TAMPER SWITCH TELEPHONE LINE - FIRE TELEPHONE LINE - SECURITY BELL N , WP OUTPUT I-U. EOLR RISER D I A G R A M DA OUTPUT KP KEYPAD KEYPAD LLJ O I_ Q C CL w PROJECT INFORMATION : 0 Z SEQUENCE OF Z J w w NUGGET LANE DUPLEX 0 J Z o VAIL, COLORADO = OPERATIONS: z X w .4- ,‹ o o N o FIRE ALARM SYSTEM J m NQ oNa wQ v7 J og Q E M N w N m N o W Z a w AHJ: VAIL FIRE & EMERGENCY SERVICES > o w O o g Z D Z Z u mi- o LL, APPLICABLE CODES: 2010 NFPA 72, 2012 IFC, 2012 IBC J Q < NE I- Lw c l 15m 0_ W W CO LL (no (no (n0 0 ~ o0 USE: DUPLEX D Z I- W W m m m W I 1.1J ES LiJN Q < (I) 0 DEVICE j- z M z M z m > w .17t z >z FIRE ALARM SYSTEM FOR DUPLEX UNIT. SYSTEM INCLUDES A NEW COMBO W J >- DESCRIPTION a a a a 1- o F- o F- o a m Q o Q oi SECURITY/FIRE ALARM CONTROL PANEL. SMOKE DETECTORS WILL BE Z W m INSTALLED IN SLEEPING ROOMS AND COMBINATION SMOKE/CARBON Q SMOKE DETECTOR X X X MONOXIDE DETECTORS WILL BE INSTALLED WITHIN 15' OF FIREPLACES Jw AND AREAS OUTSIDE OF SLEEPING ROOMS. DETECTORS HAVE INTEGRAL W J HEAT DETECTOR X X X SOUNDERS. A KNOX BOX WILL BE MOUNTED ON THE OUTSIDE OF THE 0 Z Q 0 HOME. THE SPRINKLER SYSTEM WILL BE MONITORED, SMOKE DETECTORS co LLI CARBON MONOXIDE DETECTOR X X X ARE RESTORABLE AT THE KEYPAD. co (2 w Z LL 0 SPRINKLER WATERFLOW SWITCH X X X X FIRE PROTECTION ENGINEER: SHEET DESCRIPTION: SPRINKLER TAMPER SWITCH X X DEBORAH SHANER, P.E., SHANER LIFE SAFETY COVER SHEET PO BOX 1073, FRISCO, CO 80443 DRAWN BY: DATE: POWER LOSS, OPEN CIRCUIT, GROUND FAULT X X PHONE: 970-409-9082 FAX: 970-797- 1898 DLS 5/8/15 UNIT A SHEET#: FA-0.00A