A15-0049_DATA SHEETS_1432741080.pdf
Fire Alarm Submittal Project: Vail Police &Municipal Building 75 South Frontage Road Vail, Colorado Fire Alarm Contractor: Meridian Intermountain P.O. Box 3940 tieridien Avon, CO 81620 (970) 748-8888; fax (970) 827-9126 1 to rM u rita i n Fire 8k Security Engineer: Deborah L. Shaner, P.E. Fire Protection Engineer Shaner Life Safety Shaner Lifr Safety PO Box 1073 Frisco, CO 80443 (970) 409-9082; fax (970) 797-1898 Vigilant Catalog►Small Building Fire Alarm Solutions /G/LA T TM Fire & Life Safety " • oiff � VS2 IN iff ,,,,. f _.... Life SafetySystem — -� ,_ -_ :Mi =IM 3 53000 S3000 \rte° I- 7165- 1657:0244 FDNY 1 171APPROVAL �'=� #6020 FM Overview Features The Vigilant VS2 intelligent life safety system offers the speed of • Comes standard with one loop(expandable to two)that high-end intelligent processing in a configuration that delivers an supports up to 250(expandable to 500)intelligent devices: uncomplicated solution for small to mid-sized applications.With each VS2 loop supports up to 125 detectors and up to 125 intelligent detection, electronic addressing, automatic device modules. mapping, optional Ethernet°connectivity, and a full line of easily- • Four Class B NACs or two Class A NACs. configured option cards and modules,this quick-to-install system offers versatility that benefits building owners and contractors • Form C contacts for alarm and trouble, Form A for supervisory alike. • Electronic addressing with automatic device mapping The VS2 provides one Class A or Class B analog device loop that • Optional Ethernet port for diagnostics, programming and a supports up to 250 device addresses.A second 250-point loop variety of system reports may be added to the VS2 to expand total system capacity to up • Two programmable switches with LEDs and custom labeling to 500 device addresses.The panel includes four NACs that may be wired for either Class A or Class B operation. • Supports fire suppression routines with a dedicated intelligent releasing module This life safety system features an attractive contemporary design • Supports Genesis horn silence over two wires and UL that fits with any decor. Its gently curved doorfront offers a distinc 1971 compliant strobe synchronization tive flair with available red or silver finishes. Controls are discreetly inset behind a striking black bezel. • Supports up to eight serial annunciators, (LCD, LED-only, and graphic interface). The VS2 supports a wide range of accessories and related equip- ment, including: • 1,000 event panel history log • Intelligent modules, detectors, and bases • Can use existing wiring for most retrofit applications • R-Series remote annunciators • Supports V-Series single and multisensor detectors • option cards that expand system capacity and extend system • Upload/download remotely or locally capabilities. • Two-level maintenance alert reporting • Integrated Carbon Monoxide gas sensing with V-PCOS de- • Pre-alarm and alarm verification by point tectors including distinct audible signaling • Adjustable detector sensitivity • 4 x 20 character backlit LCD display • Optional earthquake hardening: OSHPD seismic pre-approval for component Importance Factor 1.5 Page 1 of 10 DATA SHEET M85005-0130 Not to be used for installation purposes. Issue 6 Application Operation The VS2 life safety system is an easy-to-use intelligent solution for The front panel provides an easy-to-use operator's interface, as small to mid-sized buildings.Analog technology delivers the benefits well as all the necessary controls for front panel programming. of quick and uncomplicated system installation,while a clean and A large back-lit 80-character LCD displays system status, event easy-to-operatate user interface makes panel operation and system details,and programming prompts. Large tactile control buttons maintenance quick and intuitive. are easy to see in low light conditions, and bright multi-color LEDs offer at-a-glance status indication. The smart choice LCD System Electronic addressing eliminates the tedium of setting dipswitches, display LEDs and automatic device mapping ensures that each device resides ees on the system at its correct location. Meanwhile, innovative pro- gramming ro- �' ,, O a rammin allows the designer to customize the system topre- 00:00:00 01/01/07 9 9 9 Y Banner ®® cisely suit the needs of the building owner. Configurable °'A°E® �a Versatility built right in — — =g 51"'" Two fully-programmable front panel switch/LED combinations pro- f `®1-1 j 3 DEF I vide an added measure of simplicity.Their slide-in labels take the �, (3 „� 6 MNo mystery out of custom applications,and present a clean finished TEEM 0%,.. D4WD FAULT - 7 Pom 5 appearance. LiataToR o ® F0 9t® ®® Perfect for retrofits System The VS2 is particularlywell-suited to retrofit applications.All LEDs Controlo pp buttons connections are made over standard wiring—no shielded cable required.This means that in most situations existing wiring can Control buttons be used to upgrade a legacy control panel to V-Series technology without the expense or disruption of rewiring the entire building. Button Description Reset Initiates a system reset. Signals with a difference ACK/Panel Silences the panel and remote annunciators during VS2 NACs are configurable to fully support the advanced signaling Silence an active trouble,supervisory,or alarm event and capabilities of Edwards Genesis and Enhanced Integrity notifica acknowledges new event activations. tion appliances.These devices offer precision synchronization of Signal Silence Alarm mode:Silences active notification appliances. strobes to UL 1971 standards. For Genesis devices, enabling this Pressing Signal Silence a second time turns NACs back on. feature allows connected horns to be silenced while strobes on Drill Initiates a drill confirmation.Pressing drill a second time the same two-wire circuit continue to flash until the panel is reset. turns off the drill function. Remote Dialer:Disables or enables dialer. Clear-cut remote annunciation Disconnect Dialer set to modem only:Disables or enables the Remote annunciation is a strong suit of the VS2. Up to eight an- common alarm relay. nunciators can be installed on a single system. Compatible annun- Left arrow Display mode:Moves the cursor to the left. ciators include a range of LED and LCD models that provide zone Menu mode:Toggles between programming or point annunciation,as well as common control capabilities. selections. Right arrow Display mode:Moves the cursor to the right. The VS2 also supports graphic annunciation with optional RA Menu mode:Retrieves a programming option's sub Graphic Annunicator interface modules. Each interface provides menu and toggles between a programming option's common control, indicators, and 32 LEDS. Consult the Ordering selections. Information section for details. Up arrow Display mode:Advances to the previous event. Menu mode:Moves the cursor up. A complete line of accessories Down arrow Display mode:Advances to the next event. The VS2 life safety system is supported by a complete line of Menu mode:Moves the cursor down. intelligent detectors, modules and related equipment. Consult the Enter Display mode:Displays selected event details. OrderingInformation section for details. Menu mode:Retrieves a programming option's sub menu or jumps to the Save function in the menu. Entry mode:Enters the selected data into the system. Cancel Display mode:Exits the detailed information display. Menu mode:Exits the current menu level. Entry mode:Clears the current entry. Menu Display mode: Enters the menu mode Menu mode:Exits menu mode Space Enters a space,such as a space between words. Alphanumeric Entry mode:Pressing a button once enters the number keypad on the button.Pressing the button twice enters the secondary value. Programmable These buttons can be programmed to control outputs, buttons disable devices or unlatch system outputs.The buttons can be labeled with a slip-in insert. Page 2 of 10 DATA S I. M85005-0130 Not to be used for installation purposes. Issue 6 System LEDs Panel Operation Options LED Description Language English or French Alarm Red LED.On steady when there is an active Marketplace U.S.or Canada alarm. AC fail delay Off•Off-premise notification of an AC power failure Trouble Yellow LED. Flashes when there is a fault on a is immediate. monitored circuit or system component, or when 1 to 15 hours:Delays the off premise notification of a circuit is disabled. an AC power failure by the time period selected. Supv Yellow LED. On steady when there is an active Zone resound On:NACs resound each time a device in the zone goes into alarm even if they were silenced supervisory event. Off: Inhibits the NACs from turning on again(after AC Power Green LED.On when the panel has AC power. they were silenced)when a second device in the Disable Yellow LED. Double-flashes when there is a dis- zone goes into alarm. abled circuit or alarm relay. Reset inhibit after Off:Panel reset is operational immediately. Ground Yellow LED.On steady during an active ground NACs turn on 1 minute:Panel reset is inhibited for one minute. Fault fault. Auto signal Off•Allows immediate silencing of signals from an Test Yellow LED. Flashes when performing an audible silence off normal condition using the Signal Silence button walk test. Steady indicates a silent test. 5 to 30 minutes:Delays the silencing of signals from an off-normal condition by disabling the Signal Monitor Yellow LED. On steady when there is an active Silence button for the time period selected. monitor event. Day start Start time for daytime sensitivity Service Yellow LED. Indicates that detector needs servic- Night start Start time for nighttime sensitivity Detector ing. Date MM/DD/YYYY,DD/MM/YYYY Signal Yellow LED. On steady indicates that NAC cir- Sounder Base Six configuration settings Silence cults are turned off but the panel is still in alarm. Mapping Disabled:Device mapping is not available Remote Yellow LED. On steady indicates that the dialer Enabled:Device mapping is available Disconnect is disabled or that the alarm relay is enabled or LCD banner Banner text for line one and line two.Each line is disabled when the dialer is set to modem only. capable of up to 20 characters. Drill Yellow LED. Indicates that the panel is in drill. Event notification Zone:When a device is a member of a zone,only Reset Yellow LED. Indicates that the panel is resetting. the zone information is sent to the LCD display, LEDs,printer,and dialer. Panel Yellow LED. Indicates that the panel has been Zone/device:Zone information is sent to the LCD Silence silenced during an active trouble,supervisory, or display and LEDs.Device information is sent to the alarm event and indicates that new event activa- printer and dialer. tions have been acknowledged. Device:Only device information is reported. User keys Yellow LED. Programmable. Programming Dimensions V-Series panels are simple to set up, quick to program, and easy to maintain.The auto programming feature quickly gets the panel Surface mounting holes Backbox with Backbox with door and operational using factory default settings. Basic zone and point I4-D2HD3� door attach trim ring attached �D7 settings can be programmed easily through the front panel inter- 0- V 0 80 *V face,so the system is up and running in no time. I° •• u0 j °0 *0 For more advanced system configuration and correlation groups 1 1 r 0 0 programming,V-Series panels interface to a PC running compat- J ® ` ® 0 ible VS CU software.This option offers full system configuration 0.1, D1 . n<• • ® D4 Ds in the familiar Windows®operating environment. Connection is o — e N 0 0 typically made to a laptop through the panel's optional RS-232 o communications port,which can also be used to connect a sys- Surface mounting holes o 0 0 tem printer. _ ° 4--D6—o, Among the many innovations of the VS2 control panel is the D6 LD9el —riD9►I optional network card.This module provides a standard 10/100 Base T Ethernet®network connection that permits access to Backbox and backbox with door the control panel from any remote location with the correct D1* D2 D3 D4 D5* D6 D7 D8 D9 communications protocols. The connection can be used to 28.0" 3.85' 9.0" 22.0" 15.75 10.25' 3.9" 28.2" 2.7' download to the panel from the VS-CU, or upload and view 71.1cm 9.8cm 22.8cm 55.8cm 40.0cm 26.0cm 9.9cm 71.6cm 6.8cm system reports using the VS-CU. "Add 1-1/2 in.(3.81 cm)to D1 and D5 dimensions for trim kit. Available system reports include: • Correlation groups • Device details • Device maintenance • History • Internal status • System configuration • System status • Walk test • Dialer • CO Runtime Page 3 of 10 DATA SHEET M85005-0130 Not to be used for installation purposes. Issue 6 Wiring & Configuration Notification appliance circuits(TB2) Device loop V-Series control panels come equipped with two notification The control panel provides one device loop circuit that can sup- appliance circuits. Each circuit can be individually configured for port 125 detectors and 125 module addresses.The loop circuit is continuous,temporal, synchronized, latching, and coded output. supervised for opens,shorts,and grounds. Circuit specifications Circuit specifications Circuit Type 4 Class B or 2 Class A,2.5 amps each Device loops 1 loop,expandable to 2,Class A or B,each loop Voltage 24 VFWR supporting up to 250 device addresses Current 6.0 A total,2.5 A max.per circuit at 120/230 VAC 60 Hz Communication Maximum 20 V peak-to-peak 5.0 A total at 230VAC 50 Hz line voltage 2.5 A max.per circuit Circuit current 0.5 A max Impedance 26 0 total,0.35 pF max Circuit 660 total,0.5 JF,max EOLR 15 K 4,Y W impedance Isolators 64 maximum Class B wiring Class B Wiring Class A Wiring NAC1 Z + C + C 0 Loop 1 SEC +® 0 NAC1+ Data Line - 0 NAC2- /\ < < Y11+ + EOLR Loop 1 PRI 0 NAC2+ +®""(eBN "(e�N Loop Loop Loop Loop TB2 Loop card device device Data Line device device 0 NAC3 0 NAC3+ < + < Marking indicates 0 NAC4 EOLR output signal polarity X + + / when the circuit is ac- Annunciator loop(TB4) 0 NAC4+ - \ - \ tive.Polarity reverses TB6 when the circuit is not The control panel provides a connection for up to eight serially active.Wire notification driven and supervised remote annunciators. appliances accordingly. Class A wiring Notification appliance Circuit specifications polarity shown in ac- Device loops Class B(Style Y)or Class A(Style Z) 0 NAC1- + tive state. 0 NAC1+ I C Circuit voltage 2.55 V - - � Circuit current 30 mA max 0NAC2 r\b + + _ Circuit Up to 8 annunciators or 4000 feet NAcz+ impedance TB2 Class B Class A 0 0 + Channell Channell Channell Channell 0 + iQQQTB4 ® is) is) ® TB4 Annunciator Annunciator TB6 CH1(+)IN &CH1(+)IN CH1(-)IN -(S)CH1(-)IN ®CH2( IN CH2( IN Auxiliary&Smoke power outputs(TB3) (S)CH2(-)IN (S)CH2(-) IN The control panel provides two auxiliary power outputs which can be used for powering ancillary equipment such as remote an- nunciators and two wire smoke detectors. Aux 2 can be software selected to operate continuous.The circuit is supervised for shorts Alarm,trouble,and supervisory relay(TB3) and grounds. The trouble relay is normally-open, held closed, and opens on any Note: For a complete list of devices that can be connected to this trouble event or when the panel is de-energized.The supervisory circuit, refer to the VS Series Compatibility List. relay is normally-open, and closes on any supervisory event.The Circuit specifications alarm relay changes over on any alarm event. Circuit voltage range 21.9 to 28.3 V Relay specifications Resettable circuit 24 VDC nominal at 500 mA Alarm 1 Trouble Supervisory (Aux power 2) Type Form C Form A Continuous circuit 24 VDC nominal at 500 mA.Use this circuit for Voltage 24 VDC at 1 A resistive 24 VDC at 1 A resistive (Aux power 1) powering two-wire smoke detectors. Note:Any current above 0.5 amp connected to both Aux 1 and 2 will reduce the total Relay circuits can only be connected to power limited sources. available NAC power by that amount. Page 4 of 10 DATA s I.,_,_ i M85005-0130 Not to be used for installation purposes. Issue 6 Option Cards V-Series panels are supported by a complete line of modules and SMK Smoke Power Converter related equipment that enhance performance and extend system The SMK Smoke Power capabilities. Option cards are easy to install and set up.They Converter Module pro- aux ry +1®( simply plug directly into the control panel main circuit board or are vides a regulated power (not resettablepower ) ®E connected to it with a ribbon cable.After installation,terminals source for two-wire smoke remain easily accessible for quick connection of field wiring.The circuits connected to a cabinet provides ample room for wire routing, keeping wiring neat Signature data circuit.The ©l II ®®®®I o and easy to service at all times. SMK monitors the operat- SMK a ing power from the power Power in Power out supply.When power be- o P3- * + SA-ETH Ethernet Interface Card gins to degrade,the SMK SA-ETH wiring The SA-ETH card provides a provides the necessary o ®®®® © rE wor connection standard 10/100 Base T Ethernet operating voltage to the Two-wire smoke 1 Network cable i r network connection for connect- two-wire smoke detection detectors al I ing to an intranet, a local net- circuits. ©I®®®®IP!I®e® I 1 work, or the Internet.The card 16151413 3U 121110 9 can be used to download JP1 - + Pe configuration programming from o +- ❑ ® network.the VS-CU to the panel over the ®®®®I 4 3 2 1 ®®®I o U ® t Data in -1 ® The Ethernet card is installed on +' ®ii the plastic assembly and con- Two-wiresmokei_ Ethernet card detectors i nects to the main circuit board via a ribbon cable. ©I®®®®IFuzllee®e I © 16 15 14 13 311 12 11 10 9 SA-ETH specifications JP1 + Terminate or to next Ethernet 10/100 Base T UM Operating environment 6 ' 6 5 4�3 2 1 Temperature 32 to 120°F(0 to 49°C) O ®®®® ®T®® O Humidity 0 to 93%RH,noncondensing at 90°F Data out (32°C) SMK specifications Input voltage 21.9 to 28.3 VDC(not resettable) V-SLC Loop Expander Card Output voltage 24 VDC nom.at 200 mA,max.,special The V-SLC Loop Expander Card provides an additional device applications loop on the control panel.The card expands the control panel's Ground fault 10 k ohm device capacity to 500 total device addresses, 250 per loop.The impedance card is compatible with Class B or Class A wiring. It is compatible Operating environment with VS2 control panels only. Temperature 32 to 120°F(0 to 49°C) Humidity 0 to 93%RH,noncondensing at 90°F(32°C) The loop expander card connects to connector J7 on the main Storage temperature -4 to 140°F(-20 to 60°C) circuit board. Compatible electrical North American 4 inch square x 2-1/2 in. Class B Wiring Class A Wiring boxes (64 mm)deep 2 gang box or Standard 4 in. - square box 1-1/2 in.(38 mm)deep + Loop 1 SEC ® Data Line Wire size 14, 16,or 18 AWG wire(1.5, 1.0,or 0.75 sq. mm)(Sizes 16 and 18 AWG are preferred) Loop 1 PRI +® "'(epil itgeB� • Loop Loop Loop Loop Loop card device device Data Line device device V-SLC specifications Device addresses on loop 125 detectors and 125 modules Wiring Class B(Style Y)or Class A(Style Z) Operating voltage 20 V peak-to-peak Operating current 0.5 A total Circuit impedance 66 0,0.5 pF,max Terminal rating 12 to 18 AWG(0.75 to 2.5 sq mm) Operating environment Temperature 32 to 120°F(0 to 49°C) Humidity 0 to 93%RH,noncondensing at 90°F (32°C) Page 5 of 10 DATA SHEET M85005-0130 Not to be used for installation purposes. Issue 6 SA-DACT Dialer GSA-REL Releasing Module The SA-DACT provides communications between the control The GSA-REL is an analog addressable module that communicates panel and the central station over a telephone line system. It directly with the fire alarm panel Signature loop controller.The GSA- transmits system status changes(events)to a compatible digital REL controls sprinkler, pre-action and deluge systems,and may alarm communicator receiver over the public switched telephone also be used to release extinguishing agents such as CO2, Halon,or network.The dialer is capable of single, dual, or split reporting foam.The module is easily configured in the field and offers a wide of events to two different account and telephone numbers.The range of options that ensure dependable service,while preventing modem feature of the SA-DACT can also be used for uploading the unnecessary release of extinguishing agent. and downloading panel configuration, history,and current status to a PC running the VS-CU. GSA-REL specifications SA-DACT Phone line 2 The dialer phone lines connect to Input voltage 24 Vdc(power limited) wiring EB phoneljack connectors on the dialer's main circuit Power riser Supervisory current 25 mA,max. Phone line 1 board.Phone line 1 connects to connec- Riser input current 4 amps maximum Phone cables J4 and phone line 2 connects to Alarm 170 mA min.;4 A max. (supplied) -1 1 RJ31 jacks El u-1 connector J1. Output rating 2 A @ 24 Vdc(per circuit) Valves per circuit 4 valves,max. The SA-DACT queues messages ® +I Release Max.supervisory current 0.4 mA(short circuit) '..''enp 9- and transmits them based on prior- circuits Nominal supervisory current 0.18 mA o®_ ity(alarm, supervisory,trouble, and Supervisory voltage 26 Vdc,max.(open ❑a°e- p ry 9 ( P circuit) — monitor).Activations are transmitted End of line device 47k Ohm EOL a�� before restorations. 2 A @ 24 Vdc(for each °❑❑®°�° t.P"U Output rating circuit) ❑❑�0 °° o� Max.supervisory current Q❑ ao_�❑o The SA-DACT is installed on the Pre-release 0.4 mA(short circuit) °° �$ E plastic assembly and connects to the alarm circuits Nominal supervisory current 0.18 mA main circuit board via a ribbon cable. Supervisory voltage 26 Vdc,max.(open circuit) End of line device 47k Ohm resistor SA-DACT specifications Max.supervisory current 0.4 mA(short circuit) Phone line type One or two loop-start lines on a public, Nominal supervisory current 0.18 mA Manual switched network Supervisory voltage 26 Vdc,max.(open circuit) Phone line connector RJ-31/38X(C31/38X) release input End of line device 47k Ohm resistor circuit Circuit type Class B N.O.latching formats Contact ID(SIA DC-05) Yp Operating environment Circuit capacitance 0.1 pF,max Temperature 32 to 120°F(0 to 49°C) Max.supervisory current 0.4 mA(short circuit) Humidity 0 to 93%RH,noncondensing at 90°F Nominal supervisory current 0.18 mA (32°C) Abort circuit Supervisory voltage 26 Vdc,max.(open circuit) End of line device 47k Ohm resistor Compatible DACRs Circuit type Class B N.O.non-latching Receiver Models Formats Circuit capacitance 0.1 pF,max First alarm 3 A@ 24 Vdc Ademco 685 Contact ID Contact rating FBI' CP220 Contact ID output relay (0.6 power factor)Form C Osborne-Hoffman OH 2000 Contact ID Signature Operating voltage 5.2 to 19.95 Vdc Radionics D6600 Contact ID Data line Supervisory current 1000 pA Alarm current 1000 pA Silent Knight 9800 Contact ID Note:Output circuits are power-limited when the riser circuit is power-limited. Sur-Gard SG-MLR1,MLR2 Contact ID VS2 Control Panel O Signature Series smoke detectors Loop Controller i I M I Signature Series modules SA-232 RS-232 interface DI Homcircuit The SA-232 card provides an RS-232 SA-232 wiring i u J interface with VS2 panels. It can be GND(black wire) ® Strobe circuit M TXD(white wire) I SD I Service Disconnect Station used for connecting a printer to the —RXD(red wire) i i I A I Manual Abort Station control panel to print system events.The iI MR I Manual Release Station card also can be used for connecting a ;4)S( ?, Fire Alarm Control Panel l First Alarm Output Relay computer to download a configuration C program from the VS-CU to the control - M )T —I panel. — — The RS-232 card is installed on the plastic assembly and con- isD RELA-EOL Release Circuitl nects to the main circuit board via a ribbon cable. Auxiliary Releasing Module Power Supply (GSA-REL) SDRELA-EOL Release Circuitl SA-232 specifications Operating voltage Standard EIA-232 I A I I MR Terminal rating 12 to18 AWG(0.75 to 2.5 sq mm) For detailed specification and ordering information on the GSA-REL,refer Operating environment to Data Sheet M85001-0531 --Releasing Module. Temperature 32 to 120°F(0 to 49°C) Humidity 0 to 93%RH,noncondensing at 90°F(32°C) Page 6 of 10 DATA S I.i_i_ i M85005-0130 Not to be used for installation purposes. Issue 6 Specifications Device loops 1 loop,expandable to 2,Class A or B,each loop Battery placement VS2 cabinets accommodate up to 18 NH batteries. supporting up to 250 device addresses Use a external cabinet for larger battery sizes. NAC circuits 4 Class B or 2 Class A,2.5 amps each Batteries Batteries must be sealed lead acid type only. Power supply 6.0 A total,2.5 A max.per circuit at 120/230 VAC Maximum charging capacity=26 Ah. 60 Hz Loop circuit Maximum loop resistance:66 0.Maximum loop 5.0 A total at 230VAC 50 Hz,2.5 A max.per capacitance:0.5 pF.Style 4,6,and 7 wiring.64 circuit isolators maximum. 0.5 amps aux power GSA-UM/GSA-MAB 1.5 mA(see the UL and ULC compatibility list for NAC Operating 24 VDC.NAC minimum voltage: 19.5 VDC @ for the maximum quantity of detectors per circuit) voltage 20.4 V battery voltage Compatibility ID 100 SLC Loop circuit 20 V peak-to-peak Alarm contact Form C 24 VDC @ 1 A(resistive load) operating voltage Trouble contact Form C 24 VDC @ 1 A(resistive load) Primary power 120 VAC,60 Hz,230 VAC 50-60 Hz Supervisory contact Form A 24 VDC @ 1 A(resistive load) Aux Power 1 24 VDC nominal at 500 mA.A SMK module is Environmental Temperature:0 to 49°C(32 to 120°F). (Continuous circuit) required when using the GSA-UM module to Humidity:0 to 93%RH,noncondensing. support two-wire smoke detectors. Terminal rating All terminals rated for 12 to 18 AWG(0.75 to 2.5 Aux Power 2 24 VDC nominal at 500 mA. mm2) (Resettable circuit) Serial Voltage:2.55 V.Current:30 mA max Auxiliary output 19 to 25.7 VDC communications Base panel Standby: 172 mA Remote annunciator 8 drops max,RS-485 Class A or B current draw Alarm:267 mA Input zones 32 max. Panel History Log 1,000 events Agency Listing UL,CSFM,ULC and NYFD#6020 Ordering Information Part Description VS2 Intelligent Multi-Loop Systems,500 analog point capacity VS2-R 1 Loop System,4 NACs,Red door.Surface mount enclosure, 115 Vac, English. VS2-RD 1 Loop System,two-line dialer,4 NACs, Red door.Surface mount enclosure, 115 Vac,English. VS2-G 1 Loop System,4 NACs,Silver door.Surface mount enclosure, 115 Vac, English. VS2-GD 1 Loop System,two-line dialer,4 NACs,Silver door.Surface mount enclosure, 115 Vac,English. VS2-GC(1) 1 Loop System,4 NACs, 16 zone LED display,Silver door.Surface mount enclosure, 115 Vac,English. VS2-G-F(1) 1 Loop System,4 NACs, 16 zone LED display,Silver door.Surface mount enclosure, 115 Vac,French. VS2-G-2(2) 1 Loop System,4 NACs,Silver door.Surface mount enclosure,230 Vac, English. VS2-R-2(2) 1 Loop System,4 NACs,Red door.Surface mount enclosure,230 Vac, English. VS2-G-SP(2) 1 Loop System,500 point capacity,4 NACs,silver door.Surface mount enclosure, 115 Vac,Spanish VS2-G-2-SP(2) 1 Loop System,500 point capacity,4 NACs,silver door.Surface mount enclosure,230 Vac,Spanish VS2-G-PG(2) 1 Loop System,500 point capacity,4 NACs,silver door.Surface mount enclosure, 115 Vac, Portuguese VS2-G-2-PG(2) 1 Loop System,500 point capacity,4 NACs,silver door.Surface mount enclosure,230 Vac,Portuguese SA-TRIM2 Flush mount trim,black Replacement Electronics 500eIec-VS Replacement Base electronics,Vigilant,500pt system,includes main board,base plate,User interface and 1 loop. 500elec-VS-FR(1) Replacement Base electronics,Vigilant,500pt system,includes main board,base plate,User interface and 1 loop,French 500elec-VS-SP(2)Replacement Base electronics,Vigilant,500pt system,includes main board,base plate,User interface and 1 loop,Spanish 500elec-VS-PGI�1 Replacement Base electronics,Vigilant,500pt system,includes main board,base plate,User interface and 1 loop,Portuguese Option Cards SA-DACT Dual Line Dialer/Modem,supports 4/2 and Contact ID,mounts in cabinet on base plate. SA-232 Serial Port(RS-232),for connection to printers&computers,mounts in cabinet to base plate SA-ETH Ethernet Port,Slave,mounts in cabinet on base plate V-SLC SLC Loop Expansion Module.Adds second loop to VS2 systems,250 point capacity.Mounts in cabinet on main board. D16L-VS LED Annunciator Module, 16 groups,2 LEDs per group with insertable labeling. Mounts in cabinet on VS2 systems. Page 7 of 10 DATA SHEET M85005-0130 Not to be used for installation purposes. Issue 6 Remote Annunciators(refer to Data Sheet 85005-0128) LCD Remote Annunciators(mount to standard 4"square electrical box) RLCD Remote Annunciator,4X20 LCD&Common Indicators for displaying system status.Off-white housing. RLCD-R Remote Annunciator,4X20 LCD&Common Indicators for displaying system status.Red housing. RLCD-C Remote Annunciator,4X20 LCD.Common controls and status indicators.Off-white housing. RLCD-CR Remote Annunciator,4X20 LCD.Common controls and status indicators. Red housing. RLCDF(1) Remote Annunciator,4X20 LCD&Common Indicators for displaying system status.Off-white housing. RLCD-CF(1) Remote Annunciator,4X20 LCD.Common controls and status indicators.Off-white housing. RLCD-SP(2) Remote Annunciator,4X20 LCD.Common system status indicators.Off-white housing.Spanish. RLCD-PG(2) Remote Annunciator,4X20 LCD.Common system status indicators.Off-white housing. Portuguese. RLCD-C-SP(2) Remote Annunciator,4X20 LCD.Common controls and status indicators.Off-white housing.Spanish. RLCD-C-PG(2) Remote Annunciator,4X20 LCD.Common controls and status indicators.Off-white housing.Portuguese. LED Remote Annunciators&Expander(mount to standard 4"square electrical box) RLED-C Remote Annunciator.Common controls and status indicators with 16 X 2-LED groups for zone display.Off-white housing. RLED-CR Remote Annunciator.Common controls and status indicators with 16 X 2-LED groups for zone display.Red housing. RLED-CF(1) Remote Annunciator.Common controls and status indicators with 16 X 2-LED groups for zone display.Off-white housing,French. RLED-C-SP(2j Remote Annunciator,common controls and status indicators. 16 groups w/2 LEDs each for zone display.Off-white housing.Spanish. RLED-C-PG(2) Remote Annunciator,common controls and status indicators.16 groups w/2 LEDs each for zone display.Off-white housing.Portuguese. RLED24 Remote Annunciator Zone expander.24 X 2-LED groups with custom label areas for display of alarm and trouble.Off-white housing. RLED24R Remote Annunciator Zone expander.24 X 2-LED groups with custom label areas for display of alarm and trouble.Red housing. Remote Annunciator Cabinets&Accessories RA-ENC1 Remote Annunciator Enclosure,key locked with plexiglass window for one RLCD(C)or RLED(C). RA-ENC2 Remote Annunciator Enclosure,key locked with plexiglass window with space for 2 of either RLCDx,RLEDx or RLED24. RA-ENC3 Remote Annunciator Enclosure,key locked with plexiglass window with space for 3 of either RLCDx,RLEDx or RLED25. RKEY Keyswitch,single gang,provides key operated enable or disable of common controls on RLCD or RLED units. LSRA-SB Surface Mount Box-for R Series single units. Graphic Annunciator Drivers(comes with a snap track for mounting in custom graphic enclosures) GCI Provides outputs for common indicators and 32 alarm/supv zones as well as inputs for common switches. Programming Tools VS-CU Vigilant VS Series configuration and diagnostics utility. 260097 RS232 cable,4 conductor,DB9 PC interface Notes: (1)Available in Canada only. (2)Available in international markets only. Analog Addressable Detectors and Bases Shipping Wt. V-PHS Intelligent Analog Optical/Fixed Temperature Detector 0.25(0.11) V-PS Intelligent Analog Optical Smoke Detector 0.25(0.11) V-HRD Intelligent Analog Rate-of-Rise Heat Detector 0.25(0.11) V-HFD Intelligent Analog Fixed Temperature Heat Detector 0.25(0.11) V-PCOS Intelligent Photoelectric Detector with carbon monoxide sensor 0.4(0.16) GSA-SBT Audible(Sounder)Base for CO and Fire Detectors 0.3(0.15) GSA-SD Intelligent Analog Duct Detector 2.4(1.1) B4U Standard Base 0.11 (0.05) RB4U Relay Detector Base 0.11 (0.05) IB4U Isolator Detector Base 0.11 (0.05) SB4U Audible(Sounder)Detector Base 0.11 (0.05) AB4G-SB Surface Box for Audible Base 1.0(0.45) RLED Remote alarm LED,use with standard base only 0.2(.09) System Accessories Shipping Wt. CTM City Tie Module.Mounts in 2-gang electric box.Provides connection to a local energy fire alarm box. 0.6(0.3) BC-1 Battery Cabinet. 14.0"x 18.25"x 7.25"Free-standing cabinet with key lock.Supports up to 40 Ah batteries. 50.0(22.7) Holds up to 2 12V24A batteries. BC-1R Battery Cabinet-Red. 14.0"x 18.25"x 7.25"Free standing cabinet with key lock.Supports up to 40 Ah 50.0(22.7) batteries.Holds up to 2 12V24A batteries. BC-1 EQ Seismic hardening Kit for VS series panels.Includes battery hardening for BC-1 enclosure and components to harden panel internal components.See note. IOP3A Isolator Module-RS232. For use with short haul modems. 1.61 (0.7) RPM Reverse Polarity Module 3.0(1.36) MFC-A Multifunction Fire Cabinet,8"x 14"x 3.5"-RED. 20.6(9.4) MIR-PRT/S System Printer-Desktop style. 36.6(16.6) Page 8 of 10 DATA S i M85005-0130 Not to be used for installation purposes. Issue 6 Analog Addressable Modules Shipping Wt. GSA-CC1 Single Input Signal Module(Standard Mount) 0.5(0.23) GSA-MCC1 Single Input Signal Module(UIO Mount) 0.18(0.08) GSA-CC1 S Synchronization Output Module(Standard Mount) 0.5(0.23) GSA-MCC1S Synchronization Output Module(UIO Mount) 0.18(0.08) GSA-T3T4 Temporal Pattern Generator 0.2(0.1) GSA-CC2 Dual Input Signal Module(Standard Mount) 0.5(0.23) GSA-MCC2 Dual Input Signal Module(UIO Mount) 0.18(0.08) GSA-CR Control Relay Module(Standard Mount) 0.4(0.15) GSA-MCR Control Relay Module(UIO Mount) 0.18(0.08) GSA-CRR Polarity Reversal Relay Module(Standard Mount) 0.4(0.15) GSA-MCRR Polarity Reversal Relay Module(UIO Mount) 0.18(0.08) GSA-RM1 Riser Monitor Module(Standard Mount) 0.5(0.23) GSA-MRM1 Riser Monitor Module(Plug-in) 0.18(0.08) GSA-IO Input/Output Module(Standard Mount) 0.34(0.15) GSA-MIO Input/Output Module(Plug-in) 0.22(0.10) GSA-CT1 Single Input Module 0.4(0.15) GSA-CT2 Dual Input Module 0.4(0.15) GSA-MCT2 Dual Input Plug-in(UIO)Module 0.1 (0.05) GSA-IM Fault Isolator Module 0.5(0.23) GSA-MM1 Monitor Module 0.4(0.15) GSA-REL Analog addressable releasing module 0.5(0.23) 276A-REL Manual releasing station(single-action).English markings,black text on yellow polycarbonate body. 1.0(0.45) 278A-REL Manual releasing station(double-action). English markings,black text on yellow polycarbonate body. 1.0(0.45) RELA-ABT Manual Abort Station.English markings,black text on yellow polycarbonate body. 1.0(0.45) RELA SRV 1 Service Disconnect Switch.One n/c contact and one n/o contact.English markings,white text on blue 1.0(0.45) polycarbonate body. RELA-EOL Polarized end-of-line relay.English markings on stainless steel cover. 0.2(0.1) GSA-WTM Waterflow/Tamper Module 0.4(0.15) SMK Smoke Power Converter Module 0.4(0.15) Note: For earthquake anchorage,including detailed mounting weights and center of gravity detail,please refer to Seismic Application Guide 3101987- EN.Approval of panel anchorage to site structure may require local AHJ, structural,or civil engineer review. Standby batteries must be mounted externally from fire panel in separately mounted BC-1 enclosure.Order BC-1 and BC-1 EQ separately. Page 9 of 10 DATA SHEET M85005-0130 Not to be used for installation purposes. Issue 6 Vigilant Catalog ► Intelligent Initiating /G/LAN T Fire & Life Safety ■ ■ in h) ,-;r• - - - Intelligent -, . / Detectors and Bases Detectors: V-PS, V-PHS, V-HFD, V-HRD �c Bases: B4U, RB4U, IB4U, SB4U S1122 S1122 7300-1657: 0245-0248 Overview Edwards Vigilant brand intelligent analog detectors are meticu- Standard Features lously engineered to deliver high-performance features, superb reliability, and unbeatable quality.With their highly stable design, • Optical, heat, and multisensor models available these detectors resist air movement caused by heating and air • Compatible standard, relay, isolator,and audible bases conditioning, making them reliable performers ideally suited to modern building interiors. • Field replaceable optical chamber The installation and maintenance advantages of Vigilant brand • Electronic Addressing including mapping location intelligent detectors add value throughout their service life.The • Bases mount to standard North American two-gang or 4" twist-and-lock design makes short work of installation and main- square electrical boxes tenance operations.A plastic breakout on the detector housing • Dual color LED provides at a glance alarm indication optionally prevents removal from the base except with a special tool. • Tamper-resistant feature A bright, easy-to-see LED flashes red when the detector is in • Self diagnostic capability with on-board storage of results alarm,thus eliminating much of the guesswork when responding • Optical detectors feature automatic rate compensated sensitiv- to front-panel indications. ity adjustment, as well as dirty sensor warnings • The V-HFD is fixed-temperature heat detector with an alarm • Manufactured to strict international ISO 9001 standards threshold of 135° F(57°C). • The V-HRD is a rate-of-rise heat detector calibrated for 15°F • Assembled using surface mount technology for RF resistance (8°C)per minute. • Conformally coated components resist dust and humidity • The V-PHS houses an optical sensing chamber that detects • Automatic detector test smoke, as well as a fixed-temperature sensor that detects heat.The detector analyzes data from both sensors to deter- • Low Profile Design mine when an alarm is initiated. • The V-PS houses an optical sensing chamber that detects smoke. All detectors feature comprehensive self-diagnostic capability. V-PS and V-PHS optical detectors continuously adjust their sen- sitivity to compensate for changes in the environment such as the presence of dirt, smoke,temperature, and humidity.These detec- tors issue a dirty sensor warning when they reach their preset limit. Page 1 of 6 DATA SHEET M85001-0592 Not to be used for installation purposes. Issue 2 Heat Detectors Detector Bases The V-Series heat detectors are capable of performing compre- hensive self-diagnostics and storing the results. c > 4 in.square electrical box - ® j Thanks to advanced thermistor technology,V-Series heat detectors 0 are ideal for sensing fast,flaming fires and for applications where / smoke detection is inappropriate.They are particularly well-suited ' to areas such as kitchens and shower rooms,where the ambient — temperature is relatively constant,but where steam and smoke are --,-,, .J-;g,, present. gyp--- ,,!.�+; '.�., .�� J�,' r V-HRD Rate-of-Rise Heat Detector provides a 15°F(8°C)per ,k1-`'.i ,` minute rate-of-rise heat sensor for the detection of heat due to fire. ,,,,� 40 1_„------ The - Adaptor bracket The heat sensor monitors the temperature of the air and deter- . mines whether an alarm should be initiated. B4U base assembly V-HFD Fixed Temperature Heat Detector provides a 135°F(57°C) 4)1 _Screws fixed-temperature heat sensor for the detection of heat due to fire. The heat sensor monitors the temperature of the air and deter- Trim ring mines whether an alarm should be initiated. Connect the detector to the base by rotating the detector clock- Optical and combination detectors wise until it snaps into the locked position. V-Series optical detectors continuously adjust their sensitivity The head can be removed by turning it counterclockwise. based on fluctuating environmental conditions such as the pres / a ® o If the head must lock to the base, break away the ence of dirt, smoke, humidity, or changes in temperature, and // locking tab shown below using a pair of pliers. notifies the panel of any changes in sensor sensitivity.When the detector has adjusted its sensitivity to its maximum limit, it issues a a� To then remove the detector head, insert a small dirty sensor warning, allowing enough of a margin for maintenance screwdriver into the slot on the side of the base personnel to clean the detector before it goes into trouble condi- and press in while simultaneously turning the tion. Breakaway tab detector head counterclockwise. These detectors perform comprehensive self-diagnostics and store these details in their on-board memory. B4V-PHS Optical/Fixed Temperature Detector houses an optical The Standard Base sensing chamber that detects smoke, as well as a fixed-temper- detector B4U Analog Standard Detector Base features twist-and-lock ature sensor that detects heat.The detector analyzes data from detector installation and is compatible with with V-Series analog both sensors to determine when an alarm is initiated.This corn- bines om detectors.The base does not require a separate address because bines the suitability of optical sensing for slow burning fires with it shares the address of the device it is connected to. the sensitivity of fixed-temperature detection for fast flaming fires Femote LED Maximum to arrive at a solution that responds reliably to the widest range of oil. resistance - per wire fire types. must not ®� exceed A sophisticated algorithm processes data from both sensors over \`\ . ohms time so that an alarm is only reported when conditions preciselyFrommatch the signature of a fire.This eliminates the shortcomings of controllerr1O �. ^•- al single-sensor optical and heat detection,and significantly reduces or l>`a' the risk of nuisance alarms. previous !O\'0 ��0 To next device II - device V-PS Optical Smoke Detector uses an optical sensing chamber SIC in( I�–—... SIC out(-) to detect smoke.The detector analyzes data gathered by the sen- SLC in(+ SLC out(+) sor to determine when an alarm is initiated. Term Description Term Description Thanks to its high-performance optical sensing chamber,the V-PS 1 SLC in and SLC out(+) 4 Not used responds quickly and reliably to a wide range of fire types, espe- 2 SLC in(-) 5 Remote LED(+) cially slow burning fires fuelled by combustibles typically found 3 Not used 6 SLC out(-) in modern multi-use buildings.The V-PS detects extremely small 3 Not used 6 Remote LED(-) particles and triggers an alarm at the first sign of smoke. LED Indication V-Series detectors provide a bicolor status LED: • Normal: Green LED flashes • Alarm/active: Red LED flashes Page 2 of 6 DATA , M85001-0592 Not to be used for installation purposes. Issue 2 IB4U Isolator Detector Base SB4U Audible(Sounder) Detector Base The IB4U Analog Isolator Detector Base is designed to prevent The SB4U is designed to add an audible output function to corn- an entire communications loop from being disabled when a short patible detectors.The base can operate as an independent local circuit occurs.This is accomplished by isolating the part of the alarm, or as part of a zone or system alarm with synchronized loop containing the short from the remainder of the circuit.These audible output. bases automatically restore the entire loop when the cause of the Depending on the system supporting the device loop,the base short circuit is corrected. can operate as follows: SLCSLC in . SLC out in(jam • SIC out(+) • It can follow the state of the device it supports From To next • It can be controlled and configured for other operating modes controller O device or through programming. rough e pr '/ I ` 4 The SB4U is field-configurable for output tone(steady or temporal) TB2 1' ; °� I" and output volume(low dBA or high dBA).The base must be con- Wo -® nected to a continuous voltage whether the output tone is set to ® ® _ 0 `o „,...;•„, steady or temporal.The base does not require a separate address � •o because it shares the address of the device it is connected to. Term Description 2 3 SLC in(+) DATA+(IN) _ SLC in(-) DATA-(IN) 0 iii® —U— SLC out(+) DATA+(OUT) ' SLC out(-) DATA-(OUT) o 8 Oe, cal !IMIEE AUX_RISER+ A AIM= A gUX_RISER+ RB4U Relay Detector Base AUX_RISERgyM il�.E , AUX_RISER- SLC+ i- ; SLC+ The RB4U Analog Relay Detector Base is designed to add relay SLC- functionality to the listed compatible detectors. Form C latching SLc relay contacts are included for the control of appliances such as 0 door closers,fans, dampers, etc. 1. AUX-RISER IN(from power supply or previous base) SIC in(-)> ► SIC out(-) 2. Volume setting:default is high volume;cut per item 4 for low volume SII;in(+)) • SIC out(+) From 3. Tone setting:default is temporal pattern;cut per item 4 for steady tone To next controller 4 Ndevice 4. To configure output volume or tone,cut the circuit board as shown or 5. AUX_RISER OUT To next base or EOL relay previous /fAlp Q 6. SLC OUT to next intelligent addressable device device '7Ll" TB2 to j 7. SLC IN from intelligent addressable controller or previous device N �: w�� ' I . TB1 ,1' Sleeping rooms: In sleeping areas,the high dBA output and tem- p poral tone settings must be used. However, if the FACP is produc- ing the three-tone temporal evacuation signal,then the high dBA /O and steadytone settings maybe used. N/O COM N/C output g Term Description Term Description AB4G-SB:When using the AB4G-SB box, N/O(Normally open) SLC in(-) DATA-(IN) COM(Common) SLC out(+) DATA+(OUT) install a reinforcing plate at every knockout TB1 N/C(Normally DATA (OUT) used. (Reinforcing plates are included with "�-111r,--- Closed) SLC out(-) the box.) Remove the knockout first,then Contact rating: slide the reinforcing plate into the plastic SLC in(+) DATA+(IN) 2.0a 30vdc resistive housing.After the plate is in place, install the conduit connector and nut. Notes 1. Wire in accordance with NFPA 70,National Electrical Code. 2. Be sure to observe the polarity of the terminals on the terminal block as shown in the diagram. 3. Break wire run at each terminal.Do not loop signaling circuit field wires around terminals. Page 3 of 6 DATA SHEET M85001-0592 Not to be used for installation purposes. Issue 2 Specifications, SB4U Audible Detector Base Operating current in mA(RMS) Operating voltage 24 VDC or 24 VFWR,nominal Voltage Low dBA High dBA Operating current See Table 1 16 VDC 17 28 Supervisory current DC=1.46 mA,FWR=2.15 mA 24 VDC 24 41 Default settings 33 VDC 31 52 Output volume High dBA 16 VFWR 41 48 Output tone Temporal pattern 24 VFWR 51 60 Sound level output See Table 2 33 VFWR 60 66 Temporal pattern 0.5 s on,0.5 s off,0.5 s on,0.5 s off,0.5 s on, VDC=Volts direct current,regulated and filtered 1.5 s off,repeat cycle VFWR=Volts full wave rectified Operating environment Temperature 32 to 120°F(0 to 49°C) Sound level output(dBA) Humidity 0 to 93%RH,noncondensing at 90°F(32°C) Storage temperature -4 to 140°F(-20 to 60°C) Signal Voltage Low dBA High dBA Compatible V-PS,V-PHS,V-HRD,and V-HFD detectors Reverberant room per UL 464[1] detectors 16 VDC 71.3 77.2 Compatible electrical North American 2-1/2 in.(64 mm)deep 2 gang Temporal 24 VDC 75.0 79.8 boxes box 33 VDC 77.7 81.5 Standard 4"square box 1-1/2 in.(38 mm)deep 16 VDC 75.8 80.5 box Steady 24 VDC 79.2 84.1 European 100 mm square box 33 VDC 82.0 86.0 Wire size 12, 14, 16,or 18 AWG wire(2.5, 1.5, 1.0, Reverberant room per UL 268[2] or 0.75 sq.mm) (Sizes 16 and 18 AWG are preferred) 16 VDC 77.3 83.2 Base diameter 6.0 in.(152 mm) Temporal 24 VDC 81.0 85.8 Height from box 2.58 in.(66 mm) 33 VDC 83.7 87.5 (including detector) 16 VDC 81.8 86.5 Maximum distance 12 in.(305 mm) Steady 24 VDC 85.2 90.1 from ceiling(wall 33 VDC 88.0 92.0 mount) dBA=Decibels,A-weighted [1]For UL 464 applications,low dBA settings are for private mode only [2]For UL268 applications,high setting must be used for evacuation Specifications, Detectors V-PHS V-PS V-HRD V-HFD Air velocity 0 to 5,000 ft/min(0 to 25.39 m/s) N/A Smoke sensitivity range 0.67%-3.66% ULI fixed-temp alarm rating 135°F(57°C) N/A 135°F(57°C) ULC fixed-temp alarm rating 140°F(60°C) 140°F(60°C) Maximum Spacing 30 ft(9.1 m) 50 ft(15 m)centers Rate-of-Rise N/A 15°F(8°C)/min. N/A Operating voltage 15.2 to 19.95 VDC Normal operating current 45 pA,average Alarm current 45 pA,average Environmental compensation Automatic Compatible bases B4U Standard,RB4U Relay,IB4U Isolator,SB4U Audible Maximum distance from ceiling wall-mounted 12 in(305 mm) Storage temperature -4 to 140°F(-20 to 60°C) Operating environment Temperature:32 to 120°F(0 to 49°C);Humidity:0 to 93%RH,noncondensing at 90°F(32°C) Meets UL 268, Meets UL 268, Agency listings ULC-S529-02,UL 521, ULC-S529-02,NFPA 72, Meets UL 521,ULC-S530-M91,NFPA 72,and ULC-S530-M91, NFPA 72, and CAN/ULC S524-01 CAN/ULC S524-01 and CAN/ULC S524-01 Page4of6 DATA Si.,_, . M85001-0592 Not to be used for installation purposes. Issue 2 Specifications, Bases B4U Standard Base IB4U Isolator Detector Base RB4U Relay Detector Base Operating environment Temperature 32 to 120°F(0 to 49°C) Humidity 0 to 93%RH,noncondensing at 90°F(32°C) Storage temperature range -4 to 140°F(-20 to 60°C) Compatible detectors V-PS,V-PHS,V-HRD,and V-HFD detectors Compatible electrical boxes North American 2-1/2 in.(64 mm)deep 2 gang box Standard 4 in.square box 1-1/2 in.(38 mm)deep box European 100 mm square box Wire size 12, 14, 16,or 18 AWG wire(2.5, 1.5, 1.0,or 0.75 sq.mm) (Sizes 16 and 18 AWG are preferred) Base diameter 6.0 in.(152 mm) Height from box(including detector) 2.08 in.(53 mm) 2.57 in.(65 mm) Maximum distance from ceiling(wall 12 in.(305 mm) mount) Ordering Information Model Description Ship Wt.:lb.(kg) V-PHS Intelligent Analog Optical/Fixed Temperature Detector 0.25(0.11) V-PS Intelligent Analog Optical Smoke Detector 0.25(0.11) V-HRD Intelligent Analog Rate-of-Rise Heat Detector 0.25(0.11) V-HFD Intelligent Analog Fixed Temperature Heat Detector 0.25(0.11) B4U Standard Base 0.11 (0.05) RB4U Relay Detector Base 0.11 (0.05) IB4U Isolator Detector Base 0.11 (0.05) SB4U Audible(Sounder)Detector Base 0.11 (0.05) AB4G-SB Surface Box for Audible Base 1.0(0.45) GSA-LED Remote alarm LED,use with standard base only 0.2(.09) 211-10PKG Replacement optical chambers(package of 10) 0.25(0.11) Page 5 of 6 DATA SHEET M85001-0592 Not to be used for installation purposes. Issue 2 Vigilant Catalog ► Intelligent Initiating /G/LAN T Fire & Life Safety .1 Manual Pull PULL atented IN CASE Stations FiRE GSA-M270, GSA-M270P, PULLFOR '�- - GSA-M278 FIRE ' . GSA-M270 SERIES 0 roitol 4:00°. 7150-1483: 0139 MEA S2318 Overview • Break glass operation The GSA M270 and GSA M278 series Manual Pull Stations are An up-front visible glass rod on the GSA-M270 discourages part of Vigilant's Signature Series system.The GSA-M270 Fire tampering. Alarm Manual Pull Stations feature our very familiar teardrop • Intelligent device with integral microprocessor shape.They are made from die-cast zinc and finished with red All decisions are made at the station allowing lower com- epoxy powder-coat paint complemented by aluminum colored munication speed while substantially improving control panel stripes and markings. With positive pull-lever operation, one pull response time. Less sensitive to line noise and loop wiring on the station handle breaks the glass rod and turns in a posi- properties;twisted or shielded wire is not required. tive alarm, ensuring protection plus fool-proof operation. Presignal • ADA Compliant models(GSA-M270P)are equipped with a general alarm(GA) Meets ADA requirements for manual pull stations. keyswitch for applications where two stage operation is required. The up-front highly visible glass rod discourages tampering, but is • Electronic Addressing with Non-volatile memory not required for proper operation. Permanently stores programmable address, serial number, type of device, and job number.Automatically updates historic Vigilant's double action single stage GSA-M278 station is a con- information including hours of operation, last maintenance temporary style manual station made from durable red colored date, number of alarms and troubles, and time and date of last lexan. To initiate an alarm,first lift the upper door marked"LIFT alarm. THEN PULL HANDLE",then pull the alarm handle. • Automatic device mapping Each station transmits wiring information to the loop control- Standard Features ler regarding its location with respect to other devices on the Note:Some features described here may not be supported by all control sys- circuit. tems.Check your control panel's Installation and Operation Guide for details. • Stand-alone operation • Traditional familiar appearance The station inputs an alarm even if the loop controller's polling GSA-M270 models feature our familiar teardrop design with interrogation stops. simple positive pull action and sturdy die-cast metal body. • Diagnostic LEDs • One stage(GA),two stage(pre-signal),and double action Status LEDs;flashing GREEN shows normal polling;flashing models RED shows alarm state. GSA-M270 models are available for one or two stage alarm • Designed for high ambient temperature operation systems.The single stage double action GSA-M278 features a Install in ambient temperatures up to 120°F(49°C). rugged Lexan housing with keyed reset mechanism. Page 1 of 4 DATA SHEET M85001-0279 Not to be used for installation purposes. Issue 8.1.1 Application Typical Wiring The operating characteristics of the fire alarm stations are deter- The fire alarm station's terminal block accepts#18 AWG(0.75mm2) mined by their sub-type code or"Personality Code". NORMALLY- to#12 AWG(2.5mm2)wire sizes.See Signature Loop Controller OPEN ALARM-LATCHING(Pesonality Code 1)is assigned by the catalog sheet for detailed wiring requirement specifications. factory; no user configuration is required.The device is configured for Class B IDC operation.An ALARM signal is sent to the loop Wiring Notes controller when the station's pull lever is operated.The alarm con- ARefer to Signature Loop Controller manual for maximum dition is latched at the station. wire distance. 2. All wiring is power limited and supervised. Compatibility REAR VIEW of 278 Signature Series manual stations are compatible only with Vigi- lant's Signature Loop Controller. p T82 I I� Warnings & Cautions 8 7 This device will not operate without electrical power.As fires fre- quently cause power interruption,we suggest you discuss further (Al rm ActItive) o o GLED (NNoror mal) safeguards with your local fire protection specialist. 3 2 ' 0 TB,10 U►®®N ° IC:I Testing & Maintenance �■I■� To test(or reset)the station simply open the station and operate DATA IN(+) ' DATA OUT WI the exposed switch.The GSA-M270 series are opened with a tool; 1 DATA IN(-) , DATA OUT(-) the GSA-M278 requires the key which is supplied with that station. From Signature Controller To Next Device or Previous Device 0 The station's automatic self-diagnosis identifies when it is defec- tive and causes a trouble message.The user-friendly maintenance Figure 4. Single Stage Systems program shows the current state of each Signature series device and other pertinent messages. Single devices may be deactivated temporarily,from the control panel.Availability of maintenance dependent on the fire alarm system used. REAR VIEW features is y of Scheduled maintenance(Regular or Selected)for proper system 270P,270PB operation should be planned to meet the requirements of the o Authority Having Jurisdiction(AHJ). Refer to current NFPA 72 and �o ° ULC CAN/ULC 536 standards. TB2 litaffain 8 7 6 5 Red LED Green LED (Alarm/Active) I n 3 2 (Normal) TB] • O p I SII C (DATA IN(+) DATA OUT WI 1 l DATA IN(-) • DATA OUT(-) From Signature Controller To Next Device or Previous Device 0 Figure 5. Two Stage Systems Page 2 of 4 DATA SHEL M85001-0279 Not to be used for installation purposes Issue 8.1.1 Installation Single-stage Signature Series fire alarm manual pull stations mount to North American 21/2 inch(64 mm)deep 1-gang boxes. Two stage presignal(270P)models require 11/2 inch(38 mm)deep 4-inch square boxes with 1-gang, t/-inch raised covers.Openings must be angular.Rounded openings are not acceptable. Recommended box:Steel City Model 52-C-13; in Canada, use Iberville Model Cl- 52-C-49-1/2. All models include terminals are suited for#12 to#18 AWG(2.5 mm2 to 0.75 mm2)wire size. Edwards recommends that these fire alarm stations be installed according to latest recognized edition of national and local fire alarm codes. Electronic Addressing: The loop controller electronically addresses each manual station, saving valuable time during system com- missioning. Setting complicated switches or dials is not required. Each station has its own unique serial number stored in its on-board memory.The loop controller identifies each device on the loop and assigns a"soft"address to each serial number. If desired,the stations can be addressed using the SIGA-PRO Signature Program/Service Tool. Key-Latch Compatible Electrical Box OM Compatible Electrical Box -Cover Release Cover t�r� /\ Release �� � //, $Creta IILI ,50, I! iii 00 KHAN '` /�fj rl 1 Q O /° Back \ ff0 1-111 ° Back 1 Q Plate ' Plate 11U4';To le o° pt „ ,,Switch ° Switch 11 0 ri ” Glass RodGlass Rod Release Lever OPEN G \ 101i.11:11,, Figure 1. GSA-M278 installation Figure 2. GSA-M270,SIGC-270F,SIGC-270B installation Cover Release Scr-w O4—Compatible roll• Electrical Box with' inch4,0011raisedCovers 4 E5 V ofilL i r,,,,,..- Back o ®�' Plate OM Toggle ` ° Switch NORMA 0 o p • / ��l'i:,- Glass Rod Release Lever Do not use �L, boxes with rounded N • openings. Figure 3. GSA-M270P,SIGC-270PB installation Page 3 of 4 DATA SHEET M85001-0279 Not to be used for installation purposes. Issue 8.1.1 Specifications DWAR D S GSA-M270,SIGC- GSA-M270P, Catalog Number 270F,SIGC-270B SIGC-270PB GSA-M278 United Technologies Single Action Single Action-Two Double Action Description -One Stage Stage(Presignal) -One Stage Contact us... Addressing Uses 1 Module Uses 2 Module Uses 1 Module Email: edwards.fire@fs.utc.com Requirements Address Addresses Address Web: www.vigilant-fire.com Standby=250pA Standby=396pA Standby=250pA Vigilant is an EDWARDS brand. Operating Current Activated=400pA Activated=680pA Activated=400pA 1016 Corporate Park Drive Diecast Zinc-Red Epoxy Lexan-Red with Mebane,NC 27302 Construction&Finish with aluminum markings white markings ©2013 UTC Fire&Security Americas Type Code Factory Set Corporation,Inc.All rights reserved. Operating Voltage 15.2 to 19.95 Vdc(19 Vdc nominal) Specifications subject to change Operating Temperature:32°F to 120°F(0°C to 49°C) without notice.Edwards is part of UTC Storage and O eratin Climate,Controls&Security,a unit of Environment p g Storage Temperature:-4°F to 140°F(-20°C to 60°C)Humidity:0 to 93% United Technologies Corporation. RH On-board Green LED-Flashes when polled LED Operation On-board Red LED-Flashes w hen in alarm Both LEDs-Glow steady when in alarm(stand-alone) Compatibility Use With:Signature Loop Controller Agency Listings UL,ULC(note 1),MEA,CSFM,FM Note:SIGC-270F SIGC-270B and SIGC-270PB are ULC listed only.Suffix"F"indicates French markings. Suffix"B"indicates English/French biting ual markings. Ordering Information Ship Catalog Wt.lbs Number Description (kg) GSA-M270 One Stage Fire Alarm Station, English Markings-UUULC Listed SIGC-270F One Stage Fire Alarm Station, French Markings-ULC Listed SIGC-270B One Stage Fire Alarm Station,French/English Markings-ULC Listed GSA-M270P Two Stage(Presignal)Fire Alarm Station, English Markings-UUULC Listed 1 (0.5) SIGC-270PB Two Stage(Presignal)Fire Alarm Station, French/English Markings -ULC Listed GSA M278 Double Action(One Stage)Fire Alarm Station,English Markings -UUULC Listed Accessories 32997 GA Key w/Tag-for pre-signal station(CANADA ONLY) 276-K2 GA Key-for pre-signal station (USA ONLY) 276-K1 Station Reset Key, Supplied with all Key Reset Stations 0.1 (.05) 27165 12 Glass Rods-for GSA-M270 series(CANADA ONLY) 270-GLR 20 Glass Rods-for GSA-M270 series (USA ONLY) 276-GLR 20 Glass Rods-for GSA-M278 series 276B-RSB Surface Mount Box,Red-for SIGA pull stations 1 (0.6) a C Page 4 of 4 DATA SHEL M85001-0279 Not to be used for installation purposes Issue 8.1.1 Vigilant Catalog ► Intelligent Initiating /G/LAN T Fire & Life Safety -r {4{ Intelligent Duct 4'Am- 1. y. Smoke Detector ) GSA-SD I 1 —I AMMO ( ) MEA 324017383: S853 Overview Standard Features The Edwards SuperDuct Signature Series smoke detector is the • Less than 2" deep for easy installation and applications where most advanced and most reliable device in its class. Designed for space is tight easy installation and superb reliability,SuperDuct represents the • -4°F to 158°F(-20°C to 70°C) operating range with 100 ft/min. perfect balance of practical design and advanced technology. to 4,000 ft/min air velocity rating assures reliability under harsh SuperDuct detectors feature a unique design that speeds instal- environmental conditions lation and simplifies maintenance. Removable dust filters, confor- • Status LEDs remain visible through clear assembly cover mally coated circuit boards, and optional water-resistant gaskets keep contaminants away from components, ensuring years of • Cover monitor switch for added security trouble-free service.When cleaning is required,the assemblies • Standard sampling tube spacing for easy drop-in migration come apart easily and snap back together in seconds. from other detectors A Signature Series photoelectric sensor is incorporated into • Sampling tube can be installed with or without the cover in the design of each GSA-SD duct smoke detector.This sensor place and can be rotated in 45-degree increments to ensure inherits the power and benefits of this exceptional line of intelligent proper alignment with duct airflow devices. • 15.2 to 19.95 Vdc operation Signature Series sensors gather analog information from their • smoke sensing elements and convert it into digital signals.The Magnet activated test switch sensor measures and analyses these signals and compares the • One Form C auxiliary alarm relay for controlling ancillary equip- information to historical readings and time patterns to make an ment(e.g., HVAC controls) alarm decision. Digital filters remove signal patterns that are not • No special tools required for easy access to field connections typical of fires,which virtually eliminates unwanted alarms. • Signature Series intelligence WARNING: Duct detectors have specific limitations. Duct detectors are not a • Environmental compensation with differential sensing for reli- substitute for an open area smoke detector. Duct detectors are not a substitute able,stable, and drift-free sensitivity for early warning detection or a replacement for a building's regular fire detection system.Smoke detectors are not designed to detect toxic gases which can build up • Wide 0.79%to 2.46%obscuration/ft. smoke sensitivity to hazardous levels in some fires.These devices will not operate without electrical power.As fires frequently cause power interruptions,Edwards suggests you discuss • Identification of dirty or defective detectors further safeguards with your local fire protection specialist. Page 1 of 4 DATA SHEET M85001-0584 Not to be used for installation purposes. Issue 6 Application The sampling tube may be installed from either the duct side of SuperDuct detectors are ideally suited to duct smoke detection the assembly or from inside the sensor compartment, as preferred by the installer. (The exhaust tube must be installed from the duct applications where early indication of combustion is required within side.)Sampling tubes may be rotated in 45-degree increments so the confined space of ventilation ductwork. Its primary purpose that air-holes can be aligned to allow the unit to be mounted at is to provide early warning of an impending fire and to prevent virtually any angle relative to the air flow. smoke from circulating throughout the building. It is typically used to detect smoke in the supply side of the HVAC system but can In installations where the duct smoke detector's controls and indica- provide supervision of the return side as well. tors are hidden from view, a remote test station or an LED indicator can be connected to the detector to provide these functions. Protected premises Remote Remote Test Stations Alarmrelay output station Labor-saving Remote Test/Reset stations provide 1 - alarm testing from the convenience of a remote location.Tests can be performed quickly and safely Duct smoke <-1 Return —without having to climb to the roof. Magnetically- detector air — HVAC operated and key-operated one-gang models are unit _ available.Signature SuperDuct detectors are also Duct smoke_ I >Supply compatible with GSA LED remote alarm LED. detector air T Air velocity in the duct as low as 100 ft/min. maintains adequate air flow into the sensor smoke chamber through air holes in the air Alarm relay Remote output test sampling tube and discharges through the exhaust tube.Su- FACP station perDuct air sampling tubes must be installed with the inlet holes facing the airstream. Sampling tubes may be rotated in 45-degree increments so that air-holes can be aligned to allow the unit to be L SuperDuct detectors continually sample air flow in the HVAC duct mounted in virtually any angle relative to the airflow. and initiate an alarm condition whenever smoke is detected. An SuperDuct sensors are engineered to operate optimally under the alarm is activated when the quantity(percent obscuration)of harsh environmental conditions frequently found in HVAC duc- combustion products in that air sample exceeds the detector's twork. Nonetheless, before installing the detector,test the duct sensitivity setting. air velocity,temperature,and humidity to verify that it is within the operating range of the SuperDuct detector. Consult the SuperDuct Signature Series Intelligence installation sheet for details. Like all Signature detectors,the GSA-SD features electronic ad- dressing and issues a dirty sensor warning when it reaches its Dimensions preset limit.The dirty sensor warning indicates the sensor is op- erating within its specified limits but is in need of servicing.When - 8.70 in(22.1 cm) . the detector's ability to compensate for environmental changes 8.15 n(19.7cm has reached its limit,the duct smoke detector signals a trouble 3.O8in(7.82cm) 471)— condition. a.o°( - condition. The GSA-SD also uses differential sensing to prevent gradual ..L,.., — — ,_r environmental changes from triggering unwanted alarms.A rapid change in environmental conditions, such as smoke from a fire, 0 0 causes the detector to signal an alarm state, but dust and debris 7- accumulated over time does not change alarm sensitivity. i i _ .. I i Each Signature Series SuperDuct detector contains a microproc- lq essor that performs comprehensive self-diagnostics and stores i the results in nonvolatile memory. Stored results include details 2.28 in such as hours of operation, last maintenance date, and number (5.78cm) of alarms and troubles.This information can be retrieved and reviewed when desired. C ill I Detector Configurationn / 5.45 in The detector assembly cover provides easy access to the smoke ' POWER (13.84 cm) sensor, its wiring connections, sample and exhaust tubes, and the ""I � o smoke chamber itself. o 0 0 0 Air enters the detector's sensing chamber through a sampling _ - ii ii tube(ordered separately)that extends into the duct and is directed �L back into the ventilation system through an exhaust tube(in- j 1.90 in (4.83 cm) cluded).The difference in air pressure between the two tubes pulls � c I the sampled air through the sensing chamber.When a sufficient , '- Y Y ' + amount of smoke is detected in the sensing chamber,the detector initiates an alarm. ; a o 1.38 in5.40 in (3.51 cm)�• (13.72 cm) Page2of4 DATA Si.,_, . M85001-0584 Not to be used for installation purposes. Issue 6 Assembly High-humidity environments Sampling tube Detector socket Use the SD PH Protective Housing when installing SuperDuct Exhaust tube "4 +11 . � detectors in high humidity environments.The SD PH is a weather socket y+ ized housing that prevents condensation on the device by insulat- Di ing the detectors and providing circulated air from the monitored (St HVAC duct.The SD-PH also adds a layer of protection against J 7,--VIOphysical damage to the unit. tube Exhaust / 1 . ilI Thin i gasket �� ��, I Thick ' gasket `I��"NJ) Coupling '\ 0.„,.4.......'-'.111111 v1 Duct Detector SD-PH Sampling tube Protective /`® �' (ordered separately) Housing ` Plug / _________„---it,• rr Mounting ', Rear View f HVAC duct /�• Airflow �i Q Q Hinged ,' N \ Detector 114 Cover ® t i —1- 0,O\ ��� ® Housing �� r O© (e air tube N 1 ��. �� "' Housing Detector Sampling • rl 1 `` — air tube conduit holes tube 1C =\ ., ,; The SD-PH is easy to install and service.The hinged and transpar- ent cover provides ready access to the detector,while keeping its f status indicators visible at all times. #10 sheet metal screw(2X) Note: The SD-PH Protective Housing is weatherized against out- door air, but it is not intended for direct outdoor exposure. Wiring Auxiliary equipment SIGA-1LED[1] O [1] No more than one remote test station @S S or LED indicator can be connected to or the detector at the same time.Wiring ® ® 17 16 15 is unsupervised.Maximum wire Alarm resistance is 10 ohms per wire. ® SD-TRK '1 FJ Test or O0-----i_ SD-TRM[1] S * u❑ pp ppu pp li II a ❑�Co` I II II III II II IIp 11 Data Out(-) C 0 0 0 3---\ Data Out(+) Data In(+) ,_, Data In(-) ®®®®®®®® 77 n n n n n n n `,P\® 0 0 0t �J 14 13 12 11 10 9 8 7 `Powjer indicator Alarm indicator Page 3 of 4 DATA S M85001-0584 Not to be used for installation purposes. Issue 6 Specifications, detector Specifications, test stations -D WA R D 8.70 x 5.45 x 1.90 inches Remote Tn,and Stations provide alarm test,trouble Dimensions indication,and reset capability from a remote loca- tion.(221 x 138 x 48 mm) They include a one-gang plate,momentary SPST ,United Technologies Wire size 14 to 22 AWG switch,red alarm LED,and terminal block.Magnetically- Detection Photoelectric operated models(TRM)or key-operated models(TRII Contact us... method (light scattering principle) au available. North American 1-gang box Email: edwards.fire@fs.utc.com 100 to 4,000 ft/min and Compatible Standard 4-in sq square box, Web: www.vigilant-fire.com Air velocity meets the re uired minimum electrical e ratin q 1 1/2 inches deep,with Vigilant is an EDWARDS brand. g air pressure differential boxes 1-gang cover 1016 Corporate Park Drive Air pressure 0.005 to 1.00 inches of LED indicators Alarm(red) differential water LED typeClear lens Mebane,NC 27302 0.79 to 2.46%/ft Sensitivity Wire size 14 to 22 AWG ©2013 UTC Fire&Security Americas obscuration per Resistance Corporation,Inc.All rights reserved. Alarm test 10 Ohms,max. Specifications subject to change 5 seconds wire without notice.Edwards is part of UTC response time Current Climate,Controls&Security,a unit of LED indicators Alarm(red), Power(green) See controller specifications United Technologies Corporation. requirements 9 p Unsupervised and power- LED circuit Voltage:3 Vdc,max. limited ratings Current:30 mA,max. Common Quantity: 1 Switch ratings Voltage: 125 Vdc,max. alarm relay Type:Form C (SD-TRK) Current:4 A,max. Ratings:2.0 A at 30 Vdc (resistive) Switch ratings Voltage:200 Vdc,max. Operating (SD-TRM) Current:0.5 A,max. 15.2 to 19.95 Vdc SuperDuct conventional voltage Compatible two-wire and Signature duct Operating Standby:45 pA Alarm:45 detectors smoke detectors current pA Inrush: 1 mA Standalone -4°F to 158°F(-20°C to alarm: 18 mA Operating Temperature(UL):-4 to 158 environment 70°C)Humidity:93%RH, °F(-29 to 70°C). noncondensing Operating Temperature(ULC):-4 to Storage -4 to 140°F(-20 to 60°C) environment 120°F(-29 to 49°C) temperature Relative humidity: 10 to Agency listings UL,ULC,MEA,CSFM 93%,noncondensing Agency UL,ULC,CSFM,FM,MEA listings Ordering Information Catalog Number Description Ship Wt.,lb.(kg) GSA-SD Intelligent SuperDuct Detector 2.4(1.1) Accessories SD-T8 8-inch sampling tube 0.5(0.2) SD-T18 18-inch sampling tube 1.5(0.7) SD-T24 24-inch sampling tube 2.7(1.2) SD-T36 36-inch sampling tube 3.0(1.4) SD-T42 42-inch sampling tube 3.5(1.6) SD-T60 60-inch sampling tube 5.8(2.6) SD-T78 78-inch sampling tube 7.5(3.4) SD-T120 120-inch sampling tube 11.5(5.2) SD-PH Protective housing for high humidity environments 5.5(2.5) GSA-LED Remote alarm LED 1.0(0.5) SD-TRM Remote test station,magnetic 1.0(0.5) SD-TRK Remote test station,keyed 1.0(0.5) SD-VTK Air velocity test kit(stoppers only,etc) 1.0(0.5) SD-GSK Cover gasket kit 0.5(0.2) SD-MAG Test magnet kit 0.5(0.2) GSA-SDPCB Replacement PCB/Signature sensor kit 1.0(0.5) a Page 4 of 4 DATA Si. . M85001-0584 F,' Not to be used for installation purposes. Issue 6 Vigilant Catalog►Intelligent Input/Output /G/LAN T Fire & Life Safety Control Relaytioieji a. ,. Modules - 10 % at • GSA-CR, GSA-MCR, GSA-CRR, 4 400' —• GSA-MCRR V A 1 7111[ ,1111 Ijimil i I • e s !; ,^. 7300-1483: 4 a 9 0115 / GSA-CR 0 I/ GSA-MCRi L4 C) S3424 Overview Standard Features The Control Relay Module and the Polarity Reversal Relay Module • Provides one no/nc contact(GSA-CR/MCR) are part of the Signature Series system.They are intelligent analog Form "C"dry relay contact can be used to control external ap- addressable devices available in either plug-in(UIO)versions, or pliances such as door closers,fans, dampers etc. standard 1-gang mount versions. • Allows group operation of sounder bases The GSA-CR/MCR Control Relay Module provides a Form"C" The GSA-CRR/MCRR reverses the polarity of its 24 Vdc out- dry relay contact to control external appliances such as door clos- put,thus activating all Sounder Bases on the data loop. ers,fans, dampers etc.This device does not provide supervision • Plug-in(UIO)or standard 1-gang mount of the state of the relay contact. Instead,the on-board micro- UIO versions allow quick installation where multiple modules processor ensures that the relay is in the proper ON/OFF state. are required.The 1-gang mount version is ideal for remote Upon command from the loop controller,the GSA-CR/MCR relay locations that require a single module. activates the normally open or normally-closed contact. • Automatic device mapping The GSA-CRR/MCRR Polarity Reversal Relay Module provides Signature modules transmit information to the loop controller a Form"C"dry relay contact to power and activate a series of regarding their circuit locations with respect to other Signature GSA-AB4G Audible Sounder Bases. Upon command from the devices on the wire loop. Signature loop controller,the GSA-CRR reverses the polarity of its • Electronic addressing 24 Vdc output,thus activating all Sounder Bases on the data loop. Programmable addresses are downloaded from the loop con- Standard-mount versions(GSA-CR and GSA-CRR)are troller, a PC,or the SIGA-PRO Signature Program/Service Tool; installed to standard North American 1-gang electrical boxes, there are no switches or dials to set. making them ideal for locations where only one module is re- • Intelligent device with microprocessor quired. Separate I/O and data loop connections are made to each All decisions are made at the module to allow lower com- module. munication speed with substantially improved control panel Plug-in UIO versions(GSA-MCR and GSA-MCRR)are part of response time and less sensitivity to line noise and loop wiring the UIO family of plug-in Signature Series modules.They function properties;twisted or shielded wire is not required. identically to the standard mount versions, but take advantage • Ground fault detection by address of the modular flexibility and easy installation that characterizes Detects ground faults right down to the device level. all UIO modules.Two-and six-module UIO motherboards are available.All wiring connections are made to terminal blocks on the motherboard. UIO assemblies may be mounted in Edwards enclosures. Page 1 of 6 DATA SHEET M85001-0239 Not to be used for installation purposes. Issue 7.5 Installation Application GSA-CR and GSA-CRR:modules mount to North American 21/2 The operation of Signature Series control relays is determined by inch(64 mm)deep 1-gang boxes and 11/2 inch(38 mm)deep 4 their sub-type code or"Personality Code." inch square boxes with 1-gang covers and GSA MP mounting Personality Code 8:CONTROL RELAY(GSA-CR/MCR)-Dry plates.The terminals are suited for#12 to#18 AWG(2.5 mm2 to 0.75 mm2)wire size. Contact Output.This setting configures the module to provide one Form"C" DRY RELAY CONTACT to control Door Closers, Fans, Dampers, etc. Contact rating is 2.0 amp @ 24 Vdc; 0.5 Compatible electrical box amp @ 120 Vac(or 0.25A @ 220 Vac for non-UL applications). Personality Code 8 is assigned at the factory. No user configura- tion 161,1111610, --------- -poi is required. , Personality Code 8: POLARITY REVERSAL RELAY MODULE + (GSA-CRR/MCRR).This setting configures the module to reverse Wall plate,white the polarity of its 24 Vdc output. Contact rating is 2.0 amp @ 24 illi'itl ;,41'‘,,( ,I� Vdc ilot dut Personalit Code 8 is assi ned at the facto No ,i L1 gang) (p Y)• Y 9 rY•user configuration is required. �!J� a Compatibility ,, The Signature Series modules are compatible only with Vigilant's Status LEDs Signature Loop Controller. 9, LED viewing ports . 50 Warnings & Cautions � This module will not operate without electrical power.As fires fre- quently cause power interruption,we suggest you discuss further GSA-MCR and GSA-MCRR:mount the UIO motherboard inside safeguards with your local fire protection specialist. a suitable Edwards enclosure with screws and washers provided. Plug the module into any available position on the motherboard and secure the module to the motherboard with the captive Testing & Maintenance screws.Wiring connections are made to the terminals on the motherboard(see wiring diagram). UIO motherboard terminals are The module's automatic self-diagnosis identifies when it is defec- suited for#12 to#18 AWG(2.5 mm2 to 0.75 mm2)wire size. tive and causes a trouble message.The user-friendly maintenance program shows the current state of each module and other per- _u10 Motherboard tinent messages. Single modules may be turned off(deactivated) 1 6-32 temporarily,from the control panel.Availability of maintenance Self-tapping features is dependent on the fire alarm system used. Scheduled screws maintenance(Regular or Selected)for proper system operation 0- *I ` should be planned to meet the requirements of the Authority Hav- Plug-in Captive ing Jurisdiction(AHJ). Refer to current NFPA 72 and ULC CAN/ Module ULC 536 standards. -- - fl--„t I #6 Flat washers J 4—Cabinet or electrical enclosure Electronic Addressing -The loop controller electronically ad- dresses each module, saving valuable time during system com- missioning. Setting complicated switches or dials is not required. Each module has its own unique serial number stored in its on- board memory.The loop controller identifies each device on the loop and assigns a"soft"address to each serial number. If desired, the modules can be addressed using the SIGA-PRO Signature Program/Service Tool. Edwards recommends that this module be installed according to latest recognized edition of national and local fire alarm codes. Page 2 of 6 DATA SHEM85001-0239 Not to be used for installa oses. Issue 7.5 Typical Wiring Modules will accept#18 AWG(0.75mm2),#16(1.0mm2), #14 AWG(1.50mm2)and#12 AWG(2.5mm2)wire sizes. Note: Sizes#16 AWG(1.0mm2)and#18 AWG(0.75mm2)are preferred for ease of installation. See Signature Loop Controller catalog sheet for detailed wiring requirement specifications. Normally- Normally- Open Common Closed A TB2 0 8 7 6 • • • Red LED Green LED (Alarm/Active) '3O2 lO 111-- (Normal) TBl 0 0 0 0 Notes A Refer to Signature Loop Controller Installation DATA IN(+) DATA OUT(+) Sheet for wiring specifications. NFPA 72 requires that the GSA-CR/GSA-MCR I. DATA IN(-) DATA OUT(-) be installed in the same room as the device it is From Signature Controller To Next Device controlling.This requirement may not apply in all or Previous Device markets.Check with your local AHJ for details. 0 The GSA-U106R and the GSA-UI02R do not come with TB14. GSA-CR Control Relay A The GSA-U106 does not come with TB8 through qq TB13. Normally Open Common Normally Closed /o\Supervised and power-limited. /\ If the source is nonpower-limited,maintain a space of 1/4 inch from power-limited wiring or use FPL,FPLP,FPLR,or an equivalent in accordance with the National Electrical Code. L-111P/1\ 7) Maximum#12 AWG(2.5mm2)wire. Q1 2 3 4 Min.#18(0.75mm2). A Data In+ , 4 NUS® 3 4 Q IP �z 1 ,� TB14 + No connections required for Data Out 4 MCR.Other modules may a require connections. z� r, 4 "� ®3 Green LED(Normal) ® LA 2sul4 Red LED(Active) Poe:®a a TB15 1234 A'T\ No connections required for MCR.Other modules may require connections. GSA-MCR Control Relay Page 3 of 6 DATA SHEET M85001-0239 Not to be used for installation purposes. Issue 7.5 Typical Wiring Modules will accept#18 AWG(0.75mm2),#16(1.0mm2), #14 AWG(1.50mm2)and#12 AWG(2.50mm2)wire sizes. Note: Sizes#16 AWG(1.0mm2)and#18 AWG(0.75mm2)are preferred for ease of installation. See Signature Loop Controller catalog sheet for detailed wiring requirement specifications. AB4G AB4G AB4G Audible Base Audible Base Audible Base ® o o ® 1 ® a a e ® o o ® =IL 6254A-003 I EOL Relay Listed 24 VDC + —A II Nominal Power 111 111 Irl Ir n a 1 n ii 111 a II Irl fl 11 II oI, Q Supply _ — — A A A A ® A A VA ii IM lel 0 p I • • • • • • • • • CR CRR AGSA—CRR CT1 0 0 0 0 0 0 _IIr II IIA � L Signature Controller A A Optional CR for disabling/disconnecting sounder base GSA—MCRR GSA-CRR Schematic GSA-MCRR Schematic \® o o ®\ Power In Power Out Polarity Reverses O Power In Power Out _ 4=0, When AciNated Polarity reverses F p 6254A-003 + `T =�when activated. p Z Z El SII; EOL Relay [II 111 111 11 J Audible O I I8 �. kri0 � Z. _ + 1{ o., required for • Bases supevision + Q Q Q el P•: I'D IDa a a to u o 0 0 SII I I m'h �l I1j ° 14NM el4 3 2 1 II1 ® I. El • Signature A • 8 7 Notes Data Data Out " ' • • • Circuit + Al Refer to the Signature controller installation sheet for 44111111E___ normal operation CT1 wiring. Q (- *r For General Fire Alarm Operation 0 0 AOne Pair of Wires(24 Vdc power). UL/ULC Listed + 4 3 2 1 /�� 24 Vdc power — A One Pair of Wires(Signature Data). supply or I[1 f m IZI 1� /w\ Single Wire(24 Vdc power). —� ' . 1234 1234 /5 The GSA-U106R and the GSA-UIO2R do not come I I ■■- MCRR with TB14. A A pppp ipeip DIO(R)seriesmotherboard A The GSA-U106 does not come with TB8 through Data Out `wIr TB13. No connections required for • signatu14 MCRR.Other modules may ASupervised and power-limited. Data M� 'circuit 1 �� require connections. 8 If the source is nonpower-limited,maintain a space TB7 1of 1/4 inch from power-limited wiring or use FPL, + FPLP,FPLR,or an a uivalent in accordance with the Data InQ 1,I \ Green LED(Normal) National Electrical Code. 1 z Red LED(Active) 9 Maximum#12 AWG(2.5 mm2)wire;Minimum #18IWM WM . t No connections required for AWG(0.75 mm2 12:2 :: I�r�I�r/ TB15 MCRR.Other modules may ) Green LED(Normal) 10 End-of-Line Relay must monitor and report power Red LED(Active) require connections. supply trouble to control panel. Q Q 11 Class B Data wiring may be"T-tapped." Optional MCRR or MCR for No connections required for MCRR.Other disabling/disconnecting an audible base. modules may require connections. Page 4 of 6 DATA SHEM85001-0239 Not to be used for installa oses. Issue 7.5 Specifications Catalog Number GSA-CR GSA-MCR GSA-CRR GSA-MCRR Description Control Relay Polarity Reversal Relay Type Code Personality Code 8(Factory Set) Personality Code 8(Factory Set) Address Requirements Uses 1 Module Address Operating Current Standby=75 pA Activated=75 pA Operating Voltage 15.2 to 19.95 Vdc(19 Vdc nominal) Relay Type and Rating Form C,2 Amps @ 24 Vdc(pilot duty),0.5 Amps @ 120 Vac and 0.25 Amps @ 220 Vac(220 Vac is non-UL). Not rated for capacitive loads. Mounting North American 21/2 inch Plugs into UIO2R,UIO6R or North American 21/2 inch Plugs into UIO2R,UIO6R or (64 mm)deep 1-gang boxes UIO6 Motherboards (64 mm)deep 1-gang boxes UIO6 Motherboards and 11/2 inch(38 mm)deep and 11/2 inch(38 mm)deep 4 inch square boxes with 4 inch square boxes with 1-gang covers and GSA-MP 1-gang covers and GSA-MP mounting plates mounting plates Construction&Finish High Impact Engineering Polymer Storage and Operating Operating Temperature:32°F to 120°F(0°C to 49°C) Environment Storage Temperature:-4°F to 140°F(-20°C to 60°C)Humidity:0 to 93%RH LED Operation On-board Green LED-Flashes when polled On-board Red LED-Flashes when in alarm/active Compatibility Use With:Signature Loop Controller Agency Listings UL,ULC,CSFM, MEA Ordering Information Catalog Number Description Ship Weight lbs (kg) GSA-CR Control Relay Module(Standard Mount) 0.4(0.15) GSA-MCR Control Relay Module(UIO Mount) 0.18(0.08) GSA-CRR Polarity Reversal Relay Module(Standard Mount) 0.4(0.15) GSA-MCRR Polarity Reversal Relay Module(UIO Mount) 0.18(0.08) Related Equipment 27193-11 Surface Mount Box-Red, 1-gang 1 (0.6) 27193-16 Surface Mount Box-White, 1-gang 1 (0.6) GSA-UIO2R Universal Input-Output Module Board w/Riser Inputs-Two Module Positions 0.32(0.15) GSA-UIO6R Universal Input-Output Module Board w/Riser Inputs-Six Module Positions 0.62(0.28) GSA-U106 Universal Input-Output Module Board-Six Module Positions 0.56(0.25) GSA-AB4G Audible(Sounder)Detector Base 0.3(0.15) Accessories MFC-A Multifunction Fire Cabinet-Red,supports Signature Module Mounting Plates 7.0(3.1) GSA-MB4 Transponder Mounting Bracket(allows for mounting two 1-gang modules in a 2-gang box) 0.4(0.15) GSA-MP1 Signature Module Mounting Plate, 1 footprint 1.5(0.70) GSA-MP2 Signature Module Mounting Plate, 1/2 footprint 0.5(0.23) GSA-MP2L Signature Module Mounting Plate, 1/2 extended footprint 1.02(0.46) Page 5 of 6 DATA SHEET M85001-0239 Not to be used for installation purposes. Issue 7.5 Signature Series Overview c :bwAR DS The Signature Series intelligent analog-addressable system from Edwards is an entire family of multi-sensor detectors and mounting bases, multiple-function input and output ,United Technologies modules, network and non-network control panels, and user-friendly maintenance and service tools.Analog information from equipment connected to Signature devices is Contact us... gathered and converted into digital signals.An onboard microprocessor in each Signature Email: edwards.fire@fs.utc.com device measures and analyzes the signal and decides whether or not to input an alarm. Web: www.vigilant-fire.com The microprocessor in each Signature device provides four additional benefits-Self-di- Vigilant is an EDWARDS brand. agnostics and History Log,Automatic Device Mapping, Stand-alone Operation and Fast, 1016 Corporate Park Drive Stable Communication. Mebane,NC 27302 Self-diagnostics and History Log-Each Signature Series device constantly runs self- ©2013 UTC Fire&Security Americas checks to provide important maintenance information.The results of the self-check are Corporation,Inc.All rights reserved. Specifications subject to change automatically updated and permanently stored in its non-volatile memory.This information without notice.Edwards is part of UTC is accessible for review any time at the control panel, PC,or using the SIGA-PRO Signa- Climate,Controls&Security,a unit of ture Program/Service Tool.The information stored in device memory includes: United Technologies Corporation. • Device serial number, address, and type •Time and date of last alarm • Most recent trouble code logged by the detector— 32 possible trouble codes may be used to diagnose faults. Automatic Device Mapping-The Signature Data Controller(SDC)learns where each device's serial number address is installed relative to other devices on the circuit.The SDC keeps a map of all Signature Series devices connected to it.The Signature Series Data Entry Program also uses the mapping feature.With interactive menus and graphic support,the wired circuits between each device can be examined. Layout or"as-built" drawing information showing branch wiring(T-taps), device types and their address are stored on disk for printing hard copy.This takes the mystery out of the installation.The preparation of as-built drawings is fast and efficient. Device mapping allows the Signature Data Controller to discover: • Unexpected additional device addresses • Missing device addresses •Changes to the wiring in the circuit. Most Signature modules use a personality code selected by the installer to determine their actual function. Personality codes are downloaded from the SDC during system configu- ration and are indicated during device mapping. Standalone Operation-A decentralized alarm decision by the device is guaranteed. Onboard intelligence permits the device to operate in standalone(degrade)mode. If Sig- nature loop controller CPU communications fail for more than four seconds, all devices on that circuit go into standalone mode.The circuit acts like a conventional alarm receiving circuit. Each Signature device on the circuit continues to collect and analyze information from its slave devices.When connected to a panel utilizing standalone operation, modules with their"personality"set as alarm devices(IDC)will alarm should their slave alarm-initiat- ing device activate. a Page 6 of 6 DATA SHEM85001-0239 E.; Not to be used for installa oses. Issue 7.5 Vigilant Catalog► Intelligent Input-Output VGILANT Fire & Life Safety Input Modules lalki a GSA-CT1 , GSA-CT1 HT ..J., GSA-CT2, GSA-MCT2 ,R l " " 14MEA N - lifia ® 7300-1483: 0115 •'L1 . GSA-CT1/2 O �, ll GSA-MCT2 (E sp0 Application Notes S3424 Available Overview Standard Features The GSA-CT1 Single Input Module, GSA-CT1 HT High Tempera- • Multiple applications ture Single Input Module and GSA-CT2/GSA-MCT2 Dual Input Including Alarm,Alarm with delayed latching (retard)for water- Modules are intelligent analog addressable devices used to con- flow applications, Supervisory, and Monitor.The installer selects nect one or two Class B normally-open Alarm, Supervisory, or one of four"personality codes"to be downloaded to the mod- Monitor type dry contact Initiating Device Circuits(IDC). ule through the loop controller. The actual function of these modules is determined by the"personal- • GSA-CT1 HT rated for high temperature environments ity code"selected by the installer.This code is downloaded to the Suitable for attic installation and monitoring high temperature module from the Signature loop controller during system configura- heat detectors. tion. • Plug-in(UIO)or standard 1-gang mount The input modules gather analog information from the initiating U10 versions allow quick installation where multiple modules are devices connected to them and convert it into digital signals. required.The 1-gang mount version is ideal for remote loca The module's on-board microprocessor analyzes the signal and tions that require a single module. decides whether or not to input an alarm. • Automatic device mapping Signature modules transmit information to the loop controller The GSA-CT1,GSA-CT1 HT and GSA-CT2 mount to standard regarding their circuit locations with respect to other Signature North American 1-gang electrical boxes, making them ideal for lo- devices on the wire loop. cations where only one module is required. Separate I/O and data • Electronic addressing loop connections are made to each module. Programmable addresses are downloaded from the loop con- The GSA-CT1 HT module operates at an expanded temperature troller, a PC, or the Signature Program/Service Tool.There are range of 32°F to 158°F(0°C to 70°C)for those applications no switches or dials to set. requiring more extreme environmental temperature variation. • Stand-alone operation The GSA-MCT2 is part of the UIO family of plug-in Signature The module makes decisions and inputs an alarm from initiat Series modules. It functions identically to the GSA-CT2, but takes ing devices connected to it even if the loop controller's polling advantage of the modular flexibility and easy installation that interrogation stops. (Function availability dependent upon control characterizes all UIO modules.Two-and six-module UIO mother- panel.) boards are available.All wiring connections are made to terminal • Ground fault detection by address blocks on the motherboard. UIO assemblies may be mounted in Detects ground faults right down to the device level. Edwards enclosures. Pagel of 4 DATA SHEET M85001-0241 Not to be used for installation purposes. Issue 8 Signature Series Overviewui,Motherboard — The Signature Series intelligent analog-addressable system from 1 S-a2 9 9 g- y / � Self-tapping Edwards Security is an entire family of multi-sensor detectors and screws mounting bases, multiple-function input and output modules, E _--0 g-in network and non-network control panels, and user-friendly main- 0,Captive tenance ain- tenance and service tools.Analog information from equipment PluModu le s�etws connected to Signature devices is gathered and converted into __ �__� digital signals.An onboard microprocessor in each Signature de- _ vice measures and analyzes the signal and decides whether or not \ fi Flat washers to input an alarm.The microprocessor in each Signature device 1 provides four additional benefits-Self-diagnostics and History _—Cabinet or electrical enclosure Log,Automatic Device Mapping, Stand-alone Operation and Fast, Stable Communication. Electronic Addressing -The loop controller electronically ad- Self-diagnostics and History Log-Each Signature Series dresses each module, saving valuable time during system corn- device constantly runs self-checks to provide important mainte- missioning. Setting complicated switches or dials is not required. nance information.The results of the self-check are automatically Each module has its own unique serial number stored in its updated and permanently stored in its non-volatile memory.This on-board memory.The loop controller identifies each device on information is accessible for review any time at the control panel, the loop and assigns a"soft"address to each serial number. If PC, or using the Signature Program/Service Tool. desired,the modules can be addressed using the Signature Pro- Automatic Device Mapping-The Signature Data Control- gram/Service Tool. ler(SDC)learns where each device's serial number address is Edwards recommends that this module be installed according to installed relative to other devices on the circuit.The SDC keeps a latest recognized edition of national and local fire alarm codes. map of all Signature Series devices connected to it.The Signature Series Data Entry Program also uses the mapping feature.With interactive menus and graphic support,the wired circuits be- Application tween each device can be examined. Layout or"as-built"drawing information showing branch wiring(T-taps), device types and their The duty performed by the GSA-CT1 and GSA-CT2/MCT2 is de- address are stored on disk for printing hard copy. termined by their sub-type code or"Personality Code".The code is selected by the installer depending upon the desired application Installation and is downloaded from the loop controller. GSA-CT1,GSA-CT1 HT and GSA-CT2:modules mount to North One personality code can be assigned to the GSA-CT1.Two per- American 21/2 inch(64 mm)deep 1-gang boxes and 11/2 inch(38 sonality codes can be assigned to the GSA-CT2/MCT2. Codes mm)deep 4 inch square boxes with 1-gang covers and GSA-MP 1, 2,3 and 4 can be mixed on GSA-CT2/MCT2 modules only. For mounting plates.The terminals are suited for#12 to#18 AWG(2.5 example, personality code 1 can be assigned to the first address mm2 to 0.75 m w ire size. (circuit A)and code 4 can be assigned to the second address Compatible electrical box (circuit B). ��i NORMALLY-OPEN ALARM -LATCHING(Personality Code 1) -Assign to one or both circuits. Configures either circuit A or B or I1 both for Class B normally open dry contact initiating devices such I' ! as Pull Stations, Heat Detectors, etc.An ALARM signal is sent to 1` Wall plate,white the loop controller when the input contact is closed.The alarm tli',11�jQ. (1-gang) condition is latched at the module. NORMALLY-OPEN ALARM - DELAYED LATCHING (Person- ality Code 2)-Assign to one or both circuits. Configures either _..,--\i‘ • circuit A or B or both for Class B normally-open dry contact initiat- \li. ing devices such as Waterflow Alarm Switches.An ALARM signal is sent to the loop controller when the input contact is closed for Status LEDsapproximately 16 seconds.The alarm condition is latched at the module. LED viewing ports NORMALLY-OPEN ACTIVE- NON-LATCHING (Personality o, Code 3)-Assign to one or both circuits. Configures either circuit A or B or both for Class B normally-open dry contact monitoring 0 input such as from Fans, Dampers, Doors, etc.An ACTIVE signal GSA-MCT2:mount the UIO motherboard inside a suitable is sent to the loop controller when the input contact is closed.The Edwards enclosure with screws and washers provided. Plug the active condition is not latched at the module. GSA-MCT2 into any available position on the motherboard and NORMALLY-OPEN ACTIVE- LATCHING (Personality Code secure the module to the motherboard with the captive screws. 4)-Assign to one or both circuits. Configures either circuit A or Wiring connections are made to the terminals on the motherboard B or both for Class B normally open dry contact monitoring input (see wiring diagram). UIO motherboard terminals are suited for#12 such as from Supervisory and Tamper Switches.An ACTIVE signal to#18 AWG(2.5 mm2 to 0.75 mm2)wire size. is sent to the loop controller when the input contact is closed.The active condition is latched at the module. Page2of4 DATA Si.,_, . M85001-0241 Not to be used for installation purposes. Issue 8 Typical Wiring Modules will accept#18 AWG(0.75mm2),#16(1.0mm2), and#14AWG(1.50mm2), and#12 AWG(2.50mm2)wire sizes. Note: Sizes#16 AWG(1.0mm2)and#18 AWG(0.75mm2)are preferred for ease of installation.See Signature Loop Controller catalog sheet for detailed wiring requirement specifications. Initiating(Slave)Device Circuit Wire Specifications Maximum Allowable Wire Resistance 50 ohms(25 ohms per wire)per Circuit Maximum Allowable Wire Capacitance 0.1 pF per Circuit For Design Reference: Wire Size Maximum Distance to EOLR #18 AWG(0.75 mm2) #16 AWG(1.00 mm2) 4,000 ft(1,219 m) #14 AWG(1.50 mm2) #12 AWG(1.50 mm2) Typical N.O.Initiating Device Typical N.O.Inlitiating Device J• INPUT 1 INPUT 2 HH A HH iniii AAA Q4 Style B(Class B) hum .:=:. TB2 11(11171.7 TB2 I I 111 ll_ 8 7 UL/ULC Listed S le B Class B r • 471x1 EOL UL/ULC Listed ( ) e 5 s UL/ULC Listed 47KS2 EOL 1., ® 1 .7 • • l 471(2 EOL Red LED Green LED (Alarm/Active) 0 (Normal) Red LED Green LED 4 342 1 (Alarm/Active) I 4 3 2 1 I (Normal) TB1IQnI _ _ TB1I( 611. ( DATA IN(+) ► (+) DATA OUT 1 j(DATA IN(+) ' DATA OUT(+) l DATA IN(-) lo.DATA OUT(-)/ l DATA IN(-) DATA OUT(-) To Next Device From Signature Controller To Next Device From Signature Controller or Previous Device or Previous Device Q 3 GSA-CT1, GSA-CT1 HT GSA-CT2 1 1 1 Typical NO Initiating Device I i NOTES UL/ULC Listed +I pin + HD Input2 UL/ULC Listed 47KW EOL47KW EOL A Maximum 25 Ohm resistance per wire. A Maximum#12 AWG(2.5 mm2)wire;Minimum#18 AWG(0.75 mm2). •■' e e e ARefer to Signature controller installation sheet for wiring specifications. /w\Maximum 10 Vdc @ 350 pA MCT2 AThe GSA-UIO6R and the GSA-UIO2R do not come with TB14. 2 s 4A UIOIRI series motherboard 6 All wiring is supervised and power-limited. + 4 Data In Li Q 7 These modules will not support 2-wire smoke detectors. : 4 ,RI 1 �isSignature I 2 . �l TB14 No connections required for Data ■ i Uilo,MCT2Circuit+ Other modules may require DataOut+ MCT2connectionsWarnings & Cautions IIi:iIP Green LED(Normal} This module will not operate without electrical power.As fires fre- RedLED(Active) quently cause power interruption,we suggest you discuss further safeguards with your local fire protection specialist. NegconneciMCTz jumper settings Compatibility GSA-MCT2 The Signature Series modules are compatible only with Vigilant's Signature Loop Controller. Page 3 of 4 DATA SHEET M85001-0241 Not to be used for installation purposes. Issue 8 Specifications DWAR DS Catalog Number GSA-CT1HT I GSA-CT1 GSA-CT2 I GSA-MCT2 Description Single Input Module Dual Input Module ,United Technologies Type Code 48(factory set)Four sub-types 49(factory set)Four sub-types Contact us... (personality codes)are available (personality codes)are available Address Requirements Uses One Module Address Uses Two Module Addresses Email: edwards.fire@fs.utc.com Web: www.vigilant-fire.com Operating Current Standby=250pA; Standby=396pA; Activated=400pA Activated=680pA Vigilant is an EDWARDS brand. Operating Voltage 15.2 to 19.95 Vdc(19 Vdc nominal) 1016 Corporate Park Drive Mebane,NC 27302 Construction High Impact Engineering Polymer ©2013 UTC Fire&Security Americas Mounting North American 2t inch(64 mm)deep one-gang box- UIO2R/6R/6 Corporation,Inc.All rights reserved. es and 11/2 inch (38 mm)deep 4 inch square boxes Motherboard Specifications subject to change with one-gang covers and GSA-MP mounting plates without notice.Edwards is part of UTC Operating Environment 32°F to 158°F 32°F to 120°F(0°C to 49°C) Climate,Controls&Security,a unit of (0°C to 70°C) United Technologies Corporation. Storage Environment -4°F to 140°F(-20°C to 60°C);Humidity:0 to 93%RH LED Operation On-board Green LED-Flashes when polled;On-board Red LED- Flashes when in alarm/active. Both LEDs-Glow steady when in alarm(stand-alone) Compatibility Use with Signature Loop Controller Agency Listings UL,ULC,MEA,CSFM Ordering Information Catalog Description Ship Wt. Number lbs(kg) GSA-CT1 Single Input Module— UL/ULC Listed 0.4(0.15) GSA-CT1 HT Single Input Module High Teperature Operation UL/ULC Listed 0.4(0.15) GSA-CT2 Dual Input Module— UL/ULC Listed 0.4(0.15) GSA-MCT2 Dual Input Plug-in(UIO)Module — UL,ULC Listed 0.1 (0.05) Related Equipment 27193-11 Surface Mount Box-Red, 1-gang 1.0(0.6) 27193-16 Surface Mount Box-White, 1-gang 1.0(0.6) GSA U102R Universal Input-Output Module Board w/Riser Inputs 0.32(0.15) —Two Module Positions GSA UIO6R Universal Input-Output Module Board w/Riser Inputs 0.62(0.28) —Six Module Positions GSA-U106 Universal Input-Output Module Board —Six Module Positions 0.56(0.25) MFC-A Multifunction Fire Cabinet— Red,supports Signature Module 7,0(3.1) Mounting Plates GSA-MB4 Transponder Mounting Bracket(allows for mounting 0.4(0.15) two 1-gang modules in a 2-gang box) GSA-MP1 Signature Module Mounting Plate, 1 footprint 1.5(0.70) GSA-MP2 Signature Module Mounting Plate, 1/2 footprint 0.5(0.23) GSA-MP2L Signature Module Mounting Plate, 1/2 extended footprint 1.02(0.46) a Page 4 of 4 DATA S I M85001-0241 to Not to be used for installation purposes. Issue 8 Vigilant Catalog► Intelligent Input-Output /G/LAN T Fire & Life Safety Synchronization • 53424 Output Module - GSA-CC1 S, MCC1 S 7300-1483: 0115 jg MEA a r;- BEM Patented Overview Standard Features GSA-CC1 S and MCC1 S Synchronization Output Modules are • Provides UL 1971-compliant auto-sync output for visual intelligent analog addressable devices that form part of Vigilant's signals Signature line of products.The actual operation of the GSA-CC1 S Use for connecting a supervised output circuit to a supervised and MCC1 S is determined by the"personality code"selected by 24 Vdc riser input and synchronizing multiple notification appli- the installer,which is downloaded to the module from the Signa- ance circuits. ture loop controller during system configuration. • Functions as an audible signal riser selector Depending on their assigned personality, Synchronization Output Use as a synch module or for connecting supervised 24 Vdc Modules may be used as a signal power riser selector to provide AudibleNisible signal circuits,or 25 and 70 VRMS Audio synchronization of fire alarm signals across multiple zones, or for Evacuation and Telephone circuits to their power inputs. connecting, upon command from the loop controller, supervised • Built-in ring-tone generator Class B signal or telephone circuits to their respective power When configured for telephone circuits,the GSA-CC1 S gener- inputs.The power inputs may be polarized 24 Vdc to operate au- ates its own ring-tone signal, eliminating the need for a sepa- dible and visible signal appliances or 25 and 70 VRMS to operate rate ring-tone circuit. audio evacuation speakers and firefighter's telephones. • Automatic device mapping Signature modules transmit information to the loop controller regarding their circuit locations with respect to other Signature devices on the wire loop. • Electronic addressing Programmable addresses are downloaded from the loop con- troller, a PC,or the SIGA-PRO Signature Program/Service Tool; there are no switches or dials to set. • Intelligent device with microprocessor All decisions are made at the module to allow lower com- munication speed with substantially improved control panel response time and less sensitivity to line noise and loop wiring properties;twisted or shielded wire is not required. Page 1 of 4 DATA SHE._ . M85001-0543 Not to be used for installation purposes. Issue 3.1 Application Installation The GSA-CC1S mounts to a standard North American two-gang The GSA-CC1S:mounts to North American 2-1/2 inch(64 mm) electrical box, making it ideal for locations where only one module deep 2-gang boxes and 1-1/2 inch(38 mm)deep 4 inch square is required. Separate I/O and data loop connections are made to boxes with 2-gang covers and GSA-MP mounting plates.The each module. terminals are suited for#12 to#18 AWG(2.5 mm2 to 0.75 mm2) The GSA-MCC1S is part of the UIO family of plug-in Signature wire size. Series modules. It functions identically to the GSA-CC1 S, but takes advantage of the modular flexibility and easy installation that O characterize all UIO modules.Two-and six-module UIO mother- boards are available.These can accommodate individual risers for O -v, ` each on-board module,or risers that are shared by any combina- tion of its UIO modules.All wiring connections are made to termi- t nal blocks on the motherboard. UIO assemblies may be mounted c\.10 °, ►�\\ '' - � in Edwards enclosures. ..4r440-06 Personality Codes ®0 The operation of the GSA-CC1 S is determined by their sub-type code or"Personality Code".The code is selected by the installer GSA-MCC1S:mount the UIOxR motherboard inside a suitable depending upon the desired application and is downloaded from Edwards enclosure with screws and washers provided. Plug the the loop controller. module into any available position on the motherboard and secure Personality Code 5:Signal Power or Audio Evacuation(sin- the module to the motherboard with the captive screws.Wiring gle riser).Configures the module for use as a Class B Audible/ connections are made to the terminals on the motherboard(see Visible Signal power(24 Vdc polarized)or Audio Evacuation(25 wiring diagram). UIOxR motherboard terminals are suited for#12 or 70 VRMS)power selector.The ring-tone generator is disabled. to#18 AWG(2.5 mm2 to 0.75 mm2)wire size. The output circuit is monitored for open or shorted wiring. If a ulo Motherboard short exists,the control panel inhibits the activation of the audible/ 1 6-32 visible signal circuit to prevent connection to the power circuit. Self-tapping screws Personality Code 6:Telephone with ring-tone(single riser). f — ___1 Configures the module for use as a Telephone power selector. - --�U When a telephone handset is plugged into its jack or lifted from its Plug-in (e1O) 0,Captive hook,the module generates its own Ring-Tone signal.A separate ring-tone circuit is not needed.The module sends this signal to -- --j --� ' the control panel to indicate that an off-hook condition is present. When the system operator responds to the call,the ring-tone I #6 Flat washers signal is disabled. —Cabinet or electrical enclosure Personality Code 25:Visual Signal Synchronization.This personality code configures the module to provide synchronization of fire alarm signals across multiple zones. It functions as a signal power(24 Vdc)riser selector.The output wiring is monitored for Electronic Addressing open circuits and short circuits.A short circuit will cause the fire The loop controller electronically addresses each module saving alarm control panel to inhibit the activation of the audible/visual valuable time during system commissioning. Setting complicated signal circuit so the riser is not connected to the wiring fault. switches or dials is not required. Each module has its own unique serial number stored in its"on-board memory".The loop control- ler identifies each device on the loop and assigns a"soft"address Warnings & Cautions to each serial number. If desired,the modules can be addressed This module will not operate without electrical power.As fires fre- the SIGA-PRO Signature Program/Service Tool. quently cause power interruption,we suggest you discuss further safeguards with your fire protection specialist. Testing & Maintenance Edwards recommends that these modules be installed according The module's automatic self-diagnosis identifies when it is defec- to latest recognized edition of national and local fire alarm codes. tive and causes a trouble message.The user-friendly maintenance program shows the current state of each module and other perti- nent messages. Single modules may be turned off(de-activated) Compatibility temporarily,from the control panel. The Synchronization Output Module is compatible with VS and Scheduled maintenance(Regular or Selected)for proper system Quickstart loop controllers. operation should be planned to meet the requirements of the Authority Having Jurisdiction(AHJ). Refer to current NFPA 72 and ULC CAN/ULC 536 standards. Page 2 of 4 DATA SHEM85001-0543 Not to be used for installa oses. Issue 3.1 Typical Wiring GSA-CC1S(Standard Mount) GSA-MCC1S(UIO Mount) Personality Typical Speaker Circuit Personality Typical Speaker Circuit Code 5 Code 5 u4 u 4 n 4UWLCEOLiLsted •�41 •�41 ••� 4U1/KUWLCEOLiLsted Personality Typical Telephone Circuit Personality Typical Telephone Circuit Code 6 Code 6 BIB Ei 47KW EOLted BIB EJ 47KW EOLted Personality Enhanced Integrity and Genesis Devices Personality Enhanced Integrity and Genesis Devices Code 25 Code 25 0120' 01 UL/U LC Listed © ©' © UVULCListed 47KW EOL 47KW EOL 1234 11 11 I ,��!is U10(R)series motherboard 10 9 Data In+1� • 5 y+ Riser 1 Out Riser1In 4 FM 1-(+ CC 1S S19Datafe 3 I � e14 Circuit�1 /, Oo 8 7 6 5 4 3 2 1 + _ Data Out_ 111000 0 0 0 00 TB1 ®43 WMIz GreReLLEcmall re15 (A .Riser out(+) Red LED(Active) To next device •I M .Riser out I-I 1 2 3 4 Riser in I+1) •Data out 1+1 Riser 1 In±�I I� Riser 1 Out From control panel ) �+ Riser in 1-1 ) To next device or EOL resistor.,Data out I-1 Data in 1+1 ) From Signature Controller Data in 1-1 )or Previous Device Multiple CC1(S)modules using the MIRBPS's sense inputs TBI Notification appliance circuit(NAC) • 1/ + a DMZ EUL• OL AU �J E AUX1 - OLL15 KW NAC2/ + saj AUX2 - aJ Notification appliance circuit(NAC) • 3/ + 0 DMZ EUL• OL AU 0E AUX3 - OLL 15 KW NAC4/ + GAJ AUX4 - ays) 200 mAAUX Lf) Continuous co 0 IN 0 1- Sense Sense 1 COM 10JEOL 47 K OUTI©J� INI© + Sense 2 COM iS EOL 47 K OUT �J NO © Trouble COM 1 lol®® I 1 l0l°11 in NC 0 109 109 TB20 CC1(S)module CC1(S)module 0 0 0 0 8765 4321 8765 4321 Immmmll 0u1m Imalt1t I 11 1111rl +–+– [1] +–+– [1] —0.[3] Page 3 of 4 D ATA S H E . M85001-0543 Not to be used for installation purposes. Issue 3.1 Specifications DWAR DS Catalog Number GSA-CC1S GSA-MCC1S United Technologies North American 21/2 inch(64 mm) deep two-gang boxes and 11/2 Plugs into UIO2R,UIO6R or U106 Contact us... Mounting inch(38 mm)deep 4 inch square Motherboards boxes with 2-gang covers and Email: edwards.fire@fs.utc.com GSA-MP mounting plates Web: www.vigilant-fire.com Description Synchronization Output Module Vigilant is an EDWARDS brand. Type Code 50(factory set) 1016 Corporate Park Drive Address Requirements Uses one module address Mebane,NC 27302 Wiring Terminations Suitable for#12 to#18 AWG(2.5 mm2 to 0.75mm2) ©2013 UTC Fire&Security Americas Standby=223pA Corporation,Inc.All rights reserved. Operating Current Activated=100pA Specifications subject to change without notice.Edwards is part of UTC Operating Voltage 15.2 to 19.95 Vdc(19 Vdc nominal) Climate,Controls&Security,a unit of 24 Vdc=2 amps United Technologies Corporation. Output Rating 25 V Audio=50 watts 70 V Audio=35 watts Construction High Impact Engineering Polymer Storage Operating Operating:32°F to 120°F(0°C to 49°C) Environmenttorageand Storage:-4°F to 140°F(-20°C to 60°C) Humidity:0 to 93%RH LED Operation Green LED-Flashes when polled Red LED-Flashes when in alarm/ active Compatibility Use with:Signature Loop Controller under MIR3 version 2.0 or higher Agency Listings UL,ULC,CSFM, MEA Ordering Information Catalog Description Shipping Wt. Number lbs(kg) GSA-CC1 S Synchronization Output Module(Standard Mount)-UUULC Listed 0.5(0.23) GSA-MCC1S Synchronization Output Module(UIO Mount)-UUULC Listed 0.18(0.08) Related Equipment 27193-21 Surface Mount Box-Red,2-gang 2(1.2) 27193-26 Surface Mount Box-White,2-gang 2(1.2) GSA U102R Universal Input-Output Module Board w/Riser Inputs 0.32(0.15) -Two Module Positions GSA U106R Universal Input-Output Module Board w/Riser Inputs 0.62(0.28) -Six Module Positions GSA-U106 Universal Input-Output Module Board-Six Module Positions 0.56(0.25) 235196P Bi-polar Transient Protector 0.01 (0.05) MFC-A Multifunction Fire Cabinet-Red, 7.0(3.1) supports Signature Module Mounting Plates GSA-MP1 Signature Module Mounting Plate, 1 footprint 1.5(0.70) GSA-MP2 Signature Module Mounting Plate, 1/2 footprint 0.5(0.23) GSA-MP2L Signature Module Mounting Plate, 1/2 extended footprint 1.02(0.46) a m Page 4 of 4 DATA SHEM85001-0543 Not to be used for installa oses. Issue 3.1 Vigilant Catalog►Strobes,Horns, Bells,Chimes /G/LAN T Fire & Life Safety Field Configurable ...„.........,....„.. .... ...' ......... Horns and . • _..,.,.._, Strobes ,, ._ ,,- . Genesis Series ECS/MNS appliances available with clear or amber I-• - '►� A A ).—'----- M Ri E E ALERT RT T .� 0 C <>. Fc 7135-1483: 0176 S218/ MEA C E 0147-0148 S29 0/ Overview Standard Features The Genesis line of fire alarm and mass notification/emergency • Unique low-profile design communications(ECS/MNS)signals are among the smallest, — The most compact UL-1971/ULC-S526 listed strobe available most compact audible-visible life safety signaling devices in the — Ultra-slim—protrudes less than one inch world.About the size of a deck of playing cards,these devices are — Attractive appearance designed to blend with any decor. — No visible mounting screws Thanks to patented breakthrough technology, Edwards Gen- • Four field-configurable options in one device esis strobes do not require bulky specular reflectors and lenses. — Select 15, 30, 75, or 110 cd strobe output Instead,an exclusive cavity design conditions light to produce — Select high(default)or low dB horn output a highly controlled distribution pattern. Significant development — Select temporal (default)or steady horn output efforts employing this new technology have given rise to a new — Select public mode flash rate(default)or private mode benchmark in strobe performance—FullLight technology. temporal flash FullLight strobe technology produces a smooth light distribution • Fixed 15/75 cd model available pattern without the spikes and voids characteristic of specular re- • ECS/MNS models available flectors.This ensures the entire coverage area receives consistent illumination from the strobe flash.As a result, Genesis strobes with • Easy to install FullLight technology go well beyond the UL-1971 and ULC-5526 — Fits standard 1-gang electrical boxes —no trim plate needed light distribution requirements. — Optional trim plate accommodates oversized openings — Pre-assembled with captive hardware Genesis strobes and horn-strobes offer selectable candela output — #12 AWG terminals—ideal for long runs or existing wiring by means of a conveniently-located switch on the side of the • device. Models are also available that offer fixed 15/75 cd output. Unparalleled performance The candela output setting remains clearly visible even after final — Industry's most even light distribution installation,yet it stays locked in place to prevent unauthorized — Meets tough synchronizing standards for strobes tampering. — Single microprocessor controls both horn and strobe — Independent horn control over a single pair of wires Genesis ECS/MNS appliances offer emergency signaling with — Highly regulated in-rush current clear or amber lenses and with optional ALERT housing labels. — Multiple frequency tone improves sound penetration They are ideal for applications that require differentiation between — Field-programmable temporal strobe output option fire alarm and mass notification alerts. Page 1 of 6 DATA SHEET M85001-0573 Not to be used for installation purposes. Issue 11.1 Application Installation Genesis strobes are UL 1971-listed for use indoors as wall-mount- Genesis horns and strobes mount to any standard one-gang sur- ed public-mode notification appliances for the hearing impaired. face or flush electrical box. Matching optional trim plates are used Prevailing codes require strobes to be used where ambient noise to cover oversized openings and can accommodate one-gang, conditions exceed 105 dBA(87dBA in Canada),where occupants two-gang,four-inch square, or octagonal boxes,and European use hearing protection,and in areas of public accommodation 100 mm square. as defined in the Americans with Disabilities Act(see application notes—USA). All Genesis signals come pre-assembled with captive mounting screws for easy in- Combination horn-strobe signals must be installed in accordance F stallation.Two tabs at the top of the signal with guidelines established for strobe devices.Consult with your I , I unlock the cover to reveal the mounting Authority Having Jurisdiction for details. R R hardware.The shallow depth of Genesis All Genesis strobes exceed UL synchronization requirements E E devices leaves ample room behind the (within 10 milliseconds over a two-hour period)when used with a signal for extra wiring.Once installed with synchronization source. Synchronization is important in order to I the cover in place, no mounting screws avoid epileptic sensitivity. Mar are visible. WARNING:These devices will not operate without electrical power.As fires frequently cause power interruptions, further safeguards such as Field Configuration Genesis Horn/Strobe Temporal horn and horn-strobe models backup power supplies may be required. with optional trim plate p are factory set to sound in a three-pulse temporal pattern. Units may be con- figured for use with coded systems by cutting a jumper on the Horns circuit board.This results in a steady output that can be turned Genesis horn output reaches as high as 99 dB and features a on and off(coded)as the system applies and removes power to unique multiple frequency tone that results in excellent sound the signal circuit.A Genesis Signal Master is required when horn penetration and an unmistakable warning of danger. Horns may be strobe models are configured for coded systems. Non-temporal, configured for either coded or non-coded signal circuits.They can horn only models sound a steady tone. also be set for low dB output with a jumper cut that reduces horn Genesis clear strobes and horn-strobes are shipped from the fac- output by about 5 dB. Horn-only models may be ceiling-mounted tory ready for use as UL 1971 compliant signals for public mode or wall-mounted. operation.These signals may be configured for temporal flash by The suggested sound pressure level for each signaling zone used with cutting a jumper on the circuit board.This batterysaving feature is alarm signals is at least 15 dB above the average ambient sound level, intended for private mode signaling only. or 5 dB above the maximum sound level having a duration of at least Genesis clear strobes and horn-strobes may be set for 15,30,75, 60 seconds,whichever is greater,measured 5 feet(1.5 m)above the or 110 candela output.The output setting is changed by simply floor.The average ambient sound level is,A-weighted sound pressure opening the device and sliding the switch to the desired setting. measured over a 24-hour period. The device does not have to be removed to change the output Doubling the distance from the signal to the ear will theoretically result setting.The setting remains visible through a small window on the in a 6 dB reduction of the received sound pressure level.The actual side of the device after the cover is closed. effect depends on the acoustic properties of materials in the space. Horns and horn-strobes are factory set for high dB output. A 3 dBA difference represents a barely noticeable change in volume. Low dB output may be selected by cutting a jumper on the circuit board.This reduces the output by about 5 dB. ECS/MNS Applications Genesis ECS/MNS strobe appliances bring the same high- performance fire alarm features and unobtrusive design to mass notification applications.Available with amber lenses and optional Wiring ALERT housing labels,they are ideal for applications that require Field wiring terminals accommodate#18 to#12 AWG(0.75 mm2 differentiation between fire alarm and mass notification alerts. to 2.5 mm2)wiring. Horns, strobes,and combination horn-strobes are interconnected with a single pair of wires as shown below. 0 appliancTonexte, Polarity shown in end-of-line alarm condition P��©, %p©' or return to �� ►� control 63 equipment ONote:Strobes must have continuous voltage. Page 2 of 6 DATA SHEL , M85001-0573 Not to be used for installation purposes. Issue 11.1 Current Draw Strobes, Horn-Strobes Horns Multi-cd Wall Strobes(MG1-VM) Wall or Ceiling Mounted UL 15 cd* 30 cd* 15/75 cd** 75 cd* 110 cd* Temporal Horns(MG1- Rating i RMS RMS RMS RMS RMS HD) 16 Vdc 103 141 152 255 311 UL High dB Low dB 16 Vfwr 125 179 224 346 392 Rating (RMS) (RMS) *MG1-VM multi-cd;**MG1 F-V1575 fixed 15/75 cd 16 Vdc 26 19 24 Vdc 36 27 Typical 15 cd 30 cd 15/75 75 cd 110 cd 33 Vdc 41 33 Current RMS RMS RMS RMS RMS 16 Vfwr 51 37 16 Vdc 85 127 150 245 285 24 Vfwr 69 52 20 Vdc 71 98 123 188 240 33 Vfwr 76 70 24 Vdc 59 82 104 152 191 33 Vdc 46 64 84 112 137 Typical High dB Low dB 16 Vfwr 119 169 223 332 376 Current RMS RMS 20 Vfwr 103 143 189 253 331 16 Vdc 22 17 24 Vfwr 94 129 169 218 262 20 Vdc 24 19 33 Vfwr 87 112 148 179 205 24 Vdc 27 22 33 Vdc 32 26 Wall Temporal Horn-strobes—High dB Setting 16 Vfwr 34 30 15 30 15/75 75 110 *MG1-HDVM multi-cd 20 Vfwr 40 34 UL cd* cd* cd** cd* cd* **MG1 F-HDV1575 fixed 15/75 cd 24 Vfwr 45 38 Rating RMS RMS RMS RMS RMS 33 Vfwr 52 47 16 Vdc 129 167 172 281 337 Wall or Ceiling Mounted Horns(MG1-P) 16 Vfwr 176 230 269 397 443 UL Designation Voltage Range Max.Current, RMS Typical 15 cd 30 cd 15/75 75 cd 110 cd Regulated 24 16 33 Vdc 13 mA Current RMS RMS RMS RMS RMS Vdc 16 Vdc 102 135 160 246 309 24 fwr 16-33 Vfwr 11 mA 20 Vdc 88 109 137 193 248 24 Vdc 81 94 122 161 203 Typical Current RMS 33 Vdc 74 72 106 124 154 24 Vdc 10 16 Vfwr 144 182 247 352 393 24 Vdc 11 20 Vfwr 141 162 220 274 362 31 Vdc 12 24 Vfwr 136 152 203 235 282 20 Vfwr 9 33 Vfwr 125 144 196 201 232 24 Vfwr 10 Wall Temporal Horn-strobes—Low dB Setting Current values are shown in mA. UL 15 30 15/75 75 110 Rating cd* cd* cd** cd* cd* RMSiRMS RMS RMS RMS 16 Vdc 122 160 146 274 330 *MG1-HDVM multi-cd 16 Vfwr 162 216 231 383 429 **MG1 F-HDV1575 fixed 15/75 cd Typical 15 cd 30 cd 15/75 75 cd 110 cd Current RMS RMS RMS RMS RMS 16 Vdc 96 130 158 243 302 20 Vdc 79 104 133 189 241 24 Vdc 68 88 119 156 197 33 Vdc 56 71 100 118 146 16 Vfwr 128 180 241 344 389 20 Vfwr 118 _ 157 213 266 343 24 Vfwr 113 144 195 230 279 33 Vfwr 112 137 182 197 226 Page 3 of 6 DATA SHEET M85001-0573 Not to be used for installation purposes. Issue 11.1 dBA output Average Sound Output (dBA) Temporal Horns, Horn-strobes (High dB setting, anechoic, 24V, measured at 10ft) (MG1-HD, MG1-HDVM series) zo„o,00 so ao 70 30 so 00 30 zo ,o ,o zo 30 00 so 60 ,o ao so ,ao„o,zo High UL464 Average Peak 90`r— aj5° 90` dB Temporal/ Temporal/ Setting Temporal Steady Steady Steady _ -75 16 Vdc 81.4 85.5 91.4 94.2 24 Vdc 84.4 88.6 94.5 97.6 -60\33 Vdc 86.3 90.4 96.9 99.5 \ 66° Low dB UL464 Average Peak \ Temporal/ Temporal/ 30° 3°° Setting Temporal Steady Steady Steady -16° ° 16° 16 Vdc 76.0 80.1 86.3 89.2 24 Vdc 79.4 83.5 89.8 92.5 Light output - (effective cd) 33 Vdc 82.1 86.5 92.5 95.3 Percent of UL rating versus angle Steady Tone Horns(MG1-P series) UL464 Average Peak 2o„o,00 90 ao ,o ao so 00 o so so 70 30 ao,00„o 120 °°. 16 Vdc 77 dBA,min 85 dBA 91 dBA 16 Vfwr 77 dBA,min 85 dBA 91 dBA ),, 76° Notes 1. All values shown are dBA measured at 10 feet(3.01 m). -60' 2. UL464 values measured in reverberant room. \ 3. Average and Peak values are measured in anechoic chamber. 46\ 7/46° -30',,,,.. _________ 30.° 5° 6° 6° 0° Specifications Housing Red or white textured UV stabilized,color impregnated engineered plastic.Exceeds 94V-0 UL flammability rating. Lens Optical grade polycarbonate(clear) Strobes and horn-strobes are for wall-mount installation only.Horn-only models may be ceiling-or wall-mounted. Mounting Flush mount:21/2 inch(64 mm)deep one-gang box (indoor only) Surface mount:Model 27193 surface mount box,wiremold box,or equivalent surface-mount box With optional trim plate:One-gang,two-gang,four-inch square,octagonal,or European single-gang box Wire connections Screw terminals:single input for both horn and strobe.#18 to#12 AWG(0.75 mm2 to 2.5 mm2)wire size Operating environment Indoor only:32-120°F(0-49°C)ambient temperature.93%relative humidity Agency listings/approvals UL 1971 (S218),UL 1638(S218),UL 464(S218),ULC S525,ULC S526,CSFM,CE,FCC,MEA. (All models comply with ADA Code of Federal Regulation Chapter 28 Part 36 Final Rule.) Dimensions(HxWxD) Signal:4-1/2"x 2-3/4"x 13/16"(113 mm x 68 mm x 21 mm) Trimplate: 5"(127 mm);Height-5-7/8"(149 mm);Depth-Y2"(13 mm) MG1-HD series temporal-tone horns:non-coded,filtered 16-33 Vdc or unfiltered 16-33 Vdc FWR(or coded when horn set to steady tone) Operating voltage MG1-HDVM series temporal-tone horn-strobes:non-coded,filtered 16-33 Vdc or unfiltered 16-33 Vdc FWR (or coded (audible NAC only)when used with optional MG1 M Genesis Signal Master) MG1-VM series strobes:non-coded,filtered 16-33 Vdc or unfiltered 16-33 Vdc FWR MG1-P series steady-tone horns:coded or non-coded,filtered 20-31 Vdc or unfiltered 20-27 Vfwr UL 1971,UL 1638,ULC S526:selectable 15 cd,30 cd,75 cd,or 110 cd output Strobe output rating UL 1971: 15 cd(fixed 15/75 cd models) UL 1638,ULCS526:75 cd(fixed 15/75 cd models) MG1-VM strobes and MG1-HDVM series temporal-tone horn-strobes:one flash per second synchronized with optional Strobe flash rate MG1 M Genesis Signal Master indefinitely within 10 milliseconds.Temporal setting(private mode only):synchronized to temporal output of horns on same circuit GSA-CC1 S,GSA-MCC1 S,GSA-CC2A,GSA-MCC2A,MG1 M-RM MIRBPS6A,MIRBPS1 OA,APS6A,APS10A,VS1, Synchronization Sources VS2,Fireshield Plus 3,5 and 10 zone,VM. Add MG1 M for MG1-CVM&MG1-HDVM devices only. MG1-HD temporal-tone horns and MG1-HDVM series temporal-tone horn-strobes:temporal rate synchronized with Horn pulse rate optional MG1 M Genesis Signal Master indefinitely within 10 milliseconds.MG1-P steady-tone horns:continuous,steady tone only Temporal audible pattern 1/2 sec ON,1/2 sec OFF,Y sec ON,1/2 sec OFF,1/2 sec ON, 11/2 sec OFF,then repeat cycle Page 4 of 6 DATA SHE L , M85001-0573 Not to be used for installation purposes. Issue 11.1 Candela Output Fire appliances available with white or red ho Switch Switch Switch f '_ F � F Lens Switch e = — _ R p Rating Position Position Position Color Position A B C D • FIRE E s Amber UL 1638 110 cd 75 cd 30 cd 15 cd • I � . Amber UL 1971" 88 cd 60 cd 24 cd 12 cd Clear UL 1971 110 cd 75 cd 30 cd 15 cd ECS/MNS appliances available with clear or amber lenses. *Equivalent Rating A A L L Al PRE T T A[PHl fliT•1 may# [ ,- 7-:72 Ordering Information Model 1 Housing I Marking I Lens I Strobe I Horn I Ship Wt.lbs(kg) Fire Alarm Appliances(c/w running man icon screen printed on housing) MG1-VM White None Clear Selectable 15,30,75,or 110 cd Strobe only I 0.25 (0.11) MG1F-HD White FIRE Clear Horn only Selectable high/low dB 0.25 (0.11) MG1F-HDV1575 White FIRE Clear 15/75 cd" Temporal hi/lo dB-24VII 0.25 (0.11) MG1F-HDVM _ White FIRE Clear Selectable 15,30,75,or 110 cd Selectable high/low dB_ 0.25 (0.11) MG1 F-P White FIRE Clear Steady Horn(not compatible with Genesis Signal Master) 0.25 (0.11) MG1F-V1575 White FIRE Clear 15/75 cd1 Strobe only 0.25 (0.11) MG1F-VM White FIRE Clear Selectable 15,30,75,or 110 cd Strobe only 0.25 (0.11) MG1-HD White None Clear Horn only Selectable high/low dB 0.25 (0.11) MG1-HDVM White None Clear Selectable 15,30,75,or 110 cd Selectable high/low dB 0.25 (0.11) MG1-P White _ None Clear Steady Horn(not compatible with Genesis Signal Master) 0.25 (0.11) MG1RF-HD Red FIRE Clear Horn only Selectable high/low dB 0.25 (0.11) MG1RF-HDV1575 Red FIRE Clear 15/75 cd1 Temporal hi/lo dB-24V 0.25 (0.11) MG1 RF-HDVM Red FIRE Clear Selectable 15,30,75,or 110 cd Selectable high/low dB 0.25 (0.11) MG1 RF-P Red FIRE Clear Steady Horn(not compatible with Genesis Signal Master) 0.25 (0.11) MG1RF-V1575 Red FIRE Clear 15/75 cd" Strobe only _ 0.25 (0.11) MG1RF-VM Red FIRE Clear Selectable 15,30,75,or 110 cd Strobe only 0.25 (0.11) MG1R-HD Red None Clear Horn only Selectable high/low dB 0.25 (0.11) MG1 R-HDVM Red None Clear Selectable 15,30,75,or 110 cd Selectable high/low dB 0.25 (0.11) MG1 R-P Red None Clear Steady Horn(not compatible with Genesis Signal Master) 0.25 (0.11) MG1R-VM Red None Clear Selectable 15,30,75,or 110 cd Strobe only 0.25 (0.11) ECS/MNS Appliances(no running man icon on housing) G1 WA-VMA White ALERT Amber Selectable A,B,C or D Strobe only 0.25 (0.11) G1 WA-VMC White ALERT Clear Selectable 15,30,75,or 110 cd Strobe only 0.25 (0.11) G1 WN-VMA White None Amber Selectable A,B,C or D Strobe only 0.25 (0.11) G1WN-VMC White None Clear Selectable 15,30,75,or 110 cd Strobe only 0.25 (0.11) Trim Plates MG1T White None Genesis Trim Plate(for two-gang or 4"square boxes) 0.15(0.7) MG1 RT Red None Genesis Trim Plate(for two-gang or 4"square boxes) 0.15(0.7) MG1T-FIRE _White FIRE Genesis Trim Plate(for two-gang or 4"square boxes) 0.15(0.7) MG1 RT-FIRE Red FIRE Genesis Trim Plate(for two-gang or 4"square boxes) 0.15(0.7) G1 WT-ALERT White ALERT Genesis Trim Plate(for two-gang or 4"square boxes) 0.15(0.7) Surface Boxes _ 27193-16 White N/A One-gang surface mount box 1 (0.4) 27193-11 Red N/A One-gang surface mount box 1 (0.4) 1 These 15/75 cd models provide fixed output and are not multi-candela devices.The 15 cd output component complies with UL1971,while the 75 cd output component complies with UL 1638. Page 5 of 6 DATA SHEET M85001-0573 Not to be used for installation purposes. Issue 11.1 Vigilant Catalog►Strobes,Horns, Bells,Chimes /G/LAN T Fire & Life Safety Outdoor Rated .:.:: :::::.: ......... .. .................. ................. . ...... . .......... .......... ....................................... ............................................................. Horns and ........ } Horn - Strobes Genesis WG4 Series Overview Standard Features Genesis WG4 Series horns and horn-strobe appliances are among • Outdoor and indoor rated the most versatile emergency appliances of their kind. Rated for • Low profile design indoor or outdoor use,they are suitable for a wide range of wet and harsh environments with a listed operating temperature range • Wall or ceiling mount of as low as-40°F to as high as 151 °F(-40°C to 66°C). • Room-side wiring accepts 18 to 12 AWG(0.75 to 2.5 mm2) Field-configurable light and sound output settings add to their on- • Wide operating temperature range site flexibility,while optional FIRE markings make them ideal for fire alarm applications. • Field-selectable settings These appliances are suitable for indoor and outdoor applications, • Fully compatible with Genesis synchronization protocols and are ideal for challenging conditions such as parking garages • Standard and high-output strobe intensities and process areas.They are available for mounting on the ceiling • or the wall, and thanks to an ingenious optional full backplane Horn only and horn strobe options sealing gasket,can be installed to recessed(in-the-pour/block) electrical boxes.WG4 notification appliances also mount to suit- able surface boxes. Optional color-matched trim skirts provide a clean,finished appearance.All appliance wiring is accomplished room-side for easy installation. WG4 Series appliances feature an efficient and powerful piezo sounder.The multi-candela strobes are available with clear lenses in two output categories—standard and high-output.They are precision-timed to meet UL 1971 synchronization standards, and field-configurable for one of four candela intensities. Candela settings are viewable even after installation through an innovative sealed viewport display. Page 1 of 4 DATA SHE M85001-0628 Not to be used for installation purposes. Issue 2.2 Application Installation and Mounting Horns WG4 Gasket Optional trim skirt \ Genesis horn output reaches as high as 97 dBA in accordance with UL 464(104 dBA in accordance with ULC S525)and features a Backplate \ m unique frequency tone that results in excellent sound penetration �� 0 and an unmistakable warning of danger. Horns may be configured Front cover \� I'���� for either coded or non-coded notification circuits.They can also be set for low dB output with a jumper cut that reduces horn output by \ Ililiabout 5 dB. �O'~;�ao // m The suggested sound pressure level for each notification zone used % + ' \ with alarm notification appliances is at least 15 dB above the average j;', I <" • Electrical pp g ''j.;;: t ��� ambient sound level,or 5 dB above the maximum sound level havinga e l«i#; ���i ����• �i�i? box. 4 < duration of at least 60 seconds,whichever is greater,measured 5 feet ,i�i ;: r.' $` - (1.5 m)above the floor.The average ambient sound level is A-weighted Ik> ti (fast response)sound pressure measured over a 24-hour period. \j ." 'sem Doubling the distance from the notification appliance to the ear will � �"v theoretically result in a 6 dB reduction of the received sound pressure level.The actual effect depends on the acoustic properties of materi- als in the space. A 3 dBA difference represents a barely noticeable to change in volume. WG4 notification appliances are rated for outdoor use and are suitable for indoor or outdoor applications on walls or ceilings.For surface-mounting in outdoor or wet applications,appliances must be Strobe Application mounted to a 449 or 74347U electrical box. In dry conditions,they Genesis clear-lensed strobes are UL 1971-listed for use indoors are compatible with standard 4-inch square by 11/2-inch deep electri- as wall-or ceiling-mounted public-mode notification appliances for cal boxes.When using the optional WG4WTS or WG4RTS trim skirt, the hearing impaired, and UL 1638-listed for outdoor applications. a 449 or 4-inch square by 2-1/8"deep box must be used. Prevailing codes require strobes to be used where ambient noise conditions exceed specified levels,where occupants use hearing The Genesis WG4 horn and horn-strobe may be wall-or ceiling- protection, and in areas of public accommodation. mounted,and may be placed in one of four positions:strobe above, strobe below,and strobe to either side.The shallow depth of Gen- Visible appliance synchronization is required to avoid causing esis devices leaves room behind the appliance for extra wiring. issues with people who have Photosensitive Epilepsy(PSE). Noti- fication appliance synchronization is also generally required when more than two strobe appliances are in the same field of view from Field Configuration Wire slot any one location.All Genesis strobes meet UL synchronization Horn pattern:Audible requirements(within 10 milliseconds over a two-hour period)when output for WG4 horns and °/0 o used with a synchronization source. horn-strobes is factory set to to sound in a three-pulse ® O temporal pattern.Units may e) WARNING:These devices will not operate without electrical power. be configured for use with CC As fires frequently cause power interruptions,we suggest you discuss coded systems by cutting \\ + Horn further safeguards with your local fire protection specialist. candela /��� volume a JP1 on the circuit board. setting I Q \ jumper Edwards recommends that these devices always be installed in This results in a steady switch I`+'i`+'i+'i`+si — accordance with the latest recognized edition of national and local output that can be turned (S2) 9 codes. Refer to the appropriate codes and standards for mounting on and off(coded)as the height information. system applies and removes Horn 0.._ 3nowoi I power to the notification Pattern P. 3a3w circuit.A Genesis Signal jumper -� . Master is required when Strobe �+ horn-strobe models are con- pattern figured for coded systems. jumper(JP4) Horn output:Horns and horn-strobes are factory set for high dB output. Low dB output may be selected by cutting a jumper on the circuit board. This reduces the output by about 5 dB. Strobe pattern:Genesis WG4 horn-strobes are factory set for use as UL 1971 compliant notification appliances for public mode operation.These notification appliances may be configured for temporal flash by cutting JP4 on the circuit board.This battery-saving feature is intended for private mode signaling only. Strobe output:Genesis WG4 horn-strobes may be set for one of four out- put intensities.The output setting is changed by simply opening the device and sliding the switch to the desired setting.The device does not have to be removed to change the output setting.The setting remains visible after the cover is closed through a small window on the front of the device. Page 2 of 4 DATA SHEM85001-0628 Not to be used for installa oses. Issue 2.2 Wiring Light Output Angle Field wiring is connected to WG4 notification appliances with Horizontal Plot 28-15-10 -5 0 5 1015 20 terminals that accommodate#18 to#12 AWG(0.75 mm2 to 2.5 30.25 25 30 mm2)wiring. -40-35 35 40 -45 45 Signal In- Signal Out - -50 50 -55 55 -60 60 Signal In + -�� a ,,,, ,c.1 Signal Out + -65 65 I //II //I //1++ L17- te- a6 ]0 1�T�I\T�I\T�IYTVI LI u- V V -75 75 _ 0!• -80 80 OQp -85 85 90 NONONo'NNM MoNONON ON ONON 090 f"10 Percentage of rated output .0<u) k il o°. Standard Candela Horn-strobes ® ® Standard/rating Strobe Switch Position D C B A -1+designations indicate the signal polarity UL 1971 Indoor 15 cd 29 cd 70 Cd 87 Cd required to activate the device. UL 1638 Outdoor @-35°C 6 cd 12 cd 28 cd 35 cd CAN/ULC-S526 Outdoor @-40°C 1 cd 3 cd 8 cd 10 cd High Candela Horn-strobes Specifications Strobe Switch Position Horns and Horn-strobes Standard/rating D C B A UL1971 Indoor 102cd 123cd 147cd 161cd Operating voltage 24 VDC,24 VFWR nominal UL 1638 Outdoor @-35°C 41 cd 50 cd 60 cd 65 cd Dimensions(W x H x D) 5.6 x 8.5 x 1.4 in.(142 x 216 x 36 mm) CAN/ULC-S526 Outdoor @-40°C 11 cd 14 cd 17 cd 18 cd Horn tone 3.2 kHz Wire size 12 to 18 AWG(0.75 to 2.50 mm2) Compatible electrical box Outdoor Model 449 or 74347U Indoor 4 in.square by 1.5 in.deep box Operating Current Operating environment (UL specifies current ratings at 16 volts) Temperature -40 to 151°F(-40 to 66°C) Standard Candela Horn-strobes in RMS(mA),continuous Relative humidity 0 to 95%noncondensing Input Voltage Strobe Switch Position D C B A 16 VDC 127 168 297 351 Compatible Synchronization Sources 16 VFWR 218 239 393 422 Horn-strobes 24 VDC 107 130 210 238 24 VFWR 190 222 325 356 Auto sync Output Modules GSA-CC1 S,SIGA-CC2A,GSA- MCC1 S,GSA-MCC2A High Candela Horn-strobes in RMS(mA),continuous Genesis Signal Master MG1 M-RM Strobe Switch Position Booster&Auxiliary Power Supplies APS6A,APS10A,MIRMIRBPS6A, Input Voltage D C B A MIRMIRBPS10A Control Panels with Genesis FireShield Plus,VS Series,VM 16 VDC 342 408 517 526 Synchronization built-in Series 16 VFWR 447 502 614 679 24 VDC 240 271 327 365 24 VFWR 390 400 486 540 Sound Output Horn only models(mA) Horns and Horn-strobes(dBA) 16V RMS,continuous 24V,typical 16V 24V 33V Setting High dB Low dB High dB Low dB Volume Setting UL ULC- UL ULC- UL ULC- VDC 69.1 41.2 49.0 32.3 464 S525 464 S525 464 S525 VFWR 135 91.3 99.1 67.1 Continuous High 89.7 94.0 94.7 99.6 97.4 102.9 Continuous Low 85.4 92.8 89.5 97.2 92.5 98.6 Temporal High 84.2 96.5 90.5 100.5 93.5 104.2 Temporal Low 81.7 90.3 85.4 94.2 88.1 97.0 dBA=Decibels,A-weighted. UL 464:Sound level output measured in a reverberant room at 10 ft.(3.05m). CAN/ULC-5525:Sound level output measured in an anechoic room at 10ft(3.05m). Page 3 of 4 DATA , M85001-0628 Not to be used for installation purposes. Issue 2.2 Ordering Information EDWARDS iiJ F ::,,, ) . 11 UnitedTechnogies • � P Contact us... ,, Email: edwards.fire@fs.utc.com WG4RF-H WG4RF-HVMC WG4WF-H WG4WF-HVMC WG4RN-H WG4RN-HVMC WG4WN-H WG4WN-HVMC Web: www.vigilant-fire.com Vigilant is an EDWARDS brand. Model Housing Marking I Strobe Output Ship Wt. 1016 Corporate Park Drive WG4RF-HVMC Red Mebane,NC 27302 FIRE Selectable WG4WF-HVMC White standard candela ©2013 UTC Fire&Security Americas WG4RN-HVMC Red Corporation,Inc.All rights reserved. None output Specifications subject to change WG4WN-HVMC White without notice.Edwards is part of UTC WG4RF-HVMHC Red Climate,Controls&Security,a unit of FIRE United Technologies Corporation. WG4WF-HVMHC White Selectable 1.5 lbs. high candela WG4RN-HVMHC Red output (0.68kg) None WG4WN-HVMHC White WG4RF-H Red FIRE WG4WF-H White Horn Only WG4RN-H Red None WG4WN-H White Accessories WG4WTS Surface Skirt for Genesis WG4 appliance family,white. WG4RTS Surface Skirt for Genesis WG4 appliance family,red. WG4GSKT Full Body Mounting Gasket for smooth surfaces,WG4 appliance family 74347U Surface mount box,outdoor rated,red 449 Surface mount box,outdoor rated,gray Page 4 of 4 DATA SHEM85001-0628 Not to be used for installa oses. Issue 2.2